condair cp3 - australianvs.com.au

80
TECHNICAL DOCUMENTATION Electrode Humidifiers 2529291 EN 0807 Condair CP3

Upload: others

Post on 08-Feb-2022

14 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: condair cP3 - australianvs.com.au

Technical DocumenTaTion

electrode humidifiers

2529

291

en

080

7

condair cP3

Page 2: condair cP3 - australianvs.com.au
Page 3: condair cP3 - australianvs.com.au

1 Introduction 41.1 Totheverybeginning 41.2 Notesonthetechnicaldocumentation 4

2 Foryoursafety 6

3 ProductOverview 83.1 Modelsoverview 83.2 Identificationoftheunit 93.3 Steamhumidifierconstruction 103.4 Functionaldescription 113.5 Humidificationsystemoverview 123.6 Overviewunitinterconnection 133.7 Options 143.7.1 Optionsoverview 143.7.2 Optiondetails 153.8 Accessories 163.8.1 Accessoriesoverview 163.8.2 Accessorydetails 173.9 Standarddelivery 183.10 Storing/Transportation/Packaging 18

4 Notesfortheplanningengineer 194.1 Selectingtheunitversion 194.1.1 Calculatingthemaximumrequiredsteamcapacity 194.1.2 Selectingtheunit 204.2 Selectingtheoptionsanaccessories 204.3 Selectingthecontrolsystem 21

5 Mountingandinstallationwork 245.1 Importantnotesformountingandinstallationwork 245.2 Installationoverview 255.3 Mountingtheunit 265.3.1 Notesonlocatingtheunit 265.3.2 Mountingthehumidifier 285.3.3 Inspectingtheinstalledunit 295.4 Steaminstallation 305.4.1 Overviewsteaminstallation 305.4.2 Positioningandmountingofthesteamdistributionpipes 315.4.3 Installingthesteamdistributors 345.4.4 Positioningandmountingofthefanunit 355.4.5 Installingthesteamhose 365.4.6 Installingthecondensatehose 375.4.7 Inspectingthesteaminstallation 385.5 Waterinstallation 395.5.1 Overviewwaterinstallation 395.5.2 Notesonwaterinstallation 405.5.3 Inspectingthewaterinstallation 415.6 Electricinstallation 425.6.1 WiringdiagramCondairCP3Basic/Pro 425.6.2 WiringdiagramLinkUpsystems 435.6.3 FusesF3forheatingvoltagesupply 445.6.4 InsertingtheCP3Card 455.6.5 Notesonelectricinstallation 455.6.6 Inspectingtheelectricalinstallation 45

6 Operation 466.1 Commissioning 466.2 Notesonoperation 476.2.1 Functionofthedisplayandoperatingelements 476.2.2 Remoteoperatingandfaultindication 476.2.3 Inspectionsduringoperation 486.2.4 Carryingoutmanualdraining 486.3 Takingtheunitoutofoperation 486.4 Overviewandoperatingofthemenu 496.5 Interrogationfunctions 506.5.1 Interrogationoftheoperatinginformation

intheindicationlevel 506.5.2 Interrogationofunitinformation 516.5.3 Interrogationofthemalfunctionlist 526.6 Unitsettings 536.6.1 Launchingtheunitsettingsmenu 536.6.2 Selectingthedialoguelanguage 536.6.3 Controlsettings 536.6.4 Cylindersettings 556.6.5 Settingthecapacitylimitation 566.6.6 ConfiguringtheOn/Offtimer 576.6.7 Activating/Deactivatingfaultcurrentrelayoperation 576.6.8 Settingtheoperationmodeformultipleunits 586.6.9 Watermanagementsettings 586.6.10 Performingremoterelaytests 596.6.11 Settingthedate 596.6.12 Settingthetime 596.6.13 Settingthedisplaycontrast 606.7 Modbussettings 60

7 Maintenance 617.1 Importantnotesonmaintenance 617.2 Maintenancelist 627.3 Removingandinstallingpartsformaintenance 637.3.1 Removalandinstallationofthesteamcylinder 637.3.2 Disassemblyandassemblyof

thecleanablesteamcylindertypeD... 657.3.3 Removalandinstallationofthewatercup

andthewaterhoses 667.3.4 Removalandinstallationofthedrainpump 677.3.5 Removalandinstallationoftheinletvalve 677.4 Notesoncleaningtheunitcomponents 687.5 Notesoncleaningagents 697.6 Resettingthemaintenanceindication 70

8 Malfunctions 718.1 Malfunctionlist 718.1.1 Systemfaults 718.1.2 Unitfaults 728.2 Notesonfaultelimination 748.3 Resettingtheerrorindication(redLEDlights) 74

9 Takingoutofservice/Disposal 759.1 Takingoutofservice 759.2 Disposal/Recycling 75

10 Productspecifications 7610.1 Technicaldata 7610.2 Unitdimensions 77

Contents

Page 4: condair cP3 - australianvs.com.au

Limitation

The subject of this technical documentation is the steam humidifier Condair CP3 in its ver-sions “Basic” and “Pro”. The various accessories (e.g. steam distributor, steam distribution system, etc.) are only described insofar as this is necessary for proper operation of the equipment. Further information on accessories can be obtained in the respective instructions.

This technical documentation is restricted to the installation, commissioning, operation, servicing and trouble shooting of the steam humidifier Condair CP3 and is meant for well trained personnel being sufficiently qualified for their respective work.

The technical documentation is supplemented by various separate items of documentation (spare parts list, manuals for accessories, etc.). Where necessary, appropriate cross-references are made to these publications in the technical documentation.

1 Introduction

We thank you for having purchased the steam humidifier Condair CP3.

The steam humidifier Condair CP3 incorporates the latest technical advances and meets all recog-nized safety standards. Nevertheless, improper use of the Condair CP3 may result in danger to the user or third parties and/or impairment of material assets.

To ensure a safe, proper, and economical operation of the steam humidifier Condair CP3, please observe and comply with all information and safety instructions contained in the present technical documentation as well as the instructions given in the manuals for the components used in the humidification system.

If you have questions, which are not or insufficiently answered in this documentation, please contact your Condair supplier. They will be glad to assist you.

1.2 Notes on the technical documentation

1.1 To the very beginning

Page 5: condair cP3 - australianvs.com.au

Symbols used in this manual

CAUTION!The catchword “CAUTION” designates notes in this technical documentation that, if neglected, may cause damage and/or malfunction of the unit or other material assets and/or may lead to injury to persons.

WARNING!

The catchword “WARNING” used in conjunction with the general caution symbol designates safety and danger notes in this technical documentation that, if neglected, may lead to severe injury or even lethal violation of persons.

Safekeeping

Please safeguard this technical documentation in a safe place, where it can be immediately accessed. If the equipment changes hands, the documentation should be passed on to the new operator.

If the documentation gets mislaid, please contact your Condair supplier.

Language versions

This technical documentation is available in various languages. Please contact your Condair supplier for information.

Copyright protection

The present technical documentation is protected under the Copyright Act. Passing-on and reproduc-tion of the manual (or part thereof) as well as exploitation and communication of the contents are prohibited without written permission by the manufacturer. Violation of copyright terms is subject to legal prosecution and arises liability for indemnification.

The manufacturer reserves the right to fully exploit commercial patent rights.

Page 6: condair cP3 - australianvs.com.au

2 For your safety

General

Every person working with the Condair CP3 must have read and understood the Technical Docu-mentation before carrying out any work.Knowing and understanding the contents of the Technical Documentation is a basic requirement for protecting the personnel against any kind of danger, to prevent faulty operation, and to operate the unit safely and correctly.

All ideograms, signs and markings applied to the unit must be observed and kept in readable state.

Qualification of personnel

All actions described in the present Technical Documentation (installation, operation, maintenance, etc.) must be carried out only by well trained and sufficiently qualified personnel authorised by the owner.For safety and warranty reasons any action beyond the scope of this manuals must be carried out only by qualified personnel authorised by the manufacturer.

It is assumed that all persons working with the Condair CP3 are familiar and comply with the ap-propriate regulations on work safety and the prevention of accidents.

Intended use

The steam humidifier Condair CP3 is intended exclusively for air humidification via a steam dis-tributor or a ventilation unit approved by the manufacturer within the specified operating conditions (see chapter 10 “Product specifications”). Any other type of application without the express written consent of the manufacturer is considered as not conforming with the intended purpose and may lead to the Condair CP3 becoming dangerous.Operation of the equipment in the intended manner requires that all the information in these instructions is observed (in particular the safety instructions).

Page 7: condair cP3 - australianvs.com.au

Danger that may arise from the unit

– The Condair CP3 is mains powered.

WARNING!

One may get in touch with live parts when the unit is open. Touching live parts may cause severe injury or danger to life.

Prevention: Before carrying out any work set the Condair CP3 out of operation as described in chapter 6.3 (switch off the unit, disconnect it from the mains and stop the water supply) and secure the unit against inadvertent power-up.

– The Condair CP3 produces steam. When producing steam, the steam cylinder inside the humidifier gets very hot (up to 100 °C).

WARNING!

If the unit is opened immediately after having produced steam there is danger of burning when touching the steam cylinder.

Prevention: Before carrying out any work set the Condair CP3 out of operation as de-scribed in chapter 6.3, then wait until the evaporation unit has cooled down sufficiently thus preventing danger of burning.

Behaviour in case of danger

If it is suspected that safe operation is no longer possible, then the Condair CP3 should imme-diately be shut down and secured against accidental power-up according to chapter 6.3. This can be the case under the following circumstances:– if the Condair CP3 or its mains cable is damaged– if the Condair CP3 is no longer operating correctly– if connections and/or piping are not sealed

All persons working with the Condair CP3 must report any alterations to the unit that may affect safety to the owner without delay.

Prohibited modifications to the unit

No modifications must be undertaken on the Condair CP3 without the express written consent of the manufacturer.

For the replacement of defective components use exclusively original accessories and spare parts available from your Condair supplier.

Page 8: condair cP3 - australianvs.com.au

3 Product Overview

3.1 Models overview

Steam air humidifiers Condair CP3 are available in the versions “Basic" and “Pro” with different heating voltages and steam capacities ranging from 5 kg/h up to a max. of 180 kg/h.

Heatingvoltage* Max.steamcapacityinkg/h

Graduationinkg/h

ModelCondairCP3 Unitsize/Numberofunits

Basic... Pro... Singleunitsmall

Singleunitlarge

Doubleunitlarge

400V3(400V/3~/50...60Hz)

5...15 1 5...15 5...15 116...45 1 16...45 16...45 1

52 -- 52 52 160 -- 60 60 170 -- 70 70 180 -- 80 80 190 -- 90 90 1

105** -- -- 105 1 1120** -- -- 120 1 1135** -- -- 135 1 1152** -- -- 152 2160** -- -- 160 2180** -- -- 180 2

230V3(230V/3~/50...60Hz)

5...15 1 5...15 5...15 116...30 1 16...30 16...30 1

44 -- 44 44 150 -- 50 50 160 -- 60 60 1

75** -- -- 75 1 190** -- -- 90 1 1

100** -- -- 100 2120** -- -- 120 2

230V1(230V/1~/50...60Hz) 5...8 1 5...8 5...8 1

* Otherheatingvoltagesonrequest** LinkUpsystems

Key model designation

Example:Condair CP3 Pro 45 400V3

Unit Version: Pro Basic

Maximum steam capacity in kg/h:

Heating voltage:00V/3~/0...0Hz: 400V3230V/3~/0...0Hz: 230V3230V/1~/0...0Hz: 230V1

Page 9: condair cP3 - australianvs.com.au

Walter Meier (Climate International) Ltd. 8808 Pfäffikon

Made in Switzerland

Condair CP3 Pro 45

Dampf/Steam/Vapeur = 45.0 kg/hWasser/Water/Eau = 1...10 bar

Wechselstrom ACMain Unit / Modul A

400V 3~ / 50...60Hz 33.8 kWXXXXXXX 11.06

3.2 Identification of the unit

The identification of the unit is found on the type plate (for the location of the type plate see unit overview):

Type designation Serial number ( digits) Month/Year

Unit voltage (heating voltage)

Maximum steam capacity per unit

Admissible water supply pressure

Operation note

Unit designation

Total steam capacity in kg/h

Page 10: condair cP3 - australianvs.com.au

10

3.3 Steam humidifier construction

1 Housing (small, large) 2 Cable openings, top side 3 Main contactor Power board Control board with CP3 Card Display and control unit Remote operating and fault indication board Operation status indicators Cable openings, bottom side 10 Drain key 11 Unit switch 12 Steam outlet 13 Water cup

1 Filling hose 1 Water supply hose 1 Inlet valve 1 Overflow hose 1 Drain connection (not visible) 1 Water supply pipe 20 Drain pump 21 Type plate 22 Data plate CP3 Card 23 Steam cylinder 2 Level sensor 2 Auxiliary drain hose 2 Electrode plug

The illustration above shows the large unit

1

12

13

15

14

17

16

19

18

2021

22

23

25

26

24

2

3

7

4

5

6

8

11

10

9

Page 11: condair cP3 - australianvs.com.au

11

3.4 Functional description

The steam humidifier Condair CP3 is a pressureless steam generator that utilizes an electrode heating. The steam humidifier Condair CP3 is designed for air humidification via a steam distributor (steam distribution pipe, ventilation unit or steam distribution system OptiSorp).

Steam generation

Any time steam is requested, the electrodes are supplied with voltage via main contactor. Simulta-neously, the inlet valve opens and water enters the steam cylinder from the bottom via water cup and supply line. As soon as the electrodes come in contact with the water, current begins to flow between the electrodes, eventually heating and evaporating the water. The more the electrode surface is exposed to water, the higher is the current consumption and thus the steam capacity.Upon reaching the requested steam capacity, the inlet valve closes. If the steam generation de-creases below a certain percentage of the required capacity, due to lowering of the water level (e.g. because of the evaporation process or drainage), the inlet valve opens until the required capacity is available again.If the required steam capacity is lower than the actual output, the inlet valve is closed until the de-sired capacity is achieved by lowering of the water level (evaporation process).

Level monitoringA sensor provided in the steam cylinder cover detects when the water level gets too high. The mo-ment the sensor comes in contact with water, the inlet valve closes.

DrainageAs a result of the evaporation process, the conductivity of the water increases due to an escalating mineral concentration. Eventually, an inadmissibly high current consumption would take place if this concentration process were permitted to continue. To prevent this concentration from reaching a value, unsuitably high for the operation, a certain amount of water is periodically drained from the cylinder and replaced by fresh water.

Control

The steam production can be controlled steplessly via the internal or an external continuous control-ler or with an On/Off control via an external humidistat.

Page 12: condair cP3 - australianvs.com.au

12

3.5 Humidificationsystemoverview

1 Steamhumidifier 2 Steamconnection 3 Waterdrainconnection 4 Watersupplyconnection 5 Filtervalve(accessory“Z261”) 6 Manometer(installationrecommended) 7 Funnelwithsiphon(buildingside) 8 Waterdrainhose(accessory“DS80”

9 Controlvoltagesupply10 Heatingvoltagesupply11 Cableopenings12 Steamhose(accessory“DS..”)13 Condensatehose(accessory“KS10”)14 Steamdistributionpipe (accessory“41-..”/“61-..”/“81-..”)15 Ventilationunit(accessory“FAN...”)

DS808

7

9

10

125...1250 µS/cm1...10 bar1...40 °C

1

2

3

4

5

6

Z261

14 12

11

KS10

61-..

41-..

81-..

