Compact: presentation
an international referenceWith the Compact system, Merlin Gerin
is today Europes leading manufacturer ofmoulded-case circuit breakers.The Compact range covers all ratings from15 to 1250 A:c Compact NS, from 15 to 630 A;c Compact C, from 800 to 1250 A.
A number of versions:c 1, 2, 3 or 4 poles;c fixed, plug-in or withdrawable;c a comprehensive range of trip units.Circuit breakers designed for allapplications:c 1000 V AC models;c models for DC systems;c source changeover systems.
Compact NS circuit breaker
1 terminals2 cover3 toggle and position indicator4 push-to-trip button
5 trip unit6 test kit connector
1
2
5
6
053100
3
4
N R
push
totr ip
push
totrip
pushtotrip
pushtotrip
pushtotrip
pushto
trip
pushtotrip
push
totrip
push
totrip
applicationsE26988
E21272
E32454
E20999
pushtotr ip
E44356
ccccc protection of incoming devicesof industrial control panel
push
totr ip
MG
ccccc earth fault protection
E44357
-
7/29/2019 Compact 80-1250
2/355Merlin Gerin 3
rated current (A)
ultimate breaking capacity Icu (kA rms)
at 380/415 V (IEC 947-2)
ratings and breaking
capacitiesThe rating plates on the front face of thecircuit breakers indicate the breakingcapacity:N: normal
H: highL: very high.
compact
NS 250 NUi750V Uimp8kVUe(V)
Icu(kA)
220/240
380/415
440
500
525
660/690
250
85
36
35
30
22
8
50
cat A
Ics = 100 % Icu
IEC 947-2UTE VDE BS CEI UNE NEMA
compact
NS 250 HUi750V Uimp8kVUe(V)
Icu(kA)
220/240
380/415
440
500
525
660/690
250
100
70
65
50
35
10
85
cat A
Ics = 100 % Icu
IEC 947-2UTE VDE BS CEI UNE NEMA
compact
NS 250 LUi750V Uimp8kV
Ue(V)
Icu(kA)
220/240
380/415
440
500
525
660/690
250
150
150
130
70
50
20
100
cat A
Ics = 100 % Icu
IEC 947-2UTE VDE BS CEI UNE NEMA
pushtotr ip
pushtotrip
pushtotrip
pushtotrip
pushtotrip
pushtotrip
discrimination Even when equipped with standard tripunits, Compact circuit breakers offer the bestguarantee of electrical power availabilitywhen faults occur. In most cases,discrimination between protective devices
is ensured for all types of faults (overloads,low and high short-circuit currents).
E27836
E27837
E27838
E3245
6
E22051
-
7/29/2019 Compact 80-1250
3/3554 Merlin Gerin
E2460
3
Compact: presentation
modular system A wider range of add-on modules makes itpossible to adapt the Compact system to amaximum number of configurations.
Trip units, auxiliaries and installation andconnection accessories are the same for allmodels within each of following ranges:c Compact NS80 and NSA125/160c Compact NS100 to NS250,c Compact NS400 to NS630,
c Compact C801 to C1251.The common modules for Compact NS100to NS250 circuit breakers and switch-
disconnectors are shown opposite.The same principle applies to CompactNS400 to NS630 and Compact C801 toC1251 circuit breakers.Fewer catalogue numbers means immediateavailability of parts for all solutions.
2
1
7 8
12
15
16
14
10
11
2
3
6
4
9
13
5
System of add-on modules for Compact NS100N/H/L to NS250N/H/L.
1. Breaking unit.2. Trip unit.3. Vigi earth-fault protection module.
4. Insulation monitoring module.5. Voltage presence indicator.6. Ammeter.
7. Voltage releases MN or MX.8. Multifunction auxiliary switch.9. Direct rotary handle.10. Extended rotary handle.11. Motor mechanism.12. Plug-in base.
13. Connection of plug-in andwithdrawable configuration auxiliary
circuits.14. Connection accessories.15. Short terminal shields.16. Long terminal shields.
-
7/29/2019 Compact 80-1250
4/355Merlin Gerin 5
simplified installation Compact circuit breakers make it possibleto standardise switchboards, meaning faster
installation and fewer errors.
All type L Compact circuit breakers (150 kA)are housed in the same frame as the type Nand type H models with the same ratings.
Compact circuit breakers can be easilyinstalled side-by-side in a minimum amount
of space.
4 sizes from 80 to 1250 A
100 to 250 A 400 to 630 A 800 to 1250 ACompact
Connection parts for Compact NS.
connection Numerous connection possibilities, includingfront and rear connections for bare cables,cable lugs or bars, as well as plug-in orwithdrawable versions, are available using
a full set of accessories that can be rapidlyadded to the circuit breaker.
plug-in and withdrawable
versions
Withdrawable Compact NS250N on a chassis.
Plug-in and withdrawable versions for:c fast removal or insertion of the circuitbreaker without exposure to live parts;c standby outgoing circuits ready for wiring
and circuit breaker installation at a laterdate;c for visible break disconnection.
prefabricated
trunking
Compact NS circuit breakers can be
installed in junction boxes of theTelemecanique Canalis range ofprefabricated trunking (see correspondingcatalogue).
80 A
046751
045345
053100
046893
041650
042788
E32455
-
7/29/2019 Compact 80-1250
5/3556 Merlin Gerin
Compact: presentation
interchangeable
trip units
Each Compact device provides differenttypes of protection depending on theassociated trip unit:
c standard protection,c protection of networks supplied bygenerators,c protection of long cables,c protection of DC networks,c protection of motor-starters,c service connection circuit breaker (forspecial subscriber contracts).
Electronic trip unit STR22SE.
On Compact NS100 to NS250 circuit
breakers, the thermal-magnetic andelectronic trip units are interchangeable andmay be rapidly fitted to the circuit breakers.
It is therefore easy to change the protection
of a given circuit following a modification inan installation.
On Compact NS400 and NS630 circuitbreakers, the electronic trip units areinterchangeable plug-in modules.Trip unit STR53UE offers a large number ofprotection settings.
Compact NS100... 630
Thermal-magnetic trip unit TM.
Compact NS250H.
Compact C801... 1251
Compact C1251H circuit breaker.
Electronic trip units allow perfect adaptationof the protection to each circuit in the
electrical distribution network, and, at thesame time, simplify the selection, installationand operation of the devices:c wider range of settings, so that a singletrip unit can provide several types ofprotection,c easier checking during assembly or onsite,c new functions offered by the trip unit, such
as load monitoring and local indications.
Electronic trip unit STR35SE.
041625
041638
041641
046893
051
166
-
7/29/2019 Compact 80-1250
6/355Merlin Gerin 7
other functions
indicationand measurement
Compact NS250L with ammeter module.
Four indication and measurement functionsmay be mounted directly on Compact NScircuit breakers:
c voltage presence indicator for the circuitbreaker terminals, particularly useful onswitchboard incoming units,c display of current readings,c remote transmission of current readings,c earth fault indication for earth fault
detection on TNS systems or assistance inlocating earth faults on TT systems.
options for trip unitSTR53UE
On Compact NS400/630 circuit breakers,trip unit STR53UE offers:c specific indications for different faults(overloads, short-circuits, etc.),... and a number of optional functions:c built-in ammeter;c earth-fault protection;c zone selective interlocking;c transmission of all information concerning
circuit-breaker operation to a monitoring,control or automated distribution centre, viaDialpact modules (see below).
Digipact: electrical installation management Compact circuit breakers incorporate or maybe equipped with Digipact communications
modules. From a remote location (standardpersonal computer PC or programmablelogic controller PLC), the operator can:
c display the status of circuit breakers;c control the circuit breakers;c access information provided by theelectronic trip units.It is also possible to check the status of theUA150 automatic source-changeover
controllers.For more information: see Digipact
catalogue.
0452
12
053102
Compact NS trip unit STR53UE.
E37615
management
Modbus / JBus DC150 data concentrator
internal Digipact bus
PM150power meter
CLS150indicationand localcontrolmodule
circuit breaker orother power-circuitactuator
UA150 automaticsource-changeovercontroller
Multi 9 controldevice andATB 1Sinterface
-
7/29/2019 Compact 80-1250
7/3558 Merlin Gerin
Compact: presentation
common accessories
electrical auxiliaries
Auxiliary switch and MX release for Compact NS.
motor mechanism
Compact NS250N with motor mechanism.
A motor mechanism can be fitted to the frontface of Compact NS100 to C1251 circuitbreakers. Remote control of the opening,closing and reset functions is then possiblevia 2 or 3 impulse or maintained signals.If necessary, the circuit breakers can still beoperated locally via the controls on the front
face.The motor mechanism modules for each
range have a common size.The motor mechanism module forCompact NS is also available incommunicating version (see Digipact
catalogue).
Vigi earth-fault protectionmodule
Vigi modules can be added to Compact NS
circuit breakers to provide earth-faultprotection. The Vigi modules fit directly onthe circuit breaker terminals.
The addition of a Vigi module has no effecton the other performance characteristics ofthe circuit breaker.
Compact NS250H with Vigi earth-fault protection module.
c auxiliary switches:
v Compact NS: just one model, the same forall Compact NS80 to NS630 and NSA125/160 circuit breakers, provides four differentfunctions (OF, SD, SDE and SDV)depending on where it is fitted in the circuitbreaker,v Compact C: two models, the same for allCompact C801 to C1251 circuit breakers,provide remote indications of circuit breaker
status and electrical faults (e.g. 30F + 1SD),c the MN or MX voltage releases arecommon for all models within each of
following ranges:v NS80 and NSA125/160,v NS100 to NS630,v
C801 to C1251.c auxiliary switches for Compact NS arealso available in communicating version and
can be installed in place of the standardswitches (see Digipact catalogue).
