Page 1: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

SENTRON

Monitoring Devices

siemens.com/lowvoltage

Configu-rationManual

Edition10/2015

© Siemens AG 2016

Page 2: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

© Siemens AG 2016

Page 3: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

Siemens · 10/2015

For further technical product information:

Siemens Industry Online Support:www.siemens.com/lowvoltage/product-support .

→ Entry type: Application exampleCertificateCharacteristicDownloadFAQManualProduct noteSoftware archiveTechnical data

2 Introduction

Monitoring devices for electrical values

5 5SV8 residual current monitors11 5TT3 voltage relays19 5TT3 voltage and frequency relays22 5TT6 current relays27 5TT3 reverse power relays 28 5TT3 fuse monitors29 5TT3 phase and phase sequence

monitors31 5TT3 insulation monitors for industrial

applications34 7LQ3 monitors for medical premises

Monitoring devices for plants and equipment

53 5TT3 fault signaling units55 5TT5 EMERGENCY STOP modules57 5TT3 level relays59 5TT3 line circuit relays60 5TT3 p.f. monitors 62 5TT3 motor protection relays

Monitoring Devices

© Siemens AG 2016

Page 4: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

2 Siemens · 10/2015

Introduction

Monitoring Devices

■ Overview

Devices Page Application Standards Used in

Non

-res

iden

tial

bui

ldin

gs

Res

iden

tial

bui

ldin

gs

Ind

ustr

y

Monitoring devices for electrical values5SV8 residual current monitors 5 To increase system availability and

operating safety through continuous monitoring of residual current in electrical systems and signaling if a defined threshold is exceeded.

IEC 62020; EN 62020 ✓ -- ✓

Modular residual current devices (MRCD)

5 The MRCD is a modular residual current device type for personnel and fire protection.

DIN EN 60947-2(Appendix M),

IEC 60947-2 (Appendix M)

✓ -- ✓

5TT3 voltage relays 11 Monitoring the voltage of emergency lighting in public buildings, short-time failures of 20 ms, for ensuring operational parameters for devices or system components or monitoring the neutral conductor for breaks.

IEC 60255; DIN VDE 0435-303; DIN VDE 0108; DIN VDE 0435; DIN VDE 0633

✓ -- ✓

5TT3 voltage and frequency relays 19 The voltage and frequency relay monitors the status of the grid in the case of in-plant generation systems. Violation of an upper or lower limit results in shutdown and disconnection of the generation system from the grid. This ensures a stable incoming supply system.

IEC/EN 60255-1; IEC/EN 61000; VDE-AR-N-4105

✓ ✓ ✓

5TT6 current relays 22 Monitoring of emergency and signal lighting and motors.

All current relays can be short-time overloaded and connected either with direct measurement or through transformers.

IEC 60255; DIN VDE 0435-303

✓ -- ✓

5TT3 reverse power relays 27 Reverse power relays are used in power supply systems, e.g. photovoltaic, wind power, water power and unit-type cogenerating stations, to control the reverse power. They prevent voltage being returned from the grid and causing damage if the infeed system itself fails or is damaged.

IEC 50255;DIN VDE 0435-303

✓ ✓ ✓

© Siemens AG 2016

Page 5: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

3Siemens · 10/2015

Monitoring Devices

Introduction

5TT3 fuse monitors 28 Monitoring of all types of low-voltage fuses.

Can be used in asymmetric systems afflicted with harmonics and regenerative feedback motors.

IEC 60255; DIN VDE 0435

✓ -- ✓

5TT3 phase and phase sequence monitors

29 For the visual signaling of phase failures or phase sequences in three-phase systems.

The phase sequence is arbitrary. The device is also suitable for 1, 2 or 3-phase operation.

IEC 60255; DIN VDE 0435

-- -- ✓

5TT3 insulation monitors for industrial applications

31 To increase system availability and operating safety through continuous monitoring of the isolation resistance in non-grounded direct voltage or AC voltage systems.

IEC 60255; IEC 61557

-- -- ✓

7LQ3 monitors for medical premises

34 For the insulation monitoring of a medical IT system or load current monitoring of an IT system transformer for a non-permissible temperature rise.

Monitoring of the voltage supply with automatic switchover.

EN 61557-8; IEC 61557-8; DIN VDE 0100-710; IEC 60364-7-710

✓ -- --

Monitoring devices for plants and equipment5TT3 fault signaling units 53 Evaluation and display of fault alarms

and alarm signals for monitoring industrial plants and control systems. With 4 inputs and connections for 39 expansion fault signaling units.

IEC 60255, DIN VDE 0435-303

✓ -- ✓

5TT5 EMERGENCY STOP modules 55 For EMERGENCY-OFF switching in accordance with the Directive 98/37/EC on Safety of Machines. Safe types of circuits for machines, plants or test stations in industrial, commercial and private enterprise applications.

According to the Machinery Directive 98/37/EC; EN 954-1

✓ -- ✓

Devices Page Application Standards Used in

Non

-res

iden

tial

bui

ldin

gs

Res

iden

tial

bui

ldin

gs

Ind

ustr

y

© Siemens AG 2016

Page 6: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

4 Siemens · 10/2015

Introduction

Monitoring Devices

Devices Page Application Standards Used in

Non

-res

iden

tial

bui

ldin

gs

Res

iden

tial

bui

ldin

gs

Ind

ustr

y

5TT3 level relays 57 Control of liquid levels in containers with 3 electrode connections for 1-step and 2-step level control. High immunity to interference of the measuring circuit isolated from the system.

IEC 60255, DIN VDE 0435

✓ -- ✓

5TT3 line circuit relays 59 For disconnecting the voltage of unused lines when loads are disabled.

IEC 60255,DIN VDE 0435

-- ✓ --

5TT3 p.f. monitors 60 For the monitoring of asynchronous motors for underload and no-load operation, e.g. fan monitoring in the case of V-belt breakage, filter blockages, pump monitoring in the event of valve closure or dry runs.

IEC 60255, IEC 61557

-- -- ✓

5TT3 motor protection relays 62 For the prevention of thermal motor overloads, e.g. due to high switching frequency, single-phasing, disabled cooling or excessive ambient temperatures. With detection of wire breaks in the sensor circuit.

IEC 60255, DIN VDE 0435

-- -- ✓

© Siemens AG 2016

Page 7: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

5Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

5SV8 residual current monitors

■ Overview

Plant and operating safety are becoming increasingly important alongside the protection of personnel. Shutdowns due to the unexpected tripping of protective devices cause high costs. However, it is possible to detect residual currents in the electrical installation before the protective device responds.

Residual current devices (RCD)

Residual current monitors (RCM) monitor residual current in electrical installations and issue a signal when the residual current exceeds a set value.

RCMs are used primarily in plants where a fault should result in a signal, but not in disconnection. This enables plant operators to detect faults and eliminate their causes before the protective devices disconnect the installation, which increases plant and operating safety and cuts costs.

Modular residual current devices (MRCD)

Modular residual current devices (MRCD) monitor residual currents in electrical systems and trip the MCCB via a shunt or UVR after an adjustable advance warning if the residual current exceeds a defined value. See accessories for molded case circuit breakers in Catalog LV 10, chapter "Molded case circuit breakers".

This makes it possible for you to offer molded case circuit breakers with personnel and fire protection in compliance with EN 60947-2 (Appendix M) (also as a retrofit).

Summation current transformer

The summation current transformer detects all conductors required to conduct the current, including the neutral conductor where applicable. In a fault-free system, the magnetizing effects of the conductors through which current is flowing cancel each other out for the summation current transformer, i.e. the sum of all currents is zero. If a residual current is flowing due to an insulation fault, a residual magnetic field is left in the core of the transformer and produces a voltage. This voltage is evaluated using the electronics of the RCM/MRCD. The switched contact can be used to operate an acoustic/optical signaling device, a higher-level control system or a circuit breaker for example.

Time characteristic of the rated residual current ΙΔn

■ Benefits

• Higher plant availability and operating safety through permanent monitoring of residual currents

• Adjustable limit values for residual current and response time enable timely detection and signaling – plant shutdowns are often avoidable

• Devices for every application: The summation current transformers are available in various sizes; the RCMs can be used optionally for signaling and/or switching

• Additional fire protection can be implemented using the monitoring system

100 % n

50 %

t

n

nR

esid

ual c

urre

nt

Time

Alarm

Disconnection

I202

_160

44

© Siemens AG 2016

Page 8: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

6 Siemens · 10/2015

5SV8 residual current monitors

Monitoring DevicesMonitoring Devices for Electrical Values

■ Technical specifications

1) INS: Instantaneous, SEL: Selective.

5SV8000-6KK 5SV8001-6KK 5SV8200-6KK 5SV8101-6KK

Standards EN 62020, IEC 62020 DIN EN 60947-2 (Appendix M), IEC 60947-2 (Appendix M)

Approvals UL --

Rated operational voltage Ue V AC 230 230 from a 1-phase auxiliary voltage source (also externally)

• Frequency Hz 50/60

Rated residual current ΙΔn• Type A A 0.03 ... 3 0.03 ... 3 0.03 ... 3 0.03 ... 3

(default setting: 30 mA)• Type AC A >3 5 ... 30 5 ... 30 --

Response time Δt s 0.02 ... 5 0.02 ... 10, INS, SEL1) 0.02 ... 10, INS, SEL1) ΙΔn = 30 mA: INS instantaneous

ΙΔn > 30 mA: INS - SEL - 0,06 ... 101)

(default setting INS)

Relay contacts 1 × alarm 1 × pre-alarm, 1 × alarm

1 × pre-alarm, 4 × alarm

1 × alarm, 1 × tripping operation

• Rated voltage V AC 230 230 230 230• Rated current A 6 6 6 6

Summation current transformer mm ∅ 20 ... 210 35 ... 210

Maximum cable length RCM/CT (shielded cable)

m 10

Conductor cross-section mm2 1.5 0.125 ... 2.08

Test/Reset Yes/Yes

External tripping operation/external reset

--/Yes Yes/Yes Yes/Yes Yes/Yes

Mounting width MW 2 3 3 3

Degree of protection• Contacts IP20• Front IP41

Operating temperature °C -10 ... +50

© Siemens AG 2016

Page 9: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

7Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

5SV8 residual current monitors

■ Dimensional drawings

Residual current monitor

5SV8101-6KK (approved configurations)

2 5SV8101-6KK

1 EN 60715 - TH35 - 7.5 35 - 15

5 5SV8702-0KK 35 mm 5SV8902-1KK5SV8703-0KK 70 mm 5SV8903-1KK5SV8704-0KK 105 mm 5SV8904-1KK5SV8705-0KK 140 mm 5SV8905-1KK5SV8706-0KK 210 mm 5SV8906-1KK

4 3 3

3VL17... 3VL9400-1ST00 3VL9400-1UP00

3VL27... 3VL9400-1ST00 3VL9400-1UP00

3VL37... 3VL9400-1ST00 3VL9400-1UP00

3VL47... 3VL9400-1ST00 3VL9400-1UP00

3VA20... 3VA9988-0BL30 3VA9908-0BB113VA21... 3VA9988-0BL32 3VA9908-0BB203VA22... 3VA9988-0BL33 3VA9908-0BB24

3VA9908-0BB25

3VA10... 3VA9988-0BL30 3VA9908-0BB113VA11... 3VA9988-0BL32 3VA9908-0BB20

3VA9988-0BL33 3VA9908-0BB243VA9908-0BB25

1 2

34

5

I201

_189

88

Standard DIN railResidual current deviceTrip elementMolded case circuit breakerSummation current transformer

12345

RCM analog, 5SV8000-6KK RCM digital, 5SV8001-6KK, 5SV8200-6KK,

MRCD, 5SV8101-6KK

36

45 67 85

44686

I202

_116

027

54 44686

45 67 85

I202

_160

28

© Siemens AG 2016

Page 10: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

8 Siemens · 10/2015

5SV8 residual current monitors

Monitoring DevicesMonitoring Devices for Electrical Values

Summation current transformer

Summation current transformer, 5SV8700-0KK Summation current transformer, 5SV8701-0KK

Type Dimen-sions

A B C D E F G

5SV8702-0KK 100 79 26 49 35 35 43

5SV8703-0KK 130 110 32 66 70 52 57

5SV8704-0KK 170 146 38 94 105 72 73

5SV8705-0KK 230 196 49 123 140 97 98

5SV8706-0KK 299 284 69 161 210 141 142

Type Rated current Maximum current1)

5SV8700-0KK ≤ 40 A 240 A

5SV8701-0KK ≤ 63 A 380 A

5SV8702-0KK ≤ 80 A 480 A

5SV8703-0KK ≤ 200 A 1200 A

5SV8704-0KK ≤ 250 A 1500 A

5SV8705-0KK ≤ 500 A 3000 A

5SV8706-0KK ≤ 600 A 3600 A1) Transient starting current, up to max. 2s

Summation current transformer, 5SV8702-0KK, 5SV8703-0KK, 5SV8704-0KK, 5SV8705-0KK, 5SV8706-0KK

All active conductors (including the neutral) must be routed through the transformer. Cables that are not routed through the transformer must keep to a minimum clearance of 20 cm. Moreover, the transformers must have an inside diameter that is at least 1.5 times larger than the outside diameter of the conductors that pass through it.

Summation current transformer, 5SV8702-0KK, 5SV8703-0KK, 5SV8704-0KK, 5SV8705-0KK, 5SV8706-0KK

Ø46

Ø20

2460

32 I202_16029

Ø59

Ø30

3070

32 I202_16030

ØE

G46

6,5

BF33

A

D

8

C

I202_16031

OK OKOKOK

I201

_194

65

© Siemens AG 2016

Page 11: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

9Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

5SV8 residual current monitors

■ Circuit diagrams

Residual current monitor

■ More information

Switch positions

RCM digital, 5SV8001-6KK:

RCM digital, 4 channels, 5SV8200-6KK

S/R = Set/Reset

L N

T1T2T3

1S1

1S2

1S1

1S2

T4

1S1

1S2

1S1

1S2

I202

_160

40a

Reset

Test

1 2 3 4 5 6 7 8 9

10 11 12 13 14 15

S/R

Alarm contact/alarm Trip contact/trip Alarm contact/alarm Trip contact/trip

Setting "Standard" "Standard" "+" "+"

Without power supply

With power supply

Over limit

CT disconnection

456 15

1413 4

56 15

1413

456 15

1413 4

56

456 4

56 15

1413

456 4

56 15

1413

© Siemens AG 2016

Page 12: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

10 Siemens · 10/2015

5SV8 residual current monitors

Monitoring DevicesMonitoring Devices for Electrical Values

RCM digital, 4 channels, 5SV8200-6KK:

Alarm contact/alarm Trip contacts/trip Trip contacts/trip

Setting "Standard" "Standard" "+"

Without power supply

With power supply

Over limit

CT disconnection

10 1 C1: 14C2: 14C3: 8C4: 8

C1: 13C2: 15C3: 7C4: 9

C1: 14C2: 14C3: 8C4: 8

C1: 13C2: 15C3: 7C4: 9

10 1 C1: 14C2: 14C3: 8C4: 8

C1: 13C2: 15C3: 7C4: 9

C1: 14C2: 14C3: 8C4: 8

C1: 13C2: 15C3: 7C4: 9

10 1 C1: 14C2: 14C3: 8C4: 8

C1: 13C2: 15C3: 7C4: 9

C1: 14C2: 14C3: 8C4: 8

C1: 13C2: 15C3: 7C4: 9

10 1 C1: 14C2: 14C3: 8C4: 8

C1: 13C2: 15C3: 7C4: 9

C1: 14C2: 14C3: 8C4: 8

C1: 13C2: 15C3: 7C4: 9

© Siemens AG 2016

Page 13: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

11Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

5TT3 voltage relays

■ Overview

Voltage relays are used for device and plant protection, supplying safety light devices and the detection of N-conductor breaks and short-time voltage interruptions.

