2 Applications Circuit-breaker/contactor/drive combinations can be used to ensure continuous service of the installation with optimum safety. The type of circuit-breaker/contactor coordination selected can reduce maintenance costs in the event of a motor short-circuit by minimizing the time required to make the necessary repairs and the cost of replacement equipment. The suggested combinations provide type 1 or type 2 coordination depending on the drive rating. Type 2 coordination: A motor short-circuit will not damage the device or affect its settings. The motor starter must be able to operate once the electrical fault has been removed. The electrical isolation provided by the circuit- breaker will not be affected by the short-circuit. Welding of the contactor contacts is permissible if they can be separated easily. Type 1 coordination: The electrical isolation provided by the circuit-breaker will not be affected by the incident and no other elements apart from the contactor are damaged as a result of the motor short-circuit. The drive controls the motor, provides protection against short-circuits between the drive and the motor and protects the motor cable against overloads. The overload protection is provided by the drive's motor thermal protection. If this protection is removed, external thermal protection must be provided. Before restarting the installation, the cause of the trip must be removed. Motor starters for IP 20 drives Motor Drive Circuit-breaker Line contactor Power (1) Reference Reference (2) Rating Reference (3) (4) kW HP A Supply voltage 200…240 V 50/60 Hz single phase - Type 2 coordination 0.37 0.5 6.3 0.75 1 10 1.5 2 18 2.2 3 25 3 25 4 5 40 5.5 7.5 50 Supply voltage 200…240 V 50/60 Hz single phase - Type 1 coordination 0.37 0.5 10 0.75 1 14 1.5 2 18 2.2 3 25 3 25 4 5 40 5.5 7.5 50 (1) Standard power ratings for 230 V 50/60 Hz 4-pole motors. The values expressed in HP conform to the NEC (National Electrical Code). (2) Breaking capacity of circuit-breakers according to standard IEC 60947-2: Circuit-breaker Icu (kA) for 240 V GV2 L 50 GV3 L 100 (3) Composition of contactors: LC1 Dpp: 3 poles + 1 N/O auxiliary contact and 1 N/C auxiliary contact. (4) Replace ppwith the control circuit voltage reference given in the table below: Volts a 24 48 110 220 230 240 LC1 D 50 Hz B5 E5 F5 M5 P5 U5 60 Hz B6 E6 F6 M6 U6 50/60 Hz B7 E7 F7 M7 P7 U7 For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre. (5) A line choke must be added, see page 60805/16. Combinations for customer assembly Variable speed drives Altivar 71 Motor starters: 200…240 V supply voltage DF526131 DF526153 PF101002 GV2 L20 + LC1 D25pp + ATV 71HU22M3 60808-EN_Ver1.0.indd

Upload: lamduong

Post on 19-Feb-2019

216 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Combinations for Variable speed drives customer assembly ... · GV2 L22 + LC1 D25 pp + ATV 71HU30M3 DF526153 60808-EN_Ver1.0.indd. 4 Combinations for customer assembly (continued)

2

ApplicationsCircuit-breaker/contactor/drive combinations can be used to ensure continuous service of the installation with optimum safety.The type of circuit-breaker/contactor coordination selected can reduce maintenance costs in the event of a motor short-circuit by minimizing the time required to make the necessary repairs and the cost of replacement equipment. The suggested combinations provide type 1 or type 2 coordination depending on the drive rating.

Type 2 coordination: A motor short-circuit will not damage the device or affect its settings. The motor starter must be able to operate once the electrical fault has been removed. The electrical isolation provided by the circuit-breaker will not be affected by the short-circuit. Welding of the contactor contacts is permissible if they can be separated easily.

Type 1 coordination: The electrical isolation provided by the circuit-breaker will not be affected by the incident and no other elements apart from the contactor are damaged as a result of the motor short-circuit.

The drive controls the motor, provides protection against short-circuits between the drive and the motor and protects the motor cable against overloads. The overload protection is provided by the drive's motor thermal protection. If this protection is removed, external thermal protection must be provided.Before restarting the installation, the cause of the trip must be removed.

