STATE OF NEBRASKA 501 BUILDING RENOVATION CONSTRUCTION DOCUMENTS REVIEW SET 5/08/2017 501 SOUTH 14TH STREET LINCOLN, NEBRASKA 68510 PRINT SHOP BUILDOUT & STRUCTURAL DEFICIENCY RENOVATION INDEX OF DRAWINGS Architecture Engineering Planning Interiors © , DLR Group inc., a Nebraska corporation, ALL RIGHTS RESERVED Revisions 5/8/2017 2:29:41 PM C:\Revit\10-16206-00_AR_2016_Central_sburgess.rvt 10-16206-00 5/08/17 STATE OF NEBRASKA 501 BUILDING RENOVATION COVER SHEET 0.0 2017 PRINTSHOP BUILD OUT & STRUCTURAL DEFICIENCY RENOVATION .GENERAL BP1. 0.0 COVER SHEET 0.1. SYMBOLS AND ABBREVIATIONS .PLUMBING BP1. DP0.1A UNDERGROUND PLUMBING DEMOLITION PLAN - AREA A DP0.1B UNDERGROUND PLUMBING DEMOLITION PLAN - AREA B DP1.0A PLUMBING DEMOLITION PLAN, LOWER LEVEL AREA A DP1.0B PLUMBING DEMOLITION PLAN, LOWER LEVEL AREA B P0.1A UNDERGROUND PLUMBING PLAN, LOWER LEVEL AREA A P0.1B UNDERGROUND PLUMBING PLAN, LOWER LEVEL AREA B P1.0A PLUMBING PLAN, LOWER LEVEL AREA A P1.1B PLUMBING PLAN, LOWER LEVEL AREA B .ELECTRICAL BP1. E0.0 ELECTRICAL SYMBOLS AND ABBREVIATIONS DE1.0A ELECTRICAL DEMOLITION PLAN, LOWER LEVEL - AREA A DE1.0B ELECTRICAL DEMOLITION PLAN, LOWER LEVEL - AREA B DE1.1B ELECTRICAL DEMOLITION PLAN, FIRST FLOOR E1.0A LIGHTING PLAN, LOWER LEVEL - AREA A E1.0B LIGHTING PLAN, LOWER LEVEL - AREA B E2.0A POWER PLAN, LOWER LEVEL - AREA A E2.0B POWER PLAN, LOWER LEVEL - AREA B E3.0A SPECIAL SYSTEMS PLAN, LOWER LEVEL - AREA A E3.0B SPECIAL SYSTEMS PLAN, LOWER LEVEL - AREA B E5.1 DEMO ONE-LINE DIAGRAM E5.2 NEW ONE-LINE DIAGRAM E6.1 ELECTRICAL DETAILS E7.1 ELECTRICAL SCHEDULES .FIRE PROTECTION BP1. DFP1.0A FIRE PROTECTION DEMOLITION, LOWER LEVEL - AREA A DFP-1.0B FIRE PROTECTION DEMOLITION, LOWER LEVEL - AREA B FP-1.0A FIRE PROTECTION, LOWER LEVEL - AREA A FP-1.0B FIRE PROTECTION, LOWER LEVEL - AREA B .STRUCTURAL BP1. S0.1 STRUCTURAL NOTES S1.0A FOUNDATION PLAN, BASEMENT LEVEL - AREA A S1.0B FOUNDATION PLAN, BASEMENT LEVEL - AREA B S2.1B FRAMING PLAN, FIRST LEVEL - AREA B S2.2B FRAMING PLAN, SECOND LEVEL - AREA B S3.1 STRUCTURAL DETAILS I, STEPHEN H. BURGESS, AM THE COORDINATING PROFESSIONAL FOR THE NEBRASKA STATE 501 BUILDING RENOVATION, PRINTSHOP BUILD OUT AND STRUCTURAL DEFICIENCY RENOVATION PROJECT. .ARCHITECTURAL BP1. CP1.1 CODE PLANS DA1.0A DEMOLITION PLAN, LOWER LEVEL-AREA A DA1.0B DEMOLITION PLAN, LOWER LEVEL -AREA B PH1.1 LOWER LEVEL PHASING PLAN, LOWER LEVEL - AREAS A& B PH1.2 BREAK OUT COST PLAN, LOWER LEVEL - AREAS A & B A0.1 ROOM FINISH SCHEDULE, GENERAL NOTES, WALL TYPES & DETAILS A1.0A FLOOR PLAN, LOWER LEVEL -AREA A A1.0B FLOOR PLAN, LOWER LEVEL -AREA B A3.0A REFLECTED CEILING PLAN, LOWER LEVEL -AREA A A3.0B REFLECTED CEILING PLAN, LOWER LEVEL -AREA B A9.1 DOOR AND FRAME SCHEDULE A11.1 CASEWORK, LARGE SCALE PLANS & INTERIOR ELEVATIONS .MECHANICAL BP1. M0.0 MECHANICAL SYMBOLS AND ABBREVIATIONS DM1.0A HVAC DEMOLITION PLAN, LOWER LEVEL - AREA A DM1.0B HVAC DEMOLITION PLAN, LOWER LEVEL - AREA B DM2.0A HVAC PIPING DEMOLITION PLAN, LOWER LEVEL - AREA A DM2.0B HVAC PIPING DEMOLITION PLAN, LOWER LEVEL - AREA B M1.0A HVAC PLAN, LOWER LEVEL - AREA A M1.0B HVAC PLAN, LOWER LEVEL - AREA B M2.0A HVAC PIPING PLAN, LOWER LEVEL - AREA A M2.0B HVAC PIPING PLAN, LOWER LEVEL - AREA B M4.1 MECHANICAL DETAILS M5.1 MECHANICAL SCHEDULES

Upload: duongthuy

Post on 28-Apr-2018

245 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

STATE OF NEBRASKA 501 BUILDING RENOVATION

CONSTRUCTION DOCUMENTS REVIEW SET

5/08/2017

501 SOUTH 14TH STREETLINCOLN, NEBRASKA 68510

PRINT SHOP BUILDOUT & STRUCTURAL DEFICIENCY RENOVATION

INDEX OF DRAWINGS

Arch

itect

ure

Eng

inee

ring

Pla

nnin

g In

terio

rs

©

, DLR

Gro

up in

c., a

Neb

rask

a co

rpor

atio

n, A

LL R

IGH

TS R

ESER

VED

Revis

i ons

5/8/

2017

2:2

9:41

PM

C:\R

evit\

10-1

6206

-00_

AR_2

016_

Cen

tral_

sbur

gess

.rvt

10-1

6206

-00

5/08

/17

STAT

E O

F N

EBR

ASKA

501

BU

ILD

ING

REN

OVA

TIO

NC

OVE

R S

HEE

T0.

0

2017

PRIN

TSH

OP

BUIL

D O

UT

& ST

RU

CTU

RAL

DEF

ICIE

NC

Y R

ENO

VATI

ON

.GENERAL BP1.

0.0 COVER SHEET0.1. SYMBOLS AND ABBREVIATIONS

.PLUMBING BP1.

DP0.1A UNDERGROUND PLUMBING DEMOLITION PLAN - AREA ADP0.1B UNDERGROUND PLUMBING DEMOLITION PLAN - AREA BDP1.0A PLUMBING DEMOLITION PLAN, LOWER LEVEL AREA ADP1.0B PLUMBING DEMOLITION PLAN, LOWER LEVEL AREA B

P0.1A UNDERGROUND PLUMBING PLAN, LOWER LEVEL AREA AP0.1B UNDERGROUND PLUMBING PLAN, LOWER LEVEL AREA BP1.0A PLUMBING PLAN, LOWER LEVEL AREA AP1.1B PLUMBING PLAN, LOWER LEVEL AREA B

.ELECTRICAL BP1.

E0.0 ELECTRICAL SYMBOLS AND ABBREVIATIONS

DE1.0A ELECTRICAL DEMOLITION PLAN, LOWER LEVEL - AREA ADE1.0B ELECTRICAL DEMOLITION PLAN, LOWER LEVEL - AREA BDE1.1B ELECTRICAL DEMOLITION PLAN, FIRST FLOOR

E1.0A LIGHTING PLAN, LOWER LEVEL - AREA AE1.0B LIGHTING PLAN, LOWER LEVEL - AREA B

E2.0A POWER PLAN, LOWER LEVEL - AREA AE2.0B POWER PLAN, LOWER LEVEL - AREA B

E3.0A SPECIAL SYSTEMS PLAN, LOWER LEVEL - AREA AE3.0B SPECIAL SYSTEMS PLAN, LOWER LEVEL - AREA B

E5.1 DEMO ONE-LINE DIAGRAME5.2 NEW ONE-LINE DIAGRAM

E6.1 ELECTRICAL DETAILS

E7.1 ELECTRICAL SCHEDULES

.FIRE PROTECTION BP1.

DFP1.0A FIRE PROTECTION DEMOLITION, LOWER LEVEL - AREA ADFP-1.0B FIRE PROTECTION DEMOLITION, LOWER LEVEL - AREA B

FP-1.0A FIRE PROTECTION, LOWER LEVEL - AREA AFP-1.0B FIRE PROTECTION, LOWER LEVEL - AREA B

.STRUCTURAL BP1.

S0.1 STRUCTURAL NOTES

S1.0A FOUNDATION PLAN, BASEMENT LEVEL - AREA AS1.0B FOUNDATION PLAN, BASEMENT LEVEL - AREA B

S2.1B FRAMING PLAN, FIRST LEVEL - AREA BS2.2B FRAMING PLAN, SECOND LEVEL - AREA B

S3.1 STRUCTURAL DETAILS

I, STE

PHEN

H. B

URGE

SS, A

M TH

E CO

ORDI

NATI

NGPR

OFES

SION

AL F

OR T

HE N

EBRA

SKA

STAT

E 50

1 BUI

LDIN

GRE

NOVA

TION

, PRI

NTSH

OP B

UILD

OUT

AND

STR

UCTU

RAL

DEFI

CIEN

CY R

ENOV

ATIO

N PR

OJEC

T.

.ARCHITECTURAL BP1.

