commercial piping diagram - patterson-kelley · these piping diagrams are an example of possible...

85
Commercial Piping Diagram Winter 2020 *For proper formatting, download to computer and view in Adobe Acrobat*

Upload: others

Post on 19-Oct-2020

4 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Commercial Piping DiagramWinter 2020

*For proper formatting, download to computer and

view in Adobe Acrobat*

Page 2: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Disclaimer:These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities should be always be verified with a qualified engineer’s consultation on all installation details including piping schematics. Please consult Patterson-Kelley, LLC Boiler & Water-Heater Owner’s Manuals for correct operational standards for all P-K boilers and water-heaters. Patterson-Kelley LLC cannot, and will not, be held liable for any lack of due diligence of any party involved in the installation of its products.

Section 1; Starting on Page 2: Hybrid Piping System Boilers

Section 2; Starting on Page 6: Primary Piping System Boilers

Section 3; Starting on Page 10: Primary Secondary Piping System Boilers

Section 4; Starting on Page 20: Primary Condensing System Water Heater (Direct Fired)

Section 5; Starting on Page 29: Primary Non-Condensing System Water Heater (Direct Fired)

Section 6; Starting on Page 33: Product Specific: HiDRA, Mach ‘n’ Roll, Compact, Duration III

Table of Contents:

Page 3: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Flow Meter

Primary

HYDRONIC SYSTEM

PIPING

TT-3

T

T-3

From System

To SystemHouse Pumps

Primary loop diagram

T-3

PK

Co

nd

en

sin

g B

oile

r

Boiler Temperature Sensors to control Boiler Firing Rate

Header Temperature and OA Reset

Schedule to Control staging

Condensate

Notes:

1. Minimum pipe size to boiler equal to boiler supply/return connection size.

2. Return/supply header piping to be at least one pipesize larger than piping to equipment

3. Bypass loop recommended on primary-onlysystems to decrease heat exchanger wear during

boiler off times4. 2 way control valves necessary on primary andbypass loops, can be operated by boiler controls

System fill

3

Page 4: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Flow Meter

Primary

HYDRONIC SYSTEM

PIPING

TT-3

T

T-3

From System

To SystemHouse Pumps

Primary loop diagram

Boiler Temperature Sensors to control Boiler Firing Rate

Header Temperature and OA Reset

Schedule to Control staging

Patterson-Kelley

1200 Thermific

Notes:

1. Minimum pipe size to boiler equal to boiler supply/return connection size.

2. Return/supply header piping to be at least one pipesize larger than piping to equipment

3. Bypass loop recommended on primary-onlysystems to decrease heat exchanger wear during

boiler off times4. 2 way control valves necessary on primary andbypass loops, can be operated by boiler controls

System fill

4

Page 5: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Flow Meter

Primary

HYDRONIC SYSTEM

PIPING

TT-3

T

T-3

From System

Primary loop diagram

PK

Co

nd

en

sin

g B

oile

r

Boiler Temperature Sensors to control Boiler Firing Rate

Header Temperature and OA Reset

Schedule to Control staging

Condensate

PK

Co

nd

en

sin

g B

oile

r

Notes:

1. Minimum pipe size to boiler equal to boiler supply/return connection size.

2. Return/supply header piping to be at least one pipe size larger than piping to equipment

3. Bypass loop recommended on primary-only systems to decrease heat exchanger wear during

boiler off times4. 2 way control valves necessary on primary and bypass loops, can be operated by boiler controls

To SystemHouse Pumps

System fill

5

Page 6: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Primary

HYDRONIC SYSTEM

PIPING

TT-3

T

T-3

From System

Primary loop diagram

T-3

Boiler Temperature Sensors to control Boiler Firing Rate

Header Temperature and OA Reset

Schedule to Control staging

Patterson-Kelley

1200 Thermific

Patterson-Kelley

1200 Thermific Notes:

1. Minimum pipe size to boiler equal to boiler supply/return connection size.

2. Return/supply header piping to be at least one pipe size larger than piping to equipment

3. Bypass loop recommended on primary-only systems to decrease heat exchanger wear during

boiler off times4. 2 way control valves necessary on primary and bypass loops, can be operated by boiler controls

To SystemHouse Pumps

System fill

6

Page 7: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Flow Meter

Primary

HYDRONIC SYSTEM

PIPING

TT-3

T

T-3

From System

Primary loop diagram

T-3

PK

Co

nd

en

sin

g B

oile

r

Boiler Temperature Sensors to control Boiler Firing Rate

Header Temperature and OA Reset

Schedule to Control staging

Condensate

PK

Co

nd

en

sin

g B

oile

r

PK

Co

nd

en

sin

g B

oile

r

Notes:

1. Minimum pipe size to boiler equal to boiler supply/return connection size.

2. Return/supply header piping to be at least one pipe size larger than piping to equipment

3. Bypass loop recommended on primary-only systems to decrease heat exchanger wear during

boiler off times4. 2 way control valves necessary on primary and bypass loops, can be operated by boiler controls

To SystemHouse Pumps

System fill

7

Page 8: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Primary

HYDRONIC SYSTEM

PIPING

TT-3

T

T-3

From System

To SystemHouse Pumps

Primary loop diagram

Boiler Temperature Sensors to control Boiler Firing Rate

Header Temperature and OA Reset

Schedule to Control staging

Patterson-Kelley

1200 Thermific

Patterson-Kelley

1200 Thermific

Patterson-Kelley

1200 Thermific

Notes:

1. Minimum pipe size to boiler equal to boiler supply/return connection size.

2. Return/supply header piping to be at least one pipe size larger than piping to equipment

3. Bypass loop recommended on primary-only systems to decrease heat exchanger wear during

boiler off times4. 2 way control valves necessary on primary and bypass loops, can be operated by boiler controls

