SENTRON
Monitoring Devices
siemens.com/lowvoltage
Configu-rationManual
Edition10/2015
© Siemens AG 2016
![Page 2: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/2.jpg)
© Siemens AG 2016
![Page 3: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/3.jpg)
Siemens · 10/2015
For further technical product information:
Siemens Industry Online Support:www.siemens.com/lowvoltage/product-support .
→ Entry type: Application exampleCertificateCharacteristicDownloadFAQManualProduct noteSoftware archiveTechnical data
2 Introduction
Monitoring devices for electrical values
5 5SV8 residual current monitors11 5TT3 voltage relays19 5TT3 voltage and frequency relays22 5TT6 current relays27 5TT3 reverse power relays 28 5TT3 fuse monitors29 5TT3 phase and phase sequence
monitors31 5TT3 insulation monitors for industrial
applications34 7LQ3 monitors for medical premises
Monitoring devices for plants and equipment
53 5TT3 fault signaling units55 5TT5 EMERGENCY STOP modules57 5TT3 level relays59 5TT3 line circuit relays60 5TT3 p.f. monitors 62 5TT3 motor protection relays
Monitoring Devices
© Siemens AG 2016
![Page 4: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/4.jpg)
2 Siemens · 10/2015
Introduction
Monitoring Devices
■ Overview
Devices Page Application Standards Used in
Non
-res
iden
tial
bui
ldin
gs
Res
iden
tial
bui
ldin
gs
Ind
ustr
y
Monitoring devices for electrical values5SV8 residual current monitors 5 To increase system availability and
operating safety through continuous monitoring of residual current in electrical systems and signaling if a defined threshold is exceeded.
IEC 62020; EN 62020 ✓ -- ✓
Modular residual current devices (MRCD)
5 The MRCD is a modular residual current device type for personnel and fire protection.
DIN EN 60947-2(Appendix M),
IEC 60947-2 (Appendix M)
✓ -- ✓
5TT3 voltage relays 11 Monitoring the voltage of emergency lighting in public buildings, short-time failures of 20 ms, for ensuring operational parameters for devices or system components or monitoring the neutral conductor for breaks.
IEC 60255; DIN VDE 0435-303; DIN VDE 0108; DIN VDE 0435; DIN VDE 0633
✓ -- ✓
5TT3 voltage and frequency relays 19 The voltage and frequency relay monitors the status of the grid in the case of in-plant generation systems. Violation of an upper or lower limit results in shutdown and disconnection of the generation system from the grid. This ensures a stable incoming supply system.
IEC/EN 60255-1; IEC/EN 61000; VDE-AR-N-4105
✓ ✓ ✓
5TT6 current relays 22 Monitoring of emergency and signal lighting and motors.
All current relays can be short-time overloaded and connected either with direct measurement or through transformers.
IEC 60255; DIN VDE 0435-303
✓ -- ✓
5TT3 reverse power relays 27 Reverse power relays are used in power supply systems, e.g. photovoltaic, wind power, water power and unit-type cogenerating stations, to control the reverse power. They prevent voltage being returned from the grid and causing damage if the infeed system itself fails or is damaged.
IEC 50255;DIN VDE 0435-303
✓ ✓ ✓
© Siemens AG 2016
![Page 5: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/5.jpg)
3Siemens · 10/2015
Monitoring Devices
Introduction
5TT3 fuse monitors 28 Monitoring of all types of low-voltage fuses.
Can be used in asymmetric systems afflicted with harmonics and regenerative feedback motors.
IEC 60255; DIN VDE 0435
✓ -- ✓
5TT3 phase and phase sequence monitors
29 For the visual signaling of phase failures or phase sequences in three-phase systems.
The phase sequence is arbitrary. The device is also suitable for 1, 2 or 3-phase operation.
IEC 60255; DIN VDE 0435
-- -- ✓
5TT3 insulation monitors for industrial applications
31 To increase system availability and operating safety through continuous monitoring of the isolation resistance in non-grounded direct voltage or AC voltage systems.
IEC 60255; IEC 61557
-- -- ✓
7LQ3 monitors for medical premises
34 For the insulation monitoring of a medical IT system or load current monitoring of an IT system transformer for a non-permissible temperature rise.
Monitoring of the voltage supply with automatic switchover.
EN 61557-8; IEC 61557-8; DIN VDE 0100-710; IEC 60364-7-710
✓ -- --
Monitoring devices for plants and equipment5TT3 fault signaling units 53 Evaluation and display of fault alarms
and alarm signals for monitoring industrial plants and control systems. With 4 inputs and connections for 39 expansion fault signaling units.
IEC 60255, DIN VDE 0435-303
✓ -- ✓
5TT5 EMERGENCY STOP modules 55 For EMERGENCY-OFF switching in accordance with the Directive 98/37/EC on Safety of Machines. Safe types of circuits for machines, plants or test stations in industrial, commercial and private enterprise applications.
According to the Machinery Directive 98/37/EC; EN 954-1
✓ -- ✓
Devices Page Application Standards Used in
Non
-res
iden
tial
bui
ldin
gs
Res
iden
tial
bui
ldin
gs
Ind
ustr
y
© Siemens AG 2016
![Page 6: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/6.jpg)
4 Siemens · 10/2015
Introduction
Monitoring Devices
Devices Page Application Standards Used in
Non
-res
iden
tial
bui
ldin
gs
Res
iden
tial
bui
ldin
gs
Ind
ustr
y
5TT3 level relays 57 Control of liquid levels in containers with 3 electrode connections for 1-step and 2-step level control. High immunity to interference of the measuring circuit isolated from the system.
IEC 60255, DIN VDE 0435
✓ -- ✓
5TT3 line circuit relays 59 For disconnecting the voltage of unused lines when loads are disabled.
IEC 60255,DIN VDE 0435
-- ✓ --
5TT3 p.f. monitors 60 For the monitoring of asynchronous motors for underload and no-load operation, e.g. fan monitoring in the case of V-belt breakage, filter blockages, pump monitoring in the event of valve closure or dry runs.
IEC 60255, IEC 61557
-- -- ✓
5TT3 motor protection relays 62 For the prevention of thermal motor overloads, e.g. due to high switching frequency, single-phasing, disabled cooling or excessive ambient temperatures. With detection of wire breaks in the sensor circuit.
IEC 60255, DIN VDE 0435
-- -- ✓
© Siemens AG 2016
![Page 7: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/7.jpg)
5Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
5SV8 residual current monitors
■ Overview
Plant and operating safety are becoming increasingly important alongside the protection of personnel. Shutdowns due to the unexpected tripping of protective devices cause high costs. However, it is possible to detect residual currents in the electrical installation before the protective device responds.
Residual current devices (RCD)
Residual current monitors (RCM) monitor residual current in electrical installations and issue a signal when the residual current exceeds a set value.
RCMs are used primarily in plants where a fault should result in a signal, but not in disconnection. This enables plant operators to detect faults and eliminate their causes before the protective devices disconnect the installation, which increases plant and operating safety and cuts costs.
Modular residual current devices (MRCD)
Modular residual current devices (MRCD) monitor residual currents in electrical systems and trip the MCCB via a shunt or UVR after an adjustable advance warning if the residual current exceeds a defined value. See accessories for molded case circuit breakers in Catalog LV 10, chapter "Molded case circuit breakers".
This makes it possible for you to offer molded case circuit breakers with personnel and fire protection in compliance with EN 60947-2 (Appendix M) (also as a retrofit).
Summation current transformer
The summation current transformer detects all conductors required to conduct the current, including the neutral conductor where applicable. In a fault-free system, the magnetizing effects of the conductors through which current is flowing cancel each other out for the summation current transformer, i.e. the sum of all currents is zero. If a residual current is flowing due to an insulation fault, a residual magnetic field is left in the core of the transformer and produces a voltage. This voltage is evaluated using the electronics of the RCM/MRCD. The switched contact can be used to operate an acoustic/optical signaling device, a higher-level control system or a circuit breaker for example.
Time characteristic of the rated residual current ΙΔn
■ Benefits
• Higher plant availability and operating safety through permanent monitoring of residual currents
• Adjustable limit values for residual current and response time enable timely detection and signaling – plant shutdowns are often avoidable
• Devices for every application: The summation current transformers are available in various sizes; the RCMs can be used optionally for signaling and/or switching
• Additional fire protection can be implemented using the monitoring system
100 % n
50 %
t
n
nR
esid
ual c
urre
nt
Time
Alarm
Disconnection
I202
_160
44
© Siemens AG 2016
![Page 8: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/8.jpg)
6 Siemens · 10/2015
5SV8 residual current monitors
Monitoring DevicesMonitoring Devices for Electrical Values
■ Technical specifications
1) INS: Instantaneous, SEL: Selective.
5SV8000-6KK 5SV8001-6KK 5SV8200-6KK 5SV8101-6KK
Standards EN 62020, IEC 62020 DIN EN 60947-2 (Appendix M), IEC 60947-2 (Appendix M)
Approvals UL --
Rated operational voltage Ue V AC 230 230 from a 1-phase auxiliary voltage source (also externally)
• Frequency Hz 50/60
Rated residual current ΙΔn• Type A A 0.03 ... 3 0.03 ... 3 0.03 ... 3 0.03 ... 3
(default setting: 30 mA)• Type AC A >3 5 ... 30 5 ... 30 --
Response time Δt s 0.02 ... 5 0.02 ... 10, INS, SEL1) 0.02 ... 10, INS, SEL1) ΙΔn = 30 mA: INS instantaneous
ΙΔn > 30 mA: INS - SEL - 0,06 ... 101)
(default setting INS)
Relay contacts 1 × alarm 1 × pre-alarm, 1 × alarm
1 × pre-alarm, 4 × alarm
1 × alarm, 1 × tripping operation
• Rated voltage V AC 230 230 230 230• Rated current A 6 6 6 6
Summation current transformer mm ∅ 20 ... 210 35 ... 210
Maximum cable length RCM/CT (shielded cable)
m 10
Conductor cross-section mm2 1.5 0.125 ... 2.08
Test/Reset Yes/Yes
External tripping operation/external reset
--/Yes Yes/Yes Yes/Yes Yes/Yes
Mounting width MW 2 3 3 3
Degree of protection• Contacts IP20• Front IP41
Operating temperature °C -10 ... +50
© Siemens AG 2016
![Page 9: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/9.jpg)
7Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
5SV8 residual current monitors
■ Dimensional drawings
Residual current monitor
5SV8101-6KK (approved configurations)
2 5SV8101-6KK
1 EN 60715 - TH35 - 7.5 35 - 15
5 5SV8702-0KK 35 mm 5SV8902-1KK5SV8703-0KK 70 mm 5SV8903-1KK5SV8704-0KK 105 mm 5SV8904-1KK5SV8705-0KK 140 mm 5SV8905-1KK5SV8706-0KK 210 mm 5SV8906-1KK
4 3 3
3VL17... 3VL9400-1ST00 3VL9400-1UP00
3VL27... 3VL9400-1ST00 3VL9400-1UP00
3VL37... 3VL9400-1ST00 3VL9400-1UP00
3VL47... 3VL9400-1ST00 3VL9400-1UP00
3VA20... 3VA9988-0BL30 3VA9908-0BB113VA21... 3VA9988-0BL32 3VA9908-0BB203VA22... 3VA9988-0BL33 3VA9908-0BB24
3VA9908-0BB25
3VA10... 3VA9988-0BL30 3VA9908-0BB113VA11... 3VA9988-0BL32 3VA9908-0BB20
3VA9988-0BL33 3VA9908-0BB243VA9908-0BB25
1 2
34
5
I201
_189
88
Standard DIN railResidual current deviceTrip elementMolded case circuit breakerSummation current transformer
12345
RCM analog, 5SV8000-6KK RCM digital, 5SV8001-6KK, 5SV8200-6KK,
MRCD, 5SV8101-6KK
36
45 67 85
44686
I202
_116
027
54 44686
45 67 85
I202
_160
28
© Siemens AG 2016
![Page 10: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/10.jpg)
8 Siemens · 10/2015
5SV8 residual current monitors
Monitoring DevicesMonitoring Devices for Electrical Values
Summation current transformer
Summation current transformer, 5SV8700-0KK Summation current transformer, 5SV8701-0KK
Type Dimen-sions
A B C D E F G
5SV8702-0KK 100 79 26 49 35 35 43
5SV8703-0KK 130 110 32 66 70 52 57
5SV8704-0KK 170 146 38 94 105 72 73
5SV8705-0KK 230 196 49 123 140 97 98
5SV8706-0KK 299 284 69 161 210 141 142
Type Rated current Maximum current1)
5SV8700-0KK ≤ 40 A 240 A
5SV8701-0KK ≤ 63 A 380 A
5SV8702-0KK ≤ 80 A 480 A
5SV8703-0KK ≤ 200 A 1200 A
5SV8704-0KK ≤ 250 A 1500 A
5SV8705-0KK ≤ 500 A 3000 A
5SV8706-0KK ≤ 600 A 3600 A1) Transient starting current, up to max. 2s
Summation current transformer, 5SV8702-0KK, 5SV8703-0KK, 5SV8704-0KK, 5SV8705-0KK, 5SV8706-0KK
All active conductors (including the neutral) must be routed through the transformer. Cables that are not routed through the transformer must keep to a minimum clearance of 20 cm. Moreover, the transformers must have an inside diameter that is at least 1.5 times larger than the outside diameter of the conductors that pass through it.
Summation current transformer, 5SV8702-0KK, 5SV8703-0KK, 5SV8704-0KK, 5SV8705-0KK, 5SV8706-0KK
Ø46
Ø20
2460
32 I202_16029
Ø59
Ø30
3070
32 I202_16030
ØE
G46
6,5
BF33
A
D
8
C
I202_16031
OK OKOKOK
I201
_194
65
© Siemens AG 2016
![Page 11: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/11.jpg)
9Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
5SV8 residual current monitors
■ Circuit diagrams
Residual current monitor
■ More information
Switch positions
RCM digital, 5SV8001-6KK:
RCM digital, 4 channels, 5SV8200-6KK
S/R = Set/Reset
L N
T1T2T3
1S1
1S2
1S1
1S2
T4
1S1
1S2
1S1
1S2
I202
_160
40a
Reset
Test
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15
S/R
Alarm contact/alarm Trip contact/trip Alarm contact/alarm Trip contact/trip
Setting "Standard" "Standard" "+" "+"
Without power supply
With power supply
Over limit
CT disconnection
456 15
1413 4
56 15
1413
456 15
1413 4
56
456 4
56 15
1413
456 4
56 15
1413
© Siemens AG 2016
![Page 12: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/12.jpg)
10 Siemens · 10/2015
5SV8 residual current monitors
Monitoring DevicesMonitoring Devices for Electrical Values
RCM digital, 4 channels, 5SV8200-6KK:
Alarm contact/alarm Trip contacts/trip Trip contacts/trip
Setting "Standard" "Standard" "+"
Without power supply
With power supply
Over limit
CT disconnection
10 1 C1: 14C2: 14C3: 8C4: 8
C1: 13C2: 15C3: 7C4: 9
C1: 14C2: 14C3: 8C4: 8
C1: 13C2: 15C3: 7C4: 9
10 1 C1: 14C2: 14C3: 8C4: 8
C1: 13C2: 15C3: 7C4: 9
C1: 14C2: 14C3: 8C4: 8
C1: 13C2: 15C3: 7C4: 9
10 1 C1: 14C2: 14C3: 8C4: 8
C1: 13C2: 15C3: 7C4: 9
C1: 14C2: 14C3: 8C4: 8
C1: 13C2: 15C3: 7C4: 9
10 1 C1: 14C2: 14C3: 8C4: 8
C1: 13C2: 15C3: 7C4: 9
C1: 14C2: 14C3: 8C4: 8
C1: 13C2: 15C3: 7C4: 9
© Siemens AG 2016
![Page 13: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/13.jpg)
11Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
5TT3 voltage relays
■ Overview
Voltage relays are used for device and plant protection, supplying safety light devices and the detection of N-conductor breaks and short-time voltage interruptions.
