conceptual design plan - required …...check mixed air temperature and preheater size (make‐up...
TRANSCRIPT
House Floor plans Framing plans Heating Forced warm air
Plans: Elevations Site plan System: Baseboard Radiant
1.2.3.4.
Ventilation Strategy:
Distribution Strategy:
Basic System Type:
Method of Dealing with Pressure Imbalances:
Control System:
Special Customer Requirements:
Ventilation Equipment:1.2.3.4.5.
Other Exhaust Appliances: (list)1.2.3.4.
Prepared By: HRAI #: Job Name:
Signature: Date: Job #: Official Use:
W‐0
Combustion Appliances
CONCEPTUAL DESIGN PLAN - REQUIRED INFORMATION CHECKLIST
Draft Type
Exhaust only (worksheet W‐1A)
Balanced‐combined with forced air (worksheet W‐1B)
Balanced‐direct ducted (worksheet W‐1C)
© Copyright HRAI Residential Ventilation WORKSHEET W‐0 r 08/10
W‐1AFEATURES• Central or local exhaust fans• Make‐up air by infiltration
Forced warm air heating system?or NO
Small capacity recirculation system?
YES
NO
NO
= required, X = not required
Ventilation capacity W‐2Exhaust requirements W 2
Exhaust Only SystemDETAILED DESIGN PLAN
Spillage Susceptible
YES
DETAILED DESIGN TASKS:
May require make‐up air system
interlocked to ventilation systemand/or exhaust appliances
combustion appliance(s)?CAUTION
Will not meet ventilation distribution requirements
STOP
Ventilation Record
Heat recovery required?
Use balanced heat recovery system
Use worksheet W‐1B or W‐1C
Proceed with detailed design
STOP
worksheet #
Ventilation Record
YES
Exhaust requirements W‐2 System layout, recirculation system (forced warm air or small capacity recirculation) plan Imbalance at TVCC (exhaust larger than supply) or field test W‐3A Imbalance at CEC (only if spillage susceptible appliances ) or field test W‐3C Check mixed air temperature and preheater size (make‐up air connected to forced air) W‐4B
System layout, grille size, door undercuts (central exhaust fan) plan + W‐5 Select fan and size ducts (single‐duct fans, range hoods, bath fans etc., if required) W‐6A Select fan and size ducts (central fan if required) W‐6B Select fan and size ducts (small capacity recirculation system, if required) W‐6B
Size powered air intake/make‐up air duct (if required) W‐6C Size furnace outside air duct (if required) W‐6D
Size passive make‐up air duct (if required) W‐6E Describe control strategy W‐7 Other
Other
Prepared By: HRAI #: Job Name:
Signature: Date: Job #: Official Use:
Ventilation Record
YES
© Copyright HRAI Residential Ventilation WORKSHEET W1‐A r 08/10
W‐1BFeatures• Ventilation supply air connected to return duct of forced air
• Dedicated exhaust ducting or "simplified connection"
NO
NO
Proceed with detailed design
= required, X = not required DETAILED DESIGN TASKS:
W‐2
W‐2
worksheet #
Exhaust requirements
Ventilation RecordVentilation capacity
Ventilation Record
DETAILED DESIGN PLAN
Spillage Susceptible
combustion appliance(s)?
Ventilation supply connected toforced air without heat recovery?
CAUTIONIntake air heater may be required.
Check forced air system mixed air
YES
temperature & heater capacity
CAUTIONMay require make‐up air system
interlocked to exhaust appliance(s)
Balanced System, Combined with Forced Air
HRV/ERV based system?
YES
System layout, recirculation system (forced warm air) plan
W‐3C
Adjust HRV/ERV airflow W‐4A
Check mixed air temperature, preheater size (intake or HRV/ERV connected to forced air) W‐4BCheck delivered air temperature, select intake air heater (if required) W‐4C
plan + W‐5
Select fan and size ducts (single‐duct fans, range hoods, bath fans etc., if required) W‐6A
Select fan and size ducts (HRV/ERV or central fan if required) W‐6B
Size powered air intake duct (if required) W‐6C
Size furnace outside air intake duct (if required) W‐6D
Size passive make‐up air duct (if required W‐6E
Describe control strategy W‐7
Prepared By: HRAI #: Job Name:
Signature: Date: Job #: Official Use:
Other
System layout, grille size, door undercuts (HRV/ERV or central fan)
Imbalance at CEC (only if spillage susceptible appliances ) or Field Test
HRV/ERV based system?