DS60

DS80

15FAN B15

FAN B45

FAN P15

FAN P45

13

Basic Pro

DS60

DS22

DS80

Page 13: condair cP3 - australianvs.com.au

13

3.6 Overview unit interconnection

Single unit

CP3 ... 45

I/O

CP3 ... 135

I/O I/O

CP3 ... 90

I/O

Mainunit,ModuleA(CP3...45)

Pow

erb

oard

Controlboard

Heatingvoltage

Controlvoltage

Controlsignal

RemoteindicationRFI

Mainunit,ModuleB(CP3...45)

Pow

erb

oard

Heatingvoltage

Mainunit,ModuleA(CP3...45)

Controlboard

Pow

erb

oard

Ribboncable

Heatingvoltage

Controlvoltage

Controlsignal

RemoteindicationRFI

Mainunit,ModuleB(CP3...45)

Pow

erb

oard

Heatingvoltage

Mainunit,ModuleA(CP3...45)

Controlboard

Pow

erb

oard

Ribboncable

Heatingvoltage

Controlvoltage

Controlsignal

RemoteindicationRFI

Extensionunit,ModuleA(CP3...45)

Controlboard

Pow

erb

oard

Buscablemax.50m

Heatingvoltage

Controlvoltage

Double unit

Double unit + single or double unit (Link Up system, Pro version only)

Page 14: condair cP3 - australianvs.com.au

1

3.7 Options

3.7.1 Options overview

CondairCP3Basic.../CondairCP3Pro...

230V1 5...8

400V3 5...8 9...15 16...45 52/60/70/80/90 105/120/135 152/160/180

230V3 5...8 9...15 16...30 44/50/60 75/90 100/120

D... CleanablesteamcylinderCleanablesteamcylinderasanalternativetothedisposablesteamcylinderbuiltinasstandard(seealsochapter3.7.2).

P/B 1xD3.. 1xD4.. 1xD6.. 2xD6.. 3xD6.. 4xD6..

RFI RemoteoperatingandfaultindicationPCBwithrelaycontactsfortheconnec-tionofremotedisplaysfor“Operation”,“Steam”,“Fault”and“Service”.

B* 1xRFI 1xRFI 1xRFI 1xRFI 1xRFI 1xRFI

OPS OverpressuresetKit formounting thewater cup to theunitcoverwhenoperatingthesteamhumidifiersin systems with a duct air pressure of upto10kPa.

P/B 1xOPS 1xOPS 1xOPS 2xOPS 3xOPS 4xOPS

THV TerminalsheatingvoltageSeparateterminalsforsystemswheredirectconnectionofheatingvoltagetomaincontac-tor(standardversion)isnotpermittedbylocalregulations.

B* 1xM-THV 1xM-THV 1xL-THV 2xL-THV 3xL-THV 4xL-THV

PG Cablegland P/B 1xPG 1xPG 1xPG 2xPG 3xPG 4xPG

INOX Unitfrontcovermadeofstainlesssteel P/B 1xM-INOX 1xM-INOX 1xL-INOX 2xL-INOX 3xL-INOX 4xL-INOX

SC.. Steamhoseconnector B* 1xSC22 1xSC60 1xSC80 2xSC80 3xSC80 4xSC80

SCCT.. Steamhoseconnectorwithcondensatetrap

B 1xSCCT22 1xSCCT60 1xSCCT80 2xSCCT80 3xSCCT80 4xSCCT80

CT Condensatetrap P/B 1xCT 1xCT 1xCT 2xCT 3xCT 4xCT

MP Mountingprofile P/B 1xMP 1xMP 1xMP 2xMP 3xMP 4xMP

CVI Internalcontrolvoltage P/B 1xM-CVI 1xM-CVI 1xL-CVI 1xL-CVI** 2xL-CVI 2xL-CVI

TRAFO Transformer(400V/230V) P/B 1xM-Trafo 1xM-Trafo 1xL-Trafo 1xL-Trafo** 2xL-Trafo 2xL-Trafo

B UnitversionBasicP UnitversionPro* StandardforunitversionPro** UnitversionBasicrequiresadditionallyoptionTHVforunitmoduleB

Page 15: condair cP3 - australianvs.com.au

1

3.7.2 Option details

Steam cylinder

The steam humidifier is available with two different types of steam cylinders:

– Exchangeable steam cylinder type A... (standard version)

– Cleanable steam cylinder type D... (option)

The following tables present an overview of the steam cylinders used in the different models.

CondairCP3...400V3 5...8 9...15 16...25 26...45 52/60/70/80/90 105/120/135 152/160/180

Forwaterconductivityfrom125to1250µS/cm

Exchangeablesteamcylinder 1xA363 1xA464 1xA674 1xA664 2xA664 3xA664 4xA664

Cleanablesteamcylinder 1xD363 1xD464 1xD674 1xD664 2xD664 3xD664 4xD664

Forlowwaterconductivity

Exchangeablesteamcylinder 1xA343 1xA444 1xA654 1xA654 2xA654 3xA654 4xA654

Cleanablesteamcylinder 1xD343 1xD444 1xD654 1xD654 2xD654 3xD654 4xD654

CondairCP3...230V3 5...8 9...15 16...21 22...30 44/50/60 75/90 100/120

Forwaterconductivityfrom125to1250µS/cm

Exchangeablesteamcylinder 1xA343 1xA444 1xA654 1xA644 2xA644 3xA644 4xA644

Cleanablesteamcylinder 1xD343 1xD444 1xD654 1xD674 2xD674 3xD674 4xD674

CondairCP3...230V1 5...8

Forwaterconductivityfrom125to1250µS/cm

Exchangeablesteamcylinder 1xA342

Cleanablesteamcylinder 1xD342

If you have questions regarding the steam cylinders please contact your Condair representative.

Page 16: condair cP3 - australianvs.com.au

1

3.8 Accessories

3.8.1 Accessories overview

Accessories for water installation

CondairCP3Basic.../CondairCP3Pro...

230V1 5...8

400V3 5...8 9...15 16...45 52/60/70/80/90 105/120/135 152/160/180

230V3 5...8 9...15 16...30 44/50/60 75/90 100/120

Filtervalve Z261(1pcs.persystem)

Accessories for steam installation

CondairCP3Basic.../CondairCP3Pro...

230V1 5...8

400V3 5...8 9...15 16...45 52/60/70/80/90 105/120/135 152/160/180

230V3 5...8 9...15 16...30 44/50/60 75/90 100/120

Steamdistributionpipe(Detailsseechapter3.8.2)

1x41-... 1x61-... 1x81-... 2x81-... 3x81-... 4x81-...

Steam distribution system OptiSorp(Detailsseechapter3.8.2)

––– System1 System2 System3 System4

Fanunit(Detailsseechapter3.8.2)

Basic 1xFANB15 1xFANB45 2xFANB45 3xFANB45 4xFANB45

Pro 1xFANP15 1xFANP45 2xFANP45 3xFANP45 4xFANP45

Steamhose/meter 1xDS22 1xDS60 1xDS80 2xDS80 3xDS80 4xDS80

Condensatehose/meter 1xKS10 2xKS10 3xKS10 4xKS10

Accessories for humidity control

CondairCP3Basic.../CondairCP3Pro...

230V1 5...8

400V3 5...8 9...15 16...45 52/60/70/80/90 105/120/135 152/160/180

230V3 5...8 9...15 16...30 44/50/60 75/90 100/120

Humiditysensorforductinstallation EGH110(1pcs.persystem)

Humiditysensorforroominstallation EGH130(1pcs.persystem)

Ducthumidistat HBC(1pcs.persystem)

Roomhumidistat HSC(1pcs.persystem)

Page 17: condair cP3 - australianvs.com.au

1

The steam distribution pipes are selected on the basis of the duct width (for horizontal installation) or the duct height (for vertical installation) and the capacity of the steam humidifier.Important! Always select the longest possible steam distribution pipe (optimum humidification distance).

3.8.2 Accessory details

3.8.2.1 Steam distribution pipe 41-.../61-.../81-...

3.8.2.2 OptiSorp steam distribution system

The OptiSorp steam distribution system is used in ventilation ducts with a short humidification distance (for the calculation of the humidification distance refer to chapter ..2). When ordering an OptiSorp system the duct dimension must be specified. Please consult the data in the following table.

SteamdistributionpipesforCondairCP31)

Length(L)steamdistributionpipe

Ductwidth(B)

Type41-.. Type61-.. Type81-.. inmm2) inmm

41-200 200 210...40041-350 61-350 81-3503) 350 400...60041-500 61-500 81-5003) 500 550...75041-650 61-650 81-650 650 700...90041-800 61-800 81-800 800 900...110041-1000 61-1000 81-1000 1000 1100...130041-1200 61-1200 81-1200 1200 1300...1600

61-1500 81-1500 1500 1600...2000 61-1800 81-1800 1800 2000.2400 61-2000 81-2000 2000 2200...2600 81-2300 2300 2500...2900 81-2500 2500 2700...3100

1)Material:CrNisteel 3)uptomax.30kg/hsteamcapacity2)speciallengthonrequest

Note: If the humidification distance (see chapter ..2) has to be reduced for technical reasons, the amount of steam per basic unit must be divided between two steam distribution pipes or the steam distribution system OptiSorp must be used. If this is the case, contact your Condair supplier.

OptiSorp Numberofsteamconnectors

Max.steamcapacityinkg/h1)

DuctdimensionsWidthinmm Heightinmm

System1 1 45(30) 450-2700 450-1650

System2 2 90(60) 450-2700 450-2200

System3 3 135(90) 450-2700 800-3200

System4 4 180(120) 450-2700 800-3200

1)Forductwidths<600mmthevaluesinbracketsapply

Page 18: condair cP3 - australianvs.com.au

1

3.9 Standard delivery

The standard delivery includes:

– Steam humidifier Condair CP3 equipped with the options ordered according to chapter 3., fixing set and Technical Documentation (this document), packaged in cardboard box– Unit small (WxHxD): 0 mm x 20 mm x 20 mm, shipping weight: 2 kg– Unit large (WxHxD): mm x mm x 30 mm, shipping weight: 31 kg

– Ordered accessories with operating instructions according chapter 3., packed separately

– Spare parts list

3.10 Storing/Transportation/Packaging

Storing

Store the unit in a protected area meeting the following requirements:

– Room temperature: 1 ... 0 °C– Room humidity: 10 ... %rh

Transportation

For optimum protection always transport the unit in the original packaging.

The weight of the small and the large unit is more than 20 kg (weight without packaging: small unit 23 kg, large unit 2 kg). Therefore, always transport the unit with the help of another person or use a forklift or a crane. Always place the unit on its back side.

Packaging

Keep the original packaging of the Condair CP3 for later use.

In case you wish to dispose of the packaging, observe the local regulations on waste disposal. Never dispose of the packaging to the environment.

3.8.2.3 Fan unit

The fan units – in combination with the steam humidifiers Condair CP3 – are used for the direct room humidification. They are mounted separately above the unit to the wall.The type of fan unit and the amount required is dependent on the steam capacity and on the type of the basic unit(s) and can be gath-ered from the table in chapter 3..1.

Note: Further information on the Condair FAN can be found in the separate Technical Documentation supplied with the Condair FAN.

The fan units are delivered with:

– Installation accessories for wall mounting including steam hose and steam hose connector with condensate trap “SCCT” (Basic version) or condensate trap “CT” (Pro version)

– Technical Documentation Condair FAN

Page 19: condair cP3 - australianvs.com.au

1

4.1 Selecting the unit version

The maximum required steam capacity must be calculated based on one of the following formu-las:

V • ρ mD = • (x2 - x1) 1000

or V mD = • (x2 - x1) 1000 • ε

mD: maximum steam demand in kg/hV: volume of supply air portion per hour in m3/h (for indirect room humidification) or room volume

to be humidified per hour in m3/h (for direct room humidification) ρ: specific gravity of air in kg/m3

ε: specific volume of air in m3/kgx2: desired absolute room air humidity in g/kgx1: minimum absolute supply air humidity in g/kg

The values for ρ, ε, x2 and x1 can be gathered from the h,x-diagram or the Carrier-Diagram for moist air respectively.

Important notes:

– The required maximum steam capacity depends on the specific application and the installation. The calculated steam capacity based on the above formulas, the h,x diagram and the condition of the air to be humidified does not consider any steam loss (e.g. due to condensation in the steam hoses and the steam distributors), any heat loss of the unit as well as any absorption or release of humidity of materials located in the room being humidified.In addition, the calculated steam capacity does not consider any losses caused by the draining rate depending on the water quality as well as any losses occur if the steam humidifier is oper-ated on a mains circuit with a ground fault circuit interrupter.

The total amount of losses depends on the entire system and must be taken into consideration when calculating the required steam capacity. If you have any questions regarding the calculation of the steam capacity please contact your Condair supplier.

– For systems where the max. required steam capacity varies extensively (e.g. for test facilities or for systems with variable air volume flow, etc.), please contact your Condair supplier.

4 Notes for the planning engineer

To select the unit version the following planning steps are required:

1. Calculating the required maximum steam capacity according chapter .1.1

2. Selecting the unit version from the table in chapter .1.2

4.1.1 Calculating the maximum required steam capacity

Page 20: condair cP3 - australianvs.com.au

20

Condair CP3 Pro 45 400V3

4.1.2 Selecting the unit

Heatingvoltage* Max.steamcapacityinkg/h

Graduationinkg/h

ModelCondairCP3 Unitsize/Numberofunits

Basic... Pro... Singleunitsmall

Singleunitlarge

Doubleunitlarge

400V3(400V/3~/50...60Hz)

5...15 1 5...15 5...15 116...45 1 16...45 16...45 1

52 -- 52 52 160 -- 60 60 170 -- 70 70 180 -- 80 80 190 -- 90 90 1

105** -- -- 105 1 1120** -- -- 120 1 1135** -- -- 135 1 1152** -- -- 152 2160** -- -- 160 2180** -- -- 180 2

230V3(230V/3~/50...60Hz)

5...15 1 5...15 5...15 116...30 1 16...30 16...30 1

44 -- 44 44 150 -- 50 50 160 -- 60 60 1

75** -- -- 75 1 190** -- -- 90 1 1

100** -- -- 100 2120** -- -- 120 2

230V1(230V/1~/50...60Hz) 5...8 1 5...8 5...8 1

* Otherheatingvoltagesonrequest** LinkUpsystems

4.2 Selecting the options an accessories

For selecting the options and accessories see chapter 3. and 3..

Page 21: condair cP3 - australianvs.com.au

21

4.3 Selecting the control system

The various control systems

– System 1: Room humidity control

System 1 is suited for direct room humidification and air conditioning systems with mainly recirculated air. The humidity sensor or humidistat respectively is preferably located in the room itself or in the exhaust air duct.

A1 humidity sensorB1 ventilation interlockB2 airflow monitorB3 safety humidistatB humidistatPII Internal P/PI controllerPIE External continuous controller (e.g. PI controller)Y input signal from A1

– System 2: Room humidity control with continuous limitation of the supply air humidity

System 2 is suited for air conditioning systems with a large portion of supply air, low supply air temperature, post-humidification, or variable airflow volume. If the supply air humidity ex-ceeds the preset value, the continuous limitation is effected prior to the room humidity control.The humidity sensor (A1) is preferably located in the exhaust air duct or in the room itself. The humidity sensor (A2) for the limitation of the supply air humidity is located in the supply air duct after the steam distribution pipe. This control system requires a continuous controller with the option to connect a second humidity sensor.Attention! The continuous limitation of the supply air humidity is no substitute for the safety humi-distat.

