Concerning of Concerning of Cross Contamination Cross Contamination on AMC Controlon AMC Control
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
WhatWhat’’s Concerning on AMCs Concerning on AMC??
Exhaust / OA IntakeInteraction
Wind andWeather Characteristics
FAB Exterior
Online MonitoringOperation
Air Sampling as a baseAs Built
–Construction
Site SurveyWeather StudyAir SamplingCFD Simulation
Building Height EffectsChemical Filter Applications
Plan/Design
Required ConcerningStage
YieldYield
FAB Interior
Online Monitoring and Yield-Based TrendChemical Filter Applications
Operation
Air Sampling as a baseAs Built
Air Sampling for Tracing and as a baseConstruction
Tool Layout and Processes ReviewReview of Cleanroom Air Flow and Cross Contamination
Engineering JudgementCFD Aided Prediction
Review of Tool Partition
Plan/Design
Required ConcerningStage
2
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
WhatWhat’’s FAB Exterior Cross Contaminations FAB Exterior Cross Contamination??
Interactions between Buildings and Wind /
Weather Characteristics
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
Example in Science ParkExample in Science Park
Higher release of stripper from TFT/LCD FABs, that is, DMSO and MEA
Summer Time
Winter Time
• DMSO → DMS → SO2
• MEA → NH3
Waste water treatment plant
3
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
Validation by CFD and Site Sampling/AnalysisValidation by CFD and Site Sampling/Analysis
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
Effects of Cross ContaminationEffects of Cross Contamination
From others
Acidic smell
Solvent smellInteractions between Buildings and Wind /
Weather Characteristics
Lost of defect, profit and reputation
4
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
WhatWhat’’s FAB Interior Cross Contaminations FAB Interior Cross Contamination??
• Contamination between different processes, like Photo v.s. Wet, or Photo v.s. Diffusion….etc, due to special tool layout or w/wo isolation with air unbalance and mixing.
• Contamination between different tools, like outlet of vacuum pump v.s. process tools due to spreading of common return air shaft.
• Contamination between different sections inside the same tool itself due to bad air flow pattern control or ventilation design of tool.
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
Effects of Cross ContaminationEffects of Cross Contamination
Lost of defect, profit, throughput and health
無塵室回風道
Wet Etch
Stripper
Lens haze with MEA / Air-conditioner corrosion
Reticle haze
1
2
3
3
4 5
Films Defect
5
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
What are SolutionsWhat are Solutions??• To identify potential risk
– Traditional monitoring approach– Database aided approach– OP-FTIR systematic monitoring / diagnosis
approach
• Protection by air washer system in MAU– Traditional air washer system– L&K mist air washer system– L&K fan type air washer system
• Protection by chemical filter in MAU
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
Traditional Traditional MMonitoring onitoring AApproachpproach
• Only point monitoring, coverage limited
• Specific instrument for specific gases
• High initial cost if all points are required as online or quasi-online; but off-line measurement gathering if multi-point monitoring required
6
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
Database Database AAided ided AApproachpproachAfter data gathering, how and what could you do ?
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
Concentration Range(μg/m3)
Rel
ativ
e C
ontri
butio
n
MAU Common Chamber
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Concentration Range(μg/m3)
Rel
ativ
e C
ontri
butio
n
Photo Area
A database for comparison and benchmarking
0
0.05
0.1
0.15
0.2
0.25
Concentration Range(μg/m3)
Rel
ativ
e C
ontri
butio
n
Outside Air
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
Applications of Applications of OPOP--FTIRFTIR
• Line monitoring, wider coverage
• High diversity for gases detection with acceptable limit
• Real time monitoring available
SourceWind Direction
7
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
Why and How to Be SystematicWhy and How to Be Systematic??Tool Exhaust Trace Gas LibraryDue to long term of tools’ local scrubber efficiency measurement, a tool exhaust trace gas library is already set up for different tools and processes.