System fill

8

Page 9: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Flow Meter

Primary/Secondary

HYDRONIC SYSTEM

PIPING

TT-3

T

T-3

From System

To SystemHouse Pumps

Primary/Secondary loop diagram

T-3

PK

Co

nd

en

sin

g B

oile

r

Boiler Temperature Sensors to control Boiler Firing Rate

Header Temperature and OA Reset

Schedule to Control staging

Condensate

Notes:1. Header piping should be one pipe size larger than

direct boiler piping2. Primary Header should be 4" piping

3. Distance between 1st and 2nd tee should be no more than 4 pipe diameters

System fill

9

Page 10: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Primary/Secondary

HYDRONIC SYSTEM

PIPING

TT-3

T

T-3

From System

To SystemHouse Pumps

Primary/Secondary loop diagram

T-3

Boiler Temperature Sensors to control Boiler Firing Rate

Header Temperature and OA Reset

Schedule to Control staging

Patterson Kelley

Non condensing boiler

Notes:1. Header piping should be one pipe size larger than

direct boiler piping2. Primary Header should be 4" piping

3. Distance between 1st and 2nd tee should be no more than 4 pipe diameters

3 way valve

System fill

T

10

Page 11: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

System fill

Primary/Secondary

HYDRONIC SYSTEM

PIPING

TT-3

PK

Co

nd

en

sin

g B

oile

rT

T-3

From System

To SystemHouse Pumps

Primary/Secondary loop diagram

T-3

PK

Co

nd

en

sin

g B

oile

r

Boiler Temperature Sensors to control Boiler Firing Rate

Header Temperature and OA Reset

Schedule to Control staging

Condensate

Notes:1. Header piping should be one pipe size larger than

direct boiler piping2. Primary Header should be 4" piping

3. Distance between 1st and 2nd tee should be no more than 4 pipe diameters

T

11

Page 12: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

System fill

Primary/Secondary

HYDRONIC SYSTEM

PIPING

TT-3

PK

Co

nd

en

sin

g B

oile

rT

T-3

From System

To SystemHouse Pumps

Primary/Secondary loop diagram

T-3

PK

Co

nd

en

sin

g B

oile

r

Boiler Temperature Sensors to control Boiler Firing Rate

Header Temperature and OA Reset

Schedule to Control staging

Condensate

Notes:1. Header piping should be one pipe size larger than

direct boiler piping2. Primary Header should be 4" piping

3. Distance between 1st and 2nd tee should be nomore than 4 pipe diameters

T

12

Page 13: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Primary/Secondary

HYDRONIC SYSTEM

PIPING

TT-3

TT

-3

From System

Primary/Secondary loop diagram

T-3

Boiler Temperature Sensors to control Boiler Firing Rate

Header Temperature and OA Reset

Schedule to Control staging

Patterson Kelley

Non condensing boiler

Notes:1. Header piping should be one pipe size larger than

direct boiler piping2. Primary Header should be 4" piping

3. Distance between 1st and 2nd tee should be no more than 4 pipe diameters

3 way valve

Patterson Kelley

Non condensing boiler

System fill

To SystemHouse Pumps

T

13

Page 14: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Flow Meter

Primary/Secondary

HYDRONIC SYSTEM

PIPING

TT-3

PK

Co

nd

en

sin

g B

oile

rT

T-3

From System

To SystemHouse Pumps

Primary/Secondary loop diagram

T-3

PK

Co

nd

en

sin

g B

oile

r

Boiler Temperature Sensors to control Boiler Firing Rate

Header Temperature and OA Reset

Schedule to Control staging

Condensate

PK

Co

nd

en

sin

g B

oile

r

Notes:1. Header piping should be one pipe size larger than

direct boiler piping2. Primary Header should be 4" piping

3. Distance between 1st and 2nd tee should be nomore than 4 pipe diameters

System fill

14

Page 15: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Primary/Secondary

HYDRONIC SYSTEM

PIPING

TT-3

T

T-3

From System

Primary/Secondary loop diagram

T-3

Boiler Temperature Sensors to control Boiler Firing Rate

Header Temperature and OA Reset

Schedule to Control staging

Patterson Kelley

Non condensing boiler

Patterson Kelley

Non condensing boiler

Patterson Kelley

Non condensing boiler

Notes:1. Header piping should be one pipe size larger than

direct boiler piping2. Primary Header should be 4" piping

3. Distance between 1st and 2nd tee should be nomore than 4 pipe diameters

3 way valve

System fill

To SystemHouse PumpsT

15

Page 16: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Hybrid

HYDRONIC SYSTEM

PIPING

TT-3

Patterson-Kelley

Non condensing boiler

PK

Co

nd

en

sin

g B

oile

r

T

T-3

T-4 T

From System

To SystemHouse Pumps

Three Tee Piping allows for pre-heating from Condensing

Boilers to Non-condensing Boilers

T-3

PK

Co

nd

en

sin

g B

oile

r

Notes:1. Header piping should be one pipe size larger than

direct boiler piping2. Primary Header should be 4" piping

3. Distance between 2nd and 3rd tee should be nomore than 4 pipe diameters

Boiler Temperature Sensors to control Boiler Firing Rate

Header Temperature and OA Reset

Schedule to Control staging

Condensate

System fill

T-4 T

T

16

Page 17: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Flow Meter

Hybrid

HYDRONIC SYSTEM

PIPING

TT-3

Patterson-Kelley

Non condensing boilerPatterson-Kelley

Non condensing boiler

PK

Co

nd

en

sin

g B

oile

r

T

T-3

T-4 T

From System

To SystemHouse Pumps

Three Tee Piping allows for pre-heating from Condensing

Boilers to Non-condensing Boilers

T-3

PK

Co

nd

en

sin

g B

oile

r

Boiler Temperature Sensors to control Boiler Firing Rate

Header Temperature and OA Reset

Schedule to Control staging

Condensate

Notes:1. Header piping should be one pipe size larger than

direct boiler piping2. Primary Header should be 4" piping

3. Distance between 2nd and 3rd tee should be nomore than 4 pipe diameters

System fill

T

T

T-4

17

Page 18: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Flow Meter

Hybrid

HYDRONIC SYSTEM

PIPING

TT-3

Patterson-Kelley

Non condensing boiler

PK

Co

nd

en

sin

g B

oile

r

T

T-3

T-4T

From System

To SystemHouse Pumps

Three Tee Piping allows for pre-heating from Condensing

Boilers to Non-condensing Boilers

T-3

PK

Co

nd

en

sin

g B

oile

r

Boiler Temperature Sensors to control Boiler Firing Rate

Header Temperature and OA Reset

Schedule to Control staging

Condensate

PK

Co

nd

en

sin

g B

oile

r

Notes:1. Header piping should be one pipe size larger than

direct boiler piping2. Primary Header should be 4" piping

3. Distance between 2nd and 3rd tee should be nomore than 4 pipe diameters

