commissioning guide archive/air diffusers/k... · measurement and commissioning----- 4 swegon...

36
Commissioning Guide Air Diffusers Flow Control Climate Systems Version 2006-12

Upload: others

Post on 16-Mar-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

Commissioning Guide

Air DiffusersFlow ControlClimate Systems

Version 2006-12

Page 2: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

1Swegon Commissioning Guide 2006-12

www.swegon.com

CONTENTS -----------------------------------------------------------CONTENTS----------------------------------------------------------------------

Measurement and adjustment 3-4

AIR DIFFUSERSwith commissioning box ALSc

5-15

ALCa 5CBEa 5CDDb supply air 360° 5CDKa supply air 360° 6CDRb supply air 360° 6CGLa 6CKDa supply air 6CKPa supply air 360° 7CVHb supply air 360° 7EIVa 7DPGa 7KRKa supply air 8LPAa supply air 8LPKa 1 supply air 8LPKa 1 exhaust air 9COLIBRI Ceiling CC 9COLIBRI Ceiling CR 10EAGLE Ceiling 10LOCKZONE Ceiling 11PMLc 11PMTd 11PMUb 12ROCa 12RDYa supply air 12TCBa 360° distribution, supply air 13TCBa 270° distribution, supply air 13TCBa 180° distribution, supply air 13TDYc supply air 14TDYc K supply air 14TRYa 1 supply air 14TRYa 1 K supply air 14TRYa 2 supply air 15TRYa 2 K supply air 15TRYa 3 supply air 15TRYa 3 K supply air 15

AIR DIFFUSERS with commissioning box ALVb

16

VDYc supply air, conn. B and K 16VOSa supply air 16VRYc supply air, conn. B and K 16

AIR DIFFUSERSwith commissioning box ALVc

17

LPVa 17ROWa 17

AIR DIFFUSERS with commissioning box TRGc

18-19

ALGc supply air 18ALGc exhaust air 18GRLc exhaust air 19GVLc exhaust air 19GTHc supply air, straight blades 19GTHc supply air, blades 45° 19

AIR DIFFUSERS with circ. commissioning box

20-21

ACDa supply air 20ATCb supply air 21CDYb 21EAGLE F 21LOCKZONE F (LPCa) supply air 21

AIR DIFFUSERSDisplacement terminal units

22-24

DBCa 22DBRe 22DCPe 23DHCe 23DVCe 23ICPa 23IHCa 23IVCa 23DIRc 24DKCe 24DRCe 24DRIf 24

Kfactors_en-2006-12-08.fm Page 1 Friday, December 8, 2006 2:39 PM

Page 3: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

CONTENTS -----------------------------------------------------------

2Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERSDiffuser beam with discs and adjustable measuring unit

25

DDKa 25

AIR DIFFUSERS Slot diffusers 25SLAT 1 SLAa, supply air 25SLAT 2 SLAa, supply air 25

AIR DIFFUSERSLinear disc diffuser with commissioning box

26

SRYb 26

AIR DIFFUSERSwith fixed regulation function

27

UDYa supply air 27

AIR DIFFUSERSExhaust air terminal device

28-29

FDPa 28KVBb 28ROEa 29EXCa 29

AIR DIFFUSERS e.r.i.c. system 30-32ACKc 30ACLb 30AKYb 31ARPa 31AFKb 32

FLOW CONTROL 33-35DCV, dampers and measuring productsVARb 33KZMa+KZMb 33KRFa+KRFb+KRFc 33KSAa+KSAb 33CRMc 1 34CRMc 5 34AREb 2 34RSMd 35RSMe 35

CLIMATE SYSTEMS 36-44Climate beams and Comfort modulesBALTIC a 37BRCa 37ADRIATIC b 37-38BSAd 38BISCAY a 39Parasol 40-42Parasol EX 43-44

Kfactors_en-2006-12-08.fm Page 2 Friday, December 8, 2006 2:39 PM

Page 4: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

3Swegon Commissioning Guide 2006-12

www.swegon.com

Measurement and commissioning ---------------------------------------Measurement and commissioning

This commissioning guide shows the measurement instructions for measurable ventila-tion products made by Swegon AB. The products are equipped with adjustable dam-pers and measuring units, which are designed to measure a reference pressure.Measurement instructions:There are several different ways to measure a product. It depends on the product andthe design of the measuring function:• Ductwork with fixed measuring unit.• Exhaust air terminals with fixed measuring units.• Supply air terminals with fixed measuring units.

In this commissioning guide you will find these three categories plus one product with-out fixed measuring unit; the exhaust valve KVB. For KVB the airflow is measured withan anemometer device or with a commissioning "hook".Most of the products have measuring tubes connected to the measuring units. The tubescan easily be reached through the front of the terminal device. Some products have one tube and some have two tubes.A few products have what we call a "nipple well" with a cover. The cover should be shutwhen balancing has been done.Some of the flow control products do not have any measuring tubes. Instead you reachthe measuring unit easily.All the products documented together with commissioning boxes ALS, ALV and TRGmust be measured together with the commissioning boxes as the measuring units areplaced within those.

Procedure1. Define the k-factor for the specifik terminal by using the tables in this commissioningguide.2. Connect the manometer to the measuring tube(s), (measuring units, nipple well).3. The manometer gives you a measurement pressure, pi (balancing pressure).4. The airflow can now be calculated according to the equation on next page.5. Adjust the damper to change the airflow. A few of the products don’t have ordinarydampers. Instead you use adjustable slot openings or plastic plugs.6. Lock the damper regulator.

Supply air terminals1. The damper regulator consists of one black and one white nylon cord. Pull the whitecord to open and the black cord to shut the damper.2. After finding the proper damper position, stretch both cords and make a "commissio-ning knot" at the end of the cords. The knot is an index for the damper position. If forsome reason the damper position would be changed, you just stretch both cords andyou will have the right damper position again.