Photo
Etch
Thin-film
Diffusion
Make-up air
Return Shaft Monitoring
OA Monitoring
Spectrum Analysis
Spectrum Analysis Concentration Comparison between OA and Return Shaft
Return Shaft>
OA
No
Contaminants come from outside air
Database Searching and Comparison
0
2
4
6
8
10
12
14
16
00:00 12:00 00:00 12:00 00:00 12:00 00:00 12:00 00:00
Time of Day
Con
cent
rati
on /
PPB
SIH4
Time History Data
Tool Operation
History
Identification of Suspected Tools
CF4SiF4
Portable FTIR to zero-in
Yes
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
Air Washer System in MAUAir Washer System in MAU
0.788/yr/CMH0.03108 W/CMH0.0139 W/CMHL&K Fan Type Air Washer
Total = 5.4kWFor 1 year 8760hrs47304 kWh costs﹩94608/yr
5HP @ 7.2m3/hrPower consumption @ 120000CMH:3.73kW
40Pa for air sidePower consumption @ 120000CMH:1.67kW
L&K Fan Type Air Washer
3.483/yr/CMH0.15542 W/CMH0.0434 W/CMHTraditional Air Washer
0.679/yr/CMH0.02487 W/CMH0.0139 W/CMHL&K Mist Type Air WasherBenchmark Reference
-
Nozzle Type
Electric Rate:NTD 2.0/kWh
-Fan Static Efficiency 80%-Calculation
Assumption
Total = 23.858kWFor 1 year 8760hrs208996 kWh costs﹩417992/yr
25HP @ 144m3/hrPower consumption @ 120000CMH:18.65kW
125Pa for air sidePower consumption @ 120000CMH:5.208kW
Traditional Air Washer
Total = 4.654kWFor 1 year 8760hrs40769 kWh costs﹩81538/yr
4HP @ 7.2m3/hrPower consumption @ 120000CMH:2.984kW
40Pa for air sidePower consumption @ 120000CMH:1.67kW
L&K Mist Type Air Washer
Operation CostPump Power Consumption (kW)
Air Side Energy Consumption (kW)
Picture Overview
ItemSystem
8
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
What Special for L&K Air WasherWhat Special for L&K Air Washer??
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
Basic L&K Air Washer Performance Basic L&K Air Washer Performance
Air Washer Air Side Pressure Drop Curve
0
10
20
30
40
1 1.2 1.4 1.6 1.8 2 2.2 2.4
Packing Material Face Velocity (m/sec)
Air W
ashe
r Air
Side
Pre
ssur
e Dro
p (P
a)
Air Washer Saturation Efficiency
90
92
94
96
98
100
1 1.5 2 2.5
Packing Material Face Velocity (m/s)
Air W
ashe
r Sat
urtio
n Ef
ficien
cy (%
)
The basic air washer performance data of humidifying efficiency and air side pressure was measured and correlated as follows,
For conservative concern, a 90% saturation efficiency will be used for air washer design.
The air side pressure drop will be smaller than 40Pa at normal design conditions.
9
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
Chemical Removal EfficiencyChemical Removal Efficiency
Type IIType I
33.342.286.1NO3−
321Row of Nozzles1.170.50.05Liquid/Gas Mass Ratio
80.831.297.9NH4+Alkali
91.183.794.7SO42−
—85.291.2NO2−
49.937.342.9Cl-—67.450.2F-
AcidChemical Removal
Efficiency (%)
Traditional Air WasherL&KAir
WasherSystem
Item
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
Patent No.No. 209075, M325160( Taiwan )No. 02242481.4,ZL200720000460.X ( China )
What Special for L&K Fan Type Air WasherWhat Special for L&K Fan Type Air Washer??