They are available as undervoltage, overvoltage and under / overvoltage relays. The devices are equipped with different functions, depending on their intended use, and comply with the pertinent regulations.
■ Technical specifications
1) For rated operational current.
5TT3400 5TT3404 5TT3406 5TT3194 5TT31955TT3401 5TT34055TT34025TT3403
Standards IEC 60255; DIN VDE 0435-110, -303
Rated operational voltage Uc V AC 230/400 400
Operating range (overload capability) × Uc 1.1 1.35
Rated frequency Hz 50/60
Response values ON-switching × Uc 0.9/0.95 4 % hysteresisOFF-switching 0.7/0.85 0.7 ... 0.95 0.9 ... 1.3
Minimum contact load V; mA 10; 100
Phase asymmetry Setting accuracy % -- Approx. 5 ... 10 -- Approx. 5 ... 10
Repeat accuracy % -- 1 -- 1
Phase failure detection At L1 or L2 or L3 ms 100 --
N-conductor monitoring -- Yes --
Rated insulation voltage Ui Between coil/contact kV 4
Contacts μ contact (AC-11) A 4
Electrical isolation Creepage distances and clearancesActuator/contact mm 3 5.5
Rated impulse withstand voltage Uimp Actuator/contact kV > 2.5 > 4
Terminals ± Screw (Pozidriv) 1
Conductor cross-sections• Rigid, max. mm2 2 × 2.5• Flexible, with end sleeve, min. mm2 0.5
Permissible ambient temperature °C -20 ... +60
Climatic withstand capability Acc. to EN 60068-1 20/60/4
5TT3196
Standards IEC 60255; DIN VDE 0435
Rated operational voltage Uc V DC 24
Rated power loss Pv• Coil/drive VA 0.6• Contacts1) per pole VA 0.8
Hysteresis % 4
Response values × Uc • Undervoltage Undervoltage 0.82• Overvoltage Overvoltage 1.18
Residual ripple tripping ΔUc Infinitely variable % 0 ... 15
Overload capability 33 V DC Continuous35 V DC ms 50045 V DC ms 10
Creepage distances and clearances mm 4
Rated impulse withstand voltage Uimp Input/output kV > 2.5
Minimum contact load V/mA 24/300
Rated operational current Ie AC-11 A 1AC-1 A 4
Contacts μ contact
Electrical service life In switching cycles at Ie 5 × 105
Terminals ± Screw (Pozidriv) 1
Conductor cross-sections• Rigid, max. mm2 2 × 2.5• Flexible, with end sleeve, min. mm2 1 × 0.5
Permissible ambient temperature °C -20 ... +60
Climatic withstand capability Acc. to EN 60068-1 20/60/4
© Siemens AG 2016
![Page 14: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/14.jpg)
12 Siemens · 10/2015
5TT3 voltage relays
Monitoring DevicesMonitoring Devices for Electrical Values
5TT3407 5TT3408 5TT3410
Standards IEC 60255; DIN VDE 0435-303
Rated operational voltage Uc V AC 230/400
Operating range (overload capability) × Uc 1.1 1.35 1.2
Rated frequency Hz 50/60
Back-up fuse Terminals L1/L2/L3 A 2
Response values Overvoltage:OFF-switching × Uc -- 0.9 ... 1.3 --ON-switching -- 4 % hysteresis --
Undervoltage:OFF-switching × Uc 0.8 0.7 ... 1.1 --ON-switching 0.85 4 % hysteresis --
Minimum contact load V; mA 10; 100
Phase asymmetry Setting accuracy % Approx. 5 ... 10
Repeat accuracy % 1
Phase failure detection At L1, L2 or L3 ms ≥ 20 100 --
OFF delay s -- 0.1 ... 20 0.1 ... 20
Automatic reclosing delay s 0.2 ... 2 -- --
Rated insulation voltage Ui Between coil/contact kV 4
Contacts μ contact (AC-11) A 3 1 4
Electrical isolation Creepage distances and clearances Contact/contact mm -- 4 --Actuator/contact mm 4 5.5
Rated impulse withstand voltage Uimp Actuator/contact kV > 4
Rated operational power Ps AC operation:230 V and p.f. = 1 VA 2000 -- --230 V and p.f. = 0.4 VA 1250 -- --
DC operation:Ue = 24 V and Ie = 6 A W max. 100 -- --Ue = 60 V and Ie = 1 A W max. 100 -- --Ue = 110 V and Ie = 0.6 A W max. 100 -- --Ue = 220 V and Ie = 0.5 A W max. 100 -- --
Terminals ± Screw (Pozidriv) 1
Conductor cross-sections• Rigid, max. mm2 2 × 2.5• Flexible, with end sleeve, min. mm2 0.5
Permissible ambient temperature °C -20 ... +60
Humidity class Acc. to IEC 60068-2-30 F
5TT3411 5TT3412 5TT3414 5TT3415
Rated operational voltage Uc V AC 230 230/400
Overload capability × Uc 1.15 1.1 1.15
Rated frequency Hz 50/60
Response values ON-switching 2 % hysteresis 4 % hysteresis 5 %
OFF-switching × Uc 0.9 0.9 0.85
Minimum contact load V/mA 10/100
Phase failure detection At L1, L2 or L3 ms -- 100 500
N-conductor monitoring -- Yes --
Rated insulation voltage Ui Between coil/contact kV 4 --
Contacts AC-15 NO contacts 3 2 --
AC-15 NC contacts 2 1 --
AC-15 CO contacts -- 1 1 2
Electrical service life in switching cycles AC-15, 1 A, 230 V AC 5 × 105 1 × 105
Rated impulse withstand voltage Acc. to IEC 60664-1 kV 4 6
Pollution degree 2 2
Terminals ± Screw (Pozidriv) 2 --– Screw (slot) -- 3.5
Conductor cross-sections
• Rigid mm2 2 × 2.5 1 x 4• Flexible, with end sleeve mm2 2 × 1.5 1 x 2.5
Permissible ambient temperature °C -20 … +60 -25 … +60
Climatic withstand capability Acc. to EN 60068-1 20/060/04
© Siemens AG 2016
![Page 15: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/15.jpg)
13Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
5TT3 voltage relays
■ Characteristic curves
Timing interval of 5TT3400... 5TT3406undervoltage relays
Timing interval of 5TT3410 N-conductor monitors
11-14
Uab
L1L2L3
Uc
11-12
Uab= Release value
I201
_070
33b
PEN conductorinterruption
N
C
11-1411-12
I201_07516bL1, L2, L3
Timing interval of 5TT3407 short-time relays
Timing interval of 5TT3408 under/overvoltage relays
tv: Adjustable automatic reclosing delay 0.2 to 20 s t: Adjustable OFF delay 0.1 to 20 s
The undervoltage relay switches at a phase asymmetry of approx. 6 to 8 %, regardless of the response values for undervoltage. The above diagram shows the timing interval for undervoltage or asymmetry.
The undervoltage relay switches at a phase asymmetry of approx. 6 to 8 %, regardless of the response values for undervoltage. The above diagram shows the timing interval for undervoltage.
0
11-1411-12
T0
vtvt
vtvt
cU
11-1411-12
I201_07271c
"RESET""RESET"
Response time
With faultstorage
Without faultstorage
Good signalGood signal
Good signalGood signal
Response time
I201_07270b
11-1411-12
On
t
UH
U
Off
OnOff
OnOff
>U
<U
<U
>U
tt
L1, L2, L3
LED
LED
LED
green
red
red
Hysteresis
Hysteresis
© Siemens AG 2016
![Page 16: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/16.jpg)
14 Siemens · 10/2015
5TT3 voltage relays
Monitoring DevicesMonitoring Devices for Electrical Values
5TT3415 undervoltage relays 5TT3411 and 5TT3412 voltage relays
For characteristic curves of the 5TT3411 and 5TT3412 voltage relays, see "Monitors for medical premises" from page 34.
■ Dimensional drawings
5TT34, 5TT3194 and 5TT3195 voltage relays
5TT34 undervoltage relays
5TT3196 DC voltage monitors
5TT3410 N-conductor monitors
5TT3411 and 5TT3412 voltage relaysFor dimensional drawings of the 5TT3411 and 5TT3412 voltage relays, see "Monitors for medical premises" from page 34.
Hysteresis
t>0.5s
LED green
LED yellow
t=1min
U
5TT3415TEST
UsL1, L2, L3
11-1421-2411-1221-22 I202_01419
5TT3400 5TT3401
5TT3402 5TT3403
5TT3404 5TT3405 5TT3407 5TT3408
5TT3194 5TT3195 5TT3406
I201
_115
15
9045
64435
N L3L2L1
2212
21241114
12
1114
L1
L2L1
36363618
2212
21241114
NL3L2L1
2212
21241114
NL3L2L1
4355
45 90I2
01_0
6552
518
e+ f
231112
24
L1 L2 L3 N
14 11 24 21
12 22
36 5 4364
45 90
I201
_115
16
© Siemens AG 2016
![Page 17: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/17.jpg)
15Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
5TT3 voltage relays
■ Circuit diagrams
Graphical symbols
5TT34 undervoltage relays
5TT3414 5TT3415
5TT3411 and 5TT3412 voltage relays
For circuit diagrams of the 5TT3411 and 5TT3412 voltage relays, see "Monitors for medical premises" from page 34.
Typical circuit for 5TT3195, 5TT340 voltage relays1, 2, 3-phase operation against N
Typical circuit for 5TT3196 DC voltage monitors
5TT3194 5TT3195
5TT3402 5TT3403 5TT3404 5TT3405
5TT3406 5TT3407 5TT3408 5TT3410
5TT3196 5TT3400 5TT3401
5TT3414 5TT3415
N
L1 L2 L3 24 22
21
14 12
11 23
1224
11
e(+)
f N
L1 L2 L3 14 12
11N
11
L1 L2 L3 12 14
I202
_014
20
N11 21
L1 L2 L3 12 14 22 24
I202
_014
21
11 12 14
21 22 24
111214
L1
L3L2 N
212224
11 12 14
111214
L1
L3L2 N
N
L1 L2
L3N
L1 L2
L3
I202
_014
15
14 12 24 22
11 21I201
_075
94c L1 L2 L3 N
L1 N
One-phase operation
14 12 24 22
11 21I201
_075
95c L1 L2 L3 N
L1 L2
Two-phase operation
14 12 24 22
11 21I201
_075
96c L1 L2 L3 N
L1 L3 L4L2
Three-phase operation
If 0.82 × Uc is fallen short of, or 1.18 × Uc exceeded, or if the residual ripple is too high, the 11/12 contact closes and the 23/24 contact opens.
5TT3 196
L1
L2
L3
e+
f
I201_07274a
11
12
23
24Load
24 V DC
23-2411-12
c
c
1,18 x U
0,82 x U
I201
_070
35a
© Siemens AG 2016
![Page 18: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/18.jpg)
16 Siemens · 10/2015
5TT3 voltage relays
Monitoring DevicesMonitoring Devices for Electrical Values
Typical circuit for 5TT3401, 5TT3403, 5TT3405undervoltage relays
Typical circuit for 5TT3404, 5TT3405, 5TT3406, 5TT3408under/overvoltage relays
One application of undervoltage relays is the switching to a safe power supply after a fault. Buildings are distinguished according to use, such as business premises, exhibition areas or guest houses. These are all covered generically as rooms/buildings "where people meet".
There is a fault if the voltage of the general power supply drops for 0.5 seconds > 15 % in relation to the rated voltage (i.e. 195 V at 230 V).
In this case the lighting must be switched to a safety power supply after 0.5 to 15 s depending on the type of use. A safety power supply may be: a battery system, a generating set or a quick-starting standby generating set.
These voltage relays can only be used for 3-phase operation. They monitor not only under- and overvoltages in accordance with their description, but also reverse voltage, asymmetry and N-conductor breaks.
14 12 24 22
11 21
L1' L2' L3' N'
I201
_072
72d
L1 L2 L3 L4
K2
L1 L2 L3 N
K1
K1 K2
Emergencypower supply
Standardpower supply
Emergencylighting
Standardlighting
3 AC 230 V
L1 L2 L3 N
L1 L2 L3 N
K1
14 12 24 22
11 21
M
PE
Phase failureI201_07273d
© Siemens AG 2016
![Page 19: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/19.jpg)
17Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
5TT3 voltage relays
Typical circuit for 5TT3407 short-time relays
Typical circuit for 5TT3407 short-time relays
In the case of sensitive technical sequences, it is often not possible to tell whether this interrupt has interfered with the process sequence. The circuit disconnects the power supply, which can then be switched back by using the RESET pushbutton.
In simple cases, it may be sufficient for a short-time interruption to be registered without the need to disconnect the power supply. In the case of a short-time interruption, this is counted by the pulse counter. The pulse counter can be reset if required.
14 12 24 22
11 21
I201_07597d
L1 L2 L3 N
L1 L2 L3 N
K1 K1
Reset
3 AC 230 V
14 12 24 22
11 21
L1 L2 L3 N
L1 L2 L3 N
1 2 3 4
5TT3407 7KT5883
I201
_075
98d
Reset
230 V 3 AC
Typical circuit for 5TT3410 N-conductor monitors
L1
5TT3410
L2 L3
N
K1
L1L2L3NPE
F1F2F3
S1 F4 F5 F6
11
14
K1 I201_07517b
Test and serviceswitch
© Siemens AG 2016
![Page 20: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/20.jpg)
18 Siemens · 10/2015
5TT3 voltage relays
Monitoring DevicesMonitoring Devices for Electrical Values
■ More information
General voltage monitoring
For general device and plant protection, voltage relays with switching thresholds of 0.7 × Uc, i.e. 161 V are used. If they have fixed, non-changeable switching thresholds, they switch back to normal operation at 0.85 × Uc, 195 V or at 0.9 × Uc, 207 V, depending on the version. If they have adjustable thresholds, they switch back to normal operation with 4 % hysteresis, 9 V.
1, 2 or 3 phases to N or 3 phases to N
All voltage relays require an N-conductor. Devices for 1, 2 or 3 phases to N can be used for 1-, 2-, or 3-phase operation. Devices for 3 phases to N require all three phases, whereby the sequence in which they are connected is irrelevant.
Asymmetry detection
If different voltages occur in a three-phase network, this is called phase asymmetry. Some voltage relays detect an asymmetry of approx. 6 to 8 % of the phase-to-neutral voltage, i.e. approx. 14 to 16 V and switch off. This type of operation is used for example to protect motors against a "skew".
N-conductor monitoring
An N-conductor break causes a skew, depending on the phase load. In extreme cases, this could cause 400 V to be applied to a phase and destroy the connected devices. Each voltage relay with asymmetry detection is tripped by an N-conductor break, if the phase displacement is at least 14 to 18 V.
The 5TT3410 N-conductor monitor detects a phase displace-ment of 5 %, which is roughly 12 V. This provides earlier protec-tion against overvoltage for connected devices. The N-conduc-tor monitor does not react if the voltage drops or rises in all phases simultaneously; or if a phase is swapped with the N-conductor.
