Date Code 20130619 SEL Application Guide 2013-09
Application Guide Volume VII AG2013-09
Configure ACSELERATOR TEAM® and an
SEL-735 to Retrieve and Report Metering Data Chris Hilling
INTRODUCTION This application guide uses an example to describe how to configure ACSELERATOR TEAM
® SEL-5045 Software and an SEL-735 Power Quality and Revenue Meter to poll and report meter data. ACSELERATOR TEAM is a database-driven software that collects and stores load profile (LDP) metering data and voltage sag, swell, and interruption (VSSI) data from compatible SEL meters.
This application guide is used to do the following:
Configure an SEL-735 to communicate and store LDP and VSSI data.
Use ACSELERATOR QuickSet® SEL-5030 Software for meter communications and data polling.
Report LDP and VSSI data using a Microsoft® Excel® spreadsheet.
Note that ACSELERATOR TEAM must be installed on the computer prior to using this application guide. Refer to the ACSELERATOR TEAM instruction manual for installation instructions.
OVERVIEW OF REQUIRED SETTINGS Table 1 through Table 6 give example settings used to establish communications between the SEL-735 and the ACSELERATOR TEAM database. These settings are also used as the limits for the VSSI settings group.
Table 1 SEL-735 LDP Settings
Settings Group Setting Example
Value Comments
Events and Logging > Load Profile
LDFUNC EOI
User configurable (AVG, EOI, COI, MAX, MIN)
Note that LDP Recorder 1 always records energy quantities as COI
LDLIST1 WH3_DEL, QH3_DEL
User configurable (up to 16 elements maximum)
LDAR 15M User configurable
(15M minimum, 60M maximum)
2
SEL Application Guide 2013-09 Date Code 20130619
Table 2 SEL-735 VSSI Settings
Settings Group Setting Example
Value Comments
Events and Logging > Voltage Sag/
Swell/Interruption
VBASE 120.00 User configurable
(20.00 to 300.00 V)
VINT 10.00 User configurable
(5.00% to 99.00% of base; off)
VSAG 90.00 User configurable
(10.00% to 99.00% of base; off)
VSWELL 110.00 User configurable
(101.00% to 180.00% of base; off)
Table 3 SEL-735 Ethernet Communications Settings
Settings Group Setting Example
Value Comments
Communication > Ports > Port 1
(Ethernet)
EPORT Y User selectable (Yes or No) Enable EPORT for Ethernet
communications
TPORT 23 Range 23, 1025 to 65534
IPADDR 192.168.0.2 User configurable
Select different address than host computer
DEFRTR 192.168.0.1 User configurable
SUBNETM 255.255.255.0 User configurable
Table 4 SEL-735 Serial Communications Settings
Settings Group Setting Example
Value Comments
Communication > Ports >
Ports 2 or 3 (Serial)
EPORT Y User selectable (Yes or No)
Enable EPORT for serial communications
PROTO SEL User configurable
(SEL, MOD, DNP, LMD, MBA, MBB, MB8A, MB8B)
SPEED 9600 User configurable
(300 to 115200 bps)
BITS 8 Data bits
PARITY N No parity bits
STOP 1 One stop bit
3
Date Code 20130619 SEL Application Guide 2013-09
Table 5 ACSELERATOR QuickSet Settings
Settings Group Settings Example
Value Comments
Communication Parameters
Active Connection
Type Network
User configurable (Serial, Network, or Modem)
Host IP Address
192.168.0.2 User configurable
Must match SEL-735 IPADDR
Port Number 23 User configurable
Must match SEL-735 TPORT
File Transfer Option
Telnet User configurable
(FTP, Raw TCP, Telnet, SSH)
Table 6 ACSELERATOR TEAM Settings
Settings Group Settings Example
Value Comments
Communication Parameters
Active Connection
Type Network
User configurable (Serial, Network, or Modem)
Host IP Address
192.168.0.2 User configurable
Must match SEL-735 IPADDR
Port Number 23 User configurable
Must match SEL-735 TPORT
File Transfer Option
Telnet User configurable
(FTP, Raw TCP, Telnet, SSH)
CONFIGURE THE SEL-735 Use ACSELERATOR QuickSet with an Ethernet or serial connection to configure the SEL-735 LDP and VSSI settings.