System fill

T

T

T-4

18

Page 19: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Flow Meter

Hybrid

HYDRONIC SYSTEM

PIPING

TT-3

Patterson-Kelley

Non condensing boilerPatterson-Kelley

Non condensing boiler

PK

Co

nd

en

sin

g B

oile

r

T

T-3

T-4 T

From System

To SystemHouse Pumps

Three Tee Piping allows for pre-heating from Condensing

Boilers to Non-condensing Boilers

T-3

PK

Co

nd

en

sin

g B

oile

r

Boiler Temperature Sensors to control Boiler Firing Rate

Header Temperature and OA Reset

Schedule to Control staging

Condensate

PK

Co

nd

en

sin

g B

oile

r

Patterson-Kelley

Non condensing boilerNotes:

1. Header piping should be one pipe size larger than direct boiler piping

2. Primary Header should be 4" piping3. Distance between 2nd and 3rd tee should be no

more than 4 pipe diameters

System fill

T

T-4

T

19

Page 20: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Building recirculation

Cold water inlet

Hot water supply to buildingDomestic hot water with 1 condensing boiler and 1 storage tank

T

T

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into dedicated recirculation connection on side of HiDRA

4. 12k OHM tank sensor should be used in storage tanks

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Cond

ensing Bo

iler

20

Page 21: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Building recirculation

Cold water inlet

Hot water supply to building

Hot water supply to building

T

T

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into dedicated recirculation connection on side of HiDRA

4. 12k OHM tank sensor should be used in storage tanks

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Domestic hot water with 1 condensing boiler and 2 storage tanks

Cond

ensing Bo

iler

21

Page 22: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Cold water inlet

Hot water supply to buildingDomestic hot water with 1 condensing boiler and 1 storage tank

T

T

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into dedicated recirculation connection on side of HiDRA

4. 12k OHM tank sensor should be used in storage tanks

Co

nd

en

sing

Bo

iler

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

22

Page 23: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Building recirculation

Cold water inlet

Hot water supply to building

Hot water supply to building

Domestic hot water with 2 condensing boilers and 2 storage tanks

T

TNotes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into dedicated recirculation connection on side of HiDRA

4. 12k OHM tank sensor should be used in storage tanks

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Cond

ensing Bo

iler

Cond

ensing Bo

iler

23

Page 24: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Cold water inlet

Hot water supply to building

Domestic hot water with 2 condensing boiler and 1 storage tank

T

T

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into dedicated recirculation connection on side of HiDRA

4. 12k OHM tank sensor should be used in storage tanks

Cond

ensing Bo

iler

Cond

ensing Bo

iler

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

24

Page 25: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Building recirculation

Cold water inlet

Hot water supply to building

Domestic hot water with 2 condensing boilers and 1 storage tank

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into cold water inlet

4. 12k OHM tank sensor should be used in storage tanks

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Cond

ensing Boiler

Cond

ensing Boiler

T

T

25

Page 26: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Hot water supply to building

Building recirculation

Cold water inlet

Domestic hot water with 2 condensing boilers and 3 storage tanks

Hot water supply to building

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into cold water inlet

4. 12k OHM tank sensor should be used in storage tanks

T

T

Hot water supply to building

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Cond

ensing Bo

iler

Cond

ensing Bo

iler

26

Page 27: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Building recirculation

Cold water inlet

Hot water supply to buildingHot water supply to building

Domestic hot water with 3 condensing boilers and 2 storage tanks

T

T

T

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into cold water inlet

4. 12k OHM tank sensor should be used in storage tanks

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Cond

ensing Bo

iler

Cond

ensing Bo

iler

Cond

ensing Bo

iler

27

Page 28: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Building recirculation

Cold water inlet

Hot water supply to building

Domestic hot water with 4 condensing boilers and 2 storage tanks

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into cold water inlet

4. 12k OHM tank sensor should be used in storage tanks

T

T

T

Cond

ensing Boiler

Co

nd

en

sing

Bo

iler

Co

nd

ensin

g Bo

iler

Co

nd

en

sing

Bo

iler

Hot water supply to building

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

28

Page 29: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Building recirculationCold water inlet

Domestic hot water with 1 non-condensing boiler and 2 storage tanks

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into hot water supply

4. 12k OHM tank sensor should be used in storage tanks

T

T

Hot water supply to building Hot water supply to building

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

29

Page 30: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Building recirculationCold water inlet

Domestic hot water with 1 non-condensing boiler and 2 storage tanks

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into hot water supply

4. 12k OHM tank sensor should be used in storage tanks

T

T

Hot water supply to building Hot water supply to building

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

30

Page 31: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Building recirculationCold water inlet

Domestic hot water with 1 non-condensing boiler and 2 storage tanks

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into hot water supply

4. 12k OHM tank sensor should be used in storage tanks

T

T

Hot water supply to building Hot water supply to building

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

31

Page 32: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Building recirculationCold water inlet