Reverse voltage detection
If a phase fails, the motors feed a reverse voltage to the missing phase. However, voltage relays with reverse voltage detection will disconnect in this case because they are monitoring the phase angle.
Phase failure detection
If a phase fails completely, the voltage relays disconnect with a delay as specified in the technical specifications.
Short-time failure detection
Short-time failures upwards of 20 ms cannot be detected with conventional voltage relays. However, they can occur in the case of system transfers or lightning strikes and can lead to uncertainty for sensitive process sequences or measuring procedures. The 5TT3407 short-time voltage relay has a reset function that allows a procedure to be permanently interrupted after a fault.
Back-up fuse
The voltage relays do not require a back-up fuse as device protection. However, they are often installed in junctions, i.e. in main supply systems with high fusing. In this case, the supply lead to the voltage relay must be short-circuit resistant. The back-up fuse only serves as line protection.
5TT3411 and 5TT3412 voltage relays
For control elements of the 5TT3411 and 5TT3412 voltage relays, see "Insulation monitors for medical premises" from page 34.
5TT3 194
5TT3 195
5TT3 196
5TT3 400
5TT3 401
5TT3 402
5TT3 403
5TT3 404
5TT3 405
5TT3 406
5TT3 407
5TT3 408
5TT3 410
5TT3 411
5TT3 412
Overvoltage ✓ ✓ ✓ -- -- -- -- -- -- -- -- ✓ -- ✓ ✓
Undervoltage -- -- ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- -- --
Monitoring of safety light devices -- -- -- -- ✓ -- -- -- ✓ -- -- -- -- -- --
Monitoring of medical premises -- -- -- -- -- -- -- -- -- -- -- -- -- ✓ ✓
Monitoring of N-conductor -- -- -- -- -- -- -- -- -- -- -- -- ✓ -- ✓
Monitoring of short-time interruptions -- -- -- -- -- -- -- -- -- -- ✓ -- -- -- --
1, 2, 3-phase to N ✓ -- -- ✓ ✓ ✓ ✓ -- -- -- ✓ -- -- ✓ ✓
3 phases to N -- ✓ -- -- -- -- -- ✓ ✓ ✓ -- ✓ -- -- --
Asymmetry detection -- ✓ -- -- -- -- -- ✓ ✓ ✓ -- ✓ ✓ -- ✓
N-conductor monitoring -- -- -- -- -- -- -- ✓ ✓ ✓ ✓ ✓ ✓ -- ✓
Reverse voltage detection -- ✓ -- -- -- -- -- ✓ ✓ ✓ -- ✓ -- -- ✓
Short-time failure detection -- -- -- -- -- -- -- -- -- -- ✓ -- -- -- --
Phase failure detection -- -- -- ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- -- ✓
Switching thresholds: -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
0.7/0.9 × Uc, non-adjustable -- -- -- ✓ -- ✓ -- ✓ -- -- -- -- -- -- --
0.8/0.85 × Uc, non-adjustable -- -- -- -- -- -- -- -- -- -- ✓ -- -- -- --
0.85/0.95 × Uc, non-adjustable -- -- -- -- ✓ -- ✓ -- ✓ -- -- -- -- -- --
0.7 ... 0.95 × Uc, 5 % hysteresis, adjustable -- -- -- -- -- -- -- -- -- ✓ -- -- -- -- --
0.7 ... 1.1 × Uc, 4 % hysteresis, adjustable -- -- -- -- -- -- -- -- -- -- -- ✓ -- -- --
0.9 ... 1.3 × Uc, 4 % hysteresis, adjustable ✓ ✓ -- -- -- -- -- -- -- -- -- ✓ -- -- --
Adjustable time delay -- -- -- -- -- -- -- -- -- -- -- ✓ -- -- --
Contact: 1 CO -- -- -- ✓ ✓ -- -- -- -- -- -- -- -- -- --
Contact: 2 CO ✓ ✓ -- -- -- ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- --
Contact: 1 CO, 1 NO, 1 NC -- -- -- -- -- -- -- -- -- -- -- -- -- -- ✓
Contact: 1 NO, 1 NC -- -- ✓ -- -- -- -- -- -- -- -- -- -- -- --
Contact: 2 NO, 2 NC -- -- -- -- -- -- -- -- -- -- -- -- -- ✓ --
© Siemens AG 2016
![Page 21: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/21.jpg)
19Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
5TT3 voltage and frequency relays
■ Overview
The voltage and frequency relay monitors the status of the grid in the case of in-plant generation systems. Violation of an upper or lower limit results in shutdown and disconnection of the generation system from the grid. Connection or automatic re-connection of the generation system to the grid only takes place when the grid frequency and the grid voltage have remained within their respective tolerance ranges without interruption for the duration of an adjustable time delay tW. Following shutdown due to a brief interruption, re-connection takes place when the grid frequency and grid voltage have remained within the tolerance range for 5 s without interruption.
■ Benefits
• Clearance certification of the German Employer's Liability Association (Energy, Textile, Electrical and Media Products)
• Default settings in accordance with VDE-AR-N-4105• The voltage and frequency relay meets the high requirements
of VDE AR-N 4105• It can be used both for centralized and integrated grid and
plant protection• The latching rotary switches enable fast and easy setting of
the required values • An illuminated LCD display provides plant status information• The voltage and frequency relay ensures single-fault
tolerance as stipulated in the VDE-AR-N 4105 application guide
• Passive procedure for detecting islanding
■ Application
Enable via external contact
Enable using external voltage 24 V AC, 40 ... 400 HzI2
02_0
2440
Coupling switch 1
Coupling switch 2
3-phase
Safe external disconnection, e.g. via ripple control receiver
CG = clock-pulse generatorInvertersGenerator(s)Generation system
Low-voltage system
CG 2CG 1
L1L2L3N
L1 L2 L3 N 11
12
Q1
KA
KE
Q2
14 22 24 32 34
21 31X1
B1
B2
X2
Coupling switch 1
Coupling switch 2
enabled disabled
CG =clock-pulse generator
external CG
InvertersGenerator(s)Generation system
Low-voltage system
CG 2
L1L2L3N
L1 L2 L3 N 11
12
Q1
KA
KE
Q2
14 22 24 32 34
21 31X1
B1
(+) (-)
B2
X2
I202
_024
41
© Siemens AG 2016
![Page 22: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/22.jpg)
20 Siemens · 10/2015
5TT3 voltage and frequency relays
Monitoring DevicesMonitoring Devices for Electrical Values
■ Technical specifications
Voltage and frequency relays
5TT3426 5TT3427
Standards IEC/EN 60255-1; IEC/EN 61000; VDE-AR-N-4105
Supply voltage Uv V AC 3 x 85 ... 288
Supply voltage B1/B2 V AC 24 (at 40 ... 400 Hz)
Rated operational voltage Uc V AC 230/400
Rated impulse withstand voltage Acc. to IEC 60664-1• Contact 31, 32, 34 kV 6• KA, KE and measuring circuit kV 4• Pollution degree 2
Recommended fuseMeasuring inputs
gG/gL A 6
Temperature range °C -20 ... +60(in the range 0 °C ... -20 °C, there may be restrictions to the functionality of the LCD display)
Conductor cross-sections• Rigid, flexible mm2 0.5 ... 4• Flexible with end sleeve mm2 0.5 ... 2.5• Multi-conductor connection 2 conductors of same
cross-sectionmm2 0.5 ... 1.5
Output relayMode of operation Quiescent current
Contacts• NO contacts AC15 A AC/V AC 3/230• NC contacts AC15 A AC/V AC 1/230
Thermal current A AC 5
Electrical service life• NO contacts AC15, 1A, AC230 Switching
cycles300000
Rise in frequency Hz 50.2 ... 51.2
Drop in frequency Hz 47.0 ... 49.8
Rise in voltage• Phase/neutral V AC 253 ... 288• Phase/phase V AC -- 438 ... 498
Drop in voltage• Phase/neutral V AC 184• Phase/phase V AC -- 319
Mean rise in voltage over 10 minutes• Phase/neutral V AC 253 ... 267• Phase/phase V AC -- 438 ... 462
Re-connection time tw sec 0 ... 600
Disconnection response time ms < 100
Connection condition• Frequency % 5• Voltage Hz 47.5 ... 50.05
Accuracy• Frequency % (± 1 digit) ≤ ±1• Voltage % (± 1 digit) ≤ ±0.02
Dimensions W x H x D 70 x 90 x 71 mm
© Siemens AG 2016
![Page 23: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/23.jpg)
21Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
5TT3 voltage and frequency relays
■ Dimensional drawings
5TT3426 5TT3427
■ Circuit diagrams
5TT3426 and 5TT3427
I202
_024
44
71,8 637
X1 B1 B2 X2 11 12 14 21 22 24
L1 L2 L3 N KA KE 31 32 34
90
I201_18954
X1 B1 B2 X2 11 12 14 21 22 24
L1 L2 L3 N KA KE 31 32 34
K3
U>>(%) f<(Hz) f>(Hz)
>50,8
<50,9
random
tw(s)
U>=80%
5TT3 426
Mode >2sTest
f>(Hz)
K1 K2
110 112114
115
116118125 120
47,0 47,5 47,848,2
48,649,049,8 49,4
50,2 50,350,4
50,5
50,650,750,8 50,8
Off 110111
112
113114126 125
0 30 6090
180120
240600 450 300
50,8 50,9 51,051,151,2
51,351,5 51,4
U10m>(%)
B1/ K1/ K3 KA/B2 K2 KE
I201_18955
X1 B1 B2 X2 11 12 14 21 22 24
L1 L2 L3 N KA KE 31 32 34
K3
U>>(%) f<(Hz) f>(Hz)
>50,8
<50,9
random
tw(s)
U>=80%
5TT3 427
Mode >2sTest
f>(Hz)
K1 K2
110 112114
115
116118125 120
47,0 47,5 47,848,2
48,649,049,8 49,4
50,2 50,350,4
50,5
50,650,750,8 50,8
Off 110111
112
113114126 125
0 30 6090
180120
240600 450 300
50,8 50,9 51,051,151,2
51,351,5 51,4
U10m>(%)
B1/ K1/ K3 KA/B2 K2 KE
Channel 1
Error
Channel 2
L1 L2 L3 N
X1 B1 B2 X2 11 12 14 21 22 24
KAKE 31 32 34
U < >
f < >
Ū10m>
12
11
14
K1
32
31
34
K3
tw
U < >
f < > 22
21
24
K2tw
I202
_024
39
Ū10m>
© Siemens AG 2016
![Page 24: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/24.jpg)
22 Siemens · 10/2015
5TT6 current relays
Monitoring DevicesMonitoring Devices for Electrical Values
■ Overview
Current relays monitor single and three-phase systems for the flow of current, e.g. in emergency lighting installations, and the
loading of motors. They are available as undercurrent, overcurrent and under/overcurrent relays.
■ Technical specifications
5TT6111 5TT6112Standards IEC 60255; DIN VDE 0435-303Rated operational current Ic A 1 ... 10Rated operational voltage Uc V AC 230Primary operating range × Uc 0.9 ... 1.1Overload capability, continuous A 15Overload capability, short-time At 50 °C ambient
temperature max. 3 sA 20
Rated frequency Hz 50/60Response values ON-switching Infinitely variable
OFF-switching Permanent, 4 % hysteresis
Switching delay tv Infinitely variable s 0.1 ... 20Response time Non-adjustable ms Current corresponds to the rated operational power of the
continuous-flow heater
Minimum contact load V; mA 10; 100Rated insulation voltage Ui Between coil/contact kV 2.5Contactsμ contact (AC-15) NO contacts A 3
NC contacts A 1
Electrical isolation Creepage distances and mm 3Actuator/contact
Rated impulse withstand voltage Uimp Actuator/contact kV > 4Terminals ± Screw (Pozidriv) 1Conductor cross-sections Rigid max. mm2 2 × 2.5
Flexible, with end sleeve min. mm2 1 × 0.5
Permissible ambient temperature °C -20 ... +60Climatic withstand capability Acc. to EN 60068-1 20/60/4
5TT6113 5TT6114 5TT6115 5TT6120
Standards IEC 60255; DIN VDE 0435-303
Rated operational current Ic 4 ranges 1 rangeA 0.1 ... 1 0.5 ... 5A 0.5 ... 5A 1 ... 10A 1.5 ... 15
Rated operational voltage Uc V AC 230
Primary operating range × Uc 0.9 ... 1.1Overload capability, continuous A 20 15Overload capability independent of measuring range
Max. 3 s A 30
Rated frequency Hz 50/60
Response values ON-switching Infinitely variableOFF-switching Permanent, 4 % hysteresis
Switching delay tv Infinitely variable s 0.1 ... 20
Response time Non-adjustable ms See: www.siemens.com/lowvoltage/manuals
Minimum contact load V; mA 10; 100
Rated insulation voltage Ui Between coil/contact kV 2.5
Contactsμ contact (AC-15) NO contacts A 5
NC contacts A 1
Electrical isolation Creepage distances and mm 3Actuator/contact
Rated impulse withstand voltage Uimp Actuator/contact kV > 4
Terminals ± Screw (Pozidriv) 1
Conductor cross-sections Rigid max. mm2 2 × 2.5Flexible, with end sleeve min. mm2 1 × 0.5
Permissible ambient temperature °C -20 ... +60
Climatic withstand capability Acc. to EN 60068-1 20/60/4
© Siemens AG 2016
![Page 25: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/25.jpg)
23Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
5TT6 current relays
■ Dimensional drawings
5TT611 current relays 5TT6120 current relays
■ Circuit diagrams
Graphical symbols
5TT6111 5TT6112
5TT6113 5TT6114
5TT6115 5TT6120
I201
_115
18
9045
64435
Z1 Z4
24
22
21
i k
Z2 Z3
14
12
11
1A A2
36
L/k
L/iL/i
Z1 Z4
24
22
21
i k
Z2 Z3
14
12
11
N
11
12 14
1A A2
18 36
44
42
41
i3 k3
34
32
31
1A A2
72
24
22
21
i1 k1
14
12
11
1A A2
I201
_115
17
9045
55435
5TT6111 5TT6112
5TT6113 5TT6114 5TT6115 5TT6120
>LL
11
1214
N
i k>
A1 A2
2111
22241214
Z4Z3Z2Z1
i k<
A1 A2
2111
22241214
Z4Z3Z2Z1
i k><
A1 A2
2111
22241214
Z4Z3Z2Z1
i k
<
>
2111
22241214
k1-k3i1-i3
A1 A2
4131
42443234
Typical circuit for 5TT6111 undercurrent monitors
Typical circuit for 5TT6114 overcurrent monitors Measurement with transformer
L/i N
L1N
12 14
11L/kTo the 5TT3460 or 5TT3461 faultsignaling relay
230 V AC I201_07522c
i
5TT6114
A1 A2
k
K1
PE M
L1L2L3NPE
K1
12 14 22 24
11 21
3 AC 230/400 V I201_07560b
© Siemens AG 2016
![Page 26: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/26.jpg)
24 Siemens · 10/2015
5TT6 current relays
Monitoring DevicesMonitoring Devices for Electrical Values
■ More information
Direct measurement, transformer measurement
All current relays can be connected with direct measurement or through transformers.
N potential
Versions 5TT6113 to 5TT6120 can be connected with a separate N potential.
Response time
Current relays are not circuit-protective devices for lines. They switch with a delay in the ms range.