CP1.1 CODE PLANSDA1.0A DEMOLITION PLAN, LOWER LEVEL-AREA ADA1.0B DEMOLITION PLAN, LOWER LEVEL -AREA BPH1.1 LOWER LEVEL PHASING PLAN, LOWER LEVEL - AREAS A& BPH1.2 BREAK OUT COST PLAN, LOWER LEVEL - AREAS A & B

A0.1 ROOM FINISH SCHEDULE, GENERAL NOTES, WALL TYPES &DETAILS

A1.0A FLOOR PLAN, LOWER LEVEL -AREA AA1.0B FLOOR PLAN, LOWER LEVEL -AREA B

A3.0A REFLECTED CEILING PLAN, LOWER LEVEL -AREA AA3.0B REFLECTED CEILING PLAN, LOWER LEVEL -AREA B

A9.1 DOOR AND FRAME SCHEDULEA11.1 CASEWORK, LARGE SCALE PLANS & INTERIOR ELEVATIONS

.MECHANICAL BP1.

M0.0 MECHANICAL SYMBOLS AND ABBREVIATIONS

DM1.0A HVAC DEMOLITION PLAN, LOWER LEVEL - AREA ADM1.0B HVAC DEMOLITION PLAN, LOWER LEVEL - AREA BDM2.0A HVAC PIPING DEMOLITION PLAN, LOWER LEVEL - AREA ADM2.0B HVAC PIPING DEMOLITION PLAN, LOWER LEVEL - AREA B

M1.0A HVAC PLAN, LOWER LEVEL - AREA AM1.0B HVAC PLAN, LOWER LEVEL - AREA BM2.0A HVAC PIPING PLAN, LOWER LEVEL - AREA AM2.0B HVAC PIPING PLAN, LOWER LEVEL - AREA B

M4.1 MECHANICAL DETAILSM5.1 MECHANICAL SCHEDULES

Page 2: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

B to B BACK TO BACKBBO BOILER BLOW OFFBC BALANCING COCKBCMU BURNISHED CONCRETE MASONRY UNITBD BOARDBD BACK DRAFT DAMPERBET BETWEENBFP BACKFLOW PREVENTORBFR BELOW FLOORBF BOILER FEEDBFV BUTTERFLY VALVEBHP BREAK HORSE POWERBKR BREAKERBL BUILDING LINEBLDG BUILDINGBLK BLOCKBLKG BLOCKINGBLKHD BULKHEADBM BEAMBM BENCH MARKBOD BOTTOM OF DUCTBOF BOTTOM OF FOOTINGBOTT BOTTOMBRDG BRIDGINGBRG BEARINGBRKT BRACKETBSMT BASEMENTBT BATH TUBBTU BRITISH THERMAL UNITBTUH BRITISH THERMAL UNIT PER HOURBUR BUILT UP ROOFINGBV BALL VALVE

C CONDENSER WATERC CONDUITCA COMBUSTION AIRCAB CABINETCANT CANTILEVERCAP CAPACITYCAS CASINGCBD CHALKBOARDCD CONDENSATE DRAINCCTV CLOSED CIRCUIT TELEVISIONCE COVER ELEVATIONCEM CEMENTCENT CENTRIFUGALCER CERAMICCF CUBIC FEETCFH CUBIC FEET PER HOURCFM CUBIC FEET PER MINUTECG CORNER GUARDCH CHANNELCI CAST IRONCI CURB INLETCIP CAST IN PLACECIP CAST IRON PIPECIRC CIRCULATINGCJ CONTROL JOINTCJA CONTROL JOINT ABOVECKT CIRCUITCKT BK CIRCUIT BREAKERCL CENTERLINECL CIRCUIT LINECLG CEILINGCLOS CLOSETCLR CLEARCM CEILING MOUNTEDCMP CORRUGATED METAL PIPECMU CONCRETE MASONRY UNITCO CLEAN OUTCO CONDUIT ONLYCO2 CARBON DIOXIDECOL COLUMNCOM COMMONCOMB COMBINATIONCOMM COMMUNICATIONSCOMP COMPOSITECOMP COMPRESSOR UNITCOMPR COMPRESSIBLECONC CONCRETECONF CONFERENCECONFIG CONFIGURATIONCONN CONNECTCONN CONNECTIONCONST CONSTRUCTIONCONT CONTINUOUSCONTR CONTRACTOR OR CONTRACTCONV CONVECTORCORR CORRIDORCP CONDENSER PUMPCP COVER PLATECPS CYCLES PER SECONDCPT CARPETCR CONDENSER WATER RETURN

CR CORROSION RESISTANTCS COUNTERSINKCS COMBINATION SEWERCS CONDENSER WATER SUPPLYCSK COUNTERSUNKCSMU CALCIUM SILICATE MASONRY UNITCSP COMBINATION STANDPIPECSTJ CONSTRUCTION JOINTCSWK CASEWORKCT COOLING TOWERCT CERAMIC TILECT CURRENT TRANSFORMERCTR CENTERCU COPPERCU CONDENSING UNITCU CUBICCU COMBINATION UNITCUH CABINET UNIT HEATERCW COLD WATERCV CONDOM VENDORCWR CHILLED WATER RETURNCWS CHILLED WATER SUPPLYCY CUBIC YARDCYL CYLINDER

D DRAIND DEPTHD DATADB DRY BULBDB DECIBELDBA DEFORMED BAR ANCHORDBL DOUBLEDC DIRECT CURRENTDC DUST COLLECTORDCJ DUMMY CONTROL JOINTd PENNY (AS NAIL 10D)DDC DIRECT DIGITAL CONTROLDE DEIONIZED WATERDEG DEGREEDEPR DEPRESS(ION)(ED)DEPT DEPARTMENTDET DETENTIONDF DRINKING FOUNTAINDFR DIESEL FUEL RETURNDFS DIESEL FUEL SUPPLYDFV DIESEL FUEL VENTDG DOOR GRILLEDH DUCT HEATERDI DISTILLED WATERDI DUCTILE IRONDIA DIAMETERDIAG DIAGONALDIFF DIFFUSERDIM DIMENSIONDISC SW DISCONNECT SWITCHDISC DISCONNECTDISCH DISCHARGEDISTR DISTRIBUTIONDL DEAD LOADDM DAMPER MOTORDMPR DAMPERDN DOWNDN DOWNSPOUT NOZZLEDO OR " DITTODPFG DAMPROOFINGDPS DIFFERENTIAL PRESSURE SWITCHDR DOORDR DRAINDS DOWNSPOUTDS DISTILLED WATERDSP DRY STANDPIPEDTL DETAILDTR DUCT THRU ROOFDW DISHWASHERDWG DRAWINGDWL DOWELDWR DRAWERDXS DOUBLE EXTRA STRONG

E EASTEA EACHEA EXHAUST AIREAT ENTERING AIR TEMPERATUREEB EXPANSION BOLTEC ELECTRICAL CONTRACTOREDH ELECTRIC DUCT HEATEREE EACH ENDEER ENERGY EFFICIENCY RATIOEEW EMERGENCY EYEWASHEEWS EMERGENCY EYEWASH/SHOWEREF EACH FACEEF EXHAUST FANEFF EFFICIENCYEH ELECTRICAL HEATEREIFS EXTERIOR INSULATION AND FINISH SYSTEMEJ EXPANSION JOINTEL ELEVATIONELAS ELASTOMERICELEC ELECTRIC(AL)ELEV ELEVATOREMER EMERGENCYEMD ESTIMATED MAXIMUM DEMANDEMT ELECTRICAL METALLIC TUBINGEMV EMERGENCY MIXING VALVEENCL ENCLOSUREENTR ENTRANCEEOMD END OF MAIN DRIPEP ELECTRO-PNEUMATICEP EXPLOSION PROOFEPO EMERGENCY POWER OFFERF EPOXY RESIN FLOORINGEQ EQUALEQUIP EQUIPMENTER EXHAUST REGISTERES EMERGENCY SHOWERES EXTRA STRONGESP EXTERNAL STATIC PRESSUREEST ESTIMATEET EXPANSION TANKEW EACH WAYEWC ELECTRIC WATER COOLEREWH ELECTRIC WATER HEATEREWT ENTERING WATER TEMPERATUREEXC EXCAVATEEXH EXHAUSTEXIST EXISTINGEXP EXPANSIONEXP EXPOSEDEXPL EXPLOSIONEXT EXTERIOR