They are available as undervoltage, overvoltage and under / overvoltage relays. The devices are equipped with different functions, depending on their intended use, and comply with the pertinent regulations.

■ Technical specifications

1) For rated operational current.

5TT3400 5TT3404 5TT3406 5TT3194 5TT31955TT3401 5TT34055TT34025TT3403

Standards IEC 60255; DIN VDE 0435-110, -303

Rated operational voltage Uc V AC 230/400 400

Operating range (overload capability) × Uc 1.1 1.35

Rated frequency Hz 50/60

Response values ON-switching × Uc 0.9/0.95 4 % hysteresisOFF-switching 0.7/0.85 0.7 ... 0.95 0.9 ... 1.3

Minimum contact load V; mA 10; 100

Phase asymmetry Setting accuracy % -- Approx. 5 ... 10 -- Approx. 5 ... 10

Repeat accuracy % -- 1 -- 1

Phase failure detection At L1 or L2 or L3 ms 100 --

N-conductor monitoring -- Yes --

Rated insulation voltage Ui Between coil/contact kV 4

Contacts μ contact (AC-11) A 4

Electrical isolation Creepage distances and clearancesActuator/contact mm 3 5.5

Rated impulse withstand voltage Uimp Actuator/contact kV > 2.5 > 4

Terminals ± Screw (Pozidriv) 1

Conductor cross-sections• Rigid, max. mm2 2 × 2.5• Flexible, with end sleeve, min. mm2 0.5

Permissible ambient temperature °C -20 ... +60

Climatic withstand capability Acc. to EN 60068-1 20/60/4

5TT3196

Standards IEC 60255; DIN VDE 0435

Rated operational voltage Uc V DC 24

Rated power loss Pv• Coil/drive VA 0.6• Contacts1) per pole VA 0.8

Hysteresis % 4

Response values × Uc • Undervoltage Undervoltage 0.82• Overvoltage Overvoltage 1.18

Residual ripple tripping ΔUc Infinitely variable % 0 ... 15

Overload capability 33 V DC Continuous35 V DC ms 50045 V DC ms 10

Creepage distances and clearances mm 4

Rated impulse withstand voltage Uimp Input/output kV > 2.5

Minimum contact load V/mA 24/300

Rated operational current Ie AC-11 A 1AC-1 A 4

Contacts μ contact

Electrical service life In switching cycles at Ie 5 × 105

Terminals ± Screw (Pozidriv) 1

Conductor cross-sections• Rigid, max. mm2 2 × 2.5• Flexible, with end sleeve, min. mm2 1 × 0.5

Permissible ambient temperature °C -20 ... +60

Climatic withstand capability Acc. to EN 60068-1 20/60/4

© Siemens AG 2016

Page 14: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

12 Siemens · 10/2015

5TT3 voltage relays

Monitoring DevicesMonitoring Devices for Electrical Values

5TT3407 5TT3408 5TT3410

Standards IEC 60255; DIN VDE 0435-303

Rated operational voltage Uc V AC 230/400

Operating range (overload capability) × Uc 1.1 1.35 1.2

Rated frequency Hz 50/60

Back-up fuse Terminals L1/L2/L3 A 2

Response values Overvoltage:OFF-switching × Uc -- 0.9 ... 1.3 --ON-switching -- 4 % hysteresis --

Undervoltage:OFF-switching × Uc 0.8 0.7 ... 1.1 --ON-switching 0.85 4 % hysteresis --

Minimum contact load V; mA 10; 100

Phase asymmetry Setting accuracy % Approx. 5 ... 10

Repeat accuracy % 1

Phase failure detection At L1, L2 or L3 ms ≥ 20 100 --

OFF delay s -- 0.1 ... 20 0.1 ... 20

Automatic reclosing delay s 0.2 ... 2 -- --

Rated insulation voltage Ui Between coil/contact kV 4

Contacts μ contact (AC-11) A 3 1 4

Electrical isolation Creepage distances and clearances Contact/contact mm -- 4 --Actuator/contact mm 4 5.5

Rated impulse withstand voltage Uimp Actuator/contact kV > 4

Rated operational power Ps AC operation:230 V and p.f. = 1 VA 2000 -- --230 V and p.f. = 0.4 VA 1250 -- --

DC operation:Ue = 24 V and Ie = 6 A W max. 100 -- --Ue = 60 V and Ie = 1 A W max. 100 -- --Ue = 110 V and Ie = 0.6 A W max. 100 -- --Ue = 220 V and Ie = 0.5 A W max. 100 -- --

Terminals ± Screw (Pozidriv) 1

Conductor cross-sections• Rigid, max. mm2 2 × 2.5• Flexible, with end sleeve, min. mm2 0.5

Permissible ambient temperature °C -20 ... +60

Humidity class Acc. to IEC 60068-2-30 F

5TT3411 5TT3412 5TT3414 5TT3415

Rated operational voltage Uc V AC 230 230/400

Overload capability × Uc 1.15 1.1 1.15

Rated frequency Hz 50/60

Response values ON-switching 2 % hysteresis 4 % hysteresis 5 %

OFF-switching × Uc 0.9 0.9 0.85

Minimum contact load V/mA 10/100

Phase failure detection At L1, L2 or L3 ms -- 100 500

N-conductor monitoring -- Yes --

Rated insulation voltage Ui Between coil/contact kV 4 --

Contacts AC-15 NO contacts 3 2 --

AC-15 NC contacts 2 1 --

AC-15 CO contacts -- 1 1 2

Electrical service life in switching cycles AC-15, 1 A, 230 V AC 5 × 105 1 × 105

Rated impulse withstand voltage Acc. to IEC 60664-1 kV 4 6

Pollution degree 2 2

Terminals ± Screw (Pozidriv) 2 --– Screw (slot) -- 3.5

Conductor cross-sections

• Rigid mm2 2 × 2.5 1 x 4• Flexible, with end sleeve mm2 2 × 1.5 1 x 2.5

Permissible ambient temperature °C -20 … +60 -25 … +60

Climatic withstand capability Acc. to EN 60068-1 20/060/04

© Siemens AG 2016

Page 15: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

13Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

5TT3 voltage relays

■ Characteristic curves

Timing interval of 5TT3400... 5TT3406undervoltage relays

Timing interval of 5TT3410 N-conductor monitors

11-14

Uab

L1L2L3

Uc

11-12

Uab= Release value

I201

_070

33b

PEN conductorinterruption

N

C

11-1411-12

I201_07516bL1, L2, L3

Timing interval of 5TT3407 short-time relays

Timing interval of 5TT3408 under/overvoltage relays

tv: Adjustable automatic reclosing delay 0.2 to 20 s t: Adjustable OFF delay 0.1 to 20 s

The undervoltage relay switches at a phase asymmetry of approx. 6 to 8 %, regardless of the response values for undervoltage. The above diagram shows the timing interval for undervoltage or asymmetry.

The undervoltage relay switches at a phase asymmetry of approx. 6 to 8 %, regardless of the response values for undervoltage. The above diagram shows the timing interval for undervoltage.

0

11-1411-12

T0

vtvt

vtvt

cU

11-1411-12

I201_07271c

"RESET""RESET"

Response time

With faultstorage

Without faultstorage

Good signalGood signal

Good signalGood signal

Response time

I201_07270b

11-1411-12

On

t

UH

U

Off

OnOff

OnOff

>U

<U

<U

>U

tt

L1, L2, L3

LED

LED

LED

green

red

red

Hysteresis

Hysteresis

© Siemens AG 2016

Page 16: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

14 Siemens · 10/2015

5TT3 voltage relays

Monitoring DevicesMonitoring Devices for Electrical Values

5TT3415 undervoltage relays 5TT3411 and 5TT3412 voltage relays

For characteristic curves of the 5TT3411 and 5TT3412 voltage relays, see "Monitors for medical premises" from page 34.

■ Dimensional drawings

5TT34, 5TT3194 and 5TT3195 voltage relays

5TT34 undervoltage relays

5TT3196 DC voltage monitors

5TT3410 N-conductor monitors

5TT3411 and 5TT3412 voltage relaysFor dimensional drawings of the 5TT3411 and 5TT3412 voltage relays, see "Monitors for medical premises" from page 34.

Hysteresis

t>0.5s

LED green

LED yellow

t=1min

U

5TT3415TEST

UsL1, L2, L3

11-1421-2411-1221-22 I202_01419

5TT3400 5TT3401

5TT3402 5TT3403

5TT3404 5TT3405 5TT3407 5TT3408

5TT3194 5TT3195 5TT3406

I201

_115

15

9045

64435

N L3L2L1

2212

21241114

12

1114

L1

L2L1

36363618

2212

21241114

NL3L2L1

2212

21241114

NL3L2L1

4355

45 90I2

01_0

6552

518

e+ f

231112

24

L1 L2 L3 N

14 11 24 21

12 22

36 5 4364

45 90

I201

_115

16

© Siemens AG 2016

Page 17: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

15Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

5TT3 voltage relays

■ Circuit diagrams

Graphical symbols

5TT34 undervoltage relays

5TT3414 5TT3415

5TT3411 and 5TT3412 voltage relays

For circuit diagrams of the 5TT3411 and 5TT3412 voltage relays, see "Monitors for medical premises" from page 34.

Typical circuit for 5TT3195, 5TT340 voltage relays1, 2, 3-phase operation against N

Typical circuit for 5TT3196 DC voltage monitors

5TT3194 5TT3195

5TT3402 5TT3403 5TT3404 5TT3405

5TT3406 5TT3407 5TT3408 5TT3410

5TT3196 5TT3400 5TT3401

5TT3414 5TT3415

N

L1 L2 L3 24 22

21

14 12

11 23

1224

11

e(+)

f N

L1 L2 L3 14 12

11N

11

L1 L2 L3 12 14

I202

_014

20

N11 21

L1 L2 L3 12 14 22 24

I202

_014

21

11 12 14

21 22 24

111214

L1

L3L2 N

212224

11 12 14

111214

L1

L3L2 N

N

L1 L2

L3N

L1 L2

L3

I202

_014

15

14 12 24 22

11 21I201

_075

94c L1 L2 L3 N

L1 N

One-phase operation

14 12 24 22

11 21I201

_075

95c L1 L2 L3 N

L1 L2

Two-phase operation

14 12 24 22

11 21I201

_075

96c L1 L2 L3 N

L1 L3 L4L2

Three-phase operation

If 0.82 × Uc is fallen short of, or 1.18 × Uc exceeded, or if the residual ripple is too high, the 11/12 contact closes and the 23/24 contact opens.

5TT3 196

L1

L2

L3

e+

f

I201_07274a

11

12

23

24Load

24 V DC

23-2411-12

c

c

1,18 x U

0,82 x U

I201

_070

35a

© Siemens AG 2016

Page 18: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

16 Siemens · 10/2015

5TT3 voltage relays

Monitoring DevicesMonitoring Devices for Electrical Values

Typical circuit for 5TT3401, 5TT3403, 5TT3405undervoltage relays

Typical circuit for 5TT3404, 5TT3405, 5TT3406, 5TT3408under/overvoltage relays

One application of undervoltage relays is the switching to a safe power supply after a fault. Buildings are distinguished according to use, such as business premises, exhibition areas or guest houses. These are all covered generically as rooms/buildings "where people meet".

There is a fault if the voltage of the general power supply drops for 0.5 seconds > 15 % in relation to the rated voltage (i.e. 195 V at 230 V).

In this case the lighting must be switched to a safety power supply after 0.5 to 15 s depending on the type of use. A safety power supply may be: a battery system, a generating set or a quick-starting standby generating set.

These voltage relays can only be used for 3-phase operation. They monitor not only under- and overvoltages in accordance with their description, but also reverse voltage, asymmetry and N-conductor breaks.

14 12 24 22

11 21

L1' L2' L3' N'

I201

_072

72d

L1 L2 L3 L4

K2

L1 L2 L3 N

K1

K1 K2

Emergencypower supply

Standardpower supply

Emergencylighting

Standardlighting

3 AC 230 V

L1 L2 L3 N

L1 L2 L3 N

K1

14 12 24 22

11 21

M

PE

Phase failureI201_07273d

© Siemens AG 2016

Page 19: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

17Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

5TT3 voltage relays

Typical circuit for 5TT3407 short-time relays

Typical circuit for 5TT3407 short-time relays

In the case of sensitive technical sequences, it is often not possible to tell whether this interrupt has interfered with the process sequence. The circuit disconnects the power supply, which can then be switched back by using the RESET pushbutton.

In simple cases, it may be sufficient for a short-time interruption to be registered without the need to disconnect the power supply. In the case of a short-time interruption, this is counted by the pulse counter. The pulse counter can be reset if required.

14 12 24 22

11 21

I201_07597d

L1 L2 L3 N

L1 L2 L3 N

K1 K1

Reset

3 AC 230 V

14 12 24 22

11 21

L1 L2 L3 N

L1 L2 L3 N

1 2 3 4

5TT3407 7KT5883

I201

_075

98d

Reset

230 V 3 AC

Typical circuit for 5TT3410 N-conductor monitors

L1

5TT3410

L2 L3

N

K1

L1L2L3NPE

F1F2F3

S1 F4 F5 F6

11

14

K1 I201_07517b

Test and serviceswitch

© Siemens AG 2016

Page 20: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

18 Siemens · 10/2015

5TT3 voltage relays

Monitoring DevicesMonitoring Devices for Electrical Values

■ More information

General voltage monitoring

For general device and plant protection, voltage relays with switching thresholds of 0.7 × Uc, i.e. 161 V are used. If they have fixed, non-changeable switching thresholds, they switch back to normal operation at 0.85 × Uc, 195 V or at 0.9 × Uc, 207 V, depending on the version. If they have adjustable thresholds, they switch back to normal operation with 4 % hysteresis, 9 V.

1, 2 or 3 phases to N or 3 phases to N

All voltage relays require an N-conductor. Devices for 1, 2 or 3 phases to N can be used for 1-, 2-, or 3-phase operation. Devices for 3 phases to N require all three phases, whereby the sequence in which they are connected is irrelevant.

Asymmetry detection

If different voltages occur in a three-phase network, this is called phase asymmetry. Some voltage relays detect an asymmetry of approx. 6 to 8 % of the phase-to-neutral voltage, i.e. approx. 14 to 16 V and switch off. This type of operation is used for example to protect motors against a "skew".

N-conductor monitoring

An N-conductor break causes a skew, depending on the phase load. In extreme cases, this could cause 400 V to be applied to a phase and destroy the connected devices. Each voltage relay with asymmetry detection is tripped by an N-conductor break, if the phase displacement is at least 14 to 18 V.

The 5TT3410 N-conductor monitor detects a phase displace-ment of 5 %, which is roughly 12 V. This provides earlier protec-tion against overvoltage for connected devices. The N-conduc-tor monitor does not react if the voltage drops or rises in all phases simultaneously; or if a phase is swapped with the N-conductor.