Domestic hot water with 1 non-condensing boiler and 2 storage tanks

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into hot water supply

4. 12k OHM tank sensor should be used in storage tanks

T

T

Hot water supply to building Hot water supply to building

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

32

Page 33: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Double HiDRA piping diagram

HiDRA

Building Recirculation

Cold Water inlet

Hot water supplyHot Mixed

HiDRA

Condensate

Refer to mixing valve installation instructions

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into dedicated recirculation connection on side of HiDRA

TT

T

T

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

33

Page 34: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Double HiDRA with storage tank piping diagram

HiDRA

Building Recirculation

Cold Water inlet

Hot Mixed

HiDRA

Refer to mixing valve installation instructions

Hot water return

Hot water supply

Building supply

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into dedicated recirculation connection on side of HiDRA

4. 12k OHM tank sensor should be used in storage tanks

TT

T

T

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

34

Page 35: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Double HiDRA with storage tank piping diagram

HiDRA

Building Recirculation

Cold Water inlet

Hot Mixed

HiDRA

120 degree supply

140 degree supply

120 degree return

140 degree return

Refer to mixing valve installation instructions

T

T

T

T

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into dedicated recirculation connection on side of HiDRA

4. 12k OHM tank sensor should be used in storage tanks

5. Placing a temperature gauge next to a temperature sensor is recommended

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

35

Page 36: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Double HiDRA with storage tank piping diagram

HiDRA

Building Recirculation

Cold Water inlet

Hot water supply

Hot Mixed

HiDRA

Condensate

Refer to mixing valve installation instructions

TT

T

T

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into dedicated recirculation connection on side of HiDRA

4. 12k OHM tank sensor should be used in storage tanks

5. Placing a temperature gauge next to a temperature sensor is recommended

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

36

Page 37: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Single HiDRA piping diagram

Building Recirculation

Cold Water inlet

Hot water supplyHot Mixed

HiDRA

Condensate

Refer to mixing valve installation instructions

TT

T

T

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into dedicated recirculation connection on side of HiDRA

4. Placing a temperature gauge next to a temperature sensor is recommended

37

Page 38: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Triple HiDRA piping diagram direct return

HiDRA

Building Recirculation

Cold Water inlet

Hot water supply Hot Mixed

HiDRAHiDRA

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

Temp gauge

Refer to mixing valve installation instructions

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into dedicated recirculation connection on side of HiDRA

TT

T

38

Page 39: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Triple HiDRA piping diagram

HiDRA

Building Recirculation

Cold Water inlet

Hot water supplyHot Mixed

HiDRA

Condensate

Refer to mixing valve installation instructions

HiDRA

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into dedicated recirculation connection on side of HiDRA

4. Placing a temperature gauge next to a temperature sensor is recommended

TT

T

T

39

Page 40: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Triple HiDRA with storage tank piping diagram

HiDRA

Building Recirculation

Cold Water inlet

Hot water supply

Hot Mixed

HiDRA

Condensate

HiDRA

Mixing valve

T

T

T T

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into dedicated recirculation connection on side of HiDRA

4. 12k OHM tank sensor should be used in storage tanks

5. Placing a temperature gauge next to a temperature sensor is recommended

40

Page 41: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Double Mach N Roll with 200 gallon tank piping diagram

Building Recirculation

Cold Water inlet

Hot water supplyHot Mixed

Refer to mixing valve installation instructions

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

Temp gauge

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet

3. Building recirculation (if utilized) should be tied into cold water inlet

4. 12k OHM tank sensor should be used in storage tanks

TT

T

T

41

Page 42: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Double Mach N Roll with 200 gallon tank piping diagram

Building Recirculation

Cold Water inlet

Hot water supply

Hot Mixed

Refer to mixing valve installation instructions

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

Temp gauge

42

Page 43: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Tank

Sensor

Hot Water to Building

Cold Water 0

5 8

10 0

5 8

10

Recirculation Pump

BronzeDomestic Pump

Hot Water Outlet

Hi-Limitto drain

PK

Compact

0

3

0

155

1

0

PKPK

03

0

1

5510

Relief Valve to drain

Hot WaterN.C. Bypass

N.C. Bypass

Expansion

Tank

Mixed Hot

Mixing Valve

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. Refer to ASHRAE 90.1 for return water %

5. Bronze domestic pump must be sized for full COMPACT size

6. All COMPACTS must have a section VIII relief valve downstream

Single water to water 2 way valve Compact with 2 storage tanks

T

T

T

0 30

155

10

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gaugeRelief valve

Control valve

43

Page 44: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Tank

Sensor

Hot Water to Building

Cold Water 0

5 8

10 0

5 8

10

Recirculation Pump

BronzeDomestic Pump

Hot Water Outlet

Hi-Limitto drain

PK

Compact

0

3

0

155

1

0

PKPK

Relief Valve to drain

Hot WaterN.C. Bypass

N.C. Bypass

Expansion

Tank

Mixed Hot

Mixing Valve

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. Refer to ASHRAE 90.1 for return water %

5. Bronze domestic pump must be sized for full COMPACT size

6. All COMPACTS must have a section VIII relief valve downstream

Single water to water 3 way valve Compact with 2 storage tanks

T

T

T

0 30

155

10

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gaugeRelief valve

Control valve

44

Page 45: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Tank

Sensor

Hot Water to Building

Cold Water 0

5 8

10 0

5 8

10

Recirculation Pump

BronzeDomestic Pump

Hot Water Outlet

Hi-Limitto drain

PK

Compact

0

3

0

155

1

0

PKPK

03

0

1

5510

Steam Supply

Relief Valve to drain

Hot WaterN.C. Bypass

N.C. Bypass

Expansion

Tank

Mixed Hot

Mixing Valve

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. Refer to ASHRAE 90.1 for return water %

5. Bronze domestic pump must be sized for full COMPACT size

6. All COMPACTS must have a section VIII relief valve downstream

Single Compact with 2 storage tanks

T

T

T

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Steam valve

Relief valve

45

Page 46: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Hot Water

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Steam Supply

Relief Valve

to drain

Single Compact with NY TRIM

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into recirculation on compact

