Centro de Competencia Técnica – Sistemas & Comunicaciones Unity Pro v4.1 - Compatibility rules – Unity Pro and application version Version X.Y applications: application version corresponding to the processor chosen in the Unity Pro configuration screen (project creation step).  Unity Pro V4.1 handles version levels: Premium/Quantum V2.00 (V2.21), V2.30, V2.40, V2.50, V2.60, V2.70; Modicon M340 V1.0, V2.0, V2.1  Unity Pro V4.0 handles version levels: Premium/Quantum V2.00 (V2.21), V2.30, V2.40, V2.50, V2.60; Modicon M340 V1.0, V2.0  Unity Pro V3.1 handles version levels: Premium/Quantum V2.00 (V2.21), V2.30, V2.40, V2.50; Safety Quantum V1.0; Modicon M340 V1.0  Unity Pro V3.0 handles: Premium/Quantum V2.00 (V2.21), V2.30, V2.40; Modicon M340 V1.0  Unity Pro V2.3 SP1 handles: Premium/Quantum V2.00 (V2.21) and V2.30  Unity Pro V2.2 handles: Premium/Quantum V2.00 (V2.21) and V2.00 (V2.21) MFB if MFB (Motion Function Block) option was set up with Unity Pro V2.2  Unity Pro V2.1 handles: Premium/Quantum V2.00  Unity Pro V2.0 handles: Premium/Quantum V2.00 2.1. Table 1 XEF Files on the PC XEF Files on the PC Open with Unity Pro V2.0 Open with Unity Pro V2.1 Open with Unity Pro V2.2 Open with Unity Pro V2.3 SP1 Open with Unity Pro V3.0 Open with Unity Pro V3.1 Open with Unity Pro V4.0 Open with Unity Pro V4.1 Premium / Quantum V2.00 application* YES (1) YES (1) YES (1) YES YES YES YES YES Premium / Quantum V2.30 application (1) NO NO NO YES YES YES YES YES Premium / Quantum V2.40 application NO NO NO NO YES YES YES YES Premium V2.50 application NO NO NO NO NO YES YES YES Premium / Quantum V2.60 application NO NO NO NO NO NO YES YES Premium / Quantum V2.70 application NO NO NO NO NO NO NO YES Modicon M340 V1.0 application NO NO NO NO YES YES YES YES Modicon M340 V2.0 application NO NO NO NO NO NO YES YES Modicon M340 V2.1 application NO NO NO NO NO NO NO YES Quantum safety V1.0 application NA NA NA NA NA YES NA YES Quantum safety V2.0 application NA NA NA NA NA NO NA YES NA: Not Applicable (Quantum Safety only exists for Unity Pro V3.1 & V4.1) * Application version corresponds to the choice of PLC in the Unity Pro configuration screen during the creation of a project (V2.00, V2.30 …) See Unity Pro, application and PLC OS compatibility (Table 7).  Restriction:  (1) If there are MFBs in the application, thes e ones are not usable; errors are generated during the build phase, ex cept for Unity Pro V2.2 with MFB option. 1 Título Documento Jorge Moreno López – Fecha

Upload: ganesh-babu

Post on 07-Apr-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

8/6/2019 Compatibility 20rule

http://slidepdf.com/reader/full/compatibility-20rule 1/6

Centro de Competencia Técnica – Sistemas & Comunicaciones

Unity Pro v4.1 - Compatibility rules – Unity Pro and application version

Version X.Y applications: application version corresponding to the processor chosen in the Unity Pro configuration screen(project creation step). •  Unity Pro V4.1 handles version levels: Premium/Quantum V2.00 (V2.21), V2.30, V2.40, V2.50, V2.60, V2.70; Modicon

M340 V1.0, V2.0, V2.1•  Unity Pro V4.0 handles version levels: Premium/Quantum V2.00 (V2.21), V2.30, V2.40, V2.50, V2.60; Modicon M340 V1.0,

V2.0•  Unity Pro V3.1 handles version levels: Premium/Quantum V2.00 (V2.21), V2.30, V2.40, V2.50; Safety Quantum V1.0;

Modicon M340 V1.0•  Unity Pro V3.0 handles: Premium/Quantum V2.00 (V2.21), V2.30, V2.40; Modicon M340 V1.0

•  Unity Pro V2.3 SP1 handles: Premium/Quantum V2.00 (V2.21) and V2.30•  Unity Pro V2.2 handles: Premium/Quantum V2.00 (V2.21) and V2.00 (V2.21) MFB if MFB (Motion Function Block) option

was set up with Unity Pro V2.2•  Unity Pro V2.1 handles: Premium/Quantum V2.00•  Unity Pro V2.0 handles: Premium/Quantum V2.00