F FAHRENHEITF FIRELINEF FURNACEFA FIRE ALARMFA FRESH AIRFAB FABRICATED

FB FACE BRICKFC FOOT CANDLEFCMU FLUTED CONCRETE MASONRY UNITFCO FLOOR CLEAN OUTFCU FAN COIL UNITFD FIRE DAMPERFD FLOOR DRAINFDC FIRE DEPARTMENT CONNECTIONFDN FOUNDATIONFDR FEEDERFE FIRE EXTINGUISHERFEC FIRE EXTINGUISHER CABINETFF FINISH FLOORFFE FINISH FLOOR ELEVATIONFH FIRE HYDRANTFHC FIRE HOSE CABINETFIG FIGUREFIN FINISHFIX FIXTUREFL FLOORFLASH FLASHINGFLEX FLEXIBLEFLUOR FLUORESCENTFLG FLOORINGFLM FULL LENGTH MIRRORFM FACTORY MUTUALFM FIRE MAINFME FLOW MEASURING EQUIPMENTFO FACE OFFO FINISH OPENINGFOC FACE OF CONCRETEFOF FACE OF FINISHFOF FUEL OIL FILLFOM FACE OF MASONRYFOR FUEL OIL RETURNFOS FACE OF STUDFOS FUEL OIL SUPPLYFOV FUEL OIL VENTFOW FACE OF WALLFP FIREPROOFINGFPD FIRE PUMP DISCHARGEFPM FEET PER MINUTEFR FIRE RESISTIVEFR FRAMEFRP FIBERGLASS REINFORCED PANELFS FLOOR SINKFS FLOW SWITCHFSD FIRE/SMOKE DAMPERFSS FOLDING SHOWER SEATFT FEET (FOOT)FT FIN TUBEFT FLOW TRANSMITTERFTG FOOTINGFUT FUTUREFVC FIRE VALVE CABINETFWC FABRIC WALL COVERINGG GRILLEG NATURAL GASGA GAUGEGAL GALLONGALV GALVANIZEDGB GRAB BARGC GENERAL CONTRACTORGCO GRADE CLEAN OUTGCMU GLAZED CONCRETE MASONRY UNITGD GARBAGE DISPOSALGEN GENERALGEN GENERATORGFA GROSS FLOOR AREAGFI GROUND FAULT INTERRUPTERGFRC GLASS FIBER REINFORCED CONCRETEGHR GLYCOL-WATER HEATING RETURNGHS GLYCOL-WATER HEATING SUPPLYGI GALVANIZED IRONGL GLUE LAMINATEDGL GLASSGMU GLASS MASONRY UNITGND GROUNDGOVT GOVERNMENTGPH GALLONS PER HOURGPM GALLONS PER MINUTEGR GUARD RAILGR GRADEGR GRILLEGRC GLAVANIZED RIGID CONDUITGRC GLASS REINFORCED CONCRETEGRGP GLASS REINFORCED GYPSUM PLASTERGRS GALVANIZED RIGID STEELGS GASOLINEGV GATE VALVEGW GREASE WASTEGWB GYPSUM WALL BOARDGYP GYPSUMH HEIGHTH 1E HOOK ONE ENDHB HOSE BIBHC HANDICAPHC HOLLOW COREHCB HANDICAP BENCHHCR HOT / CHILLED WATER RETURNHCS HOT / CHILLED WATER SUPPLYHD HAND DRYER OR HAIR DRYERHDBD HARDBOARDHDR HEADERHDWD HARDWOODHDWR HARDWAREHEV HOSE END VALVEHID HIGH INTENSITY DISCHARGEHM HOLLOW METALHOA HAND OFF AUTOMATICHORIZ HORIZONTALHP HEAT PUMPHP HIGH PRESSUREHP HORSEPOWERHPR HIGH PRESSURE STEAM RETURNHPS HIGH PRESSURE SODIUMHPS HIGH PRESSURE STEAM SUPPLYHR HANDRAILHR HOURHS HEADSTUDHSS HOLLOW STRUCTURAL SECTIONHSTR HIGH STRENGTHHT HEIGHTHTG HEATINGHTR HEATERHTWR HIGH TEMP HOT WATER RETURNHTWS HIGH TEMP HOT WATER SUPPLYHUM HUMIDIFIERHV HEATING VENTILATING UNITHVAC HEATING VENTILATING AND AIR CONDITIONINGHW DOMESTIC HOT WATERHWC DOMESTIC HOT WATER RECIRCULATINGHWR LOW TEMP HOT WATER RETURNHWS LOW TEMP HOT WATER SUPPLYHX HEAT EXCHANGERHZ HERTZ

JAN JANITORJB JUNCTION BOXJCT JUNCTIONJST JOISTJFB JOINT FILLER BOARDJT JOINTKCJ KEYED CONSTRUCTION JOINTKCP KEENE'S CEMENT PLASTERKD KNOCKDOWNKH KITCHEN HOODKHE KITCHEN HOOD EXHAUST FANKHS KITCHEN HOOD SUPPLY FANKIT KITCHENKO KNOCKOUTKS KITCHEN SINKKV KILOVOLTKVA KILOVOLT AMPERESKVAR KILOVOLT AMPERES REACTIVEKW KILOWATTKWH KILOWATT HOURL ANGLEL LAVATORYLA LABORATORY COMPRESSED AIRLAB LABORATORYLAM LAMINATE(D)LAT LEAVING AIR TEMPERATURELAV LAVATORYLB POUNDLBR LUMBERLBS POUNDSLDG LOADINGLF LINEAR FOOT (FEET)LG LENGTH (LONG)LIN LINEARLINO LINOLEUMLKR LOCKERLL LIVE LOADLLH LONG LEG HORIZONTALLLV LONG LEG VERTICALLOC LOCATIONLONG LONGITUDINALLOX LIQUID OXYGENLPG LIQUEFIED PETROLEUM GASLPR LOW PRESSURE STEAM RETURNLPS LOW PRESSURE STEAM SUPPLYLR LIVING ROOMLS LAWN SPRINKLERLSC LIFE SAFETY CODELT LIGHTLTD LINED TRANSFER DUCTLTG LIGHTINGLV LOUVERLV LABORATORY VACUUMLW LONG WAYLWT LEAVING WATER TEMPERATURE

M THOUSANDMA MIXED AIRMA MEDICAL COMPRESSED AIRMAC MACHINEMAG MAGNETICMAINT MAINTENANCEMAN MANUALMAS MASONRYMATL MATERIALMAU MAKEUP AIR UNITMAV MANUAL AIR VENTMAX MAXIMUMMB MACHINE BOLTMB MOP BASINMBD MARKER BOARDMBH THOUSAND BTU PER HOURMBTUH THOUSAND BTU PER HOURMC MECHANICAL CONTRACTORMC MEDICINE CABINETMCA MINIMUM CIRCUIT AMPSMCB MAIN CIRCUIT BREAKERJMCM THOUSAND CIRCULAR MILLSMD MANUAL VOLUME DAMPERMDO MEDIUM DENSITY OVERLAYMECH MECHANICALMEMB MEMBRANEMET METALMEZZ MEZZANINEMFR MANUFACTURERMFRG MANUFACTURINGMG MOTOR GENERATORMH MANHOLEMH METAL HALIDEMH MOP HOLDERMIN MINIMUMMISC MISCELLANEOUSML MOTORIZED LOUVERMLDG MOLDINGMLO MAIN LUGS ONLYMLWK MILLWORKMO MASONRY OPENINGMPG MEDIUM PRESSURE GASMPR MEDIUM PRESSURE STEAM RETURNMPS MEDIUM PRESSURE STEAM SUPPLYMR MIRRORMR/S MIRROR WITH SHELFMS MAGNETIC STARTERMTD MOUNTEDMTG MOUNTINGMTL METALMTWR MEDIUM TEMP HOT WATER RETURNMTWS MEDIUM TEMP HOT WATER SUPPLYMUL MULLIONMV MERCURY VAPORMV MEDICAL VACUUMMW MARKER WALL

N NITROGENN NORTHN2O NITROUS OXIDEN/A NOT APPLICABLE

P PAINTP POLEP/T PRESSURE/TEMPERATURE TEST PORTP PUMPPA PUBLIC ADDRESSPAN B PANIC BOLTPAR PARALLELPB PARTICLE BOARDPB PULL BOXPB PUSH BUTTONPBS PUSH BUTTON STATIONPC PRECASTPC PUMPED CONDENSATEPCD PAPER CUP DISPENSERPCF POUNDS PER CUBIC FOOTPCT PORCELAIN CERAMIC TILEPD PRESSURE DROPPD PUMP DISCHARGEPDI PLUMBING & DRAINAGE INSTITUTEPENT PENTHOUSEPERF PERFORATEDPERP PERPENDICULARPF POWER FACTORPG PRESSURE GAGEPH PHASEPI POINT OF INTERSECTIONPI PRESSURE INDICATORPIC PORTABLE INSTRUMENT CONNECTIONPIV POST INDICATOR VALVEPL PLACE(S)PL PLATEPLAM;PL PLASTIC LAMINATEPLAS PLASTERPLBG PLUMBINGPLYWD PLYWOODPNEU PNEUMATICPNL PANELPOC POINT OF CONNECTIONPORC PORCELAINPPM PARTS PER MILLIONPR PAIRPREFAB PREFABRICATEDPROJ PROJECTIONPRV PRESSURE REDUCING VALVEPS PIPE SUPPORTPS PROJECTION SCREENPSF POUNDS PER SQUARE FOOTPSI POUNDS PER SQUARE INCHPSV PRESSURE SAFETY VALVEPT PLASTER TRAPPT POINTPT POTENTIAL TRANSFORMERPTD PAPER TOWEL DISPENSERPTD/R COMBINATION TOWEL DISPENSER/RECEPTACLEPTN PARTITIONPVC POLYVINYL CHLORIDEPVI POINT OF VERTICAL INTERSECTIONPVT POINT OF VERTICAL TANGENCYPWL SOUND POWER LEVELPWR POWER

QT QUARRY TILEQTR RND QUARTER ROUNDR RISERRA RETURN AIRRAD RADIATORRAD or R RADIUSRB RUBBER BASERC REMOVE CONTROLRCP REFLECTED CEILING PLANRCP REINFORCED CONCRETE PIPERCU RECIPROCATING CHILLER JOINTRD ROOF DRAINRD REFRIGERANT DISCHARGERECP RECEPTACLEREF REFERENCEREFL REFLECTEDREFR REFRIGERANTREFR REFRIGERATORREG REGISTERREINF REINFORCEMENTREM REMOVABLEREQ(D) REQUIRE(D)RESIL RESILIENTRET RETAINING (WALL)REV REVISIONSRF RETURN FANRF RUBBER FLOORRFM RECESSED FLOOR MATRH RELATIVE HUMIDITYRH RELIEF HOODRHC REHEAT COILRH ROBE HOOKRHG REFRIGERANT HOT GASRI&C ROUGH IN AND CONNECTRIJS RISE IN JOIST SPACERL REFRIGERANT LIQUIDRM ROOMRND ROUNDRO ROUGH OPENING

S SINKS SANITARY SEWERS SOAP DISHS SOUTHS SPRINKLER LINESA SHOCK ABSORBERSA SUPPLY AIRSAN SANITARY WASTESC SECURITYSC SOLID CORESC SHOWER CURTAINSC SPECIAL COATINGSCD SEAT COVER DISPENSERSCH SHOWER CURTAIN HOOKSSCHED SCHEDULESCR SHOWER CURTAIN RODSCT STRUCTURAL CLAY TILESCUT SCUTTLESCW SOFT COLD WATERSD SOAP DISPENSERSD SMOKE DAMPERSD SMOKE DETECTORSD STORM DRAINSE STEAM EXHAUST VENTSEC SECONDARYSECT SECTIONSECY SECRETARYSENS SENSIBLESF SQUARE FOOTSF SUPPLY FANSFCMU SPLIT-FACED CONCRETE MASONRY UNITSFU STRUCTURAL FACING UNITSGL SINGLESH SHOWERSHEATH SHEATHINGSHM SECURITY HOLLOW METALSHT SHEETSHW SOFT HOT WATERSIM SIMILARSL SHORT LEGSLNT SEALANTSM SHEET METALSM SPRINKLER MAINSND SANITARY NAPKIN DISPOSALSNV SANITARY NAPKIN VENDORSP STATIC PRESSURE (H2O)SP STAND PIPESP STATIC PRESSURESPEC SPECIFICATIONSSPK SPRINKLERSPL SOUND PRESSURE LEVELSPL SPECIALSPL BLK SPLASH BLOCKSQ SQUARESS STAINLESS STEELSSA STORM SHELTER AREASS SERVICE SINKSS SOLID SURFACEST STAIRST STORM SEWERSTAG'D STAGGEREDSTC SOUND TRANSMISSION CLASSSTC STAINED CONCRETESTD STANDARDSTE SINGLE TAPERED ENDSTGR STRINGERSTL STEELSTOR STORAGESTR STRUCTURAL - STRUCTURESUB SUBSTATIONSUBFL SUBFLOORSURF SURFACESUSP SUSPENDEDSV SHEET VINYLSV SOLENOID VALVESW SHORT WAYSW SWITCHSWBD SWITCH BOARDSWP STEAM WORKING PORESSURESYM SYMMETRICAL