Kfactors_en-2006-12-08.fm Page 3 Friday, December 8, 2006 2:39 PM

Page 5: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

Measurement and commissioning ---------------------------------------

4Swegon Commissioning Guide 2006-12

www.swegon.com

3. Each product is equipped with a locking screw to hold the damper regulators. Youwill find it in the diffuser part. Open the screw, twist the cords around it and tighten thescrew. Now you have locked the damper position.

Exhaust air terminalsAs supply air terminals when combinations commissioning box + terminal are used.• When using terminal KVB, you lock the valve position with a wing nut placed on therear of the terminal.• When using terminal FPD, you lock the slot opening with two screws behind the per-forated front plate.

Flow control products (dampers)The damper’s actuator is lockable with a special locking device. You will just need ascrewdriver.

Calculation of airflow - k-factor equationsThere is a specific balancing factor, k-factor for each measurable Swegon product.The products are normally marked with a k-factor. If not, you find them in this k-factor gui-de. The following equations are used to obtain the actual airflow or the balancing pres-sure that is valid for the designed airflow.

q = measured airflow (l/s)pi = actual balancing pressure (Pa)k = k-factor

pi = balancing pressure at designed airflow (Pa)q = designed airflow (l/s)k = k-factor

If temperature and atmospheric pressure differ from standard settings (20°C and 1013 mbar) at the time of commissioning, the balancing pressure is recalculated accor-ding to the following equation:

Or the airflow can be recalculated to the standard settings according to:

q = k · √p [l/s]i p = [Pa] i ( )k

q 2

p = p · [Pa] i

1,2i, measured

time of measurement

q = q · [l/s] 1,2

measuredtime of measurement√

Kfactors_en-2006-12-08.fm Page 4 Friday, December 8, 2006 2:39 PM

Page 6: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

5Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS with commissioning box ALSc ----------------------------AIR DIFFUSERS with commissioning box ALSc----------------------------------------------------------------------

Figure 1. Measuring with two tubes. Figure 2. Measuring with one tube.

ALSc ALBATROSS ALCasize size supply air

200-250 250 30.1250-315 315 42.6315-400 400 59.4400-500 500 78.2500-630 630 153.0

ALSc 400-500 and ALSc 500-630 don’t have a commissioning damper.

ALSc CBEa CDDb supply air 360° CDDb exhaust air 360°size size supply air size slot

20 mmslot

30 mmslot

40 mmslot

20 mmslot

30 mm80-80 80 3.3

80-100 100 4.6 100 5.8 6.1 6.4100-125 125 7.6 125 8.2 8.9 8.2125-160 160 11.9 160 14.4 15.0 15.4160-200 200 21.3 23.4 19.9200-250 250 24.4 31.1 27.4250-315 315 34.6 43.3 30.6

1 measuring tube 1 measuring tube Note! tolerance ± 7%

Kfactors_en-2006-12-08.fm Page 5 Friday, December 8, 2006 2:39 PM

Page 7: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

AIR DIFFUSERS with commissioning box ALSc ----------------------------

6Swegon Commissioning Guide 2006-12

www.swegon.com

ALSc CDKa supply air 360° CDKa exhaust air 360°size size slot

20 mmslot

30 mmslot

40 mmslot

20 mmslot

30 mm80-100 100 6.8 6.9 8.7

100-125 125 9.8 10.1 9.8125-160 160 16.3 16.5 23.8160-200 200 26.9 27.6 37.8200-250 250 38.5 42.1 51.3250-315 315 57.6 69.9 67.1

1 measuring tube Note! tolerance ± 7%

ALSc CDRb supply air 360° CDRb exhaust air 360°size size slot

20 mmslot

30 mmslot

40 mmslot

20 mmslot

30 mm80-100 100 5.0 5.6 4.9

100-125 125 7.1 8.1 7.5125-160 160 13.1 13.9 14.6160-200 200 18.4 20.3 17.9200-250 250 24.3 28.5 31.7250-315 315 36.1 42.6 39.5

1 measuring tube Note! tolerance ± 4%

ALSc CGLa CKDa supply airsize size supply air size diffus. concent.

125-160 160 2.3160-200 220 4.7 200 13.9 12.6200-250 250 22.8 21.1250-315 315 34.7 32.3315-400 400 55.8 52.9

1 measuring tube 1 measuring tube

Kfactors_en-2006-12-08.fm Page 6 Friday, December 8, 2006 2:39 PM

Page 8: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

7Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS with commissioning box ALSc ----------------------------

ALSc CKPa supply air 360° CKPa exhaust air 360°size size slot

20 mmslot

30 mmslot

40 mmslot

20 mmslot

30 mm80-100 100 3.8 6.8 8.5

100-125 125 9.9 10.1 12.5125-160 160 16.2 16.5 21.9160-200 200 27.3 27.9 34.1200-250 250 39.8 42.2 45.1250-315 315 60.6 68.7 59.6

1 measuring tube Note! tolerance ± 7%

ALSc CVHb supply air 360° CVHb exhaust air 360°size size horizontal vertical horizontal

100-125 125 8.9 8.3 11.1125-160 160 13.5 11.8 15.5160-200 200 22.3 16.8 28.7200-250 250 33.9 24.3 39.5250-315 315 52.4 37.7 74.1315-400 400 79.8 58.7 112.0

1 measuring tube Note! tolerance ± 7%

ALSc EIVa DPGasize size supply air size supply air

80-80 80 4.680-100 100 5.9

100-125 125 8.2 125-0 3.8125-160 160 10.3

1 measuring tube 1 measuring tube

Kfactors_en-2006-12-08.fm Page 7 Friday, December 8, 2006 2:39 PM

Page 9: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

AIR DIFFUSERS with commissioning box ALSc ----------------------------

8Swegon Commissioning Guide 2006-12

www.swegon.com

ALSc KRKa supply airsize size 1-way 2M-way 3-way 4-way

125-160 160 12.1 12.6 12.0 13.2160-200 200 13.2 14.7 14.7 14.8200-250 250 20.5 26.0 24.5 23.9250-315 315 31.6 37.5 35.2 34.3315-400 400 50.8 66.6 63.9 65.5