2.1.  Table 1 XEF Files on the PC

XEF Files on the PC 

Open with Unity Pro

V2.0 

Open withUnity Pro

V2.1 

Open withUnity Pro

V2.2 

Open withUnity Pro

V2.3 SP1 

Open with Unity Pro

V3.0 

Open with Unity Pro

V3.1 

Open withUnity Pro

V4.0 

Open withUnity Pro

V4.1 

Premium / QuantumV2.00 application* 

YES (1)  YES (1)  YES (1)  YES  YES  YES  YES  YES 

Premium / QuantumV2.30 application (1) 

NO  NO  NO  YES  YES  YES  YES  YES 

Premium / QuantumV2.40 application 

NO  NO  NO  NO  YES  YES  YES  YES 

PremiumV2.50 application 

NO  NO  NO  NO  NO  YES  YES  YES 

Premium / QuantumV2.60 application 

NO  NO  NO  NO  NO  NO  YES  YES 

Premium / QuantumV2.70 application 

NO  NO  NO  NO  NO  NO  NO  YES 

Modicon M340V1.0 application 

NO  NO  NO  NO  YES  YES  YES  YES 

Modicon M340V2.0 application 

NO  NO  NO  NO  NO  NO  YES  YES 

Modicon M340

V2.1 application  NO  NO  NO  NO  NO  NO  NO  YES 

Quantum safetyV1.0 application 

NA  NA  NA  NA  NA  YES  NA  YES 

Quantum safetyV2.0 application 

NA  NA  NA  NA  NA  NO  NA  YES 

NA: Not Applicable (Quantum Safety only exists for Unity Pro V3.1 & V4.1)* Application version corresponds to the choice of PLC in the Unity Pro configuration screen during the creation of a project (V2.00,V2.30 …)See Unity Pro, application and PLC OS compatibility (Table 7). Restriction: (1) If there are MFBs in the application, these ones are not usable; errors are generated during the build phase, except for UnityPro V2.2 with MFB option.

1Título Documento

Jorge Moreno López – Fecha

8/6/2019 Compatibility 20rule

http://slidepdf.com/reader/full/compatibility-20rule 2/6

Centro de Competencia Técnica – Sistemas & Comunicaciones

2.2.  Table 2 STA Files on the PC

STA Files on the PC 

Open with Unity Pro

V2.0 

Open withUnity Pro

V2.1 

Open withUnity Pro

V2.2 

Open withUnity ProV2.3 SP1 

Open withUnity Pro

V3.0 

Open with Unity Pro

V3.1 

Open withUnity Pro

V4.0 

WithUnity Pro

V4.1 

Premium / QuantumV2.00 application 

YES(1)  YES (2)  YES (2)  YES (3)  YES  YES  YES  YES 

Premium / QuantumV2.30 application 

NO  NO  NO  YES  YES  YES  YES  YES 

Premium / QuantumV2.40 application 

NO  NO  NO  NO  YES  YES  YES  YES 

PremiumV2.50 application 

NO  NO  NO  NO  NO  YES  YES  YES 

Premium / QuantumV2.60 application 

NO  NO  NO  NO  NO  NO  YES  YES 

Premium / Quantum

V2.70 application NO  NO  NO  NO  NO  NO  NO  YES 

Modicon M340V1.0 application 

NO  NO  NO  NO  YES  YES  YES  YES 

Modicon M340V2.0 application 

NO  NO  NO  NO  NO  NO  YES  YES 

Modicon M340V2.1 application 

NO  NO  NO  NO  NO  NO  NO  YES 

Quantum safetyV1.0 application 

NA  NA  NA  NA  NA  YES  NA  YES 

Quantum safetyV2.0 application 

NA  NA  NA  NA  NA  NO  NA  YES 

NA: Not Applicable (Quantum Safety only exists for Unity Pro V3.1 & V4.1)

Restrictions: (1) Unity Pro V2.0 does not allow to open STA other than those generated with Unity Pro V2.0(2) When application generated doesn’t contain MFB functions, except for Unity Pro V2.2 with MFB option(3) When application contains writing on read only variable, the STA is not opened, the corrections must be done before creatingthe STA 

