    A LOAD DATA Unit

    A1 Maximum Wind Velocity (V) > 110 Km/Hour

    A2 Exposure Factor (Category C@ 60ft above ground) 1.07

    A3 Wind Pressure (P) 0.66 Kpa

    A4 Recommended Design Pressure (W) SI Unit 0.99 Kpa

    Metric Unit 100.85 Kg/m^2

    Imperial Unit 20.66 psf

    B GLASS DATA Unit

    B1 Fixed Panel Thickness (Tp) > 12 mm

    B2 Width of Panel Between Supports (Wp) > 1.60 meter

    B3 Height of Panel Parallel to Supports (Hp) > 3.00 meter

    B4 Fin Thickness (Tf) > 12 mm

    B5 Width of Fin (Wf) > 0.30 meter

    B6 Overall Height of Fin (Fh) > 3.00 meter

    C CALCULATING STRESS OF FIXED PANEL Unit

    C1 Bending Moment (M) 0.32 KN-M

    C2 Allowable Bending Stress of Toughened Glass (Fba) 50.0 N/mm^2

    C3 Actual Bending Stress of Fixed Panel (Fb) 13.18 N/mm^2

    3.79 Safety Factor

    D CHECKING INDIVIDUAL PANEL DEFLECTION Unit

    D1 Allowable Deflection (Ya) ; L/ 175 9.14 mm

    D2 Actual Deflection (Y) 8.14 mm

    1.12 Safety Factor

    E CALCULATING STRESS OF FIN Unit

    E1 Total Weight of System 1677.51 N

    E2 Working Load 1.58 KN/m

    E3 Bending Moment of Fin 1.78 KN-m

    E4 Allowable Bending Stress for Tempered Glass 50.0 N/mm^2

    E5 Actual Bending Stress of Fins 10.35 N/mm^2

    4.83 Safety Factor

    CHECKING STRESS OF FIN AT SUPPORT (AFFECTED BY HOLES)

    E6 Number of Holes (20mm dia.) 3 Total Area: 1,945.49 mm2

    E7 Combine Load (Dead Load + Windload) 4050.6 N

    E8 Allowable Bending Stress for Tempered Glass 50.0 N/mm^2

    E9 Actual Stress of Fins @ Support (Reduce Area due to Holes) 2.45 N/mm^2

    20.42 Safety Factor

    F CHECKING FOR OVERALL FIN DEFLECTION Unit

    F1 Fin Deflection Limit: L / 175 17.14 mm

    F2 Actual Fin Deflection (Should Not Exceed 19mm ) 0.34 mm

    50.12 Safety Factor

    G

    1.60

    W= 0.99 Kpa

    3.00

    0.34

    1.60

    Fig. 01: Fixed Panel Dimension Fig.02 : Load/Support Diagram

    Structural Glass Analysis Design of Simply-Supported Glass with Semi-Rigid FinDesign of Simply-Supported Glass with Semi-Rigid FinDesign of Simply-Supported Glass with Semi-Rigid FinDesign of Simply-Supported Glass with Semi-Rigid Fin

    Project Name:

    Location:

    Leaders Aluminium

    Al Nabooda Building

    Al Nabooda Building

    Dubai

    November 4, 2014

    DEFLECTION IS WITH-IN LIMIT >>>

    DESIGN IS ACCEPTABLE >>>

    DESIGN DIAGRAM

    DESIGN IS ACCEPTABLE >>>

    Note: Verify available glass size and tempering capacity