Follow the appropriate steps based on what type of connection to the SEL-735 is available.
Connect Via Ethernet
Step 1
Use an Ethernet cable (not supplied) to connect Port 1 of the SEL-735 to the computer network interface card (NIC).
Step 2
Open ACSELERATOR QuickSet.
4
SEL Application Guide 2013-09 Date Code 20130619
Step 3
Select Communication > Parameters from the drop-down toolbar to open the Communication Parameters window (see Figure 1).
Figure 1 Communications Parameters Window
Step 4
Change Active Connection Type to Network.
Step 5
Enter the Host IP Address. This is the IP address assigned to the SEL-735.
Step 6
Ensure that the Port Number is 23 and that the File Transfer Option is Telnet.
5
Date Code 20130619 SEL Application Guide 2013-09
Step 7
Enter the Level One and Level Two passwords for the SEL-735. The default Level One Password is OTTER, and the default Level Two Password is TAIL. Note that the passwords are case sensitive.
Step 8
Click Apply to accept the changes.
Step 9
Click OK to close the window.
Step 10
The connection status window in the lower left-hand corner of the ACSELERATOR QuickSet main screen should show Connected (see Figure 2). If the status does not say Connected, refer to the SEL-735 instruction manual for communications troubleshooting.
Figure 2 Connection Status
Connect Via Serial
Step 1
Use an SEL-C662 USB to 9-pin serial cable (purchased separately) to connect Port 2 or Port 3 of the SEL-735 to a USB port on the computer.
Step 2
Open ACSELERATOR QuickSet.
Step 3
Select Communication > Parameters from the drop-down toolbar to open the Communication Parameters window (see Figure 3).
6
SEL Application Guide 2013-09 Date Code 20130619
Figure 3 Communications Parameters Window
Step 4
Change Active Connection Type to Serial.
Step 5
Select the serial device from the Device drop-down menu. Note that the computer may assign a different COM channel than shown.
Step 6
Ensure that the Data Speed, Data Bits, Stop Bits, and Parity options match the settings on the serial port used on the meter. The example in Figure 3 shows the default meter settings.
Step 7
Enter the Level One and Level Two passwords for the SEL-735. The default Level One Password is OTTER, and the default Level Two Password is TAIL. Note that the passwords are case sensitive.
7
Date Code 20130619 SEL Application Guide 2013-09
Step 8
Click Apply to accept the changes.
Step 9
Click OK to close the window.
Step 10
The connection status window in the lower left-hand corner of the ACSELERATOR QuickSet main screen should show Connected (see Figure 4). If the status does not say Connected, refer to the SEL-735 instruction manual for communications troubleshooting.
Figure 4 Connection Status
VIEW AND UPDATE THE SEL-735 SETTINGS
Step 1
Open ACSELERATOR QuickSet.
Step 2
Click on the Read Settings button on the ACSELERATOR QuickSet screen.
Step 3
Click on Events and Logging > Load Profile (see Figure 5) to open the LDP Profile Settings window for configuration. Make any necessary changes to the LDP recorder settings.
We recommend selecting only the minimum number of elements in the LDP recorder that ACSELERATOR TEAM is polling. This is to optimize the size of the ACSELERATOR TEAM database.
Figure 5 ACSELERATOR QuickSet Window
8
SEL Application Guide 2013-09 Date Code 20130619
Step 4
Click on Voltage Sag/Swell/Interruption. Make any necessary changes to the VSSI settings.
Step 5
Click on the Send Active Settings icon on the toolbar to open the Settings Group/Class Select window (see Figure 6). ACSELERATOR QuickSet will automatically select any modified settings groups in the window to download to the meter.
Figure 6 Settings Group/Class Select Window
Step 6
Click OK to send the settings.
Step 7
Select File > Close from the drop-down menu to exit to the main ACSELERATOR QuickSet screen.
CONFIGURE ACSELERATOR QUICKSET DATABASE Use ACSELERATOR QuickSet to add and configure the SEL-735.
Step 1
Click on the Device Manager icon on the ACSELERATOR QuickSet main screen to open the Log on to AcSELerator Database screen.
Step 2
Enter the proper credentials into the User Name and Password fields (see Figure 7).
Note: If this is the first time that the ACSELERATOR database has been used, then the default user is admin, and there is no default password.