4. Refer to ASHRAE 90.1 for return water %

5. All COMPACTS must have a section VIII relief valve downstream

0

5 8

100

5 8

10

Cold water

Building recirculation

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Steam valve

Relief valve

T

T

46

Page 47: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Hot Water

Cold Water

0

5 8

100

5 8

10

N.C. BypassHouse Recirculation

Expansion

Tank

Hot Water

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Steam Supply

Relief Valve

to drain

Single Compact with NY TRIM and Hot water storage tank

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into compact recirculation

4. Refer to ASHRAE 90.1 for return water %

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Steam valve

Relief valve

47

Page 48: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Single Water to Water with 2 way valve Compact installation

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Relief Valve

to drain

Cold Water

0

5 8

100

5 8

10

House Recirculation

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. Refer to ASHRAE 90.1 for return water %

5. All COMPACTS must have a section VIII relief valve downstream

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gaugeRelief valve

Control valve

48

Page 49: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Single Water to Water with 3 way valve Compact installation

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Relief Valve

to drain

Cold Water

0

5 8

100

5 8

10

House Recirculation

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. Refer to ASHRAE 90.1 for return water %

5. All COMPACTS must have a section VIII relief valve downstream

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gaugeRelief valve

Control valve

49

Page 50: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Steam Supply

Single Compact installation

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Steam Supply

Relief Valve

to drain

Cold Water

0

5 8

100

5 8

10

House Recirculation

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. Refer to ASHRAE 90.1 for return water %

5. All COMPACTS must have a section VIII relief valve downstream

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Steam valve

Relief valve

50

Page 51: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Hot Water

Cold Water

0

5 8

100

5 8

10

N.C. Bypass

House Recirculation

Circulation Pump

(Size for

Full Capacity

of Compact)

N.C. Bypass

Hot Water

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Steam Supply

Relief Valve

to drain

1 Compact with Hot water storage tank

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. Refer to ASHRAE 90.1 for return water %

5. Bronze domestic pump must be sized for full COMPACT size

6. All COMPACTS must have a section VIII relief valve downstream

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Steam valve

Relief valve

51

Page 52: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Tank

Sensor

Hot Water to Building

Cold Water 0

5 8

10 0

5 8

10

Recirculation Pump

Recirculation Pump

BronzeDomestic Pump

Hot Water Outlet

Hi-Limitto drain

PK

Compact

0

3

0

155

1

0

PKPK

03

0

1

5510

Steam Supply

Relief Valve to drain

Hot WaterN.C. Bypass

N.C. Bypass

Expansion

Tank

Mixed Hot

Mixing Valve

Single Compact with 3 storage tanks

TT

T

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. Refer to ASHRAE 90.1 for return water %

5. Bronze domestic pump must be sized for full COMPACT size

6. All COMPACTS must have a section VIII relief valve downstream

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Steam valve

Relief valve

52

Page 53: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Tank

Sensor

Hot Water to Building

Cold Water 0

5 8

10 0

5 8

10

Recirculation Pump

Recirculation Pump

BronzeDomestic Pump

Hot Water Outlet

Hi-Limitto drain

PK

Compact

0

3

0

155

1

0

PKPK

03

0

1

5510

Steam Supply

Relief Valve to drain

Hot WaterN.C. Bypass

N.C. Bypass

Mixed Hot

Mixing Valve

2 Compacts with 2 storage tanks

PK

Compact

0

3

0

155

1

0

PKPK

03

0

1

5510

Steam Supply

Relief Valve to drain

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. Refer to ASHRAE 90.1 for return water %

5. Bronze domestic pump must be sized for full COMPACT size

6. All COMPACTS must have a section VIII relief valve downstream

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Steam valve

Relief valve

TT

T

53

Page 54: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Tank

Sensor

Hot Water to Building

Cold Water 0

5 8

10 0

5 8

10

Recirculation Pump

Recirculation Pump

BronzeDomestic Pump

Hot Water Outlet

Hi-Limitto drain

PK

Compact

0

3

0

155

1

0

PKPK

03

0

1

5510

Steam Supply

Relief Valve to drain

Hot WaterN.C. Bypass

N.C. Bypass

Mixed Hot

Mixing Valve

2 Compacts with 3 storage tanks

PK

Compact

0

3

0

155

1

0

PKPK

03

0

1

5510

Steam Supply

Relief Valve to drain

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. Refer to ASHRAE 90.1 for return water %

5. Bronze domestic pump must be sized for full COMPACT size

6. All COMPACTS must have a section VIII relief valve downstream

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Steam valve

Relief valve

T T

T

54

Page 55: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Hot Water

Cold Water

Hi-Limitto drain

0

5 8

100

5 8

10

N.C. Bypass

House Recirculation

Condensate Return

(Drain by Gravity to

Vented Receiver)

Circulation Pump

(Size for Full Capacity

of Heater)

N.C. Bypass

Steam Supply

PK

Compact

0

30 15

510

PK

PK

0 30

15510 Relief Valve

to drain

PK

Compact

0

30 15

510

PK

PK

0 30

15510

Expansion

Tank

2 Horizontal Compacts and 2 storage tanks

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Steam valve

Relief valve

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. Refer to ASHRAE 90.1 for return water %

5. Bronze domestic pump must be sized for full COMPACT size

6. All COMPACTS must have a section VIII relief valve downstream

T

T

55

Page 56: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Hot Water

Cold Water

Hi-Limitto drain

0

5 8

100

5 8

10

N.C. Bypass

House Recirculation

Condensate Return

(Drain by Gravity to

Vented Receiver)

Circulation Pump

(Size for Full Capacity

of Heater)

N.C. Bypass

Steam Supply

PK

Compact

0

30 15

510

PK

PK

0 30

15510 Relief Valve

to drain

PK

Compact

0

30 15

510

PK

PK

0 30

15510

2 Horizontal Compacts and 2 storage tanks

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Steam valve

Relief valve

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. Refer to ASHRAE 90.1 for return water %