2 measuring tubes

ALSc LPAasize size supply air exhaust air

125-160 160 11.0 13.6160-200 200 18.1 23.4200-250 250 27.5 32.2250-315 315 38.0 46.3315-400 400 58.7 71.2

1 measuring tube

ALSc LPKa 1 supply airsize size closed slot open slot

100-125 125-400 7.4 8.4100-125 125-600 7.6 8.1125-160 160-400 11.1 12.6125-160 160-600 10.7 12.9160-200 200-500 17.8 20.5160-200 200-600 17.8 20.5200-250 250-600 27.1 30.9250-315 315-600 37.3 43.3315-400 400-600 48.7 59.0

1 measuring tube

Kfactors_en-2006-12-08.fm Page 8 Friday, December 8, 2006 2:39 PM

Page 10: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

9Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS with commissioning box ALSc ----------------------------

ALSc LPKa 1 exhaust airsize size closed slot open slot

100-125 125-400 10.3 11.4100-125 125-600 11.1 12.3125-160 160-400 14.4 18.0125-160 160-600 15.2 17.2160-200 200-500 23.5 24.8160-200 200-600 21.9 24.8200-250 250-600 27.2 32.4250-315 315-600 42.1 44.2315-400 400-600 54.8 66.6

1 measuring tube

ALSc COLIBRI Ceiling CC supply airSize Size standard low Tube color

100-125 125-400 7.3 7.0 Red100-125 125-600 7.3 7.0 Red100-160 160-400 9.3 8.9 Blue100-160 160-600 9.3 8.9 Blue125-160 160-400 9.8 9.3 Red125-160 160-600 9.8 9.3 Red125-200 200-500 15.6 14.5 Blue125-200 200-600 15.6 14.5 Blue160-200 200-500 16.8 15.2 Red160-200 200-600 16.8 15.0 Red160-250 250-600 23.4 21.7 Blue200-250 250-600 24.9 22.8 Red200-315 315-600 26.4 25.4 Blue250-315 315-600 27.4 25.6 Red

1 measuring tube

Kfactors_en-2006-12-08.fm Page 9 Friday, December 8, 2006 2:39 PM

Page 11: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

AIR DIFFUSERS with commissioning box ALSc ----------------------------

10Swegon Commissioning Guide 2006-12

www.swegon.com

ALSc COLIBRI Ceiling CR supply airstorlek storlek standard low tube color

100-125 125-400 7.4 7.2 Red100-125 125-600 7.4 7.2 Red100-160 160-400 9.5 9.2 Blue100-160 160-600 9.5 9.2 Blue125-160 160-400 10.0 9.6 Red125-160 160-600 10.0 9.6 Red125-200 200-500 16.7 15.5 Blue125-200 200-600 16.7 15.5 Blue160-200 200-500 17.7 16.5 Red160-200 200-600 17.7 16.5 Red160-250 250-600 26.4 24.7 Blue200-250 250-600 28.9 26.4 Red200-315 315-600 30.3 28.6 Blue250-315 315-600 32.1 29.5 Red

1 measuring tube

ALSc EAGLE Ceiling a supply airsize size standard low tube color

100-125 125-400 7.8 7.6 Red100-125 125-600 7.7 7.6 Red100-160 160-400 11.8 11.5 Blue100-160 160-600 11.8 11.2 Blue125-160 160-400 12.6 11.9 Red125-160 160-600 12.6 11.7 Red125-200 200-500 17.6 16.9 Blue125-200 200-600 17.6 16.7 Blue160-200 200-500 19.9 17.9 Red160-200 200-600 19.9 17.9 Red160-250 250-600 26.5 24.1 Blue200-250 250-600 28.2 25.9 Red200-315 315-600 35.2 32.2 Blue250-315 315-600 37.3 33.5 Red

1 measuring tube

Kfactors_en-2006-12-08.fm Page 10 Friday, December 8, 2006 2:39 PM

Page 12: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

11Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS with commissioning box ALSc ----------------------------

ALSc LOCKZONE Ceiling a supply airsize size standard low tube color

100-125 125-400 8.3 7.9 Red100-125 125-600 8.2 7.8 Red100-160 160-400 11.1 10.8 Blue100-160 160-600 11.2 10.8 Blue125-160 160-400 12.1 11.4 Red125-160 160-600 12.4 11.4 Red125-200 200-500 18.0 16.9 Blue125-200 200-600 17.8 16.9 Blue160-200 200-500 19.7 18.4 Red160-200 200-600 19.7 18.0 Red160-250 250-600 28.1 25.6 Blue200-250 250-600 30.9 27.4 Red200-315 315-600 36.5 35.1 Blue250-315 315-600 39.6 39.6 Red

1 measuring tube

ALSc PMLc PMTdsize size supply air exhaust air size supply air exhaust air

80-100 100 3.1 3.7100-125 125 4.8 5.5100-160 100 7.5 10.0125-160 160 8.3 9.6125-200 125 12.1 16.1160-200 200 13.8 14.7160-250 160 21.6 29.7200-250 250 22.3 23.1200-315 200 33.9 37.4250-315 315 38.9 33.0 250 40.7 38.3315-400 400 64.3 53.0

2 measuring tubes 2 measuring tubes

Kfactors_en-2006-12-08.fm Page 11 Friday, December 8, 2006 2:39 PM

Page 13: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

AIR DIFFUSERS with commissioning box ALSc ----------------------------

12Swegon Commissioning Guide 2006-12

www.swegon.com

ALSc PMUb supply air PMUb exhaust airsize size supply air size closed slot open slot