A1/2 humidity sensorB1 ventilation interlockB2 airflow monitorB3 safety humidistatPII Internal P/PI controllerPIE External continuous controller (e.g. PI controller)Y input signal from A1Z input signal from A2

Page 22: condair cP3 - australianvs.com.au

22

– System 3: Supply air humidity control with continuous output limitation

Supply air humidity control (humidity sensor installed in supply air duct) should be used only where room humidity control is impracticable for technical reasons. Such systems always require a PI-controller.The humidity sensor (A1) is located in the supply air duct after the steam distribution pipe. The humidity sensor (A2) for the continuous output limitation is located in the supply air duct before the steam distribution pipe. Such a system requires a PI-controller with the option to connect a second humidity sensor.

A1/2 humidity sensorB1 ventilation interlockB2 airflow monitorB3 safety humidistatPII Internal PI controllerPIE External PI controllerY input signal from A1Z input signal from A2

Which humidity control system for which application?

Application Location of the humidity sensor

room or exhaust air duct supply air duct

Air conditioning systems with:

– supply air portion up to 33% System 1 System 1

– supply air portion up to % System 1 or 2 System 2 or 3

– supply air portion up to 100% System 2 System 3

– supply air humidity control — System 3

Direct room humidification System 1 —

Please contact your Condair supplier, if your application meets the following conditions:

– Humidification of small rooms up to 200 m3

– Air conditioning systems with a high number of air exchanges

– Systems with variable air volume flow

– Test facilities with extreme control accuracy requirements

– Rooms with a high variation in max. steam capacity

– Systems with temperature fluctuations

– Cold rooms and systems with dehumidification

Page 23: condair cP3 - australianvs.com.au

23

Input signals

Control with external controller Control with internal PI controller

Control signals Humidity sensor signals

0... VDC (Potentiometer 13 Ω ... 10 kΩ) 0... VDC (Potentiometer 13 Ω ... 10 kΩ)

1... VDC 1... VDC

0...10 VDC 0...10 VDC

2...10 VDC 2...10 VDC

0...1 VDC 0...1 VDC

3.2...1 VDC 3.2...1 VDC

0 ... 20 mA 0 ... 20 mA

... 20 mA ... 20 mA

Humidistat (2 V On/Off)

Page 24: condair cP3 - australianvs.com.au

2

5 Mounting and installation work

Qualification of personnel

All mounting and installation work must be carried out only by well qualified personnel authorised by the owner. It is the owner’s responsibility to verify proper qualification of the personnel.

General note

Strictly observe and comply with all information given in the present Technical Documentation regard-ing the location of the unit and the installation of water, steam and electricity.

Observe and comply with all local regulations dealing with water, steam and electrical installa-tions.

Safety

Some installation work requires removal of the unit cover. Please note the following:

WARNING!

Danger of electrical shock! You may get in touch with live parts when the unit is open. The steam humidifier must be connected to the mains only after all mounting and installation work has been completed and the cover has been relocated properly.

CAUTION!

The electronic components inside the humidifier are very sensitive to electro-static discharge. When the unit is open for installation work, appropriate measures must be taken to protect these components against damage caused by electrostatic discharge (ESD protection).

5.1 Important notes for mounting and installation work

Page 25: condair cP3 - australianvs.com.au

2

DS80

≥ 40 mm

min. 10 %–

Ømin. 200 mm

max. 4 m

125...1250 µS/cm1...10 bar1...40 °C

DS60

DS22

DS80

61-...

81-...

61-...

41-...

41-...

81-...

FAN B45FAN B15

FAN P45FAN P15

max

. 4 m

60...70 °C

ø40 mm

ø10/8 mm 230V/1~/50Hz

400V/3~/50Hz

min. 5 %–

min

. 300

mm

G 1/2"

Z261

KS10

Rmin. 300 mm min. 5 %–

min. 10 %–

min. 20 %+

min. 20 %–

min. 20 %–

G 1/2"

1 ... 40 °Cmax. 75 %rhIP20

Pmin1500 Pa-800 Pa

Pmax

Pmin1500 Pa-800 Pa

Pmaxm

in. 5

0 cm

Rmin. 30

0 mm

Ømin. 200 mm

KS10

230V/1~/50Hz

DS60

DS80

ProBasic

5.2 Installation overview

Water installation, see chapter .

Electric installation, see chapter .

Steam installation, see chapter .

Mounting the unit, see chapter .3

Page 26: condair cP3 - australianvs.com.au

2

min

. 400

mm

B

min. 600 mm

Hmin. 250 mm

min. 400 mm

min

. 600

mm

50 mm

60...70 °C

1 ... 40 °Cmax. 75 %rhIP20

T

5.3 Mounting the unit

5.3.1 Notes on locating the unit

CondairCP3...230V1Basic Pro

5...8

CondairCP3...230V3Basic Pro Basic Pro Basic Pro Basic Pro Basic Pro Pro Pro

5...8 9...15 16...21 22...30 44/50 75/90 100/120

CondairCP3...400V3Basic Pro Basic Pro Basic Pro Basic Pro Basic Pro Pro Pro

5...8 9...15 16...25 26...45 52/60/70/80/90 105/120/135 152/160/180

DimensionsHousing(BxHxT)inmm 456x620x280 1 1

559x667x350 1 1 2 3 4WeightsNetweightinkg 21 21 21 28 2x28 3x28 4x28Operatingweightinkg 26 32 32 65 2x65 3x65 4x65

Module A

Module B

Page 27: condair cP3 - australianvs.com.au

2

The installation site of the steam humidifier depends largely on the location of the steam distributor (see chapter .). To ensure proper functioning of the steam humidifier and to obtain an optimal efficiency, the following points must be considered and observed when choosing the location for the steam humidifier:

– Install the steam humidifier so that the length of the steam hose is kept as short as possible (max. 4 m) and that the minimum bend radius (R= 300 mm) and up-slope (20 %) or down-slope (5 %) of the steam hose is observed (see chapter ..).

– The steam humidifiers Condair CP3 are designed for wall-mounting. Make sure that the construc-tion (wall, pillar, floor-mounted console, etc.) to which the humidifiers are to be mounted, offers a sufficiently high load-bearing capacity (take notice of the weight information found in the dimension sand weights table above), and is suitable for the installation.

CAUTION!Do not mount the steam humidifier directly to the ventilation duct (insufficient stability).

– The back panel of the Condair CP3 is retaining heat during operation (max. surface temperature of the metal housing approx. 0 - 0 °C). Make sure, therefore, that the construction (wall, pillar, etc.) to which the units are to be mounted, does not consist of heat-sensitive material.

– Install the steam humidifier in such a manner that it is freely accessible with sufficient space available for maintenance purposes (refer to the above illustration for minimum distances).

– The Condair CP3 is protected according to IP20. Make sure the units are installed in a drip-proof location and the admissible ambient conditions are complied with.

– The steam humidifier Condair CP3 may only be installed in rooms with a floor drain.

CAUTION!If for some reason the Condair CP3 must be installed in a location without floor drain, it is mandatory to provide a leakage monitoring device to safely interrupt the water supply in case of leakage.

– When fixing the Condair CP3 use only the fixing materials supplied with the unit. If fixing with the materials supplied is not possible in your particular case, select a method of fixing that is of similar stability.

Page 28: condair cP3 - australianvs.com.au

2

5.3.2 Mounting the humidifier

Procedure

1. Mark the attachment point “A” on the wall.

2. Drill hole for attachment point “A” (diameter: mm, depth: 0 mm).

3. Insert the supplied plastic plug, and tighten the screw until the distance between the wall and the screw head is mm.

. Unlock the two screws fixing the front panel to the unit, then remove the front panel.

. Hang up the unit onto the screw and adjust it horizontally and vertically using a spirit level. Then, mark the fixing points “B”.

. Drill the holes for the fixing points “B” (diameter: mm, depth: 0 mm).

. Insert the supplied plastic plugs, and tighten the screws until the distance between the wall and the screw head is mm.

. Hang the unit up onto the screws. Before tightening the screws, readjust the unit with the spirit level.

. Reattach the front panel and secure it with the two screws.

d

e

bc

a

A

B

B

Dimension Housingsizesmall large

a 228mm 284mmb 51mm 51mmc 500mm 545mmd 90mm 144mme 180mm 216mm

Page 29: condair cP3 - australianvs.com.au

2

5.3.3 Inspecting the installed unit

Check the following points:

Is the unit installed in the correct place (see chapter .3.1)?

Is the supporting surface stable enough?

Is the unit correctly aligned, vertically and horizontally?

Is the unit properly secured (see chapter .3.2)?

Has the front panel of the unit been relocated and correctly fixed with the two screws?

Page 30: condair cP3 - australianvs.com.au

30

5.4 Steam installation

5.4.1 Overview steam installation

Ømin. 200 mmmax. 4 m

DS60

DS22

DS80

61-...

81-...

61-...

41-...

41-...

81-...

max

. 4 m

min. 5 %–

min

. 300

mm

KS10Rmin. 300 mm min. 5 %

min. 20 %+

min. 20 %–

min. 20 %–

Pmin1500 Pa-800 Pa

Pmax

Pmin1500 Pa-800 Pa

Pmax

Rmin. 30

0 mm

Ømin. 200 mm

KS10

DS60

DS80

FAN B15

FAN B45

FAN P15

FAN P45

Basic Pro

Page 31: condair cP3 - australianvs.com.au

31

The calculation of the humidification distance “BN” is dependent on several factors. For a rough es-timation of the humidification distance “BN”, the following table is useful. Recommended standard values listed in this table are based on a supply-air temperature range of 15 °C to 30 °C. The values given in bold type only apply to steam distribution pipes 41-..., 61-... and 81-..., the values in brackets apply to the OptiSorp steam distribution system.

Humidity at inletϕ1 in %rh

Length of humidification distance BN in m Humidity at outlet ϕ2 in %rh

40 50 60 70 80 905 0,9 (0,22) 1,1 (0,28) 1,4 (0,36) 1,8 (0,48) 2,3 (0,66) 3,5 (1,08)10 0,8 (0,20) 1,0 (0,26) 1,3 (0,34) 1,7 (0,45) 2,2 (0,64) 3,4 (1,04)20 0,7 (0,16) 0,9 (0,22) 1,2 (0,30) 1,5 (0,41) 2,1 (0,58) 3,2 (0,96)30 0,5 (0,10) 0,8 (0,17) 1,0 (0,25) 1,4 (0,36) 1,9 (0,52) 2,9 (0,88)40 – 0,5 (0,11) 0,8 (0,20) 1,2 (0,30) 1,7 (0,45) 2,7 (0,79)50 – – 0,5 (0,13) 1,0 (0,24) 1,5 (0,38) 2,4 (0,69)60 – – – 0,7 (0,16) 1,2 (0,30) 2,1 (0,58)70 – – – – 0,8 (0,20) 1,7 (0,45)

For duct widths <600 mm the humidification distance for the OptiSorp system increases by ap-prox. 50%

ϕ1 in %rh: Relative supply air humidity prior to humidification at the lowest supply air temperatureϕ2 in %rh: Relative supply air humidity after the steam distribution pipe at maximum capacity

Example

given: ϕ1= 30 %rh, ϕ2= 70 %rh

humidification distance BN: 1,4 m (0.36 m for steam distribution system OptiSorp)

Note: If the humidification distance has to be reduced for technical reasons, the amount of steam per basic unit must be divided between two steam distribution pipes or the steam distribution system OptiSorp must be used. If this is the case, contact your Condair supplier.

5.4.2 Positioning and mounting of the steam distribution pipes

The location for the steam distribution pipes should be determined at the time of dimensioning the air conditioning system. Please note the following instructions to ensure proper humidification of the duct air.

Calculating the humidification distance

The water vapour, emitting from the steam distribution pipes, requires a certain distance to be absorbed by the ambient air so that it is no longer visible as steam. This distance is referred to as humidification distance “BN” and serves as a basis for the determination of the minimum distances from the upstream components in the system.

Humidificationdistance BN

Expansion and mixing zone

ϕ1: Supply air humidity before humidificationϕ2: Supply air humidity after humidification

Page 32: condair cP3 - australianvs.com.au

32

Minimum distances to be observed

To prevent the water vapour, that is emitting from the steam distribution pipe, from condensing on downstream system components, a minimum distance to the steam distribution pipe must be observed (depends on the humidification distance “BN”).

before/after constriction after expansion before bend

before branch before diffuser before control sensor

before/after filter/register before/after fan, zone exit

2, x BN before aerosol filter

Installation notes and dimensions

The steam distribution pipes are designed for either horizontal installation (on the duct wall) or, with accessories, for vertical installation (in the duct floor). The outlet orifices should always point upwards and at right angles to the airflow.

If possible, the steam distribution pipes should be installed on the pressure side of the duct (max. duct pressure 1500 Pa). If the steam distribution pipes are installed on the suction side of the duct, the maximum vacuum must not exceed 800 Pa.

Select a location for the installation, tailored to suit your duct (see the following illustrations) and posi-tion the steam distribution pipes in the duct so that a uniform distribution of steam is achieved.

1.5 x BN * BN BN5 cm

Page 33: condair cP3 - australianvs.com.au

33

In positioning the steam distribution pipes, the following dimensions should be observed:

Note: When locating the OptiSorp steam distribution system please note the instructions in the separate documentation for this product.

hmin

hminhmin

hmin

hminhmin

1/2 H1/2

H

H

1/3

2/3H

1/5

1/5

2/51/5

H2/72/73/7

1/51/5 H

2/51/5

1/4 H1/41/41/4

1/3 H1/31/3

2/7

2/7

3/7

H

1/21/2

1/5H

1/51/51/51/5

H

1/61/6

2/6

1/61/6

H

1/61/6

2/61/61/6

hmin

gmin gmin

gmin

gmin gmin

gmin

g min.= 100 mmh min.= mm

H min.= 20 mm H ≥00 mm H min.= 200 mm

H min.= 00 mm H min.= 30 mm H min.= 300 mm

H min.= 00 mm H min.= 00 mm H min.= 00 mm

H min.= 20 mm H min.= 00 mm H min.= 00 mm

Page 34: condair cP3 - australianvs.com.au

3

5.4.3 Installing the steam distributors

Detailed information on the installation of steam distribution pipes 1-.., 1-.../1-... and OptiSorp steam distribution system can be found in the separate “Mounting Instructions” for this products.

Guidelines for dimensioning the ventilation ducts

– To facilitate the installation of the steam distribution pipes and for control purposes, a sufficiently sized control opening should be planned.

– Within the range of the humidification distance, the ventilation duct should be waterproofed.

– Air ducts passing through cold rooms should be insulated to prevent the humidified air from condensing along the duct wall.

– Poor airflow conditions within the air duct (e.g. caused by obstacles, tight bends, etc.) can lead to condensation of the humidified air.

– Steam distribution pipes must not be mounted to round ducts.

If you have questions relating to the dimensioning of ventilation ducts in combination with steam humidifiers Condair CP3, contact your Condair supplier.

Page 35: condair cP3 - australianvs.com.au

3

5.4.4 Positioning and mounting of the fan unit

FANB15/FANP15 FANB45/FANP45

mDmax. 8kg/h 15kg/h 30kg/h 45kg/h

Amin. 3.0m 6.0m 8.0m 10.0m

Bmin. 0.5m 0.7m 1.0m 1.5m

Capprox. 2.2m 2.2m 2.2m 2.2m

Dapprox. 0.5m 0.7m 1.0m 1.5m

E 0.15...2.0m 0.2...2.0m 0.3...2.0m 0.5...2.0m

Note:Theminimumspacesinthetableapplyforaroomatmosphereof15°Candmax.60%rh.Forlowertemperaturesand/orhigherhumiditythevaluesshouldbeadjustedaccordingly

Note: In order to achieve a uniform distribution of the humidity within the room, additional factors such as the room size, the room height, etc., must be taken into consideration besides observing the minimum distances. If you have questions concerning the direct room humidification, please contact your Condair supplier.