10
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
Chemical Removal EfficiencyChemical Removal Efficiency
DownstreamUpstream
ND68.2 -ND>94.8ND87.9 >95.9>92.3Removal Efficiency (%)ND46.67 NDNDNDND0.63 NDNDND146.9 0.79 ND8.52 ND5.17 1.92 0.81 MAU01
2008/10/06
MEANH4+Na+SO4
2-PO43-NO3
-NO2-Cl-F-Description
Unit: μg/m3
DownstreamUpstream
ND74.6 -ND>92.7>84.694.1 >99>92.2Removal Efficiency (%)ND50.71 21.94 NDNDND0.43 NDNDND199.49 13.94 ND6.03 0.38 7.29 8.45 0.80 MAU02
2008/10/06
MEANH4+Na+SO4
2-PO43-NO3
-NO2-Cl-F-Description
DownstreamUpstream
ND30.0 -94.2 ND>98.675.0 >96.4>92.3Removal Efficiency (%)ND12.36 ND0.69 NDND0.19 NDNDND17.65 0.82 11.95 ND5.70 0.77 2.87 1.07 MAU01
2008/11/03
MEANH4+Na+SO4
2-PO43-NO3
-NO2-Cl-F-Description
DownstreamUpstream
ND56.4 -93.4 ND65.5 >87.259.2 -Removal Efficiency (%)ND7.10 0.68 0.67 ND0.44 ND0.62 NDND16.29 0.43 10.20 ND1.29 0.96 1.51 NDMAU02
2008/11/03
MEANH4+Na+SO4
2-PO43-NO3
-NO2-Cl-F-Description
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
The Situation If Chemical Filter on FFU OnlyThe Situation If Chemical Filter on FFU Only
90% Removal Efficiency
20μg/m3 Inlet
11.3806μg/m3
10.9143μg/m3
1.0003μg/m3
9.8921μg/m3
9.8851μg/m3
MAU Outlet 0.2μg/m3
If outside air increases up to 200μg/m3 suddenly ﹖
The critical roomstill 1.0003μg/m3 ﹖
2.7374μg/m3
The concentration still fluctuates, even chemical filter has been installed
on critical room
11
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
WhatWhat’’s the Solution s the Solution ﹖﹖Install Chemical Filter On MAU
﹖
What will you do if outside air continues keeping a low level ?
What will you do if outside air increases up but the chemical filter installed on MAU just reach the end life ?
And more, why do you lose the energy just for
unpredictable outside air ?
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
WhatWhat’’s the L&K Solution s the L&K Solution ﹖﹖
Damper 1
Damper 2
Damper 3
Monitor Point
A Ducted Chemical Filter Unit Ducted Chemical Filter Unit (DCFU)(DCFU) will be installed on the end of OA duct and three dampers operate the correct position via the information from the monitor point.
Chemical Filter
Patent No.
No. I295721( Taiwan, ROC )No. 200610087018.5(China)
12
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
How Does It Work How Does It Work ﹖﹖
Damper 1
Damper 2
Damper 3
Monitor Point
Chemical Filter
Normal ConditionNormal Condition
OA concentration is lower than set point
Damper 1 → OpenOpenDamper 2 → CloseDamper 3 → CloseFan → Off
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
How Does It Work How Does It Work ﹖﹖
Damper 1
Damper 2
Damper 3
Monitor Point
Chemical Filter
Abnormal ConditionAbnormal Condition
OA concentration is higher than set point
Damper 1 → CloseDamper 2 → OpenOpenDamper 3 → CloseCloseFan → OnOn
13
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
How Does It Work How Does It Work ﹖﹖
Damper 1
Damper 2
Damper 3
Monitor Point
Chemical Filter
Chemical Spill in CRChemical Spill in CR
Some accident of chemicals spilled in cleanroom
Damper 1 → OpenOpenDamper 2 → CloseDamper 3 → OpenOpenFan → OnOn
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
Case StudyCase Study
The difference of air volume distribution
and pressure drop are very small for w. and
wo DCFU.
14
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
Conclusions (I)Conclusions (I)
Cross contamination is a prevalent phenomena in FAB exterior and interior.
It will bring losses to FAB operation accompanying the shrink of device critical dimension.
A new application of FTIR combined with process trace gas database is proposed for such new era of semiconductor manufacturing.
The application of air washer in MAU already becomes a standard requirement for semiconductor and TFT industry. And a new design concept of air washer also proposed for better chemical removal efficiency and lower power consumption.
Confidential, unpublished property of L&K. Do not duplicate or distribute© L&K Engineering Co., Ltd. 2009
Conclusions (II)Conclusions (II)
Finally, another patented concept of chemical filter applications in MAU is also proposed for economical and effective usage of chemical filters in MAU.