5. Bronze domestic pump must be sized for full COMPACT size

6. All COMPACTS must have a section VIII relief valve downstream

56

Page 57: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Hot Water

Hi-Limitto drain

Condensate Return

(Drain by Gravity to

Vented Receiver)

Circulation Pump

(Size for Full Capacity

of Heater)

N.C. Bypass

Steam Supply

PK

Compact

0

30 15

510

PK

PK

0 30

15510 Relief Valve

to drain

Hi-Limitto drain

Condensate Return

(Drain by Gravity to

Vented Receiver)

Circulation Pump

(Size for Full Capacity

of Heater)

N.C. Bypass

Steam Supply

PK

Compact

0

30

15

510

PK

PK

030

15 510Relief Valve

to drain

Cold Water

0

5 8

100

5 8

10

House Recirculation

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. 12k ohm tank sensor must be used.

5. Refer to ASHRAE 90.1 for return water %

6. Domestic water side must have a volume of water on supply side.

2 Horizontal Compacts

57

Page 58: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Hot Water

Cold Water

N.C. Bypass

Expansion

Tank

Hot Water

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Steam Supply

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Steam Supply

Relief Valve

to drain

Relief Valve

to drain

2 Compacts with NY TRIM and Hot water storage tank

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into COMPACT recirculation

4. Refer to ASHRAE 90.1 for return water %

5. Bronze domestic pump must be sized for full COMPACT size

6. All COMPACTS must have a section VIII relief valve downstream

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Steam valve

Relief valve

0

5 8

100

5 8

10

House Recirculation

T

T

58

Page 59: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Hot Water

Cold Water

0

5 8

100

5 8

10

N.C. Bypass

House Recirculation

Circulation Pump

(Size for

Full Capacity

of Compact)

N.C. Bypass

Hot Water

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Steam Supply

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Steam Supply

Relief Valve

to drain

Relief Valve

to drain

2 Compacts with Hot water storage tank

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. Refer to ASHRAE 90.1 for return water %

5. Bronze domestic pump must be sized for full COMPACT size

6. All COMPACTS must have a section VIII relief valve downstream

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Steam valve

Relief valve

T

T

59

Page 60: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Hot Water

Steam Supply

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Relief Valve

to drain

2 Compacts parallel installation

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Steam Supply

Relief Valve

to drain

Cold Water

0

5 8

100

5 8

10

House Recirculation

T

T

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. Refer to ASHRAE 90.1 for return water %

5. Bronze domestic pump must be sized for full COMPACT size

6. All COMPACTS must have a section VIII relief valve downstream

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Steam valve

Relief valve

60

Page 61: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Tank

Sensor

Hot Water to Building

Cold Water 0

5 8

10 0

5 8

10

Recirculation Pump

Recirculation Pump

BronzeDomestic Pump

Hot Water Outlet

Hi-Limitto drain

PK

Compact

0

3

0

155

1

0

PKPK

03

0

1

5510

Steam Supply

Relief Valve to drain

Hot WaterN.C. Bypass

N.C. Bypass

Mixed Hot

Mixing Valve

3 Compacts with 2 storage tanks

PK

Compact

0

3

0

155

1

0

PKPK

03

0

1

5510

Steam Supply

Relief Valve to drain

PK

Compact

0

3

0

155

1

0

PKPK

03

0

1

5510

Steam Supply

Relief Valve to drain

TT

T

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. Refer to ASHRAE 90.1 for return water %

5. Bronze domestic pump must be sized for full COMPACT size

6. All COMPACTS must have a section VIII relief valve downstream

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Steam valve

Relief valve

61

Page 62: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Tank

Sensor

Hot Water to Building

Cold Water 0

5 8

10 0

5 8

10

Recirculation Pump

BronzeDomestic Pump

Hot Water Outlet

Hi-Limitto drain

PK

Compact

0

3

0

155

1

0

PKPK

03

0

1

5510

Steam Supply

Relief Valve to drain

Hot WaterN.C. Bypass

N.C. Bypass

Mixed Hot

Mixing Valve

3 Compacts with 3 storage tanks

PK

Compact

0

3

0

155

1

0

PKPK

03

0

1

5510

Steam Supply

Relief Valve to drain

PK

Compact

0

3

0

155

1

0

PKPK

03

0

1

5510

Steam Supply

Relief Valve to drain

TT

T

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. Refer to ASHRAE 90.1 for return water %

5. Bronze domestic pump must be sized for full COMPACT size

6. All COMPACTS must have a section VIII relief valve downstream

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Steam valve

Relief valve

62

Page 63: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Hot Water

Cold Water

0

5 8

100

5 8

10

N.C. Bypass

House Recirculation

Expansion

Tank

Hot Water

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Steam Supply

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Steam Supply

Relief Valve

to drain

Relief Valve

to drain

3 Compacts with NY TRIM and Hot water storage tank

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. 12k ohm tank sensor must be used.