T TEMPEREDT THERMOSTATT & B TOP & BOTTOMT& G TONGUE & GROOVET TREADTA TRANSFER AIRTAB TEST AND BALANCETAN TANGENTTB TERMINAL BOXTB TOWEL BARTBD TACK BOARDTC TEMPERATURE CONTROLTC TIME CLOCKTD TRANSFER DUCTTD TRENCH DRAINTDH TOTAL DYNAMIC HEADTEL TELEPHONETEMP TEMPERED - TEMPORARYTEMP TEMPERATURETERR TERRAZZOTEXT TEXTUREDTGL TOGGLETH THRESHOLDTH TOWEL HOOKTHK THICK(NESS)TMR TILT MIRROR UNITTMV THERMOSTATIC MIXING VALVETOB TOP OF BEAMTOC TOP OF CONCRETETOF TOP OF FOOTINGTOIL TOILETTOP TOP OF PAVINGTOS TOP OF STEELTOW TOP OF WALLTPV TRAP PRIMERTR TRIPTRANS TRANSVERSETRD TREADTS TEMPERATURE SENSORTSP TOTAL STATIC PRESSURETT TEMPERATURE TRANSMITTERTT TERRAZZO TILETTD TOILET TISSUE DISPENSERTV TELEVISIONTW TACK WALLTYP TYPICAL

U URINALUC UNIT COOLERUG UNDERGROUND

V VENTV VOLTV VACUUMVA VALVEVAC VACUUMVAV VARIABLE AIR VOLUMEVB VAPOR BARRIERVB VINYL BASEVBF VENT BELOW FLOORVCB VENTED COVE BASEVCP VITRIFIED CLAY PIPEVCT VINYL COMPOSITION TILEVD VOLUME DAMPER - MANUALVEL VELOCITYVENT VENTILATIONVENT VENTILATORVERT VERTICALVEST VESTIBULEVF VINYL FLOORVFD VARIABLE FREQUENCY DRIVEVM VOLTMETERVOL VOLUMEVP VENEER PLASTERVP VACUUM PUMPVSMC VARIABLE SPEED MOTOR CONTROLLERVT VINYL TILEVTR VENT THROUGH ROOFVWC VINYL WALLCOVERINGW WATER SERVICEW WIDE; WIDTHW WASTE (PLUG)W WATTW WESTW WIDE FLANGEW/ WITHW/O WITHOUTWB WET BULBWC WALL COVERINGWC WATER COLUMNWC WATER CLOSETWCC WATER COOLED CONDENSERWCL WATER CLOSET/LAVATORY COMBINATIONWCO WALL CLEAN OUTWD WOODWDW WINDOWWF WASH FOUNTAINWH WALL HYDRANTWFMD WATER FLOW MEASURING DEVICEWH WATER HEATERWHM WATT HOUR METERWI WROUGHT IRONWLR WATER LOOP RETURNWLS WATER LOOP SUPPLYWMG WATER MOTOR GONGWNSCT WAINSCOTWP WEATHERPROOFWPB WHIRLPOOL BATHWPF WATERPROOFWPFG WATERPROOFINGWR WATER RESISTANTWR WASTE RECEPTACLEWRHS WAREHOUSEWSP WET STAND PIPEWT WEIGHTWW WARM WHITEWWF WELDED WIRE FABRIC

XFMR TRANSFORMERXMTR TRANSMITTERYD YARDYH YARD HYDRANTZ IMPEDANCEZCV ZONE CONTROL VALVEZVB ZONE VALVE BOX& AND@ ATi.e. THAT IS# NUMBER

CG CLEAR FLOAT GLASSCIG CLEAR INSULATING GLASSCTG CLEAR TEMPERED FLOAT GLASSCTIG CLEAR TEMPERED INSULATING GLASSLG LAMINATED GLASSPG PATTERN GLASSPIG PATTERN INSULATING GLASSSG SPANDREL GLASSTG TINTED FLOAT GLASSTIG TINTED INSULATING GLASSTTG TINTED TEMPERED FLOAT GLASSTTIG TINTED TEMPERED INSULATING GLASSWG POLISHED WIRE GLASS

THE FOLLOWING ABBREVIATIONSARE USED WITH GLAZING:

IAQ INDOOR AIR QUALITYIAW IN ACCORDANCE WITHIBC INTERNATIONAL BUILDING CODEIC INTERCOMID INSIDE DIAMETERIE INVERT ELEVATIONIES ILLUMINATING ENGINEERING SOCIETYIF INSIDE FACEIG ISOLATED GROUNDIH INTAKE HOODIJ ISOLATION JOINTIJS IN JOIST SPACEIMC INTERMEDIATE METAL CONDUITIN INCHINC INCLUDE (ING)INSUL INSULATIONINT INTERIORIP IRON PIPEIW INDIRECT WASTE

O&M OPERATION AND MAINTENANCEO to O OUT TO OUTOA OVERALLOA OUTSIDE AIROBSC OBSCUREOC ON CENTEROD OUTSIDE DIAMETEROD OVERFLOW DRAINOF OUTSIDE FACEOVFL OVERFLOWOFC OWNER FURNISHED CONTRACTOR INSTALLEDOFF OFFICEOFOI OWNER FURNISHED OWNER INSTALLEDOHP OVERHEAD POWEROHT OVERHEAD TELEPHONEOPG OPENINGOPP OPPOSITEOSD OVERFLOW STORM DRAINOS&Y OUTSIDE SCREW AND YOKEOTCS OPEN TO CEILING SPACEOVHD OVERHEADOX OXYGEN

A/C AIR CONDITIONING(ER)A AMP AMPEREA COMPRESSED AIRAAP AREA ALARM PANELAAV AUTOMATIC AIR VENTAB ANCHOR BOLTABS ACRYLONITRILE-BUTADIENE-STYRENEAC ACOUSTICAL CEILINGAC ALTERNATING CURRENTACC AIR COOLED CONDENSERACCU AIR COOLED CONDENSING UNITACM ALUMINUM COMPOSITE MATERIALACST ACOUSTICAD ACCESS DOORAD AREA DRAINADDN ADDITION OR ADDITIONALADJ ADJUSTABLEADJT ADJACENTADMIN ADMINISTRATIONAF AIR FILTERAFF ABOVE FINISH FLOORAHJ AUTHORITY HAVING JURISDICTIONAHU AIR HANDLING UNITAI AREA INLETALT ALTERNATEALUM ALUMINUMAMB AMBIENTANCH ANCHORAP ACCESS PANELAPC ACOUSTICAL PANEL CEILINGAPPROX APPROXIMATEAR ACID RESISTINGARCH ARCHITECTURALASB ASBESTOSASPH ASPHALTAUTO AUTOMATICAV ACID VENTAV AIR VENTAV AVERAGEAW ACID WASTEAWG AMERICAN WIRE GAUGEAWP ACOUSTICAL WALL PANEL

ABBREVIATIONS GENERAL SYMBOLS

SHEET ON WHICH DRAWN

REVISION NUMBER

WALL TYPE

WINDOW NUMBER

DOOR NUMBER

ROOM NUMBER

COLUMN LINE

LEGEND/KEY NOTE

BUILDING ELEVATIONINTERIOR ELEVATION

DETAIL REFERENCE

WALL SECTION

CROSS REFERENCEDETAIL NUMBER

(CONTINUOUS BLOCKING)

BATT INSULATION

RIGID INSULATION

CARPET (LARGE SCALE)

TILE (LARGE SCALE)

ACOUSTICAL TILE (LARGE SCALE)

PROTECTION BOARD

CONCRETE MASONRY UNIT

METAL STUDS

STEEL (LARGE SCALE)

(LARGE SCALE)GYPSUM WALL BOARD

PLYWOOD (LARGE SCALE)

BRICK VENEER

SHINGLES

STONE

GLASS

(TRIM/FINISH)WOOD

(NON-CONTINUOS BLOCKING)WOOD

GRAVEL/BALLAST

WOOD

GYM FLOOR

STEEL

PRECAST CONCRETE

CONCRETE

SAND

EARTH

CASEWORKELEVATION

SIMILAR OR TYPICAL REFERENCE

SIMILAR OR TYPICAL REFERENCE

?

DESCRIPTION

?

???? SIM

BUILDING SECTION

?

NC NOISE CRITERIANC NORMALLY CLOSEDNC NURSE CALLNEC NATIONAL ELECTRIC CODENEMA NATIONAL ELECTRICAL MANUFACTURERS ASSN.NEUT NEUTRALNIC NOT IN CONTRACTNO NORMALLY OPENNO NUMBERNO NITROUS OXIDENOM NOMINALNS NEUTRAL SENSORNTS NOT TO SCALE

RPM REVOLUTIONS PER MINUTERPZ REDUCED PRESSURE BACKFLOW PREVENTERRS REFRIGERANT SUCTIONRWC RESILIENT WALL COVERINGRWL RAIN WATER LEADERS SENSOR

UGE UNDERGROUND ELECTRICALUGT UNDERGROUND TELEPHONEUH UNIT HEATERUL UNDERWRITERS LABORATORIESUNEX UNEXCAVATEDUNFIN UNFINISHEDUNO UNLESS NOTED OTHERWISEUR URINALURD UNDERGROUND RESIDENTIAL DISTRIBUTIONUS UTILITY SHELFUTIL UTILITYUV UNIT VENTILATOR

?

ROOM NAME???

???

????

SIM

????

SIM

????

SIM ????