2.3.  Table 3: STU Files on PC

STU Files on PC 

Open withUnity Pro

V2.0 

Open withUnity Pro

V2.1 

Open withUnity Pro

V2.2 

Open withUnity ProV2.3 SP1 

Open withUnity Pro

V3.0 

Open withUnity Pro

V3.1 

Open withUnity Pro

V4.0 

WithUnity Pro

V4.1 

Application generatedwithUnity Pro V2.0 

YES  NO  NO  NO  NO  NO  NO  NO 

Application generatedwithUnity Pro V2.1 

NO  YES  YES  NO  NO  NO  NO  NO 

Application generatedwithUnity Pro V2.2 

NO  NO  YES (1)  NO  NO  NO  NO  NO 

Application generatedwithUnity Pro V2.3 SP1 

NO  NO  NO  YES  NO  NO  NO  NO 

Application generated

withUnity Pro V3.0  NO 

NO 

NO 

NO 

YES 

NO 

NO 

NO 

2Título Documento

Jorge Moreno López – Fecha

8/6/2019 Compatibility 20rule

http://slidepdf.com/reader/full/compatibility-20rule 3/6

Centro de Competencia Técnica – Sistemas & Comunicaciones

Application generatedwithUnity Pro V3.1 

NO  NO  NO  NO  NO  YES  NO  NO 

Application generatedwithUnity Pro V4.0 

NO  NO  NO  NO  NO  NO  YES  NO 

Application generated

withUnity Pro V4.1 

NO  NO  NO  NO  NO  NO  NO  YES 

Restriction: (1) When application contains MFB it can be opened only when MFB option is set up with Unity Pro V2.2 

2.4.  Table 4: PLC => PC Transfer

PLC => PC Transfer With

Unity ProV2.0 

WithUnity Pro

V2.1 

WithUnity Pro

V2.2 

WithUnity ProV2.3 SP1 

WithUnity Pro

V3.0 

WithUnity Pro

V3.1 

WithUnity Pro

V4.0 

WithUnity Pro

V4.1 

Premium / QuantumV2.00 application 

YES (1)  YES (1)  YES (2)  YES  YES  YES  YES  YES 

Premium / QuantumV2.30 application 

NO  NO  NO  YES  YES  YES  YES  YES 

Premium / QuantumV2.40 application 

NO  NO  NO  NO  YES  YES  YES  YES 

PremiumV2.50 application 

NO  NO  NO  NO  NO  YES  YES  YES 

Premium / QuantumV2.60 application 

NO  NO  NO  NO  NO  NO  YES  YES 

Premium / QuantumV2.70 application 

NO  NO  NO  NO  NO  NO  NO  YES 

Modicon M340V1.0 application 

NO  NO  NO  NO  YES  YES  YES  YES 

Modicon M340V2.0 application 

NO  NO  NO  NO  NO  NO  YES  YES 

Modicon M340V2.1 application 

NO  NO  NO  NO  NO  NO  NO  YES 

Quantum safetyV1.0 application 

NA  NA  NA  NA  NA  YES  NA  YES 

Quantum safety

V2.0 application 

NA  NA  NA  NA  NA  NO  NA  YES 

NA: Not Applicable (Quantum Safety only exists for Unity Pro V3.1 & V4.1) 

Restrictions: (1) Transfer not possible when application contains MFB(2) Exception: the application switches to "V2.00 MFB Application" level when MFB option is set up with Unity Pro V2.2 

2.5.  Table 5: PC => PLC Transfer

PC => PLC Transfer(1) 

WithUnity Pro

V2.0 

WithUnity Pro

V2.1 

WithUnity Pro

V2.2 

WithUnity ProV2.3 SP1 

WithUnity Pro

V3.0 

WithUnity Pro

V3.1 

WithUnity Pro

V4.0 

WithUnity Pro

V4.1 

Premium / QuantumV2.00 application 

YES  YES  YES  YES  YES  YES  YES  YES 

3Título Documento

Jorge Moreno López – Fecha

8/6/2019 Compatibility 20rule

http://slidepdf.com/reader/full/compatibility-20rule 4/6

Centro de Competencia Técnica – Sistemas & Comunicaciones

Premium / QuantumV2.30 application 

NO  NO  NO  YES  YES  YES  YES  YES 

Premium / QuantumV2.40 application 

NO  NO  NO  NO  YES  YES  YES  YES 

PremiumV2.50 application  NO  NO  NO  NO  NO  YES  YES  YES 

Premium / QuantumV2.60 application 

NO  NO  NO  NO  NO  NO  YES  YES 

Premium / QuantumV2.70 application 

NO  NO  NO  NO  NO  NO  NO  YES 

Modicon M340V1.0 application 

NO  NO  NO  NO  YES  YES  YES  YES 

Modicon M340V2.0 application 

NO  NO  NO  NO  NO  NO  YES  YES 

Modicon M340V2.1 application 

NO  NO  NO  NO  NO  NO  NO  YES 

Quantum safetyV1.0 application 

NA  NA  NA  NA  NA  YES  NA  YES 

Quantum safetyV2.0 application 

NA  NA  NA  NA  NA  NO  NA  YES 

NA: Not Applicable (Quantum Safety only exists for Unity Pro V3.1 & V4.1)