YES
© Copyright HRAI Residential Ventilation WORKSHEET W1‐B r 08/10
W‐1CFeatures• HRV/ERV or exhaust + intake fan and heater
• Direct supply or exhaust from all habitable rooms
NO
YES Yes
Caution Spillage Susceptible May require make‐up air system
combustion appliance(s)? interlocked to exhaust appliance(s)
NO
Proceed with detailed design
= required, X = not required DETAILED DESIGN TASKS:
Ventilation capacity W‐2 Exhaust requirements W‐2
Ventilation Record
Ventilation Record
DETAILED DESIGN PLANBalanced System, Direct Ducted
worksheet #
HRV/ERV based system?
YES
Exhaust system with intake fan and heater?
Check air delivery arrangement(high or low wall) against
heater capacity
Check air delivery arrangement (high or low wall) againstHRV/ERV effectiveness
Exhaust requirements W 2 Imbalance at CEC (only if spillage susceptible appliances ) W‐3C Adjust HRV/ERV airflow (if required) W‐4A Check delivered air temperature /select intake air heater (if required) W‐4C
System layout, grille size, door undercuts (central fan or HRV/ERV) plan + W‐5 Select fan and size ducts (Single‐duct fans, range hoods, bath fans etc., if required) W‐6A Select fan and size ducts (central fan/HRV/E W‐6B Size powered air intake duct (if required) W‐6C Size passive air intake (if required) W‐6E Describe control strategy W‐7 Other
Other
Prepared By: HRAI #: Job Name:
Signature: Date: Job #: Official Use:
Ventilation Record
HRV/ERV based system?
YES
Exhaust system with intake fan and heater?
Check air delivery arrangement(high or low wall) against
heater capacity
Check air delivery arrangement (high or low wall) againstHRV/ERV effectiveness
© Copyright HRAI Residential Ventilation WORKSHEET W1‐C r 08/10
A H Oil Other
Solid Fuel (including Fireplaces) I Direct Vent (sealed combustion)
Positive Venting Induced Draft P.C.
Email Address:
B Clothes Dryer(s) J Downdraft Cook Top
Other (exhaust) P.C.
No
C @ 20 cfm Email Address:
@ 10 cfm
@ 10 cfm CSA F326 M‐91
@ 10 cfm R‐2000Signature: Date:
Controls Functioning KD Filters Clean
@ 60 = cfm Dampers Accessible
@ 20 = cfm Drain loop and connectioncfm
@ 100 = cfm @ 50 = cfm
cfm
E LF
M
G 1 cfm P.C.
TVC HVI
2 cfm Email Address:
TVC HVI
3 cfm
TVC HVI R‐2000
4 cfm
TVC HVI
Prepared By: HRAI #: Job Name:
Signature: Date: Job #: Official Use:
Date: Manufacturer/Model:
Location: Signature:(exhau
st)EQUIPMEN
T
Location:
% Sensible Efficiency @ ‐25°C
ADDITIONAL
Manufacturer/Model:
Location:
Sones
I certify this ventilation system install to be in accordance with:Manufacturer/Model:
CSA F326 M‐91Location: Sones
Manufacturer/Model:
TVC
Manufacturer/Model: HVI rated
cfm HighDesign Airflow cfm high cfm low
HRV/ERV % Sensible Efficiency @ 0°C watts
Sones
Phone:
Sones
cfm High cfm Low
MEA
SURE
D
Fax:
Address:City:
TVC SYSTEM
S
cfm Low
Continuo
us Minimum Continuous Exhaust
Insulated ducts sealed
SYSTEM
Location: TVC system EXHAUST airflow measured
watts Name: HRAI #: HRV/ERV
TVC system SUPPLY airflow measured
EXHAUST CAPA
CITY
Kitchen(s) cfm Label supply/exhaust hoodBathroom(s)
Total Forced air system Continuous mode Interlocked
Kitchen intake grease filter Kitchen exh. 40" to range
Interm
ittent Minimum Intermittent Exhaust
Total
TOTA
L VEN
TILA
TION Other Bedrooms cfm I certify this ventilation system design to be in accordance with:
Bathrooms & Kitchens cfm
cfmTotal Ventilation Capacity (TVC) cfm
Fans operating and clean
CAPA
CITY
(TVC)
Bsmt & Master Bedroom
EXHAUST (220 cfm default) Address:
(over 150 cfm) City: Depressurization test/Calc. Required? Fax: EQ
UIPMEN
T (150 cfm default) Name: HRAI #:
Yes Phone:
cfm
Other Hab. Rooms
INSTALLATION CHEC
KLIST
Exhaust 4" above grade Supply 18" above gradeKitchen(s) cfm Supply intake 6' from exhaust (recommended)Bathroom(s)
Other #
DESIGNER
Flow measuring stations
cfm Supply intake 3' from other exhaust
cfm Distribution to all habitable rooms (non forced air)
House ID#:
BUILDERNo Dep Limit Address:
Lowest Depressurization Limit _________ Pa.