Overload capability
Independent of the set measuring range and set measured value, current relays can be permanently overloaded up to 15 A and 20 A; for 3 s; even up to 20 A and 30 A.
Buildings/object-safe guiding lights
In the approach corridors of planes, high buildings must be fitted with position lighting. The same planning instructions apply to the monitoring of this type of lighting and runway lighting as the monitoring of emergency lighting.
Monitoring of emergency lighting with incandescent lamps
The function of emergency lighting according to DIN VDE 0108 must be checked at regular intervals. The operational current is continuously monitored using current relays. The lighting can either be integrated in the general lighting system or just supplied on demand with emergency current.
The current relay is set so that it switches on at the max. lamp current. If an incandescent lamp fails, a fault is signaled.
Monitoring of motors
If the warning is sent early enough, the fault can be eliminated before the motor starts to overheat and the circuit breaker switches the motor off.
Current relays reliably safeguard the monitoring of fault-free running motors and, in some cases are more suitable than a voltage relay, which is geared more towards motor protection.
Typical circuit for 5TT6114 With direct measurement up to 15 A for overcurrent measurement
Typical circuit for 5TT6120 With direct measurement of up to 5 A for undercurrent/overcurrent measurement
i
5TT6114
A1 A2
k
K1
PE M
L1L2L3NPE
K1
12 14 22 24
11 21
3 AC 230/400 V I201_07559b
5TT6120
A1 A2
K1
PEM
L1L2L3NPE
K1
12 14 22 24
11 21
i
k
1 i2 i3
k2 k31
32 34 42 44
31 41
min max
3 AC 230/400 V I201_07561b
Device overview 5TT6111 5TT6112 5TT6113 5TT6114 5TT6115 5TT6120
Undercurrent ✓ -- ✓ -- ✓ ✓
Overcurrent -- ✓ -- ✓ ✓ ✓
Single-phase ✓ ✓ ✓ ✓ ✓ --
Three-phase -- -- -- -- -- ✓
Separate N potential -- -- ✓ ✓ ✓ ✓
Measuring ranges: Jumper:0.1 - 1 A Z1 – Z2 -- -- ✓ ✓ ✓ --0.5 - 5 A Z1 – Z3 -- -- ✓ ✓ ✓ ✓1 ... 10 A Z1 – Z4 ✓ ✓ ✓ ✓ ✓ --1.5 - 15 A Z1 – Z3 – Z4 -- -- ✓ ✓ ✓ --Can be programmed over jumpers -- -- ✓ ✓ ✓ --
Contacts 1 CO ✓ ✓ -- -- -- --2 CO -- -- ✓ ✓ ✓ ✓
© Siemens AG 2016
![Page 27: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/27.jpg)
25Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
5TT6 current relays
Example: Screw conveyor
Hard objects in screw conveyors, e.g. in sewage treatment plants, can often jam the conveyor system. Appropriately set, the current relay signals over its contact(s) that a hazardous situation has occurred and threatens to block the motor.
Example: Agitators
As with the conveyor processes, changes to the viscosity can lead to an overload of the motors.
Example: Crane motor control system
The current monitoring of the main motor (hoisting motor) ensures that the electrical holding brake is not released until the main motor is in operation and the load is held.
Example: Dust extraction
In the interests of work safety and to protect against massive dust development, it is essential to ensure that the dust extraction system is working perfectly before a saw or sanding machine is switched on.
Planning the monitoring of an incandescent lamp
Current relays have a hysteresis of approx. 4 %. The smallest lamp must not exceed the set measuring range by more than 8 %.
Example: 12 lamps of 100 W each = 1200 W, which corresponds to a current of approx. 5.2 A. If a lamp fails, the current drops by 0.4 A. This 0.4 A corresponds to 8 % of the set measured value 5.2 A.
Response time
The response time of the fault signal is produced by the “adjustable switching delay" (see the technical specifications) and an additional delay, which is determined from the actual current and the set value.
Function charts for 5TT61 overcurrent relay signal
5TT61 overcurrent relay signal
F Pickup Dropoutms ms
1 10 250
2 70 70
5 120 30
10 180 15
20 220 10
30 240 12
F =Iact
Imeas
Iact: Instantaneously flowing current
Imeas: Set current threshold value to be measured
Pickup: With an overcurrent relay, the contact 11 – 14 (21 – 24) to the fault signal closes when the instantaneous current flowing is higher than the switching threshold. The relay picks up.
Dropout: With an overcurrent relay, the contact 11 – 12 (21 – 22) to the fault signal closes when the instantaneous current flowing is higher than the switching threshold. The relay drops out.
I201_07508c
On
t
Off
OnOff
LED
LED
t
1 4
2
UN
N
tv tv
green
red
Fault
Hyst.
I201_07469b
On
t
U
Off
OnOff
LED
LED
t
1 4
2
t
N
N
v
green
red
Fault
Hyst.
© Siemens AG 2016
![Page 28: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/28.jpg)
26 Siemens · 10/2015
5TT6 current relays
Monitoring DevicesMonitoring Devices for Electrical Values
Function charts for 5TT6115 under/overcurrent relay signal
Contrary to all other current relays, a fault signal is always output over the contact 11 – 14 (21 – 24). The red LEDs indicate whether the signal is for an undercurrent or an overcurrent.
I201_07472b
On
t
U
Off
OnOff
LED
LED
t
t
14
2
OnOff
LED
N
N
tvv tv
green
red
red
Fault Fault
Hyst.
Hyst.
© Siemens AG 2016
![Page 29: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/29.jpg)
27Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
5TT3 reverse power relays
■ Overview
The 5TT3424 and 5TT3425 reverse power relays monitor the direction of the energy transport in an electric grid. This may be necessary where public grids and industrial grids intersect, e.g. when using emergency generators, motor-driven generators, etc.
■ Technical specifications
Reverse power relays
5TT3424 5TT3425
Standards IEC 60255; DIN VDE 0435-303
Rated voltage Un V AC 230, 3-phase systems without N 400, 1- or 3-phase systems without N
Rated current In A 5
Response value Reverse power % 2 ... 20
Hysteresis % 12.5 of the set response value
Rated frequency Hz 45 ... 65
Response delay tan s 0.2 ... 10, adjustable
Contact arrangement 2 CO
OutputContact arrangement 2 CO
Breaking capacity IEC 60947-5-1
• NO contacts AC15 A AC/V AC 3/230• NC contacts AC15 A AC/V AC 1/230• Acc. to DC 13 A DC/V DC 1/24
Thermal current A 2 x 5
Electrical service life IEC 60947-5-1
• NO contacts AC 15, 3A, 230 AC Switching cycles
2 x 105
Permissible switching frequency Switching cycles/h
1800
Short-circuit strength, max. melting fuse
IEC 60947-5-1 4 A gL
Mechanical service life Switching cycles
30 x 106
General dataPermissible ambient/storage temperature °C -20 ... +60
Clearance and creepage distances
• Rated impulse withstand voltage kV 4
• Pollution degree IEC 60664-1 II
Degree of protection
• Enclosure IP40
• Terminals IP20
Wire connections
• Fixed screw terminal (S) 0.2 ... 4 mm2 solid or 0.2 ... 1.5 mm2 stranded wire with sleeve
Dimensions W x H x D 70 x 90 x 71 mm
© Siemens AG 2016
![Page 30: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/30.jpg)
28 Siemens · 10/2015
5TT3 fuse monitors
Monitoring DevicesMonitoring Devices for Electrical Values
■ Overview
Fuse monitors serve to monitor all types and versions of melting fuses that cannot be equipped with a fault signal contact. This
enables integration in fault signaling circuits or a central alarm in order to improve plant availability.
■ Technical specifications
■ Dimensional drawings ■ Circuit diagrams
Graphical symbols
■ More information
Typical circuit, function chart
If the fuse fails, the motor is immediately disconnected (prevention of two-phase run). After changing the fuse, the motor can be restarted by pressing the "ON" button.Unlike conventional motor circuit breakers, it is not possible to switch the motor on if the fuse is faulty.
Note:The internal resistance of the measuring paths of the fuse monitor is in the MΩ range so that the VDE regulations with regard to touch voltage are met in the event of faulty fuses (> 1000 Ω/V). To isolate the main switch, it must be switched off. The enclosed label should be affixed to the switchgear as a reminder.
5TT3170
Standards IEC 60255; DIN VDE 0435-110
Rated operational voltage Uc V 3 AC 380 ... 415
Primary operating range × Uc 0.8 ... 1.1
Rated frequency Hz 50 ... 400
Internal resistance of measuring paths Ω/V > 1000
Max. permissible feedback % 90
Response/release time ms < 50
Rated impulse withstand voltage UimpInput/output
kV > 4
Rated operational voltage Ue V AC 250
Rated operational current Ie AC-1 A 4
Electrical service life AC-11 In switching cycles at 1 A 1.5 × 105
Terminals ± Screw (Pozidriv) 1
Conductor cross-sections Rigid, max. mm2 2 × 2.5Flexible, with end sleeve, min. mm2 1 × 0.5
Permissible ambient temperature °C -20 ... +45
Climatic withstand capability Acc. to EN 60068-1 20/45/4
I201
_115
12
9045
64435
15
L3L2L1
14
L3L2L1
36
L3L2 14L1
13L3'L2'L1'
M
N
L2
L1 L2 L3
13
I201_07251b
3 ~
L1 L3
L2' 14L1' L3'
L
F1 F2 F3
3 AC 400 V
Off
On
��������
����� ������
© Siemens AG 2016
![Page 31: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/31.jpg)
29Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
5TT3 phase and phase sequence monitors
■ Overview
Phase monitors monitor the voltages in three-phase system and signal the power failure of one or more phases over a floating contact. Phase sequence monitors monitor the phase sequence
in three-phase systems and signal any changes in the phase sequence – change of rotating field – over a floating changeover contact.
■ Technical specifications
■ Dimensional drawings
■ Circuit diagrams
Graphical symbols
5TT3421 5TT3423
Standards IEC 60255; DIN VDE 0435
Rated operational voltage Uc V AC 230/400 400
Primary operating range × Uc 0.8 ... 1.1
Rated frequency Hz 50/60
Rated power loss Pv Electronics VA 9Contacts VA 0.2
Rated operational voltage Ue V AC 250
Rated operational current Ie A 4
Minimum contact load V; mA 10; 100
Rated insulation voltage Ui Between coil/contact kV 4
Contacts μ contact (AC-11) A 3
Electrical isolation Creepage distances and clearancesActuator/contact mm 4
Rated impulse withstand voltage Uimp Actuator/contact kV > 2.5
Terminals ± Screw (Pozidriv) 1
Conductor cross-sections Rigid, max. mm2 2 × 2.5Flexible, with end sleeve, min. mm2 --
Degree of protection Acc. to EN 60529 IP20, with connected conductors
Safety class Acc. to EN 61140/VDE 0140-1 II
Permissible ambient temperature °C -20 ... +60
Climatic withstand capability Acc. to EN 60068-1 20/60/4
5TT3421 5TT3423
11
21
41
3L
1L
2L
21
41 11
3L
1L N
2L
18
I201
_107
80
18
9045
64435
5TT3421 5TT3423
N
L1 L2 L3
11
1214 L1 L2 L3
11
1214
© Siemens AG 2016
![Page 32: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/32.jpg)
30 Siemens · 10/2015
5TT3 phase and phase sequence monitors
Monitoring DevicesMonitoring Devices for Electrical Values
■ More information
Typical circuit diagrams
5TT3421 phase monitors
The phase monitor can be operated either in 1, 2 or 3-phase operation.
5TT3423 phase sequence monitors
Phase sequence monitors must always be connected in three-phase.
Single-phase operation
I201
_107
76a 14 12
11
L1 L2 L3 N
NL1
Two-phase operation
14 12
11I201
_107
77a L1 L2 L3 N
L1 L2 N
Three-phase operation
1412
11
I201
_107
78 L1 L2 L3 N
L1 L3L2 N
I2_10779a
L1 L2 L3
K1
14 12
11
M
L1 L2 L3PE
© Siemens AG 2016
![Page 33: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/33.jpg)
31Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
5TT3 insulation monitors for industrial applications
■ Overview
Insulation monitors are used for protection of persons and against fire in non-grounded systems (IT systems). The insulation resistance of the system being monitored is measured against ground.
Such measurements are prescribed in accordance with DIN VDE 0100-410 – Power installations up to 1,000 V – Protection against electric shock.
■ Technical specifications
■ Dimensional drawings
5TT3470 5TT3471
Supply voltage Uc V AC 220 ... 240 --V DC -- --
Primary operating range With AC supply × Uc 0.8 ... 1.1 --For DC supply V DC -- --
Frequency range for Uc Hz 45 ... 400 --
Rated power loss Pv VA Approx. 2 --For DC supply W -- Approx. 1
Rated impulse withstand voltage Uimp Terminals A1 to A2 kV < 4 < 4Terminals L to PU kV < 4 < 4Terminals A1, A2 to L, PU kV < 4 < 3Terminals against contacts kV < 6 < 6
Measuring circuit For three-phase and AC systems For direct voltage systems
Measurement voltage range Umeas V AC 0 ... 500 --V DC -- 12 ... 280
Primary operating range × Umeas 0 ... 1.1 0.9 ... 1.1
Frequency range for Umeas Hz 10 ... 10000 --
Alarm values Measuring shunt RAL kΩ 5 ... 100 5 ... 200
Setting of alarm value On absolute scale Infinitely variable Infinitely variable
Alternating current internal resistance Internal test resistance kΩ > 250 --
Direct current internal resistance Internal test resistance kΩ > 250 --L+ and L- to PU kΩ -- 75 each
Measurement voltage Umeas Internal V DC Approx. 15 --
Max. measurement current Imeas Short circuit mA < 0.1 0.2 ... 4 depending on the voltage
Direct interference voltage Max. permissible V DC 500 --
Response delay At RAL 50 kΩ and 1 μFand ∞ to 0.9 × Rmeas s < 1.3 0.8and Rmeas from ∞ to 0 Ω s < 0.7 0.4
Switching hysteresis At Rmeas 50 kΩ % 15 10 ... 15
Contacts μ contact 2 CO 2 CO
Rated operational voltage Ue V 230 AC DC 12 ... 280
Rated operational current Is Thermal current Ith A 4 4DC-13 at 24 V DC A -- 2DC-13 at 250 V DC A -- 0.2AC-15 A -- 3AC-15 NO contacts A 5 --AC-15 NC contacts A 2 --
Terminals ± Screw (Pozidriv) 2 2
Conductor cross-sections Rigid, max. mm2 2 × 2.5Flexible, with end sleeve, min. mm2 1 × 0.50
Permissible ambient temperature °C -20 ... +60
Degree of protection Terminals (acc. to EN 60529) IP20Enclosure (acc. to EN 60529) IP40
Resistance to climate Acc. to EN 60068-1 20/060/04
5TT3470 5TT3471
24
22
2114
12
11 I201
_115
19
9045
64435
X1 LT
L+ L-
PE PT
36
A1 A2
24
22
2114
12
11
LT1 LT2
L
PE PT
36
© Siemens AG 2016
![Page 34: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/34.jpg)
32 Siemens · 10/2015
5TT3 insulation monitors for industrial applications
Monitoring DevicesMonitoring Devices for Electrical Values
■ More information
Function chartsl
Typical circuit diagrams
5TT3470 for three-phase and AC systems 5TT3471 for direct voltage systems
5TT3470, 5TT3471
I201_11522
Uc
R
11-1411-12
11-14
11-12
Insulation resistanceSet value
Without fault storage
Red LED OnOff
With fault storageReset-button
Red LED OnOff
The power supply to terminals A1 – A2 can be taken from the system being monitored. However, in this case it is important to ensure compliance of the voltage range with the technical specifications.