0
44313
0
44314
047313
044333
-
7/29/2019 Compact 80-1250
8/3559
LV circuit breakersand switch-disconnectors
Compact80 to 1250 A
functions
and characteristics
page
Compact range and its applications 10
general characteristics 14
circuit breakers for:
low-voltage distribution 16circuit breaker C1251N 1000 V 36earth fault protection 38
motor protection 40industrial control panels 50
switch-disconnectors 54
installation 58
connection 60auxiliaries 64
accessories 72
source changeover systems 76
-
7/29/2019 Compact 80-1250
9/35510 Merlin Gerin
circuit breakers for protection of low voltage distribution networks page 16
Compact: functions and characteristics
applications
motor rating 0.37 37 1.1 220 110250 160670
power (kW)
Compact NS80 NS100/160/250 NS400/630 C801/C1001/C1251
breaking N 25/36 50
capacity (kA rms) H 70 70 70 70
380/415 V L 150 150
circuit breakers for motor protection page 40
rated 12.5 12.5 12.5 60 250 320 400 500
current (A) 100 160 250 400 630 800 1000 1250
Compact NS100 NS160 NS250 NS400 NS630 C801 C1001 C1251
Vigicompact
breaking N 25 36 36 45 45 50 50 50
capacity (kA rms) H 70 70 70 70 70 70 70 70
380/415 V L 150 150 150 150 150 150 150
0467
51
041624
045198
051162
053100
045345
046893
E20999
E26988
for AC networks up to 1000 V : page 36
Compact NS400 N 1000 VCompact C1251N 1000 V
The interchangeable thermal-magnetic or electronic trip units of the Compact NS are designedto protect the following types of electrical installations:
c Standard installation (supplied by a transformer);
c Installations supplied by a generator;
c DC installations;
c Long cable lengths for IT and TN;
c Motors and motor starters.
protection page 22
E43842
E43843
pushtotrip
pushtotrip
pushtotrip
pushto
tr ip
G
push
to
tr ip
+
push
totr ip
-
7/29/2019 Compact 80-1250
10/355
Merlin Gerin 11
rated 12.5 100 12.5 12.5 ... 12.5 ... 60... 250...current (A) 100 160 250 400 630
Compact NSC100 NS100 NS160 NS250 NS400 NS630(CEI947-2 / UL508 / CSA22-2)breaking capacity N 18 25 35 35 42 42
(kA rms) 380/480 V H 65 65 65 65 65rated 15-100 15-250 60-600current (A)
Compact NSE100 NSF150 NSF250 NSJ400 NSJ600
(UL 489 / CEI947-2 / CSA22-2)
breaking capacity N 18 35 35 35 35(kA rms) 480 V H 65 65 65 65
L 100 100
circuit breakers for protection of industrial control panels page 50
E44356
refe
rtoded
icate
dca
talog
054556
041624
045198
054561
054569
054580
rated 100630
current (A)
Compact NSC100 N NS100 N/H/L NS400 N/H/L
Vigicompact NS160 N/H/L NS630 N/H/L
NS250 N/H/L
circuit breakers and relays for earth fault protection page 38
Vigirex earth fault relays separate toroids
circuit breakers all Compact NS equiped by a voltage release (MN or MX)associated
refe
rto
dedic
ated
cata
log
E44357
044333
044322 0
51352
054556
push
totrip
pushtotrip
MG
-
7/29/2019 Compact 80-1250
11/35512Merlin Gerin
source-changeover page 76
E3245
4
rated 12.5 12.5 12.5 160 250 320 400 500current (A) 100 160 250 400 630 800 1000 1250
manual source- by toggle
changeover by rotary handle
system by keylock
automatic
source-
changeover
systems
Compact NS100 to NS250 NS400 to NS630 C801 to C1251
Al l NS100 to NS250 type Al l NS400 to NS630 type Al l C801 to C1251 type N/H/NI
N/H/L/NA fi xed or pl ug -i n N/H/L/NA fi xed or pl ug- in and C801 to C1251 type L
devices. devices. fixed devices.
Compact: functions and characteristics
applications(cont.)
053060
053042
053058
N R
pushtotr ip
pushtot r ip
-
7/29/2019 Compact 80-1250
12/355Merlin Gerin 13
E21272
rated 406380 100125...160 250400...630 1000...1600... 2500current (A)
Interpact INS40 INS100 IN250 IN1000
INS63 INS125 IN400 IN1600
INS80 INS160 IN630 IN2500
rated 50...63 125...160 250...400 630current (A)
Fupact UC50 UC125 UD250T UD630T
switches UD63 UD125 UD400T
UD160
switch-disconnectors page 56
rated 100160250 400630 8001250current (A)
Compact NSC100NA NS400NA C801NI
Vigicompact NS100NA NS630NA C1251NI
NS160NA
NS250NA
refer
toded
icated
catal
og
refer
tode
dicate
dcat
alog
035053
052168
052164
86081
86083
86087
084642
pushtotrip
pushtotrip
pushtotrip
-
7/29/2019 Compact 80-1250
13/35514Merlin Gerin
Compact: functions and characteristics
general characteristics
tropicalisationCompact and derived circuit breakers
comply with NF C 63-100 standard level 2conditions (95% relative humidity at 45C or80% at 55C, hot and humid climateconditions). They also comply with thefollowing standards:c IEC 68-2-30 damp heat;c IEC 68-2-2 dry heat;c IEC 68-2-11 salt spray;c IEC 68-2-1 low temperatures.
environmental protectionCompact circuit breakers takeinto account current concerns forenvironmental protection. Most componentsare recyclable and parts are marked as
specified in applicable standards.
ambient temperaturec Compact circuit breakers can be used attemperatures ranging from -25C to 70C.Above 40C (or 65C for circuit breakersused to protect motor feeders), always take
into account the derating coefficientsindicated in the documentation;c wherever possible the circuit breakersshould be put into service at their normal
ambient operating temperature, however thiscan be done at temperatures between -35Cand -25C as long as this condition does notlast for an extended period;c in their original pack, Compact circuitbreakers may be stored at temperaturesranging from -50 to +85C.
conformity with standards Compact circuit breakers and auxiliariescomply with the following internationalrecommendations:c IEC 947-1: general rules;c IEC 947-2: circuit breakers;c IEC 947-3: switches, disconnectors,switch-disconnectors, etc;c IEC 947-4: contactors and motors startersc IEC 947-5.1 and following - control circuitdevices and switching elements; automaticcontrol components.In that these recommendations are appliedin most countries, Compact circuit breakers
and auxiliaries comply with European(EN 60947-1 and EN 60947-2) and thecorresponding national standards:c France NF;c Germany VDE;c U.K BS;c Austrialia AS;c Italy CEI.They also comply with the specifications ofthe marine classification companies (Veritas,Lloyds Register of Shipping, Det NorskeVeritas, etc).Compact circuit breakers are also designedfor the protection of machine tools in thatthey comply with French standardNF C 79-130 and with the recommendationsissued by the CNOMO organisation.Concerning the United States UL, CanadianCSA, Mexican NOM and Japanese JISstandards, please consult us.
pollution degreeCompact circuit breakers are certified foroperation in pollution-degree IIIenvironments as defined by IECstandard 947 (industrial environments).
Standardised characteristics indicatedon the rating plateUi: rated insulation voltageUimp: rated impulse withstand voltageIcu: ultimate breaking capacity, for variousvalues of the rated operational voltage Ue
cat: utilisation categoryIcw: short-time withstand currentIcs: service breaking capacityIn: rated current
: suitable for isolation
discriminationIn most cases, discrimination is totalbetween two Compact NS circuit breakersequipped with standard trip units(or between Compact NS and Multi 9 circuitbreakers).The table opposite indicates the
combinations providing total discriminationfor N-type circuit breakers equipped withstandard trip units.
upstream Compact NS160N NS250N NS400N NS630Nrating (A) 80 100 125 160 200 250 400 630
downstreamcircuit breaker rating (A)
multi 9 C60N 1025 c c c c c c c c
3240 c c c c c c
63 c c c c c
Compact NS80H 2.56.3 c c c c c c c c
12.5 c c c c c c c
2580 c c c c c
NS100N 16100 c c c c
NS160N 125160 c c
NS250N 200250 c
ctotal discrimination: only the circuit breaker immediately upstream from a fault trips.
E18567
E22037
MERLIN GERIN
compact
NS160 HUi 750V. Uimp 8kV.
Ue
(V)
220/240
380/415
440
500/525
660/690
250
Icu
(kA)
100
70
65
50
10
85
cat A
Ics = 100% Icu
IEC 947.2UTE VDE BS CEI UNE NEMA
D2
D1
-
7/29/2019 Compact 80-1250
14/355Merlin Gerin 15
All Compact circuit breakers aresuitable for isolation as defined in IECstandard 947-2:cthe isolation position corresponds to the O(OFF position);cthe operating handle cannot indicatethe "off" position unless the contacts areeffectively open;cpadlocks may not be installed unless thecontacts are open.Installation of a rotary handle or a motormechanism does not alter the reliabilitythe position indication system.
The isolation function is certified by testsguaranteeing:cthe mechanical reliability of the positionindication system;cthe absence of leakage currents;covervoltage withstand capacity betweenupstream and downstream connections.
suitability for isolationpositive contact indication
degree of protection(as per standards IEC 529)
installation in class II
switchboardsAll Compact circuit breakers, even whenfitted with a rotary handle or a motormechanism, may be installed throughthe door of class II switchboards (as per IECstandard 664).