Reverse voltage detection

If a phase fails, the motors feed a reverse voltage to the missing phase. However, voltage relays with reverse voltage detection will disconnect in this case because they are monitoring the phase angle.

Phase failure detection

If a phase fails completely, the voltage relays disconnect with a delay as specified in the technical specifications.

Short-time failure detection

Short-time failures upwards of 20 ms cannot be detected with conventional voltage relays. However, they can occur in the case of system transfers or lightning strikes and can lead to uncertainty for sensitive process sequences or measuring procedures. The 5TT3407 short-time voltage relay has a reset function that allows a procedure to be permanently interrupted after a fault.

Back-up fuse

The voltage relays do not require a back-up fuse as device protection. However, they are often installed in junctions, i.e. in main supply systems with high fusing. In this case, the supply lead to the voltage relay must be short-circuit resistant. The back-up fuse only serves as line protection.

5TT3411 and 5TT3412 voltage relays

For control elements of the 5TT3411 and 5TT3412 voltage relays, see "Insulation monitors for medical premises" from page 34.

5TT3 194

5TT3 195

5TT3 196

5TT3 400

5TT3 401

5TT3 402

5TT3 403

5TT3 404

5TT3 405

5TT3 406

5TT3 407

5TT3 408

5TT3 410

5TT3 411

5TT3 412

Overvoltage ✓ ✓ ✓ -- -- -- -- -- -- -- -- ✓ -- ✓ ✓

Undervoltage -- -- ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- -- --

Monitoring of safety light devices -- -- -- -- ✓ -- -- -- ✓ -- -- -- -- -- --

Monitoring of medical premises -- -- -- -- -- -- -- -- -- -- -- -- -- ✓ ✓

Monitoring of N-conductor -- -- -- -- -- -- -- -- -- -- -- -- ✓ -- ✓

Monitoring of short-time interruptions -- -- -- -- -- -- -- -- -- -- ✓ -- -- -- --

1, 2, 3-phase to N ✓ -- -- ✓ ✓ ✓ ✓ -- -- -- ✓ -- -- ✓ ✓

3 phases to N -- ✓ -- -- -- -- -- ✓ ✓ ✓ -- ✓ -- -- --

Asymmetry detection -- ✓ -- -- -- -- -- ✓ ✓ ✓ -- ✓ ✓ -- ✓

N-conductor monitoring -- -- -- -- -- -- -- ✓ ✓ ✓ ✓ ✓ ✓ -- ✓

Reverse voltage detection -- ✓ -- -- -- -- -- ✓ ✓ ✓ -- ✓ -- -- ✓

Short-time failure detection -- -- -- -- -- -- -- -- -- -- ✓ -- -- -- --

Phase failure detection -- -- -- ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- -- ✓

Switching thresholds: -- -- -- -- -- -- -- -- -- -- -- -- -- -- --

0.7/0.9 × Uc, non-adjustable -- -- -- ✓ -- ✓ -- ✓ -- -- -- -- -- -- --

0.8/0.85 × Uc, non-adjustable -- -- -- -- -- -- -- -- -- -- ✓ -- -- -- --

0.85/0.95 × Uc, non-adjustable -- -- -- -- ✓ -- ✓ -- ✓ -- -- -- -- -- --

0.7 ... 0.95 × Uc, 5 % hysteresis, adjustable -- -- -- -- -- -- -- -- -- ✓ -- -- -- -- --

0.7 ... 1.1 × Uc, 4 % hysteresis, adjustable -- -- -- -- -- -- -- -- -- -- -- ✓ -- -- --

0.9 ... 1.3 × Uc, 4 % hysteresis, adjustable ✓ ✓ -- -- -- -- -- -- -- -- -- ✓ -- -- --

Adjustable time delay -- -- -- -- -- -- -- -- -- -- -- ✓ -- -- --

Contact: 1 CO -- -- -- ✓ ✓ -- -- -- -- -- -- -- -- -- --

Contact: 2 CO ✓ ✓ -- -- -- ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- --

Contact: 1 CO, 1 NO, 1 NC -- -- -- -- -- -- -- -- -- -- -- -- -- -- ✓

Contact: 1 NO, 1 NC -- -- ✓ -- -- -- -- -- -- -- -- -- -- -- --

Contact: 2 NO, 2 NC -- -- -- -- -- -- -- -- -- -- -- -- -- ✓ --

© Siemens AG 2016

Page 21: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

19Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

5TT3 voltage and frequency relays

■ Overview

The voltage and frequency relay monitors the status of the grid in the case of in-plant generation systems. Violation of an upper or lower limit results in shutdown and disconnection of the generation system from the grid. Connection or automatic re-connection of the generation system to the grid only takes place when the grid frequency and the grid voltage have remained within their respective tolerance ranges without interruption for the duration of an adjustable time delay tW. Following shutdown due to a brief interruption, re-connection takes place when the grid frequency and grid voltage have remained within the tolerance range for 5 s without interruption.

■ Benefits

• Clearance certification of the German Employer's Liability Association (Energy, Textile, Electrical and Media Products)

• Default settings in accordance with VDE-AR-N-4105• The voltage and frequency relay meets the high requirements

of VDE AR-N 4105• It can be used both for centralized and integrated grid and

plant protection• The latching rotary switches enable fast and easy setting of

the required values • An illuminated LCD display provides plant status information• The voltage and frequency relay ensures single-fault

tolerance as stipulated in the VDE-AR-N 4105 application guide

• Passive procedure for detecting islanding

■ Application

Enable via external contact

Enable using external voltage 24 V AC, 40 ... 400 HzI2

02_0

2440

Coupling switch 1

Coupling switch 2

3-phase

Safe external disconnection, e.g. via ripple control receiver

CG = clock-pulse generatorInvertersGenerator(s)Generation system

Low-voltage system

CG 2CG 1

L1L2L3N

L1 L2 L3 N 11

12

Q1

KA

KE

Q2

14 22 24 32 34

21 31X1

B1

B2

X2

Coupling switch 1

Coupling switch 2

enabled disabled

CG =clock-pulse generator

external CG

InvertersGenerator(s)Generation system

Low-voltage system

CG 2

L1L2L3N

L1 L2 L3 N 11

12

Q1

KA

KE

Q2

14 22 24 32 34

21 31X1

B1

(+) (-)

B2

X2

I202

_024

41

© Siemens AG 2016

Page 22: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

20 Siemens · 10/2015

5TT3 voltage and frequency relays

Monitoring DevicesMonitoring Devices for Electrical Values

■ Technical specifications

Voltage and frequency relays

5TT3426 5TT3427

Standards IEC/EN 60255-1; IEC/EN 61000; VDE-AR-N-4105

Supply voltage Uv V AC 3 x 85 ... 288

Supply voltage B1/B2 V AC 24 (at 40 ... 400 Hz)

Rated operational voltage Uc V AC 230/400

Rated impulse withstand voltage Acc. to IEC 60664-1• Contact 31, 32, 34 kV 6• KA, KE and measuring circuit kV 4• Pollution degree 2

Recommended fuseMeasuring inputs

gG/gL A 6

Temperature range °C -20 ... +60(in the range 0 °C ... -20 °C, there may be restrictions to the functionality of the LCD display)

Conductor cross-sections• Rigid, flexible mm2 0.5 ... 4• Flexible with end sleeve mm2 0.5 ... 2.5• Multi-conductor connection 2 conductors of same

cross-sectionmm2 0.5 ... 1.5

Output relayMode of operation Quiescent current

Contacts• NO contacts AC15 A AC/V AC 3/230• NC contacts AC15 A AC/V AC 1/230

Thermal current A AC 5

Electrical service life• NO contacts AC15, 1A, AC230 Switching

cycles300000

Rise in frequency Hz 50.2 ... 51.2

Drop in frequency Hz 47.0 ... 49.8

Rise in voltage• Phase/neutral V AC 253 ... 288• Phase/phase V AC -- 438 ... 498

Drop in voltage• Phase/neutral V AC 184• Phase/phase V AC -- 319

Mean rise in voltage over 10 minutes• Phase/neutral V AC 253 ... 267• Phase/phase V AC -- 438 ... 462

Re-connection time tw sec 0 ... 600

Disconnection response time ms < 100

Connection condition• Frequency % 5• Voltage Hz 47.5 ... 50.05

Accuracy• Frequency % (± 1 digit) ≤ ±1• Voltage % (± 1 digit) ≤ ±0.02

Dimensions W x H x D 70 x 90 x 71 mm

© Siemens AG 2016

Page 23: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

21Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

5TT3 voltage and frequency relays

■ Dimensional drawings

5TT3426 5TT3427

■ Circuit diagrams

5TT3426 and 5TT3427

I202

_024

44

71,8 637

X1 B1 B2 X2 11 12 14 21 22 24

L1 L2 L3 N KA KE 31 32 34

90

I201_18954

X1 B1 B2 X2 11 12 14 21 22 24

L1 L2 L3 N KA KE 31 32 34

K3

U>>(%) f<(Hz) f>(Hz)

>50,8

<50,9

random

tw(s)

U>=80%

5TT3 426

Mode >2sTest

f>(Hz)

K1 K2

110 112114

115

116118125 120

47,0 47,5 47,848,2

48,649,049,8 49,4

50,2 50,350,4

50,5

50,650,750,8 50,8

Off 110111

112

113114126 125

0 30 6090

180120

240600 450 300

50,8 50,9 51,051,151,2

51,351,5 51,4

U10m>(%)

B1/ K1/ K3 KA/B2 K2 KE

I201_18955

X1 B1 B2 X2 11 12 14 21 22 24

L1 L2 L3 N KA KE 31 32 34

K3

U>>(%) f<(Hz) f>(Hz)

>50,8

<50,9

random

tw(s)

U>=80%

5TT3 427

Mode >2sTest

f>(Hz)

K1 K2

110 112114

115

116118125 120

47,0 47,5 47,848,2

48,649,049,8 49,4

50,2 50,350,4

50,5

50,650,750,8 50,8

Off 110111

112

113114126 125

0 30 6090

180120

240600 450 300

50,8 50,9 51,051,151,2

51,351,5 51,4

U10m>(%)

B1/ K1/ K3 KA/B2 K2 KE

Channel 1

Error

Channel 2

L1 L2 L3 N

X1 B1 B2 X2 11 12 14 21 22 24

KAKE 31 32 34

U < >

f < >

Ū10m>

12

11

14

K1

32

31

34

K3

tw

U < >

f < > 22

21

24

K2tw

I202

_024

39

Ū10m>

© Siemens AG 2016

Page 24: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

22 Siemens · 10/2015

5TT6 current relays

Monitoring DevicesMonitoring Devices for Electrical Values

■ Overview

Current relays monitor single and three-phase systems for the flow of current, e.g. in emergency lighting installations, and the

loading of motors. They are available as undercurrent, overcurrent and under/overcurrent relays.

■ Technical specifications

5TT6111 5TT6112Standards IEC 60255; DIN VDE 0435-303Rated operational current Ic A 1 ... 10Rated operational voltage Uc V AC 230Primary operating range × Uc 0.9 ... 1.1Overload capability, continuous A 15Overload capability, short-time At 50 °C ambient

temperature max. 3 sA 20

Rated frequency Hz 50/60Response values ON-switching Infinitely variable

OFF-switching Permanent, 4 % hysteresis

Switching delay tv Infinitely variable s 0.1 ... 20Response time Non-adjustable ms Current corresponds to the rated operational power of the

continuous-flow heater

Minimum contact load V; mA 10; 100Rated insulation voltage Ui Between coil/contact kV 2.5Contactsμ contact (AC-15) NO contacts A 3

NC contacts A 1

Electrical isolation Creepage distances and mm 3Actuator/contact

Rated impulse withstand voltage Uimp Actuator/contact kV > 4Terminals ± Screw (Pozidriv) 1Conductor cross-sections Rigid max. mm2 2 × 2.5

Flexible, with end sleeve min. mm2 1 × 0.5

Permissible ambient temperature °C -20 ... +60Climatic withstand capability Acc. to EN 60068-1 20/60/4

5TT6113 5TT6114 5TT6115 5TT6120

Standards IEC 60255; DIN VDE 0435-303

Rated operational current Ic 4 ranges 1 rangeA 0.1 ... 1 0.5 ... 5A 0.5 ... 5A 1 ... 10A 1.5 ... 15

Rated operational voltage Uc V AC 230

Primary operating range × Uc 0.9 ... 1.1Overload capability, continuous A 20 15Overload capability independent of measuring range

Max. 3 s A 30

Rated frequency Hz 50/60

Response values ON-switching Infinitely variableOFF-switching Permanent, 4 % hysteresis

Switching delay tv Infinitely variable s 0.1 ... 20

Response time Non-adjustable ms See: www.siemens.com/lowvoltage/manuals

Minimum contact load V; mA 10; 100

Rated insulation voltage Ui Between coil/contact kV 2.5

Contactsμ contact (AC-15) NO contacts A 5

NC contacts A 1

Electrical isolation Creepage distances and mm 3Actuator/contact

Rated impulse withstand voltage Uimp Actuator/contact kV > 4

Terminals ± Screw (Pozidriv) 1

Conductor cross-sections Rigid max. mm2 2 × 2.5Flexible, with end sleeve min. mm2 1 × 0.5

Permissible ambient temperature °C -20 ... +60

Climatic withstand capability Acc. to EN 60068-1 20/60/4

© Siemens AG 2016

Page 25: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

23Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

5TT6 current relays

■ Dimensional drawings

5TT611 current relays 5TT6120 current relays

■ Circuit diagrams

Graphical symbols

5TT6111 5TT6112

5TT6113 5TT6114

5TT6115 5TT6120

I201

_115

18

9045

64435

Z1 Z4

24

22

21

i k

Z2 Z3

14

12

11

1A A2

36

L/k

L/iL/i

Z1 Z4

24

22

21

i k

Z2 Z3

14

12

11

N

11

12 14

1A A2

18 36

44

42

41

i3 k3

34

32

31

1A A2

72

24

22

21

i1 k1

14

12

11

1A A2

I201

_115

17

9045

55435

5TT6111 5TT6112

5TT6113 5TT6114 5TT6115 5TT6120

>LL

11

1214

N

i k>

A1 A2

2111

22241214

Z4Z3Z2Z1

i k<

A1 A2

2111

22241214

Z4Z3Z2Z1

i k><

A1 A2

2111

22241214

Z4Z3Z2Z1

i k

<

>

2111

22241214

k1-k3i1-i3

A1 A2

4131

42443234

Typical circuit for 5TT6111 undercurrent monitors

Typical circuit for 5TT6114 overcurrent monitors Measurement with transformer

L/i N

L1N

12 14

11L/kTo the 5TT3460 or 5TT3461 faultsignaling relay

230 V AC I201_07522c

i

5TT6114

A1 A2

k

K1

PE M

L1L2L3NPE

K1

12 14 22 24

11 21

3 AC 230/400 V I201_07560b

© Siemens AG 2016

Page 26: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

24 Siemens · 10/2015

5TT6 current relays

Monitoring DevicesMonitoring Devices for Electrical Values

■ More information

Direct measurement, transformer measurement

All current relays can be connected with direct measurement or through transformers.