Restriction: (1) See application compatibility with the OS table

2.6.  Table 6: Online modification

Online modification With

Unity ProV2.0 

WithUnity Pro

V2.1 

WithUnity Pro

V2.2 

WithUnity ProV2.3SP1 

WithUnity Pro

V3.0 

WithUnity Pro

V3.1 

WithUnity Pro

V4.0 

WithUnity Pro

V4.1 

Premium / QuantumV2.00 application 

YES  YES  YES (1)  YES (2)  YES (2)  YES (2)  YES  YES 

Premium / QuantumV2.30 application 

NO  NO  NO  YES  YES  YES  YES  YES 

Premium / QuantumV2.40 application 

NO  NO  NO  NO  YES  YES  YES  YES 

PremiumV2.50 application 

NO  NO  NO  NO  NO  YES  YES  YES 

Premium / QuantumV2.60 application 

NO  NO  NO  NO  NO  NO  YES  YES 

Premium / QuantumV2.70 application 

NO  NO  NO  NO  NO  NO  NO  YES 

Modicon M340V1.0 application 

NO  NO  NO  NO  YES  YES  YES  YES 

4Título Documento

Jorge Moreno López – Fecha

8/6/2019 Compatibility 20rule

http://slidepdf.com/reader/full/compatibility-20rule 5/6

Centro de Competencia Técnica – Sistemas & Comunicaciones

Modicon M340V2.0 application 

NO  NO  NO  NO  NO  NO  YES  YES 

Modicon M340V2.1 application 

NO  NO  NO  NO  NO  NO  NO  YES 

Quantum safetyV1.0 application  NA  NA  NA  NA  NA  YES  NA  YES 

Quantum safetyV2.0 application 

NA  NA  NA  NA  NA  NO  NA  YES 

NA: Not Applicable (Quantum Safety only exists for Unity Pro V3.1 & V4.1)

Restrictions: (1) Exception: When MFB option is set up with Unity Pro V2.00 the application switches to "V2.00 MFB" level(2) Adding a new EFB Type needs to update the library in the project (rebuild all) 

2.7.  Table 7 Unity Pro application and PLC OS compatibility

Unity Pro,

application and PLC OScompatibility 

PREMIUM

minimum OSversion 

QUANTUM

minimum OSversion 

QUANTUM

SAFETYminimum OS

version 

M340

minimum OSVersion 

2.70  2.70  2.00  2.10 

2.60  2.60  x  2.00 

2.50 (2)  x  1.00  x 

2.40  2.40  x  1.00 

2.30  2.30  x  x 

2.21 (1)  x  x  x 

2.00 MFB  x  x  x 

Unity Pro V4.1 

2.00  2.00  x  x 

PREMIUM QUANTUM QUANTUMSAFETY

M340

2.60  2.60 QuantumSafetyNot supported 

2.00 

2.50 (2)  x  x  x 

2.40  2.40  x  1.00 

2.30  2.30  x  x 

2.21 (1)  x  x  x 

2.00 MFB  x  x  x 

Unity Pro V4.0 

2.00  2.00  x  x 

PREMIUM QUANTUM QUANTUMSAFETY

M340

2.50 (2)  x  1.00  x 

2.40  2.40  x  1.00 

2.30  2.30  x  x 

2.21 (1)  x  x  x 

2.00 MFB  x  x  x 

Unity Pro V3.1 

2.00  2.00  x  x 

PREMIUM QUANTUM QUANTUMSAFETY

M340

2.40  2.40  x  1.00 

2.30  2.30  x  x 

Unity Pro V3.0 

2.21 (1)  x  x  x 

5Título Documento

Jorge Moreno López – Fecha

8/6/2019 Compatibility 20rule

http://slidepdf.com/reader/full/compatibility-20rule 6/6

Centro de Competencia Técnica – Sistemas & Comunicaciones

2.00 MFB  x  x  x 

2.00  2.00  x  x 

PREMIUM QUANTUM QUANTUMSAFETY

M340

2.30  2.30  x  x 

2.21 (1)  x  x  x 

2.00 MFB  x  x  x Unity Pro V2.3 SP1 

2.00  2.00  x  x 

PREMIUM QUANTUM QUANTUMSAFETY

M340

2.21 (1)  x  x  x 

2.00 MFB  x  x  x Unity Pro V2.2 

2.00  2.00  x  x 

PREMIUM QUANTUM QUANTUMSAFETY

M340

Unity Pro V2.1  2.00  2.00  x  x 

PREMIUM QUANTUM QUANTUM

SAFETY

M340

Unity Pro V2.0  2.00  2.00  x  x 

The OS version corresponds to the minimum version required to execute a functional level of the application. Higher OS versionsensure compatibility with existing applications (for example: an application version V2.00 generated by Unity Pro V2.20 can beexecuted by a PLC V2.30).

(1) Only TSX P 57 5634 M.(2) Only TSX H57 24 M and TSX H57 44 M 

6Título Documento