Further information is provided in the separate “Technical documentation for the fan unit”.

The fan unit is mounted on the wall separately above the unit. To allow the steam coming from the fan unit to spread out evenly, without condensing on obstacles (ceilings, joists, pillars, etc.), the following minimum dimensions must be observed when selecting the location for the fan unit.

A

C

B

D

D

E

Page 36: condair cP3 - australianvs.com.au

3

5.4.5 Installing the steam hose

Important! Use original Condair steam hose exclusively. Other types of steam hoses can cause undesired operational malfunctions.

Instructions for the hose layout

The hose layout depends on the position of the steam distribution pipe:

– Steam distribution pipe is mounted more than 300 mm above the top edge of the humidifier:

Initially, lead the steam hose with an upslope of at least 20% over a minimum height of 300 mm, then lead the hose with a minimum upslope of 20% and/or a minimum downslope of 5% to the steam distribution pipe.

– Steam distribution pipe is mounted less than 300 mm above the top edge of the humidifier:

Initially, the steam hose is led with an upslope of at least 20 % over a minimum height of 300 mm above the top edge of the humidifier and then down to the steam distribution pipe with a minimum slope of 5 %.

– The steam hose should be kept as short as possible (max. 4 m) while observing the minimum bend radius of 300 mm. Important! Allowance must be made for a pressure loss of 10 mm water column (approx. 100 Pa) per meter steam hose.Note: If your particular installation exceeds the maximum steam hose length of m contact your Condair representative. In any case, steam hoses longer than m must be insulated in their entire length.

– Reductions in the cross section such as kinks should be avoided throughout the entire length of the hose. The installation of a stop cock in the steam hose is not permissible.

min

.300

mm

Rmin.

300m

m

min.5% min.20%

max

.4m

min

.300

mmRmin.

300mm

min.20%

max

.4m

max

.4m

min.5%

Rmin

.30

0m

m

max

.4m

min

.300

mm

min.20%

min

.300

mm

min.20%min.5%

Rmin. 300m

mmin.20%

Page 37: condair cP3 - australianvs.com.au

37

– Steamhosesmustbepreventedfromsagging(condensatepockets);ifnecessary,supportwithpipeclamps,trough,orwallbrackets,orinstallacondensatedraininthesteamhose.

– Important!Whendecidingonthe lengthandlayoutofthehose, itshouldbenotedthatthesteamhosemaybecomesomewhatshorterwithprogressiveageing.

Securing the hose

Thesteamhosemustbesecuredtothesteamdistributionpipeandhumidifiersteamoutletbymeansofhose clamps.Caution!Donotovertightenthehoseclamponthesteamconnectorofthesteamhumidifier.

Steam line with fixed piping

Forsteamlineswithfixedpiping,thesameinstructionsapplytothelayingofthepipingasalreadydescribed.Thefollowingadditionalnotesshouldbeobserved:

– Theminimum internal diameter of 22 mm, 30 mm or 45 mmrespectivelyshouldbeappliedoverthewholelengthofthepiping.

– UseexclusivelyCupipeorstainlesssteel(min.DIN1.4301).

– Tominimizethecondensateformation(=loss),thesteampipesmustbeinsulated.

– Theminimum bend radiusforsolidpipesis4-5 x internal diameter.

– Connectionofthesteampipestothesteamdistributionpipeandsteamhumidifieriseffectedbymeansofshortlengthsofsteamhosesecuredwithhoseclamps.ConnectiontothesteamhumidifierissecuredviaaG2”coupling.

– Important! Allowancemustbemadeforapressure loss of 10 mm water column (approx. 100 Pa)permeterlengthorper90°bend.

5.4.6 Installing the condensate hose

Important! Use original Condair condensate hose exclusively. Other types ofhoses can causeoperationalmalfunctions.

Thehoselayoutdependsonthepositionofthesteamdistributionpipe:

– Steamdistributionpipeismountedmore than 300 mm above the top edge of the humidifier:

Condensatehoseisleddowntothehumidifierwithaminimum slope of 20 %,intheformofa siphon (min. hose bend diameter Ø200 mm ),andinsertedabout2cmintothespecifiedopening.

min

. 300

mm min. 20 %

Ømin. 200 mm

min

. 300

mm

min. 20 %

Ømin. 200 mm

Page 38: condair cP3 - australianvs.com.au

3

– Steam distribution pipe is mounted less than 300 mm above the top edge of the humidifier:

Condensate hose is led down with a minimum slope of 20 %, in the form of a siphon (min. hose bend diameter Ø200 mm), directly into a discharge funnel.

Note: If your unit feeds a number of steam distribution pipes, the individual condensate hoses are to be led into the discharge funnel.

Important! Before putting the unit into operation, the siphon of the condensate hose must be filled with water.

5.4.7 Inspecting the steam installation

Use the following check list to ascertain that the steam installation was performed correctly:

– Steam distribution pipe

Steam distributors (steam distribution pipe or OptiSorp steam distribution system) correctly positioned and secured (screws tightened)?

Are the outlet orifices at right angles to the air flow direction?

– Steam hose

Maximum length of m?

Minimum bend radius of 300 mm (- x internal diameter with fixed piping)?

Have the instructions for hose positioning been followed?

Steam hose: no sagging (condensate pocket) or condensate drain with siphon (hose bend with a minimum diameter of 200 mm) installed at the lowest point?

Rigid steam lines: properly insulated? Correct installation material used? Minimum internal diameter maintained?

Steam hose(s) securely attached with clamps?

Heat expansion during operation and shortening of the hose with ageing taken into considera-tion?

– Condensate hose

Downslope of at least 20 %?

Siphon (min. ø 200 mm) existing and filled with water?

Condensate hose correctly fixed and not kinked?

min

.300

mmmin.20%

Ømin.20

0mm

min

.300

mm

min.20%

Ømin.20

0mm

Page 39: condair cP3 - australianvs.com.au

3

DS80

125...1250 µS/cm1...10 bar1...40 °C

ø40 mm

ø10/8 mm

G 1/2"

Z261

≥ 40 mm

G 1/2"

min

. 50

cm

min. 10 %–

min. 10 %–

5.5 Water installation

5.5.1 Overview water installation

Page 40: condair cP3 - australianvs.com.au

0

Water supply

The water supply is to be carried out according to the figure found in chapter ..1 and the applicable local regulations for water installations. The indicated connection specifications must be observed.

– The installation of the filter valve (accessory “Z21”, alternatively a shut-off valve and a µm water filter can be used) should be made as close as possible to the steam humidifier.

– Admissible mains pressure 1.0 to 10.0 bar (hammer-free system)For mains pressures >10 bar, the connection must be made via a pressure reducing valve (adjusted to 1.0 bar). For mains pressures <1.0 bar please contact your Condair supplier.

– Notes on water quality:

– For the water supply of the Condair CP3, use exclusively untreated drinking water.

– The use of additives such as corrosion inhibitors, disinfectants, etc. is not allowed, since these additives may endanger health and affect proper operation.

– If the Condair CP3 shall be operated with softened or partly softened water, please contact your Condair supplier.

– The connection material must be pressure-proof and certified for use in drinking water systems.

– Important! Before connecting the water line, the line should be well flushed out.

CAUTION!The thread at the humidifier connection is made of plastic. To avoid overtightening, the union nut of the water pipe must be tightened by hand only.

Water drain

The water drain is to be carried out according to the figure found in chapter ..1 and the applicable local regulations for water installations. The indicated connection specifications must be observed.

– Make sure that the drain pipe is correctly fixed and easily accessible for inspections and cleaning purposes.

– The draining temperature is: 80…90 °C (approx. 0...0 °C with activated drain water cooling). Use temperature-resistant installation materials only!

5.5.2 Notes on water installation

Page 41: condair cP3 - australianvs.com.au

1

5.5.3 Inspecting the water installation

Check the following topics:

– Water supply

Has filter valve (accessory “Z21”) or shut-off valve and µm water filter respectively been installed in supply line?

Have admissible water pressure (1 – 10 bar) and admissible temperature (1 – 0 °C) been observed?

Does the supply capacity match the humidifier and is the minimum inside diameter of the supply pipe maintained throughout the entire length?

Are all components and pipes properly secured and are all threaded connections securely tightened?

Is the water system properly sealed?

Does the water supply installation meet the requirements of the local regulations for water installations?

– Water drain

Is the minimum inside diameter of the drain pipe of 0 mm maintained throughout the entire length?

Has drain pipe been installed with a downslope of at least 10 %?

Has the heat resistance of the material used been verified to be at least 100 °C?

Is the drain hose properly secured (hose clamps at unit connection tightened)?

Does the water drain installation meet the requirements of the local regulations for water installations?

Page 42: condair cP3 - australianvs.com.au

42

5.6 Electricinstallation

5.6.1 WiringdiagramCondairCP3Basic/Pro

A1

Cont

rolle

r(ac

tive)

orh

umid

itys

enso

rA2

Co

ntro

ller(

pass

ive)

,set

JP3

top

ositi

on5

VA3

On

/Off

cont

rolle

r,se

tJP3

top

ositi

on2

4VA4

Li

mita

tion

sign

alB1

Ve

ntila

tion

inte

rlock

B2

Safe

tyh

umid

ista

tB3

Ai

rflow

mon

itor

F1

Inte

rnal

fuse

“Dr

iver

boa

rd”

(6.3

A,s

low

act

ing)

F2

Inte

rnal

fuse

“Dr

iver

boa

rd”

cont

rols

igna

l(20

0m

A,fa

sta

ctin

g)F3

Ex

tern

alfu

seh

eatin

gvo

ltage

sup

ply

F4

Exte

rnal

fuse

con

trolv

olta

ges

uppl

yH1

Re

mot

eop

erat

ing

and

faul

tind

icat

ion

JSh

ortc

ircui

ted,

ifn

oex

tern

alm

onito

ring

devi

ces

are

conn

ecte

dJ2

Li

nkU

psy

stem

“Dr

iver

boa

rd”

JP1

Term

inat

ion

Link

Up

syst

emJP

3Ju

mpe

rcon

trols

igna

l

KEx

tern

als

afet

ych

ain

(230

V/5A

)K1

M

ain

cont

acto

r(fo

rcon

nect

ing

the

heat

ing

volta

ges

uppl

yto

the

unit)

M

Vent

ilatio

nun

itQ3

Ex

tern

als

ervi

ces

witc

hhe

atin

gvo

ltage

sup

ply

Q4

Exte

rnal

ser

vice

sw

itch

cont

rolv

olta

ges

uppl

yX0

Co

nnec

tion

term

inal

hea

ting

volta

ge(u

nitv

ersi

onP

ro)

X1

Conn

ectio

nte

rmin

alc

ontro

lvol

tage

X6

Conn

ectio

nto

mod

ule

B

CPU

BOAR

D M

AIN

UN

IT

J3 DRIV

ER B

J2 FAUL

T RE

MOT

E

J1 D

RIVE

R A

J4(R

S485

)

CP3

Card

Mai

n un

it 4 3 2 1 2 1

Analog Out

F110

0mA

Sensor Supply Max. 60mA

Unit

ONSt

eam

Serv

ice

Erro

r

Faul

t Rem

ote

Boar

d

12

34

56

78

910

H1

Q4

J

F4

L1∆p

N

230

V/1N

~/50

..60

HzB

3

B2

B1

M

K

V+IN

On/O

ffSe

t JP3

OUT

to

24

V

Set J

P3 O

UT

to 5

V

GND

V+IN+

P / P

I

+–

P / P

I

GND

140Ω

...10

A1

A4

A2

A3

L1

Q3K1 X0 F3

L1L2

L3

L1L2

L3PE

L1L2

L3

Heat

ing

Mod

ule

B

400

V/3~

/50.

.60

Hz23

0 V/

3~/5

0..6

0 Hz

Q3 F3

L1N

PE

230

V/1~

/50.

.60

Hz

L1

Q3K1 X0 F3

L1L2

L3

L1L2

L3PE

L1L2

L3

Heat

ing

Mod

ule

A

400

V/3~

/50.

.60

Hz23

0 V/

3~/5

0..6

0 Hz

Q3 F3

L1N

PE

230

V/1~

/50.

.60

Hz

Mod

ule

BM

odul

e A

F220

0mAF

X2X7X4X3INLET V.DRAIN V.CONTACTOR

X5

PN

P1M

odul

BV+

INGN

DCO

NT.S

IGN

DRIV

ER B

OARD

MOD

ULE

B

J1 CPU

BOAR

D

J4 EXTE

RNAL

CON

.

J2 LIN

K UP

INGN

DLI

M. S

IGN

V+IN

BLOW

ERX6

PEL1

NSC

1M

AIN

SUP

PLY

X1

SC2

LEV.

SEN

SOR

F16.

3 AT

VTX SUPPLY SWITCH

OUT

24V

OUT

5VJP

3

Link

UpTe

rmin

atio

nJP1

F220

0mAF

X2X7X4X3INLET V.DRAIN V.CONTACTOR

X5

PN

P1M

odul

BV+

INGN

DCO

NT.S

IGN

DRIV

ER B

OARD

MOD

ULE

A

J1 CPU

BOAR

D

J4 EXTE

RNAL

CON

.

J2 LIN

K UP

INGN

DLI

M. S

IGN

V+IN

BLOW

ERX6

PEL1

NSC

1M

AIN

SUP

PLY

X1

SC2

LEV.

SEN

SOR

F16.

3 AT

VTX SUPPLY SWITCH

OUT

24V

OUT

5VJP

3

Link

UpTe

rmin

atio

nJP1

L1N

ϕ max

.

Supp

ly c

able

* (1

.4 m

)

CPU

cab

le *

(0.6

m)

*su

pplie

dw

ithd

oubl

eun

its**

su

pplie

dw

ithL

ink

Ups

yste

ms

Page 43: condair cP3 - australianvs.com.au

43

CPU

BOAR

D M

AIN

UN

IT

J3 DRIV

ER B

J2 FAUL

T RE

MOT

E

J1 D

RIVE

R A

J4(R

S485

)

CP3

Card

Mai

n un

it

CPU

BOAR

D EX

TEN

SION

UN

IT

J3 DRIV

ER B

DRIV

ER B

OARD

MOD

ULE

B

J2 FAUL

T RE

MOT

E

J1 D

RIVE

R A

J4

CP3

Card

Exte

ns. u

nit

4 3 2 1 2 1

Analog Out

F110

0mA

Sensor Supply Max. 60mA

Unit

ONSt

eam

Serv

ice

Erro

r

Faul

t Rem

ote

Boar

d

12

34

56

78

910

H1

4 3 2 1 2 1

Analog Out

F110

0mA

Sensor Supply Max. 60mA

Unit

ONSt

eam

Serv

ice

Erro

r

Faul

t Rem

ote

Boar

d

12

34

56

78

910

H1

Q4

J

F4

L1∆p

N

230

V/1N

~/50

..60

Hzϕ max

.

B3

B2

B1

K

V+IN

On/O

ffSe

t JP3

OUT

to

24

V

Set J

P3 O

UT

to 5

V

GND

V+IN+

P / P

I

+–

P / P

I

GND

140Ω

...10

A1

A4

A2

A3

L1

Q3K1 X0 F3

L1L2

L3

L1L2

L3PE

L1L2

L3

Heat

ing

Mod

ule

B

400

V/3~

/50.