With a jumper LT1 – LT2: A fault signal is not stored; the device is automatically released again if the insulation resistance improves. Without a jumper LT1 – LT2: the fault signal is stored; pressing the RESET button or an external key at the terminals LT1 – LT2 clears the fault signal.
Pressing the Test button or an external key at the terminals PT – PE simulates a fault.
The measurement voltage to the terminals L+ and L- serves at the same time as the power supply.
With a jumper LT – X1: A fault signal is not stored; the device is automatically released again if the insulation resistance improves. Without a jumper LT – X1: The fault signal is stored; pressing the RESET button or an external key at the terminals LT – X1 clears the fault signal.
Pressing the Test button or an external key at the terminals PT – X1 simulates a fault.
I201
_115
20b
N
L
242221141211LT2LT1
A2A1
PE
LPEPT
L3
L2
L1
L+
L-
PT
L- PE
PE
LT X1 11 12 14 21 22 24
L+
I201
_115
21a
© Siemens AG 2016
![Page 35: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/35.jpg)
33Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
5TT3 insulation monitors for industrial applications
Front views
5TT3470 for three-phase and AC systems
Direct interference voltage
While direct interference voltages do not damage the devices they often interfere with conditions in the measuring circuit. In a system being monitored, only one insulation monitor should be connected. This must be taken into account if gateways are used.
System capacitances to protective ground CE do not corrupt the insulation measurement because it is implemented with direct current. However, the response time may be extended in the event of an insulation fault, namely in the magnitude of the time constant RE times CE. The power supply to the insulation monitors can be taken from a separate system or from the one being monitored. However, the above mentioned power supply range must be taken into account.
LEDs:• Green LED lights up if power supply Uc is applied• Red LED lights up in the event of an insulation fault
5TT3471 for direct voltage systems
Leakage capacitance
The insulation monitor can be installed in systems with high leakage capacitance to PE. In the case of high-resistance alarm values, a transient alarm signal may occur when switching on the system being monitored due to an existing ground leakage capacitance.The values of the capacitance CE given the following set values of R are approximately:• R = 200 kΩ: CE > 0.8 μF• R = 50 kΩ: CE > 2.0 μF• R = 20 kΩ: CE > 4.5 μFIn these applications, you should work without an alarm storage. Due to the measuring function with bridge circuit, the insulation monitor does not respond in the event of a simultaneous, exactly symmetrical ground fault of L+ and L-. However, exactly symmetrical ground faults are highly unlikely in practice.LEDs:• Green LED lights up if power supply Uc is applied• Red LED 1 lights up for insulation fault L+ to PE• Red LED 2 lights up for insulation fault L- to PE
5TT3470 5TT3471
I201
_119
71
PE PT LT1 LT2
L A1 A2
T1
T2
12 22
14 11 24 21
E1
LED green:LED red:
E1:T1:T2:
Status display (ON)Insulation fault (AL)Alarm value adjuster (RAL)TestReset
LED red
LED green
I201
_119
72
PE PX X1 LT
L+
T1
T2
12 22
14 11 24 21
L–
E1
LED 1 red
LED green
LED 2 red
LED green:LED 1 red:LED 2 red:
E1:T1:T2:
Status display (ON)Insulation fault L– (RE–)Insulation fault L+ (RE+)Alarm value adjuster (RAL)TestReset
© Siemens AG 2016
![Page 36: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/36.jpg)
34 Siemens · 10/2015
7LQ3 monitors for medical premises
Monitoring DevicesMonitoring Devices for Electrical Values
■ Overview
In areas that conform to Group 2 of DIN VDE 0100-710, any interruption to the examination and/or treatment of patients would place those patients at risk.
Limit monitoring
This is prevented through the use of changeover and monitoring units. These monitor the insulation resistance of the non-grounded IT system, the load current and the temperature of the
transformer. If the limit value is exceeded, the insulation monitor gives out a warning signal.
Voltage monitoring
In addition, a special voltage relay monitors the voltage of the power supply and switches to a second power supply if it falls below the specified limit values.
■ Technical specifications
Switchover devices7LQ3361 7LQ3362
Standards IEC 60364-7-710; DIN VDE 0100-710
Supply voltage Uv V AC 230 230/400
Primary operating range × Uv 0.9 ... 1.1
Supply frequency fv Hz 50 … 60
Insulation coordination IEC 60664-1
Rated impulse withstand voltage kV 4
Pollution degree 3
Max. power loss Pv W 10.7
Power sectionContactors Mechanically latched; mechanically and electrically locked
Rated operational current acc. to DIN VDE 0100-710 A 51 32
Rated operational current AC-3 A 113 71
Short-circuit protection acc. to DIN VDE 0100-710 • Max. backup protection gG A 63
Switchover time s 0.1 ... 10
Measuring circuit insulation monitoringResponse value Ran kΩ 50
Response deviation EN 61557-8
Response time tan at Ran = 50 kΩ, Ce = 1 μF RF from ∞ to 0.5 × Ran s < 1.3RF from ∞ to 0 kΩ s < 0.7
Hysteresis % 15
Measurement voltage Um V DC Approx. 15
Measurement current Im max (at RF = 0 Ω) µA < 50
Internal resistance DC Ri kΩ > 250
Impedance Zi at 50 Hz kΩ > 250
Permissible direct interference voltage Ufg V DC < 300
Test button External/internal
Measuring circuit load current monitoringResponse value, adjustable with external transformer 50/5 A, Class 1
A 5 … 50
Hysteresis % 4
Temperature influence %/°C ≤ 0.05
Delay tv adjustable s 0.1 ... 20
Measuring circuit, temperature monitoringResponse value kΩ 3.2 ... 3.8
Release value kΩ 1.5 ... 1.8
PTC thermistor Acc. to DIN 44081/44082 Unit(s) 1 … 6 in series
Measuring circuit, voltage monitoringResponse values ON-switching 2 % hysteresis 4 % hysteresis
OFF-switching × Uc 0.9 0.9
Phase failure detection At L1, L2 or L3 ms -- 100
N-conductor monitoring -- Yes
© Siemens AG 2016
![Page 37: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/37.jpg)
35Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
7LQ3 monitors for medical premises
Switchover devices7LQ3361 7LQ3362
ConnectionTerminals
• Load circuit Feeder terminals mm² 4 ... 16Output terminals
• Communication Status signals mm² 2.5Fault indications
Environmental conditionsPermissible ambient temperature °C -20 ... 45
Mounting position Vertical
Insulation monitors7LQ3354 7LQ3355
Standards EN 61557-8
Supply voltage Uv V AC 230
Primary operating range × Uv 0.9 ... 1.1
Supply frequency fv Hz 50 … 60
Max. power loss Pv VA Approx. 7
Rated line voltage Un (measuring circuit) V AC 0 … 300
Rated frequency fn Hz 10 … 1000
EMC immunity to interference IEC 61000-6-2
EMC emitted interference IEC 61000-6-3
Insulation coordination IEC 60664-1
Rated impulse withstand voltage kV 4
Pollution degree 3
Flammability class UL 94V-0
Measuring circuit insulation monitoringResponse value Ran kΩ 50 50 ... 500
Response deviation EN 61557-8
Response time tan at Ran = 50 kΩ, Ce = 1 μF RF from ∞ to 0.5 × Ran s < 1.3RF from ∞ to 0 kΩ s < 0.7
Hysteresis % 15
Measurement voltage Um V DC Approx. 15
Measurement current Im max (at RF = 0 Ω) µA < 50
Internal resistance DC Ri kΩ > 250
Impedance Zi at 50 Hz kΩ > 250
Permissible direct interference voltage Ufg V DC < 300
Measuring circuit load current monitoringResponse value, adjustable with external transformer 50/5 A, Class 1
A 5 … 50
Hysteresis % 4
Temperature influence %/°C ≤ 0.05
Delay tv adjustable s 0.1 ... 20
Measuring circuit, temperature monitoringResponse value kΩ 3.2 ... 3.8
Release value kΩ 1.5 ... 1.8
PTC thermistor Acc. to DIN 44081/44082 Unit(s) 1 … 6 in series
Display and control elementsOperating error Acc. to IEC 61557-8
LED display
• Current and temperature monitoring One red and one green LED• Ready-to-run Green• Insulation fault Red• Line breakage monitoring of the isolation measuring circuit Red
• Display of current insulation resistance -- 11-step LED chain
Pushbuttons TEST and RESET
© Siemens AG 2016
![Page 38: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/38.jpg)
36 Siemens · 10/2015
7LQ3 monitors for medical premises
Monitoring DevicesMonitoring Devices for Electrical Values
Insulation monitors7LQ3354 7LQ3355
Output relayContacts for Overtemperature 2 CO
Overload 2 COInsulation fault 2 CO
Mode of operation Working current
Contacts AC-15 NO contacts A AC/V AC 3/230 AC-15 NC contacts A AC/V AC 1/230
Electrical service life AC-15, 1 A, 230 V AC Switching cycles
30000
Thermal current A AC 5
ConnectionTerminals ± Screw (Pozidriv) 2
• Conductor cross-sections Rigid mm2 2 × 2.5• Insulation fault Flexible, with end sleeve mm2 1 × 2.5
Environmental conditionsPermissible ambient temperature °C -20 … +60
Climatic withstand capability Acc. to EN 60068-1 20/060/04
Degree of protection Acc. to EN 60529 IP20, with connected conductors
Mounting position Any
Vibration stress Acc. to IEC 60068-2-6• Amplitude mm 0.35• Frequency Hz 10 … 55
Test and signaling panels 7LQ3356 7LQ3357
Standards DIN VDE 0100-710; IEC 60364-7-710
Rated voltage Un V AC/DC 24
Rated impulse withstand voltage Acc. to IEC 60664-1 kV 4
Voltage range AC 0.8 ... 1.1 x UnDC 0.9 ... 1.2 x Un
Rated current per input mA 0.25
Rated consumption VA 6
Rated operating mode Continuous operation
Pollution degree Acc. to IEC 60664-1 2
Degree of protection• Enclosure Acc. to IEC/EN 60529 IP40• Terminals Acc. to IEC/EN 60529 IP20
Flammability class UL 94V-0
Vibration stress Acc. to IEC/EN 60068-2-6• Amplitude mm 0.35• Frequency Hz 10 … 55
Climatic withstand capability Acc. to IEC/EN 60068-1 20/045/04
Terminal marking EN 50005
Wire connections
• Solid mm2 1 × 1.5mm2 2 × 0.5
• Strand mm2 1 × 1mm2 2 × 0.2
• Strand with sleeve mm2 1 × 0.5
Conductor mounting Box terminals with wire protection
Device dimensions mm 80 × 160 × 57 82 × 150 × 57
Temperature range °C -20 ... +45
© Siemens AG 2016
![Page 39: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/39.jpg)
37Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
7LQ3 monitors for medical premises
Current transformers Class 17LQ3358
Standards IEC/EN 60044-1, VDE 0414-44-1
Rated operational voltage Uc V AC 230
Rated frequency Hz 50/60
Test voltage 50 Hz, 1 min kV 3
Rated transformation ratio kn A 50/5
Primary rated current A 50
Secondary rated current A 5
Rated power V/A 1.5
Class 1
Rated frequency Hz 50 ... 60
Highest voltage at equipment/insulation level kV 0.72/3
Overcurrent factor FS5• Thermal rated short-time current × In 60• Thermal rated continuous current × In 1.2
Expanded current range % 120
Permissible ambient temperature °C -20 … +60
Test and signaling combination for insulation monitors7LQ3360
Standards DIN VDE 0100-710; IEC 60364-7-710
Rated voltage Un V AC 24
Voltage range AC 0.8 ... 1.1 × Un
Connected load W 0.5
Rated operating mode Continuous operation
EMC• Static discharge Acc. to IEC/EN 61000-4-2 kV 8 (air discharge)• RF irradiation Acc. to IEC/EN 61000-4-3 V/m 10• Rapid transients Acc. to IEC/EN 61000-4-4 kV 2• Surge voltage (surge) Acc. to IEC/EN 61000-4-5 kV 1
Degree of protection IP30
Amplitude mm 0.35
Frequency Hz 10 ... 55
Temperature range °C -5 ... +55
Climatic withstand capability Acc. to IEC/EN 60068-1 05/055/04
Terminal marking EN 50005
Wire connections• Solid mm2 1 × 4• Strand with sleeve and plastic collar mm2 1 × 2.5• Strand with sleeve and plastic collar DIN 46228-1/-2/-3/-4 mm2 2 × 1.5• Strand with sleeve DIN 46228-1/-2/-3 mm2 2 × 2.5
Conductor mounting Box terminals with wire protection
Device dimensions mm 80 × 80 × 35
© Siemens AG 2016
![Page 40: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/40.jpg)
38 Siemens · 10/2015
7LQ3 monitors for medical premises
Monitoring DevicesMonitoring Devices for Electrical Values
1) Tripping units must be ordered separately.
■ Accessories
SIRIUS 4AT isolating transformers
Further information about the SIRIUS 4AT isolating transformers can be found in Catalog IC 10 · 2016.
Voltage relays
5TT3411 5TT3412
Rated operational voltage Uc V AC 230 230/400
Overload capability × Uc 1.15 1.1
Rated frequency Hz 50/60
Response values ON-switchingOFF-switching × Uc
2 % hysteresis0.9
4 % hysteresis0.9
Minimum contact load V/mA 10/100
Phase failure detection At L1, L2 or L3 ms -- 100
N-conductor monitoring -- Yes
Rated insulation voltage Ui Between coil/contact kV 4
Contacts AC-15 NO contactsAC-15 NC contacts
32
31
Electrical service life in switching cycles AC-15, 1 A, 230 V AC 5 × 105
Rated impulse withstand voltage Acc. to IEC 60664-1 kV 4
Pollution degree 2
Terminals ± Screw (Pozidriv) 2
Conductor cross-sections• Rigid• Flexible, with end sleeve
mm2
mm22 × 2.52 × 1.5
Permissible ambient temperature °C -20 … +60
Climatic withstand capability Acc. to EN 60068-1 20/060/04
IT line transformers4AT3/4AT4
In the case of isolating transformers used to set up medical IT systems, overcurrent protective devices are only permissible as protection against short circuits. To protect the isolating transformers against overload they are fitted with monitoring devices that signal an excessive rise in temperature (e.g. 7LQ3354 insulation monitors).
Standards EN 61558-2-15
Safety class I
Static shield between primary and secondary winding With insulated connection
Thermistor transformer protection Warning in the event of thermal overload1)
Insulation monitoring With center tap
Short-circuit voltage uz % ≤ 3
No-load current i0 % ≤ 3• Starting current (rush), max. x I1N 8
Rated ambient temperature ta/thermal class 55 °C/H
© Siemens AG 2016
![Page 41: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/41.jpg)
39Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
7LQ3 monitors for medical premises
■ Characteristic curves
7LQ3354 and 7LQ3355 insulation monitors
The following diagrams show the function of the measuring circuits of the temperature monitors (top left), the load current monitors (bottom left) and the insulation monitors (right).
