communication with dtp relay
TRANSCRIPT
How to make communication with REJ525
DTP (TR. DIFF. RELAY)Install GE LOCAL software {setting edit software}
Install, GE INTRO32 {configuration ( BI,BO,LEDS) edit software}
Install (DTP00004) {DATA BASE model for TDP GE relay}1. To get the relay communication parameters
From the relay keypad press this keys 7 , 1 , 6 , 9
Then press ENT key
And match with this specification
Baud rate 9600
Stop bit 1
Time out 120
2. connect USB SERIAL comm. port to the laptop
Right click in my computer then select properties then hardware then device manager then ports then double click USB SERIAL comm. Port(com2) then adjust the parameters like above then close
3. From desktop window select start , programs , GE_NESIS , GE LOCAL
4. This screen will appeared then Enter user name (any name) and password 7169 default in DTP manual section 11 sheet 1 then press OK
5. This screen will appeared then click comm. parameters
6. Then adjust the comm. Parameters according to the above points (1,2) then click ok
7. Then press relay connection then enter the number & password our device relay no. =1 , password =1 then ok
8. Waiting up to download the setting from the relay
9. This screen will appeared according to good comm.
10. Then this screen will appeared main screen
You can enter any item by press click
11. Like as device status that gives you all of the status of the relay to go back press closes
12. If you want to edit setting so in the main screen press settings this screen will appear then press protection
13. This screen will appear then press general
14. This screen will appear then press general setting
15. This screen will appear double click make on any parameter if you want to make edit
16. Like this by double click on 1st winding ct ratio after edit press send
GE INTRO 32 software17. From desktop window select start , programs , GE_NESIS , Select GE intro32
18. This the main screen for GE intro32 software will be appeared
19. This figure show all parameters in main screen
20. From file menu select new
21. The model selection screen will appeared Then select DTP then press accept
22. the main screen will appearedClick configuration and adjust the port specification then accept and already we adjust it when we connected by GE LOCAL softwarePort: com 2
Speed: 9600
Word length: 8
Parity: none
Stop bits : 1
And press accept
23. The main screen will appeared press relay on/off switch
24. This screen will appeared then enter NO. =1 , password = 1 & press accept
25. The main screen will appear From setting menu select protection You will find:
Input : for configure digital inputAND: for making and gate from some parameters
Output : for configure digital output
Event : for configure protection events
25 /1 select digital input this screen will appeared here we can select the function for BIs
This screen will appear
After select BI function then press here to save and here to send
25/ 2 ANDWe can select the inputs for AND 1 to use it in another position
25 / 3 OUTPUTS
Here we can configure the binary outputs ( OR gate )
25 / 4 Event: for configure protection events ( OR gate )
26. From the main screen select setting menu select general configuration You will find
Events: for configure the communication eventsLEDS: for configure the lads
Graphical : for make the Graphical drawing
26 / 1 Events: for configure the communication events
26 / 2 LEDS: for configure the lads by using protection events that we configure it before
26 / 3 Graphical: for make the Graphical drawing and send Graphic
Eng. Mohammed Deraz ThyssenKrupp Co.
PAGE 2 /24