Installation requires no special operationsbecause the Compact provides class II
insulation between the front face and allinternal circuits.
bare circuit breaker with terminal shieldswith toggle IP40
with direct rotary handle standard / VDE IP40
circuit breaker installed in switchboardwith toggle IP 40
with direct rotary handle standard / VDE IP40
MCC IP43
CNOMO IP54
with extended rotary handle IP55
with motor mechanism IP40
044
334
E18569
E18570
E28439
E21277
E28440
E28441
E28442
pushtotrip
2
I
pushON
Opush
OFF
1
manu/aut
o
push
totrip
pushtotrip
ONI
OOFF
pushtotrip
ONI
OOFF
pushtotr ip
ONI
OOFF
ONI
OFF
pushtotr ip
-
7/29/2019 Compact 80-1250
15/355Merlin Gerin16
Compact: functions and characteristics
protection of low-voltage distribution networks (cont.)
circuit breakers
for power distribution
switchboards
pushtotrip
pushtotrip
pushtotrip
(*) 2P only for N-types
(**) for operational voltage up to 500 V
Compact circuit breakersnumber of poles
electrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 40C
rated insulation voltage (V) Ui
rated impulse withstand voltage (kV) Uimp
rated operational voltage (V) Ue AC 50/60 Hz
DC
ultimate breaking capacity Icu AC 50/60 Hz 220/240 V(kA rms) 380/415 V
440 V
500 V
525 V
660/690 V
DC 250 V (1 P)500 V (2 P in series)
service breaking capacity Ics (% Icu)
utilisation category
suitability for isolation
endurance (C-O cycles) mechanical
electrical 440 V - In/2
440 V - In
electrical characteristics as per standard Nema AB1breaking capacity (kA) 240 V
480 V
600 V
protection (see following pages)protection against interchangeable trip unitsovercurrents (A) Ir setting current
earth fault protection add-on Vigi module
Vigirex relay
installation and connectionfixed/front connection
fixed/rear connection
plug-in (on base)
withdrawable (on chassis)
indication and measurement auxiliariesauxiliary switches
electronic trip unit related functions
voltage presence indicator
current transformer module
ammeter module
insulation monitoring module
control auxiliariesauxiliary releases
motor mechanism
rotary handles (direct, extended)
manual/automatic source changeover systems
installation and connection accessoriesbare cable connectors
terminal extensions and spreaders
terminal shields and phase barriers
escutcheonsdimensions and weightsdimensions 2/3 poles, fixed, FC
L x H x D (mm) 4 poles, fixed, FC
weight (kg) 3 poles, fixed, FC
4 poles, fixed, FC
045345
Compact NS250H
048286
Compact NS630L
E20999
-
7/29/2019 Compact 80-1250
16/35517Merlin Gerin
NS100 NS160 NS250 NS400 NS6302 (*), 3, 4 2 (*), 3, 4 2 (*), 3, 4 3, 4 3, 4
100 160 250 400 630
750 750 750 750 750
8 8 8 8 8
690 690 690 690 690
500 500 500 500 500
N H L N H L N H L N H L N H L85 100 150 85 100 150 85 100 150 85 100 150 85 100 150
25 70 150 36 70 150 36 70 150 45 70 150 45 70 150
25 65 130 35 65 130 35 65 130 42 65 130 42 65 130
18 50 100 30 50 70 30 50 70 30 50 100 30 50 70
18 35 100 22 35 50 22 35 50 22 35 100 22 35 50
8 10 75 8 10 20 8 10 20 10 20 75 10 20 35
50 85 100 50 85 100 50 85 100 85 8550 85 100 50 85 100 50 85 100 85 85
100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%** 100%** 100%**
A A A A A A A A A A A A A A A
c c c c c c c c c c c c c c c
50000 40000 20000 15000 15000
50000 40000 20000 12000 8000
30000 20000 10000 6000 4000
85 100 200 85 100 200 85 100 200 85 100 200 85 100 200
25 65 130 35 65 130 35 65 130 42 65 130 42 65 130
10 35 50 20 35 50 20 35 50 20 35 50 20 35 50
c c c c c
12.5...100 12.5...160 12.5...250 160...400 250...630
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
105 x 161 x 86 105 x 161 x 86 105 x 161 x 86 140 x 255 x 110 140 x 255 x 110
140 x 161 x 86 140 x 161 x 86 140 x 161 x 86 185 x 255 x 110 185 x 255 x 110
1.6 1.6 1.9 6.0 6.0
2.1 2.1 2.3 7.8 7.8
-
7/29/2019 Compact 80-1250
17/355Merlin Gerin18
Compact: functions et characteristics
protection of low-voltage distribution networks (cont.)
circuit breakers for powerdistribution switchboards,
single-pole and two-polecircuit breakers
Compact circuit breakersnumber of poles
electrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 40C
rated insulation voltage (V) Ui
rated impulse withstand voltage (kV) Uimp
rated operational voltage (V) Ue AC 50/60 Hz
DC
ultimate breaking capacity Icu AC 50/60 Hz 220 V
(kA rms) 277 V
380/415 V
440 V
500 V
525 V660/690 V
DC 250 V (1 pole)
500 V (2 poles)
service breaking capacity Ics (% Icu)
utilisation category
suitability for isolation
endurance (C-O cycles) mechanical
electrical 440 V (277 V for 1P) - In/2
440 V (277 V for 1P) - In/2
electrical characteristics as per Nema AB1breaking capacity (KA) 240 V
277 V
480 V600 V
protection (see next pages)protection against interchangeable trip units
overcurrents (A) Ir setting current
earth fault protection add-on Vigi module
Vigirex relay
installation and connectionsfixed/front connection
fixed/rear connection
plug-in (on base)
withdrawable (on chassis)
indication and measurement auxiliariesauxiliary switches
voltage presence indicator
voltage transformer module
ammeter module
control auxiliariesauxiliary releases
motor mechanism
rotary handles (direct, extended)
manual/automatic source changeover systems
installation and connection accessoriesbare-cable connectors
terminal extensions and spreaders
terminal shields and phase barriers
front panel escutcheons
dimensions and weightsdimensions: W x H x D (mm)
weight (kg)
86099
single-pole Compact NS160H
86101
two-pole Compact NS100N
E29210
-
7/29/2019 Compact 80-1250
18/35519Merlin Gerin
NS100 NS160 NS2501 2 1 2 1
100 100 160 160 250
750 750 750 750 750
8 8 8 8 8
277 690 277 690 277
250 500 250 500 250
N H N H N H N H N25 40 85 100 25 40 85 100 25
25 40 25 40 25
25 70 36 70
25 65 35 65
18 50 30 50
18 35 22 358 10 8 10
25 40 50 85 25 40 50 85 25
50 85 50 85
100% 100% 100% 100% 100% 100% 100% 100% 100%
A A A A A A A A A
c c c c c c c c c
20000 20000 20000 20000 20000 20000 20000 20000 10000
20000 20000 20000 20000 20000 20000 20000 20000 10000
10000 10000 10000 10000 10000 10000 10000 10000 5000
25 40 85 100 25 40 85 100 25
25 40 25 40 25
25 65 25 6510 35 10 35
16...100 16...100 125...160 125...160 160250
c c c c c
c c c c c
c c
c c
c c c c c
c c c c c
c c c c c
c c c c c
35 x 161 x 86 70 x 161 x 86 35 x 161 x 86 70 x 161 x 86 35 x 161 x 86
0.7 1.2 0.7 1.2 0.7
-
7/29/2019 Compact 80-1250
19/355Merlin Gerin20
Compact: functions and characteristics
protection of low-voltage distribution networks (cont.)
circuit breakersfor power distribution
switchboards (cont.)
(*) rated current In at 40C for plug-in/withdrawable units:- C1001N/H: 1000 A- C1001L: 910 A
- C1251N/H: 1160 A
046893
Compact C1251H
The Compact range also includes a circuitbreaker for 1000 V AC distribution networks(see page 0023).
Compact circuit breakersnumber of poles
electrical characteristics as per CEI 947-2 and EN 60947-2rated current (A) In 40C
rated insulation voltage (V) Ui
rated impulse withstand voltage (kV) Uimp
rated operational voltage (V) Ue AC 50/60 Hz
DC
ultimate breaking capacity Icu AC 50/60 Hz 220/240 V(kA rms) 380/415 V
440 V
500 V
525 V
660/690 V
DC 125 V250 V
500 V
750 V
service breaking capacity Ics (% Icu)
short-time withstand current Icw kA rms
t (s)
utilisation category
suitability for isolation
endurance (cycles C-O) mechanical
electrical 440 V - In/2
440 V - In
electrical characteristics as per standard Nema AB1breaking capacity (kA) 240 V
480 V
600 V
protection (see following pages)protection against interchangeable trip unitovercurrents (A) Ir setting current
eart fault protection add-on Vigi module
Vigirex relay
installation and connectionfixed/front connection
fixed/rear connection
plug-in (on base)
withdrawable (on chassis)
indication and measurement auxiliariesauxiliary switches
electronic trip unit related functions
voltage presence indicator
insulation monitoring module
control auxiliariesauxiliary releases
motor mechanism
rotary handles (direct, extended)
manual/automatic source changeover systems
installation and connection accessoriesbare cable connectors
terminal extensions and spreadersterminal shields and phase barriers
escutcheons
dimensions and weightsdimensions W x H x D (mm) 3/4 poles, fixed, FC
weight (kg) 3/4 poles, fixed, FC
-
7/29/2019 Compact 80-1250
20/35521Merlin Gerin
C801 C1001 C12513, 4 3, 4 3, 4
800 1000 (*) 1250 (*)
750 750 750
8 8 8
690 690 690
750
N H L N H L N H85 100 150 85 100 150 85 100
50 70 150 50 70 150 50 70
42 65 150 42 65 150 42 65
40 50 100 40 50 100 40 50
25 40 60 25 40 60 25 40
50 (1P)50 (2P)
50 (3P)
25 (3P)
50% 50% 50% 50% 50% 50% 50% 50%
12 12 6.4 15 15 8 15 15
1 1 1 1 1 1 1 1
B B A B B A B B
c c c
12000 6400 15000 6400 15000
3000 3000 3000
1500 1500 1500
85 100 150 85 100 150 85 100
42 65 100 42 65 100 42 65
30 42 65 30 42 65 30 42
c c c
320...800 400...1000 500...1250
c c c
c c c
c c c
c c (*) c (*)
c c c
c c c
c c c
c c c
c c c
c c c
c c c
c c c
c c c
c c c
210 / 280 x 374 x 172 210 / 280 x 374 x 262 210 / 280 x 374 x 172 210 / 280 x 374 x 262 210 / 280 x 374 x 172
13 / 17 25 / 33 13 / 17 25 / 33 13 / 17
-
7/29/2019 Compact 80-1250
21/35530Merlin Gerin
Compact: functions and characteristics
protection of low-voltage distribution networkstrip units for Compact C801 to C1251
320 400 500 630 800 1000 1250
STR 25 DE
STR 35 GE
STR 35 SE
STR 55 UE
STR 45 AE
STR 45 BE
P21 / P41
N
H
L
N H
L
N
standard protection,
protection of networks supplied bygenerators,
protection with discrimination onshort-circuits,
protection with total discrimination,
protection of DC networks.