Motor starters for IP 20 drives Motor Drive Circuit-breaker Line contactor Power(1)

Reference Reference (2)

Rating Reference (3) (4)

kW HP ASupply voltage 200…240 V 50/60 Hz single phase - Type 2 coordination

0.37 0.5 6.30.75 1 101.5 2 182.2 3 253 – 254 5 405.5 7.5 50

Supply voltage 200…240 V 50/60 Hz single phase - Type 1 coordination0.37 0.5 100.75 1 141.5 2 182.2 3 253 – 254 5 405.5 7.5 50

(1) Standard power ratings for 230 V 50/60 Hz 4-pole motors.The values expressed in HP conform to the NEC (National Electrical Code).

(2) Breaking capacity of circuit-breakers according to standard IEC 60947-2:Circuit-breaker Icu (kA) for 240 V

GV2 L 50GV3 L 100(3) Composition of contactors:

LC1 Dpp: 3 poles + 1 N/O auxiliary contact and 1 N/C auxiliary contact.(4) Replace ppwith the control circuit voltage reference given in the table below:

Volts a 24 48 110 220 230 240LC1 D 50 Hz B5 E5 F5 M5 P5 U5

60 Hz B6 E6 F6 M6 – U650/60 Hz B7 E7 F7 M7 P7 U7

For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.(5) A line choke must be added, see page 60805/16.

Combinations forcustomer assembly

Variable speed drives Altivar 71Motor starters: 200…240 V supply voltage

DF5

2613

1D

F526

153

PF1

0100

2

GV2 L20+LC1 D25pp+ATV 71HU22M3

60808-EN_Ver1.0.indd

Page 2: Combinations for Variable speed drives customer assembly ... · GV2 L22 + LC1 D25 pp + ATV 71HU30M3 DF526153 60808-EN_Ver1.0.indd. 4 Combinations for customer assembly (continued)

3

Combinations forcustomer assembly (continued)

Motor starters for IP 20 drives Motor Drive Circuit-breaker Line contactor Power (1) Reference Reference (2) Rating Irm Reference (3) (4)kW HP A AThree-phase supply voltage 200…240 V 50/60 Hz - Type 2 coordination

0.37 0.5 4 –0.75 1 10 –1.5 2 10 –2.2 3 14 –3 – 18 –4 5 25 –5.5 7.5 40 –7.5 10 50 –11 15 65 –15 20 80 48018.5 25 100 60022 30 100 60030 40 150 135037 50 150 135045 60 220 198055 75 220 198075 100 320 1920Three-phase supply voltage 200…240 V 50/60 Hz - Type 1 coordination

0.37 0.5 4 –0.75 1 10 –1.5 2 10 –2.2 3 14 –3 – 18 –4 5 25 –5.5 7.5 40 –7.5 10 50 –11 15 65 –15 20 80 48018.5 25 100 60022 30 100 60030 40 150 135037 50 150 135045 60 220 198055 75 220 198075 100 320 1920

(1) Standard power ratings for 230 V 50/60 Hz 4-pole motors.The values expressed in HP conform to the NEC (National Electrical Code).

(2) NS80HMA, NSXppp: Products sold under the Merlin Gerin brand. For references to be completed, replace the dot with the letter corresponding to the circuit-breaker breaking performance (B, F, N, H, S, L). Breaking capacity of circuit-breakers according to standard IEC 60947-2:

Circuit-breaker Icu (kA) for 240 VB F N H S L

130 – – – – – –50 – – – – – –100 – – – – – –– 40 85 90 100 120 150– – 40 85 100 120 150

(3) Composition of contactors:LC1 Dpp: 3 poles + 1 N/O auxiliary contact and 1 N/C auxiliary contact.LC1 Fppp: 3 poles. To add auxiliary contacts or other accessories, please refer to the “Motor-starter solutions - Control and protection components” catalogue.