Step 3
Click Log on.
9
Date Code 20130619 SEL Application Guide 2013-09
Figure 7 Log in to ACSELERATOR Database
Step 4
Folders are used to organize different connections. In this example, the SEL-735 meter is stored in the SEL Meters folder. Right-click on the SEL Meters folder in the Connection Explorer window and select Add > Device (see Figure 8).
Figure 8 Add Device in Connection Explorer
Step 5
Scroll down to select SEL-735 in the Select Device Type window (see Figure 9).
Figure 9 Device Selection Window
10
SEL Application Guide 2013-09 Date Code 20130619
Step 6
Click OK to accept the changes.
Step 7
Right-click on SEL-735 in the Connection Explorer and select Rename to enter a unique name for the meter (see Figure 10). In this example, the meter has been named One Meter.
Figure 10 Rename Connection
Step 8
Click OK to accept the name change.
CONFIGURE METERING POINTS Use ACSELERATOR QuickSet to configure a metering point and assign a device to that point. A metering point is a physical location where one or more meters are located. Descriptive naming, such as Building One, is used to clarify different points.
Step 1
In the Connection Explorer, expand the TEAM tree as shown in Figure 11.
11
Date Code 20130619 SEL Application Guide 2013-09
Figure 11 Select Metering Points
Step 2
Double-click on Metering Points.
Step 3
Click the Create button to open the Metering Points Wizard. Click Next to open the Metering Point Name window.
Step 4
Enter SEL One 735 in the Metering Point Name field. Ensure that the Enable Metering Point box is checked (see Figure 12).
Figure 12 Metering Point Name Window
12
SEL Application Guide 2013-09 Date Code 20130619
Step 5
Click the Next button to open the Metering Point Time Zone window.
Step 6
Scroll down, and select the time zone appropriate for the meter installation. Click Next to open the Metering Point Notes window.
Step 7
Enter any notes about the meter in the Notes field of the Metering Points Wizard. Click Next to open the Metering Points Wizard Complete window.
Step 8
Click Finish to complete the metering point setup process.
Step 9
Click the Edit button under the Devices Assigned box to open the Metering Point Device Assignment window.
Step 10
Click + to expand the SEL Meters tree, and select SEL One 735 (see Figure 13).
Figure 13 Metering Point Device Assignment Window
Step 11
Click >> to add the meter to the Devices Assigned box.
Step 12
Click OK to accept the changes and close the window.
13
Date Code 20130619 SEL Application Guide 2013-09
CONFIGURE ACSELERATOR TEAM Use ACSELERATOR QuickSet to configure ACSELERATOR TEAM to do the following:
Configure ACSELERATOR TEAM global options.
Create data collection connections.
Create polling processes.
Configure ACSELERATOR TEAM Global Options
Step 1
Double-click on TEAM in the Connection Explorer window.
Step 2
Select the Global Options tab (see Figure 14).
Figure 14 ACSELERATOR TEAM Global Options Window
14
SEL Application Guide 2013-09 Date Code 20130619
Step 3
Click on the Configure button to open the Global Options Wizard. Click Next to open the Date and Time Format window.
Step 4
Ensure the date and time formats are acceptable. Click Next to open the Date and Time Settings window.
Step 5
Ensure the date and time settings are acceptable, and click Next to open the Archive Directories window (see Figure 15).
Figure 15 Global Options Window
Step 6
Click … for the Event Report Directory (EARCHIVE) to open the Browse for Folder window. Select an appropriate folder location for the EARCHIVE files, and click OK.
Step 7
Click … for the User Command Directory (UARCHIVE) to open the Browse for Folder window. Select an appropriate folder location for the UARCHIVE files, and click OK. Click Next to open the Event Report File Name Template window.
Step 8
Ensure that the settings are acceptable, and click Next to open the User Command File Name Template window.
Step 9
Ensure that the settings are acceptable, and click Next to complete the wizard.
Step 10
Click Finish to complete the global options configuration process.
15
Date Code 20130619 SEL Application Guide 2013-09
Configure ACSELERATOR TEAM DDC (Device Data Collection) Connections
Step 1
Double-click on TEAM in the Connection Explorer window.