11-1421-2411-1221-22
V
P1/P2
≥ 3,2 kΩ
R
U
t
t
≤ 1,8 kΩ
Over-temperature/sensor break
Power failure
I201_13579
V
>
U
N
31/4134/44
32/42
t t
t
v
> onoff
LEDred
onoff
LEDgreen
Hysteresis
I201_13580a
V
F
51-5461-64
U
R
R
t
t
51-5261-62
51-5461-6451-5261-62
an
BreakMeasuring circuit
With
out f
ault
stor
age
(jum
per L
T1-L
T2)
With
faul
t sto
rage
(w
ithou
t jum
per L
T1-L
T2)
LED “MK“OnOff
LED “AL“
Reset push-button LT
OnOff
LED “MK“OnOff
LED “AL“OnOff
Ground fault
I201_13581
© Siemens AG 2016
![Page 42: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/42.jpg)
40 Siemens · 10/2015
7LQ3 monitors for medical premises
Monitoring DevicesMonitoring Devices for Electrical Values
Test and signaling panels Test and signaling combination for insulation monitors
Voltage relays
The voltage relay switches at a phase asymmetry of approx. 6 % to 8 %, regardless of the response values for undervoltage. The above diagram also shows the timing interval.
7LQ3356, 7LQ3357
X1-L1
X2-L1
X3-L2
X4-L2
X5-
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
X11-
X8-
X6-
X7-
>
>
Line 1 OK
Line 1 failure
Line 2 OK
Line 2 failure
Test /
lationIso-
Over-temperature
Overload
Output
HornAcknowledgementlamp test
Dark Bright
SM
I201
_139
89
7LQ3360
X1/X2
UUH
REt
t
ON
Ground fault
Horn
GreenLED
Yellow LED
Acknow-ledgement
pushbutton
Ron
I201
_139
90
5TT3411
L
L
b
aN
.3 - .4
U
U
t
.1 - .2
Response value
Hysteresis
I201_13574
5TT3412
L3U
U
UU
t
L2L1
N
11 - 14
11 - 12
on
off
I201_13576a
© Siemens AG 2016
![Page 43: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/43.jpg)
41Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
7LQ3 monitors for medical premises
■ Dimensional drawings
Switchover devices
The 7LQ3361 and 7LQ3362 switchover devices are designed for mounting in series ALPHA 630 DIN floor-mounted distribution boards and ALPHA AS side-by-side switchgear cabinets with a cabinet depth of at least 320 mm. More information about the distribution boards can be found in Catalog LV 10. Contact your local Siemens representative for information about additional versions.
7LQ3361
I201_17066250 132
171
212
-X1 -X2
-X3
K1
K3 K4
K5
K20 S1
K6 K7
K9
K8
K10
T01
F1 F2 F3 K13
K2
7622
537
647
058
572
884
0 900
© Siemens AG 2016
![Page 44: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/44.jpg)
42 Siemens · 10/2015
7LQ3 monitors for medical premises
Monitoring DevicesMonitoring Devices for Electrical Values
The 7LQ3361 and 7LQ3362 switchover devices are designed for mounting in series ALPHA 630 DIN floor-mounted distribution boards and ALPHA AS side-by-side switchgear cabinets with a cabinet depth of at least 320 mm. More information about the distribution boards can be found in Catalog LV 10. Contact your local Siemens representative for information about additional versions.
Insulation monitors
7LQ3362
250 132
171
212
-X1 -X2
-X3
K1
K3 K4
K5
K20 S1
K6 K7
K9
K8
K10
T01
F1 F2 F3 K13
K2
76
I201_17067
225
376
470
585
728
840 90
0
7LQ3354 7LQ3355
14055
43
45 90
P2P1 i k PE‘
L‘
PE
L
PT LT1 LT2A1
2124 3134 4144 54 51 64 61 X2 X514
22 32 42 52 62 X112
11
A2
A1 P1 P2 i k PE PT LT1 LT2
14 2411 21 34 31 44 41 54 51 64 61
PE‘ LL‘A2
52 6232 4212 22
105
I201
_138
07
© Siemens AG 2016
![Page 45: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/45.jpg)
43Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
7LQ3 monitors for medical premises
Test and signaling panels
Current transformers Test and signaling combination for insulation monitors
Voltage relays
7LQ3356
80 57
160
I201
_139
85
7LQ3357
150
82 4710
I201
_139
86
7LQ3358
1078
4627
6,5
60
40
20 30
I201
_138
10
7LQ3360
I201
_140
02
80
80
55
5535
6
ON
TEST
5TT3411 5TT3412
L3L2L1 N
241114
23 31
3212
N La
Lb
Y1 Y2 11 12
41 42
23 24
33 34
727255
43
45 90
I201
_137
12
© Siemens AG 2016
![Page 46: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/46.jpg)
44 Siemens · 10/2015
7LQ3 monitors for medical premises
Monitoring DevicesMonitoring Devices for Electrical Values
■ Circuit diagrams
Switchover devices
7LQ3361
7LQ3362
Circuit diagram of 7LQ3361 and 7LQ3362 switchover device to test signaling device (e.g. 7LQ3356 or 7LQ3357 test and signaling panels)
I201
_170
68
X1:7
L1 N L1 N
X1:8L1
230 115 115 2N SCH P1 P20
NX2:1 X2:2L1
X2:4 X2:10 X2:11X2:SN (MZ)L2
X1:PE X1:4 X1:5X1:1 X1:2L1 L2
X2:5 X2:3X1:PE
Line 1
To IT transformer From IT transformer
IT system loadLine 2
I201
_170
69
400 400 400 230 230 230 2N SCH P1 P2
X1:9
L1 L2 L3 N
X1:10L1 L2
X1:11L3
X1:12N
X2:1 X2:4L1
X2:7 X2:10 X2:12 X2:13X2:SN(STP)L2 L3
X1:3 X1:4 X1:PEX1:1 X1:2L1 L2 L3 N
X1:7 X1:8 X1:PEX1:5 X1:6L1 L2
X2:2 X2:6L3
X2:8
Line 1
To IT transformer From IT transformer
IT system loadLine 2
I201
_170
70
X3:1 X3:2 X3:4 X3:5 X3:6 X3:7 X3:8 X3:9 X3:10 X3:11 X3:12 X3:13 X3:14 X3:15
Test buttonISO
Line 1Operation
Line 1Failure
Line 2Operation
Line 2Failure
Temperaturemonitoring
Currentmonitoring
ISOmonitoring
IT transformer
© Siemens AG 2016
![Page 47: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/47.jpg)
45Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
7LQ3 monitors for medical premises
Insulation monitors
Test and signaling panels Test and signaling combination for insulation monitors
Voltage relays
Use La and Lb for monitoring 2 phases or 2-channel monitoring of 1 phase. Lb must be jumpered with La if only La is used.
Circuit diagram of 7LQ3361 and 7LQ3362 switchover device to the central building control system devices
I201
_170
71
X3:18
X3:16 X3:17
X3:19 X3:20 X3:21 X3:22 X3:23 X3:24 X3:25 X3:26 X3:27 X3:28 X3:29 X3:30
MCBtripped
Line 1Operation
Line 2Operation
Line 1Failure
Line 2Failure
Temperaturemonitoring
Currentmonitoring
ISObad
ISOgood
ContactorLine 1 not
switched off
ContactorLine 2 not
switched off
IT transformer IT system
7LQ3354
7LQ3355
I201
_137
13b
11 14 12 21 24 22 31 34 32 41 44 42 51 54 52 61 64 62
LT1
LT2
iP2P1 PE'A2A1 PE PTLL'k
7LQ3354Transformer protection Insulation monitors
11 14 12 21 24 22 31 34 32 41 44 42 51 54 52 61 64 62 X1 X2 X5
7LQ3355 LT1
LT2
iP2P1 PE'A2A1 PE PTLL'k
Transformer protection Insulation monitorsI2
01_1
3811
b
7LQ3356, 7LQ3357
1 2 3 4 5 6 7 8
X5 X4 X3 X2 X1A1 A2 SM PT2 PT1 X8 X7 X6
PT
QH/LT
+
I201_13987
7LQ3360
PT1PT2X1X2X5
Test
Ack.
ON
Ground fault
I201_13988
5TT3411 5TT3412
N
Lb Y1 Y2La
11
12
23
24
33
34
41
42
I201
_137
14a L1L2
N
L3112331
14 122432
© Siemens AG 2016
![Page 48: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/48.jpg)
46 Siemens · 10/2015
7LQ3 monitors for medical premises
Monitoring DevicesMonitoring Devices for Electrical Values
■ More information
Connection examples
Switchover devices
Insulation monitors
7LQ3361, 7LQ3362
I202_01367a
Test
but
ton
Line
1O
pera
tion
Line
1Fa
ilure
Line
2O
pera
tion
Line
2Fa
ilure
Insu
latio
nO
KIn
sula
tion
Faul
t
Tran
sfor
mer
Tem
pera
ture
Tran
sfor
mer
Ove
rload
Ack
now
ledg
men
t ke
y ex
tern
al
Out
put
Gro
up m
essa
ge
Terminal block X3
Test button ISO Operation Failure Operation Failure
Temperaturemonitoring
Currentmonitoring
ISOmonitoring
LINE 1 LINE 2 IT transformer
X5X4X3X2X1 A1 A2 SMPT2PT1 X8X7X6
7LQ3356 / 7LQ3357
L (L+)N (L-)
X3:1 X3:2 X3:4 X3:5 X3:6 X3:7 X3:8 X3:9 X3:10 X3:11 X3:12 X3:13 X3:14 X3:15
7LQ3361 / 7LQ3362
7LQ3354
I201
_170
57a
11 14 12 21 24 22 31 34 32 41 44 42 51 54 52 61 64 62
P1 P2 i k L PE PTA1 A2
PE PEN L2
L L1
> >
L ' PE '
1)
7LQ3360
X1 X2 X5 PT1 PT2
Isolating transformer3.15 ... 8 kVA
Current transformer
Transformer protection
Overtemperature Overcurrent
Insulation monitor
230 V AC
24 V ACTest and
signaling combination2)
1) If there is no center tap, L/L' is connected to L1 or L2.
2) The 24 V AC power supply unit needs to be powered over the IT system.
7LQ3358
7LQ3354
© Siemens AG 2016
![Page 49: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/49.jpg)
47Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
7LQ3 monitors for medical premises
Insulation monitors
Test and signaling panels
7LQ3355
Up to four 7LQ3360, 7XV9306, 7XV9304 or 7XV9302 test and signaling combinations can be connected; cf. connection example and comparison of contact assignment between previous and current test and signaling combinations
3,15 … 8 kVA
11 21 31 41 51 6114 24 34 44 54 6412 22 32 42 52 62
P1
LT1
LT2
P2 i k L PE PTA1 A2
PE PEN L2
230 V AC
L1)
L1
7LQ3355
> >
L' PE'
7LQ3360
X1 X2 X5
X1 X2 X5 PT1 PT2
PE PT
Overtemperature Overcurrent
Transformer protection
Current transfor.
ResetExternal
External test
Insulation monitor
R <F ALR /Measuring circuit break
Insulation fault
Jumpers =non-latching
Isolating transformer
1) If there is no center tap, L/L' is connected to L1 or L2.Test and
signaling combination
7LQ3358
I201
_139
94a
X1 ... X7 Fault signaling inputs
X8 Acknowledgement horn/lamp test
SM Central indication output
PT1, PT2 Test button for insulation monitors
7LQ3356, 7LQ3357
X1
PT1PT2
PT PE
X2 X3 X4 X5 X6 X7 X8 SM A1
A2
L(L+)
N(L-)
1 2 3 4 65 7 8
externoQH / LT
7LQ3354 / 7LQ3355
7LQ3356 /7LQ3357
11 14 31 34 51 54
OK
Failu
re
OK
Failu
re
Line 2Line 1
Voltage monitoring
I201
_139
91a
© Siemens AG 2016
![Page 50: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/50.jpg)
48 Siemens · 10/2015
7LQ3 monitors for medical premises
Monitoring DevicesMonitoring Devices for Electrical Values
Connection example for 7LQ3355 insulation monitors with 7XV9306 test and signaling combination
Up to four test and signaling combinations (e.g. the 7LQ3360 test and signaling combination and the previous 7XV9306, 7XV9304 or 7XV9302 test and signaling combinations (now no longer available) can be connected.
An external 24 V AC (e.g. 4AC3616) transformer is required to power the test and signaling combination.
7LQ3355
11 14 12 21 24 22 31 34 32 41 44 42 51 54 52 61 64 62
PT 52 51 PE
X1 X2 X5
P1
LT1
LT2
P2 i k L PE PTA1 A2
PE PEN L2
L L1
L ' PE '
1)
4
5
2
3
6
18
A2A1 15
4
5
2
3
6
4
5
2
3
6
4
5
2
3
6
B1
2)
RF < R
1) If there is no center tap, L/L' is connected to L1 or L2.2) The 24 V AC power supply unit needs to be powered over the IT system.
230 V AC
> >
Isolating transformer3.15 ... 8 kVA
Current transformer
Transformer protection
Overtemperature Overcurrenton
/ measuring circuit interruptionInsulation fault
Insulation monitor
External test
ResetExternal
Jumper =non-latching
24 V AC
I201_13812d
7LQ3358
7LQ
5TT
7XV9306
7XV9306
7XV9306
7XV9306
© Siemens AG 2016
![Page 51: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/51.jpg)
49Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
7LQ3 monitors for medical premises
Comparison between the contact assignment for the previous, no longer available test and signaling combinations 7XV9306, 7XV9304 and 7XV9302 and the contact assignment for the current 7LQ3360 test and signaling combination.
Monitoring of medical premises
Medical premises are all rooms used for the examination or treatment of persons or animals. Besides doctors' surgeries and clinics, these also include hydro-therapeutic and physical therapeutic treatment and massage rooms.
TÜV-certified switchover and monitoring devices are used for a reliable power supply. The insulation monitors and voltage relays in the switchover and monitoring devices need to comply with the requirements of standard DIN VDE 0100-710 and IEC 60364-7-710.
Medical premises were divided up into three groups in DIN VDE 0100-710, which was published in 2002.
For premises in groups 0 and 1, the standard requires, among other things, implementation of the system type TN-S and residual current protective devices (RCDs) for protection against excessively high touch voltages.
The premises of group 2 are defined as follows:• The system must not be disconnected in the event of a first
short circuit to frame or to ground or if the general power supply fails
• Repetition of treatment is unacceptable for patients or it is impossible to obtain results of examinations again
• An irregularity (a fault) in the power supply can cause danger to life
• A piece of equipment used for medical purposes, which is used occasionally for applications in accordance with DIN VDE 0100-710.2.7, should be assigned to group 2
Typical locations in group 2 are anesthetic rooms, operating rooms and recovery rooms in hospitals, clinics or doctors' surgeries, as well as equipment used in veterinary medicine.
Standard DIN VDE 0100-710 makes the following stipulations:• Constant monitoring of the power supply on the preferred
supply line and on the second supply line• Automatic changeover to the 2nd supply line within a defined
time (< 0.5 s or < 15 s)• Reliable operation even if a fault occurs
(one-fault security)
The switchover device monitors the supply voltage on the preferred and second supply line for undervoltage and power failure. As soon as a voltage drop to a defined value is determined, the voltage relays respond and the switchover device automatically switches to the second supply line. As soon as the power is restored on the preferred supply line, the system switches back to it.
IT system
In the IT system name, the first letter describes the grounding relationships of the current source. I stands for insulation of all live parts from ground or connection of a point to ground via an impedance. The second letter identifies the grounding relationships of the body of the electrical system.
T means that the body is directly grounded, independently of any existing grounding of a point of the power source.