N potential

Versions 5TT6113 to 5TT6120 can be connected with a separate N potential.

Response time

Current relays are not circuit-protective devices for lines. They switch with a delay in the ms range.

Overload capability

Independent of the set measuring range and set measured value, current relays can be permanently overloaded up to 15 A and 20 A; for 3 s; even up to 20 A and 30 A.

Buildings/object-safe guiding lights

In the approach corridors of planes, high buildings must be fitted with position lighting. The same planning instructions apply to the monitoring of this type of lighting and runway lighting as the monitoring of emergency lighting.

Monitoring of emergency lighting with incandescent lamps

The function of emergency lighting according to DIN VDE 0108 must be checked at regular intervals. The operational current is continuously monitored using current relays. The lighting can either be integrated in the general lighting system or just supplied on demand with emergency current.

The current relay is set so that it switches on at the max. lamp current. If an incandescent lamp fails, a fault is signaled.

Monitoring of motors

If the warning is sent early enough, the fault can be eliminated before the motor starts to overheat and the circuit breaker switches the motor off.

Current relays reliably safeguard the monitoring of fault-free running motors and, in some cases are more suitable than a voltage relay, which is geared more towards motor protection.

Typical circuit for 5TT6114 With direct measurement up to 15 A for overcurrent measurement

Typical circuit for 5TT6120 With direct measurement of up to 5 A for undercurrent/overcurrent measurement

i

5TT6114

A1 A2

k

K1

PE M

L1L2L3NPE

K1

12 14 22 24

11 21

3 AC 230/400 V I201_07559b

5TT6120

A1 A2

K1

PEM

L1L2L3NPE

K1

12 14 22 24

11 21

i

k

1 i2 i3

k2 k31

32 34 42 44

31 41

min max

3 AC 230/400 V I201_07561b

Device overview 5TT6111 5TT6112 5TT6113 5TT6114 5TT6115 5TT6120

Undercurrent ✓ -- ✓ -- ✓ ✓

Overcurrent -- ✓ -- ✓ ✓ ✓

Single-phase ✓ ✓ ✓ ✓ ✓ --

Three-phase -- -- -- -- -- ✓

Separate N potential -- -- ✓ ✓ ✓ ✓

Measuring ranges: Jumper:0.1 - 1 A Z1 – Z2 -- -- ✓ ✓ ✓ --0.5 - 5 A Z1 – Z3 -- -- ✓ ✓ ✓ ✓1 ... 10 A Z1 – Z4 ✓ ✓ ✓ ✓ ✓ --1.5 - 15 A Z1 – Z3 – Z4 -- -- ✓ ✓ ✓ --Can be programmed over jumpers -- -- ✓ ✓ ✓ --

Contacts 1 CO ✓ ✓ -- -- -- --2 CO -- -- ✓ ✓ ✓ ✓

© Siemens AG 2016

Page 27: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

25Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

5TT6 current relays

Example: Screw conveyor

Hard objects in screw conveyors, e.g. in sewage treatment plants, can often jam the conveyor system. Appropriately set, the current relay signals over its contact(s) that a hazardous situation has occurred and threatens to block the motor.

Example: Agitators

As with the conveyor processes, changes to the viscosity can lead to an overload of the motors.

Example: Crane motor control system

The current monitoring of the main motor (hoisting motor) ensures that the electrical holding brake is not released until the main motor is in operation and the load is held.

Example: Dust extraction

In the interests of work safety and to protect against massive dust development, it is essential to ensure that the dust extraction system is working perfectly before a saw or sanding machine is switched on.

Planning the monitoring of an incandescent lamp

Current relays have a hysteresis of approx. 4 %. The smallest lamp must not exceed the set measuring range by more than 8 %.

Example: 12 lamps of 100 W each = 1200 W, which corresponds to a current of approx. 5.2 A. If a lamp fails, the current drops by 0.4 A. This 0.4 A corresponds to 8 % of the set measured value 5.2 A.

Response time

The response time of the fault signal is produced by the “adjustable switching delay" (see the technical specifications) and an additional delay, which is determined from the actual current and the set value.

Function charts for 5TT61 overcurrent relay signal

5TT61 overcurrent relay signal

F Pickup Dropoutms ms

1 10 250

2 70 70

5 120 30

10 180 15

20 220 10

30 240 12

F =Iact

Imeas

Iact: Instantaneously flowing current

Imeas: Set current threshold value to be measured

Pickup: With an overcurrent relay, the contact 11 – 14 (21 – 24) to the fault signal closes when the instantaneous current flowing is higher than the switching threshold. The relay picks up.

Dropout: With an overcurrent relay, the contact 11 – 12 (21 – 22) to the fault signal closes when the instantaneous current flowing is higher than the switching threshold. The relay drops out.

I201_07508c

On

t

Off

OnOff

LED

LED

t

1 4

2

UN

N

tv tv

green

red

Fault

Hyst.

I201_07469b

On

t

U

Off

OnOff

LED

LED

t

1 4

2

t

N

N

v

green

red

Fault

Hyst.

© Siemens AG 2016

Page 28: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

26 Siemens · 10/2015

5TT6 current relays

Monitoring DevicesMonitoring Devices for Electrical Values

Function charts for 5TT6115 under/overcurrent relay signal

Contrary to all other current relays, a fault signal is always output over the contact 11 – 14 (21 – 24). The red LEDs indicate whether the signal is for an undercurrent or an overcurrent.

I201_07472b

On

t

U

Off

OnOff

LED

LED

t

t

14

2

OnOff

LED

N

N

tvv tv

green

red

red

Fault Fault

Hyst.

Hyst.

© Siemens AG 2016

Page 29: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

27Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

5TT3 reverse power relays

■ Overview

The 5TT3424 and 5TT3425 reverse power relays monitor the direction of the energy transport in an electric grid. This may be necessary where public grids and industrial grids intersect, e.g. when using emergency generators, motor-driven generators, etc.

■ Technical specifications

Reverse power relays

5TT3424 5TT3425

Standards IEC 60255; DIN VDE 0435-303

Rated voltage Un V AC 230, 3-phase systems without N 400, 1- or 3-phase systems without N

Rated current In A 5

Response value Reverse power % 2 ... 20

Hysteresis % 12.5 of the set response value

Rated frequency Hz 45 ... 65

Response delay tan s 0.2 ... 10, adjustable

Contact arrangement 2 CO

OutputContact arrangement 2 CO

Breaking capacity IEC 60947-5-1

• NO contacts AC15 A AC/V AC 3/230• NC contacts AC15 A AC/V AC 1/230• Acc. to DC 13 A DC/V DC 1/24

Thermal current A 2 x 5

Electrical service life IEC 60947-5-1

• NO contacts AC 15, 3A, 230 AC Switching cycles

2 x 105

Permissible switching frequency Switching cycles/h

1800

Short-circuit strength, max. melting fuse

IEC 60947-5-1 4 A gL

Mechanical service life Switching cycles

30 x 106

General dataPermissible ambient/storage temperature °C -20 ... +60

Clearance and creepage distances

• Rated impulse withstand voltage kV 4

• Pollution degree IEC 60664-1 II

Degree of protection

• Enclosure IP40

• Terminals IP20

Wire connections

• Fixed screw terminal (S) 0.2 ... 4 mm2 solid or 0.2 ... 1.5 mm2 stranded wire with sleeve

Dimensions W x H x D 70 x 90 x 71 mm

© Siemens AG 2016

Page 30: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

28 Siemens · 10/2015

5TT3 fuse monitors

Monitoring DevicesMonitoring Devices for Electrical Values

■ Overview

Fuse monitors serve to monitor all types and versions of melting fuses that cannot be equipped with a fault signal contact. This

enables integration in fault signaling circuits or a central alarm in order to improve plant availability.

■ Technical specifications

■ Dimensional drawings ■ Circuit diagrams

Graphical symbols

■ More information

Typical circuit, function chart

If the fuse fails, the motor is immediately disconnected (prevention of two-phase run). After changing the fuse, the motor can be restarted by pressing the "ON" button.Unlike conventional motor circuit breakers, it is not possible to switch the motor on if the fuse is faulty.

Note:The internal resistance of the measuring paths of the fuse monitor is in the MΩ range so that the VDE regulations with regard to touch voltage are met in the event of faulty fuses (> 1000 Ω/V). To isolate the main switch, it must be switched off. The enclosed label should be affixed to the switchgear as a reminder.

5TT3170

Standards IEC 60255; DIN VDE 0435-110

Rated operational voltage Uc V 3 AC 380 ... 415

Primary operating range × Uc 0.8 ... 1.1

Rated frequency Hz 50 ... 400

Internal resistance of measuring paths Ω/V > 1000

Max. permissible feedback % 90

Response/release time ms < 50

Rated impulse withstand voltage UimpInput/output

kV > 4

Rated operational voltage Ue V AC 250

Rated operational current Ie AC-1 A 4

Electrical service life AC-11 In switching cycles at 1 A 1.5 × 105

Terminals ± Screw (Pozidriv) 1

Conductor cross-sections Rigid, max. mm2 2 × 2.5Flexible, with end sleeve, min. mm2 1 × 0.5

Permissible ambient temperature °C -20 ... +45

Climatic withstand capability Acc. to EN 60068-1 20/45/4

I201

_115

12

9045

64435

15

L3L2L1

14

L3L2L1

36

L3L2 14L1

13L3'L2'L1'

M

N

L2

L1 L2 L3

13

I201_07251b

3 ~

L1 L3

L2' 14L1' L3'

L

F1 F2 F3

3 AC 400 V

Off

On

��������

����� ������

© Siemens AG 2016

Page 31: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

29Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

5TT3 phase and phase sequence monitors

■ Overview

Phase monitors monitor the voltages in three-phase system and signal the power failure of one or more phases over a floating contact. Phase sequence monitors monitor the phase sequence

in three-phase systems and signal any changes in the phase sequence – change of rotating field – over a floating changeover contact.

■ Technical specifications

■ Dimensional drawings

■ Circuit diagrams

Graphical symbols

5TT3421 5TT3423

Standards IEC 60255; DIN VDE 0435

Rated operational voltage Uc V AC 230/400 400

Primary operating range × Uc 0.8 ... 1.1

Rated frequency Hz 50/60

Rated power loss Pv Electronics VA 9Contacts VA 0.2

Rated operational voltage Ue V AC 250

Rated operational current Ie A 4

Minimum contact load V; mA 10; 100

Rated insulation voltage Ui Between coil/contact kV 4

Contacts μ contact (AC-11) A 3

Electrical isolation Creepage distances and clearancesActuator/contact mm 4

Rated impulse withstand voltage Uimp Actuator/contact kV > 2.5

Terminals ± Screw (Pozidriv) 1

Conductor cross-sections Rigid, max. mm2 2 × 2.5Flexible, with end sleeve, min. mm2 --

Degree of protection Acc. to EN 60529 IP20, with connected conductors

Safety class Acc. to EN 61140/VDE 0140-1 II

Permissible ambient temperature °C -20 ... +60

Climatic withstand capability Acc. to EN 60068-1 20/60/4

5TT3421 5TT3423

11

21

41

3L

1L

2L

21

41 11

3L

1L N

2L

18

I201

_107

80

18

9045

64435

5TT3421 5TT3423

N

L1 L2 L3

11

1214 L1 L2 L3

11

1214

© Siemens AG 2016

Page 32: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

30 Siemens · 10/2015

5TT3 phase and phase sequence monitors

Monitoring DevicesMonitoring Devices for Electrical Values

■ More information

Typical circuit diagrams

5TT3421 phase monitors

The phase monitor can be operated either in 1, 2 or 3-phase operation.

5TT3423 phase sequence monitors

Phase sequence monitors must always be connected in three-phase.

Single-phase operation

I201

_107

76a 14 12

11

L1 L2 L3 N

NL1

Two-phase operation

14 12

11I201

_107

77a L1 L2 L3 N

L1 L2 N

Three-phase operation

1412

11

I201

_107

78 L1 L2 L3 N

L1 L3L2 N

I2_10779a

L1 L2 L3

K1

14 12

11

M

L1 L2 L3PE

© Siemens AG 2016

Page 33: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

31Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

5TT3 insulation monitors for industrial applications

■ Overview

Insulation monitors are used for protection of persons and against fire in non-grounded systems (IT systems). The insulation resistance of the system being monitored is measured against ground.

Such measurements are prescribed in accordance with DIN VDE 0100-410 – Power installations up to 1,000 V – Protection against electric shock.

■ Technical specifications

■ Dimensional drawings

5TT3470 5TT3471

Supply voltage Uc V AC 220 ... 240 --V DC -- --

Primary operating range With AC supply × Uc 0.8 ... 1.1 --For DC supply V DC -- --

Frequency range for Uc Hz 45 ... 400 --

Rated power loss Pv VA Approx. 2 --For DC supply W -- Approx. 1

Rated impulse withstand voltage Uimp Terminals A1 to A2 kV < 4 < 4Terminals L to PU kV < 4 < 4Terminals A1, A2 to L, PU kV < 4 < 3Terminals against contacts kV < 6 < 6

Measuring circuit For three-phase and AC systems For direct voltage systems

Measurement voltage range Umeas V AC 0 ... 500 --V DC -- 12 ... 280

Primary operating range × Umeas 0 ... 1.1 0.9 ... 1.1

Frequency range for Umeas Hz 10 ... 10000 --

Alarm values Measuring shunt RAL kΩ 5 ... 100 5 ... 200

Setting of alarm value On absolute scale Infinitely variable Infinitely variable

Alternating current internal resistance Internal test resistance kΩ > 250 --

Direct current internal resistance Internal test resistance kΩ > 250 --L+ and L- to PU kΩ -- 75 each

Measurement voltage Umeas Internal V DC Approx. 15 --

Max. measurement current Imeas Short circuit mA < 0.1 0.2 ... 4 depending on the voltage

Direct interference voltage Max. permissible V DC 500 --

Response delay At RAL 50 kΩ and 1 μFand ∞ to 0.9 × Rmeas s < 1.3 0.8and Rmeas from ∞ to 0 Ω s < 0.7 0.4

Switching hysteresis At Rmeas 50 kΩ % 15 10 ... 15

Contacts μ contact 2 CO 2 CO

Rated operational voltage Ue V 230 AC DC 12 ... 280

Rated operational current Is Thermal current Ith A 4 4DC-13 at 24 V DC A -- 2DC-13 at 250 V DC A -- 0.2AC-15 A -- 3AC-15 NO contacts A 5 --AC-15 NC contacts A 2 --

Terminals ± Screw (Pozidriv) 2 2

Conductor cross-sections Rigid, max. mm2 2 × 2.5Flexible, with end sleeve, min. mm2 1 × 0.50

Permissible ambient temperature °C -20 ... +60

Degree of protection Terminals (acc. to EN 60529) IP20Enclosure (acc. to EN 60529) IP40

Resistance to climate Acc. to EN 60068-1 20/060/04

5TT3470 5TT3471

24

22

2114

12

11 I201

_115

19

9045

64435

X1 LT

L+ L-

PE PT

36

A1 A2

24

22

2114

12

11

LT1 LT2

L

PE PT

36

© Siemens AG 2016

Page 34: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

32 Siemens · 10/2015

5TT3 insulation monitors for industrial applications

Monitoring DevicesMonitoring Devices for Electrical Values

■ More information

Function chartsl

Typical circuit diagrams

5TT3470 for three-phase and AC systems 5TT3471 for direct voltage systems

5TT3470, 5TT3471

I201_11522

Uc

R

11-1411-12

11-14

11-12

Insulation resistanceSet value

Without fault storage

Red LED OnOff

With fault storageReset-button

Red LED OnOff

The power supply to terminals A1 – A2 can be taken from the system being monitored. However, in this case it is important to ensure compliance of the voltage range with the technical specifications.