80-100 100 3.6 100 4.1 3.9100-125 125 6.8 125 6.9 6.9125-160 160 9.6 160 11.2 11.7160-200 200 16.4 200 15.0 16.1200-250 250 29.0 250 22.0 22.7250-315 315 44.5 315 30.5 35.3315-400 400 71.1 66.3

1 measuring tubeK-factor is valid for 4-way distribution

1 measuring tube

ALSc ROCasize size supply air exhaust air

100-125 125 7.1 9.6125-160 160 11.2 14.8

1 measuring tube

ALSc RDYa supply airsize size variant 1 variant 2

80-100 100 4.9 5.6100-125 125 7.4 8.4125-160 160 11.4 14.2160-200 200 18.7 22.1200-250 250 29.9 34.5250-315 315 37.9 48.6315-400 400 69.9

1 measuring tube

Kfactors_en-2006-12-08.fm Page 12 Friday, December 8, 2006 2:39 PM

Page 14: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

13Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS with commissioning box ALSc ----------------------------

ALSc TCBa supply air 360° TCBa exhaust air 360°size size slot

5 mmslot

10 mmslot

20 mmslot

30 mmslot

40 mmslot

20 mmslot

30 mm80-100 100 3.5 5.3 6.2 7.6

100-125 125 5.6 8.6 9.9 12.9125-160 160 6.8 10.8 15.1 15.8 21.8160-200 200 13.4 23.2 26.7 30.9200-250 250 19.7 36.4 43.6 45.9 54.3250-315 315 19.3 39.0 54.9 58.9 65.8

1 Measuring tube Note! tolerance ± 15%

ALSc TCBa supply air 270°size size slot

5 mmslot

10 mmslot

20 mmslot

30 mm80-100 100 2.5 4.3 5.8

100-125 125 4.3 6.8 8.9125-160 160 8.0 12.0 14.2160-200 200 9.1 18.1 23.4200-250 250 14.5 27.2 37.6250-315 315 13.1 26.9 41.9

1 measuring tube

ALSc TCBa supply air 180°size size slot

5 mmslot

10 mmslot

20 mmslot

30 mm80-100 100 1.6 3.0 4.8

100-125 125 2.5 4.8 7.3125-160 160 5.3 8.4 11.2160-200 200 5.8 12.3 16.0200-250 250 9.1 18.0 27.6250-315 315 8.1 17.3 26.3

1 measuring tube

Kfactors_en-2006-12-08.fm Page 13 Friday, December 8, 2006 2:39 PM

Page 15: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

AIR DIFFUSERS with commissioning box ALSc ----------------------------

14Swegon Commissioning Guide 2006-12

www.swegon.com

ALSc TDYc supply air TDYc K supply airsize size open slot closed slot size open slot closed slot

100-125 125-320 8.0 6.3100-125 125-600 8.0 6.3 125-600 8.3 6.9100-125 125-1200 6.3125-160 160-320 12.0 8.0125-160 160-600 12.5 8.0 160-600 12.7 8.6125-160 160-1200 8.0160-200 200-400 18.3 13.0160-200 200-600 20.1 13.0 200-600 18.3 12.7160-200 200-1200 13.0200-250 250-600 29.5 21.5 250-600 26.5 21.7200-250 250-1200 21.5250-315 315-600 36.0 25.3 315-600 33.8 26.1250-315 315-1200 25.3

1 measuring tube 1 measuring tube

ALSc TRYa 1 supply air TRYa 1 K supply airsize size open slot closed slot size open slot closed slot

100-125 125-320 9.0 5.2100-125 125-600 8.2 4.6 125-600 8.4 5.4100-125 125-1200 4.6125-160 160-320 13.0 6.0125-160 160-600 12.9 5.5 160-600 12.8 6.6125-160 160-1200 5.5160-200 200-400 19.3 9.0160-200 200-600 18.4 8.2 200-600 16.5 8.5160-200 200-1200 8.2200-250 250-600 29.5 18.5 250-600 24.0 16.6200-250 250-1200 18.5250-315 315-600 37.7 20.9 315-600 29.7 20.1250-315 315-1200 20.9

1 measuring tube 1 measuring tube

Kfactors_en-2006-12-08.fm Page 14 Friday, December 8, 2006 2:39 PM

Page 16: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

15Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS with commissioning box ALSc ----------------------------

ALSc TRYa 2 supply air TRYa 2 K supply airsize size open slot closed slot size open slot closed slot

100-125 125-320 8.8 6.7100-125 125-600 8.4 6.0 125-600 8.7 6.7100-125 125-1200 6.0125-160 160-320 13.5 8.3125-160 160-600 12.8 7.6 160-600 13.0 8.6125-160 160-1200 7.6160-200 200-400 20.0 12.3160-200 200-600 18.9 11.5 200-600 17.8 11.6160-200 200-1200 11.5200-250 250-600 31.6 24.8 250-600 27.3 21.8200-250 250-1200 24.8250-315 315-600 42.2 30.1 315-600 35.1 26.9250-315 315-1200 30.1

1 measuring tube 1 measuring tube

ALSc TRYa 3 supply air TRYa 3 K supply airsize size open slot closed slot size open slot closed slot

100-125 125-320 9.0 7.1100-125 125-600 8.2 6.1 125-600 8.6 6.6100-125 125-1200 6.1125-160 160-320 13.2 8.7125-160 160-600 12.8 7.7 160-600 12.7 8.1125-160 160-1200 7.7160-200 200-400 21.4 15.0160-200 200-600 18.9 11.5 200-600 18.4 12.9160-200 200-1200 11.5200-250 250-600 32.7 27.7 250-600 28.2 24.5200-250 250-1200 27.7250-315 315-600 44.6 35.1 315-600 38.1 31.2250-315 315-1200 35.1

1 measuring tube 1 measuring tube

Kfactors_en-2006-12-08.fm Page 15 Friday, December 8, 2006 2:39 PM

Page 17: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

AIR DIFFUSERS with commissioning box ALVb ----------------------------

16Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS with commissioning box ALV b----------------------------------------------------------------------

Figure 1. Measuring with one tube. Figure 2. Measuring with one tube.