SIM

XX/ A11.X

? ?Eas

t

X'

X"

QC

FH

A

PIV

CO

OR

AREA INLET

CURB INLET

MANHOLE

OBSERVATION RISER

HEAD WALL

FLARED END

CLEAN OUT

CAP

THRUST BLOCK

VALVE

POST INDICATOR VALVE

REDUCER

MAGNESIUM ANODE

DIELECTRIC COUPLING

CATHODIC TEST STATION

FIRE HYDRANT

POWER POLE

LIGHT POLE

TELEPHONE MANHOLE

TELEPHONE BOX

SPRINKLER HEAD, 360°

SPRINKLER HEAD, 270°

SPRINKLER HEAD, 180°

SPRINKLER HEAD, 90°

QUICK COUPLING

TREE, EXISTING DECIDUOUS

TREE, EXISTING CONIFER

SHADE TREE

ORNAMENTAL TREE

DECIDUOUS TREE

SHRUB

CLIPPED SHRUB

100

100

99

991% SLOPE

DOWN

KCJ

KCT

EJ

xx xx xx xx

x x x x

LAT

HOT

OHP

UGE/UGT

LPS

MPS

HPS

G

F

W

FM

S

SD

PROPERTY LINE

LOT LINE

EASEMENT LINE

BUILDING LINE, EXISTING

BUILDING LINE, NEW W/ DOOROPENING AND STRUCTURAL STOOPPRMARY CONTOUR, EXISTING

PRIMARY CONTOUR, NEW

SECONDARY CONTOUR, EXISTING

SECONDARY CONTOUR, NEW

SLOPE, PAVEMENT

DRAINAGE DITCH OR SWALE

STREET CENTERLINE

CURB, THICKENED EDGE

CURB, EXISTING

CURB, NEW

PAVING CONTRACTION JOINT

PAVING KEYED CONSTRUCTION JOINT

PAVING TIED CONSTRUCTION JOINT

PAVING EXPANSION JOINT

FENCE, SECURITY

FENCE, BARBED WIRE

FENCE, CHAIN LINK

FENCE, WOOD

SEED LIMIT

SOD LIMIT

STORM DRAIN

SUBDRAIN

SUBDRAIN, PREFORATED

SANITARY SEWER

FORCE MAIN

WATER

FIRE

GAS

HIGH PRESSURE STEAM

MEDIUM PRESSURE STEAM

LOW PRESSURE STEAM

UNDERGROUND ELEC/TELEPHONE

OVERHEAD POWER

LAWN SPRINKLER HOT LINE

LAWN SPRINKLER LATERAL

SITE SYMBOLS

Arch

itect

ure

Eng

inee

ring

Pla

nnin

g In

terio

rs

©

, DLR

Gro

up in

c., a

Neb

rask

a co

rpor

atio

n, A

LL R

IGH

TS R

ESER

VED

Revis

i ons

5/8/

2017

2:2

9:42

PM

C:\R

evit\

10-1

6206

-00_

AR_2

016_

Cen

tral_

sbur

gess

.rvt

10-1

6206

-00

5/08

/17

STAT

E O

F N

EBR

ASKA

501

BU

ILD

ING

REN

OVA

TIO

NSY

MBO

LS A

ND

ABB

REV

IATI

ON

S0.

1

2017

PRIN

TSH

OP

BUIL

D O

UT

& ST

RU

CTU

RAL

DEF

ICIE

NC

Y R

ENO

VATI

ON

Page 3: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

UP

- COMBINED OCCUPANT LOAD AT A GIVEN EXIT DOOR. (SUM OF THESE EQUALS TOTAL OCCUPANT LOAD)

(OCCUPANCY LOAD IS NOT INCLUDED IN LOADS BEYOND THIS ROOM)

(THE CAPACITY OF DOORS ARE DETERMINED AS FOLLOWS:CLEAR OPENING WIDTH IN INCHES DIVIDED BY 0.2THE CAPACITY OF STAIRS ARE DETERMINED AS FOLLOWS:WIDTH IN INCHES DIVIDED BY 0.3)

- COMBINED OCCUPANT LOAD AT A GIVEN DOOR OR STAIR

- TOTAL EXIT CAPACITY OF DOOR(THE CAPACITY OF DOORS ARE DETERMINED AS FOLLOWS:CLEAR OPENING WIDTH IN INCHES DIVIDED BY 0.2)

WALL SEPARATION LEGEND

SYMBOL LEGEND- OCCUPANCY LOAD####

00

###

- TOTAL EXIT CAPACITY OF DOOR OR STAIR

- ACCESSORY USE AREA

00

WALL FIRE RATING TYPEC = CORRIDORFB = FIRE BARRIERVS = VERTICAL SHAFTVX = VERTICAL EXIT

WALL HOURLY FIRE RATING0 = 0 HOUR1 = 1 HOUR2 = 2 HOURSP = SMOKE PARTITION

B

B

B

B

B

B B

B

B S-2

B

S-2

S-2

45 320

39 320

B

106160

61320

122 SF

RECORDS STORAGE007

130 SF

CART STORAGE004

780 SF

MECHANICAL009

262 SF

RECEPTION006

138 SF

OFFICE010

475 SF

CONFERENCE012

FILES008C

1998 SF

PRE-PRESS/DIGITAL GRAPHICS016

688 SF

OPEN OFFICE008

CORRIDOR001

1878 SF

SECURED PRINT020

684 SF

COLOR COPY019

251 SF

SECURED STORAGE021

CART STORAGE022A

HALL023

WOMEN'S024

MEN'S025

JAN026

CORRIDOR022

HALL005

117 SF

OFFICE014

138 SF

OFFICE008A

94 SF

OFFICE018

HALL008B

158 SF

OFFICE011

B B117 SF

OFFICE015

448 SF

BREAK ROOM027

B

5

586 SF

ELECTRICAL029

267 SF

FUTURE UPS028

MATC

HLIN

E - A

REA

AMA

TCHL

INE

- ARE

A B

MATC

HLIN

E - A

REA

AMA

TCHL

INE

- ARE

A B

24160

EXISTING MECH

EXISTING ELEC

EXISTING ELEC

EXISTING ELECEXISTING MECH

EXISTING ELECEXISTINGDATA

CORRIDOR041

120

160

20320

24160

EXISTING UPS ROOMOPEN TO SHAFT ABOVE

TUNNEL TO STATE CAPITOL

SPSP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

EXISTINGELEVEQUIP

SP

SP

SP

SP

0 C0 C

0 C

2 VS

2 VS

2 VS0 C

0 C

0 C

2 FB

2 FB

2 VX2 V

X

2 VX

2 FB2 V

S

2 VS 2 FB

2 VS

SP

SP

SP

11

SP

SP

SP

1

3

3

6

11167 SF

SCHED.017

B

1

211 1

217

1

EXISTING PRINT SHOP12,190 sf

122

SP

2 VX

2 VX

DEDI

CATE

D EG

RESS

AIS

LE

300'

MAXI

MUM

TRAV

EL D

ISTA

NCE

2 FB

21

110 SF

CART STORAGE002

72 SF

ELEC/DATA003

2-VX24120

120120

0-C

0-C

0-C

TRAVEL DISTANCE 49'

..

.

.CO

MMON

PAT

H OF

TRA

VEL =

65'

COMM

ON P

ATH

OF T

RAVE

L =49

'

.

.

120

106

CR

CR

CR

4467 SF

FUTURE031

SP

SPSP

SPELEV

Arch

itect

ure

Eng

inee

ring

Pla

nnin

g In

terio

rs

©

, DLR

Gro

up in

c., a

Neb

rask

a co

rpor

atio

n, A

LL R

IGH

TS R

ESER

VED

Revis

i ons

5/8/

2017

2:3

0:03

PM

C:\R

evit\

10-1

6206

-00_

AR_2

016_

Cen

tral_

sbur

gess

.rvt

10-1

6206

-00

5/08

/17

STAT

E O

F N

EBR

ASKA

501

BU

ILD

ING

REN

OVA

TIO

NC

OD

E PL

ANS

CP1

.1

2017

PRIN

TSH

OP

BUIL

D O

UT

& ST

RU

CTU

RAL

DEF

ICIE

NC

Y R

ENO

VATI

ON

NORTHSCALE: 1/16" = 1'-0"CODE PLAN -LOWER LEVEL PLAN, AREAS A & B

NAME OF PROJECT: 501 BUILDING RENOVATION

LOCATION: 501 S. 14TH STREET LINCOLN, NE 68508

PROPOSED USE: BUSINESS, DATA CENTER, OFFICE

CODE ENFORCEMENT JURISDICTION: LANCASTER COUNTY

ARCHITECT: DLR GROUPJOHN P. BADAMI, NEBRASKA ARCHITECT CERTIFICATE NO. A-25661111 LINCOLN MALL - SUITE 201LINCOLN, NE 68508(402) 972-4123

APPLICABLE BUILDING CODES: INTERNATIONAL BUILDING CODE - 2012 EDITIONNFPA 101 LIFE SAFETY CODE - 2000 EDITION AS CURRENTLY ADOPTED BY THE NEBRASKA STATE FIRE MARSHALAPPLICABLE NFPA PAMPHLETS CURRENTLY LISTED BY THE NEBRASKA STATE FIRE MARSHALANSI STANDARD A17.1 FOR ELEVATORS AND STATE OF NEBRASKA ELEVATOR INSPECTOR REQUIREMENTSINTERNATIONAL MECHANICAL CODE - 2009 EDITIONINTERNATIONAL PLUMBING CODE - 2009 EDITIONINTERNATIONAL FUEL GAS CODE - 2009 EDITIONNATIONAL ELECTRICAL CODE (NFPA 70) - 2011 EDITIONINTERNATIONAL ENERGY CONSERVATION CODE - 2009 EDITION / ASHRAE 90.1 - 2007

BUILDING AREAS, CONSTRUCTION TYPE AND OCCUPANCY TYPE REQUIREMENTS

CONSTRUCTION TYPE: Reclassified per IBC as II-BOCCUPANCY TYPE: B, S-2LEVEL SQUARE FOOTAGE: 12,200 SF - 69,000 ALLOWED PER IBC TABLE 503 WITH SPRINKLER AREA INCREASE (200%)BUILDING HEIGHT: 56 FEET - 75 FEET ALLOWED PER IBC TABLE 503# OF STORIES: 4 STORIES -4 ALLOWED PER IBC TABLE 503 WITH HEIGHT INCREASE PER 504.1CORRIDORS: CORRIDORS NOT RATED PER TABLE 1018.1