With a jumper LT1 – LT2: A fault signal is not stored; the device is automatically released again if the insulation resistance improves. Without a jumper LT1 – LT2: the fault signal is stored; pressing the RESET button or an external key at the terminals LT1 – LT2 clears the fault signal.

Pressing the Test button or an external key at the terminals PT – PE simulates a fault.

The measurement voltage to the terminals L+ and L- serves at the same time as the power supply.

With a jumper LT – X1: A fault signal is not stored; the device is automatically released again if the insulation resistance improves. Without a jumper LT – X1: The fault signal is stored; pressing the RESET button or an external key at the terminals LT – X1 clears the fault signal.

Pressing the Test button or an external key at the terminals PT – X1 simulates a fault.

I201

_115

20b

N

L

242221141211LT2LT1

A2A1

PE

LPEPT

L3

L2

L1

L+

L-

PT

L- PE

PE

LT X1 11 12 14 21 22 24

L+

I201

_115

21a

© Siemens AG 2016

Page 35: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

33Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

5TT3 insulation monitors for industrial applications

Front views

5TT3470 for three-phase and AC systems

Direct interference voltage

While direct interference voltages do not damage the devices they often interfere with conditions in the measuring circuit. In a system being monitored, only one insulation monitor should be connected. This must be taken into account if gateways are used.

System capacitances to protective ground CE do not corrupt the insulation measurement because it is implemented with direct current. However, the response time may be extended in the event of an insulation fault, namely in the magnitude of the time constant RE times CE. The power supply to the insulation monitors can be taken from a separate system or from the one being monitored. However, the above mentioned power supply range must be taken into account.

LEDs:• Green LED lights up if power supply Uc is applied• Red LED lights up in the event of an insulation fault

5TT3471 for direct voltage systems

Leakage capacitance

The insulation monitor can be installed in systems with high leakage capacitance to PE. In the case of high-resistance alarm values, a transient alarm signal may occur when switching on the system being monitored due to an existing ground leakage capacitance.The values of the capacitance CE given the following set values of R are approximately:• R = 200 kΩ: CE > 0.8 μF• R = 50 kΩ: CE > 2.0 μF• R = 20 kΩ: CE > 4.5 μFIn these applications, you should work without an alarm storage. Due to the measuring function with bridge circuit, the insulation monitor does not respond in the event of a simultaneous, exactly symmetrical ground fault of L+ and L-. However, exactly symmetrical ground faults are highly unlikely in practice.LEDs:• Green LED lights up if power supply Uc is applied• Red LED 1 lights up for insulation fault L+ to PE• Red LED 2 lights up for insulation fault L- to PE

5TT3470 5TT3471

I201

_119

71

PE PT LT1 LT2

L A1 A2

T1

T2

12 22

14 11 24 21

E1

LED green:LED red:

E1:T1:T2:

Status display (ON)Insulation fault (AL)Alarm value adjuster (RAL)TestReset

LED red

LED green

I201

_119

72

PE PX X1 LT

L+

T1

T2

12 22

14 11 24 21

L–

E1

LED 1 red

LED green

LED 2 red

LED green:LED 1 red:LED 2 red:

E1:T1:T2:

Status display (ON)Insulation fault L– (RE–)Insulation fault L+ (RE+)Alarm value adjuster (RAL)TestReset

© Siemens AG 2016

Page 36: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

34 Siemens · 10/2015

7LQ3 monitors for medical premises

Monitoring DevicesMonitoring Devices for Electrical Values

■ Overview

In areas that conform to Group 2 of DIN VDE 0100-710, any interruption to the examination and/or treatment of patients would place those patients at risk.

Limit monitoring

This is prevented through the use of changeover and monitoring units. These monitor the insulation resistance of the non-grounded IT system, the load current and the temperature of the

transformer. If the limit value is exceeded, the insulation monitor gives out a warning signal.

Voltage monitoring

In addition, a special voltage relay monitors the voltage of the power supply and switches to a second power supply if it falls below the specified limit values.

■ Technical specifications

Switchover devices7LQ3361 7LQ3362

Standards IEC 60364-7-710; DIN VDE 0100-710

Supply voltage Uv V AC 230 230/400

Primary operating range × Uv 0.9 ... 1.1

Supply frequency fv Hz 50 … 60

Insulation coordination IEC 60664-1

Rated impulse withstand voltage kV 4

Pollution degree 3

Max. power loss Pv W 10.7

Power sectionContactors Mechanically latched; mechanically and electrically locked

Rated operational current acc. to DIN VDE 0100-710 A 51 32

Rated operational current AC-3 A 113 71

Short-circuit protection acc. to DIN VDE 0100-710 • Max. backup protection gG A 63

Switchover time s 0.1 ... 10

Measuring circuit insulation monitoringResponse value Ran kΩ 50

Response deviation EN 61557-8

Response time tan at Ran = 50 kΩ, Ce = 1 μF RF from ∞ to 0.5 × Ran s < 1.3RF from ∞ to 0 kΩ s < 0.7

Hysteresis % 15

Measurement voltage Um V DC Approx. 15

Measurement current Im max (at RF = 0 Ω) µA < 50

Internal resistance DC Ri kΩ > 250

Impedance Zi at 50 Hz kΩ > 250

Permissible direct interference voltage Ufg V DC < 300

Test button External/internal

Measuring circuit load current monitoringResponse value, adjustable with external transformer 50/5 A, Class 1

A 5 … 50

Hysteresis % 4

Temperature influence %/°C ≤ 0.05

Delay tv adjustable s 0.1 ... 20

Measuring circuit, temperature monitoringResponse value kΩ 3.2 ... 3.8

Release value kΩ 1.5 ... 1.8

PTC thermistor Acc. to DIN 44081/44082 Unit(s) 1 … 6 in series

Measuring circuit, voltage monitoringResponse values ON-switching 2 % hysteresis 4 % hysteresis

OFF-switching × Uc 0.9 0.9

Phase failure detection At L1, L2 or L3 ms -- 100

N-conductor monitoring -- Yes

© Siemens AG 2016

Page 37: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

35Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

7LQ3 monitors for medical premises

Switchover devices7LQ3361 7LQ3362

ConnectionTerminals

• Load circuit Feeder terminals mm² 4 ... 16Output terminals

• Communication Status signals mm² 2.5Fault indications

Environmental conditionsPermissible ambient temperature °C -20 ... 45

Mounting position Vertical

Insulation monitors7LQ3354 7LQ3355

Standards EN 61557-8

Supply voltage Uv V AC 230

Primary operating range × Uv 0.9 ... 1.1

Supply frequency fv Hz 50 … 60

Max. power loss Pv VA Approx. 7

Rated line voltage Un (measuring circuit) V AC 0 … 300

Rated frequency fn Hz 10 … 1000

EMC immunity to interference IEC 61000-6-2

EMC emitted interference IEC 61000-6-3

Insulation coordination IEC 60664-1

Rated impulse withstand voltage kV 4

Pollution degree 3

Flammability class UL 94V-0

Measuring circuit insulation monitoringResponse value Ran kΩ 50 50 ... 500

Response deviation EN 61557-8

Response time tan at Ran = 50 kΩ, Ce = 1 μF RF from ∞ to 0.5 × Ran s < 1.3RF from ∞ to 0 kΩ s < 0.7

Hysteresis % 15

Measurement voltage Um V DC Approx. 15

Measurement current Im max (at RF = 0 Ω) µA < 50

Internal resistance DC Ri kΩ > 250

Impedance Zi at 50 Hz kΩ > 250

Permissible direct interference voltage Ufg V DC < 300

Measuring circuit load current monitoringResponse value, adjustable with external transformer 50/5 A, Class 1

A 5 … 50

Hysteresis % 4

Temperature influence %/°C ≤ 0.05

Delay tv adjustable s 0.1 ... 20

Measuring circuit, temperature monitoringResponse value kΩ 3.2 ... 3.8

Release value kΩ 1.5 ... 1.8

PTC thermistor Acc. to DIN 44081/44082 Unit(s) 1 … 6 in series

Display and control elementsOperating error Acc. to IEC 61557-8

LED display

• Current and temperature monitoring One red and one green LED• Ready-to-run Green• Insulation fault Red• Line breakage monitoring of the isolation measuring circuit Red

• Display of current insulation resistance -- 11-step LED chain

Pushbuttons TEST and RESET

© Siemens AG 2016

Page 38: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

36 Siemens · 10/2015

7LQ3 monitors for medical premises

Monitoring DevicesMonitoring Devices for Electrical Values

Insulation monitors7LQ3354 7LQ3355

Output relayContacts for Overtemperature 2 CO

Overload 2 COInsulation fault 2 CO

Mode of operation Working current

Contacts AC-15 NO contacts A AC/V AC 3/230 AC-15 NC contacts A AC/V AC 1/230

Electrical service life AC-15, 1 A, 230 V AC Switching cycles

30000

Thermal current A AC 5

ConnectionTerminals ± Screw (Pozidriv) 2

• Conductor cross-sections Rigid mm2 2 × 2.5• Insulation fault Flexible, with end sleeve mm2 1 × 2.5

Environmental conditionsPermissible ambient temperature °C -20 … +60

Climatic withstand capability Acc. to EN 60068-1 20/060/04

Degree of protection Acc. to EN 60529 IP20, with connected conductors

Mounting position Any

Vibration stress Acc. to IEC 60068-2-6• Amplitude mm 0.35• Frequency Hz 10 … 55

Test and signaling panels 7LQ3356 7LQ3357

Standards DIN VDE 0100-710; IEC 60364-7-710

Rated voltage Un V AC/DC 24

Rated impulse withstand voltage Acc. to IEC 60664-1 kV 4

Voltage range AC 0.8 ... 1.1 x UnDC 0.9 ... 1.2 x Un

Rated current per input mA 0.25

Rated consumption VA 6

Rated operating mode Continuous operation

Pollution degree Acc. to IEC 60664-1 2

Degree of protection• Enclosure Acc. to IEC/EN 60529 IP40• Terminals Acc. to IEC/EN 60529 IP20

Flammability class UL 94V-0

Vibration stress Acc. to IEC/EN 60068-2-6• Amplitude mm 0.35• Frequency Hz 10 … 55

Climatic withstand capability Acc. to IEC/EN 60068-1 20/045/04

Terminal marking EN 50005

Wire connections

• Solid mm2 1 × 1.5mm2 2 × 0.5

• Strand mm2 1 × 1mm2 2 × 0.2

• Strand with sleeve mm2 1 × 0.5

Conductor mounting Box terminals with wire protection

Device dimensions mm 80 × 160 × 57 82 × 150 × 57

Temperature range °C -20 ... +45

© Siemens AG 2016

Page 39: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

37Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

7LQ3 monitors for medical premises

Current transformers Class 17LQ3358

Standards IEC/EN 60044-1, VDE 0414-44-1

Rated operational voltage Uc V AC 230

Rated frequency Hz 50/60

Test voltage 50 Hz, 1 min kV 3

Rated transformation ratio kn A 50/5

Primary rated current A 50

Secondary rated current A 5

Rated power V/A 1.5

Class 1

Rated frequency Hz 50 ... 60

Highest voltage at equipment/insulation level kV 0.72/3

Overcurrent factor FS5• Thermal rated short-time current × In 60• Thermal rated continuous current × In 1.2

Expanded current range % 120

Permissible ambient temperature °C -20 … +60

Test and signaling combination for insulation monitors7LQ3360

Standards DIN VDE 0100-710; IEC 60364-7-710

Rated voltage Un V AC 24

Voltage range AC 0.8 ... 1.1 × Un

Connected load W 0.5

Rated operating mode Continuous operation

EMC• Static discharge Acc. to IEC/EN 61000-4-2 kV 8 (air discharge)• RF irradiation Acc. to IEC/EN 61000-4-3 V/m 10• Rapid transients Acc. to IEC/EN 61000-4-4 kV 2• Surge voltage (surge) Acc. to IEC/EN 61000-4-5 kV 1

Degree of protection IP30

Amplitude mm 0.35

Frequency Hz 10 ... 55

Temperature range °C -5 ... +55

Climatic withstand capability Acc. to IEC/EN 60068-1 05/055/04

Terminal marking EN 50005

Wire connections• Solid mm2 1 × 4• Strand with sleeve and plastic collar mm2 1 × 2.5• Strand with sleeve and plastic collar DIN 46228-1/-2/-3/-4 mm2 2 × 1.5• Strand with sleeve DIN 46228-1/-2/-3 mm2 2 × 2.5

Conductor mounting Box terminals with wire protection

Device dimensions mm 80 × 80 × 35

© Siemens AG 2016

Page 40: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

38 Siemens · 10/2015

7LQ3 monitors for medical premises

Monitoring DevicesMonitoring Devices for Electrical Values

1) Tripping units must be ordered separately.

■ Accessories

SIRIUS 4AT isolating transformers

Further information about the SIRIUS 4AT isolating transformers can be found in Catalog IC 10 · 2016.

Voltage relays

5TT3411 5TT3412

Rated operational voltage Uc V AC 230 230/400

Overload capability × Uc 1.15 1.1

Rated frequency Hz 50/60

Response values ON-switchingOFF-switching × Uc

2 % hysteresis0.9

4 % hysteresis0.9

Minimum contact load V/mA 10/100

Phase failure detection At L1, L2 or L3 ms -- 100

N-conductor monitoring -- Yes

Rated insulation voltage Ui Between coil/contact kV 4

Contacts AC-15 NO contactsAC-15 NC contacts

32

31

Electrical service life in switching cycles AC-15, 1 A, 230 V AC 5 × 105

Rated impulse withstand voltage Acc. to IEC 60664-1 kV 4

Pollution degree 2

Terminals ± Screw (Pozidriv) 2

Conductor cross-sections• Rigid• Flexible, with end sleeve

mm2

mm22 × 2.52 × 1.5

Permissible ambient temperature °C -20 … +60

Climatic withstand capability Acc. to EN 60068-1 20/060/04

IT line transformers4AT3/4AT4

In the case of isolating transformers used to set up medical IT systems, overcurrent protective devices are only permissible as protection against short circuits. To protect the isolating transformers against overload they are fitted with monitoring devices that signal an excessive rise in temperature (e.g. 7LQ3354 insulation monitors).

Standards EN 61558-2-15

Safety class I

Static shield between primary and secondary winding With insulated connection

Thermistor transformer protection Warning in the event of thermal overload1)

Insulation monitoring With center tap

Short-circuit voltage uz % ≤ 3

No-load current i0 % ≤ 3• Starting current (rush), max. x I1N 8

Rated ambient temperature ta/thermal class 55 °C/H

© Siemens AG 2016

Page 41: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

39Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

7LQ3 monitors for medical premises

■ Characteristic curves

7LQ3354 and 7LQ3355 insulation monitors

The following diagrams show the function of the measuring circuits of the temperature monitors (top left), the load current monitors (bottom left) and the insulation monitors (right).