(4) Replace pp with the control circuit voltage reference given in the table below:Volts a 24 48 110 220 230 24050 Hz60 Hz50/60 Hz50 Hz (LX1 coil)60 Hz (LX1 coil)40…400 Hz (LX9 coil)50 Hz (LX1 coil)60 Hz (LX1 coil)40…400 Hz (LX9 coil)40…400 Hz (LX1 coil)

For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.

Variable speed drives Altivar 71Motor starters: 200…240 V supply voltage

PF1

0100

3

GV2 L22+LC1 D25pp+ATV 71HU30M3

DF5

2615

3D

F526

131

60808-EN_Ver1.0.indd

Page 3: Combinations for Variable speed drives customer assembly ... · GV2 L22 + LC1 D25 pp + ATV 71HU30M3 DF526153 60808-EN_Ver1.0.indd. 4 Combinations for customer assembly (continued)

4

Combinations forcustomer assembly (continued)

Motor starters for IP 20 drives Motor Drive Circuit-breaker Line contactorPower (1) Reference Reference (2) Rating Irm Reference (3) (4)kW HP A AThree-phase supply voltage 380…415 V 50/60 Hz - Type 2 coordination

0.75 1 4 –1.5 2 6.3 –2.2 3 10 –3 – 14 –4 5 14 –5.5 7.5 25 –7.5 10 32 –11 15 40 –15 20 50 –18.5 25 50 –22 30 65 –30 40 80 48037 50 100 80045 60 150 135055 75 150 135075 100 220 198090 125 220 1980110 150 220 1980132 200 320 1920160 250 320 1920200 300 320 1920220 350 500 3000250 400 500 3000280 450 500 3000315 500 NS800L Micrologic 2 or 5 500 3000355 – NS800L Micrologic 2 or 5 800 1600400 600 NS800L Micrologic 2 or 5 800 1600500 700 NS1000L Micrologic 2 or 5 1000 2000

(1) Standard power ratings for 4-pole motors 50/60 Hz 400 V.The values expressed in HP comply with the NEC (National Electrical Code).

(2) NS80HMA, NSXppp, NS800L, NS1000L: Products sold under the Merlin Gerin brand.For references to be completed, replace the dot with the letter corresponding to the circuit-breaker breaking performance (B, F, N, H, S, L).Breaking capacity of circuit-breakers according to standard IEC 60947-2:

Circuit-breaker Icu (kA) for 400 VB F N H S L

130 – – – – – –50 – – – – – –70 – – – – – –– 25 36 50 70 100 150– – 36 50 70 100 150– – – – – – 150

(3) Composition of contactors:LC1 Dpp: 3 poles + 1 N/O auxiliary contact and 1 N/C auxiliary contact.LC1 Fppp , LC1 B: 3 poles. To add auxiliary contacts or other accessories, please refer to the “Motor-starter solutions - Control and protection components” catalogue.

(4) Replace pp with the control circuit voltage reference given in the table below:Volts a 24 48 110 220 230 24050 Hz60 Hz50/60 Hz50 Hz (LX1 coil)60 Hz (LX1 coil)40…400 Hz (LX9 coil)40…400 Hz (LX1 coil)40…400 Hz (LX1 coil)40…400 Hz (LX1 coil)40…400 Hz (LX1 coil)50…400 Hz (WB1 coil)

For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.

Variable speed drives Altivar 71Motor starters: 380…415 V supply voltage

PF0

9551

6P

F107

476S

E

NSX160pMA150 +LC1 D115pp+ATV 71HD45N4

DF5

2615

8

60808-EN_Ver1.0.indd

Page 4: Combinations for Variable speed drives customer assembly ... · GV2 L22 + LC1 D25 pp + ATV 71HU30M3 DF526153 60808-EN_Ver1.0.indd. 4 Combinations for customer assembly (continued)

5

Combinations forcustomer assembly (continued)

Variable speed drives Altivar 71Motor starters: 380…415 V supply voltage

Motor starters for IP 20 drives Motor Drive Circuit-breaker Line contactorPower (1) Reference Reference (2) Rating Irm Reference (3) (4)kW HP A AThree-phase supply voltage 380…415 V 50/60 Hz - Type 1 coordination