.60

Hz23

0 V/

3~/5

0..6

0 Hz

Q3 F3

L1N

PE

230

V/1~

/50.

.60

Hz

L1

Q3K1 X0 F3

L1L2

L3

L1L2

L3PE

L1L2

L3

Heat

ing

Mod

ule

A

400

V/3~

/50.

.60

Hz23

0 V/

3~/5

0..6

0 Hz

Q3 F3

L1N

PE

230

V/1~

/50.

.60

Hz

L1

Q3K1 X0 F3

L1L2

L3

L1L2

L3PE

L1L2

L3

Heat

ing

Mod

ule

A

400

V/3~

/50.

.60

Hz23

0 V/

3~/5

0..6

0 Hz

Q3 F3

L1N

PE

230

V/1~

/50.

.60

Hz

F220

0mAF

X2X7X4X3INLET V.DRAIN V.CONTACTOR

X5

PN

P1M

odul

BV+

INGN

DCO

NT.S

IGN

DRIV

ER B

OARD

MOD

ULE

B

J1 CPU

BOAR

D

J4 EXTE

RNAL

CON

.

J2 LIN

K UP

INGN

DLI

M. S

IGN

V+IN

BLOW

ERX6

PEL1

NSC

1M

AIN

SUP

PLY

X1

SC2

LEV.

SEN

SOR

F16.

3 AT

VTX SUPPLY SWITCH

OUT

24V

OUT

5VJP

3

Link

UpTe

rmin

atio

nJP1

MA

IN U

NIT

EXTE

NSI

ON

UN

IT

Q4 F4

L1N

230

V/1N

~/50

..60

Hz

Mod

ule

B Sa

fety

cha

in fo

r Ext

ensi

on u

nit

F220

0mAF

X2X7X4X3INLET V.DRAIN V.CONTACTOR

X5

PN

P1M

odul

BV+

INGN

DCO

NT.S

IGN

DRIV

ER B

OARD

MOD

ULE

A

J1 CPU

BOAR

D

J4 EXTE

RNAL

CON

.

J2 LIN

K UP

INGN

DLI

M. S

IGN

V+IN

BLOW

ERX6

PEL1

NSC

1M

AIN

SUP

PLY

X1

SC2

LEV.

SEN

SOR

F16.

3 AT

VTX SUPPLY SWITCH

OUT

24V

OUT

5VJP

3

Link

UpTe

rmin

atio

nJP1

F220

0mAF

X2X7X4X3INLET V.DRAIN V.CONTACTOR

X5

PN

P1M

odul

BV+

INGN

DCO

NT.S

IGNDR

IVER

BOA

RD E

XTEN

SION

MOD

ULE

A

J1 CPU

BOAR

D

J4 EXTE

RNAL

CON

.

J2 LIN

K UP

INGN

DLI

M. S

IGN

V+IN

BLOW

ERX6

PEL1

NSC

1M

AIN

SUP

PLY

X1

SC2

LEV.

SEN

SOR

F16.

3 AT

VTX SUPPLY SWITCH

OUT

24V

OUT

5VJP

3

Link

UpTe

rmin

atio

nJP1

Set J

umpe

r on

JP1

Link

Up

cabl

e **

(10

m)

Supp

ly c

able

* (1

.4 m

)

CPU

cab

le *

(0.6

m)

5.6.2 WiringdiagramLinkUpsystems

A1

Cont

rolle

r(ac

tive)

orh

umid

itys

enso

rA2

Co

ntro

ller(

pass

ive)

,set

JP3

top

ositi

on5

VA3

On

/Off

cont

rolle

r,se

tJP3

top

ositi

on2

4VA4

Li

mita

tion

sign

alB1

Ve

ntila

tion

inte

rlock

B2

Safe

tyh

umid

ista

tB3

Ai

rflow

mon

itor

F1

Inte

rnal

fuse

“Dr

iver

boa

rd”

(6.3

A,s

low

act

ing)

F2

Inte

rnal

fuse

“Dr

iver

boa

rd”

cont

rols

igna

l(20

0m

A,fa

sta

ctin

g)F3

Ex

tern

alfu

seh

eatin

gvo

ltage

sup

ply

F4

Exte

rnal

fuse

con

trolv

olta

ges

uppl

yH1

Re

mot

eop

erat

ing

and

faul

tind

icat

ion

JSh

ortc

ircui

ted,

ifn

oex

tern

alm

onito

ring

devi

ces

are

conn

ecte

dJ2

Li

nkU

psy

stem

“Dr

iver

boa

rd”

JP1

Term

inat

ion

Link

Up

syst

emJP

3Ju

mpe

rcon

trols

igna

l

KEx

tern

als

afet

ych

ain

(230

V/5A

)K1

M

ain

cont

acto

r(fo

rcon

nect

ing

the

heat

ing

volta

ges

uppl

yto

the

unit)

M

Vent

ilatio

nun

itQ3

Ex

tern

als

ervi

ces

witc

hhe

atin

gvo

ltage

sup

ply

Q4

Exte

rnal

ser

vice

sw

itch

cont

rolv

olta

ges

uppl

yX0

Co

nnec

tion

term

inal

hea

ting

volta

ge(u

nitv

ersi

onP

ro)

X1

Conn

ectio

nte

rmin

alc

ontro

lvol

tage

X6

Conn

ectio

nto

mod

ule

B

*su

pplie

dw

ithd

oubl

eun

its**

su

pplie

dw

ithL

ink

Ups

yste

ms

Page 44: condair cP3 - australianvs.com.au

5.6.3 Fuses F3 for heating voltage supply

Heatingvoltage Max.steamcapacity

[kg/h]

ModelCondairCP3 Unitdesign

**

Nominalpower[kW]

Nominalcurrent

[A]

MainfusesF3[A]Basic... Pro...

400V3(400V/3~/50...60Hz)

5...8 5...8 5...8 EK 6.0 8.7 3x109...12 9...12 9...12 EK 9.0 13.0 3x1613...15 13...15 13...15 EK 11.3 16.3 3x2016...20 16...20 16...20 EG 15.0 21.7 3x2521...25 21...25 21...25 EG 18.8 27.1 3x3526...30 26...30 26...30 EG 22.5 32.5 3x4031...42 31...42 31...42 EG 31.5 45.5 3x5043...45 43...45 43...45 EG 33.8 48.8 3x63

52 52 52 DG 2x19.5 2x28.1 2x(3x40)60 60 60 DG 2x22.5 2x32.5 2x(3x40)70 70 70 DG 2x26.3 2x37.9 2x(3x63)80 80 80 DG 2x30.0 2x43.3 2x(3x63)90 90 90 DG 2x33.8 2x48.8 2x(3x63)105 -- 105 DG+EG 3x26.3 3x37.9 3x(3x63)120 -- 120 DG+EG 3x30.0 3x43.3 3x(3x63)135 -- 135 DG+EG 3x33.8 3x48.8 3x(3x63)152 -- 152 2xDG 4x28.5 4x41.1 4x(3x63)160 -- 160 2xDG 4x30.0 4x43.3 4x(3x63)180 -- 180 2xDG 4x33.8 4x48.8 4x(3x63)

230V3(230V/3~/50...60Hz)

5...8 5...8 5...8 EK 6.0 15.8 3x209...15 9...15 9...15 EK 11.3 29.6 3x4016...21 16...21 16...21 EG 15.8 41.4 3x5022...30 22...30 22...30 EG 22.5 59.1 3x63

44 44 44 DG 2x16.5 2x43.4 2x(3x63)50 50 50 DG 2x18.8 2x49.3 2x(3x63)60 60 60 DG 2x22.5 2x59.1 2x(3x63)75 -- 75 DG+EG 3x18.8 3x49.3 3x(3x63)90 -- 90 DG+EG 3x22.5 3x59.1 3x(3x63)100 -- 100 2xDG 4x22.5 4x59.1 4x(3x63)120 -- 120 2xDG 4x22.5 4x59.1 4x(3x63)

230V1(230V/1~/50...60Hz)

5 5 5 EK 3.8 16.3 206...8 6...8 6...8 EK 6.0 26.1 35

** EK=SingleunitsmallEG=SingleunitlargeDG=Doubleunitlarge

Note: The minimum cross section of the supply cable must comply with the local regulations.

Page 45: condair cP3 - australianvs.com.au

5.6.4 Inserting the CP3 Card

All important operating parameters such as the maximum steam capacity, the heating voltage, the number of base units as well as the differentiation between main and extension unit are permanently stored on the CP3 Card.Before you start the electrical installation, check whether the CP3 Card is installed. If it is not, check whether the type designation on the CP3 Card supplied corresponds with the type designation on the data plate on the bottom side of the unit (the data plate is located beside the type plate of the unit). If the designations match, place the CP3 Card in the card holder on control print . Then cover the data plate on the right side of the unit above the type plate with the data plate supplied (self-adhesive).If the type designation on the CP3 Card and the data plate do not match, the CP3 Card must not be installed. If this is the case, contact your Condair supplier.

5.6.5 Notes on electric installation

– The electric installation must be carried out according to the wiring diagram in chapter ..1 and the applicable local regulations. All information given in the wiring diagram must be followed and observed.

– All cables must be lead into the unit via the cable openings equipped with cable glands (e.g. op-tion “PG-cable gland”). The cable for the heating voltage supply must be lead into the unit from the bottom via the cable opening equipped with the clamp strap. Fix the cable with the clamp strap.

– Make sure the cables do not scrub on any components.

– Maximum cable length and required cross section per wire must be observed.

– The supply voltages for heating and control must match the respective voltages stated in the wiring diagram.

5.6.6 Inspecting the electrical installation

Check the following points:

Do the supply voltages for heating and control comply with the relevant voltages given in the wiring diagram?

Is the correct CP3 Card inserted?

Are the voltage supplies (heating and control voltage) correctly fused?

Is the service switch “Q..” installed in the supply line for to the heating and control voltage?

Are all components correctly connected according to the wiring diagram?

Are all connecting cables fastened?

Are the connecting cables free of tension (passed through cable glands?)

Does the electric installation meet the applicable local regulations for electric installations?

Is the front panel mounted and correctly fixed with the two screws?

Page 46: condair cP3 - australianvs.com.au

6 Operation

Proceed as follows when putting the unit into operation:

1. Examine the steam humidifier and installation for possible damage.

WARNING!

Damaged devices or devices with damaged installation may present danger to human life or cause severe damage to material assets. Damaged units and/or units with damaged or faulty installation must not be operated.

2. Check whether the front panel is mounted and fixed with the two screws.

3. Open the filter valve (or the shut-off valve, respectively) in the water supply line.

. Verify the set humidity value at the humidity controller or at the humidistat, and readjust as re-quired.

. Switch on the service switches for mains supplies (heating and control voltage).

. Actuate the unit switch of the steam humidifier. Switch lights up.

6.1 Commissioning

STARTUP: CP3 PRO

INIT MODULeXXXXXXXXXXXXXXXXXXXX

Menu Set

The steam humidifier carries out a system test, during which all the LEDs light up and the opposite display is shown.

If a failure occurs on the system test, a corresponding error message is shown in the display.

After the system test the unit is in normal operation mode. The display shows the standard operating display (first page of the indication level). Note: The contents of the standard operating display depends on the actual operating status and on the configuration of the Condair CP3 and can differ from the opposite display.

As soon as the humidity controller or the humidistat requires humidity, power is switched on for heating. The inlet valve opens (slight delay) and the steam cylinder fills with water. As soon as the submerged electrodes heat the water up the green LED lights up and after a few minutes (approx. –10 minutes, depending on the conductivity of the water) steam is produced.

StandbyCP3 P45 400V3

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX11.11.2006 12.00.00Menu Set

Demand :100%CP3 P45 400V3

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX11.11.2006 12.00.00Menu Set

Note: If the Condair CP3 is operated with water of low conductivity it may happen that the maxi-mum steam capacity is not reached in the first few hours of operation. This is normal. As soon as the conductivity has reached a sufficient level (due to the vaporisation process) the humidifier will reach the maximum steam capacity.

Page 47: condair cP3 - australianvs.com.au

6.2 Notes on operation

6.2.1 Function of the display and operating elements

Display and control unitFunction: Configuration of the Condair CP3. Indication of operating parameters. Reset of maintenance counter and error indication.

red LED “Error”Function: The LED lights in case of a malfunction of the unit. The

type of malfunction is shown in the display, see chap-ter ).

The LED flashes alternately with the green LED if the external safety chain (ventilation interlock, safety humidi-stat, etc.) is open.

yellow LED “Warning”Function: The LED lights if the cylinder maintenance is due.

green LED “Steam”Function: The LED lights if the unit produces steam. The LED flashes alternately with the red LED if the

external safety chain (ventilation interlock, safety hu-midistat, etc.) is open.

Drain keyFunction: Manual draining of the steam cylinder. After having

pressed the drain key, the draining is controlled via the display and control unit.

Unit switchFunction: Switches the unit on and off. The switch is illuminated

when the unit is running.

6.2.2 Remote operating and fault indication

Via the operating and fault indication the following operating status are shown remotely:

Activated remote indication relay

When? Display on unit

H1 “Error” A malfunction is present, further operation is not possible, the heating voltage is interrupted

Red LED lightsAn error message is shown in the display

H2 “Service” Steam cylinder maintenance is due. The unit remains operational for a certain time

Yellow LED lightsThe service warning message is shown in the display

H3 “Steam demand” Steam demand/Steam production

Green LED lightsThe standard operating display is shown.

H4 “Unit on” Unit ready for operation Unit switch lightsThe standard operating display is shown.

Page 48: condair cP3 - australianvs.com.au

6.2.3 Inspections during operation

During operation the Condair CP3 and the humidification system have to be inspected weekly. On this occasion check the following:

• the water and steam installation for any leakage.

• the steam humidifier and the other system components for correct fixing and any damage.

• the electric installation for any damage.

If the inspection reveals any irregularities (e.g. leakage, error indication) or any damaged compo-nents take the Condair CP3 out of operation as described in chapter .3. Then, contact your Condair representative.

6.2.4 Carrying out manual draining

Proceed as follows to drain the unit manually:

Manual Drain

Modul A

Press START or STOP

Esc SetStart

6.3 Taking the unit out of operation

In order to take the steam humidifier out of operation, perform the following steps:

1. If the unit has to be switched off because of a malfunction, please note the error code of the actual error message shown in the display.

2. Close the shut-off valve in the water supply line

3. Start manual draining (see chapter .2.) and wait until the steam cylinder is empty.

. Actuate the unit switch

. Disconnect steam humidifier from the mains: Switch off all service switches to mains sup-plies (heating and control voltage) and secure switches in “off” position against accidentally being switched on, or clearly mark the switches.

WARNING!

If steam was produced just before the unit is taken out of operation, wait be-fore opening the unit and let the steam cylinder cool down to prevent danger of burning.

1. Briefly press the drain key. The drain dialogue appears in the display.

2. Press the <Start> key. The heating voltage is interrupted and the drain pump starts. The yellow LED flashes. To stop the drain cycle press the <Stop> key.

Note: By pressing the <Esc> key the unit returns to the indication level. A drain cycle in progress will be stopped automatically.