Ir I
5
I
t
0
1
5
Ir Im
3
I I
t
0
1
4
electronic trip units STR35SE/GE
15 8
C 801 NHC 1001 NH
LL
12
C 1251NH
t
i
Ir
Im
tm
I
120s
A
A1,5 Ir
x In
5
STR 35SE
.63 .8
.5 1
xIn
Io
60 70 80 90 % Ir105
test Ir Im
+
tm
.9
.95
.8 1.85
4
6
1.5 10xIr
.3
0 0
.1
.3
.2
82
3
.2
.1
on I2t off
5
1
xIo
1 38 47
Legend1 "long time" protection threshold2 "long time" protection time delay3 "short time" protection threshold
4 "short time" protection time delay5 "instantaneous" protection threshold
6 option (see page 34)7 overload indication8 test connector
electronic trip unit STR25DE
5
STR 25DE
.63 .8
.5 1
xIn
Io
60 70 80 90 % Ir
t Ir
I
i
105
test Ir I
+
.9
.95
.8 1xIo
.85
4
6
1.5 10xIr
82
3
5
1 51 7
E23659
E24039
E23820
E24040
E23821
-
7/29/2019 Compact 80-1250
22/355Merlin Gerin 31
electronic trip unit STR45AE
electronic trip unit STR45BE
electronic trip unit STR55UE
2
5
Ir Im
3
I I
t
0
1
4
2
Ir Im
3
I
t
0
1
4
2
5
Ir Im
3
I I
t
0
1
4
protectionc"long time" protection against overloads;c"short time" protection against short-circuits of low intensity;c"instantaneous" protection against short-circuits of high intensity;cresidual earth fault protection as an option(see page 34).Trip units do not have a predefined rating.The "long time" protection thresholddepends only on the circuit breaker currentrating and on the "long time" protectionsetting (see page 32).
other functions
Overload indicationsLoad indication (LED) in front (7) allowing to
avoid tripping:clit at 90% of Ir setting;cflashing at 105% or more of Ir setting.
TestTest connector in front (8) to check circuitbreaker operation, using a mini test kit or acalibration test kit (see page 73).
Indication and measurement options (6)(see page 34).
5
STR 55UE
.63 .8
.5 1
xIn
Io
60 70 80 90 % Ir
t Ir
tr
Im
i
tm
Ih
th
105
test Ir Im
S
T
+
+
tr tm
.9.95
.8 1xIo
.85
15 48030
24060
at 1.5Ir
4
6
1.5 10xIr
.3
0 0
.1
.3
.2
82
3
.2
.1
Ic1
.4
.1
.3
on I2t offon I2t off
TFR
5
120
I5
8
2
3
4
6
.9.95
.8 1xIr
.85
A
B
10
15
8
8
C 801 NHC 1001 NH
LL
10
C 1251NH
12
B
A
th
Ih
.2 .6
.4
.5
.3
xIn
Ic1
I
fault
.4
.3
.1
.2.2
test
xIn
3 51 48 21 7 6
5
STR 45BE
.63 .8
.5 1
xIn
Io
60 70 80 90 % Ir
t Ir
tr
Im
i
tm
Ih
th
105
test Ir Im Ih
S
T
+
+tr tm th
.9.95
.8 1xIo
.85
120
15 48030
24060
at 1.5Ir
4
6
1.5 10xIr
.3
0 0.1
.3
.2
82
3
.2
.1
.2 .6xIn
.4
.1 .1.2
.4
.3
.4
.5
.3
.3
.2
on I2t offon I2t off
T
5
1 1 7 68 2 43
5
STR 45AE
.63 .8
.5 1
xIn
Io
90 % Ir
t Ir
tr
Im
i
tm
Ih
th
105
test Ir Im
S
T
+
+
tr tm
.9
.95
.8 1xIo
.85
15 480
30
240
60
at 1.5Ir
4
6
1.5 10xIr
.3
0 0
.1
.3
.2
82
3
.2
.1
Ic1
.4
.1
.3
on I2t offon I2t off
TFR
5
120 .9.95
.8 1xIr
.85
60 70 80
th
Ih
.2 .6
.4
.5
.3
xIn
A 20
C 801NH
Ic1
x In 23
C 1001NH
18
C 1251NH
A
I
.2
.1
.2
.3
.4
fault
3 61 48 21 7E
24037
E
23823
E24036
E23824
E24038
E23822
-
7/29/2019 Compact 80-1250
23/35532Merlin Gerin
Compact: functions and characteristics
protection of low-voltage distribution networkstrip units for Compact C801 to C1251 (cont.)
(*) For Compact C801L and C1001L, current settings must not exceed eight times the circuit breaker rating (C801L: 6300 A, C1001L: 8000 A)
trip units STR25DE STR35SEfor Compact C801...1251N/H c c
C801...1001L c c
overload protection (long time)tripping threshold Ir adjustable (4 settings or adjustable (32 settings)
"fine setting" version: 32 settings)
0.4...1 x In 0.4...1 x In
thermal memory
OFF position
neutral protection 4P 3d no protection no protection
4P 4d 1 x Ir 1 x Ir
4P 3d + Nr 500 A x Ir/In 500 A x Ir/In
tripping time (s) type fixed fixed
(min...max) at 1.5 x Ir 96...120 96...120
at 6 x Ir 6.0...7.5 6.0...7.5
at 7.2 x Ir 4.2...5.2 4.2...5.2
short-circuit protection (short time)tripping Im adjustable adjustable
threshold (A) 1.5...10 x Ir (*) 1.5...10 x Ir (*)
accuracy 15% 15%
time delay (ms) max. overcurrent fixed adjustable (4 settings)
time before tripping 0 0 i 60 i 140 i 230
total breaking time i 60 i 60 i 140 i 230 i 350
const I2t positions
short-circuit protection (instantaneous)tripping I no fixed
threshold (A) C801N/H 15 x In
C1001N/H 15 x InC1251N/H 12 x In
C801L 8 x In
C1001L 8 x In
other functionsoverload indications c c
test connector c c
earth fault protection option (T)
fault indications option (F)
load monitoring option (R)
communication option (COM)
zone selective interlocking (Z)
Constant I2t positionsInverse-time tripping (ST short-timeprotection) to improve discrimination(particularly with downstream fuses).
Neutral protectionIn the event 4P 4d or 4P 3d + Nr devicesand the corresponding trip units are suppliedseparately, a current sensor must beinstalled on the fourth pole inside the circuitbreaker.
Tripping thresholds are indicated for 2 or3 poles on load.
OFF positionLT (long time) protection deactivated formotor-starter protection.
Thermal memoryConductor cooling time following trippingtaken into account by LT protection.
Overload indicationLED in front of trip unit:clit at 90% of Ir setting;cflashing at 105 % or more of Ir setting.Option F offers a five threshold indication(60, 70, 80, 90, 105%).
TestTest connector to check circuit breakeroperation using a mini test kit or a calibrationtest kit (see page 73).
Indication and measurement options (seepage 34).
-
7/29/2019 Compact 80-1250
24/355Merlin Gerin 33
STR35GE STR45AE STR45BE STR55UEc c c
c c c
adjustable (32 settings) adjustable (32 settings) adjustable (32 settings) adjustable (32 settings)
0.4...1 x In 0.4...1 x In 0.4...1 x In 0.4...1 x In
c
c
no protection no protection no protection no protection
1 x Ir 1 x Ir 1 x Ir 1 x Ir
500 A 500 A x Ir/In 500 A x Ir/In 500 A x Ir/In
fixed adjustable (6 settings)
12...15 12...15 24...30 48...60 96...120 192...240 384...480
0.75...0.94 0.75...0.94 1.50...1.88 3.00...3.75 6.0...7.5 12...15 24...30
0.50...0.65 0.52...0.65 1.04...1.30 2.06...2.60 4.2...5.2 8.3...10.4 17...21
adjustable adjustable adjustable adjustable
1.5...10 x Ir (*) 1.5...10 x Ir 1.5...10 x Ir (*) 1.5...10 x Ir (*)
15% 15% 15% 15%
adjustable (4 settings)
0 i 60 i 140 i 230
i 60 i 140 i 230 i 350
c
fixed fixed no adjustable
15 x In 20 x In 2...15 x In
15 x In 23 x In 2...15 x In12 x In 18 x In 2...12 x In
8 x In 2...8 x In
8 x In 2...8 x In
c c c c
c c c c
c c c
c c
c c c
c c c
c
-
7/29/2019 Compact 80-1250
25/35534Merlin Gerin
Compact: functions and characteristics
protection of low-voltage distribution networkstrip units for Compact C801 to C1251 (cont.)
I
t
0
Ih
th
Load monitoring (R)
tm
6
1.5 10xIr
.3
0 0
.1
.3
.2
82
3
.2
.1
Ic1
.8
.5 1
.7 9
on I2t off
8
1,5
2
3
.9.95
.8 1xIr
.85
Ic2
B
A
xIr
Two adjustable threshold (only one, Ic1, ifoption R is combined with option T), thatdepends on the LT setting, control the opto-decoupled outputs (transistors) or send asignal via the communication outputs. Thesetwo thresholds (Ic1 and Ic2) are used forapplications such as load shedding andreconnection, interlocking systems andalarms.
I
t
0
Ic2 Ic1
Fault indications (F) In addition to indications for standard faults(toggle, SD and SDE auxiliary switches), thisoption differentiates between the threepossible causes of tripping via three LEDs:c overload (LT);c short-circuit (ST + INST);c earth fault.
A three-LED load monitoring functionindicates 60, 70 and 80% of the LTthresholds in addition to the standard 90 and105% indications. Option F is not available
on STR45BE trip units. It requires anexternal power supply.
5
60 70 80 90 % Ir105
Ir Im.9
.95
.81
.85
4
6
1.5 10
82
3
5
fault
I4
8
1,5
2
3
6Ih
.2.
.4
.3
B
A
Communication (COM)The following information is transmitted toDigipact distribution monitoring and controlmodules: all data concerning the currentspassing through the CTs, all trip-unitsettings, including those of options T andR,load-shedding orders, fault indicationsprovided by option F and an alarm indicationwhen the internal temperature is 10C belowthe circuit breaker self-protection threshold.
Possible combinationsc option Z;c options Z, R and F;c options Z, T, R and F;c options Z, F and COM;c options Z, R, F and COM;c options Z, T, F and COM;c options Z, T, R, F and COM.