FIRE PROTECTION SYSTEMSFIRE ALARM & SMOKE DETECTION SYSTEMAUTOMATIC SPRINKLER SYSTEMPORTABLE FIRE EXTINGUISHERSEMERGENCY LIGHTING AND EXIT SIGNAGE

PLUMBING FIXTURE REQUIREMENTS (IBC TABLE 2902.1):MALE WC: 1 PER 25 FOR FIRST 50 - 1 PER 50 REMAINDER

LAV: 1 PER 40 FOR THE FIRST 80 - 1 PER 80 FOR REMAINDERFEMALE WC: 1 PER 25 FOR FIRST 50 - 1 PER 50 FOR REMAINDER

LAV: 1 PER 40 FOR FIRST 80 - 1PER 80 FOR REMAINDER

TOTAL BUILDING LEVEL OCCUPANTS = 270TOTAL OCCUPANTS AGAINST PUBLIC FIXTURE COUNT = 270 (DIV BY 2 = 135 PER SEX)

4 PUBLIC MEN'S WC FIXTURES REQUIRED - __4__ PROVIDED 2 PUBLIC MEN'S WC FIXTURES REQUIRED - __2__ PROVIDED 2 PUBLIC MEN'S LAVS REQUIRED - __2___ PROVIDED

5 PUBLIC WOMEN'S WC FIXTURES REQUIRED - ___5__ PROVIDED 3 PUBLIC WOMEN'S LAVS REQUIRED - __3___ PROVIDED

PLUMBING FIXTURE SUMMARY

BUILDING CODE SUMMARY

Zero RATED CORRIDOR PARTITION (0-C) (IBC with NFPA 101 Smoke Partition requirements)

A. Zero rated vertical fire partition (floor to floor or floor to roof deck) as permitted by IBC Table 1018.1 for occupancies as indicated andbuildings equipped throughout with an automatic sprinkler system. Zero-Rated Corridor partitions shall extend from the top of the foundation orfloor/ceiling assembly below to the under-side of the floor or roof sheathing, slab or deck above and shall be securely attached thereto.

Exceptions to Fire Partition Continuity per IBC Section 708.4:1. Where the room-side fire-resistance-rated membrane of the corridor is carried through to the underside of the floor or roof sheathing, deck orslab of a fire-resistance-rated floor or roof above, the ceiling of the corridor shall be permitted to be protected by the use of ceiling materials asrequired for a 1-hour fire-resistance-rated floor or roof system.2. Where the corridor ceiling is constructed as required for the corridor walls, the walls shall be permitted to terminate at the upper membrane ofsuch ceiling assembly.

B. Corridor width IBC Section 1018.2. The minimum corridor width of corridors specified in Table 1018.2 shall be as determined in Section1005.1.Table 1018.2:1. Forty-four inches – minimum width required for any facilities not listed in Table 1018.2.2. Twenty-four inches – access to and utilization of electrical, mechanical or plumbing systems or equipment.3. Thirty-six inches – With a required occupant capacity of less than 50.4. Seventy-two inches – In Group E with a corridor having a required capacity of 100 or more.

C. The required width of corridors shall be unobstructed.Exception: Encroachments complying with Section 1005.7 as follows:1. Doors, when fully opened, shall not reduce the required width by more than 7 inches. Doors in any position shall not reduce the required widthby more than one-half.

Exceptions:a. Surface-mounted latch release hardware shall be exempt from inclusion in the 7-inch maximum (178 mm) encroachment where:i. The hardware is mounted to the side of the door facing away from the adjacent wall where the door is in the open position; andii. The hardware is mounted not less than 34 inches (865 mm) nor more than 48 inches (1219 mm) above the finished floor.

2. Other projections. Handrail projections shall be in accordance with the provisions of Section 1012.8. Other nonstructural projections such astrim and similar decorative features shall be permitted to project into the required width a maximum of 1-1/2 inches (38 mm) on each side.3. Protruding objects. Protruding objects shall comply with the applicable requirements of Section 1003.3.

D. Door and window openings in a zero-rated corridor partitions are not required to have a fire resistance rating.

E. Doors and window assemblies may have unlimited size glass panels complying with safety glazing requirements of IBC Section 2406.

F. Penetrations of zero-rated corridor partitions shall limit the transfer of smoke.1. Seal all pipe, sleeves, and conduit penetrations and around all ducts with non-combustible sealants continuously applied so as to resist thepassage of smoke.2. Dampers at duct penetrations shall be mounted and sealed in wall with factory fabricated sleeves and perimeter mounting angles.3. Seal top of wall to floor or roof deck with an approved fire resistant joint system or non-combustible sealants continuously applied so as toresist the passage of smoke from one side of the wall to the other.

G. Duct penetrations are not required to be protected with smoke dampers.

H. Air transfer openings of zero-rated corridor partitions and ducts with openings serving both the corridor and an adjacent space shall beprotected with smoke dampers complying with IBC Section 717.3. The smoke damper actuating device shall comply with IBC Section 717.3.3.2.

I. Air movement in corridors, IBC Section 1018.5. Corridors shall not serve as supply, return, exhaust, relief or ventilation air ducts. Exceptions:1. Use of a corridor as a source of makeup air for exhaust systems in rooms that open directly onto such corridors, including toilet rooms,bathrooms, dressing rooms, smoking lounges and janitor closets, shall be permitted, provided that each such corridor is directly supplied withoutdoor air at a rate greater than the rate of makeup (exhaust) air taken from the corridor.2. Where located within a dwelling unit, the use of corridors for conveying return air shall not be prohibited.3. Where located within tenant spaces of 1,000 square feet or less in area, utilization of corridors for conveying return air is permitted.4. Incidental air movement from pressurized rooms within health care facilities, provided that the corridor is not the primary source of supply orreturn to the room.

J. Corridor ceiling, IBC Section 1018.5.1. Use of the space between the corridor ceiling and the floor or roof structure above as a return air plenumis permitted for one or more of the following conditions:1. The corridor is not required to be of fire-resistance-rated construction;2. The corridor is separated from the plenum by fire-resistance-rated construction;3. The air-handling system serving the corridor is shut down upon activation of the air-handling unit smoke detectors required by theInternational Mechanical Code;4. The air-handling system serving the corridor is shut down upon detection of sprinkler waterflow where the building is equipped throughout withan automatic sprinkler system; or5. The space between the corridor ceiling and the floor or roof structure above the corridor is used as a component of an approved engineeredsmoke control system.

K. Zero-rated corridor partitions shall also meet the requirements of NFPA 101, Life Safety Code (LSC) smoke partitions (SP) as follows: Inaccordance with NFPA 101 LSC 14.3.6 Exception No. 2, new educational occupancies corridor walls are not required to be rated in buildingsprotected throughout by an approved supervised automatic sprinkler system, provided such walls form smoke partitions in accordance with LSC8.2.4.1. Doors shall not include louvers.2. Doors shall be self-closing or automatic-closing in accordance with LSC 7.2.1.8.

a. NE State Fire Marshal Interpretation Number 07-04: When the building is protected throughout by an approved, supervised automatic firesprinkler system and smoke detection tied to the building fire alarm system in all egress corridors, corridor door assemblies from classrooms arenot required to be rated and not required to be automatic-closing or self-closing but must be latchable. Corridor door assemblies from rooms otherthan normally occupied Classrooms are not required to be rated but must be automatic-closing or self-closing and latchable.b. Automatic closing doors shall have smoke detector activated (SDA) magnetic hold open devices per LSC 7.2.1.8. All SDA automatic closingdoors shall be activated by actuation of any fire alarm device or sprinkler system, where required, and power failure.c. Per LSC 8.2.4.4.3, corridor smoke partitions with air transfer openings and ducts with openings serving both the corridor and an adjacentspace shall be provided with approved smoke dampers designed to limit the transfer of smoke. Smoke dampers in air transfer openings shallclose upon detection of smoke by approved detectors installed in accordance with NFPA 72, National Fire Alarm Code.

1) Per Life Safety Code Handbook, if ductwork runs to a smoke partition, pierces the partition, and continues its run on the other side of thepartition, no transfer opening exists, and therefore, no smoke damper is required.

1-HOUR SMOKE BARRIER WALL (1-SB) – IBC

A. 1-Hour fire-resistive vertical (floor to floor or floor to roof deck) and/or horizontal (wall or floor).

B. Continuity: Smoke barriers shall form an effective membrane continuous from outside wall to outside wall and from the top of the foundationor floor/ceiling assembly below to the underside of the floor or roof sheathing, deck or slab above, including continuity through concealedspaces, such as those found above suspended ceilings, and interstitial structural and mechanical spaces. The supporting construction shall beprotected to afford the required fire-resistance rating of the wall or floor supported in buildings of other than Type IIB, IIIB or VB construction.Exception:1. Smoke-barrier walls are not required in interstitial spaces where such spaces are designed and constructed with ceilings that provideresistance to the passage of fire and smoke equivalent to that provided by the smoke-barrier walls.2. Smoke barriers used for elevator lobbies in accordance with Section 405.4.3 for underground buildings, 3007.7.2 for fire service accesselevator or 3008.7.2 for occupant evacuation elevators are not required to extend from outside wall to outside wall.3. Smoke barriers used for areas of refuge for accessible means of egress in accordance with Section 1007.6.2 are not required to extend fromoutside wall to outside wall.

C. Openings in a smoke barrier shall be protected in accordance with IBC Section 716.Exceptions:1. In Group I-2 and ambulatory care facilities, where doors are installed across corridors, a pair of opposite-swinging doors without a centermullion shall be installed having vision panels with fire-protection-rated glazing materials in fire-protection-rated frames, the area of which shallnot exceed that tested. The doors shall be close fitting within operational tolerances, and shall not have undercuts in excess of 3/4 inch, louversor grilles. The doors shall have head and jamb stops, astragals or rabbets at meeting edges and shall be automatic-closing by smoke detectionin accordance with Section 716.5.9.3. Where permitted by the door manufacturer’s listing, positive-latching devices are not required.2. In Group I-2 and ambulatory care facilities, horizontal sliding doors installed in accordance with Section 1008.1.4.3 and protected inaccordance with Section 716.