Pascals limit City: Natural Draft or B‐Vent Atmospheric 5 pa depress limit Phone: Fax:
INSTALLER
RESIDENTIAL MECHANICAL VENTILATION RECORDFor Certification of Design and Performance of Residential Ventilation Systems W2
COMBU
STION APP
LIANCE
S
Forced Air Non Forced air Roll #: Permit #:
LOCA
TION
HEA
TING SYSTEM/
Electric Gas Lot & Plan: No Combustion Appliances No Depressurization limit Civic address:
5 pa Depress limit Name:
© Copyright HRAI Residential Ventilation WORKSHEET W‐2 r 08/10
W‐3Aline #
1. FLOOR AREA ft2 301 (total heated floor area including basement; count crawl space at 1/2 actual area)
House ACH50 302
3. COMBUSTION APPLIANCE DEPRESSURIZATION LIMIT
pa 303
304
4. ALLOWABLE NET EXHAUST
305
cfm
5. ACTUAL NET EXHAUST cfm 306
‐ minus
cfm 307
= equals
cfm 308
Total Floor Area
IMBALANCE @ TVCC (Total Ventilation Capacity Condition)
TVCC Exhaust
Allowable Net Exhaust @ TVCC
Flow Factor
Floor Area (301) ________ ft2 x ACH50 (302) ________ x Flow Factor (304) ________ =
2. ASSUMED AIR CHANGES PER HOUR AT 50 PASCAL'S
If spillage susceptible, = ‐5pa.
If non‐spillage susceptible, = ‐10pa
for systems with more exhaust than supply @ TVCC
flow factor = 0.037
flow factor = 0.022 Depressurization Limit @ TVCC
TVCC Supply
Actual Net Exhaust @ TVCC
Tight R‐2000 0.5 ACH Typical R‐2000 1.0 ACH Prairies/North (new) 1.0 ACHAtlantic (new) 1.5 ACH Other provinces (new) 1.4 ACH Older homes 2.5 ACHor actual test _________
Note: If supply is greater than exhaust, use worksheet #W‐3B
6. REQUIRED MAKE‐UP AIR FLOW
cfm
‐ minus
cfm
= equals
cfm 309
pa
7. DESCRIPTION OF MAKE‐UP AIR SYSTEM
8. ON‐SITE TEST DEPRESSURIZATION TEST Required Not Required 310
Prepared By: HRAI #:
Signature: Date: Official Use:
Job Name:
Job #:
Actual Net Exhaust @ TVCC (line 308)
Required Make‐Up Airflow @ TVCC
At Depressurization Limit (line 303)
Allowable Net Exhaust @ TVCC (line 305)
Note:If Actual Net Exhaustis less than AllowableNet Exhaust no actionis required.