11-1421-2411-1221-22

V

P1/P2

≥ 3,2 kΩ

R

U

t

t

≤ 1,8 kΩ

Over-temperature/sensor break

Power failure

I201_13579

V

>

U

N

31/4134/44

32/42

t t

t

v

> onoff

LEDred

onoff

LEDgreen

Hysteresis

I201_13580a

V

F

51-5461-64

U

R

R

t

t

51-5261-62

51-5461-6451-5261-62

an

BreakMeasuring circuit

With

out f

ault

stor

age

(jum

per L

T1-L

T2)

With

faul

t sto

rage

(w

ithou

t jum

per L

T1-L

T2)

LED “MK“OnOff

LED “AL“

Reset push-button LT

OnOff

LED “MK“OnOff

LED “AL“OnOff

Ground fault

I201_13581

© Siemens AG 2016

Page 42: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

40 Siemens · 10/2015

7LQ3 monitors for medical premises

Monitoring DevicesMonitoring Devices for Electrical Values

Test and signaling panels Test and signaling combination for insulation monitors

Voltage relays

The voltage relay switches at a phase asymmetry of approx. 6 % to 8 %, regardless of the response values for undervoltage. The above diagram also shows the timing interval.

7LQ3356, 7LQ3357

X1-L1

X2-L1

X3-L2

X4-L2

X5-

LED 1

LED 2

LED 3

LED 4

LED 5

LED 6

LED 7

LED 8

X11-

X8-

X6-

X7-

>

>

Line 1 OK

Line 1 failure

Line 2 OK

Line 2 failure

Test /

lationIso-

Over-temperature

Overload

Output

HornAcknowledgementlamp test

Dark Bright

SM

I201

_139

89

7LQ3360

X1/X2

UUH

REt

t

ON

Ground fault

Horn

GreenLED

Yellow LED

Acknow-ledgement

pushbutton

Ron

I201

_139

90

5TT3411

L

L

b

aN

.3 - .4

U

U

t

.1 - .2

Response value

Hysteresis

I201_13574

5TT3412

L3U

U

UU

t

L2L1

N

11 - 14

11 - 12

on

off

I201_13576a

© Siemens AG 2016

Page 43: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

41Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

7LQ3 monitors for medical premises

■ Dimensional drawings

Switchover devices

The 7LQ3361 and 7LQ3362 switchover devices are designed for mounting in series ALPHA 630 DIN floor-mounted distribution boards and ALPHA AS side-by-side switchgear cabinets with a cabinet depth of at least 320 mm. More information about the distribution boards can be found in Catalog LV 10. Contact your local Siemens representative for information about additional versions.

7LQ3361

I201_17066250 132

171

212

-X1 -X2

-X3

K1

K3 K4

K5

K20 S1

K6 K7

K9

K8

K10

T01

F1 F2 F3 K13

K2

7622

537

647

058

572

884

0 900

© Siemens AG 2016

Page 44: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

42 Siemens · 10/2015

7LQ3 monitors for medical premises

Monitoring DevicesMonitoring Devices for Electrical Values

The 7LQ3361 and 7LQ3362 switchover devices are designed for mounting in series ALPHA 630 DIN floor-mounted distribution boards and ALPHA AS side-by-side switchgear cabinets with a cabinet depth of at least 320 mm. More information about the distribution boards can be found in Catalog LV 10. Contact your local Siemens representative for information about additional versions.

Insulation monitors

7LQ3362

250 132

171

212

-X1 -X2

-X3

K1

K3 K4

K5

K20 S1

K6 K7

K9

K8

K10

T01

F1 F2 F3 K13

K2

76

I201_17067

225

376

470

585

728

840 90

0

7LQ3354 7LQ3355

14055

43

45 90

P2P1 i k PE‘

L‘

PE

L

PT LT1 LT2A1

2124 3134 4144 54 51 64 61 X2 X514

22 32 42 52 62 X112

11

A2

A1 P1 P2 i k PE PT LT1 LT2

14 2411 21 34 31 44 41 54 51 64 61

PE‘ LL‘A2

52 6232 4212 22

105

I201

_138

07

© Siemens AG 2016

Page 45: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

43Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

7LQ3 monitors for medical premises

Test and signaling panels

Current transformers Test and signaling combination for insulation monitors

Voltage relays

7LQ3356

80 57

160

I201

_139

85

7LQ3357

150

82 4710

I201

_139

86

7LQ3358

1078

4627

6,5

60

40

20 30

I201

_138

10

7LQ3360

I201

_140

02

80

80

55

5535

6

ON

TEST

5TT3411 5TT3412

L3L2L1 N

241114

23 31

3212

N La

Lb

Y1 Y2 11 12

41 42

23 24

33 34

727255

43

45 90

I201

_137

12

© Siemens AG 2016

Page 46: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

44 Siemens · 10/2015

7LQ3 monitors for medical premises

Monitoring DevicesMonitoring Devices for Electrical Values

■ Circuit diagrams

Switchover devices

7LQ3361

7LQ3362

Circuit diagram of 7LQ3361 and 7LQ3362 switchover device to test signaling device (e.g. 7LQ3356 or 7LQ3357 test and signaling panels)

I201

_170

68

X1:7

L1 N L1 N

X1:8L1

230 115 115 2N SCH P1 P20

NX2:1 X2:2L1

X2:4 X2:10 X2:11X2:SN (MZ)L2

X1:PE X1:4 X1:5X1:1 X1:2L1 L2

X2:5 X2:3X1:PE

Line 1

To IT transformer From IT transformer

IT system loadLine 2

I201

_170

69

400 400 400 230 230 230 2N SCH P1 P2

X1:9

L1 L2 L3 N

X1:10L1 L2

X1:11L3

X1:12N

X2:1 X2:4L1

X2:7 X2:10 X2:12 X2:13X2:SN(STP)L2 L3

X1:3 X1:4 X1:PEX1:1 X1:2L1 L2 L3 N

X1:7 X1:8 X1:PEX1:5 X1:6L1 L2

X2:2 X2:6L3

X2:8

Line 1

To IT transformer From IT transformer

IT system loadLine 2

I201

_170

70

X3:1 X3:2 X3:4 X3:5 X3:6 X3:7 X3:8 X3:9 X3:10 X3:11 X3:12 X3:13 X3:14 X3:15

Test buttonISO

Line 1Operation

Line 1Failure

Line 2Operation

Line 2Failure

Temperaturemonitoring

Currentmonitoring

ISOmonitoring

IT transformer

© Siemens AG 2016

Page 47: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

45Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

7LQ3 monitors for medical premises

Insulation monitors

Test and signaling panels Test and signaling combination for insulation monitors

Voltage relays

Use La and Lb for monitoring 2 phases or 2-channel monitoring of 1 phase. Lb must be jumpered with La if only La is used.

Circuit diagram of 7LQ3361 and 7LQ3362 switchover device to the central building control system devices

I201

_170

71

X3:18

X3:16 X3:17

X3:19 X3:20 X3:21 X3:22 X3:23 X3:24 X3:25 X3:26 X3:27 X3:28 X3:29 X3:30

MCBtripped

Line 1Operation

Line 2Operation

Line 1Failure

Line 2Failure

Temperaturemonitoring

Currentmonitoring

ISObad

ISOgood

ContactorLine 1 not

switched off

ContactorLine 2 not

switched off

IT transformer IT system

7LQ3354

7LQ3355

I201

_137

13b

11 14 12 21 24 22 31 34 32 41 44 42 51 54 52 61 64 62

LT1

LT2

iP2P1 PE'A2A1 PE PTLL'k

7LQ3354Transformer protection Insulation monitors

11 14 12 21 24 22 31 34 32 41 44 42 51 54 52 61 64 62 X1 X2 X5

7LQ3355 LT1

LT2

iP2P1 PE'A2A1 PE PTLL'k

Transformer protection Insulation monitorsI2

01_1

3811

b

7LQ3356, 7LQ3357

1 2 3 4 5 6 7 8

X5 X4 X3 X2 X1A1 A2 SM PT2 PT1 X8 X7 X6

PT

QH/LT

+

I201_13987

7LQ3360

PT1PT2X1X2X5

Test

Ack.

ON

Ground fault

I201_13988

5TT3411 5TT3412

N

Lb Y1 Y2La

11

12

23

24

33

34

41

42

I201

_137

14a L1L2

N

L3112331

14 122432

© Siemens AG 2016

Page 48: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

46 Siemens · 10/2015

7LQ3 monitors for medical premises

Monitoring DevicesMonitoring Devices for Electrical Values

■ More information

Connection examples

Switchover devices

Insulation monitors

7LQ3361, 7LQ3362

I202_01367a

Test

but

ton

Line

1O

pera

tion

Line

1Fa

ilure

Line

2O

pera

tion

Line

2Fa

ilure

Insu

latio

nO

KIn

sula

tion

Faul

t

Tran

sfor

mer

Tem

pera

ture

Tran

sfor

mer

Ove

rload

Ack

now

ledg

men

t ke

y ex

tern

al

Out

put

Gro

up m

essa

ge

Terminal block X3

Test button ISO Operation Failure Operation Failure

Temperaturemonitoring

Currentmonitoring

ISOmonitoring

LINE 1 LINE 2 IT transformer

X5X4X3X2X1 A1 A2 SMPT2PT1 X8X7X6

7LQ3356 / 7LQ3357

L (L+)N (L-)

X3:1 X3:2 X3:4 X3:5 X3:6 X3:7 X3:8 X3:9 X3:10 X3:11 X3:12 X3:13 X3:14 X3:15

7LQ3361 / 7LQ3362

7LQ3354

I201

_170

57a

11 14 12 21 24 22 31 34 32 41 44 42 51 54 52 61 64 62

P1 P2 i k L PE PTA1 A2

PE PEN L2

L L1

> >

L ' PE '

1)

7LQ3360

X1 X2 X5 PT1 PT2

Isolating transformer3.15 ... 8 kVA

Current transformer

Transformer protection

Overtemperature Overcurrent

Insulation monitor

230 V AC

24 V ACTest and

signaling combination2)

1) If there is no center tap, L/L' is connected to L1 or L2.

2) The 24 V AC power supply unit needs to be powered over the IT system.

7LQ3358

7LQ3354

© Siemens AG 2016

Page 49: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

47Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

7LQ3 monitors for medical premises

Insulation monitors

Test and signaling panels

7LQ3355

Up to four 7LQ3360, 7XV9306, 7XV9304 or 7XV9302 test and signaling combinations can be connected; cf. connection example and comparison of contact assignment between previous and current test and signaling combinations

3,15 … 8 kVA

11 21 31 41 51 6114 24 34 44 54 6412 22 32 42 52 62

P1

LT1

LT2

P2 i k L PE PTA1 A2

PE PEN L2

230 V AC

L1)

L1

7LQ3355

> >

L' PE'

7LQ3360

X1 X2 X5

X1 X2 X5 PT1 PT2

PE PT

Overtemperature Overcurrent

Transformer protection

Current transfor.

ResetExternal

External test

Insulation monitor

R <F ALR /Measuring circuit break

Insulation fault

Jumpers =non-latching

Isolating transformer

1) If there is no center tap, L/L' is connected to L1 or L2.Test and

signaling combination

7LQ3358

I201

_139

94a

X1 ... X7 Fault signaling inputs

X8 Acknowledgement horn/lamp test

SM Central indication output

PT1, PT2 Test button for insulation monitors

7LQ3356, 7LQ3357

X1

PT1PT2

PT PE

X2 X3 X4 X5 X6 X7 X8 SM A1

A2

L(L+)

N(L-)

1 2 3 4 65 7 8

externoQH / LT

7LQ3354 / 7LQ3355

7LQ3356 /7LQ3357

11 14 31 34 51 54

OK

Failu

re

OK

Failu

re

Line 2Line 1

Voltage monitoring

I201

_139

91a

© Siemens AG 2016

Page 50: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

48 Siemens · 10/2015

7LQ3 monitors for medical premises

Monitoring DevicesMonitoring Devices for Electrical Values

Connection example for 7LQ3355 insulation monitors with 7XV9306 test and signaling combination

Up to four test and signaling combinations (e.g. the 7LQ3360 test and signaling combination and the previous 7XV9306, 7XV9304 or 7XV9302 test and signaling combinations (now no longer available) can be connected.

An external 24 V AC (e.g. 4AC3616) transformer is required to power the test and signaling combination.

7LQ3355

11 14 12 21 24 22 31 34 32 41 44 42 51 54 52 61 64 62

PT 52 51 PE

X1 X2 X5

P1

LT1

LT2

P2 i k L PE PTA1 A2

PE PEN L2

L L1

L ' PE '

1)

4

5

2

3

6

18

A2A1 15

4

5

2

3

6

4

5

2

3

6

4

5

2

3

6

B1

2)

RF < R

1) If there is no center tap, L/L' is connected to L1 or L2.2) The 24 V AC power supply unit needs to be powered over the IT system.

230 V AC

> >

Isolating transformer3.15 ... 8 kVA

Current transformer

Transformer protection

Overtemperature Overcurrenton

/ measuring circuit interruptionInsulation fault

Insulation monitor

External test

ResetExternal

Jumper =non-latching

24 V AC

I201_13812d

7LQ3358

7LQ

5TT

7XV9306

7XV9306

7XV9306

7XV9306

© Siemens AG 2016

Page 51: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

49Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

7LQ3 monitors for medical premises

Comparison between the contact assignment for the previous, no longer available test and signaling combinations 7XV9306, 7XV9304 and 7XV9302 and the contact assignment for the current 7LQ3360 test and signaling combination.

Monitoring of medical premises

Medical premises are all rooms used for the examination or treatment of persons or animals. Besides doctors' surgeries and clinics, these also include hydro-therapeutic and physical therapeutic treatment and massage rooms.

TÜV-certified switchover and monitoring devices are used for a reliable power supply. The insulation monitors and voltage relays in the switchover and monitoring devices need to comply with the requirements of standard DIN VDE 0100-710 and IEC 60364-7-710.

Medical premises were divided up into three groups in DIN VDE 0100-710, which was published in 2002.

For premises in groups 0 and 1, the standard requires, among other things, implementation of the system type TN-S and residual current protective devices (RCDs) for protection against excessively high touch voltages.

The premises of group 2 are defined as follows:• The system must not be disconnected in the event of a first

short circuit to frame or to ground or if the general power supply fails

• Repetition of treatment is unacceptable for patients or it is impossible to obtain results of examinations again

• An irregularity (a fault) in the power supply can cause danger to life

• A piece of equipment used for medical purposes, which is used occasionally for applications in accordance with DIN VDE 0100-710.2.7, should be assigned to group 2

Typical locations in group 2 are anesthetic rooms, operating rooms and recovery rooms in hospitals, clinics or doctors' surgeries, as well as equipment used in veterinary medicine.

Standard DIN VDE 0100-710 makes the following stipulations:• Constant monitoring of the power supply on the preferred

supply line and on the second supply line• Automatic changeover to the 2nd supply line within a defined

time (< 0.5 s or < 15 s)• Reliable operation even if a fault occurs

(one-fault security)

The switchover device monitors the supply voltage on the preferred and second supply line for undervoltage and power failure. As soon as a voltage drop to a defined value is determined, the voltage relays respond and the switchover device automatically switches to the second supply line. As soon as the power is restored on the preferred supply line, the system switches back to it.