Step 2
Select the DDC Instances tab in the TEAM window to open the DDC Connections window (see Figure 16). The Host Name window will show the computer host name. If this window is empty, install or start the ACSELERATOR TEAM DDC service.
Figure 16 ACSELERATOR TEAM DDC Instances Tab
Step 3
In the DDC Connections window, click the Add button to add an ACSELERATOR TEAM DDC connection.
Step 4
Click Next in the DDC Wizard window.
Step 5
Select Telnet for the Communication Method, and then click Next (see Figure 17).
16
SEL Application Guide 2013-09 Date Code 20130619
Figure 17 DDC Wizard
Step 6
Click Next in the Enable Listening window to continue without enabling listening.
Step 7
Click Finish to complete the configuration.
Configure an ACSELERATOR TEAM Polling Process
Use ACSELERATOR QuickSet to enable the meters and configure the communications channels for the polling processes.
Step 1
Double-click on SEL One 735 in the Connection Explorer window to open the Device window (see Figure 18).
Figure 18 Meter Device Tab
Step 2
Click on the Edit button on the lower right-hand side of the screen to modify the Device parameters.
17
Date Code 20130619 SEL Application Guide 2013-09
Step 3
Check the In Service box.
Step 4
Enter the device passwords in the Password Fields (see Figure 19). Note that the default passwords (OTTER for ACC and TAIL for 2AC) automatically appear in these fields.
Figure 19 Device Passwords
Step 5
Click the Connection tab in the Device window (see Figure 20).
Figure 20 Meter Connection Tab
Step 6
Select Network in the Connection Type drop-down box.
Step 7
Enter the SEL-735 IP address, 192.168.0.2 in this example, in the Host IP Address field. Ensure that the Port Number is 23 and that the File Transfer Option is set to Telnet.
18
SEL Application Guide 2013-09 Date Code 20130619
Step 8
Click on the TEAM tab in the Device window (see Figure 21).
Figure 21 ACSELERATOR TEAM Communications Channel Selection
Step 9
Click the Add button under the Communication Channel box to open the Server Configuration Wizard.
Step 10
Click Next to open the Service Selection window (see Figure 22). Select the available Host Name, and click Next to open the Service Connection window.
Figure 22 ACSELERATOR TEAM Service Selection Window
19
Date Code 20130619 SEL Application Guide 2013-09
Step 11
Ensure the Available box is checked, and click Next (see Figure 23).
Figure 23 Network Service Connection Window
Step 12
Click Finish to complete the server configuration process.
Configure an ACSELERATOR TEAM Polling Job
Use ACSELERATOR QuickSet to configure metering points, polling profiles, and job frequencies.
Step 1
Click the TEAM tab in the Device window. Click the Add button under the Polling Jobs box (see Figure 24) to open the Polling Job Assignment Wizard.
20
SEL Application Guide 2013-09 Date Code 20130619
Figure 24 Add Polling Jobs
Step 2
Click Next to open the Service Selection window. Select the desired service from the Service drop-down window (see Figure 25). Click Next to open the Polling Job Selector window.
Figure 25 Polling Job Service Selection
Step 3
Select Profile Collection in the Job drop-down box (see Figure 26). Ensure that the Enable Job box is checked.
21
Date Code 20130619 SEL Application Guide 2013-09
Figure 26 Polling Job Selection
Step 4
Click Next to open the Device Recorders Configuration window.
Step 5
Click + to expand the Metering Point Device tree (see Figure 27). Select the desired number of recorder channels for the polling job. Click Next to open the Metering Point Configuration window.
We recommend selecting only the minimum number of profile recorders required to poll the needed data. Doing so optimizes the size of the ACSELERATOR TEAM database on the computer or server.
The date shown in the Beginning Time Stamp column is the earliest date that ACSELERATOR TEAM will collect data from the device. To poll older data, change the beginning time stamp to include data from the period required.
Figure 27 Polling Job Device Recorders Configuration
22
SEL Application Guide 2013-09 Date Code 20130619
Step 6
Click Next to open the Polling Frequency window (see Figure 28).
Step 7
Select an appropriate polling frequency. Click Next. We recommend selecting the longest acceptable polling frequency. This is usually defined by the type of report needed. For instance, use the Monthly polling frequency if the data are only gathered once a month. Doing so optimizes the size of the ACSELERATOR TEAM database on the computer or server.