Tight R‐2000 0.5 ACH Typical R‐2000 1.0 ACH Prairies/North (new) 1.0 ACHAtlantic (new) 1.5 ACH Other provinces (new) 1.4 ACH Older homes 2.5 ACHor actual test _________
© Copyright HRAI Residential Ventilation WORKSHEET W‐3A r 08/10
W‐3Bline #
1. FLOOR AREA Total Floor Area ft2 301
302
3. ALLOWABLE NET SUPPLY
cfm 311
4. ACTUAL NET EXHAUST TVCC Supply cfm 312
‐ minus
cfm 313
= equals
cfm 314
5. REQUIRED RELIEF AIR FLOW
cfm
‐ minus
cfm
= equals
IMBALANCE @ TVCC (Total Ventilation Capacity Condition)for systems with more supply than exhaust @ TVCC
Allowable Net Supply @ TVCC
House ACH50
Actual Net Supply @ TVCC (line 314)
TVCC Exhaust
Allowable Net Supply @ TVCC (line 311)
Note: If exhaust is greater than supply, use worksheet #W‐3A
Actual Net Supply @ TVCC
(total heated floor area including basement; count crawl space at 1/2 actual area)
Floor Area (301) __________ ft2 x ACH50 (302) _________ x 0.037 =
2. ASSUMED AIR CHANGES PER HOUR AT 50 PASCAL'S
Note:If Actual Net Supplyis less than AllowableNet Supply no action
Tight R‐2000 0.5 ACH Typical R‐2000 1.0 ACH Prairies/North (new) 1.0 ACHAtlantic (new) 1.5 ACH Other provinces (new) 1.4 ACH Older homes 2.5 ACHor actual test _________
= equals
cfm
315
6. DESCRIPTION OF RELIEF AIR SYSTEM
7. ON‐SITE PRESSURIZATION TEST Required Not Required 316
Prepared By: HRAI #: Job Name:
Signature: Date: Job #: Official Use:
Required Relief Airflow @ TVCC
Note:If Actual Net Supplyis less than AllowableNet Supply no action is required.
Tight R‐2000 0.5 ACH Typical R‐2000 1.0 ACH Prairies/North (new) 1.0 ACHAtlantic (new) 1.5 ACH Other provinces (new) 1.4 ACH Older homes 2.5 ACHor actual test _________
© Copyright HRAI Residential Ventilation WORKSHEET W3‐B r 08/10
W‐3Cline #
1. FLOOR AREA Total Floor Area ft2 301
2. ASSUMED AIR CHANGES PER HOUR AT 50 PASCAL'S
House ACH50 302
3. COMBUSTION APPLIANCE DEPRESSURIZATION LIMITIf spillage susceptible = ‐5pa,
flow factor = 0.022 Depressurization Limit @ CEC pa 320if "other" appliance, limit =
for flow factor use chart at left Flow Factor 321
4. ALLOWABLE NET EXHAUST
cfm 322
5. ACTUAL NET EXHAUST TVCC Exhaust cfm 323‐ minus
cfm 324+ plus
cfm 325
cfm 325a
cfm 325b
IMBALANCE @ CEC (Critical Exhaust Condition)for systems with spillage susceptible combustion appliances
(total heated floor area including basement; count crawl space at 1/2 actual area)
Dryer Exhaust (default 150)
+ plus Large Exhaust Device over 150 cfm (a)
+ plus Large Exhaust Device over 150 cfm (b)
Floor Area (301) ________ ft2 x ACH50 (302) ________ x Flow Factor(321) ________ =
Allowable Net Exhaust @ CEC
manufacturer's rating = _____ pa
TVCC Supply
OTHER LIMIT = flow factor
‐5 to ‐10pa 0.022‐10 to ‐20pa 0.036‐20 to ‐30pa 0.059‐30 to ‐40pa 0.080‐40 to ‐50pa 0.101‐50 and over 0.143
Tight R‐2000 0.5 ACH Typical R‐2000 1.0 ACH Prairies/North (new) 1.0 ACHAtlantic (new) 1.5 ACH Other provinces (new) 1.4 ACH Older homes 2.5 ACHor actual test _________
cfm 325c= equals
cfm 326
6. REQUIRED MAKE‐UP AIR FLOW cfm
‐ minus cfm
= equals
cfm 327
pa
Required Not Required 328
Prepared By: HRAI #: Job Name:
Signature: Date: Job #: Official Use:
+ plus Large Exhaust Device over 150 cfm (c)
Allowable Net Exhaust @ CEC (line 322)
8. ON‐SITE TEST DEPRESSURIZATION TEST
7. DESCRIPTION OF MAKE‐UP AIR SYSTEM
Required Make‐Up Airflow @ CEC
@ Depressurization Limit (line 320)
(List devices over 150 CFM) Actual Net Exhaust @ CEC
Actual Net Exhaust @ CEC (line 326)Note:
If Actual Net Exhaustis less than AllowableNet Exhaust no action is required.