IT system

In the IT system name, the first letter describes the grounding relationships of the current source. I stands for insulation of all live parts from ground or connection of a point to ground via an impedance. The second letter identifies the grounding relationships of the body of the electrical system.

T means that the body is directly grounded, independently of any existing grounding of a point of the power source.

Medical IT systems

Standard DIN VDE 0100-710 makes the following stipulations for a medical IT system in group 2:• The medical IT system must be used for socket outlet circuits

in the patient environment. This also applies for circuits supplying operating room lights

• At least one IT system is required for each room group• Separate circuits must be provided for multiple socket outlets• First faults must not lead to disconnection of the system

The IT system is powered by an isolating transformer or an independent power source (such as a battery). The special feature is that no active conductors in this network are linked directly to ground. This has the advantage that only a small residual current can flow in the event of an insulation fault. This is essentially dictated by the leakage capacitances and is harmless to patients and staff. The upstream fuse element does not respond so that the power supply, and therefore operation, is maintained, even in the event of a phase-to-ground fault. The high reliability of an IT system is ensured by continuous insulation monitoring. The insulation monitor detects insulation faults as they develop and signals in good time if a value falls below a limit value, before any further insulation faults can lead to an unexpected shutdown. The temperature of the transformer and the transformer load continue to be monitored constantly. Any exceeding of limit values is signaled immediately.

31

32

33

34

35

7XV93027XV93047XV9306

1

23

3

4

5

2

4

5

6

X5

PT1

PT2

X2

X1

7LQ3360

Test

24 V AC

Fault input

I201

1381

3c

I201_12110

L2L3

L1

Body

IT system

PE

© Siemens AG 2016

Page 52: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

50 Siemens · 10/2015

7LQ3 monitors for medical premises

Monitoring DevicesMonitoring Devices for Electrical Values

Insulation monitoring

The 7LQ3354 and 7LQ3355 insulation monitors are used to monitor the insulation resistance of non-grounded IT systems in medical premises. They also simultaneously monitor the load current and the temperature of the IT isolating transformer. The devices can monitor both three-phase and AC systems.

Temperature measurement: The temperature in the transformer winding is recorded using a PTC thermistor or NC contacts.

As well as an adjustable response value of 50 ... 500 kΩ, the 7LQ3355 insulation monitor also has an 11-step LED chain for displaying the current insulation resistance of the system. A range of differently colored LEDs indicates the insulation resistance within the range of 20 kΩ … 1 MΩ. This allows insulation deteriorations to be detected even before an alarm is triggered. The device is also equipped with an additional relay for connection of a test and signaling combination. This allows the 7LQ3360 test and signaling combination and the previous and no longer available test and signaling combinations 7XV9306, 7XV9304 and 7XV9302 to be connected to the 7LQ3355 insulation monitor (see also the graphic under "Connection example: 7LQ3355 insulation monitors with 7XV9306 test and signaling combination").

Load current sensing: The 7LQ3358 current transformer detects the load current of a phase. Evaluation is carried out over the 7LQ3354 and 7LQ3355 insulation monitors.

Evaluation: If one of the values is outside the limit values, an alarm is triggered. The LED for the relevant fault lights up and the alarm relay switches. The information is made available over the changeover contacts and can be displayed on the 7LQ3356 and 7LQ3357 test and signaling panels.

Voltage monitoring

In the case of undervoltage, there is no guarantee that medical equipment will continue to function. Because of the risk this presents to patients, e.g. during operations, it is essential that a switchover unit switches to a second power supply in the event of an undervoltage in the preferred power supply.

The voltage relays switch when the voltage falls below 90 % of the rated voltage. The 5TT3411 relays serve to monitor a 1-phase infeed. 3-phase infeeds can be monitored using 5TT3412 relays. These relays also offer asymmetry, reverse voltage and phase failure detection.

TÜV-certified switchover device

The 7LQ3361 and 7LQ3362 switchover devices have been tested and certified by TÜV Rhineland. Switchover devices comply with DIN VDE 0100-710:2002-11 and IEC 60364-7-710:2002-11.

Rhineland TÜV certificate for 7LQ3361 and 7LQ3362 switchover devices

© Siemens AG 2016

Page 53: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

51Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Electrical Values

7LQ3 monitors for medical premises

Components and control elements in 7LQ3361 and 7LQ3362 switchover devices

Control elements for insulation monitors

I201

_170

73

1

4

5

6

7

2

3

8

Meaning

1 Terminal block X1

2 Terminal block X2

3 Terminal block X3

4 Mechanical latching

5 Miniature circuit breakers

6 Voltage relay test pushbuttons

7 Insulation monitors

8 Temperature monitoring test pushbuttons

7LQ3354

7LQ3355

A1 P1 P2 i k PE PT LT1 LT2

14 2411 21 34 31 44 41 54 51 64 61

PE‘ LL‘A2

52 6232 4212 22

1 2 3 54

76

89

11

10

I201

_137

16

P2P1 i k PE‘

L‘

PE

L

PT LT1 LT2A1

2124 3134 4144 54 51 64 61 X2 X514

22 32 42 52 62 X112

11

A2

1 2 3 545a

76

89

119a

10

I201

_138

14

LED Meaning

1 Current monitoring (green)

Lights up if the current is correct (Go state)

2 Current monitoring">I" (red)

Lights up in the case of overcurrent

3 Insulation monitoring "ON" (green)

Lights up when the power supply is switched on (ready-to-run)

4 Insulation monitoring "MK" (red)

Lights up if a line of the measuring circuit is interrupted (L, L’, PE, PE’)

5 Insulation monitoring "AL" (red)

Lights up in the case of an insulation fault, RF<Ran (value has fallen below the response value)

5a Insulation monitoring "RF" (red, yellow, green)

11-step LED chain to display the current resistance

6 Temperature monitoring (green)

Lights up when the power supply is switched on

7 Temperature monitoring (red)

Lights up in the event of overtemperature or an interruption in the sensor circuit

Pushbutton/rotary controller

Meaning

8 Rotary controller response value ">I"

Setting of the response value for current monitoring

9 Rotary controller delay time

Setting of delay time after which the CO contacts return to their normal position if the current value exceeds the set response value.

9a Rotary controller response value "Ran kΩ"

Setting of the response value for insulation monitoring

10 "TEST" pushbutton Pressing the "Test" test button simulates an insulation deterioration in the measuring circuit (RF approx. 40 kΩ), thus checking that the insulation monitor is fully functional

11 "RESET" button Deletion of fault if fault storage is activated

© Siemens AG 2016

Page 54: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

52 Siemens · 10/2015

7LQ3 monitors for medical premises

Monitoring DevicesMonitoring Devices for Electrical Values

Control elements of the test and signaling panels

Note: Customized reporting and signaling panels can be produced, for instance with an integrated intercom, for the switchover and monitoring devices. For more information on this contact your local Siemens representative.

Control elements of the test and signaling combination

Control elements of voltage relay

7LQ3356, 7LQ3357

I201

_139

95

>

7LQ3 356

line 1on

line 1failure

insulationok

test

line 2failure

line 2on

LED window displays Meaning

Line 1 On Power supply is implemented over the preferred infeed

Line 2 On + Line 1 Failure

Power supply is implemented over the second line as the preferred infeed has failed

Line 1 On + Line 2 Failure

Power supply is implemented over the preferred infeed. However the second line is no longer available

Line 2 On + Line 1 Failure + Line 2 Failure

Power supply is implemented over the second line as the preferred infeed is faulty. There is undervoltage on the second line

Overload Excessive power consumption of the IT system

Overtemperature The transformer of the IT system is overloaded

Insulation is good The transformer of the IT system is overloaded

Insulation is defective The insulation resistance of the IT system is too low

TEST Pushbutton for testing the insulation monitoring devices

Acknowledgement pushbutton/lamp test

Pushbutton for acknowledging the acoustic alarm signal/function test of the display elements

7LQ3360

I201

_139

96

ON

TEST

LED/pushbutton Meaning

ON Green LED The LED lights up if the power supply is applied

Ground fault

Yellow LED Insulation fault: The insulation resistance of the IT system is too low

TEST Pushbutton for testing the insulation monitoring devices

Acknowledgement pushbutton

Button for acknowledging the acoustic alarm signal

5TT3411 5TT3412

N La

Lb

Y1 Y2 11 12

41 42

23 24

33 34

12

L3L2L1 N

241114

23 31

3212

12

2

2

I201

_137

20

LED/pushbutton Meaning

1 5TT3411: Yellow LED 5TT3412: Green LED

The LED lights up if the system is fault-free

2 TEST button Pressing the test button simulates an undervoltage. The 3-phase 5TT3412 voltage relay has a test button for each phase.

© Siemens AG 2016

Page 55: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

53Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Plants and Equipment

5TT3 fault signaling units

■ Overview

Fault signaling units are used in small plants where the installation of complex fault signaling systems would be too labor-intensive and too expensive. In the event of a fault, they enable fast fault localization of all monitoring devices and limit monitors installed in a plant from a central location. This increases plant availability. With the correct sensor configuration, they also provide the option of preventative maintenance.• 4 fault signaling inputs with LED• 1 LED as centralized fault indicator

• One unit each for centralized fault indication and acoustic signaling

• With acknowledgment for acoustic indicators• Open/closed-circuit principle so the 4 inputs can be adjusted

via jumpers X1 - X2• A maximum of 39 5TT3461 expansion fault signaling units can

be connected to the 5TT3460 centralized fault signaling unit• The maximum possible cable length between 5TT3460

centralized fault signaling units and 5TT3461 expansion fault signaling units is approx. 100 m with a conductor cross-section of 1.5 mm2

■ Technical specifications

■ Dimensional drawings

■ Circuit diagrams

Graphical symbols

5TT3460 5TT3461

Standards IEC 60255; DIN VDE 0435-110, -303

Rated operational voltage Uc V AC 230

Primary operating range × Uc 0.8 ... 1.1

Rated frequency fn Hz 50/60

Fault signaling inputs S1 ... S4 V AC 230

Signal voltage

To terminals S and H

V 7 ... 10

Noise pulse duration ms ≥ 100

Acknowledgment pulse duration ms ≥ 200

Contacts

• Rated operational voltage Ue V AC 230 --

• Rated operational current Ie A 5 --

• Minimum contact load V; mA 10; 100 --

Connections

• Terminals ± Screw (Pozidriv) PZ 1

• Conductor cross-sections- Rigid, max. mm2 2 × 2.5- Flexible, with end sleeve, min. mm2 1 × 0.5

Permissible ambient temperature °C -20 ... +60

Humidity class Acc. to IEC 60068-2-30 F

5TT3460 5TT3461

5 4364

45 90

I201

_115

11a

36 36

A1 S H

S1 S2 S3 S4

A1 S H

S1 S2 S3 S4

14 24 QH A2

13 23 X1 X2

A2

X1 X2

5TT3460 5TT3461

24

23

14

13

I201

_001

54

QHHSX2X1

S4S3S2A1 A2 S1

I201

_001

55

HSX2X1

S4S3S2A1 A2 S1

© Siemens AG 2016

Page 56: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

54 Siemens · 10/2015

5TT3 fault signaling units

Monitoring DevicesMonitoring Devices for Plants and Equipment

Typical circuit, function chart

If there is a fault, the SM fault indication contact closes and a centralized fault is indicated over an LED. The assigned LED remains lit until the fault is eliminated. Until the acknowledgment, momentary faults can be identified by the remaining centralized fault.

The terminals A1, S1 to S4 and QH must be operated in-phase. If no external acknowledgment key is connected, terminal QH must be applied to L1.

If jumper X1 – X2 is inserted, open-circuit protection (otherwise closed-circuit protection).

Contacts 13/14 and 23/24 close in the event of an incoming fault. The assigned LED and the SM centralized fault indication LED light up.

The alarm sensor (contact 13/14) is switched off using the acknowledgment key. The assigned LED and the centralized fault indication LED continue to light up and contact 23/24 remains closed until the fault is eliminated.

Cables S and H carry an extra-low voltage. In the case of long connections between different distribution boards a shielded cable must be laid parallel to the installed load lines.

As a light signal sensor for the group messages we recommend devices 5TE57 or 5TE58; as an alarm sensor the devices 5TT3450 to 5TT3453.

A1 A2

N

13 23 S1 S2 S3 S4 A1 A2 S1 S2 S3 S4

X1 X2 S HX1 X2 S H

QH

SM14 24

5TT3460 5TT3461

I201

_072

82d

L1 230 V AC

(Working current) (Closed-circuit current)

Acknow-ledgementkey

FaultalarmFA

I201_07283c

Fault 1

LED 1

Fault 2

LED 2

Central indicationrelay

Central indicationhorn

Acknowledge.horn

dark bright

LED SM

© Siemens AG 2016

Page 57: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

55Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Plants and Equipment

5TT5 EMERGENCY STOP modules

■ Overview

EMERGENCY STOP circuits are common safety measures in all laboratory equipment and industrial plants. The EMERGENCY STOP modules used here must meet the most rigorous demands

with regard to functional reliability. Benchmark is the degree of self-monitoring.

■ Technical specifications

■ Dimensional drawings

5TT5200 EMERGENCY STOP module

5TT5200

Standards IEC 60204-1; EN 60204-1 (VDE 0113-1)

Supply

• Rated operational voltage Uc V AC 230- Primary operating range × Uc 0.8 ... 1.1

• Rated frequency fn Hz 50

• Rated power loss Pv Coil/drive 3.5Contact per pole VA 0.8

Control voltage Terminal Y1 V AC/DC 24

Control current Terminal Y1 mA DC 45

Recovery time ms 500

Safety

• Electrical isolation, creepage distances and clearances, actuator/contact mm 3

• Rated impulse withstand voltage Uimp actuator/contact kV > 4

Contacts

• Contacts NO contacts AC-15 A 3NC contacts AC-15 A 2NO contact/NC contact

AC-1 A 5

• Contact gap mm > 1

• Electrical service life AC-15, 2 A, 230 V AC Switching cycles

105

• Permissible switching frequency Switching cycles/h

600

Vibration resistanceAmplitude Acc. to

EN 60068-2-610Up to 55 Hz

mm 0.35

Connections

• Terminals ± Screw (Pozidriv) PZ 1

• Conductor cross-sections of main current paths- Rigid Max. mm2 2 × 2.5- Flexible, with end sleeve Min. mm2 1 × 0.5

Permissible ambient temperature °C 0 ... +50

Climatic withstand capability Acc. to EN 60068-1 0/55/04

4355

45 90

571

33

A2

13Y1

16

Y2

23 41

3414 24 42

K1/2

A1

I201

_084

37a

A1

Sup

ply

© Siemens AG 2016

Page 58: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

56 Siemens · 10/2015

5TT5 EMERGENCY STOP modules

Monitoring DevicesMonitoring Devices for Plants and Equipment

■ Circuit diagrams

Typical circuit diagrams

Direct connection 230 V/400 V to 5 A

The monitoring logic checks internal relay contacts (not shown) to see whether both relays have been released prior to switching on. This ensures that no contacts are welded. The voltage level at terminal A1 is also monitored. The parallel NC contacts K1 and K2 (terminals 41 and 42) can be connected as required.

Connection of external contactors

External contactors may be used when they are equipped with positively driven contacts according to safety regulations ZH1/457 of the German Trade Association. Contactors with 3 NO contacts and 1 NC contact must be used, in which case the NC contacts must be integrated in the monitoring loop – terminals Y1/Y2. The parallel NC contacts K1 and K2 (terminals 41 and 42) can be connected as required.