Medical IT systems
Standard DIN VDE 0100-710 makes the following stipulations for a medical IT system in group 2:• The medical IT system must be used for socket outlet circuits
in the patient environment. This also applies for circuits supplying operating room lights
• At least one IT system is required for each room group• Separate circuits must be provided for multiple socket outlets• First faults must not lead to disconnection of the system
The IT system is powered by an isolating transformer or an independent power source (such as a battery). The special feature is that no active conductors in this network are linked directly to ground. This has the advantage that only a small residual current can flow in the event of an insulation fault. This is essentially dictated by the leakage capacitances and is harmless to patients and staff. The upstream fuse element does not respond so that the power supply, and therefore operation, is maintained, even in the event of a phase-to-ground fault. The high reliability of an IT system is ensured by continuous insulation monitoring. The insulation monitor detects insulation faults as they develop and signals in good time if a value falls below a limit value, before any further insulation faults can lead to an unexpected shutdown. The temperature of the transformer and the transformer load continue to be monitored constantly. Any exceeding of limit values is signaled immediately.
31
32
33
34
35
7XV93027XV93047XV9306
1
23
3
4
5
2
4
5
6
X5
PT1
PT2
X2
X1
7LQ3360
Test
24 V AC
Fault input
I201
1381
3c
I201_12110
L2L3
L1
Body
IT system
PE
© Siemens AG 2016
![Page 52: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/52.jpg)
50 Siemens · 10/2015
7LQ3 monitors for medical premises
Monitoring DevicesMonitoring Devices for Electrical Values
Insulation monitoring
The 7LQ3354 and 7LQ3355 insulation monitors are used to monitor the insulation resistance of non-grounded IT systems in medical premises. They also simultaneously monitor the load current and the temperature of the IT isolating transformer. The devices can monitor both three-phase and AC systems.
Temperature measurement: The temperature in the transformer winding is recorded using a PTC thermistor or NC contacts.
As well as an adjustable response value of 50 ... 500 kΩ, the 7LQ3355 insulation monitor also has an 11-step LED chain for displaying the current insulation resistance of the system. A range of differently colored LEDs indicates the insulation resistance within the range of 20 kΩ … 1 MΩ. This allows insulation deteriorations to be detected even before an alarm is triggered. The device is also equipped with an additional relay for connection of a test and signaling combination. This allows the 7LQ3360 test and signaling combination and the previous and no longer available test and signaling combinations 7XV9306, 7XV9304 and 7XV9302 to be connected to the 7LQ3355 insulation monitor (see also the graphic under "Connection example: 7LQ3355 insulation monitors with 7XV9306 test and signaling combination").
Load current sensing: The 7LQ3358 current transformer detects the load current of a phase. Evaluation is carried out over the 7LQ3354 and 7LQ3355 insulation monitors.
Evaluation: If one of the values is outside the limit values, an alarm is triggered. The LED for the relevant fault lights up and the alarm relay switches. The information is made available over the changeover contacts and can be displayed on the 7LQ3356 and 7LQ3357 test and signaling panels.
Voltage monitoring
In the case of undervoltage, there is no guarantee that medical equipment will continue to function. Because of the risk this presents to patients, e.g. during operations, it is essential that a switchover unit switches to a second power supply in the event of an undervoltage in the preferred power supply.
The voltage relays switch when the voltage falls below 90 % of the rated voltage. The 5TT3411 relays serve to monitor a 1-phase infeed. 3-phase infeeds can be monitored using 5TT3412 relays. These relays also offer asymmetry, reverse voltage and phase failure detection.
TÜV-certified switchover device
The 7LQ3361 and 7LQ3362 switchover devices have been tested and certified by TÜV Rhineland. Switchover devices comply with DIN VDE 0100-710:2002-11 and IEC 60364-7-710:2002-11.
Rhineland TÜV certificate for 7LQ3361 and 7LQ3362 switchover devices
© Siemens AG 2016
![Page 53: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/53.jpg)
51Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Electrical Values
7LQ3 monitors for medical premises
Components and control elements in 7LQ3361 and 7LQ3362 switchover devices
Control elements for insulation monitors
I201
_170
73
1
4
5
6
7
2
3
8
Meaning
1 Terminal block X1
2 Terminal block X2
3 Terminal block X3
4 Mechanical latching
5 Miniature circuit breakers
6 Voltage relay test pushbuttons
7 Insulation monitors
8 Temperature monitoring test pushbuttons
7LQ3354
7LQ3355
A1 P1 P2 i k PE PT LT1 LT2
14 2411 21 34 31 44 41 54 51 64 61
PE‘ LL‘A2
52 6232 4212 22
1 2 3 54
76
89
11
10
I201
_137
16
P2P1 i k PE‘
L‘
PE
L
PT LT1 LT2A1
2124 3134 4144 54 51 64 61 X2 X514
22 32 42 52 62 X112
11
A2
1 2 3 545a
76
89
119a
10
I201
_138
14
LED Meaning
1 Current monitoring (green)
Lights up if the current is correct (Go state)
2 Current monitoring">I" (red)
Lights up in the case of overcurrent
3 Insulation monitoring "ON" (green)
Lights up when the power supply is switched on (ready-to-run)
4 Insulation monitoring "MK" (red)
Lights up if a line of the measuring circuit is interrupted (L, L’, PE, PE’)
5 Insulation monitoring "AL" (red)
Lights up in the case of an insulation fault, RF<Ran (value has fallen below the response value)
5a Insulation monitoring "RF" (red, yellow, green)
11-step LED chain to display the current resistance
6 Temperature monitoring (green)
Lights up when the power supply is switched on
7 Temperature monitoring (red)
Lights up in the event of overtemperature or an interruption in the sensor circuit
Pushbutton/rotary controller
Meaning
8 Rotary controller response value ">I"
Setting of the response value for current monitoring
9 Rotary controller delay time
Setting of delay time after which the CO contacts return to their normal position if the current value exceeds the set response value.
9a Rotary controller response value "Ran kΩ"
Setting of the response value for insulation monitoring
10 "TEST" pushbutton Pressing the "Test" test button simulates an insulation deterioration in the measuring circuit (RF approx. 40 kΩ), thus checking that the insulation monitor is fully functional
11 "RESET" button Deletion of fault if fault storage is activated
© Siemens AG 2016
![Page 54: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/54.jpg)
52 Siemens · 10/2015
7LQ3 monitors for medical premises
Monitoring DevicesMonitoring Devices for Electrical Values
Control elements of the test and signaling panels
Note: Customized reporting and signaling panels can be produced, for instance with an integrated intercom, for the switchover and monitoring devices. For more information on this contact your local Siemens representative.
Control elements of the test and signaling combination
Control elements of voltage relay
7LQ3356, 7LQ3357
I201
_139
95
>
7LQ3 356
line 1on
line 1failure
insulationok
test
line 2failure
line 2on
LED window displays Meaning
Line 1 On Power supply is implemented over the preferred infeed
Line 2 On + Line 1 Failure
Power supply is implemented over the second line as the preferred infeed has failed
Line 1 On + Line 2 Failure
Power supply is implemented over the preferred infeed. However the second line is no longer available
Line 2 On + Line 1 Failure + Line 2 Failure
Power supply is implemented over the second line as the preferred infeed is faulty. There is undervoltage on the second line
Overload Excessive power consumption of the IT system
Overtemperature The transformer of the IT system is overloaded
Insulation is good The transformer of the IT system is overloaded
Insulation is defective The insulation resistance of the IT system is too low
TEST Pushbutton for testing the insulation monitoring devices
Acknowledgement pushbutton/lamp test
Pushbutton for acknowledging the acoustic alarm signal/function test of the display elements
7LQ3360
I201
_139
96
ON
TEST
LED/pushbutton Meaning
ON Green LED The LED lights up if the power supply is applied
Ground fault
Yellow LED Insulation fault: The insulation resistance of the IT system is too low
TEST Pushbutton for testing the insulation monitoring devices
Acknowledgement pushbutton
Button for acknowledging the acoustic alarm signal
5TT3411 5TT3412
N La
Lb
Y1 Y2 11 12
41 42
23 24
33 34
12
L3L2L1 N
241114
23 31
3212
12
2
2
I201
_137
20
LED/pushbutton Meaning
1 5TT3411: Yellow LED 5TT3412: Green LED
The LED lights up if the system is fault-free
2 TEST button Pressing the test button simulates an undervoltage. The 3-phase 5TT3412 voltage relay has a test button for each phase.
© Siemens AG 2016
![Page 55: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/55.jpg)
53Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Plants and Equipment
5TT3 fault signaling units
■ Overview
Fault signaling units are used in small plants where the installation of complex fault signaling systems would be too labor-intensive and too expensive. In the event of a fault, they enable fast fault localization of all monitoring devices and limit monitors installed in a plant from a central location. This increases plant availability. With the correct sensor configuration, they also provide the option of preventative maintenance.• 4 fault signaling inputs with LED• 1 LED as centralized fault indicator
• One unit each for centralized fault indication and acoustic signaling
• With acknowledgment for acoustic indicators• Open/closed-circuit principle so the 4 inputs can be adjusted
via jumpers X1 - X2• A maximum of 39 5TT3461 expansion fault signaling units can
be connected to the 5TT3460 centralized fault signaling unit• The maximum possible cable length between 5TT3460
centralized fault signaling units and 5TT3461 expansion fault signaling units is approx. 100 m with a conductor cross-section of 1.5 mm2
■ Technical specifications
■ Dimensional drawings
■ Circuit diagrams
Graphical symbols
5TT3460 5TT3461
Standards IEC 60255; DIN VDE 0435-110, -303
Rated operational voltage Uc V AC 230
Primary operating range × Uc 0.8 ... 1.1
Rated frequency fn Hz 50/60
Fault signaling inputs S1 ... S4 V AC 230
Signal voltage
To terminals S and H
V 7 ... 10
Noise pulse duration ms ≥ 100
Acknowledgment pulse duration ms ≥ 200
Contacts
• Rated operational voltage Ue V AC 230 --
• Rated operational current Ie A 5 --
• Minimum contact load V; mA 10; 100 --
Connections
• Terminals ± Screw (Pozidriv) PZ 1
• Conductor cross-sections- Rigid, max. mm2 2 × 2.5- Flexible, with end sleeve, min. mm2 1 × 0.5
Permissible ambient temperature °C -20 ... +60
Humidity class Acc. to IEC 60068-2-30 F
5TT3460 5TT3461
5 4364
45 90
I201
_115
11a
36 36
A1 S H
S1 S2 S3 S4
A1 S H
S1 S2 S3 S4
14 24 QH A2
13 23 X1 X2
A2
X1 X2
5TT3460 5TT3461
24
23
14
13
I201
_001
54
QHHSX2X1
S4S3S2A1 A2 S1
I201
_001
55
HSX2X1
S4S3S2A1 A2 S1
© Siemens AG 2016
![Page 56: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/56.jpg)
54 Siemens · 10/2015
5TT3 fault signaling units
Monitoring DevicesMonitoring Devices for Plants and Equipment
Typical circuit, function chart
If there is a fault, the SM fault indication contact closes and a centralized fault is indicated over an LED. The assigned LED remains lit until the fault is eliminated. Until the acknowledgment, momentary faults can be identified by the remaining centralized fault.
The terminals A1, S1 to S4 and QH must be operated in-phase. If no external acknowledgment key is connected, terminal QH must be applied to L1.
If jumper X1 – X2 is inserted, open-circuit protection (otherwise closed-circuit protection).
Contacts 13/14 and 23/24 close in the event of an incoming fault. The assigned LED and the SM centralized fault indication LED light up.
The alarm sensor (contact 13/14) is switched off using the acknowledgment key. The assigned LED and the centralized fault indication LED continue to light up and contact 23/24 remains closed until the fault is eliminated.
Cables S and H carry an extra-low voltage. In the case of long connections between different distribution boards a shielded cable must be laid parallel to the installed load lines.
As a light signal sensor for the group messages we recommend devices 5TE57 or 5TE58; as an alarm sensor the devices 5TT3450 to 5TT3453.
A1 A2
N
13 23 S1 S2 S3 S4 A1 A2 S1 S2 S3 S4
X1 X2 S HX1 X2 S H
QH
SM14 24
5TT3460 5TT3461
I201
_072
82d
L1 230 V AC
(Working current) (Closed-circuit current)
Acknow-ledgementkey
FaultalarmFA
I201_07283c
Fault 1
LED 1
Fault 2
LED 2
Central indicationrelay
Central indicationhorn
Acknowledge.horn
dark bright
LED SM
© Siemens AG 2016
![Page 57: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/57.jpg)
55Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Plants and Equipment
5TT5 EMERGENCY STOP modules
■ Overview
EMERGENCY STOP circuits are common safety measures in all laboratory equipment and industrial plants. The EMERGENCY STOP modules used here must meet the most rigorous demands
with regard to functional reliability. Benchmark is the degree of self-monitoring.
■ Technical specifications
■ Dimensional drawings
5TT5200 EMERGENCY STOP module
5TT5200
Standards IEC 60204-1; EN 60204-1 (VDE 0113-1)
Supply
• Rated operational voltage Uc V AC 230- Primary operating range × Uc 0.8 ... 1.1
• Rated frequency fn Hz 50
• Rated power loss Pv Coil/drive 3.5Contact per pole VA 0.8
Control voltage Terminal Y1 V AC/DC 24
Control current Terminal Y1 mA DC 45
Recovery time ms 500
Safety
• Electrical isolation, creepage distances and clearances, actuator/contact mm 3
• Rated impulse withstand voltage Uimp actuator/contact kV > 4
Contacts
• Contacts NO contacts AC-15 A 3NC contacts AC-15 A 2NO contact/NC contact
AC-1 A 5
• Contact gap mm > 1
• Electrical service life AC-15, 2 A, 230 V AC Switching cycles
105
• Permissible switching frequency Switching cycles/h
600
Vibration resistanceAmplitude Acc. to
EN 60068-2-610Up to 55 Hz
mm 0.35
Connections
• Terminals ± Screw (Pozidriv) PZ 1
• Conductor cross-sections of main current paths- Rigid Max. mm2 2 × 2.5- Flexible, with end sleeve Min. mm2 1 × 0.5
Permissible ambient temperature °C 0 ... +50
Climatic withstand capability Acc. to EN 60068-1 0/55/04
4355
45 90
571
33
A2
13Y1
16
Y2
23 41
3414 24 42
K1/2
A1
I201
_084
37a
A1
Sup
ply
© Siemens AG 2016
![Page 58: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/58.jpg)
56 Siemens · 10/2015
5TT5 EMERGENCY STOP modules
Monitoring DevicesMonitoring Devices for Plants and Equipment
■ Circuit diagrams
Typical circuit diagrams
Direct connection 230 V/400 V to 5 A
The monitoring logic checks internal relay contacts (not shown) to see whether both relays have been released prior to switching on. This ensures that no contacts are welded. The voltage level at terminal A1 is also monitored. The parallel NC contacts K1 and K2 (terminals 41 and 42) can be connected as required.
Connection of external contactors
External contactors may be used when they are equipped with positively driven contacts according to safety regulations ZH1/457 of the German Trade Association. Contactors with 3 NO contacts and 1 NC contact must be used, in which case the NC contacts must be integrated in the monitoring loop – terminals Y1/Y2. The parallel NC contacts K1 and K2 (terminals 41 and 42) can be connected as required.