0.75 1 4 –1.5 2 6.3 –2.2 3 10 –3 – 14 –4 5 14 –5.5 7.5 25 –7.5 10 32 –11 15 40 –15 20 50 –18.5 25 50 –22 30 65 –30 40 80 48037 50 100 80045 60 150 135055 75 150 135075 100 220 198090 125 220 1980110 150 220 1980132 200 320 1920160 250 320 1920200 300 320 1920220 350 500 3000250 400 500 3000280 450 500 3000315 500 NS800L Micrologic

2 or 5 (LR OFF)500 3000

355 – NS800L Micrologic 2 or 5 (LR OFF)

800 1600

400 600 NS800L Micrologic 2 or 5 (LR OFF)

800 1600

500 700 NS1000L Micrologic 2 or 5 (LR OFF)

1000 2000

(1) Standard power ratings for 4-pole motors 50/60 Hz 400 V.The values expressed in HP comply with the NEC (National Electrical Code).

(2) NS80HMA, NSXppp, NS800L, NS1000L: Products sold under the Merlin Gerin brand.For references to be completed, replace the dot with the letter corresponding to the circuit-breaker breaking performance (B, F, N, H, S, L).Breaking capacity of circuit-breakers according to standard IEC 60947-2:

Circuit-breaker Icu (kA) for 400 VB F N H S L

130 – – – – – –50 – – – – – –70 – – – – – –– 25 36 50 70 100 150– – 36 50 70 100 150– – – – – – 150

(3) Composition of contactors:LC1 Dpp: 3 poles + 1 N/O auxiliary contact and 1 N/C auxiliary contact.LC1 Fppp: 3 poles. To add auxiliary contacts or other accessories, please refer to the “Motor-starter solutions - Control and protection components” catalogue.

(4) Replace pp with the control circuit voltage reference given in the table below:Volts a 24 48 110 220 230 24050 Hz60 Hz50/60 Hz50 Hz (LX1 coil)60 Hz (LX1 coil)40…400 Hz (LX9 coil)40…400 Hz (LX1 coil)40…400 Hz (LX1 coil)40…400 Hz (LX1 coil)40…400 Hz (LX1 coil)50…400 Hz (WB1 coil)

For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.

PF0

9551

6P

F107

476S

E

NSX160pMA150 +LC1 D115pp+ATV 71HD45N4

DF5

2615

8

60808-EN_Ver1.0.indd

Page 5: Combinations for Variable speed drives customer assembly ... · GV2 L22 + LC1 D25 pp + ATV 71HU30M3 DF526153 60808-EN_Ver1.0.indd. 4 Combinations for customer assembly (continued)

6

Combinations forcustomer assembly (continued)

Motor starters for IP 20 drives Motor Drive Circuit-breaker Line contactorPower (1) Reference Reference (2) Rating Irm Reference (3) (4)kW HP A AThree-phase supply voltage 440…480 V 50/60 Hz - Type 2 coordination

0.75 1 4 –1.5 2 6.3 –2.2 3 10 –3 – 10 –4 5 14 –5.5 7.5 25 –7.5 10 32 –11 15 40 –15 20 50 –18.5 25 50 –22 30 50 –30 40 65 –37 50 100 60045 60 100 60055 75 150 135075 100 150 135090 125 150 1350110 150 220 1980132 200 220 1980160 250 320 1920200 300 320 1920220 350 320 1920250 400 500 3000280 450 500 3000315 500 NS800L Micrologic 2 or 5 500 3000355 – NS800L Micrologic 2 or 5 500 3000400 600 NS800L Micrologic 2 or 5 800 1600500 700 NS1000L Micrologic 2 or 5 1000 2000

(1) Standard power ratings for 400 V 50/60 Hz 4-pole motors.The values expressed in HP conform to the NEC (National Electrical Code).