L1

A1 Y1 13 23 33 41

14 24 34 42

K2

K1

A2

NI201_08435b

Y2

EMERGENCY-STOP

Monitoringlogic

On

L1

A1 Y1 13 23 33 41

14 24 34 42

K2

K1

A2

I201_08436b

K3

K4

Y2

K4

K3

L1 L2 L3

N N

EMERGENCY-STOP

Monitoringlogic

On

© Siemens AG 2016

Page 59: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

57Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Plants and Equipment

5TT3 level relays

■ Overview

Level relays are used for the monitoring and control of con-ductive, non-combustible liquids and powders. They ensure overflow and dry run protection. Due to their sensor perfor-mance, the devices can also be used for general resistance monitoring.

LED displays:- Green LED: lights up when operational voltage is applied- Yellow LED: lights up if MIN output relay is activated- Red LED: lights up if MAX output relay is activated

■ Technical specifications

■ Dimensional drawings

5TT3435 level relays 5TG8223 immersion electrodes

5TT3435

Standards IEC 60255; DIN VDE 0435-110

Supply

• Rated operational voltage Uc V AC 230- Primary operating range × Uc 0.8 ... 1.1

• Rated frequency fn Hz 50/60

Setting range of the liquid level kΩ 2 ... 450

Switching point hysteresis of set value

• At 450 kΩ % 3• At 2 kΩ % 6

Voltage temperature influence From set value % < 2

Max. cable length to the Setting kΩelectrodes at 100 μF/km 450 m 50

100 m 20035 m 50010 m 15005 m 3000

Electrode voltage Max. V AC Approx. 10

Electrode current Max. mA AC Approx. 1.5

Response delay Adjustable s 0.2 ... 20

OFF-delay Adjustable s 0.2 ... 20

Rated operational voltage Ue V 250

Rated operational current Ie A 5

Test voltageInput/auxiliary circuit kV 4Input/output circuit kV 4Auxiliary/output circuit kV 4

Connections

• Terminals ± Screw (Pozidriv) PZ 2

• Conductor cross-sections- Rigid Max. mm2 2 × 2.5- Flexible, with end sleeve Min. mm2 1 × 0.5

Permissible ambient temperature °C -20 ... +60

Climatic withstand capability Acc. to EN 60068-1 20/60/4

5TT3435

36 5 4364

45 90

I201

_137

60

COMX1 X2

MINMAXA1A2

12 22

14 11 24 21

5TG8223

7914

013

5

Ø16

21

5I2

01_1

2435

© Siemens AG 2016

Page 60: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

58 Siemens · 10/2015

5TT3 level relays

Monitoring DevicesMonitoring Devices for Plants and Equipment

■ Circuit diagrams

Graphical symbols

Typical circuit for 5TT3435

One-step level control

Two-step level control

X1

MIN MAX COM

X2 A1 A2 14

11 21

12 24 22

The one-step level control is particularly suitable for dry run or overrun protection with free inflow/outflow.

The COM reference electrode and MAX electrode are needed.

Without the jumper X1-COM only relay 21-22-24 switches.

With the jumper X1-COM both relays switch together.

21-2421-22

21-2421-22

COM X2

COM X2

MAX

0

11-14/21-2411-12/21-22

t

11-14/21-2411-12/21-22

COM X2

COM X2t t

X1

X1

X1

X1

COM X2

COM X2I2

01_0

7520

d

Supply

Level

Static current

Load current

L1 N

A1 A2

141112242122

COM MIN MAX X2

MIN

MAX

X1

I201

_075

18b

230 V AC

Level

t = tv max adjustable from 0.2 s to 20 s

The 2-step level control keeps the liquid level between a minimum and a maximum level. Three electrodes are required: MIN, MAX and COM.

Without the jumper X1-COM, switching is as follows:

• If the MAX level is fallen below/exceeded, only relay 21–22–24 switches.

• If the MIN level is fallen below/exceeded, only relay 11–12–14 switches.

With the jumper X1–COM, both relays switch together if the value exceeds the MAX level or falls below the MIN level.

L1 N

A1 A2

141112242122

COM MAXMIN X2

MIN

MAX

X1

I201

_075

19bLevel

230 V AC

21-2421-22

11-1411-12

COM X2

MAX

U0

MIN

H

12

X1

21-2421-22

11-1411-12

COM X2

min

X1

11-14, 21-2411-12, 21-22

max

COM X2X1

11-14, 21-2411-12, 21-22COM X2X1

COM X2

COM X2

I201

_075

21d

tvtv

mintvmaxtv

Level

Static current

Load current

tv max and tv min adjustable from 0.2 s to 20 s

© Siemens AG 2016

Page 61: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

59Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Plants and Equipment

5TT3 line circuit relays

■ Overview

Line circuit relays are used to interrupt circuits and prevent electromagnetic fields in circuits where there are currently no active loads. If the loads are disconnected, and the line circuit relay measures a usage of only 2 to 20 VA – adjustable – it disconnects the cable to the supply voltage and switches over to extra-low voltage. As soon as loads are reconnected, the line circuit relay detects the increase in usage and switches back to the supply voltage. While the line circuit relay switches off any unnecessary system

components, it is not a device for ensuring isolation in the sense of safe disconnection.

The line circuit relay is unable to detect consumers with electronic power supply units, e.g. electronically controlled vacuum cleaners. It is expedient to connect such devices to a base load resistor (PTC resistor) so that the line circuit relay is reset to supply voltage.

■ Technical specifications

■ Dimensional drawings

■ Circuit diagrams

Typical circuit diagram If the line circuit relay does not respond to a load, it must be connected with a 5TG8222 base load resistor. Devices in active standby operation may impair the function of the line circuit relay.

5TT3171

Standards IEC 60255; DIN VDE 0435-110

Rated operational voltage Uc V AC 230

Primary operating range × Uc 0.85 ... 1.15

Rated frequency Hz 50/60

Rated power loss Pv Electronics VA 5Contacts VA 2.6

Monitoring voltage V 3

Response value Adjustable VA 2 ... 20

Release value % of the response value 70

Rated impulse withstand voltage Uimp Input/output kV > 4

Rated operational voltage Ue V AC 250

Rated operational current Ie AC-1 A 16AC-11 A 3

Contacts μ contact

Electrical service life In switching cycles at 3 A AC-11 5 × 105

Terminals ± Screw (Pozidriv) PZ 1

Conductor cross-sections

• Rigid Max. mm2 2 × 2.5• Flexible, with end sleeve Min. mm2 1 × 0.5

Permissible ambient temperature °C -20 ... +45

Degree of protection Acc. to IEC/EN 60529 IP20, with connected conductors

Safety class Acc. to EN 61140/VDE 0140-1 II

Humidity class Acc. to IEC 60068-2-30 F

5TT3171

L N

5 4364

18

I201

_107

75a

45 90

L N

L1N

PTC

i

I201

_070

36b

230 V AC

Elec-tronic

© Siemens AG 2016

Page 62: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

60 Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Plants and Equipment

■ Overview

The p.f. monitor monitors the phase displacement between current and voltage. Because the phase displacement angle changes with the load of the motor, this measurement method is ideal for the monitoring of asynchronous motors for underload and no-load operation, independent of size. However, in some cases, the p.f. barely changes if the load of the motor changes, e.g. in the case of relatively minor load changes on large-scale motors or single-phase split-pole motors or collector motors.

The p.f. monitor monitors single and three-phase asynchronous motors up to approx. 5 A (without current transformer) for underload and no-load operation, thus increasing plant availability. Typical applications are fan monitoring in the case of V-belt breakage, pump monitoring in the event of valve closure

or dry runs. A current transformer is used for higher rated currents.

If the lower p.f. value set at the p.f. monitor is violated for the duration of the set response delay, the output relay switches to the alarm state and the red LED lights up. If the higher p.f. value is violated, the output relay switches back without any significant delay.• Adjustable p.f. response value, from 0 to 0.97• Current range up to 8 A• LED display for operation and alarm• Automatic resetting of alarm

■ Technical specifications

■ Dimensional drawings

5TT3472

5TT3472

Standards IEC/EN 60255, VDE 0435

Rated operational voltage Uc 3 V AC 400

Primary operating range With AC supply × Uc 0.8 ... 1.1

Frequency range fn Hz 45 ... 65

Rated power loss Pv VA Approx. 11

Rated impulse withstand voltage Uimp Against contacts kV < 4

Current measuring circuits For AC systems

Current measuring range Imeas A AC 0.4 ... 8

Short-time load carrying capacity For 2 s A 20For 0.5 s A 40

Current transformer, class 3 or better Secondary current A 1 or 5

Setting range Adjustable p.f. 0 ... 0.97

Response delay Adjustable s 1 ... 100

Short-circuit strength Fuse 4 A gL A 4

Contacts μ contact 1 CO

• Rated operational voltage Ue V AC 250

• Rated operational current Ie Thermal current A 4AC-15 NO contacts A 3AC-15 NC contacts A 1AC-13 at 24 V DC A 1

• Minimum contact load V; mA 10; 100

Connections

• Terminals ± Screw (Pozidriv) PZ 2

• Conductor cross-sections- Rigid Max. mm2 2 × 2.5- Flexible, with end sleeve Min. mm2 1 × 0.5

Permissible ambient temperature °C -20 ... +60

Resistance to climate Acc. to EN 60068-1 20/60/4

Degree of protection Acc. to EN 60529 IP20, with connected conductors

L3

L1

12

141

18 5 43

45 90

I201

_115

28b

1

L2

64

L1'

5TT3 p.f. monitors

© Siemens AG 2016

Page 63: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

61Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Plants and Equipment

■ Circuit diagrams

■ More information

Function charts

If the lower p.f. value set at the p.f. monitor is violated for the duration of the set response delay, the output relay switches to the alarm state and the red LED lights up. Contact 11–14 closes and the red LED lights up.

Front view

Connection of three-phase load Connection of single-phase load

Connection of motors with separate windings

Connection of three-phase load with external current transformer, whereby the winding direction of the current transformer must be taken into account.

L1

11 12 14

L1' L2 L3

L1

M3

L2

L3

I201

_115

24b

L1

11 12 14

L2 L3

L

N

I201

_115

25b

L1'

Load

L1

11 12 14

L1' L2 L3

L1

M3

L2

L3

Kk

l L

Kk

l L

1W11V1

1U1

2W12V1

2U1

I201

_115

27b

LowSpeed

HighSpeed

L1

11 12 14

L1' L2 L3

L1

M3

L2

L3

K L

k l

I201

_115

26b

Tripp.f.

I201

_115

23b

11-1411-12

ty

U(L1/L2/L3)

I(L1/L2)

L3 L2

11

L1 L1'

14

I201

_119

73a12

E1

E2LED red

LED green

Underloading indicator (p.f. alarm)LED red:Response valueE1:Response delay tyE2:

LED green: Status display (U)

5TT3 p.f. monitors

© Siemens AG 2016

Page 64: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

62 Siemens · 10/2015

5TT3 motor protection relays

Monitoring DevicesMonitoring Devices for Plants and Equipment

■ Overview

Thermistor motor protection relays monitor the thermistors wound in motors. This helps to prevent thermal motor overloads, e.g. due to high switching frequency, single-phasing, disabled cooling or excessive ambient temperatures. Up to 6 thermistors in series can be monitored. A conductor break in the sensor conductor will immediately trip the device. The device can also be used for monitoring wound quick-break switches – e.g. bimetal thermostats. This offers all-round motor protection.• For the detection of

- Violation of upper temperature limits- Wire breaks in sensor circuits

• 1 input for 1 to 6 thermistors• With 2 LEDs green/red for ready-to-run and fault

• Response value: 3.2 to 3.8 kΩ• Release value: 1.5 to 1.8 kΩ• The max. cable length of the sensor supply cable NYM 2 × 1.5

is 100 m• Remote Reset: over A1/A2 (NC contact) or over X1/X2

(NO contact)

LED displays:• Green LED: Lights up when operational voltage is applied• Red LED: Lights up in the event of overtemperatures or an

interruption in the sensor circuit

■ Technical specifications

■ Dimensional drawings

5TT343 motor protection relays

5TT34315TT3432

Standards IEC 60255; DIN VDE 0435-110

Rated operational voltage Uc V AC 230

Primary operating range × Uc 0.9 ... 1.1

Rated frequency Hz 50/60

Response value kΩ 3.2 ... 3.8

Release value kΩ 1.5 ... 1.8

Minimum contact load V; mA 10; 100

Rated insulation voltage Ui Between coil/contact kV 4

Rated impulse withstand voltage Uimp Actuator/contact kV > 2.5

Contacts μ contact (AC-11) A 3

• Rated operational voltage Ue V AC 230

• Rated operational current Ie A 5Actuator/contact mm 4

Connections

• Terminals ± Screw (Pozidriv) PZ 1

• Conductor cross-sections- Rigid Max. mm2 2 x 2.5- Flexible, with end sleeve Min. mm2 1 x 0.5

Permissible ambient temperature °C -20 ... +60

Climatic withstand capability Acc. to EN 60068-1 20/60/4

5TT3431 5TT3432

36 36 5 4364

45 90

I201

_115

30a

A1 P1 P2 A1

A1

12

14 11 24 2114 11 24 21

2212 22

P1 P2

X1 X2A2

© Siemens AG 2016

Page 65: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

63Siemens · 10/2015

Monitoring DevicesMonitoring Devices for Plants and Equipment

5TT3 motor protection relays

■ Circuit diagrams

Graphical symbols

Typical circuit for 5TT3431, 5TT3432

If one of the thermistors (possible for up to 6) reaches the response temperature, the device switches.

5TT3431 (without terminals X1/X2 and without RESET button) switches back on after cooling and after the value falls below that permanently set for the hysteresis. To switch on before this time, briefly disconnect the power supply.

5TT3432 stores the fault and remains switched off until the RESET button is pressed.

5TT3431 5TT3432

2111

22241214

P1 P2

A1 A2

2111

22241214

X2X1P2P1

A1 A2

L1 N

A1 A2

141112242122

X2X1

1...6 v +

M

I201_07041c

Resetpushbutton

230 V AC

R

I201_07280e

11-14

P1/P2

5TT3432: 11-12

11-14 5TT3431: 11-12

(X1/X2)

HU

t

t

3,2 k

1,8 k

TEST/RESET

TEST/RESET

TEST/RESETpushbutton

Overtemperature/sensor breakage

Voltagefailure RESET

© Siemens AG 2016

Page 66: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

64 Siemens · 10/2015

Notes

Monitoring Devices

© Siemens AG 2016

Page 67: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

© Siemens AG 2016

Page 68: Configuration Manual for Catalog LV 10 2016/2017 – Chapter 12 · and alarm signals for monitoring industrial plants and control systems. ... single-phasing, ... monitoring system

The information provided in this brochure contains merely generaldescriptions or characteristics of performance which in case of actualuse do not always apply as described or which may change as a resultof further development of the products. An obligation to provide therespective characteristics shall only exist if expressly agreed in theterms of contract. Availability and technical specifications are subjectto change without notice.All product designations may be trademarks or product names ofSiemens AG or supplier companies whose use by third parties for theirown purposes could violate the rights of the owners.