5. Refer to ASHRAE 90.1 for return water %

6. Domestic water side must have a volume of water on supply side.

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Steam Supply

Relief Valve

to drain

63

Page 64: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Hot Water

Cold Water

0

5 8

100

5 8

10

N.C. Bypass

House Recirculation

Circulation Pump

(Size for

Full Capacity

of Compact)

N.C. Bypass

Hot Water

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Steam Supply

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Steam Supply

Relief Valve

to drain

Relief Valve

to drain

3 Compacts with Hot water storage tank

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Steam Supply

Relief Valve

to drain

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. Refer to ASHRAE 90.1 for return water %

5. Bronze domestic pump must be sized for full COMPACT size

6. All COMPACTS must have a section VIII relief valve downstream

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Steam valve

Relief valve

T

T

64

Page 65: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Hot Water

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Steam Supply

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Steam Supply

Relief Valve

to drain

Relief Valve

to drain

3 Compacts parallel installation

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Steam Supply

Relief Valve

to drain

Cold Water

0

5 8

100

5 8

10

House Recirculation

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water line

4. Refer to ASHRAE 90.1 for return water %

5. All COMPACTS must have a section VIII relief valve downstream

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Steam valve

Relief valve

T

T

65

Page 66: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Hi-Limit

to drain

PK

Compact

0 30

155

10

PKPK

0 30

155

10

Steam Supply

Relief Valve

to drainNotes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. Refer to ASHRAE 90.1 for return water %

5. Bronze domestic pump must be sized for full COMPACT size

6. All COMPACTS must have a section VIII relief valve downstream

0

5 8

100

5 8

10

House Recirculation

B I D O

D IB O

Condensate Pump/Trap

Hot water outlet

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Steam valve

Relief valve

COMPACT with condensate reclamation for domestic water preheat

66

Page 67: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

B I D O

D IB O

PK

B I D O

D IB O

PK

PK

Co

nd

en

sin

g B

oile

r

Condensate

Recirculation loop return

Cold water make up

Single condensing boiler with 2 Duration III and hot water storage tank

System fill

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. 12k ohm tank sensor must be used.

5. Refer to ASHRAE 90.1 for return water %

T

T

T

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

T

67

Page 68: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

B I D O

D IB O

PK

B I D O

D IB O

PK

PK

Co

nd

en

sin

g B

oile

r

Condensate

Zone 1 Recirculation loop return

Cold water make up

Single condensing boiler with 2 Duration III independent zones

Zone 2 Recirculation loop return

Zone 2 supplyZone 1 supply

System fill

Wye Strainer

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

Temp gauge

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. 12k ohm tank sensor must be used.

5. Refer to ASHRAE 90.1 for return water %

6.Domestic water side must have a volume of water on supply side.

68

Page 69: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

B I D O

D IB O

PK

B I D O

D IB O

PK

PK

Co

nd

en

sin

g B

oile

r

Condensate

Recirculation loop return

Cold water make up

Single condensing boiler with 2 Duration III and hot water storage tank

System fill

Wye Strainer

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

Temp gauge

T

T

T

T Temp sensor

B I D O

D IB O

PK

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. 12k ohm tank sensor must be used.

5. Refer to ASHRAE 90.1 for return water %

6.Domestic water side must have a volume of water on supply side.

T

69

Page 70: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

B I D O

D IB O

PK

PK

Co

nd

en

sin

g B

oile

r

Condensate

Recirculation loop return

Cold water make up

Single condensing boiler with Duration III and hot water storage tank

TT

System fill

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. 12k ohm tank sensor must be used.

5. Refer to ASHRAE 90.1 for return water %

6.Domestic water side must have a volume of water on supply side.

Wye Strainer

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

Temp gauge

T

70

Page 71: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

B I D O

D IB O

PK

B I D O

D IB O

PK

PK

Co

nd

en

sin

g B

oile

r

Condensate

Recirculation loop return

Cold water make up

Double condensing boiler with 2 Duration III and hot water storage tank

System fill

T

T

T

PK

Co

nd

en

sin

g B

oile

r

Condensate

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. 12k ohm tank sensor must be used.

5. Refer to ASHRAE 90.1 for return water %

6.Domestic water side must have a volume of water on supply side.

T

Wye Strainer

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

Temp gauge

71

Page 72: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

B I D O

D IB O

PK

B I D O

D IB O

PK

PK

Co

nd

en

sin

g B

oile

r

Condensate

Recirculation loop return

Cold water make up

Triple condensing boiler with 2 Duration III and hot water storage tank

System fill

T

T

T

PK

Co

nd

en

sin

g B

oile

r

Condensate

B I D O

D IB O

PK

T

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. 12k ohm tank sensor must be used.

5. Refer to ASHRAE 90.1 for return water %

6.Domestic water side must have a volume of water on supply side. Wye Strainer

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

Temp gauge

72

Page 73: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

B I D O

D IB O

PK

PK

Co

nd

en

sin

g B

oile

r

Condensate

Notes:1. Header piping should be one pipe size larger than direct boiler piping

2. Distance between 1st and 2nd tee should be no more than 4 pipe diameters

3.For actual piping locations and dimensions, refer to appropriate appliance submittal

4. Appropriately sized expansion tank should be located on cold water inlet of air elimination

5. Building recirculation (if utilized) should be tied into cold water make up

6.12k OHM tank sensor to be installed in tankR

ecirculation loop return

Cold water make up

Double condensing boiler with Duration III and hot water storage tank

PK

Co

nd

en

sin

g B

oile

r

System fill

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

Temp gauge

TT

Control valve

73

Page 74: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

B I D O

D IB O

PK

PK

Co

nd

en

sin

g B

oile

r

Condensate

Notes:1. Header piping should be one pipe size larger than direct boiler piping

2. Distance between 1st and 2nd tee should be no more than 4 pipe diameters

3.For actual piping locations and dimensions, refer to appropriate appliance submittal

4. Appropriately sized expansion tank should be located on cold water inlet of air elimination

5. Building recirculation (if utilized) should be tied into cold water make up

6.12k OHM tank sensor to be installed in tankR

ecirculation loop return

Cold water make up

Double condensing boiler with Duration III and hot water storage tank

PK

Co

nd

en

sin

g B

oile

r

System fill

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

Temp gauge

TT

74

Page 75: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

B I D O

D IB O

PK

B I D O

D IB O

PK

PK

Co

nd

en

sin

g B

oile

r

Condensate

Recirculation loop return

Cold water make up

Triple condensing boiler with 2 Duration III and hot water storage tank

System fill

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. 12k ohm tank sensor must be used.