ALVb VDYc, supply air, conn. B

VDYc, supply air, conn. K

VOSa, supply air

size open slot closed slot open slot closed slot conn. back (B) conn. side (K)300-125-80 5.3 3.7 4.5 3.4 4.7 3.7

400-150-100 10.0 7.2 8.3 6.6 7.3 6.8500-150-125 11.9 9.2 10.7 8.8 10.1 9.3600-200-160 18.4 14.9 16.5 13.8 13.2 12.5700-250-200 23.9 19.7 22.7 19.0 21.7 19.5

1 measuring tube 1 measuring tube 1 measuring tube

ALVb VRYc, supply air, conn. B VRYc, supply air, conn. Ksize open slot closed slot open slot closed slot

300-125-80 6.6 4.6 5.3 4.1400-150-100 10.0 7.5 8.7 7.0500-150-125 11.8 9.2 10.7 8.7600-200-160 18.3 14.7 16.6 13.8700-250-200 25.6 21.3 23.8 20.2

1 measuring tube 1 measuring tube

Kfactors_en-2006-12-08.fm Page 16 Friday, December 8, 2006 2:39 PM

Page 18: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

17Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS with commissioning box ALVc ----------------------------AIR DIFFUSERS with commission ing box ALVc

ALVc conn. B LPVb ALVc conn. K LPVbsize supply air size supply air

300-150-100 6.9 300-150-100 5.8400-150-125 10.8 400-150-125 9.7500-200-160 17.4 500-200-160 15.5600-250-200 26.1 600-250-200 24.6600-300-250 33.1 600-300-250 31.3

1 measuring tube 1 measuring tube

ALVc conn. B ROWa ALVc conn. K ROWasize supply air size supply air

400-150-125 10.8 400-150-125 9.7500-200-160 17.4 500-200-160 15.5

1 measuring tube 1 measuring tube

Kfactors_en-2006-12-08.fm Page 17 Friday, December 8, 2006 2:39 PM

Page 19: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

AIR DIFFUSERS with commissioning box TRGc ---------------------------

18Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS with commissioning box TRGc

Figure 1. Measuring with two tubes.

TRGc ALGc supply air ALGc exhaust airsize conn. B conn. K conn. L conn. B conn. K conn. L

200-100-125 7.2 7.1 7.4 7.6 7.7 7.2300-100-160 11.9 12.2 12.3 13.4 13.0 12.3400-100-160 15.9 16.2 15.5 19.3 18.2 17.4500-100-200 21.4 21.4 22.2 23.2 23.0 21.2300-150-200 19.5 19.4 20.2 20.0 21.4 19.2400-150-250 26.9 26.3 27.3 28.9 28.2 26.4500-150-250 35.0 34.5 32.4 36.3 35.7 33.3400-200-250 36.8 38.5 42.0 45.6 44.3 41.0500-200-315 52.4 50.8 48.5 56.3 56.1 51.5600-200-315 61.9 60.7 57.6 70.7 69.6 61.0

No of measuring tubes: 2. Connection alternatives B=Back side, K=Short side, L=Long side

Kfactors_en-2006-12-08.fm Page 18 Friday, December 8, 2006 2:39 PM

Page 20: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

19Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS with commissioning box TRGc ---------------------------

TRGc GRLc exhaust air GVLc exhaust airsize conn. B conn. K conn. L conn. B conn. K conn. L

200-100-125 7.9 8.5 7.0 7.9 7.5 6.9300-100-160 13.3 13.2 11.8 11.9 12.0 10.8400-100-160 18.9 18.5 16.9 16.7 17.5 16.5500-100-200 23.2 23.3 21.0 20.8 22.5 19.6300-150-200 21.0 20.9 18.5 19.2 18.3 18.4400-150-250 29.1 28.4 25.3 26.0 25.6 24.1500-150-250 36.6 35.7 32.4 33.1 31.5 31.2400-200-250 46.6 42.9 39.8 40.2 37.2 36.7500-200-315 56.8 55.4 47.9 49.6 45.7 44.6600-200-315 70.0 68.5 59.4 55.6 50.7 49.3600-300-400 109.0 107.0 104.0

No of measuring tubes: 2. Connection alternatives B=Back side, K=Short side, L=Long side

TRGc GTHc supply air straight blades

GTHc supply airblades 45°

size conn. B conn. K conn. L conn. B conn. K conn. L200-100-125 7.5 7.2 7.3 7.2 7.0 7.1300-100-160 12.1 12.1 12.3 11.3 11.9 12.1400-100-160 16.2 16.6 15.4 15.0 16.1 15.0500-100-200 21.1 20.7 22.1 20.1 20.4 21.1300-150-200 19.3 19.2 19.7 19.4 18.8 19.2400-150-250 26.5 26.1 27.9 25.4 25.8 26.6500-150-250 34.8 33.5 32.9 33.8 33.4 30.9400-200-250 38.1 39.2 41.2 37.4 38.1 41.1500-200-315 50.5 48.4 48.3 48.0 48.2 46.4600-200-315 60.3 58.7 56.6 57.6 57.8 54.4

No of measuring tubes: 2. Connection alternatives B=Back side, K=Short side, L=Long side

Kfactors_en-2006-12-08.fm Page 19 Friday, December 8, 2006 2:39 PM

Page 21: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

AIR DIFFUSERS with circular commissioning box --------------------------

20Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS with circular commission ing box----------------------------------------------------------------------

Figure 1. Measuring with two tubes. Figure 2. Measuring with two tubes.