(2) NS80HMA, NSXppp, NS800L, NS1000L: Products sold under the Merlin Gerin brand.For references to be completed, replace the dot with the letter corresponding to the circuit-breaker breaking performance (B, F, N, H, S, L).Breaking capacity of circuit-breakers according to standard IEC 60947-2:

Circuit-breaker Icu (kA) for 440 VB F N H S L

130 – – – – – –20 – – – – – –50 – – – – – –65 – – – – – –– 20 35 50 65 90 130– – 30 42 65 90 130– – – – – – 130

(3) Composition of contactors:LC1 Dpp: 3 poles + 1 N/O auxiliary contact and 1 N/C auxiliary contact.LC1 Fppp: 3 poles. To add auxiliary contacts or other accessories, please refer to the “Motor-starter solutions - Control and protection components” catalogue.

(4) Replace pp with the control circuit voltage reference given in the table below:Volts a 24 48 110 220 230 24050 Hz60 Hz50/60 Hz50 Hz (LX1 coil)60 Hz (LX1 coil)40…400 Hz (LX9 coil)40…400 Hz (LX1 coil)40…400 Hz (LX1 coil)40…400 Hz (LX1 coil)

For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.

Variable speed drives Altivar 71Motor starters: 440…480 V supply voltage

PF0

9551

6P

F107

476S

E

NSX160pMA150 +LC1 D115pp+ATV 71HD55N4

DF5

2615

8

60808-EN_Ver1.0.indd

Page 6: Combinations for Variable speed drives customer assembly ... · GV2 L22 + LC1 D25 pp + ATV 71HU30M3 DF526153 60808-EN_Ver1.0.indd. 4 Combinations for customer assembly (continued)

7

Combinations forcustomer assembly (continued)

Motor starters for IP 20 drives Motor Drive Circuit-breaker Line contactorPower (1) Reference Reference (2) Rating Irm Reference (3) (4)kW HP A AThree-phase supply voltage 440…480 V 50/60 Hz - Type 1 coordination

0.75 1 4 –1.5 2 6.3 –2.2 3 10 –3 – 10 –4 5 14 –5.5 7.5 25 –7.5 10 32 –11 15 40 –15 20 50 –18.5 25 50 –22 30 50 –30 40 65 –37 50 100 60045 60 100 60055 75 150 135075 100 150 135090 125 150 1350110 150 220 1980132 200 220 1980160 250 320 1920200 300 320 1920220 350 320 1920250 400 500 3000280 450 500 3000315 500 NS800L Micrologic 2 or 5 500 3000355 – NS800L Micrologic 2 or 5 500 3000400 600 NS800L Micrologic 2 or 5 800 1600500 700 NS1000L Micrologic 2 or 5 1000 2000

(1) Standard power ratings for 400 V 50/60 Hz 4-pole motors.The values expressed in HP conform to the NEC (National Electrical Code).

(2) NS80HMA, NSXppp, NS800L, NS1000L: Products sold under the Merlin Gerin brand.For references to be completed, replace the dot with the letter corresponding to the circuit-breaker breaking performance (B, F, N, H, S, L).Breaking capacity of circuit-breakers according to standard IEC 60947-2:

Circuit-breaker Icu (kA) for 440 VB F N H S L

130 – – – – – –20 – – – – – –50 – – – – – –65 – – – – – –– 20 35 50 65 90 130– – 30 42 65 90 130– – – – – – 130

(3) Composition of contactors:LC1 Dpp: 3 poles + 1 N/O auxiliary contact and 1 N/C auxiliary contact.LC1 Fppp: 3 poles. To add auxiliary contacts or other accessories, please refer to the “Motor-starter solutions - Control and protection components” catalogue.

(4) Replace pp with the control circuit voltage reference given in the table below:Volts a 24 48 110 220 230 24050 Hz60 Hz50/60 Hz50 Hz (LX1 coil)60 Hz (LX1 coil)40…400 Hz (LX9 coil)40…400 Hz (LX1 coil)40…400 Hz (LX1 coil)40…400 Hz (LX1 coil)

For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.