OTHER LIMIT = flow factor
‐5 to ‐10pa 0.022‐10 to ‐20pa 0.036‐20 to ‐30pa 0.059‐30 to ‐40pa 0.080‐40 to ‐50pa 0.101‐50 and over 0.143
Tight R‐2000 0.5 ACH Typical R‐2000 1.0 ACH Prairies/North (new) 1.0 ACHAtlantic (new) 1.5 ACH Other provinces (new) 1.4 ACH Older homes 2.5 ACHor actual test _________
© Copyright HRAI Residential Ventilation WORKSHEET W3‐C r 08/10
W‐4Aline #
1. EQUIPMENT Make:
Model:
2. LOW TEMPERATURE CORRECTION
401
402
403
x times
cfm 404
= equals
cfm 405
1. from map in the "Tables and Charts" section of the HRAI ventilation manual
2. lowest of supply or exhaust from HRV/ERV manufacturer spec sheet
3. from table in the "Tables and Charts" section of the HRAI ventilation manual
3. AIRFLOW ADJUSTMENT FACTOR
cfm 406
‐ minus
cfm
+ plus
cfm
= equals
cfm 406A
cfm
÷ divide by
cfm= equals
407
1) the GROSS SUPPLY AIRFLOW from HRV/ERV manufacturer spec sheet which
corresponds to the lowest NET SUPPLY AIRFLOW that meets or exceeds
the corresponding corrected ventilation rate from line 405
Prepared By: HRAI #: Job Name:
Signature: Date: Job #: Official Use:
Notes:
Temperature Zone (note 1)
Low Temperature Ventilation Reduction (note 2)
Low Temperature Adjustment Factor (note 3)
Total Ventilation Capacity (TVC from W‐2)
Net Supply Airflow
Total Ventilation Capacity (404)
Low Temperature Corrected Ventilation Rate (405)
Low Temperature Corrected Ventilation Rate
Adjusted Design Gross Supply Airflow
Adjusted Design Gross Supply Airflow (406A)
HRV AIRFLOW ADJUSTMENTS
Notes:
Design Gross Supply Airflow (note 1)
Airflow Adjustment Factor
© Copyright HRAI Residential Ventilation WORKSHEET W4‐A r 08/10
W‐4B
line #
1. HRV AIR DELIVERY TEMPERATURE
% 408
DT= °C 409
100
°C 410
Note: use formula above or HRV air delivery temperature chart found in the Tables and If HRV/ERV not used DT = ODT
Charts section of the HRAI ventilation manual.
2. PERCENTAGE HOUSE AIRcfm 411
RAF ‐ OAF cfm 412
RAF
% 413Note: use formula above or percentage
house air chart found in the Tables and Charts section of the HRAI ventilation manual
3. MIXED AIR TEMPERATURE
MAT= °C
%100
°C 414
Note: use formula above or mixed air temperature chart
found in the Tables and Charts section of the HRAI ventilation manual
4. PREHEATING
15.5 °C
‐ minus
°C
= equals °C
415
°C
x times
cfm
x times
0.57
Note: Preheater only required if mixed air temperature is below ‐15.5 °C = equals
watts 416
Prepared By: HRAI #: Job Name:
Signature: Date: Job #: Official Use:
Air Delivery Temperature (DT)
Outdoor Airflow (OAF) (Supply)
Return Airflow (RAF)
MIXED AIR TEMPERATURE ‐ FORCED WARM AIR SYSTEMS
Job Location:
HRV/ERV Apparent Sensible Effectiveness
Outdoor Design Temperature (ODT)
RAT ‐ [(RAT‐DT) x (100 ‐ %HA)]
TR = 15.5 ‐ MAT
Preheater = TR x RAF x 0.57
ODT + [(21 ‐ ODT) x %HRV/ERV eff.]