Straight sections are required beforethe diffuser to secure that the statedmethod errors, 5 %, will be obtained,see table:

1 x 90° bend 3 x ∅d2 x 90° bends 4 x ∅dT-joint 4 x ∅dDamper 45° 6 x ∅d

ACDa supply air ACDa exhaust airsize slot

20 mmslot

30 mmslot

40 mmslot

20 mmslot

30 mm100 5.5 5.5 7.7125 8.9 8.9 10.2160 15.5 15.5 16.6200 25.8 25.8 21.3250 39.6 39.6 33.7315 67.4 67.4 46.9

No of measuring tubes: 2. Spread pattern 360º 1 measuring tube

Kfactors_en-2006-12-08.fm Page 20 Friday, December 8, 2006 2:39 PM

Page 22: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

21Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS with circular commissioning box --------------------------

ATCb supply air ATCb exhaust airsize slot 20 mm slot 30 mm slot 40 mm slot 20 mm slot 30 mm100 5.5 5.5 7.3125 8.9 8.9 7.7160 15.5 15.5 16.7200 25.8 25.8 28.0250 39.6 39.6 31.5315 68.1 68.1 55.3

No of measuring tubes: 2. Spread pattern 360º 1 measuring tube

CDYb supply air CDYb exhaust airsize supply air exhaust air100 5.0 6.1125 8.2 10.6160 15.1 15.0200 25.9 25.0250 39.4 38.4315 67.1 41.1400 101.0 73.7

No of measuring tubes: 2 1 measuring tube

size EAGLE F supply air100 4.9125 8.0160 14.7200 24.6250 38.2315 62.6400 103.0

No of measuring tubes: 2

LOCKZONE F (LPCa) supply airsize slot 20 mm slot 30 mm125 14.1 15.2160 23.4 25.7200 35.1 38.6250 51.5 56.7315 74.5 83.1

No of measuring tubes: 1Spread pattern 360ºNo straight section required.

Kfactors_en-2006-12-08.fm Page 21 Friday, December 8, 2006 2:39 PM

Page 23: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

AIR DIFFUSERS Displacement terminal units -----------------------------

22Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS Displacement terminal units

Figure 1. DBC, DHC, DVC. Measuringwith one tube.

Figure 2. DCP. Measuring with one tu-be.

DBCa DBResize supply air supply air200 34.0 36.8250 54.0 41.0315 89.5 46.5400 142.5

200-600 122.0300-600 185.0

1 measuring tube

Kfactors_en-2006-12-08.fm Page 22 Friday, December 8, 2006 2:39 PM

Page 24: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

23Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS Displacement terminal units -----------------------------

DCPe DHCe DVCesize supply air supply air supply air125 12.2 12.0 12.0160 22.8 20.0 20.0200 37.0 33.0 33.0250 58.0 50.0 50.0315 88.0 84.0 84.0400 141.0 134.0 134.0500 210.0 202.0630 295.0 285.0800 520.0

1 measuring tube

ICPa IHCa IVCasize supply air supply air supply air200 22.9 22.9 22.9250 35.9 35.9 35.9315 54.4 54.4 54.4

1 measuring tube

Kfactors_en-2006-12-08.fm Page 23 Friday, December 8, 2006 2:39 PM

Page 25: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

AIR DIFFUSERS Displacement terminal units -----------------------------

24Swegon Commissioning Guide 2006-12

www.swegon.com

Figure 3. DIR. Measuring with one tube. Figure 4. DRC and DKC. Measuringwith one tube.

Figure 5. DRI. Measuring with one tube.

DIRc DKCe DRCe DRIfsize supply air supply air supply air supply air

400-100 13.1500-125 18.7600-160 23.5900-200 46.8

200 32.0 32.0250 53.0 53.0315 85.0 85.0400 130.0 130.0

200-600 120.0 120.0250-800 176.0 176.0

500 133.0630 223.0800 350.0

1 measuring tube

Kfactors_en-2006-12-08.fm Page 24 Friday, December 8, 2006 2:39 PM

Page 26: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

25Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS Diffuser beam with discs and adjustable measuring unit ----AIR DIFFUSERS Diffuser beam with discs and adjustable measuring unit

AIR DIFFUSERS Slot diffusers

DDKT 1a DDKasize size125 9.6160 15.8200 23.5250 35.6315 59.2400 95.6

No of measuring tubes: 2

SLAT 1 SLAa supply airsize 90° 0°

2-600 7.1 7.94-600 14.8 17.56-600 22.0 27.52-900 10.6 12.54-900 21.2 25.36-900 29.4 35.4

1 measuring tube

SLAT 2 SLAa supply airsize 90° 0°

2-600 7.5 9.24-600 15.0 18.46-600 22.5 27.62-900 11.0 13.84-900 22.0 27.66-900 33.0 41.4

1 measuring tube

Kfactors_en-2006-12-08.fm Page 25 Friday, December 8, 2006 2:39 PM

Page 27: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

AIR DIFFUSERS Linear disc diffuser with commissioning box ---------------

26Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS Linea r disc diffuser with commission ing box

SRYT 1b SRYbsize size supply air size supply air

1-500-125-L 1-900-1 4.5 1-1200-1 5.32-500-160-L 2-900-1 8.6 2-1200-2 6.53-500-160-L 3-900-1 12.4 3-1200-2 9.44-500-200-L 4-900-1 16.2 4-1200-2 12.4

1 measuring tube.Note! The K-factor is valid for one commissioning box. Ex: With two or three commissioning boxes for one diffuser, the total of the designed airflow shall be divided by the number of commissioning boxes.