Zone selective interlocking (Z)A number of circuit breakers areinterconnected one after another by a pilot-
wire. In the event of a short-time or earthfault, the control unit applies the set timedelay only if it receives a signal from adownstream circuit breaker. If not, it trips
instantaneously (tripping time as 0.1 short-time setting). In this way, the fault is clearedrapidly by the nearest circuit breaker. Thethermal stresses in the installation areminimised while maintaining time
discrimination throughout the entireinstallation.Opto-electronic outputsThe use of opto-transistors ensures totalisolation between the internal circuits of thecontrol unit and the circuits wired by theuser.
options for electronic trip units STR45/55
Earth fault protection (T)
The earth fault protection is of the residualcurrent type. The circuit breaker trips, afteran adjustable time delay th, at an adjustablethreshold In that depends on the ratedcurrent In.On request, the earth fault protection may beof the "W" type (source ground return) or ofthe neutral protection type.The thermal memory is identical to that ofthe LT protection, with a time constant of20 seconds.
For distributed neutral systems, option Trequires installation of the 4th polesensor downstream the circuit breaker.
5Im
tm
4
6
1.5 10xIr
.3
0 0
.1
.3
.2
82
3
.2
.1
on I2t off
5Ih
th
.2 .6xIn
.4
.1 .1
.2
.4
.3
.4
.5
.3
.3
.2
on I2t off
I4
8
1,5
2
3
6
B
A
E24042
E23825
E23826
E24041
E24043
-
7/29/2019 Compact 80-1250
26/355Merlin Gerin 35
integrated trip unit for Compact C1251N P21 P41
tripping threshold Im (A) adjustable
1600...3200 3200...6400
accuracy 20% 20%
(1) For the Ic2 minimum setting, the Ir setting and/or the load must be u 0.5 In:
load and/or setting Ic2 setting
0.4 x In 0.81.0 x In
0.5 x In 0.61.0 x In
0.6 x In 0.51.0 x In (complete range)
(2) Minimum operating current 0.22 x In.Ir: tripping threshold of overload protection.
earth fault protection (T)tripping threshold Ih Ih = 0.20.6 x In
settings 0.2 - 0.25 - 0.3 - 0.35 - 0.4 - 0.45 - 0.5 - 0.6
accuracy 15%
time delay th th = settings 0.1 0.2 0.3 0.4
max. overcurrent time before tripping 60 140 230 350
total breaking time 140 230 350 500
power supply self powered
load monitoring (R)Ic1 threshold Ic1 = 0.8...1 x Ir
settings 0.8 - 0.85 - 0.88 - 0.9 - 0.93 - 0.95 - 0.98 - 1.0
accuracy 8%
time delay closing tr/2 (tr = LT protection time delay)
opening 10 s
Ic2 threshold Ic2 = 0.5...1 x Ir
settings (1) 0.5 - 0.6 - 0.7 - 0.8 - 0.85 - 0.9 - 0.95 - 1.0
accuracy 8%
time delay closing tr/4 (tr = LT protection time delay)
opening 10 s
transmission 100 mA opto-decoupled triac outputs, 120 to 240 V, 50/60 Hz or asignal via the communication output when the trip unit isequipped with the COM option.
power supply self powered (2)
fault indications (F)3 LEDs on front indicate cause of fault: Ir, Im/I, Ih
bar graph, 3 LEDs 60, 70, 80% of Ir
accuracy 6.6%
reset automatic when circuit breaker is reset
power supply 24 to 240 V, 50/60 Hz or CCcommunication (COM)
type of data transmitted I1, I2, I3 Ineutral, Imax, all trip-unit settings, rating plugidentification (UL and JIS versions), load monitoring, faultindications, causes of malfunction, internal temperature.
power supply self powered (2)
Magnetic trip units for Compact C1251N,3 poles version, designed particularly for theprotection of DC networks. These tripunits are not interchangeable: the circuitbreaker is supplied fully assembled.All electrical characteristics and circuitbreaker enhancements (auxiliaries andaccessories) are indicated on page 20.
magnetic trip units P21/P41
P21 3P
4800
6000
9600
7800
t(s)
I(A)
E29212
-
7/29/2019 Compact 80-1250
27/35536Merlin Gerin
circuit breaker NS400 1000 V
Compact circuit breaker NS400 1000 Vnumber of poles 3
CT (A) (current transformer) 150 250 400
electrical characteristicsrated operational voltage (V) Ue AC 50/60 Hz 1150 1150 1150
ultimate breaking capacity (kA rms) Icu AC - 1000 V 10 10 10
service breaking capacity Ics (% Icu) 100% 100% 100%
electrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 40C 150 250 400
rated insulation voltage (V) Ui 1250 1250 1250
rated impulse withstand voltage (kV) Uimp 8 8 8
rated operational voltage (V) Ue AC 50/60 Hz 1000 1000 1000
ultimate breaking capacity (kA rms) Icu AC - 1000 V 10 10 10service breaking capacity Ics (% Icu) 100% 100% 100%
suitable for isolation c c c
utilisation category A A A
pollution degree III III III
protectionprotection against overcurrents electronic trip unit
STR23SP c c c
instantaneous 9 In 9 In 9 In
earth fault protection
installation and connectionsfixed/front connection c c c
fixed/rear connection consult us
plug-in (on base) consult uswithdrawable (on chassis) consult us
indication and measurement auxiliariesauxiliary switches c c c
voltage presence indicator
current transformer module
ammeter module
insulation monitoring module
control auxiliariesauxiliary releases c c c
motor mechanism c c c
rotary handles (direct extended) c c c
manual/automatic source changeover systems consult us
installation and connection accessoriesbare cable connectors consult us
terminal extensions and spreaders consult us
terminal shields standard
escutcheon c c c
dimensions and weightsdimensions L x H x D (mm) (1) 3 poles, fixed, FC 140 x 480 x 110
weight (kg) 3 poles, fixed, FC 13
0531
82
NS400 1000 V
Compact: functions and characteristics
protection of low-voltage distribution networks1000 V circuit breakers
(1) with terminal shields.
-
7/29/2019 Compact 80-1250
28/355Merlin Gerin 37
circuit breaker C1251N 1000 V
(1): For withdrawable version do not use acurrent setting higher than:- 1160 A at 40C,- 1080 A at 50C,- 1000 A at 60C.(2): Defined for a power factor cos = 0.3.
Compact circuit breaker C1251N 1000 Vnumber of poles 3
CT (A) (current transformer) 400 800 1250
electrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 40C 400 800 1250 (1)
50C 400 800 1150 (1)
60C 400 800 1050 (1)
rated insulation voltage (V) Ui 1000 1000 1000
rated impulse withstand voltage (kV) Uimp 8 8 8
rated operational voltage (V) Ue AC 50/60 Hz 1000 1000 1000
ultimate breaking capacity (kA rms) (2) Icu AC - 1000 V 20 20 20
service breaking capacity Ics (% Icu) 50% 50% 50%
short-time withstand current Icw kA rms 15 15 15
t (s) 1 1 1suitable for isolation c c c
utilisation category B B B
pollution degree III III III
protectionprotection against overcurrents interchangeable
electronic trip unit c c c
STR25DE c c c
STR35GE/SE/ME(3) c c cSTR55UE (3) c c c
earth fault protection c c c
installation and connectionsfixed/front connection c c c
fixed/rear connection c c c
plug-in (on base)
withdrawable (on chassis) c c c
indication and measurement auxiliariesauxiliary switches c c c
electronic trip unit related functions c c c
voltage presence indicator
current transformer module
ammeter module
insulation monitoring module
control auxiliariesauxiliary releases c c c
motor mechanism c c c
rotary handles (direct extended) c c c
manual/automatic source changeover systems c c c
installation and connection accessoriesbare cable connectors c c c
terminal extensions and spreaders c c c
terminal shields and phase barriers c c c
escutcheon c c c
dimensions and weightsdimensions L x H x D (mm) 3 poles, fixed, FC 210 x 374 x 172weight (kg) 3 poles, fixed, FC 13
(3)
instantaneous CT400/800 CT1250fixed: STR35 15 x In 12 x In
adjustable: STR552 to: 15 x In 12 x In
0513
53
C1251N 1000 V
-
7/29/2019 Compact 80-1250
29/35538Merlin Gerin
Compact: functions and characteristics
protection oflow-voltage distribution networksearth fault protection
Vigi earth fault modules
Vigicompact NS250N
Compliance with standardsc IEC 947-2, appendix B;c IEC 255-4 and IEC 801-2 to 5, coveringprotection against nuisance tripping due totransient overvoltages, lightning strikes,switching of devices on the network,electrostatic discharges, radiofrequencyinterference;c IEC 755, class A, immunity to DC
components up to 6 mA;c VDE 664, operation down to - 25C.
vigi
200 / 440 V - 50 / 60 Hz
2 4 6
1 3 5
T
NS 250
before dielectric testr e m o v e t h i s c o v e r
avant test dilectriqueenlever ce couvercle
N
310
150
60
0
0,03 ( t = 0 )
vigi MH3
1
0,3
t(ms)
In(A)
10
HS
T R
1 2 3 4 5 6 7
Power supplyVigi modules are self-supplied internally bythe network voltage and therefore do notrequire any external source. They continueto function even when supplied by only twophases.
Remote indicationsVigi modules may be equipped with an SDVauxiliary switch (see page 64) to remotelyindicate tripping due to an earth fault.
1 sensitivity setting
2 time-delay setting (for discrimination with earth
fault protection)
3 lead seal preventing access to settings
4 test button for routine tripping checks by
internally simulating an earth fault
5 reset button (resetting is required following a trip
due to an earth fault)
6 rating plate
7 slot for SDV auxiliary switch
Vigicompact circuitbreakers
Dimensions and weights NS100 - NS160 NS250 NS400 - NS630
dimensions 3 poles 105 x 236 x 86 135 x 355 x 110L x H x D (mm) 4 poles 140 x 236 x 86 180 x 355 x 110
weight (kg) 3 poles 2.5 2.8 8.8
4 poles 3.2 3.4 10.8
For Compact NS100 to NS630 circuitbreakers, earth fault protection is obtained
by fitting a "Vigi" earth fault module directlyon the circuit breaker terminals.The addition of the Vigi module does notaffect circuit breaker characteristics (seepages 10 to 13);c conformity with standards;c protection degrees, class II insulation front
face;
c suitability for isolation as defined byIEC 947-2;
celectrical characteristics;c trip unit characteristics;c installation and connection methods;c indication,measurement and controlauxiliaries;c installation and connection accessories.
earth fault protection modules Vigi ME Vigi MH Vigi MBnumber of poles 3. 4 (*) 3. 4 (*) 3. 4 (*)
for Compact NS100 N/H/L ccccc ccccc
NS160 N/H/L ccccc ccccc
NS250 N/H/L ccccc
NS400 N/H/L ccccc
NS630 N/H/L ccccc
earth fault protection characteristicssensitivity In (A) fixed adjustable adjustable
0.3 0.03 - 0.3 - 1 - 3 - 10 0.3 - 1 - 3 - 10 - 30
time delay intentional delay (ms) fixed adjustable adjustable< 40 0 60 (**) 150 (**) 310 (**) 0 60 150 310
total breaking time (ms) < 40 < 40 < 140 < 300 < 800 < 40 < 140 < 300 < 800
rated voltage (V) AC 50/60 Hz 200 to 440 200 to 440-440 to 550 200 to 440-440 to 550(*) Vigi 3P modules may also be used on 2P circuit breakers
(**) If the sensitivity is set to 30 mA, the tripping is not delayed
044333
E21007
-
7/29/2019 Compact 80-1250
30/355Merlin Gerin 39
pushtotrip
MG
combination of
Compact circuit breaker
Vigirex earth faultprotection relay
This solution can be used with all Compactcircuit breakers.