Page 49: condair cP3 - australianvs.com.au

Demand :50%CP3 P90 400V3

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX11.11.2006 12.00.00Menu Set

Software :1.00LA00CP3 P90 400V3

Controlsign.:0-10VLimitsignal :0-10VModbus Addr.:1Menu Set

Power Limit :100%CP3 P90 400V3

Request A :50%Request B :50%∑ Steam :45kg/hMenu Set

Cylindertype:A644CP3 P90 400V3

Operating HoursCylinder A :22hCylinder B :21hMenu Mdl B

Main menu

User :SetWerksebene :Set

Info :Set

Esc Set

Info

ErrorHistory:SetUnit Status :Set

Esc Set

Main menu

User :SetInfo :Set

Esc Set

User CodeUser Code

88088808

Enter Number Enter Number Confirm with Set Confirm with SetEsc Set

UserUser

Settings :SetSettings :SetModbus :SetModbus :Set

Maintenance :SetMaintenance :Set

EscEsc Set

Drain Factor:1.0CP3 P90 400V3

Conductivity:>125µSStandbyDrain:PartialForce Drain :OnMenu Mdl B

TimerCP3 P90 400V3

On/Off Timer:OffPower Limit :OffHum.Setpoint:OffMenu Set

6.4 Overview and operating of the menu

The operating and display unit is operated via the four keys located just below the display. The status fields at the bottom of the display show the active keys the functions assigned to them.

Menu overview

actual key setting

keys

Indication level

Menu level

Operating

Menu Info– Interrogation of unit information– Interrogation of the malfunction list

Menu User– Resetting the maintenance counter– Unit settings– Modbus settings

StandbyCP3 P45 400V3

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX11.11.2006 12.00.00Menu Set

Page 50: condair cP3 - australianvs.com.au

0

6.5 Interrogation functions

6.5.1 Interrogation of the operating information in the indication level

In the normal operating mode the operating and display unit is in the indication level. The indication level forms a loop that includes several pages holding operating information which can be accessed with the arrow keys. The various displays of the indication level are shown below.

Standard operating display

The appearance of the standard operating display depends on the actual operating status and the configuration of the Condair CP3. The following display are possible.

Demand :100%CP3 P90 400V3

Limiter : 70% 11.11.2006 12.00.00Menu Set

Standard operating display with control via the external controller– Standby (no humidity demand) or Demand % (humidity demand

present) – Set supply air limitation in % *

* this parameter appears only if external supply air limitation is acti-vated

Act.Humidity: 75%rHCP3 P90 400V3

Hum.Setpoint: 50%rHLim.Humidity: 60%rHLim.Range : 70-90%Menu Set

Standard operating display with control via the internal controller– Actual humidity in %rh– Set nominal humidity %rh– Set supply air limitation in % **– Set range for supply air limitation in % **

** these parameters appear only if internal supply air limitation is activated

Info page: Settings

Software :1.00LA00CP3 P90 400V3

Controlsign.:0-10VLimitsignal :0-10VModbus Addr.:1Menu Set

– Software version (1.00)/language version (LA00)– Set control signal range (signal Y)– Set control signal range for the supply air limitation (signal Z). Ap-

pears only if supply air limitation is activated.– Set Modbus address of the unit

Info page: Performance data

Power Limit :100%CP3 P90 400V3

Request A :50%Request B :50%∑ Steam :45kg/hMenu Set

– Set power limitation in %– Actual humidity demand unit A in %rh– Actual humidity demand unit B in %rh (if present)– Actual steam capacity of the unit in kg/h

Info page: Steam cylinder type and operating hours

Cylindertype:A644CP3 P90 400V3

Operating HoursCylinder A :20hCylinder B :20hMenu Set

– Steam cylinder type– Operating hours of the steam cylinder A since the last reset.– Operating hours of the steam cylinder B since the last reset.

Info page: Drain settings

Drain Factor:1.0CP3 P90 400V3

Conductivity:>125µSStandbyDrain:FullForced Drain:OffMenu Set

– Set drain factor– Conductivity of the water– Set draining type in standby operation– Set time interval for forced draining

Page 51: condair cP3 - australianvs.com.au

51

6.5.2 Interrogationofunitinformation

Select the list with the unit information:Path: Mainmenu>Info>Unit Status

Press < > and < > keys, in order to select the unit information available in the list:

1 Total operating hours since the initial commissioning.

2 Actual status of the remote indication relay “Steam”

3 Actual status of the remote indication relay “Service”

4 Actual status of the remote indication relay “Error”

5 Actual status of the remote indication relay “Unit on”

6 Actual signal value at analog output 1 (corresponds to the actual steam capacity converted to the signal range of 0...10 V)

7 Actual signal value at analog output 2 (0...10V)

8 Calculated mean drain time in seconds of unit A (and B)

9 Current average request of unit A (and B)

10 Actual status of the maximum level sensor in the steam cylinder A (and B)

11 Counter showing the number of times the maximum level in the steam cylinder A (and B) has been exceeded

12 Actual status of the inlet valve of unit A (and B)

13 Actual status of the drain pump of unit A (and B)

14 Actual status of the main contactor of unit A (and B)

Press the <Esc> key several times to quit the unit information list and to return to the standard operating display.

InfoPage:Timersettings

TimerCP3 P90 400V3

On/Off Timer :OffPower Limit :OffHum.Setpoint:OffMenu Set

– Actual status of On/Off timer– Actual status of power limit timer– Actual status of humidity setpoint timer (appears only if internal

P/PI controller is activated)

Unit Status

0hRemote SteamOff

System Operating Hour

11.11.2006 12.00.00

Esc Set

Remote ServiceOffRemote ErrorOffRemote Unit OnOnRemote Analog Out-10.0 VRemote Analog Out-20.0 VAverage Drain TimeA 0.0 s B 0.0 s

Max. Level SensorA Off B OffMax. Level CounterA 0 B 0Inlet ValveA Off B OffOutlet PumpA Off B OffMain ContactorA Off B Off

Average RequestA 100% B 0 %

1

2

3

4

5

6

7

8

9

10

111213

14

Page 52: condair cP3 - australianvs.com.au

2

6.5.3 Interrogation of the malfunction list

Select the error history list:Path: Main menu > Info > ErrorHistory

The last error that occurred is shown with:– running number of the error– date and time of occurrence (version Pro only)– error code (Warning: W..., Error: E...– error message– additional info text regarding the error

Press < > and < > keys, in order to select further error messages in the list.

Press the <Esc> key several times to quit the error history list and to return to the standard operating display.

The error messages generated by the last 20 malfunctions that occurred are saved in the malfunc-tion list of the Condair CP3 and can be interrogated.

ErrorHistory

E32A HumSensor brokenNo sensor signalHumidity sensor def.

01/05 11.11.06 12.34

11.11.2006 12.00.00Esc Set

Page 53: condair cP3 - australianvs.com.au

3

6.6 Unit settings

6.6.1 Launching the unit settings menu

Select the unit settings menu:Path: Main menu > User > Password entry: 8808 > Settings

Press the < > and < > keys in order to select the individual settings in the settings menu. Detailed information on the different settings are found in the following chapters.

6.6.2 Selecting the dialogue language

Settings

Controls :SetCylinder :SetPower Limit :Set

Language :English

On/Off Timer:SetEsc Set

Select “Language” in the settings menu, then press the <Set> key.In the upcoming modification dialogue select the desired dialogue lan-guage. After confirmation, the unit automatically switches to the selected dialogue language.

Factory setting: country specificOptions: divers languages

6.6.3 Control settings

Select “Controls” in the settings menu, then press the <Set> key.

The control settings appear. The settings available depend on the selected signal source and the control type. The opposite display shows the maxi-mum number of settings available.

Settings

Controls :SetCylinder :SetPower Limit :Set

Language :English

On/Off Timer:SetEsc Set

Description of the control settings

– SignalSource: Selecting the signal source.

Factory setting: AnalogOptions: Analog, Modbus

– Hum.Control: Selecting the control type.

Factory setting: ExternOptions: Extern (external continuous controller), 24VOn/Off (external On/Off humidistat), Int. (P) (Internal P controller) Int. (PI) (Internal PI controller)

Lim. Control:OnLimitsignal :0-10VLimit Min :70%rH

Integr.-Time:8min

Limit Max :90%rH

Controls

Hum.Control :Int.(PI)Controlsign.:0-10VHum.Setpoint:Set

SignalSource:Analog

P-Band :18%rHEsc Set

Remote Test :SetDate :19.10.07Time :12:00

Water Manag.:Set

Contrast :15

Settings

Controls :SetCylinder :SetPower Limit :Set

Language :English

On/Off Timer:SetEsc Set

GFCI-Mode :OffMulti-Mode :Sequence

Page 54: condair cP3 - australianvs.com.au

– Controlsign.: Selecting the control signal.

Note: This setting is available only if the internal or external P or PI control-ler is activated.

Factory setting: 0–10VOptions: 0–5V, 1–5V, 0–10V, 2–10V, 0–16V, 3.2–16V,

0–20mA, 4–20mA

– Hum.Setpoint: This menu item is available only if the internal P or PI controller is activated. With the parameters in the “Hum.Setpoint” submenu you determine whether the Condair CP3 is to be controlled with a fix humidity setpoint (factory setting) or whether it is to be operated timer controlled with dif-ferent humidity setpoints.

– Control with fix humidity setpoint:

Timer deactivated, humidity setpoint adjust-able (factory setting: 0 %rH, Setting range: 1... %rH)

– Timer controlled with different humidity setpoints:

If the timer is activated, up to eight switching points (events 1 - ) with different humidity setpoints can be defined.

Each switching point is defined by a weekday or weekday range, the switching point and the humidity setpoint.

Configuration notes: – the settings of an event remain active up to the next event.– the software does not check the plausibility of the timer settings.

Therefore, make sure your settings make sense.– the On/Off timer (see chapter ..) overrides the humidity setpoint

timer.

– P-Band: Setting the proportional range in % for the internal P/PI controller.

Note: This setting is available only if the internal P or PI controller is acti-vated.

Factory setting: 18 %Setting range: 6...65 %

– Integr.-Time: Setting the integral time in minutes for the internal PI controller.

Note: This setting is available only if the internal PI controller is activated.

Factory setting: 8 minutesSetting range: 1...60 minutes

– Lim. Control: Activating/Deactivating the supply air limitation (signal Z).

Note: This setting is available only if the external or internal P or PI control-ler is activated.

Factory setting: OffOptions: On, Off

Hum.Setpoint

Hum.Setpoint:50%rH

Timer :Off

Esc Set

Hum.Setpoint

Event 1 :06:00Event 2 :18:00Event 3 :--:--

Timer :On

Event 4 :--:--Esc Set

Event 2

Time :18:00Hum.Setpoint:30%rH

Weekday :Mo-Fr

Esc Set

Page 55: condair cP3 - australianvs.com.au

6.6.4 Cylinder settings

Settings

Controls :SetCylinder :SetPower Limit :Set

Language :English

On/Off Timer:SetEsc Set

Cylinder

Cyl. Number :644Cyl. Line :Dispos

Esc Set

Select “Cylinder” in the settings menu, then press the <Set> key.

The cylinder settings appear. Press the < > and < > keys in order to select the individual settings and press the <Set> key to call up the modification dialogue for the selected setting.

Description of the cylinder settings

– Cyl. Line: Selecting the cylinder type.

Factory setting: DisposOptions: Dispos (Disposable cylinder A..) Clean (Cleanable cylinder D..)

– Cyl. Number: Selecting the cylinder number

Factory setting: according the installed cylinderOptions: 342, 343, 363, 444, 464, 654, 644, 664, 674

– Limitsignal: Selecting the supply air limitation signal.

Note: This setting is available only if the external or internal P or PI control-ler and the supply air limitation are activated.

Factory setting: 0–10VOptions: 0–5V, 1–5V, 0–10V, 2–10V, 0–16V, 3.2–16V,

0–20mA, 4–20mA

– Limit Min: Setting the lower limit value in %rh for the supply air limitation.

Note: This setting is available only if the internal P or PI controller and the and the supply air limitation are activated.

Factory setting: 70 %rhSetting range: 15 ... 95 %rh

– Limit Max: Setting the upper limit value in %rh for the supply air limitation.

Note: This setting is available only if the internal P or PI controller and the and the supply air limitation are activated.

Factory setting: 90 %rhSetting range: 15 ... 95 %rh

Page 56: condair cP3 - australianvs.com.au

Settings

Cylinder :SetPower Limit :SetOn/Off Timer:Set

Controls :Set

GFCI-Mode :OffEsc Set

6.6.5 Setting the capacity limitation

Select “Power Limit” in the settings menu, then press the <Set> key. With the parameters in the “Power Limit” submenu you determine whether the Condair CP3 is to be operated with a fix capacity limit (factory setting) or whether it is to be operated with a timer controlled capacity limitation. Note: set the desired capacity limitation in % of the maximum capacity of the humidifier.

– Operation with fix capacity limit:

Timer deactivated, capacity limit adjust-able (factory setting: 100 %, Setting range: 30...100 %).

– Timer controlled capacity limitation:

If the timer is activated, up to eight switch-ing points (events 1 - ) with different capacity limits can be defined.

Each switching point is defined by a week-day or weekday range, the switching point and the capacity limit.

Configuration notes:

– the settings of an event remain active up to the next event.

– the software does not check the plausibility of the timer settings. Therefore, make sure your settings make sense.

– the On/Off timer (see chapter ..) overrides the capacity limit timer.

Power Limit

Power Limit :100%

Timer :Off

Esc Set

Power Limit

Event 1 :06:00Event 2 :18:00Event 3 :--:--

Timer :On

Event 4 :--:--Esc Set

Event 2

Time :18:00Power Limit :50%

Weekday :Mo-Fr

Esc Set

Page 57: condair cP3 - australianvs.com.au

6.6.7 Activating/Deactivating fault current relay operation

Settings

On/Off Timer:SetGFCI-Mode :OffMulti-Mode :Sequence

Power Limit :Set

Water Manag.:SetEsc Set

Select “GFCI-Mode” in the settings menu, then press the <Set> key.In the upcoming modification dialogue select whether or not the Condair CP3 is connected to a fault current relay protected mains supply.

Factory setting: OffOptions: On (mains supply with fault current relay protec-

tion) Off (mains supply without fault current relay

protection)

Settings

Power Limit :SetOn/Off Timer:SetGFCI-Mode :Off

Cylinder :Set

Multi-Mode :SequenceEsc Set

6.6.6 Configuring the On/Off timer

Select “On/Off Timer” in the settings menu, then press the <Set> key. With the parameters in the “On/Off Timer” submenu you determine whether or not the Condair CP3 is to be switched on and off timer con-trolled.

– On/Off timer deactivated:

– On/Off timer activated:

If the timer is activated, up to eight switch-ing points (events 1 - ) with different On/Off events can be defined.

Each switching point is defined by a week-day or weekday range, the switching point and the operating mode.

Configuration notes:

– the settings of an event remain active up to the next event.

– the software does not check the plausibility of the timer settings. Therefore, make sure your settings make sense.

– the On/Off timer overrides all other timers.

On/Off Timer

Timer :Off

Esc Set

On/Off Timer

Event 1 :06:00Event 2 :22:00Event 3 :--:--

Timer :On

Event 4 :--:--Esc Set

Event 2

Time :22:00Mode :On

Weekday :Mo-Fr

Esc Set

Page 58: condair cP3 - australianvs.com.au

6.6.9 Water management settings

Select “Water Manag.” in the settings menu, then press the <Set> key.

The water management settings menu appears. Press the < > and < > keys in order to select the individual settings and press the <Set> key to call up the modification dialogue for the selected setting.

Settings

Multi-Mode :SequenceWater Manag.:SetRemote Test :Set

GFCI-Mode :Off

Date :19.10.07Esc Set

Description of the water management settings

– Conductivity: Selecting the conductivity range of the supply water.

Factory setting: >125 μS/cmOptions: >125 μS/cm, <125 μS/cm

– Drain Factor: Setting the drain factor

Factory setting: 1.0Setting range: 0.5...2.0

– StandbyDrain: Selecting the type of draining which takes place after a certain time (see following setting) of standby operation.