%HA = x 100
Temperature Rise (TR) (415)
Return Airflow (RAF) (412)
Preheater Size
Percentage House Air (%HA)
Air Delivery Temperature (DT) (410)
Percentage House Air (%HA) (413)
Mixed Air Temperature (MAT)
Temperature Rise (TR)
constant
Mixed Air Temperature (MAT) (414)
Minimum Mixed Air Temperature
Note: If TR (418) is a negative number no heater is required.
© Copyright HRAI Residential Ventilation WORKSHEET W4‐B r 08/10
W‐4C
line #
1. HRV AIR DELIVERY TEMPERATURE
% 408
°C 409
100
°C 410
Note: use formula above or HRV air delivery temperature chart found in the Tables and
Charts section of the HRAI ventilation manual.
2. HEATING
°C 417
‐ minus
°C
= equals
°C 418
°C
x times
cfm 419
x times
DELIVERED AIR TEMPERATURE ‐ DIRECT DUCTED SYSTEMS OR MAKE UP AIR SYSTEMS
DT=
Job Location
Outdoor Design Temperature (ODT)
HRV/ERV Apparent Sensible Effectiveness
TR = DDT ‐ DT
If HRV/ERV not used DT = ODT
Air Delivery Temperature (DT)
Desired Delivered Air Temperature (DDT)
Temperature Rise (TR) (418)
Air Delivery Temperature (DT) (410)
Temperature Rise (TR)
System Airflow (SAF)
ODT + [(21 ‐ ODT) x %HRV/ERV eff.]
Note: If TR (418) is a negative number no heater is required.
Delivered Air Temperatureminimums:
high wall diffusers = 12°Cfloor diffusers = 15.5°C
constant 0.57
= equals
watts 420
Heater Type HRV Postheater Direct outside air heater
Prepared By: HRAI #: Job Name:
Signature: Date: Job #: Official Use:
Heater = TR X SAF x 0.57 Heater Size
Delivered Air Temperatureminimums:
high wall diffusers = 12°Cfloor diffusers = 15.5°C
© Copyright HRAI Residential Ventilation WORKSHEET W4‐C r 08/10
W‐5
SYSTEM: Small capacity recirculation
DOOR
UNDERCUT
Supply Exhaust Exhaust Supply TYPE SIZE
(cfm) (cfm) (cfm) (cfm) (inches)
Column 1 2 3 5 7 9 10 11
TOTAL CFM
Prepared By: HRAI #: Job Name:
Signature: Date: Job #: Official Use:
ADJUSTED AIRFLOW
SYSTEM LAYOUT ‐ GRILLE SIZE ‐ DOOR UNDERCUTS
Balanced ventilation
Supply
(cfm)
4
Central Exhaust
(design airflow X col. 6)
6
AIRFLOW
ADJUST.
FACTOR
(line 407)
(cfm)
8
(as per system layout)
(type a or b)
ROOM NAME REQUIRED AIRFLOW GRILLE / DIFFUSERDESIGN AIRFLOW
AND TYPE (CSA F‐326 table 1)
Exhaust
© Copyright HRAI Residential Ventilation WORKSHEET W5 r 08/10
W‐6A1. EQUIPMENT 2. SYSTEM TOTAL EFFECTIVE LENGTH
Fan #. Actual Length Duct Run: ft
Make: Equivalent length outside hood: ft
Model : ft
ft
Design airflow: cfm ft
Equipment E.S.P.: "w.c. ft
ft
3. DUCT SIZE ft
ft
" dia.@ w.c. ft
Total Effective Length: ft
1. EQUIPMENT 2. SYSTEM TOTAL EFFECTIVE LENGTHFan #. Actual Length Duct Run: ft
Make: Equivalent length outside hood: ft
Model : ft
ft
Design airflow: cfm ft
Equipment E.S.P.: "w.c. ft
ft
3. DUCT SIZE ft
ft
" dia.@ w.c. ft
Total Effective Length: ft
Prepared By: HRAI #: Job Name:
Signature: Date: Job #: Official Use:
DUCT SIZING ‐ SINGLE DUCT
Sketch
Sketch
© Copyright HRAI Residential Ventilation WORKSHEET W‐6A r 08/10
DUCT SIZING ‐ BRANCHED SYSTEM1. EQUIPMENT 2. DESIGN CONDITIONS
Model: cfm
System: cfm
3. OUTSIDE DUCT RUN SIZING
Airflow: cfm Diameter in "w.c.
ft " w.c.