L1
A1 Y1 13 23 33 41
14 24 34 42
K2
K1
A2
NI201_08435b
Y2
EMERGENCY-STOP
Monitoringlogic
On
L1
A1 Y1 13 23 33 41
14 24 34 42
K2
K1
A2
I201_08436b
K3
K4
Y2
K4
K3
L1 L2 L3
N N
EMERGENCY-STOP
Monitoringlogic
On
© Siemens AG 2016
![Page 59: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/59.jpg)
57Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Plants and Equipment
5TT3 level relays
■ Overview
Level relays are used for the monitoring and control of con-ductive, non-combustible liquids and powders. They ensure overflow and dry run protection. Due to their sensor perfor-mance, the devices can also be used for general resistance monitoring.
LED displays:- Green LED: lights up when operational voltage is applied- Yellow LED: lights up if MIN output relay is activated- Red LED: lights up if MAX output relay is activated
■ Technical specifications
■ Dimensional drawings
5TT3435 level relays 5TG8223 immersion electrodes
5TT3435
Standards IEC 60255; DIN VDE 0435-110
Supply
• Rated operational voltage Uc V AC 230- Primary operating range × Uc 0.8 ... 1.1
• Rated frequency fn Hz 50/60
Setting range of the liquid level kΩ 2 ... 450
Switching point hysteresis of set value
• At 450 kΩ % 3• At 2 kΩ % 6
Voltage temperature influence From set value % < 2
Max. cable length to the Setting kΩelectrodes at 100 μF/km 450 m 50
100 m 20035 m 50010 m 15005 m 3000
Electrode voltage Max. V AC Approx. 10
Electrode current Max. mA AC Approx. 1.5
Response delay Adjustable s 0.2 ... 20
OFF-delay Adjustable s 0.2 ... 20
Rated operational voltage Ue V 250
Rated operational current Ie A 5
Test voltageInput/auxiliary circuit kV 4Input/output circuit kV 4Auxiliary/output circuit kV 4
Connections
• Terminals ± Screw (Pozidriv) PZ 2
• Conductor cross-sections- Rigid Max. mm2 2 × 2.5- Flexible, with end sleeve Min. mm2 1 × 0.5
Permissible ambient temperature °C -20 ... +60
Climatic withstand capability Acc. to EN 60068-1 20/60/4
5TT3435
36 5 4364
45 90
I201
_137
60
COMX1 X2
MINMAXA1A2
12 22
14 11 24 21
5TG8223
7914
013
5
Ø16
21
5I2
01_1
2435
© Siemens AG 2016
![Page 60: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/60.jpg)
58 Siemens · 10/2015
5TT3 level relays
Monitoring DevicesMonitoring Devices for Plants and Equipment
■ Circuit diagrams
Graphical symbols
Typical circuit for 5TT3435
One-step level control
Two-step level control
X1
MIN MAX COM
X2 A1 A2 14
11 21
12 24 22
The one-step level control is particularly suitable for dry run or overrun protection with free inflow/outflow.
The COM reference electrode and MAX electrode are needed.
Without the jumper X1-COM only relay 21-22-24 switches.
With the jumper X1-COM both relays switch together.
21-2421-22
21-2421-22
COM X2
COM X2
MAX
0
11-14/21-2411-12/21-22
t
11-14/21-2411-12/21-22
COM X2
COM X2t t
X1
X1
X1
X1
COM X2
COM X2I2
01_0
7520
d
Supply
Level
Static current
Load current
L1 N
A1 A2
141112242122
COM MIN MAX X2
MIN
MAX
X1
I201
_075
18b
230 V AC
Level
t = tv max adjustable from 0.2 s to 20 s
The 2-step level control keeps the liquid level between a minimum and a maximum level. Three electrodes are required: MIN, MAX and COM.
Without the jumper X1-COM, switching is as follows:
• If the MAX level is fallen below/exceeded, only relay 21–22–24 switches.
• If the MIN level is fallen below/exceeded, only relay 11–12–14 switches.
With the jumper X1–COM, both relays switch together if the value exceeds the MAX level or falls below the MIN level.
L1 N
A1 A2
141112242122
COM MAXMIN X2
MIN
MAX
X1
I201
_075
19bLevel
230 V AC
21-2421-22
11-1411-12
COM X2
MAX
U0
MIN
H
12
X1
21-2421-22
11-1411-12
COM X2
min
X1
11-14, 21-2411-12, 21-22
max
COM X2X1
11-14, 21-2411-12, 21-22COM X2X1
COM X2
COM X2
I201
_075
21d
tvtv
mintvmaxtv
Level
Static current
Load current
tv max and tv min adjustable from 0.2 s to 20 s
© Siemens AG 2016
![Page 61: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/61.jpg)
59Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Plants and Equipment
5TT3 line circuit relays
■ Overview
Line circuit relays are used to interrupt circuits and prevent electromagnetic fields in circuits where there are currently no active loads. If the loads are disconnected, and the line circuit relay measures a usage of only 2 to 20 VA – adjustable – it disconnects the cable to the supply voltage and switches over to extra-low voltage. As soon as loads are reconnected, the line circuit relay detects the increase in usage and switches back to the supply voltage. While the line circuit relay switches off any unnecessary system
components, it is not a device for ensuring isolation in the sense of safe disconnection.
The line circuit relay is unable to detect consumers with electronic power supply units, e.g. electronically controlled vacuum cleaners. It is expedient to connect such devices to a base load resistor (PTC resistor) so that the line circuit relay is reset to supply voltage.
■ Technical specifications
■ Dimensional drawings
■ Circuit diagrams
Typical circuit diagram If the line circuit relay does not respond to a load, it must be connected with a 5TG8222 base load resistor. Devices in active standby operation may impair the function of the line circuit relay.
5TT3171
Standards IEC 60255; DIN VDE 0435-110
Rated operational voltage Uc V AC 230
Primary operating range × Uc 0.85 ... 1.15
Rated frequency Hz 50/60
Rated power loss Pv Electronics VA 5Contacts VA 2.6
Monitoring voltage V 3
Response value Adjustable VA 2 ... 20
Release value % of the response value 70
Rated impulse withstand voltage Uimp Input/output kV > 4
Rated operational voltage Ue V AC 250
Rated operational current Ie AC-1 A 16AC-11 A 3
Contacts μ contact
Electrical service life In switching cycles at 3 A AC-11 5 × 105
Terminals ± Screw (Pozidriv) PZ 1
Conductor cross-sections
• Rigid Max. mm2 2 × 2.5• Flexible, with end sleeve Min. mm2 1 × 0.5
Permissible ambient temperature °C -20 ... +45
Degree of protection Acc. to IEC/EN 60529 IP20, with connected conductors
Safety class Acc. to EN 61140/VDE 0140-1 II
Humidity class Acc. to IEC 60068-2-30 F
5TT3171
L N
5 4364
18
I201
_107
75a
45 90
L N
L1N
PTC
i
I201
_070
36b
230 V AC
Elec-tronic
© Siemens AG 2016
![Page 62: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/62.jpg)
60 Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Plants and Equipment
■ Overview
The p.f. monitor monitors the phase displacement between current and voltage. Because the phase displacement angle changes with the load of the motor, this measurement method is ideal for the monitoring of asynchronous motors for underload and no-load operation, independent of size. However, in some cases, the p.f. barely changes if the load of the motor changes, e.g. in the case of relatively minor load changes on large-scale motors or single-phase split-pole motors or collector motors.
The p.f. monitor monitors single and three-phase asynchronous motors up to approx. 5 A (without current transformer) for underload and no-load operation, thus increasing plant availability. Typical applications are fan monitoring in the case of V-belt breakage, pump monitoring in the event of valve closure
or dry runs. A current transformer is used for higher rated currents.
If the lower p.f. value set at the p.f. monitor is violated for the duration of the set response delay, the output relay switches to the alarm state and the red LED lights up. If the higher p.f. value is violated, the output relay switches back without any significant delay.• Adjustable p.f. response value, from 0 to 0.97• Current range up to 8 A• LED display for operation and alarm• Automatic resetting of alarm
■ Technical specifications
■ Dimensional drawings
5TT3472
5TT3472
Standards IEC/EN 60255, VDE 0435
Rated operational voltage Uc 3 V AC 400
Primary operating range With AC supply × Uc 0.8 ... 1.1
Frequency range fn Hz 45 ... 65
Rated power loss Pv VA Approx. 11
Rated impulse withstand voltage Uimp Against contacts kV < 4
Current measuring circuits For AC systems
Current measuring range Imeas A AC 0.4 ... 8
Short-time load carrying capacity For 2 s A 20For 0.5 s A 40
Current transformer, class 3 or better Secondary current A 1 or 5
Setting range Adjustable p.f. 0 ... 0.97
Response delay Adjustable s 1 ... 100
Short-circuit strength Fuse 4 A gL A 4
Contacts μ contact 1 CO
• Rated operational voltage Ue V AC 250
• Rated operational current Ie Thermal current A 4AC-15 NO contacts A 3AC-15 NC contacts A 1AC-13 at 24 V DC A 1
• Minimum contact load V; mA 10; 100
Connections
• Terminals ± Screw (Pozidriv) PZ 2
• Conductor cross-sections- Rigid Max. mm2 2 × 2.5- Flexible, with end sleeve Min. mm2 1 × 0.5
Permissible ambient temperature °C -20 ... +60
Resistance to climate Acc. to EN 60068-1 20/60/4
Degree of protection Acc. to EN 60529 IP20, with connected conductors
L3
L1
12
141
18 5 43
45 90
I201
_115
28b
1
L2
64
L1'
5TT3 p.f. monitors
© Siemens AG 2016
![Page 63: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/63.jpg)
61Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Plants and Equipment
■ Circuit diagrams
■ More information
Function charts
If the lower p.f. value set at the p.f. monitor is violated for the duration of the set response delay, the output relay switches to the alarm state and the red LED lights up. Contact 11–14 closes and the red LED lights up.
Front view
Connection of three-phase load Connection of single-phase load
Connection of motors with separate windings
Connection of three-phase load with external current transformer, whereby the winding direction of the current transformer must be taken into account.
L1
11 12 14
L1' L2 L3
L1
M3
L2
L3
I201
_115
24b
L1
11 12 14
L2 L3
L
N
I201
_115
25b
L1'
Load
L1
11 12 14
L1' L2 L3
L1
M3
L2
L3
Kk
l L
Kk
l L
1W11V1
1U1
2W12V1
2U1
I201
_115
27b
LowSpeed
HighSpeed
L1
11 12 14
L1' L2 L3
L1
M3
L2
L3
K L
k l
I201
_115
26b
Tripp.f.
I201
_115
23b
11-1411-12
ty
U(L1/L2/L3)
I(L1/L2)
L3 L2
11
L1 L1'
14
I201
_119
73a12
E1
E2LED red
LED green
Underloading indicator (p.f. alarm)LED red:Response valueE1:Response delay tyE2:
LED green: Status display (U)
5TT3 p.f. monitors
© Siemens AG 2016
![Page 64: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/64.jpg)
62 Siemens · 10/2015
5TT3 motor protection relays
Monitoring DevicesMonitoring Devices for Plants and Equipment
■ Overview
Thermistor motor protection relays monitor the thermistors wound in motors. This helps to prevent thermal motor overloads, e.g. due to high switching frequency, single-phasing, disabled cooling or excessive ambient temperatures. Up to 6 thermistors in series can be monitored. A conductor break in the sensor conductor will immediately trip the device. The device can also be used for monitoring wound quick-break switches – e.g. bimetal thermostats. This offers all-round motor protection.• For the detection of
- Violation of upper temperature limits- Wire breaks in sensor circuits
• 1 input for 1 to 6 thermistors• With 2 LEDs green/red for ready-to-run and fault
• Response value: 3.2 to 3.8 kΩ• Release value: 1.5 to 1.8 kΩ• The max. cable length of the sensor supply cable NYM 2 × 1.5
is 100 m• Remote Reset: over A1/A2 (NC contact) or over X1/X2
(NO contact)
LED displays:• Green LED: Lights up when operational voltage is applied• Red LED: Lights up in the event of overtemperatures or an
interruption in the sensor circuit
■ Technical specifications
■ Dimensional drawings
5TT343 motor protection relays
5TT34315TT3432
Standards IEC 60255; DIN VDE 0435-110
Rated operational voltage Uc V AC 230
Primary operating range × Uc 0.9 ... 1.1
Rated frequency Hz 50/60
Response value kΩ 3.2 ... 3.8
Release value kΩ 1.5 ... 1.8
Minimum contact load V; mA 10; 100
Rated insulation voltage Ui Between coil/contact kV 4
Rated impulse withstand voltage Uimp Actuator/contact kV > 2.5
Contacts μ contact (AC-11) A 3
• Rated operational voltage Ue V AC 230
• Rated operational current Ie A 5Actuator/contact mm 4
Connections
• Terminals ± Screw (Pozidriv) PZ 1
• Conductor cross-sections- Rigid Max. mm2 2 x 2.5- Flexible, with end sleeve Min. mm2 1 x 0.5
Permissible ambient temperature °C -20 ... +60
Climatic withstand capability Acc. to EN 60068-1 20/60/4
5TT3431 5TT3432
36 36 5 4364
45 90
I201
_115
30a
A1 P1 P2 A1
A1
12
14 11 24 2114 11 24 21
2212 22
P1 P2
X1 X2A2
© Siemens AG 2016
![Page 65: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/65.jpg)
63Siemens · 10/2015
Monitoring DevicesMonitoring Devices for Plants and Equipment
5TT3 motor protection relays
■ Circuit diagrams
Graphical symbols
Typical circuit for 5TT3431, 5TT3432
If one of the thermistors (possible for up to 6) reaches the response temperature, the device switches.
5TT3431 (without terminals X1/X2 and without RESET button) switches back on after cooling and after the value falls below that permanently set for the hysteresis. To switch on before this time, briefly disconnect the power supply.
5TT3432 stores the fault and remains switched off until the RESET button is pressed.
5TT3431 5TT3432
2111
22241214
P1 P2
A1 A2
2111
22241214
X2X1P2P1
A1 A2
L1 N
A1 A2
141112242122
X2X1
1...6 v +
M
I201_07041c
Resetpushbutton
230 V AC
R
I201_07280e
11-14
P1/P2
5TT3432: 11-12
11-14 5TT3431: 11-12
(X1/X2)
HU
t
t
3,2 k
1,8 k
TEST/RESET
TEST/RESET
TEST/RESETpushbutton
Overtemperature/sensor breakage
Voltagefailure RESET
© Siemens AG 2016
![Page 66: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/66.jpg)
64 Siemens · 10/2015
Notes
Monitoring Devices
© Siemens AG 2016
![Page 67: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/67.jpg)
© Siemens AG 2016
![Page 68: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system](https://reader031.vdocument.in/reader031/viewer/2022022600/5b3af32b7f8b9a4b0a8e7059/html5/thumbnails/68.jpg)
The information provided in this brochure contains merely generaldescriptions or characteristics of performance which in case of actualuse do not always apply as described or which may change as a resultof further development of the products. An obligation to provide therespective characteristics shall only exist if expressly agreed in theterms of contract. Availability and technical specifications are subjectto change without notice.All product designations may be trademarks or product names ofSiemens AG or supplier companies whose use by third parties for theirown purposes could violate the rights of the owners.
Siemens AGEnergy ManagementLow Voltage & ProductsPostfach 10 09 5393009 REGENSBURGGERMANY
Subject to change without prior noticePDF (3ZW1012-5SV80-0AC1)PH 0216 64 EnProduced in Germany© Siemens AG 2016