T

T

T

PK

Co

nd

en

sin

g B

oile

r

Condensate

PK

Co

nd

en

sin

g B

oile

r

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Control valve

75

Page 76: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

B I D O

D IB O

PK

B I D O

D IB O

PK

PK

Co

nd

en

sin

g B

oile

r

Condensate

Recirculation loop return

Cold water make up

Triple condensing boiler with 2 Duration III and hot water storage tank

System fill

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. 12k ohm tank sensor must be used.

T

T

T

PK

Co

nd

en

sin

g B

oile

r

Condensate

B I D O

D IB O

PK

PK

Co

nd

en

sin

g B

oile

r

Condensate

T

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

76

Page 77: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

B I D O

D IB O

PK

B I D O

D IB O

PK

PK

Co

nd

en

sin

g B

oile

r

Condensate

Recirculation loop return

Cold water make up

Triple condensing boiler with 2 Duration III and hot water storage tank

System fill

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. 12k ohm tank sensor must be used.

T

T

T

PK

Co

nd

en

sin

g B

oile

r

Condensate

PK

Co

nd

en

sin

g B

oile

r

T

Condensate

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

77

Page 78: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

B I D O

D IB O

PK

PK

Co

nd

en

sin

g B

oile

r

CondensateR

ecirculation loop return

Cold water make up

Triple condensing boiler with Duration III and hot water storage tank

PK

Co

nd

en

sin

g B

oile

r

PK

Co

nd

en

sin

g B

oile

r

System fill

Notes:1. Header piping should be one pipe size larger than direct boiler piping

2.For actual piping locations and dimensions, refer to appropriate appliance submittal

3. Appropriately sized expansion tank should be located on cold water inlet of air elimination

4. Building recirculation (if utilized) should be tied into cold water make up

5.12k OHM tank sensor to be installed in tank

T

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

78

Page 79: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

B I D O

D IB O

PK

Co

nd

en

sin

g b

oile

r

System fill

To SystemHouse Pumps

Cold water make up

Building domestic recirculation

Building Domestic Supply

1 condensing boiler with 2 Duration III on Primary/Secondary system

B I D O

D IB O

PK

T

T

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. 12k ohm tank sensor must be used.

5. Refer to ASHRAE 90.1 for return water %

6. Domestic water side must have a volume of water on supply side.

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

79

Page 80: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

B I D O

D IB O

PK

Co

nd

en

sin

g b

oile

r

To System

House Pumps

Cold water make up

Building domestic recirculation

Building Domestic Supply

Single condensing boiler with 1 Duration III and buffer tank

System fill

Notes:1. Header piping should be one pipe size larger than direct boiler piping

2.For actual piping locations and dimensions, refer to appropriate appliance submittal

3. Appropriately sized expansion tank should be located on cold water inlet of air elimination

4. Building recirculation (if utilized) should be tied into cold water make up

Buffer tank

System

Return

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

80

Page 81: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

B I D O

D IB O

PK

Co

nd

en

sin

g b

oile

r

System fill

To SystemHouse Pumps

Cold water make up

Building domestic recirculation

Building Domestic Supply

Single condensing boiler with 1 Duration III on Primary/Secondary system

T

T

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. 12k ohm tank sensor must be used.

5. Refer to ASHRAE 90.1 for return water %

6. Domestic water side must have a volume of water on supply side.

81

Page 82: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

B I D O

D IB O

PK

Co

nd

en

sin

g b

oile

r

System fill

To SystemHouse Pumps

Cold water make up

Building domestic recirculation

Building Domestic Supply

2 condensing boilers with 2 Duration III on Primary/Secondary system

Co

nd

en

sin

g b

oile

r

B I D O

D IB O

PK

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. 12k ohm tank sensor must be used.

5. Refer to ASHRAE 90.1 for return water %

6. Domestic water side must have a volume of water on supply side.

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

82

Page 83: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Co

nd

en

sin

g b

oile

r

System fill

To SystemHouse Pumps

Cold water make up

Building domestic recirculation

Building Domestic Supply

3 condensing boilers with 1 Duration III on Primary/Secondary system

Co

nd

en

sin

g b

oile

r

B I D O

D IB O

PK

Co

nd

en

sin

g b

oile

r

T

T

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. 12k ohm tank sensor must be used.

5. Refer to ASHRAE 90.1 for return water %

6. Domestic water side must have a volume of water on supply side.

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

83

Page 84: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Co

nd

en

sin

g b

oile

r

System fill

To SystemHouse Pumps

3 condensing boilers with 2 Duration III on Primary/Secondary system

Co

nd

en

sin

g b

oile

r

Co

nd

en

sin

g b

oile

r

T

T

B I D O

D IB O

PK

Cold water make up

Building domestic recirculation

Building Domestic Supply

B I D O

D IB O

PK

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. 12k ohm tank sensor must be used.

5. Refer to ASHRAE 90.1 for return water %

6. Domestic water side must have a volume of water on supply side.

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

84

Page 85: Commercial Piping Diagram - Patterson-Kelley · These piping diagrams are an example of possible configurations which may not work in all applications. Local codes and authorities

Co

nd

en

sin

g b

oile

r

System fill

To SystemHouse Pumps

3 condensing boilers with 3 Duration III on Primary/Secondary system

Co

nd

en

sin

g b

oile

r

Co

nd

en

sin

g b

oile

r

T

T

Notes:

1.For actual piping locations and dimensions, refer to appropriate appliance submittal

2. Appropriately sized expansion tank should be located on cold water inlet of air elimination

3. Building recirculation (if utilized) should be tied into cold water make up

4. 12k ohm tank sensor must be used.

5. Refer to ASHRAE 90.1 for return water %

6. Domestic water side must have a volume of water on supply side.

Balancing valve

Condensate neutraliztion

Circulator pump

Isolation valve

LEGEND

Flow direction

Expansion tank

T Temp sensor/gauge

B I D O

D IB O

PK

Cold water make up

Building domestic recirculation

Building Domestic Supply

B I D O

D IB O

PK

B I D O

D IB O

PK

85