SRYT 1b SRYbsize size supply air size supply air

1-500-125-L 1-1500-2 5.8 1-1800-2 4.62-500-160-L 2-1500-2 7.8 2-1800-2 8.63-500-200-L 3-1500-2 11.4 3-1800-2 13.04-500-200-L 4-1500-2 14.4 4-1800-3 12.4

1 measuring tube.Note! The K-factor is valid for one commissioning box. Ex: With two or three commissioning boxes for one diffuser, the total of the designed airflow shall be divided by the number of commissioning boxes.

Kfactors_en-2006-12-08.fm Page 26 Friday, December 8, 2006 2:39 PM

Page 28: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

27Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS with fixed regulation function ----------------------------AIR DIFFUSERS with fixed regulation function

Figure 1. Measuring with one tube.

UDYa supply airsize 0 plugs 2 plugs 3 plugs 5 plugs 6 plugs 9 plugs1-5 3.4 2.2 1.61-6 4.0 2.8 2.21-9 6.1 4.3 3.02-5 6.7 4.8 3.62-6 8.1 6.3 4.52-9 12.0 8.9 6.5

1 measuring tube

Kfactors_en-2006-12-08.fm Page 27 Friday, December 8, 2006 2:39 PM

Page 29: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

AIR DIFFUSERS Exhaust air terminal device ------------------------------

28Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS E xhaust air terminal device

Figure 1. FDP. Measuring with one tube. Figure 2. KVB, ROE and EXC. Measur-ing with one tube.

FDPasize slot

5 mmslot

10 mmslot

15 mmslot

20 mmslot

25 mmslot

30 mmslot

40 mm300-150 2.6 4.1 5.6 7.2 8.8 10.3 13.4500-150 5.2 7.9 9.5 13.8 15.5 18.0 22.5800-150 8.3 12.0 16.4 21.9 25.1 29.8 36.9

1 measuring tube

KVBb 100 KVBb 125 KVBb 160 KVBb 200cone position k-factor k-factor k-factor k-factor

-15 1.4-10 1.4-7 0.9-5 0.6 1.1 1.9 3.0-3 0.80 1.0 1.7 2.6 3.8

+5 1.5 2.2 3.2 4.7+10 1.9 2.7 3.8+15 2.3 3.2 4.5 6.6+25 8.2

Measured by pressure guage

Kfactors_en-2006-12-08.fm Page 28 Friday, December 8, 2006 2:39 PM

Page 30: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

29Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS Exhaust air terminal device ------------------------------

ROEa 100 ROEa 125 ROEa 160 ROEa 200cone position k-factor k-factor k-factor k-factor

-15 0.6-12 0.8-10 1.0 1.3 2.0-5 1.4 1.9 2.8-3 1.80 1.8 2.6 3.6 2.6

+5 2.3 3.2 4.5 3.8+10 2.7 3.9 5.4 5.2+15 6.2 6.4+20 7.5+25 8.6

Measured by pressure guage

EXCa 100 EXCa125 EXCa 160 EXCa 200cone position k-factor k-factor k-factor k-factor

-15 0.6-12 0.8-10 1.0 1.3 2.0-5 1.4 1.9 2.8-3 1.80 1.8 2.6 3.6 2.6

+5 2.3 3.2 4.5 3.8+10 2.7 3.9 5.4 5.2+15 6.2 6.4+20 7.5+25 8.6

Measured by pressure guage

Kfactors_en-2006-12-08.fm Page 29 Friday, December 8, 2006 2:39 PM

Page 31: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

AIR DIFFUSERS e.r.i.c. System ------------------------------------------

30Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS e.r.i.c . System

ACKc + ALEa 1 supply air ACLb supply airsettings 160 200 250 settings 125 160 200

10% 0.6 0.8 1.0 10% 0.80 1.13 0.8315% 1.8 2.1 2.2 15% 2.28 2.52 2.3720% 2.9 3.4 3.4 20% 2.97 3.90 3.9025% 4.0 4.9 5.1 25% 4.03 5.28 5.6530% 5.1 6.4 6.9 30% 5.08 6.67 7.4035% 6.2 7.9 8.6 35% 6.14 8.05 9.1540% 7.3 9.3 10.3 40% 7.20 9.43 10.9045% 8.4 10.7 12.1 45% 8.04 10.68 12.5350% 9.4 12.1 13.8 50% 8.88 11.93 14.1755% 10.5 13.5 15.6 55% 9.72 13.18 15.8060% 11.5 14.9 17.3 60% 10.56 14.43 17.4365% 12.5 16.3 19.1 65% 11.39 15.68 19.0770% 13.6 17.6 20.8 70% 12.23 16.93 20.7075% 14.2 18.6 22.4 75% 12.61 17.61 21.8580% 14.8 19.5 23.9 80% 12.99 18.29 23.0085% 15.4 20.5 25.5 85% 13.37 18.97 24.1590% 16.0 21.4 27.0 90% 13.74 19.64 25.3095% 16.6 22.4 28.6 95% 14.12 20.32 26.45

100% 17.2 23.3 30.1 100% 14.50 21.00 27.601 measuring tube 1 measuring tube

Kfactors_en-2006-12-08.fm Page 30 Friday, December 8, 2006 2:39 PM

Page 32: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

31Swegon Commissioning Guide 2006-12

www.swegon.com

AIR DIFFUSERS e.r.i.c. System ------------------------------------------

AKYb + ALEc 3 - supply air ARPa supply airsettings 400-400 600-600 settings 160

10% 0.80 1.5015% 1.90 3.1520% 3.00 4.8025% 3.80 6.30 25% 0.9030% 4.60 7.80 30% 1.4035% 5.40 9.30 35% 2.0540% 6.20 10.80 40% 2.7045% 6.73 11.88 45% 3.7550% 7.27 12.97 50% 4.8055% 7.80 14.05 55% 5.8560% 8.33 15.13 60% 6.9065% 8.87 16.22 65% 8.7570% 9.40 17.30 70% 10.6075% 9.63 17.93 75% 12.4580% 9.87 18.57 80% 14.3085% 10.10 19.20 85% 18.4590% 10.33 19.83 90% 22.6095% 10.57 20.47 95% 26.75