Factory setting: FullOptions: Full (complete draining) Partial (partial draining) ** Off (draining deactivated)

** The cylinder is drained so far that the water does not touch the elec-trodes any longer.

– StandbyDelay: Setting the period of time in standby operation after which an automatic cylinder draining takes place.

Factory setting: 72 hoursSetting range: 1...720 hours

6.6.8 Setting the operation mode for multiple units

Settings

GFCI-Mode :OffMulti-Mode :SequenceWater Manag.:Set

On/Off Timer:Set

Remote Test :SetEsc Set

Select “Multi-Mode” in the settings menu, then press the <Set> key. In the upcoming modification dialogue you determine how the demanded steam capacity is shared among the units.

Factory setting: SequenceOptions: Sequence (sequential load sharing) Parallel (even load sharing)

Note: This setting is available only on main module A of multiple units.

Force Delay :72h

Water Manag.

Drain Factor:1.0StandbyDrain:FullStandbyDelay:72h

Conductivity:>125µS

Force Drain :OnEsc Set

Page 59: condair cP3 - australianvs.com.au

6.6.10 Performing remote relay tests

Settings

Water Manag.:SetRemote Test :SetDate :19.10.07

Multi-Mode :Sequence

Time :12:00Esc Set

Select “Remote Test” in the settings menu, then press the <Set> key.

The list with the remote relay tests appears, the first relay test is shown. Press the < > and < > keys in order to select the further relay tests available and press the <Set> key to activate/deactivate the correspond-ing relay for testing.

Remote Test

Remote Steam:Off

Esc Set

Remote ServiceOff 12.00.00Remote ErrorOffRemote Unit OnOn.11.2006 12.00.00Remote Analog Out-10.0 VRemote Analog Out-20.0 V

6.6.11 Setting the date

Select “Date” in the settings menu, then press the <Set> key. In the up-coming modification dialogue set the actual date (format:“dd.mm.yy”).

Settings

Remote Test :SetDate :19.10.07Time :12:00

Water Manag.:Set

Contrast :15Esc Set

Settings

Remote Test :SetDate :19.10.07Time :12:00

Water Manag.:Set

Contrast :15Esc Set

6.6.12 Setting the time

Select “Time” in the settings menu, then press the <Set> key. In the upcoming modification dialogue set the actual time (format:“hh.mm”).

– Force Drain: Activating/Deactivating the forced draining which takes place after a cer-tain time of operation. The forced draining takes place also during steam production.

Factory setting: OffOptions: On (Forced draining activated) Off (Forced draining deactivated)

– Force Delay: Setting the time of operation after which a forced draining takes place.

Factory setting: 72 hoursSetting range: 1...720 hours

Page 60: condair cP3 - australianvs.com.au

0

6.6.13 Setting the display contrast

Select “Contrast” in the settings menu, then press the <Set> key.In the upcoming modification dialogue set the desired value for the display contrast.

Factory setting: 15Setting range: 0 (no display) ...100 (display turns black)

Settings

Remote Test :SetDate :19.10.07Time :12:00

Water Manag.:Set

Contrast :15Esc Set

6.7 Modbus settings

Select the Modbus menu:Path: Main menu > User > Password entry: 8808 > Modbus

The settings for the Modbus appear.

Modbus

Parity :noneTimeout :5sXXXXXXXXXXXXXXXXXXXX

Modbus Addr.:1

11.11.2006 12.00.00Esc Set

Description of the Modbus settings

– Modbus Addr.: Setting the modbus address of the Condair CP3.

Factory setting: 1

Setting range: 1...247

– Parity: Selecting the parity bit for the data transmission

Factory setting: None

Options: None, Odd, Even

– Timeout: Setting the time out time for the data transmission.

Factory setting: 5 Seconds

Setting range: 1...600 Seconds

Page 61: condair cP3 - australianvs.com.au

1

7 Maintenance

Qualification of personnel

All maintenance work must be carried out only by well qualified and trained personnel authorised by the owner. It is the owner’s responsibility to verify proper qualification of the personnel.

General note

The instructions and details for maintenance work must be followed and upheld.

Only the maintenance work described in this documentation may be carried out.

Only use original Condair spare parts to replace faulty parts.

Safety

Some maintenance work requires removal of the unit cover. Please note the following:

WARNING!

Danger of electrical shock! You may get in touch with live parts when the unit is open. Touching live parts may cause severe injury or even lethal viola-tion.

Prevention: Before carrying out any maintenance work set the Condair CP3 out of operation as described in chapter 6.3 (switch off the unit, disconnect it from the mains and stop the water supply) and secure the unit against inadvertent power-up.

CAUTION!The electronic components inside the humidifier are very sensitive to electrostatic discharge.

Prevention: Before carrying out any maintenance work to the electrical or electronic equipment of the humidifier, appropriate measures must be taken to protect the respective com-ponents against damage caused by electrostatic discharge (ESD protection).

7.1 Important notes on maintenance

Page 62: condair cP3 - australianvs.com.au

2

7.2 Maintenance list

To maintain operational safety the Condair CP3 steam humidifier must be maintained at regular intervals. This is differentiated between the first maintenance after approx. 500 operating hours (I), steam cylinder maintenance after the yellow LED lights (II) and annual maintenance (III).

Below you will find a summary of the work to be carried out for each of the three maintenance stages.

Components Interval Work to be done

I II III

Cleanable steam cylinder Type D.. X X X Clean steam cylinder and electrodes and check for damage, replace if necessary. Note: The steam cyl-inder must be replaced after a maximum operating time of ,000 h.

Electrode plug X X X Check to see firmly positioned (remove cover and tighten fixing screw with hexagonal head socket wrench). Warning! This work should only be carried out by an electrician.

Replacement steam cyl. type A.. X Remove and replace.

Drain pump X Remove, disassemble and clean, replace if neces-sary.

Steam cylinder receptacle X Inspect, clean if necessary.

Inlet valve X Remove and clean filter insert, replace if neces-sary.

Drain pipe and siphon X Inspect, clean if necessary (decalcify and rinse out).

Steam installation X X Inspect steam and condensate hoses for cracks and to see that they are correctly attached, replace faulty hoses.

Water installation X X Inspect water hoses in the unit for cracks and to see that they are correctly attached, replace faulty hosesCheck supply pipe is tight, make tight if necessary. Clean water filter, if available.

Electrical installation X X Check all cables in the unit are firmly positioned and examine status of insulation.

Page 63: condair cP3 - australianvs.com.au

3

7.3 Removing and installing parts for maintenance

7.3.1 Removal and installation of the steam cylinder

1. Use a screwdriver to undo the two screws fixing the front panel to the unit, then remove the front panel.

2. Units with steam hose connector in housing top: release the two hose clamps on the rubber sleeve using a screwdriver, then detach the rubber sleeve from the connection in the unit cover and from the steam outlet connection of the steam cylinder.

Units without steam hose connector in housing top (not shown): release the hose clamp on the steam hose using a screwdriver, then detach the steam hose from the steam outlet con-nection of the steam cylinder.

1 2

3 4

3. Remove all plugs from the electrodes and from the level sensor.

. Loosen the two screws of the steam cylinder fixing device by a few turns, then push the fixing device upwards until it comes loose and remove it.

Page 64: condair cP3 - australianvs.com.au

. Carefully lift steam cylinder away from the cylinder receptacle, then remove it to the front.

CAUTION!Put steam cylinder down carefully to avoid damage to the lower connection piece!

Installation of the steam cylinder follows the reverse sequence. Observe the following:

– Before installing the steam cylinder in the unit, check the O-ring of the cylinder receptacle for damage and replace if necessary.

– Moisten the O-ring of the cylinder receptacle with water (do not use grease or oil), then insert steam cylinder into the receptacle and push it down to the stop.

– Attach the electrode plugs and the level sensor plug to the respective electrode and sensor con-nections according to the following table.

Steam cylinder type

A363 / D363A464 / D464

A664 / D664A674 / D674

Cable configuration

5

Sensor white

brown

red

blackSensor white

brown

red

black brown

red

black

– Fasten steam hose on the connector in the unit cover and on steam connector of the cylinder with hose clamps.

CAUTION! A leaky steam hose can cause damage due to moisture inside the unit.

CAUTION!The outlet connector of the steam cylinder is made of plastic. Do not overtighten the hose clamp on the steam connector of the steam cylinder.

Page 65: condair cP3 - australianvs.com.au

7.3.2 Disassembly and assembly of the cleanable steam cylinder type D...

1. Fasten electrode snap fastenings and push electrodes approx. 2 cm downwards into the steam cylinder.

2. Release clamp clips of the cylinder cover and raise cover.

3. Remove carefully electrodes by lifting upwards.

. Remove O-rings from the electrodes.Note: Intact O-rings can be reused.

The assembly of the cleanable steam cylinder follows the reverse sequence. Observe the following:

– Before assembling the steam cylinder, check the O-ring in the steam cylinder cover and the O-rings on the electrodes for damage, and replace if necessary. Make sure to relocate O-rings correctly.

– Insert electrodes into steam cylinder cover and push them upwards until the snap fasteners engage.

– Place the cylinder cover (with mounted O-ring) in the correct position (align the two cams on the steam cylinder body with the corresponding grooves in the cylinder cover) on the cylinder body and secure cover with the fastening clips.

1 3

2

4

Page 66: condair cP3 - australianvs.com.au

7.3.3 Removal and installation of the water cup and the water hoses

To improve accessibility for removing the water cup and the water hoses we recommend to remove the steam cylinder first (see chapter .3.1).

1. Release hose clamps using pliers, then disconnect all hoses from the corresponding connectors and remove the hoses.Note: The hoses connected to the water cup may also be removed together with the water cup (see illustration) and then disconnected from the connectors of the water cup outside the unit.

2. Carefully pull fixing clip of the water cup to the front, then push water cup down from the hold-ing device and remove it to the front.

The installation of the water cup and the water hoses follows the reverse sequence. Before fixing the water hoses to the connector using the hose clamps, align the hoses in a way that they are not twisted.

Page 67: condair cP3 - australianvs.com.au

7.3.4 Removal and installation of the drain pump

The steam cylinder does not need to be removed when removing the drain pump.

1. Detach electric cables (polarity of the cables must not be observed).

2. Release hose clamps and remove the hoses from the connectors.

3. Pull the drain pump off the holding device.

. Separate the electric motor from the pump body: release the lock on the bayonet catch, then counter-rotate the electric motor and the pump body.

The assembly and the installation of the drain pump follows the reverse sequence. Before as-sembling the pump, check O-ring for damage and replace if necessary. Then, place the O-ring on the centering collar and moisten the O-ring with water.

7.3.5 Removal and installation of the inlet valve

The steam cylinder does not need to be removed when removing the inlet valve.

1. Detach electric cables (polarity of the cables must not be observed).

2. Release hose clamp and remove the hose from the connector.

3. Unlock union nut of the water pipe and remove water pipe.

. Pull the inlet valve off the holding device.

The installation of the inlet valve follows the reverse sequence. The union nut of the water pipe must be tightened by hand only.

1

2

2

3

4

2

3

3

1

Page 68: condair cP3 - australianvs.com.au

7.4 Notes on cleaning the unit components

Unit component What to clean and how to clean

Steam cylinder cover Steam cylinder bodyCylinder strainer

• Knock off or brush away any limescale as much as pos-sible (do not use a wire brush). If the parts are heavily calcified, place them in an % formic acid solution (observe safety notes in chap-ter 7.5), until the limescale comes off.

• Finally wash parts in a lukewarm soap solution and rinse well with tap water.

Heating electrodes • Immerse the heating electrodes (up to 2 cm below the snap fastening) in a container with -percent formic acid (observe safety notes in chapter 7.5). Allow the acid to take effect until the limescale has dissolved.Note: The heating elements do not have to be entirely free from scale.

• Finally rinse the heating electrodes well with tap water and let them dry.

CAUTION!

On no account remove limescale from the heating electrodes using tools (screw-driver, scraper, etc.) or by striking. This could damage the heating elements.

Water hoses • Remove any limescale by slightly knocking on the tubes using a rubber hammer. Then, rinse the tubes well with hot tap water.

Inlet valve

Strainer insert

• Remove strainer insert with pointed pliers. Use a brush (do not use a wire brush) to remove any limescale.

• Wash strainer insert with a lukewarm soap solution, then rinse well with tap water.

Let the inlet valve dry before reinstallation!

Page 69: condair cP3 - australianvs.com.au

Unit component What to clean and how to clean

Drain pump

O-ring

pump wheel

• Use a brush to remove any limscale from the pump hous-ing and the pump wheel (do not use a wire brush).

• Then, wipe pump wheel with a damp cloth. Wash the pump housing with a lukewarm soap solution and rinse well with tap water.

Cylinder receptacle in the unit • Remove any limscale from the cylinder receptacle and its connectors using a brush (do not use a wire brush).

• Wash the cylinder receptacle with a lukewarm soap solution and rinse well with tap water.

Water cup • Remove any limscale from the water cup and its con-nectors using a brush (do not use a wire brush).

• Wash the water cup with a lukewarm soap solution and rinse well with tap water.

Interior of the unit (water side only)

Wipe the interior of the unit with a damp cloth without using any cleaning agent.

CAUTION!Take care that the electrical connections and the electronic components remain dry.

7.5 Notes on cleaning agents

Only use cleaning agents stated in the table above. The use of disinfectants is only permitted if they do not leave any toxic residues. In any case the parts must be thoroughly rinsed with water after cleaning.

WARNING!

Formic acid is indeed harmless to the skin, but it attacks the mucous membranes. Therefore prevent your eyes and respiratory tracts from getting in touch with the acid and its vapours (wear goggles and work in a well ventilated room or outside).

CAUTION!Do not use any solvents, aromatized or halogenized hydrocarbons or other ag-gressive substances as they may cause damage to the components of the unit.

It is mandatory to observe and comply with the information and instructions regarding cleaning agents. Observe in particular: all information relating to the protection of personnel, environmental protection and restrictions regarding usage.

Page 70: condair cP3 - australianvs.com.au

0

7.6 Resetting the maintenance indication

After completing maintenance work, the maintenance indication (yellow LED lights) must be reset as follows:

Select the maintenance menu:Path: Main menu > User > Password entry: 8808 >

Select “Cyl. A Reset” (or “Cyl. B Reset”) in the maintenance menu, then press the <Set> key.

The reset dialogue shows up in the display. Press the <Yes> key to reset the maintenance counter.Note: Press the <No> key if you wish to abort the reset procedure.

To return to the standard operating display press the <Esc> key several times.

Maintenance

Cyl. A Reset:Set

XXXXXXXXXXXXXXXXXXXX

HistoryReset:Set

11.11.2006 12.00.00Esc Set

Cyl. A Reset

Attention ! Resetwithout cyl. Mainten.

Are you sure?

is very dangerous!Esc SetNo Yes

Page 71: condair cP3 - australianvs.com.au

1

8 Malfunctions

Important! Most operational malfunctions are not caused by faulty equipment but rather by improper installation or disregarding of planning guidelines. Therefore, a complete fault diagnosis always involves a thorough examination of the entire system. Often, the steam hose connection has not been properly executed, or the fault lies with the humidity control system.

8.1 Malfunction list

8.1.1 System faults

Warning Error Cause Remedy

LED Display LED Display

CP3Cardmissing(Testrunpossible)

CP3Cardmissing

––– WarningW1:CP3-CardMissing

redlights

ErrorE1:CP-CardMissing

NoCP3Cardinstalledonthecontrolboard.