Variable speed drives Altivar 71Motor starters: 440…480 V supply voltage

PF0

9551

6P

F107

476S

E

NSX160pMA150 +LC1 D115pp+ATV 71HD55N4

DF5

2615

8

60808-EN_Ver1.0.indd

Page 7: Combinations for Variable speed drives customer assembly ... · GV2 L22 + LC1 D25 pp + ATV 71HU30M3 DF526153 60808-EN_Ver1.0.indd. 4 Combinations for customer assembly (continued)

8

Combinations for customer assembly (continued)

Motor starters for IP 54 drives Motor Drive Circuit-breaker Line contactorPower (1) Reference Reference (2) Rating Irm Reference (3) (4)kW HP A AThree-phase supply voltage 380…415 V 50/60 Hz - Type 2 coordination

0.75 1 4 –1.5 2 6.3 –2.2 3 10 –3 – 14 –4 5 14 –5.5 7.5 25 –7.5 10 32 –11 15 40 –15 20 50 –18.5 25 50 –22 30 65 –30 40 80 48037 50 100 80045 60 150 135055 75 150 135075 100 150 1350

Three-phase supply voltage 440…480 V 50/60 Hz - Type 2 coordination0.75 1 4 –1.5 2 6.3 –2.2 3 10 –3 – 10 –4 5 14 –5.5 7.5 25 –7.5 10 32 –11 15 40 –15 20 50 –18.5 25 50 –22 30 65 –30 40 100 60037 50 100 60045 60 100 60055 75 150 135075 100 150 1350

(1) Standard power ratings for 400 V 50/60 Hz 4-pole motors.The values expressed in HP conform to the NEC (National Electrical Code).

(2) NS80HMA, NSXppp: Products sold under the Merlin Gerin brand.For references to be completed, replace the dot with the letter corresponding to the circuit-breaker breaking performance (N, H, L). Breaking capacity of circuit-breakers according to standard IEC 60947-2:

Circuit-breaker Icu (kA) for 400 VB F N H S L

100 – – – – – –50 – – – – – –70 – – – – – –– 25 36 50 70 100 150

Circuit-breaker Icu (kA) for 440 VB F N H S L

100 – – – – – –20 – – – – – –50 – – – – – –– 20 35 50 65 90 130

(3) Composition of contactors:LC1 Dpp: 3 poles + 1 N/O auxiliary contact and 1 N/C auxiliary contact.

(4) Replace pp with the control circuit voltage reference given in the table below:Volts a 24 48 110 220 230 24050 Hz60 Hz50/60 Hz

For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.

Variable speed drives Altivar 71Motor starters: 380…480 V supply voltage

PF0

9551

6D

F510

7482

NSX160pMA150 +LC1 D115pp+ATV 71WD55N4

DF5

2615

8

60808-EN_Ver1.0.indd

Page 8: Combinations for Variable speed drives customer assembly ... · GV2 L22 + LC1 D25 pp + ATV 71HU30M3 DF526153 60808-EN_Ver1.0.indd. 4 Combinations for customer assembly (continued)

9

Motor starters for IP 20 drives on base plate Motor Drive Circuit-breaker Line contactorPower (1) Reference Reference (2) Rating Irm Reference (3) (4)kW HP A AThree-phase supply voltage 380…415 V 50/60 Hz - Type 2 coordination

0.75 1 4 –

1.5 2 6.3 –

2.2 3 10 –

3 – 14 –

4 5 14 –

5.5 7.5 25 –

7.5 10 32 –

Three-phase supply voltage 440…480 V 50/60 Hz - Type 2 coordination0.75 1 4 –

1.5 2 6.3 –

2.2 3 10 –

3 – 10 –

4 5 14 –

5.5 7.5 25 –

7.5 10 32 –

(1) Standard power ratings for 4-pole motors 50/60 Hz 400 V.The values expressed in HP comply with the NEC (National Electrical Code).

(2) Breaking capacity of circuit-breakers according to standard IEC 60947-2:Circuit-breaker Icu (kA) for 400 V

10050

(3) Composition of contactors:LC1 Dpp: 3 poles + 1 N/O auxiliary contact and 1 N/C auxiliary contact.