D. Doors shall have a 1/3-Hour fire resistance rating in accordance with IBC Table 716.5, be tested in accordance with NFPA 252 or UL 10Cwithout the hose stream test, and be self- or automatic closing.1. Per IBC Section 716.5.3.1, fire door assemblies shall also meet the requirements for a smoke and draft control door assembly tested inaccordance with UL 1784. Louvers shall be prohibited. Installation of smoke doors shall be in accordance with NFPA 105.2. Glazing in Door Assemblies per IBC Section 716.5.3.2: In a 20-minute fire door assembly, the glazing material in the door itself shall have aminimum fire-protection-rated glazing of 20 minutes and shall be exempt from the hose stream test. Glazing material in any other part of the doorassembly, including transom lights and sidelights, shall be tested in accordance with NFPA 257 or UL 9, including the hose stream test, inaccordance with Section 716.6.3. Fire door frames with 3/4 hour transom lights and sidelights shall be permitted in accordance with Table 716.5 and IBC Section 716.5.6.4. Smoke activated doors per IBC Section 716.5.9.3. Automatic closing doors installed in the following locations shall be automatic-closing bythe actuation of smoke detectors installed in accordance with Section 907.3 or by loss of power to the smoke detector or hold-open device. Doorsthat are automatic-closing by smoke detection shall not have more than a 10 second delay before the door starts to close after the smokedetector is actuated:

i. Doors installed across a corridor.ii. Doors that protect openings in exits or corridors required to be of fire resistance rated construction.iii. Doors installed in smoke barriers in accordance with IBC Section 709.5.iv. Doors installed in the smoke barrier walls for compartmentation of underground buildings in accordance with Section 405.4.2.v. Doors installed in the elevator lobby smoke barrier walls of underground buildings in accordance with Section 405.4.3.

Exceptions per IBC Section 716.5.3:a. Corridor door assemblies in occupancies of Group I-2 shall be in accordance with Section 407.3.1, shall not have a required fire protectionrating and shall not be required to be equipped with self-closing or automatic-closing devises, but shall provide an effective barrier to limit thetransfer of smoke and shall be equipped with positive latching.b. Horizontal sliding doors in smoke barriers that comply with Sections 408.3 and 408.8.4 in occupancies in Group I-3.

5. Fire protection rated glazing used in fire doors shall comply with the size limitations of NFPA 80 in accordance with IBC Section 716.5.8.1.6. Safety Glazing: Per IBC Section 716.5.8.4, fire protection rated glazing installed in fire doors in areas subject to human impact in hazardouslocations shall comply with IBC Chapter 24.

D. Fire window assemblies shall have a 3/4-Hour assembly rating per IBC Table 716.6.1. Safety glazing. Fire-protection-rated glazing installed in fire window assemblies in areas subject to human impact in hazardous locationsshall comply with Chapter 24.2. Per IBC Section 716.6.4. Glazing in fire window assemblies shall be fire protection rated glazing installed in accordance with and complyingwith the size limitations set forth in NFPA 80.3. The total area of glazing in fire protection rated window assemblies shall not exceed 25 percent of the area of a common wall with any roomper IBC Section 716.6.7.2.

E. Penetrations of smoke barriers shall comply with IBC Section 714.1. Through penetrations shall be protected with an approved penetration firestop system installed as tested in accordance with ASTM E814 orUL 1479 with a minimum positive pressure differential of 0.01 inch of water and shall have an F rating of not less than the required fire resistancerating of the wall penetrated.2. Dampers at duct penetrations shall be mounted and sealed in wall with factory fabricated sleeves and perimeter mounting angles.

F. Seal top of wall to floor or roof deck with a fire-resistant joint system tested in accordance with the requirements of either ASTM E 1966 or UL2079 as specified. Per IBC Section 715.6, fire resistant joint systems in smoke barriers, and joints at the intersection of a horizontal smoke barrierand an exterior curtainwall, shall be tested in accordance with the requirements of UL 2079 for air leakage. The L rating of the joint system shallnot exceed 5 cfm per linear foot (0.00775 m3/s m) of joint at 0.30 inch (7.47 Pa) of water for both the ambient temperature and elevatedtemperature tests.

G. A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates asmoke barrier. Smoke dampers and smoke damper actuation methods shall comply with Section 717.3.3.2.Exception IBC Section 717.5.5:1. Smoke dampers are not required where the openings in ducts are limited to a single smoke compartment and the ducts are constructed ofsteel.

FIRE BARRIERs 2-Hour (2-FB)– IBC

A. 2-Hour, fire-resistive vertical (floor to floor or roof deck) and/or horizontal (floor) construction. Fire barriers shall extend from the top of the floor/ceiling assembly below to theunderside of the floor or roof sheathing, slab or deck above and shall be securely attached thereto. Such fire barriers shall be continuous through concealed spaces, such as thespace above a suspended ceiling. The supporting construction for fire barrier walls shall be protected to afford the required fire-resistance rating of the fire barrier supported,except for 1-hour fire-resistance-rated incidental accessory occupancies’ separations as required by Table 509 in buildings of Type IIB, IIIB and VB construction is not required tobe fire-resistant rated unless required by other sections of the IBC. Hollow vertical spaces within a fire barrier shall be fireblocked in accordance with Section 718.2 at every floorlevel.

B. Openings in a fire barrier wall shall be protected in accordance with Section 716. Openings shall be limited to a maximum aggregate width of 25 percent of the length of thewall, and the maximum area of any single opening shall not exceed 156 square feet.Exceptions:1. Openings shall not be limited to 156 square feet where adjoining floor areas are equipped throughout with an automatic sprinkler system.2. Openings shall not be limited to 156 square feet or an aggregate width of 25 percent of the length of the wall where the opening protective is a fire door serving enclosures forexit access stairways, exit access ramps, interior exit stairways and interior exit ramps.3. Openings shall not be limited to 156 square feet or an aggregate width of 25 percent of the length of the wall where the opening protective assembly has been tested inaccordance with ASTM E 119 or UL 263 and has a minimum fire-resistance rating not less than the fire-resistance rating of the wall.4. Fire window assemblies permitted in atrium separation walls shall not be limited to a maximum aggregate width of 25 percent of the length of the wall.

C. Doors shall have a fire protection rating per IBC Table 716.4 and be self- or automatic closing per Section 716.5.9.1. Single fire doors and both leaves of pairs of side-hinged swinging fire doors shall be provided with an active latch bolt that will secure the door when it is closed per IBCSection 716.5.9.1.2. Smoke-activated doors. Automatic-closing doors installed in the following locations shall be automatic-closing by the actuation of smoke detectors installed in accordance withSection 907.3 or by loss of power to the smoke detector or hold-open device. Doors that are automatic-closing by smoke detection shall not have more than a 10-second delaybefore the door starts to close after the smoke detector is actuated:i. Doors installed across a corridor.ii. Doors that protect exits or corridors required to be of fire resistance rated construction.iii. Doors that protect openings in walls that are capable of resisting the passage of smoke in accordance with Section 509.4.3. 1-Hour Fire Barrier doors shall have a 3/4 Hour assembly rating.4. 2-Hour Fire Barrier doors shall have a 1-1/2 Hour assembly rating.5. 3-Hour and 4-Hour Fire Barrier doors shall have a 3 Hour assembly rating.

D. Fire window assemblies are not permitted in 1-Hour or greater assembly rating fire barriers in accordance with Table 716.6. 3/4 hour fire window assemblies are permitted in1-Hour fire barriers separating incidental use areas indicated in Table 509 and mixed occupancy separations required by Table 508.4.1. Exception per Section 716.2: Fire-resistance-rated glazing tested as part of a fire-resistance-rated wall assembly in accordance with ASTM E 119 or UL 263 and labeled inaccordance with IBC Section 703.6.2. Per IBC Section 716.6.7, fire-protection-rated glazing used in interior fire window assemblies located in fire partitions and fire barriers shall be limited to use in assemblies witha maximum fire-resistance rating of 1 hour.i. Where 3/4 hour fire protection window assemblies permitted, fire-protection-rated glazing requiring 45-minute opening protection in accordance with Table 716.6 shall belimited to fire partitions designed in accordance with Section 708 and fire barriers utilized in the applications set forth in Sections 707.3.7 (incidental accessory occupancies) and707.3.9 (separated occupancies) where the fire-resistance rating does not exceed 1 hour.ii. The total area of glazing in fire protection rated windows assemblies shall not exceed 25 percent of the area of a common wall with any room per IBC Section 716.6.7.2.

3. Per IBC Section 716.6.4, glazing in fire window assemblies shall be fire-protection-rated glazing installed in accordance with and complying with the size limitations set forth inNFPA 80.

E. Doors may have glass panels complying with the following:1. 3/4 Hour assembly rating doors/sidelite/transom may have up to the maximum size tested fire protection rated glazing impact tested in accordance with CPSC 16 CFR 1201.2. Per IBC Section 716.5.8.1.2.2, 1-1/2 Hour assembly rating doors may have up to 100 square-inch fire protection rated glazing impact tested in accordance with CPSC 16 CFR1201. Fire protection rated sidelites and transom panels are not permitted in 1-1/2 Hour doors except where fire resistance rated glazing tested to ASTM E 119 is provided.3. Door vision panels and sidelite and transom panels are not permitted in 3 Hour assembly rating doors except where fire resistance rated glazing tested to ASTM E 119 isprovided.

F. Penetrations of fire barrier shall comply with IBC Section 714.1. Seal all pipe and conduit penetrations and around all ducts without dampers with an approved firestop system installed as tested in accordance with ASTM E814 or UL 1479as specified.2. Dampers at duct penetrations shall be mounted and sealed in wall with factory fabricated sleeves and perimeter mounting angles.3. Seal top of wall to floor or roof deck with a fire-resistant joint system tested in accordance with the requirements of either ASTM E 1966 or UL 2079 as specified.

G. Joints made in or between fire barriers, and joints made at the intersection of fire barriers with underside of a fire-resistance rated floor or roof sheathing, slab, or deck above,and the exterior vertical wall intersection shall comply with IBC Section 715.1. Voids at intersections, IBC Section 707.9. The voids created at the intersection of a fire barrier and a non-fire-resistance-rated roof assembly shall be filled. An approvedmaterial or system shall be used to fill the void, shall be securely installed in or on the intersection for its entire length so as not to dislodge, loosen or otherwise impair its ability toaccommodate expected building movements and to retard the passage of fire and hot gases.