4. BRANCH DUCT SIZINGRun ID Run ID Run IDLocation Location LocationAirflow: cfm Airflow: cfm Airflow:
Actual Length Actual Length Actual Length
Elbows x __ Elbows x __ Elbows x __ Eff. Length ft Eff. Length ft Eff. LengthDiameter in Diameter in DiameterRect. Size x Rect. Size Rect. Size
Run ID Run ID Run IDLocation Location LocationAirflow: cfm Airflow: cfm Airflow:
Actual Length Actual Length Actual Length Actual Length
Elbows x __ Elbows x __ Elbows x __
Eff. Length ft Eff. Length ft Eff. LengthDiameter in Diameter in DiameterRect. Size x Rect. Size Rect. Size
5. TRUNK DUCT DESIGNTRUNK I.D.
cfm in x cfm in x cfm in x cfm in x cfm in x cfm in x
Prepared By: HRAI #: Job Name:
Signature: Date: Job #: Official Use:
EFFECTIVE LENGTH
x
x
ftin
x
Note: The available static pressure is to be used to select all duct sizes in the following sections 4 & 5
ft
ft
ft
DIAMETER
ft
ft
ft
ft
x
cfm cfm
ftin
x
Outside duct effective length
Design Airflow:
in. w.c. @
Elbows x __
Eff. Length
Run IDLocationAirflow:
DiameterRect. Size
cfm
AIRFLOW RECTANGULAR SIZE
Run IDLocationAirflow:
Actual Length
Elbows x __
Eff. Length
DiameterRect. Size
in
ftin
x
W‐6B
Pressure loss, outside duct:
Available static pressure:
cfm
Equipment E.S.P.:
© Copyright HRAI Residential Ventilation WORKSHEET W‐6B r 08/10
1. EQUIPMENT 3. TOTAL EFFECTIVE LENGTHFan: Make: ft
Model : ft
ft
Heater: Make: ft
Model : ft
ft
Design airflow cfm ft
ft
2. OPERATING POINT ft
Equipment ESP: " w.c. ft
minus ‐ ft
" w.c. ft
equals =
" w.c. 4. DUCT SIZE
DUCT SIZING ‐ POWERED INTAKE/MAKE‐UP AIR W‐6C
Actual Length Duct Run:
Equivalent length outside hood:
" w.c.
Sketch
" dia @:
Available static pressure:
Heater static pressure drop: Total Effective Length:
Prepared By: HRAI #: Job Name:
Signature: Date: Job #: Official Use:
© Copyright HRAI Residential Ventilation WORKSHEET W‐6C r 08/10
1. REQUIRED AIRFLOW 3. TOTAL EFFECTIVE LENGTH
ft
high ft
low ft
Airflow: cfm ft
ft
2. SUCTION PRESSURE ft
ft
ft
ft
ft
ft
high speed " w.c. ft
low speed " w.c. 4. INTAKE DUCT SIZE
highlow " w.c.
Sketch
DUCT SIZING ‐ FURNACE OUTSIDE AIR INTAKE W‐6D
"dia @: speed
System operating speedActual Length Duct Run: Equivalent length outside hood:
Total Effective Length:
Note: Use actual static pressure atconnection point if possible If pressure is unknown use .1 " w.c. for high speed and .05 in.w.c. for low speed
Prepared By: HRAI #: Job Name:
Signature: Date: Job #: Official Use:
Note: Use actual static pressure atconnection point if possible If pressure is unknown use .1 " w.c. for high speed and .05 in.w.c. for low speed
© Copyright HRAI Residential Ventilation WORKSHEET W‐6D r 08/10
W‐6E1. PRESSURE 3. TOTAL EFFECTIVE LENGTH
ft
Depressurization/pressurization ft
Pa. ft
ft
2. AIRFLOW ft
test ft
Pa. ft
ft
ft
cfm ft
ft
cfm Total Effective Length: ft
‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ OR ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ calculation 4. DUCT SIZE
form: W‐3A W‐3B W‐3C cfm w.c
Limit:
Sketch
DUCT SIZING ‐ PASSIVE MAKE‐UP / RELIEF AIR DUCT SIZING
Design airflow: " dia@:
depressurization at CEC
(pg 220 Manual) excessive flow factor
times x
net exhaust at CEC
equals =
Design airflow
Actual Length Duct Run:
Equivalent length outside hood:
Prepared By: HRAI #: Job Name:
Signature: Date: Job #: Official Use:
© Copyright HRAI Residential Ventilation WORKSHEET W‐6E r 08/10
VENTILATION DEVICE CONTROL STRATEGY CONTROL DEVICE
1.