For Compact NS100 to NS630, the Vigirexresidual current relays can be used when:c special time delay or tripping thresholdvalues are required;c there are major installation constraints(circuit breaker already installed andconnected, limited space available, etc.).
Vigirex relay characteristicsResidual current operated relay with
separated toroid:c sensivity adjustable from 30 mAto 250 A;c eight time-delay settings (0 to 1s);c closed toroids (30 to 300 mm diameter);c split toroids (46 to 110 mm diameter);c options :
vtrip alarm by a failsafe contact,vpre-alarm contact and indicating light(threshold: 0.5 x In),v400 Hz network, etc.
Conformity with standardsc IEC 947-2, appendix B;c IEC 255-4 and IEC 801-2 to 5, covering
protection against nuisance tripping due totransient overvoltages, lightning strikes,switching of devices on the network,electrostatic discharges, radiofrequencyinterference;c IEC 755, class A, immunity to DCcomponents up to 6 mA;c VDE 664, operation down to - 25C.
For complete information on theVigirex range, consult the correspondingMerlin Gerin documentation.
residual current measurement toroid
Vigirex earth fault detection relay
MN or MX auxiliary release for earth fault tripping.
E18577
-
7/29/2019 Compact 80-1250
31/355Merlin Gerin40
Compact: functions and characteristics
motor protection
push
to
tr ip
The circuit breakers presented here:cccccprovide protection against short-circuits;cccccare suitable for isolation as defined byIEC 947-2 standard.For a complete protection of the motor andits control device, overload protection maybe ensured by either:cccccthe circuit breaker;ccccca separate Telemecanique thermal relay.The control device may be of the direct on-line type (with or without reversing) or of the"star-delta" type.Combinations are governed by IEC 947-4standard.
protection coordination
(as defined by IEC 947-4)Whatever the power of the motor, thecoordination between circuit breaker,contactor and relay can be of either type 1 or2 (see the complementary technicalinformation chapter page 195). Selectiondepends on operational requirementsconcerning continuity of service and thetechnical skills of servicing personnel.
All type 2 Merlin Gerin/Telemecaniquecombinations have been tested under theconditions defined by standards, and theyare certified ASEFA/LOVAG.
E26988
Compact circuit breakersnumber of poles
electrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 65C
rated insulation voltage (V) Ui
rated impulse withstand voltage (kV) Uimp
rated operational voltage (V) Ue AC 50/60 Hz
ultimate breaking capacity Icu AC 50/60 Hz 220/240 V(kA rms) 380/415 V
440 V
500 V
525 V
660/690 V
DC 250 V (1 pole)
500 V (2 poles)
service breaking capacity Ics (% Icu)
utilisation category
suitability for isolation
endurance (C-O cycles) mechanical
electrical 440 V - In/2
440 V - In
electrical characteristics as per Nema AB1breaking capacity (kA) 240 V
480 V
600 V
protection
overload and short-circuit protection rating (A)interchangeable trip units
short-circuit protection (separate thermal relay) rating (A)
interchangeable trip units
earth fault protection add-on Vigi module
Vigirex relay
installation and connectionfixed/front connection
fixed/rear connection
plug-in (on base)
withdrawable (on chassis)
indication and measurement auxiliariesauxiliary switches
electronic trip unit function
voltage presence indicator
current transformer module
ammeter module
insulation monitoring module
control auxiliariesauxiliary releases
motor mechanism
rotary handles (direct, extended)
locking systems
installation and connection accessoriesbare-cable connectors
terminal extensions and spreadersterminal shields and phase barriers
front panel escutcheons
dimensions and weightsdimensions: L x H x D (mm)
weight (kg)
-
7/29/2019 Compact 80-1250
32/35541Merlin Gerin
NS80 NS100 NS160 NS2503 3, 4 3, 4 3, 4
80 100 150 220
750 750 750 750
8 8 8 8
690 690 690 690
H N H L N H L N H L
100 85 100 150 85 100 150 85 100 150
70 25 70 150 36 70 150 36 70 150
65 25 65 130 35 65 130 35 65 130
25 18 50 100 30 50 100 30 50 70
25 18 35 100 22 35 100 22 35 50
6 8 10 75 8 10 75 8 10 20
50 85 100 50 85 100 50 85 100
50 85 100 50 85 100 50 85 100
100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
A A A A A A A A A
c c c c
20000 50000 40000 20000
10000 50000 40000 20000
7000 30000 20000 10000
100 85 100 200 85 100 200 85 100 200
65 25 65 130 35 65 130 35 65 130
10 10 35 50 20 35 50 20 35 50
24100 24...150 24...220c c c
1.5...80 2.5...100 2.5...150 2.5...220
c c c
c c c
c c c c
c c c c
c c c
c c c
c c c
c c c c
c c c
c c c
c c c
c c c
c c c c
c c c
c c c c
c c c c
built-in c c c
c c c
c c c c
c c c
90 x 120 x 80 105 x 161 x 86 105 x 161 x 86 105 x 161 x 86
1.0 1.6 1.6 1.9
-
7/29/2019 Compact 80-1250
33/355Merlin Gerin42
Compact: functions and characteristics
motor protection(cont.)
push
totr ip
The circuit breakers presented here:cccccprovide protection against short-circuits;cccccare suitable for isolation as defined byIEC 947-2 standard.
For a complete protection of the motor andits control device, overload protection maybe ensured by either:cccccthe circuit breaker;
ccccca separate Telemecanique thermal relay.The control device may be of the direct on-line type (with or without reversing) or of the"star-delta" type.Combinations are governed by IEC 947-4standard.
protection coordination(as defined by IEC 947-4)Whatever the power of the motor, thecoordination between circuit breaker,contactor and relay can be of either type 1 or2 (see the complementary technicalinformation chapter page 195). Selectiondepends on operational requirementsconcerning continuity of service and thetechnical skills of servicing personnel.
All type 2 Merlin Gerin/Telemecaniquecombinations have been tested under theconditions defined by standards, and theyare certified ASEFA/LOVAG.
E26988
Compact circuit breakersnumber of poles
electrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 65Crated insulation voltage (V) Ui
rated impulse withstand voltage (kV) Uimp
rated operational voltage (V) Ue AC 50/60 Hz
ultimate breaking capacity Icu AC 50/60 Hz 220/240 V(kA rms) 380/415 V
440 V
500 V
525 V
660/690 V
DC 125 V
250 V500 V
750 V
service breaking capacity Ics (% Icu)
utilisation category
suitability for isolation
endurance (C-O cycles) mechanical
electrical 440 V - In/2
440 V - In
electrical characteristics as per Nema AB1breaking capacity (kA) 240 V
480 V
600 V
protectionoverload and short-circuit protection rating (A)
interchangeable trip units
short-circuit protection (separate thermal relay) rating (A)
interchangeable trip units
earth fault protection add-on Vigi module
Vigirex relay
installation and connectionsfixed/front connection
fixed/rear connection
plug-in (on base)
withdrawable (on chassis)
indication and measurement auxiliariesauxiliary switches
electronic trip unit related functionvoltage presence indicator
voltage transformer module
ammeter module
insulation monitoring module
control auxiliariesauxiliary releases
motor mechanism
rotary handles (direct, extended)
locking systems
installation and connection accessoriesbare-cable connectors
terminal extensions and spreaders
terminal shields and phase barriersfront panel escutcheons
dimensions and weightsdimensions: L x H x D (mm)
weight (kg)
(*) Ics = 100% Icu for Ue < 500 V
(**) Rated current In at 65 C for withdrawable Compact C1251N/H: 960 A
-
7/29/2019 Compact 80-1250
34/35543Merlin Gerin
NS400 NS630 C801 C1001 C12513 3 3 3 3
320 500 750 875* 1000**750 750 750 750 750
8 8 8 8 8
690 690 690 690 690
N H L N H L N H N H N H
85 100 150 85 100 150 85 100 85 100 85 100
45 70 150 45 70 150 50 70 50 70 50 70
42 65 130 42 65 130 42 65 42 65 42 65
30 50 100 30 50 70 40 50 40 50 40 50
22 35 100 22 35 50 40 50 40 50 40 50
10 20 75 10 20 35 25 40 25 40 25 40
50 (1P)
85 85 50 (2P)85 85 50 (3P)
25 (3P)
100% 100% 100% 100%* 100%* 100%* 50% 50% 50% 50% 50% 50%
A A A A A A B B B B B B
c c c c c
15000 15000 10000 10000 10000
12000 8000 3000 3000 3000
6000 4000 1500 1500 1500
85 100 200 85 100 200 85 100 85 100 85 100
42 65 130 42 65 130 42 65 42 65 42 65
20 35 50 20 35 50 30 42 30 42 30 42
320 320 320 500 500 500 320...800 400...1000 500...1250c c c c c c c c c
320 320 500 500 320...800 400...1000 500...1250
c c c
c c
c c c c c
c c c c c
c c c c c
c c
c c c c c
c c c c c
c c c
c c
c c
c c
c c
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
c c c c c
140 x 255 x 110 140 x 255 x 110 210 x 374 x 172 210 x 374 x 172 210 x 374 x 172
6 6 13 13 25
-
7/29/2019 Compact 80-1250
35/355Merlin Gerin44
E26530
trip units
protection
Compact: functions and characteristics
motor protectiontrip units selection (cont.)