100% 10.80 21.10 100% 30.901 measuring tube 1 measuring tube

Kfactors_en-2006-12-08.fm Page 31 Friday, December 8, 2006 2:39 PM

Page 33: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

AIR DIFFUSERS e.r.i.c. System ------------------------------------------

32Swegon Commissioning Guide 2006-12

www.swegon.com

AFKb + ALEc 2 - exhaust airsettings 160 200 250 315

10% 0.47 0.60 0.57 1.0015% 1.03 1.70 2.03 2.7820% 1.60 2.80 3.50 4.5725% 2.04 3.78 4.67 6.3230% 2.48 4.75 5.83 8.0735% 2.93 5.73 7.00 9.6040% 3.37 6.70 8.17 11.1345% 3.76 7.40 9.00 12.2550% 4.14 8.10 9.83 13.3755% 4.53 8.80 10.67 14.4860% 4.92 9.50 11.50 15.6065% 5.31 10.20 12.33 16.7270% 5.70 10.90 13.17 17.8375% 5.89 11.11 13.69 18.3980% 6.08 11.32 14.22 18.9685% 6.27 11.53 14.75 19.5290% 6.46 11.74 15.28 20.0895% 6.64 11.96 15.81 20.64

100% 6.83 12.17 16.33 21.201 measuring tube

Kfactors_en-2006-12-08.fm Page 32 Friday, December 8, 2006 2:39 PM

Page 34: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

33Swegon Commissioning Guide 2006-12

www.swegon.com

FLOW CONTROL DCV, dampers and measuring products ------------------FLOW CONTROL DCV, dampers and measuring products

Figure 1.No of measuring tubes: 2. Connected to"nipple well". The K-factor is also validfor the combination VARc with sound attenuator CLA L=500 or 1000mm.

size VARc100 4.7125 7.2160 11.7200 17.8250 28.0315 42.9400 84.7500 101.0

Straight sections are required befo-re the damper to secure that stated method errors, 5%, will be obtai-ned, see table:

1 x 90° bend 3 x ∅d2 x 90° bends 4 x ∅d1 x T-joint 4 x ∅dMixing box 4 x ∅d

KZMa+KZMb KRFa+KRFb+KRFc KSAa+KSAbsize k-factor k-factor k-factor100 5.5 5.5 5.5125 9.5 9.5 9.5160 16.0 16.0 16.0200 25.5 25.5 25.5250 40.0 40.0 40.0315 64.0 64.0 64.0400 104.0 104.0 104.0500 165.0 165.0 165.0

No of measuring tubes: 2.The two measuring tubes will be used after disconnection from the pressure sensor. Af-ter commissioning, the two tubes must be reconnected to the pressure sensor.

Straight sections are required before the damper to secure that the stated method errors, 5%, will be obtained, see table:

1 x 90° bend 2 x ∅d2 x 90° bends 4 x ∅d1 x T-joint 2 x ∅d

Kfactors_en-2006-12-08.fm Page 33 Friday, December 8, 2006 2:39 PM

Page 35: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

FLOW CONTROL DCV, dampers and measuring products ------------------

34Swegon Commissioning Guide 2006-12

www.swegon.com

Figure 2. Measuring with two tubes.

Straight sections are requiredbefore the damper to securethat the stated method errors, 5%,will be obtained, see table:

1 x 90° bend 3 x ∅d2 x 90° bends 4 x ∅dT-joint 4 x ∅dDamper 45° 6 x ∅d

size CRMc 1 CRMc 5 AREb 280 5.0

100 9.2 9.2 9.2125 9.6 9.6 9.6160 15.8 15.8 15.8200 23.5 23.5 23.5250 35.6 35.6 35.6315 59.2 59.2 59.2400 95.6 95.6 95.6500 147.0630 230.0

No of measuring tubes: 2.

Kfactors_en-2006-12-08.fm Page 34 Friday, December 8, 2006 2:39 PM

Page 36: Commissioning Guide Archive/Air diffusers/K... · Measurement and commissioning----- 4 Swegon Commissioning Guide 2006-12 3. Each product is equipped with a locking screw to hold

35Swegon Commissioning Guide 2006-12

www.swegon.com

FLOW CONTROL DCV, dampers and measuring products ------------------

Figure 3. Measuring with two tubes.

Straight sections are required before the damper to secure that the stated method er-rors, 5%, will be obtained, see table:Straight sections >2Ød are required after the damper.

1 x 90° bend 3 x ∅d2 x 90° bends 4 x ∅dT-joint 4 x ∅dDamper 45° 6 x ∅d

RSMd/e sizeDamper RSMd

100RSMd 125

RSMd 160

RSMd 200

RSMd 250

RSMd 315

RSMd 400

15° 6.6 11.5 19.5 29.0 38.5 60.020° 15.0 22.0 33.0 50.025° 15.0 22.0 28.0 42.530° 4.8 7.6 11.8 17.0 23.0 36.5 83.735° 9.5 13.0 18.5 31.0 68.040° 9.5 13.0 15.5 26.0 56.045° 3.5 4.9 7.5 9.0 13.0 22.5 47.850° 4.8 7.5 11.0 17.0 41.055° 4.8 7.5 9.5 13.7 35.060° 2.4 3.2 4.4 6.0 8.0 11.5 29.865° 3.4 4.7 7.5 9.5 25.570° 3.4 4.7 6.5 8.0 22.075° 1.7 2.4 2.8 4.0 6.0 7.0 18.880° 2.4 3.5 5.6 6.0 17.085° 2.4 3.5 5.4 5.5 15.590° 14.6

No of measuring tubes: 2.

Kfactors_en-2006-12-08.fm Page 35 Friday, December 8, 2006 2:39 PM