InstallCP3Cardorstarttestrun.

CP3Cardisempty

––– ––– redlights

ErrorE2:CP-CardEmpty

NodatastoredontheCP3Card. InstallnewCP3Card.

CP3Cardisdefective

––– ––– redlights

ErrorE3:CP-CardInvalid

InvaliddatastoredontheCP3Card. InstallnewCP3Card.

CP3Cardisincompatible

––– ––– redlights

ErrorE4:CP-Cardincompat

TheinstalledCP3Cardisnotcompatiblewiththehardwareoftheunitorwiththebasicsettingsofthecontrolelectronics.

InstallcorrectCP3Card.LetyourCondairservicetechnicianadjustthebasicsettings.

ModuleBmissing

––– ––– redlights

ErrorE5:ModulBMissing

Module B not correctly connected or de-fective.

CheckmoduleBandbothconnectingcables.

Extensionunitmissing Mainunitmissing

––– WarningW6:ExtendedMissing

redlights

ErrorE6:MainMissing

Nocommunicationbetweenmainunitandextensionunit.

Check/connectbuscable.

Mainorextensionunitnotswitchedon. Switchonmainunitand/orextensionunit.

Extensionunitisinerrorstatus

––– ––– redlights

ErrorE7:ExtendedError

Thedisplayofthemainunitindicatesthattheextensionunitisinerrorstatus.Thetypeoferrorisshownonthedisplayoftheextensionunit.

Takecorrespondingmeasuresaccordingtotheindicatederrortype.

Extensionunitisnotcompatible

––– ––– redlights

ErrorE8:Extend.Incompat.

TheCP3Cardofthemainunitisnotcompat-iblewiththeoneoftheextensionunit.

InstallcorrectCP3Cardsintotheunits.

Wronghardwaresettings

––– ––– redlights

ErrorE9:IllegalSettings

Falsetestrunparameters. LetyourCondairservicetechnicianadjustthe test runparameters (heatingvoltage,Cylinder-No.).

Page 72: condair cP3 - australianvs.com.au

2

Warning Error Cause Remedy

LED Display LED Display

Hardwarefault

––– ––– redlights

ErrorE10:FlashR/WFault

Controlboarddefective. Replacecontrolboard.

––– ––– ErrorE11:ClockR/WFault

Backupbatteryoncontrolboarddischarged.

Lethavethebackupbatterybereplaced.

On/Offtimeractive

––– WarningW12:TimerDisable

––– ––– ThesystemisdeactivatedviatheOn/Off-Timer.

None.IfnecessaryadjustOn/Offtimersettings.

8.1.2 Unit faults

Warning Error Cause Remedy

LED Display LED Display

Externalsafetychainisopen

redandgreenflash

WarningW20A:Safetyloopopen

––– ––– Ventilationinterlockopen. Ifapplicable,check/turnonventilationsystem.

Airflowmonitortriggered. Checkventilator/filteroftheventilationsystem.

Safetyhumidistattriggered. Wait.Ifapplicable,checksafetyhumidistat

Max.fillinglevelofsteamcylinderreached

Max.fillinglevelofsteamcylinderreachedbut

noheatingcurrent

––– WarningW21A:Cyl.Max.Level

redlights

ErrorE21A:Cyl.Max.&NoCurr

Water conductivity too low (after initialoperation).

Waituntilthemineralcontentofthecylinderhasincreased

Water conductivity too low for type ofsteamcylinder.

Selectcorrectsteamcylindertype.

Phasefailureheatingvoltage. Checkserviceswitchinthemainssupplylineandswitchonifapplicable.Checkmainsfuse(s)andreplaceifapplicable.

Permissiblefillingtimeex-ceeded(20minutes)

Permissiblefillingtimeex-ceeded(morethan4hours)

––– WarningW22A:Max.Filltime

redlights

ErrorE22A:Max.Filltime

Water supply obstructed/shut-off valveclosed/waterpressuretoolow.

Inspectwatersupply (filter,waterpiping,etc.),check/openshut-offvalve,checkwaterpressure.

Inletvalveblockedordefective. Inspectstrainerinsertintheinletvalve,ifapplicablecleanstrainerinsertorreplaceinletvalve.

Excessivebackpressureinthesteamline(duct pressure too high, steam line toolong or kinked), causing water loss viafillingcup.

Check duct pressure, inspect steam in-stallation. If applicable install pressurecompensationkit(seeoptions).

Leakageinthewatersystem. Inspectwatersystemandsealifnecessary.

Page 73: condair cP3 - australianvs.com.au

3

Warning Error Cause Remedy

LED Display LED Display

Noelectrodecurrentformorethan20minutes

Noelectrodecurrentformorethan4hours

––– WarningW23A:NoCurrent

redlights

ErrorE23A:NoCurrent

Phasefailureheatingvoltage. Inspect/turnonserviceswitchofthemainssupplyline.Inspectthefusesofthemainssupply,replaceifnecessary.

Water supply obstructed/shut-off valveclosed/waterpressuretoolow.

Inspectwatersupply (filter,waterpiping,etc.),check/openshut-offvalve,checkwaterpressure.

Inletvalveblockedordefective. Inspectstrainerinsertoftheinletvalve,ifapplicablecleanstrainerinsertorreplaceinletvalve.

Excessivebackpressureinthesteamline(duct pressure too high, steam line toolong or kinked), causing water loss viafillingcup.

Check duct pressure, inspect steam in-stallation. If applicable install pressurecompensationkit(seeoptions).

Leakageinthewatersystem. Inspectwatersystemandsealifnecessary.

Electrodecurrentinrelationtothesteamdemandtoohigh

Electrodecurrentinrelationtothesteamdemandtoohigh

––– WarningW24A:OverCurrent

redlights

ErrorE24A:OverCurrent

Humiditydemandhasdecreasedtoofast. Automaticadaptationoftheoperatingpoint.

Drainpumpdefective. Inspectdrainpump,replaceifnecessary.

Draininsteamcylinderblocked. Clean/replacesteamcylinder.

Waterconductivitytoohighforthistypeofsteamcylinder.

Selectcorrectsteamcylindertype.

Max.admissibleelectrodecurrentexceeded

Max.admissibleelectrodecurrentexceeded

––– WarningW25A:ExcessCurrent

redlights

ErrorE25A:ExcessCurrent

Drainpumpdefective. Inspectdrainpump,replaceifnecessary.

Draininsteamcylinderblocked. Clean/replacesteamcylinder.

Waterconductivitytoohighforthistypeofsteamcylinder.

Selectcorrectsteamcylindertype.

Maincontactorjammed

––– ––– redlights

ErrorE26A:Req.OffCurrent

Maincontactorjammedinactivatedposi-tion.

Inspectmaincontactor,replaceifnecessary.

Foamdetection Foamdetection(4automaticdrainingswithin24hours)

––– WarningW27A:Foam

redlights

ErrorE27A:Foam

Foaminginsteamcylinder. Drainsteamcylinderviadrainkey(sev-eraltimes,ifnecessary).Checkqualityofthesupplywater.

Steamcylinderneedsservice Serviceintervalforsteamcylinderexceeded

yellowlights

WarningW28A:Cyl.Maintenance

redandyellowflash

ErrorE28A:Cyl.Maintenance

Mineraldepositsand/orelectrodesspent. SteamcylinderTypeA:replaceSteamcylinderTypeD:clean

Important:Afterreplacementorcleaningofthesteamcylinder,resetthemaintenancecounter(seechapter7.6).

Steamcylinderneedsservice Max.operatinghoursofthesteamcylinderreached

yellowlights

WarningW29A:Cyl.Maintenance

redandyellowflash

ErrorE29A:Cyl.Maintenance

Maximum operating hours of the steamcylinderreached.

SteamcylinderTypeA:replaceSteamcylinderTypeD:clean

Important:Afterreplacementorcleaningofthesteamcylinder,resetthemaintenancecounter(seechapter7.6).

Page 74: condair cP3 - australianvs.com.au

8.2 Notes on fault elimination

WARNING!

For the elimination of faults set the steam humidifier out of operation as described in chapter .3, separate the unit from the mains and secure it against inadvert-ent power-up.

The elimination of faults must be carried out by qualified and well trained professionals only.Malfunctions relating to the electrical installation (e.g. replacement of fuses) must be repaired by authorized personnel or by your Condair representative’s service technician only.

Repair work and the replacement of faulty components must be carried out by your Condair repre-sentative’s service technician only!

8.3 Resetting the error indication (red LED lights)

To reset the error indication:

Disconnect the steam air humidifier from the mains. Wait approx. 5 seconds, then reconnect the unit to the mains.

Note: If the fault has not been eliminated, the error indication reappears after a short while.

Warning Error Cause Remedy

LED Display LED Display

Humiditysensorsignal(signalY)missing

Humiditysensorsignal(signalY)missingformorethan1minute

––– WarningW32A:Ctrl.Sens.Broken

redlights

ErrorE32A:Ctrl.Sens.Broken

Nosensorsignalpresentatsignalinput(SignalY).

Checkhumiditysensor(signalY),replaceifnecessary.Inspectwiring.

Signalofhumiditylimitationsen-sor(signalZ)missing

Signalofhumiditylimitationsen-sor(signalZ)missingformore

than1minute

––– WarningW33A:Lim.-Sens.def.

redlights

ErrorE33A:Lim.Sens.Broken

Nosensorsignalpresentatsignalinput(signalY).

Checkhumiditysensor(signalY),replaceifnecessary.Inspectwiring.

ModuleA(B)lockedviaModbus

––– WarningW34A:Modbusdisable

––– ModuleA(B)lockedbecausethecorre-spondingModbusregisterisdeactivated.

ActivatethecorrespondingModbusregister.

ModbusTimeout(5s)

––– ––– redlights

ErrorE35A:ModbusTimeout

NoactualdemandorhumiditysignalreceivedviaModbus.

Sendactualdemandorhumiditysignal.

Standbydrainingofsteamcylinderactive

––– WarningW36A:StandbyDrain

––– ––– Automaticstandbydrainingofsteamcylinderactive.

Nomeasuresmustbetaken.

Forceddrainingofsteamcylinderactive

––– WarningE37A:ForcedDrain

––– ––– Forceddrainingofsteamcylinderactive. Nomeasuresmustbetaken.

Page 75: condair cP3 - australianvs.com.au

9 Taking out of service/Disposal

9.1 Taking out of service

If the Condair CP3 must be replaced or if the humidification system is not needed any more, proceed as follows:

1. Take the unit out of operation as described in chapter .3.

2. Have the unit (and all other system components, if necessary) unmounted by a qualified service technician.

9.2 Disposal/Recycling

Dismantled components must be disposed of and/or recycled according to the local regulations. In case of doubt please contact your Condair supplier.

Page 76: condair cP3 - australianvs.com.au

10 Product specifications

10.1 Technical data

Heatingvoltage230V/1~/50..60HzUnitmodel: Basic Pro

5...8Steamcapacityinkg/h: 5...8Max.powerconsumptioninkW 3.8...6.0Heatingvoltage230V/3~/50..60HzUnitmodel: Basic Pro Basic Pro Basic Pro Basic Pro Basic Pro Pro Pro

5...8 9...15 16...21 22...30 44/50 75/90 100/120Steamcapacityinkg/h: 5...8 9...15 16...21 22...30 44/50 75/90 100/120Max.powerconsumptioninkW 3.8...6.0 6.8...11.3 12.0...15.8 16.5...22.5 33.0/37.6 56.5/76.5 75.0/90.0Heatingvoltage400V/3~/50..60HzUnitmodel: Basic Pro Basic Pro Basic Pro Basic Pro Basic Pro Pro Pro

5...8 9...15 16...25 26...45 52/60/70/80/90 105/120/135 152/160/180Steamcapacityinkg/h: 5...8 9...15 16...25 26...45 52/60/70/80/90 105/120/135 152/160/180Max.powerconsumptioninkW 3.8...6.0 6.8...11.3 12.0...18.8 19.5...33.8 39.0...67.5 78.8...101.3 114.0...135.0Controlvoltage 1x230V/50-60Hz 2x230V/50-60HzOperatingconditionsAdmissiblewaterpressure 1...10barWaterquality Untreateddrinkingwaterwithaconductivityof125...1250uS/cmAdmissiblewatertemperature 1...40°CAdmissibleambienttemperature 1...40°CAdmissibleambienthumidity max.75%rhAdmissibleductairpressure -0.8kPa...1.5kPa;overpressurekit(option)upto10.0kPaTypeofprotection IP20Conformity CE,VDE,GOSTDimensions/WeightsHousing(WxHxD)inmm 456x620x280 1 1 1 1

559x667x350 1 1 1 1 2 2 3 4Netweightinkg 21 21 21 21 28 28 28 28 2x28 2x28 3x28 4x28Operatingweightinkg 26 26 32 32 32 32 65 65 2X65 2X65 3X65 4x65Equipment/optionsSteamcylindertype(TypeA..standardequipment)

A3.../D3... 1 1A4.../D4... 1 1A6.../D6... 1 1 1 1 2 2 3 4

Steamhoseconnector SC22 1 S SC60 1 S SC80 1 S 1 S 2 S S SSteamhoseconnectorwithcondensatetrap

SCCT22 1SCCT60 1SCCT80 1 1 2

Condensatetrap CT22 1 CT60 1 CT80 1 1 2 3 4Cablegland PG 1 S 1 S 1 S 1 S 1 S S SOverpressureset OPS 1 1 1 1 1 1 1 1 2 2 3 4Remoteoperatingandfaultindication RFI 1 S 1 S 1 S 1 S 1 S S STerminalsheatingvoltage M-THV 1 S 1 S

L-THV 1 S 1 S 2 S S SMountingprofile MP 1 1 1 1 1 1 1 1 1 1 3 4Internalcontrolvoltagewithterminals M-CVI 1 1 1 1

L-CVI 1 1 1 1 1 1 2 2Transformer400V/230V M-Trafo 1 1 1 1

L-Trafo 1 1 1 1 1 1 2 2Housingfrontcover,stainlesssteel M-INOX 1 1 1 1

L-INOX 1 1 1 1 2 2 3 4AccessoriesSteamdistributionpipe 41-... 1 1

61-... 1 181-... 1 1 1 1 2 2 3 4

SteamdistributionsystemOptiSorp System1 1 1 1 1 1 1 1 1System2 1 1System3 1System4 1

Fanunit FANB15 1 1FANB45 1 1 2FANP15 1 1FANP45 1 1 2 3 4

Steamhose/meter DS22 1 1DS60 1 1DS80 1 1 1 1 2 2 3 4

Condensatehose/meter KS10 1 1 1 1 1 1 1 1 2 2 3 4

Page 77: condair cP3 - australianvs.com.au

10.2 Unit dimensions

Condair CP3 5...15 (dimensions in mm)

456

ø42.5178

177 73

28

105

71

28

93

34 40

280

150 228

51

180 90

500620

Page 78: condair cP3 - australianvs.com.au

Condair CP3 16...45 (Dimensions in mm)

559

228

ø42.566

7

40

28105

71

175

34

93350

73

177

284

51

216 144

545

32

Page 79: condair cP3 - australianvs.com.au

© Walter meier (climate international) ltd. 2007, Printed in SwitzerlandTechnical modifications reserved

Page 80: condair cP3 - australianvs.com.au

manufacturer:Walter meier (climate international) ltd.Talstr. 35-37, P.o. Box, ch-8808 Pfäffikon (Switzerland)Phone +41 55 416 61 11, Fax +41 55 416 62 62www.waltermeier.com, [email protected]

conSulTing, SaleS anD Service:

reg.no. 40002-2

Solutions for indoor climate