    Annexure A

    MARMOL

    ACSR Conductors

    Bare conductors shall be of the ACSR (Aluminum Conductor SteelReinforced) type, with a

    cross-section of 70/12 mm2.The conductors and their testing procedure shall comply with the

    latest edition of the recommendations, standards and conditions directly or indirectly applicable,

    which include but are not necessarily limited to: DIN-VDE 0210, 0211, DIN 46391, 48201,

    48204, 48303, 57103 and IEC61089.

    Equipment, material or workmanship meeting other internationally recognized standards that

    ensure an equivalent or higher quality than the standard specified will be accepted.

    Operating conditions:

    Mormal operating temperature: 80C

    Maximum temperature (short circuit): 160C

    Maximum operating load: 70 N/mm

    Average span: 90 m

    Every day temperature 25C

    Temperature with max wind 10C

    Temperature with ice -40C

    Packing and delivery

    Bare conductors shall be delivered on non-returnable drums. Drums shall contain a

    quantity of 1000 m each.

    Conductors shall be placed on reels having a drum diameter sufficiently large so that the bending radius

    will not unduly modify the physical properties of the conductors.

    In order to protect the aerial cables against adverse effects of water and moisture, both ends shall be

    coated with hot melted paste and provided with shrunk on end-caps.

    Conductors and aerial cables shall be protected during ordinary handling and transportation to

    prevent damage.

    Proof of quality

    The Supplier shall state all technical particulars and basic design characteristics of the conductors

    as requested in the data sheets, and shall additionally submit the following:

    Page 1 of 3

  • 8/10/2019 Conductors and Accessories_Annex A

    2/3

    AEPCAfghan Electrical Power Corporation - -

    Page 2 of 3

    Street 15, lane3, House 260 260315

    Wazir Akbar Khan

    KabulAfghanistan -Mobile: +93(0)700 285 246 Or 0700 285 306

    :

    028530607)0(930700285246 +

    )0(93+ 799 323 890 Or 0799 323 060 93+ )0( [email protected] [email protected]

    www.aepc.af www.aepc.af

    Type test certificates issued by an internationally acknowledged testing laboratory

    Manufacturing methods and technology

    Drawing of drum giving its main dimensions and weight

    Description of quality assurance program

    Conductor

    Reference lists stating deliveries and installation in the past 5 (five) years, including quantity soldand addresses of customers.

    Inspection and testing

    Tests shall be carried out to the relevant standards and recommendations, supplemented by the

    specific requirements set out in the specification.

    In the absence of IEC standards, inspections and tests shall be carried out in such a manner as to be at

    least equivalent to the conditions, provisions and definitions set out in one of the standards listed in this

    specification.

    The Supplier shall provide with his offer a program of factory acceptance tests, which he intends to

    carry out.

    Type test

    Type tests shall be carried out if the Supplier is not in a position to produce type test certificates that are

    duly approved by an independent authority of international repute and that cover the exact design (type)

    of equipment to be supplied by the Tenderer and manufactured in complete accordance with this

    Specification.

    Routine tests

    These tests will be carried out on the whole batch of conductors and cables and will include:

    Visual inspection (conductor examination)

    Conductor resistance measurement carried out in DC and corrected to 20C

    Continuous measurement of insulation thickness (for aerial cable only) Checking of outside diameter and eccentricity of finished conductors

    Checking of mechanical characteristics of the insulating material (for aerial cable only)

    Inspection for conformity with specification.

    Page 2 of 3

  • 8/10/2019 Conductors and Accessories_Annex A

    3/3

    AEPCAfghan Electrical Power Corporation - -

    Page 3 of 3

    Street 15, lane3, House 260 260315

    Wazir Akbar Khan

    KabulAfghanistan -Mobile: +93(0)700 285 246 Or 0700 285 306

    :

    028530607)0(930700285246 +

    )0(93+ 799 323 890 Or 0799 323 060 93+ )0( [email protected] [email protected]

    www.aepc.af www.aepc.af

    Acceptance test

    The following acceptance test shall be carried out in the Employers or his engineers presence to

    check the quality of a consignment:

    Visual inspection

    Check of dimensions and quality of workmanship

    Dielectric tests on samples taken at random (for aerial cables only)

    Tests to DIN 48201 (for bare conductors)

    Study of the results of routine testing and repeating if necessary some tests.