(4) Replace pp with the control circuit voltage reference given in the table below:Volts a 24 48 110 220 230 24050 Hz60 Hz50/60 Hz

For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.

Combinations for customer assembly (continued)

Variable speed drives Altivar 71Motor starters: 380…480 V supply voltage

GV2 L16+LC1 D18pp+ATV 71PU40N4Z

DF5

2613

1D

F526

153

60808-EN_Ver1.0.indd

Page 9: Combinations for Variable speed drives customer assembly ... · GV2 L22 + LC1 D25 pp + ATV 71HU30M3 DF526153 60808-EN_Ver1.0.indd. 4 Combinations for customer assembly (continued)

10

Motor starters for IP 20 drives Motor Drive Circuit-breaker Line contactorPower (1) Reference Reference (2) Rating Irm Reference (3) (4)kW A AThree-phase supply voltage 690 V 50/60 Hz - Type 2 coordination

2.2 6.3 783 6.3 784 10 1385.5 10 1387.5 14 17011 18 22315 25 32718.5 25 35022 32 44830 40 56037 50 70045 65 91055 100 110075 100 110090 320 2880110 320 2880132 320 2880160 320 2880200 320 2880200 630 5670250 630 5670315 630 5670400 630 5670500 800 7200

(1) Standard power ratings for 690 V 50 Hz 4-pole motors.(2) NSppp: Products sold under the Merlin Gerin brand.

Breaking capacity of circuit-breakers according to standard IEC 60947-2:Circuit-breaker Icu (kA) for 690 V

4575

(3) Composition of contactors:LC1 Dpp: 3 poles + 1 N/O auxiliary contact and 1 N/C auxiliary contact.LC1 Fppp: 3 poles. To add auxiliary contacts or other accessories, please refer to the “Motor-starter solutions - Control and protection components” catalogue.

(4) Replace pp with the control circuit voltage reference given in the table below:Volts a 24 48 110 220 230 24050 Hz60 Hz50/60 Hz40…400 Hz (LX1 coil)40…400 Hz (LX1 coil)40…400 Hz (LX1 coil)

For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.

Combinations for customer assembly (continued)

Variable speed drives Altivar 71Motor starters: 690 V supply voltage

DF5

2613

1D

F526

153

1010

14

GV2 L16+LC1 D25pp+ATV 71HU75Y

60808-EN_Ver1.0.indd

Page 10: Combinations for Variable speed drives customer assembly ... · GV2 L22 + LC1 D25 pp + ATV 71HU30M3 DF526153 60808-EN_Ver1.0.indd. 4 Combinations for customer assembly (continued)

11

Motor starters for IP 20 drives Motor Drive Circuit-breaker Line contactorPower (1) Reference Reference (2) Rating Irm Reference (3) (4)kW A AThree-phase supply voltage 690 V 50/60 Hz - Type 1 coordination

250 500 –315 500 –400 500 –500 630 –630 800 –

(1) Standard power ratings for 690 V 50 Hz 4-pole motors.(2) NSX630LMA, NSppp: Products sold under the Merlin Gerin brand.

Breaking capacity of circuit-breakers according to standard IEC 60947-2:Circuit-breaker Icu (kA) for 690 V

3575

(3) Composition of contactors:LC1 Fppp, LC1 BL: 3 poles. To add auxiliary contacts or other accessories, please refer to the “Motor-starter solutions - Control and protection components” catalogue.

(4) Replace pp with the control circuit voltage reference given in the table below:Volts a 24 48 110 220 230 24040…400 Hz (LX1 coil) –50…400 Hz (WB1 coil) –

For other voltages available between 24 V and 660 V, or a DC control circuit, please contact our Customer Care Centre.

Combinations for customer assembly (continued)

Variable speed drives Altivar 71Motor starters: 690 V supply voltage

NSX630LMA500+LC1 F400+ATV 71HC25Y

PF1

0758

6SE

PF1

0327

3P

F526

089

60808-EN_Ver1.0.indd