For motor protection, Compact circuitbreakers may be fitted with:
c magnetic trip units, wich provide short-circuit protection;
c electronic trip units, specifically designedto provide:
v short-circuit protection,v overload protection,v phase-failure protection.
overload (long time)tripping Ir adjustable (10 settings) adjustable (40 settings) adjust. (32 settings) adjustable (32 settings)threshold (A) 0.6...1 x In 0.4...0.8 x In 0.4...1 x In 0.4...1 x In
tripping class 10 10A 10 20 10 10A 10 20 30(IEC 947-4)
tripping time (s) fixed adjustable fixed adjustable
(minimaxi) to 1.5 x Ir 120320 144198 270357 433595 96120 4860 96120 192240 384480
to 6 x Ir 615 5.87.3 10.913.1 17.421.8 67.5 33.7 67.5 1215 2430
to 7.2 Ir 410 45 7.39.1 1215 4.25.2 2.12.6 4.25.2 8.310.4 1721
phase-failure (complied with the standard IEC 947-4-1)built into the trip unit c c
tripping time for phase between 3.5 and 6 s 4 s 10%
failures (s)
short-circuit (short time)tripping Im or Isd fixed adjustable (8 settings) adjust. (8 settings) adjustable (8 settings)threshold (A) 13 x Ir 6...13 x Ir 1.5...10 x Ir 1.5...10 x Ir
accuracy 20% 15% 15% 15%
max. overcurrent time fixed fixed adjustable adjustable
before tripping (ms) 10 10 0 60 140 230 0 60 140 230
total breaking time (ms) 60 60 60 140 230 350 60 140 230 350
short-circuit (instantaneous)tripping Ii fixed fixed fixed = In x ... adjustable = In x ...
threshold 15 x In 13 x Ir maxi 15 15 12 2...15 2...15 2...12
(A) 8(type L) 2...8(type L)
other functionsSDTAM module c c
motor overload light c c (standard)
indications module c (standard) c
built-in ammeter (I) c
P (kW) (400 V, 50 Hz)
Ir (A)
CompactNS100 NS250
CompactNS80H-MA
CompactNS400 NS630
CompactC801 C1251
MA
MA
STR22ME
MA
STR43ME
STR35ME (LR OFF)
STR55UE
0.37
1.5
18.5
40
3
6 48
37
80 100 160
110
205 220
160
320
250
500 800
560
1000
670
1250
1.1
2.5
trip units STR22ME STR43ME STR35ME STR55UErating (A) 20 to 70C 10, 12.5, 20, 25, 40, 50, 80,100 150 220 120 200 320 500 800 1000 1250 800 1000 1250
NS100N/H/L c
NS160N/H/L c c
NS250N/H/L c c c
NS400N/H/L c c c
NS630N/H/L c
C801N/H/L c c
C1001N/H/Lc c
C1251N/H c c
-
7/29/2019 Compact 80-1250
36/35545Merlin Gerin
rating (A) threshold settings (A)
10 6 6.3 6.7 7.1 7.5 8 8.5 9 9.5 10
12.5 7.5 7.9 8.4 8.9 9.4 10 10.6 11.2 11.9 12.5
20 12 12.6 13.4 14.2 15 16 17 18 19 20
25 15 15.7 16.7 17.7 18.7 20 21.2 22.5 23.7 25
40 24 25.5 27 28.5 30 32 34 36 38 40
50 30 31.5 33.5 35.5 37.5 40 42.5 45 47.5 50
80 48 51 54 57 60 64 68 72 76 80
100 60 63 67 71 75 80 85 90 95 100
150 90 95 101 107 113 120 127 135 142 150
220 132 140 148 157 166 177 187 198 209 220
I
t
0
1
3
2
4
5
Ir 13Ir
Ir ImIn=50A
IEC 947.4 / cl.10
Ir 13 Ir
7,2Ir
7,0s
Ir
u1,05 Ir
testA30 50
31.5 47.5
33.5 45
37.5 40
35.5 42.5
STR 22 ME
1 7 8
E26985
E26984
electronic trip unit STR22ME
for Compact NS100 to NS250 circuit breakers
protection c LT (long time) overload protection withadjustable Ir threshold (1), in compliancewith tripping class 10 as defined byIEC 947-4 (2);c single-phasing protection (trips in 3.5 and6 s);c ST (short-time) short-circuit protection:v fixed tripping threshold (13 x Ir) (3),v fixed time delay (4);c INST (instantaneous) short-circuitprotection, with fixed threshold (15 x In) (5).
other functions IndicationsLoad indication by LED in front (7):c off when: I < 1.05 x Ir;c flashing when: I u 1.05 x Ir.
TestTest connector in front (8) for connection toa mini test kit or calibration test kit to checkcircuit breaker operation after fitting the tripunit or other accessories.
Contactor tripping module SDTAM (early
thermal fault signal, optional):c opens the contactor in the event of anoverload. It is thus possible to differentiatebetween tripping due to overloads and short-
circuits;
c may also be used to signal a thermal fault;c must be reset manually (locally orremotely);c compatible with the following controlvoltages:v 24 to 72 V DC and 24 to 48 V AC,v 110 to 240 V AC / DC;c fits in place of the MN or MX auxiliaryvoltage releases.
c single - phasing protection. The single -phasing complies with the recommendationsof standard IEC 947-4-1. It becomesoperational whenever a phase currentimbalance of 40% or more is present.
trip unit STR22ME
-
7/29/2019 Compact 80-1250
37/355Merlin Gerin46
I
t
0
1
3
2
4
5
Ir Isd Ii
> Ih
> Im
> Ir
P
faulttestSTR 43 ME
Io
x In
-test
+
31
.90.93.95
.98
1
.88
.85
.8
9 1011
12
13
8
7
6x Io
Ir Isd
x Ir
%Ir >Ir >Isd
A
Ir I1 I2 I3IsdIr li
tr
tsd
class
8 6
.71 .8.63
.56
.5 .8
20
10
10A
20
10
10A
tr
2
IEC 947-4-1
Compact: functions and characteristics
motor protection (cont.)
electronic trip unit STR43ME for Compact NS400to NS630 circuit breakers
E32566
E26987
protection cLT (long time) overload protection,adjustable threshold, based on the actual
rms current:vadjustable threshold (1)using five Io basesettings (0.5 to 0.8), and fine adjustment Irwith eight settings ranging from 0.8 to 1,v adjustable tripping time (2), in compliancewith tripping classes 10 A, 10 and 20 asdefined by IEC 947-4;c the STR43ME offers two motor coolingtime constants, associated with the motorstarting class:v short cooling time constant (the same as
the heating time constant), providingmaximum continuity of service andsatisfactory motor protection,v long cooling time constant (four times theheating time constant), providing maximummotor protection,
c single - phasing protection. The single -phasing complies with the recommendations
of standard IEC 947-4-1. It becomesoperational whenever a phase currentimbalance of 40% or more is present;c ST (short time) short-circuit protection:v adjustable threshold Isd (3),v fixed time delay (4);c INST (instantaneous) short-circuitprotection, with fixed threshold (5).
other functions Overload indications (%Ir)LED flashes when the current exceeds the
long-time threshold Ir.
Fault indicationsLEDs indicate the type of fault that causedtripping:c overload (LT protection)
or abnormal component temperature (>Ir);c short-circuit (ST or instantaneousprotection) (>Isd);c single-phasing (LED on the right);c microprocessor malfunction (all three (>Ir),(>Isd) and single-phasing LEDs go on);Battery powered. Spare batteries aresupplied in an adapter box. When a faultoccurs, the LED indicating the type of faultgoes off after about 10 minutes to conservebattery power.The information is howeverstored in memory and the LED can be re-illuminated by pressing the battery/LED testpushbutton (6). The LED automatically goesoff and the memory is cleared when thecircuit breaker is reset.
Testc test connector in front (8), for connection
to a mini test kit or calibration test kit (seepage 73) to check circuit breaker operationafter fitting the trip unit or other accessories.c test button (6) for (%Ir), (>Ir), (>Isd) and(single-phasing) LEDs and battery.
Self-monitoringThe circuit breaker trips for:c microprocessor faults;c abnormal temperatures.
-
7/29/2019 Compact 80-1250
38/35547Merlin Gerin
A
Ir I1 I2 I3
options for trip unit STR43ME
ammeter (I)A digital display continuously indicates the
current of the phase with the greatest load.By pressing a scroll button, it is alsopossible to display successively thereadings of I1, I2, I3 an the long timethreshold setting Ir.LEDs indicate the phase or setting for whichthe current is displayed.
Ammeter display limits:c minimum current u 0,2 x In (lower currentsare not displayed) ;c maximum current i 10 x In.
E33990
contactor tripping module(SDTAM)
c opens the contactor in the event of an
overload. It is thus possible to differentiatebetween tripping due to overloads and short-circuits;c may also be used to signal a thermal fault;c must be reset manually (locally or
remotely;c compatible with the following controlvoltages:v 24 to 72 V DC and 24 to 48 V AC,v 110 to 240 V AC / DC;
c fits in place of the MN and MX auxiliary
voltage releases.
communication (COM) Transmission of data to Digipact distributionmonitoring and control modules.
Transmitted data:c settings;c phase currents (rms values);c highest current of the three phases;
c overload condition alarm;c cause of tripping (overload, short-circuit,
etc.).
possible combinations c I;c I + COM;
c SDTAM;c SDTAM + I;c SDTAM + I + COM.
-
7/29/2019 Compact 80-1250
39/355Merlin Gerin48
electronic trip units for Compact C801...C1251
electronic trip unit STR35ME
electronic trip unit STR55UE
other functions
(STR35ME and STR55UE)Overload indication
A LED in front (7) indicates the load level(current flowing through the circuit breakerwith respect to the Ir setting):c lit when load u 90% Ir;c flashing when load > 105% Ir.