Figure 28 Polling Frequency Window
Step 8
Select an appropriate polling interval in the window. Click Next to complete the Polling Job Wizard.
Step 9
Click Finish to complete the polling job configuration process.
Step 10
Click the Save icon in the toolbar to save all the changes.
CONFIGURE REPORTING Use a Microsoft Excel spreadsheet to collect the polled LDP and VSSI data from the ACSELERATOR TEAM database and organize the data in a report.
Create and View an LDP Data Report
Step 1
Open a Microsoft Excel spreadsheet, and click on the Office button. Select New to open the New Workbook window.
23
Date Code 20130619 SEL Application Guide 2013-09
Step 2
Select My Templates to open the Templates window.
Step 3
Select TEAM LDP, and click OK.
Step 4
In the Database Configuration cells, ensure the Hostname or IP is 127.0.0.1 and the Port is 5434.
Step 5
Click Refresh to display the Metering Points and Channels available for reporting.
Step 6
In the Report Configuration area, select the SEL One metering point (see Figure 29). This will display the channels available for reporting. Select the channels as shown in the Channels box.
Figure 29 Report Configuration
Step 7
Check the Scale LDP Data to Primary box to display the reported data in primary values.
Step 8
Check the Generate Load Profile Report box.
24
SEL Application Guide 2013-09 Date Code 20130619
Step 9
Select the Start Date and End Date in the calendar boxes.
Step 10
Click Fill New Sheet to generate the LDP report.
Step 11
The LDP Report Generator will create two new spreadsheet tabs: Load Profile 1 and LDP Report 2. The Load Profile 1 tab displays collected data and LDP information (see Figure 30).
Figure 30 Example LDP Profile Information
Step 12
Click on the LDP Report 2 tab to display a graph of the LDP data (see Figure 31).
25
Date Code 20130619 SEL Application Guide 2013-09
Figure 31 Example LDP Data Report Screen
Create and View a VSSI Data Report
Use a Microsoft Excel spreadsheet to collect VSSI data from the meter and create two VSSI reports.
Step 1
Open a Microsoft Excel spreadsheet, and click on the Office button. Select New to open the New Workbook window.
Step 2
Select My Templates.
Step 3
Select the TEAM VSSI Excel Template, and click OK.
Step 4
In the Database Configuration cells, ensure the Hostname or IP is 127.0.0.1 and the Port is 5434.
26
SEL Application Guide 2013-09 Date Code 20130619
Step 5
Check the Include Device in VSSI Query and Disable Configuration Form boxes (see Figure 32). Checking the Include Device in VSSI Query ensures that only the selected device for the metering point is shown. Leaving the box unchecked will include all data from all devices assigned to the metering point. Checking the Disable Configuration Form box prevents accidental changes to date selections. The report display is not affected by this setting.
Figure 32 VSSI Detail Sheet
Step 6
Select the Start Date and End Date in the calendar boxes.
Step 7
Click Fill New Sheet with VSSI Details to create a VSSI Detail Report tab in the worksheet (see Figure 33).
27
Date Code 20130619 SEL Application Guide 2013-09
Figure 33 Example VSSI Detail Report
Step 8
Click Fill New Sheet with VSSI Summary to create a VSSI Summary Report tab in the worksheet (see Figure 34).
Figure 34 Example VSSI Summary Report
CONCLUSION This application guide describes how to use ACSELERATOR TEAM with an SEL-735 to retrieve and store data and how to use a Microsoft Excel spreadsheet to collect LDP and VSSI data and report the data in a spreadsheet.
28
SEL Application Guide 2013-09 Date Code 20130619
FACTORY ASSISTANCE We appreciate your interest in SEL products and services. If you have questions or comments, please contact us at:
Schweitzer Engineering Laboratories, Inc. 2350 NE Hopkins Court Pullman, WA 99163-5603 USA Telephone: +1.509.332.1890 Fax: +1.509.332.7990 www.selinc.com • [email protected]
© 2013 by Schweitzer Engineering Laboratories, Inc. All rights reserved.
All brand or product names appearing in this document are the trademark or registered trademark of their respective holders. No SEL trademarks may be used without written permission.
SEL products appearing in this document may be covered by U.S. and Foreign patents.
*AG2013-09*