2.
3.
4.
5.
6.
7.
Prepared By: HRAI #: Job Name:
Signature: Date: Job #: Official Use:
VENTILATION SYSTEM CONTROLS W‐7
© Copyright HRAI Residential Ventilation WORKSHEET W‐7 r 08/10
Note: This test is for code‐compliance of the ventilation system only.
1)cfm (L/s)
2)
cfm (L/s)
3)cfm (L/s)
4) Test to be carried out when house is substantially complete
cfm (L/s)
5)
cfm (L/s)
6)
cfm (L/s) Pa (a)
Pa (b)
Pa (c)
1. Pa (d)
Pa
2.
Pa (b) (a) = Pa (e)
3. (b) (d) = Pa (f)Pa Pa
4.
Pa
5. (c) (a) = Pa (g)Pa (c) (d) = Pa (h)
Pa
Pa
conforms does not conform
to the depressurization requirements of CSA F‐326 M91.
I CERTIFY THAT THE TEST HAS BEEN PERFORMED IN ACCORDANCE WITH THE TEST
PROCEDURE SET OUT IN CSA F326 M91 PARAGRAPH 11.2.2.a(i) AND 11.2.2b(i)
capacity
capacity
capacity
it must be simulated and the flow verified by flow measurement station
Note: If any exhaust equipment required to run at the CEC is not installed
Note: Wind conditions should be less than 15 km/h (9mph)
Largest of (g) or (h) = Dep. @ CEC
DEPRESSURIZATION @ TVCCminus
COMBUSTION APPLIANCES
TEST INSTRUMENT
Note: The test must be performed using an instrument capable of
Make:
Type:
Depressurization Limit
0.004 0.008 0.01 0.016
On at CEC?
On at TVCC? On at CEC?
On at TVCC? On at CEC?
On at TVCC? On at CEC?
On at TVCC? On at CEC?
On at TVCC?
Date of test:
Note:
Pressure @ TVCC
Pressure @ CEC
Ending "Rest" Pressure
Starting "Rest" Pressure
DEPRESSURIZATION @ CEC
minus
Note: Depressurization limit from left, but no more than 10 Pa.
Wind: km/h (mph)
DEPRESSURIZATION TEST REPORT
Postal Code:
Name:
0.04
TEST TESULTS
10 50
measuring 0 to 60 Pa. range with a sensitivity of 2 Pa.
TEST FIRM INFORMATION3 4 5
SEE OVER FOR PROCEDURE DESCRIPTION
MEASUREMENTSmm/dd/yy
minus
City:
Email Address:
Phone:
Address:
Fax:
P.C.
Name:
This is not a combustion system test or a back‐spillage test.
BUILDER/HOUSE
EXHAUST APPLIANCESDescribe All Exhaust Appliances House ID#:
capacity
capacity
Job Name: Job Number:
Name:
Address:
Tel: Fax:
HRAI Certification #:
Signature:
mm/dd/yyDate:
Tel:
Pa 1 2
Largest of (e) or (f) = Dep. @ TVCC
0.02 0.20in. w.c.
The dwelling unit and systems at the time of test:
minus
or equivelant
capacity On at TVCC? On at CEC?
Lowest Depressurization Limit
Depressurization Limit
Depressurization Limit
Depressurization Limit
Depressurization Limit
CERTIFICATION
© Copyright HRAI Residential Ventilation r 08/10