Test
Test connector in front (8) for connection toa mini test kit or calibration test kit (seepage 73).
protection (STR55UE)The trip units do not have a specific rating:c LT (long time) overload protection:v adjustable threshold Ir (1),v adjustable time delay (2), in compliancewith tripping classes 5, 10, 20 and 30 asdefined by IEC 947-4-1;c ST (short time) protection against medium-intensity short-circuits:v adjustable threshold Im (3),v adjustable time delay (4);c INST (instantaneous) protection againsthigh-intensity short-circuits, with adjustablethreshold I (5).
protection (STR35ME)The trip units do not have a specific rating:c LT (long time) overload protection:v adjustable threshold Ir (1), with an OFF
position to disable the LT protection,v fixed time delay, in compliance withtripping class 10 as defined by IEC 947-4-1;c ST (short time) protection against medium-intensity short-circuits:v adjustable threshold Im (3),v adjustable time delay (4);c INST (instantaneous) protection againsthigh-intensity short-circuits, with fixedthreshold I (5).
Compact: functions and characteristics
motor protection (cont.)
E27366
E27368
E24038
E23822
5
STR 55UE
.63 .8
.5 1
xIn
Io
60 70 80 90 % Ir
t Ir
tr
Im
i
tm
Ih
th
105
test Ir Im
S
T
+
+
tr tm
.9.95
.8 1xIo
.85
15 48030
24060
at 1.5Ir
46
1.5 10xIr
.3
0 0
.1
.3
.2
82
3
.2
.1
Ic1
.4
.1
.3
on I2t offon I2t off
TFR
5
120
I5
8
2
3
46
.9.95
.8 1xIr
.85
A
B
10
15
8
8
C 801 NHC 1001 NH
LL
10
C 1251NH
12
B
A
th
Ih
.2 .6
.4
.5
.3
xIn
Ic1
I
fault
.4
.3
.1
.2.2
test
xIn
3 51 48 21 7 6
15 8
C 801 NHC 1001 NH
LL
12
C 1251NH
t
i
Ir
Im
tm
I
120s
A
A1,5 Ir
x In
5
STR 35ME
.81
.5xIn
Io
60 70 80 90 % Ir105
test Ir Im
+
tm
.9
.95
.8 1.85
4
6
1.5 10xIr
.3
0 0
.1
.3
.2
82
3
.2
.1
on I2t off
5
1 1 38 47
xIo
on off
off
LR inoprant
LT inoprativeIr = In
off
.63
5
Ir Im
3
I I
t
0
1
4
OFF
2
5
Ir Im
3
I I
t
0
1
4
-
7/29/2019 Compact 80-1250
40/35549Merlin Gerin
Functionsc short-circuit protection using an integratedmagnetic trip unit MA with adjustablesettings;c suitability for isolation.
ConnectionsFront connection to integrated connectors
for bare cables with cross-sections from1.5 to 70 mm2.
characteristics of short-circuit protection deviceswith separate overload protection
Compact NS100...NS630with trip unit MAFor the protection of motors from 1.1 to250 kW (400 V), Compact NS100 to NS630circuit breakers must be equipped with aspecial trip unit MA with adjustablethresholds.
This assembly ensures:cshort-circuit protection (magnetic trip unitwith adjustable thresholds);csuitability for isolation.For the Compact NS400 to NS630 circuitbreakers, trip unit MA is not interchangeable.The circuit breaker and trip unit are suppliedalready assembled.
short-circuit protection (magnetic)rating (A) In (65C) 1.5 2.5 6.3 12.5 25 50 80
tripping threshold (A) Im adjustable from
6...14 x In
Compact C801...C1251For the protection of motors from 160 to670 kW with Compact C801 to C1251 circuit
breakers, equipped with an STR35ME or anSTR55UE trip unit, it is possible to disablethe LT protection.
The circuit breakers ensure:c
short-circuit protection (short time orinstantaneous);csuitability for isolation.
Electrical characteristicsc Compact NS80/630, see page 40;cCompact C801/1251, see page 42.
Compact NS80H-MAThis circuit breaker is specially designed forthe protection of motors rated up to 37 kW:cdue to its high current-limiting capacity, iteffectively protects motor starters (type-2coordination as defined by IEC 947-4, withcontactors);csmall size for easy installation in motorcontrol centre (MCC) switchboards.
046751
Compact NS80H-MA
041624
Compact NS250H
045198
Compact NS400H-MA
trip unit forCompact NS100...NS630rating (A) In (65C) 2.5 6.3 12.5 25 50 100 150 220 320 500
for Compact N/H/L NS100 c c c c c c
circuit breaker NS160 c c c c
NS250 c c c
H/L NS400 c
NS630 c
short-circuit protection (magnetic)tripping Im adjustable from adjustable from
threshold (A) 6...14 x In 9..14 x In 9..14 x In
-
7/29/2019 Compact 80-1250
41/355Merlin Gerin50
Compact functions and characteristics
protection of industrial control panels
(**) for operational voltage up to 500 V
Compact NS250H
push
totrip
E44356
Compact NSC100N
054556
0416
25
Compact circuit breakersnumber of poles
electrical characteristics as per CEI 947-2 and EN 60 947-2rated current (A) In 40C
rated insulation voltage (V) Ui
ratde impulse withstand voltage (kV) Uimp
rated operational voltage (V) Ue AC 50/60 Hz
DC
ultimate breaking capacity Icu AC 50/60 Hz 220/240 V(kA rms) 380/415 V
440 V
500 V
525 V
660/690 V
DC 250 V (1 pole)
500 V (2 poles in series)
service breaking capacity Ics (% Icu)
utilisation category
suitability for isolation
endurance (C-O cycles) mechanical
electrical 440 V - In/2
440 V - In
electrical characteritics as per UL 508breaking capacity (kA) 240 V
480 V
600 V
protection (see following pages)protection against interchangeable trip unitsovercurrents (A) Ir setting current
earth fault protection add-on Vigi module
Vigirex relay
installation and connectionfixed / front connection
adaptator for 60 mm busbars
indication and measurement auxiliariesauxiliary switches
early-make or early-break contact
electronic trip unit related functions
voltage presence indicator
current transformer module
ammeter module
insulation monitoring module
control auxiliariesauxiliary releases
motor mechanism
rotary handles (direct, extended)
installation and connection accessoriesbare cable connectors
terminal extensions and spreaders
terminal shields and phase barriers
escutcheons
DIN rail plate
dimensions and weightsdimensions 3 poles, fixed, FCW x H x D (mm) 4 poles, fixed, FC
weights (kg) 3 poles, fixed, FC
4 poles, fixed, FC
-
7/29/2019 Compact 80-1250
42/35551Merlin Gerin
AVAIL
ABLE
IN
199
9
NSC100N NS100 NS160 NS250 NS400 NS6303, 4 3, 4 3, 4 3, 4 3, 4 3, 4
100 100 150 220 320 500
750 750 750 750 750 750
8 8 8 8 8 8
690 690 690 690 690 690
250 500 500 500 500 500
N N H N H N H N H N H42 85 100 85 100 85 100 85 100 85 100
18 25 70 36 70 36 70 45 70 45 70
18 25 65 35 65 35 65 42 65 42 65
10 18 50 30 50 30 50 30 50 30 50
10 18 35 22 35 22 35 22 35 22 35
- 8 10 8 10 8 10 10 20 10 20
5 (125 V) 50 85 50 85 50 85 - 85 - 85
5 (250 V) 50 85 50 85 50 85 - 85 - 85
100 100 100 100 100 100 100 100 100 100 100
A A A A A A A A A A A
c c c c c c c c c c c
20000 50000 40000 20000 15000 15000
10000 50000 40000 20000 12000 8000
7000 30000 20000 10000 6000 4000
42 85 85 85 85 85 85 85 85 85 85
18 25 65 35 65 35 65 42 65 42 65
10 10 10 10 10 18 18 18 18 30 30
built-in c c c c c
16...100 12.5...100 12.5...160 12.5...250 160...400 250...630
c c c c c c
c c c c c c
c c c c c c
- c c c c c
c c c c c c
c c c c c c
c c c c c
- c c c c c
- c c c c c
- c c c c c
- c c c c c
c c c c c c
- c c c c c
c c c c c c
- c c c c c
- c c c c c
c c c c c c
c c c c c c
c c c c - -
90 x 120 x 80 105 x 161 x 86 105 x 161 x 86 105 x 161 x 86 140 x 255 x 110 140 x 255 x 110
120 x 120 x 80 140 x 161 x 86 140 x 161 x 86 140 x 161 x 86 185 x 255 x 110 185 x 255 x 110
1.0 1.6 1.6 1.9 6.0 6.0
1.3 2.1 2.1 2.3 7.8 7.8
-
7/29/2019 Compact 80-1250
43/355Merlin Gerin52
installation in an enclosure
E44458
200 150
300
Marking
test
+ -IEC 947.4 / cl.10
A
Ir
198209
148
157166 177
187
140220132
Ir 13Ir
7.2 Ir
7.0 s
STR 22 MEIn=220A > 1.05 Ir
Vac115
230460575
15
505050
40
75
200150
1ph 3phhp
220A
100% rated
Minimum enclosure dimensions for installation
Height (mm) Depth (mm) Width (mm)
NSC100N 300 150 200NS100 N/H 457 130 208
NS160 N/H 457 130 208
NS250 N/H 457 130 208
NS400 N/H - - -
NS630 N/H - - -
E42651
LISTED MAN. MOTOR. CTRL.34XL
NSC100N-NA
Vac 115 230 460 575
ratings (A) hp
1 ph 3 ph 1 ph 3 ph 1 ph 3 ph 1 ph 3 ph
16
20
25
32
40
50
63
70
80
100
1
1.5
2
2
3
3
5
5
7.5
10
2
3
5
5
7.5
10
10
10
3
10
10
15
15
15
20
7.5
5
2
3
3
5
5
7.5
10
10
15
20
25
30
30
5
7.5
10
10
15
20
25
30
30
40
10
10
15
20
30
30
40
50
60
75
7.5
10
10
15
20
25
30
40
50
40
10
15
20
30
30
40
60
60
75
100tripping current 125% 100% rated
This MMC is suitable for use on a circuit capable of deliveringnot more than the short-circuit current rating of this MMCindicated here below, or the upstream protective deviceinterrupting capability, whichever is less, when protected byany protective device for Group fusing or Group installation.
SC current rating kA 50/60 HzVac
240
480600
42
1810
wire size
tightening torque
lb-inch Nm
14 AWG to 3/0 AWG Cu
12 AWG to 4/0 AWG Al50 5.5
temperature rating
75C
R
Trip-unit marking
device marking (circuit breaker with integreted tripunit)
E42651
UL / CSA logo
cable cross