H. Ducts and air transfer openings of fire barriers shall be protected with approved fire dampers complying with the following: 1-1/2 hour rated for 1- Hour and 2-Hour FireBarriers, 3 hour rated for 3-Hour and 4-Hour Fire Barriers. The fire damper actuating device shall comply with IBC Section 717.3.3.1.Exception: Fire dampers are not required at penetrations of fire barriers where any of the following apply:1. Penetrations are tested in accordance with ASTM E 119 or UL 263 as part of the fire-resistance-rated assembly.2. Ducts are used as part of an approved smoke control system in accordance with Section 909 and where the use of a fire damper would interfere with the operation of a smokecontrol system.3. Such walls are penetrated by ducted HVAC systems, have a required fire-resistance rating of 1 hour or less, are in areas of other than Group H and are in buildings equippedthroughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. For the purposes of this exception, a ducted HVAC system shall be a duct systemfor conveying supply, return or exhaust air as part of the structure’s HVAC system. Such a duct system shall be constructed of sheet steel not less than 26 gage thickness and shallbe continuous from the air-handling appliance or equipment to the air outlet and inlet terminals.

I. Fire Barrier/Smoke Separations at Corridors: Air transfer openings of fire barrier walls that form Corridors and that have ducts with openings serving both the Corridor and anadjacent space shall be protected with fire dampers as indicated above in Paragraph H and protected with smoke dampers or combination fire/smoke dampers. The damperactuating device shall comply with IBC Section 717.3.3.

Page 4: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

UP

6

7

5

4

3

2

1

HA B C D E F G

8

9

10

1

1 REMOVE STUD WALL IN ITS ENTIRETY

1

2

2 REMOVE DOOR AND ASSOCIATED HARDWARE AND FRAME

2

2

4' - 4" 6' - 4"

3

3 REMOVE PORTION OF STUD WALL AS INDICATED IN PREPARATION FOR NEW DOOR OPENING

2

4 REMOVE CEILING PADS AND GRID IN ITS ENTIRETY.

44

4

5

5 REMOVE BULKHEAD AND ASSOCIATED CEILING PADS AND GRID IN ITS ENTIRETY.

6 REMOVE CARD READER AND ASSOCIATED MAGNETIC LOCK AND RETURN TOOWNER IN GOOD WORKING ORDER.

6

6

DEMOLITION KEY NOTES

8' - 0" 3' - 4"

MATC

HLIN

E - A

REA

AMA

TCHL

INE

- ARE

A B

MATC

HLIN

E - A

REA

AMA

TCHL

INE

- ARE

A B

7

7 SAWCUT CONCRETE SLAB. SEE PLUMBING.

HATCHED AREA TO REMAINOPERATIONAL UNTIL NEW SECUREPRINT ROOM 020 IS FULLYOPERATIONAL. THIS SPACE MUSTREMAIN PHYSICALLY SECURE DURINGALL DEMOLITION AND CONSTRUCTION.DUE TO SENSITIVE NATURE OF PRINTEQUIPMENT, THE DEMOLITION AND NEWCONSTRUCTION TO EXPANDMECHANICAL ROOM 009 MUST BESEALED OFF FROM THE OPERATIONALAREAS OF THE SPACE.

8

8 REMOVE HIGH DENSITY FILING CABINET AND DISPOSE OFF-SITE

1

1

1

2

2

8

8

AREA A/PHASE 1 DEMOLITION AND NEWCONSTRUCTION MUST BE COMPLETE PRIORTO STARTING ON AREA B/PHASE 2.

DEMOLITION GENERAL NOTES

A. DEMOLITION GENERAL NOTES APPLY TO ALL DEMOLITION SHEETS.B. COORDINATE DEMOLITION AND PHASING EFFORTS WITH ARCHITECT

AND OWNER'S REPRESENTATIVES. EVERY EFFORT SHALL BE MADETO MINIMIZE DISRUPTION OF OWNER'S OPERATIONS AND TO PROVIDEBUILDING USER'S SAFETY. EXCESSIVE NOISE OR VIBRATION SHALL BEPRE-APPROVED AND COORDINATED WITH OWNER'SREPRESENTATIVE. SEE SPECIFICATION SECTION 011001"PROCEDURES AND GUIDELINES FOR WORKING IN AN ACTIVE DATACENTER".

C. COORDINATE DISRUPTION OF UTILITY SERVICES WITH OWNER AND ASSPECIFIED.

D. CONSTRUCT TEMPORARY CONSTRUCTION PARTITIONS WITHINEXISTING BUILDING WHICH OFFER A ONE-HOUR ENCLOSURE TOISOLATE DEMOLITION AND CONSTRUCTION WORK FROM GENERALPUBLIC AND AS DEEMED NECESSARY BY OWNER AND CODE OFFICIALHAVING JURISDICTION. COORDINATE LOCATIONS WITH OWNER ANDMAINTAIN MEANS OF EGRESS THROUGHOUT THE WORK.

E. MAINTAIN A SECURE AND WEATHER-TIGHT ENCLOSURE.F. VERIFY EXISTING CONDITIONS, DIMENSIONS, AND ELEVATIONS AND

NOTIFY ARCHITECT OF DISCREPANCIES.G. REMOVE EXISTING WALLS, DOORS, MILLWORK, PLUMBING FIXTURES,

CEILINGS, SOFFITS, MARKERBOARDS, ETC. IN THEIR ENTIRETY ANDAS REQUIRED TO EXECUTE DEMOLITION AND CONSTRUCTIONWORK DESCRIBED ON THE DRAWINGS AND DISPOSE OFF-SITE.

H. THE OWNER SHALL RESERVE THE RIGHT TO SALVAGE ANYMATERIALS.

I. PROVIDE PROTECTION FOR EXISTING BUILDING MATERIALS ANDEQUIPMENT FROM DAMAGE DUE TO DEMOLITION OR CONSTRUCTION-RELATED INCIDENT PERFORMED UNDER THIS CONTRACT.

J. REPAIR OR REPLACE ITEMS DAMAGED AS A RESULT OF DEMOLITIONOR CONSTRUCTION TO MATCH EXISTING FINISH AND /OR CONDITION.

K. EXISTING MATERIALS SHALL NOT BE REUSED UNLESS NOTEDOTHERWISE OR AS AUTHORIZED BY ARCHITECT.

L. VERIFY AND MAINTAIN LOCATION OF EXISTING POWER,COMMUNICATION AND DATA CABLES TO PREVENT INTERRUPTION OFSERVICE.

M. PATCH FLOOR, WALL AND CEILING PENETRATIONS RESULTING FROMREMOVAL OR REROUTING OF NEW OR EXISTING PIPING, DUCTWORK,CONDUIT, ETC. AS REQUIRED TO MAINTAIN FIRE SEPARATIONS.MATCH FINISH OF NEW OR EXISTING ADJACENT SURFACES.

N. CAP DISCONNECTED MECHANICAL PIPING LINES WITHIN WALL ORFLOOR. PATCH AND FINISH AS REQUIRED TO MATCH NEW OREXISTING ADJACENT SURFACES.

O. SEE MECHANICAL AND ELECTRICAL DRAWINGS AND NOTES FORFURTHER SEQUENCING AND SCOPE OF WORK.

P. AVOID DISTURBING OF SOILS WITHIN ZONE OF INFLUENCE AROUNDEXISTNG FOOTINGS AND FLOOR SLABS AS DIRECTED BYGEOTECHNICAL ENGINEER.

Q. WHERE CMU WALLS ARE INDICATED TO BE REMOVED; PREPAREADJACENT WALLS TO RECEIVE NEW PATCH/FINISH BY REMOVINGCMU IN TOOTH-IN PATTERN BOTH SIDES OF DEMOLITION FORCONTRACTOR TO TOOTH IN NEW CMU PATCHES.

R. WHERE PLASTER/STUD WALLS ARE INDICATED TO BE REMOVED;PREPARE ADJACENT WALLS TO RECEIVE NEW PATCH/FINISH BYSAWCUTTING ADJACENT PLASTER FINISH A MINIMUM OF 12 INCHESBEYOND DEMOLITION.

Arch

itect

ure

Eng

inee

ring

Pla

nnin

g In

terio

rs

©

, DLR

Gro

up in

c., a

Neb

rask

a co

rpor

atio

n, A

LL R

IGH

TS R

ESER

VED

KEY PLAN

BA

NORTH

Revis

i ons

5/8/

2017

2:3

0:04

PM

C:\R

evit\

10-1

6206

-00_

AR_2

016_

Cen

tral_

sbur

gess

.rvt

10-1

6206

-00

5/08

/17

STAT

E O

F N

EBR

ASKA

501

BU

ILD

ING

REN

OVA

TIO

ND

EMO

LITI

ON

PLA

N, L

OW

ER L

EVEL

-AR

EA A

DA1.

0A

2017

PRIN

TSH

OP

BUIL

D O

UT

& ST

RU

CTU

RAL

DEF

ICIE

NC

Y R

ENO

VATI

ON

NORTHSCALE: 1/8" = 1'-0"DEMOLITION PLAN, LOWER LEVEL -AREA A

Page 5: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

UP

6

7

5

4

3

2

1

H I J K L M

8

1

1 REMOVE STUD WALL IN ITS ENTIRETY

2 REMOVE DOOR AND ASSOCIATED HARDWARE AND FRAME

2

3

4

3 REMOVE TOILET PARTITIONS IN THEIR ENTIRETY

4 REMOVE RESTROOM VANITY AND ASSOCIATED PLUMBING

5 REMOVE ELECTRIC WATER COOLER AND RETURN TO OWNER

4

3

25

2

1

2

2

6 REMOVE CMU WALL IN ITS ENTIRETY

7

7 REMOVE DOOR, ASSOCIATED HARDWARE AND FRAME WITH SIDELIGHT

7

1

1

1

1

12

1

1

1

1 11

2

2

1

2

2

2

1

1

1

2

2

8 REMOVE CEILING PADS AND ASSOCIATED GRID IN ITS ENTIRETY

8

9

9 REMOVE VCT FLOORING MATERIAL IN ITS ENTIRETY. REMOVE ADHESIVE ANDCLEAN SURFACE READY FOR INSTALLATION OF NEW FLOORING MATERIAL - SEEROOM FINISH SCHEDULE FOR FLOORING TYPE

10

10 REMOVE CASEWORK IN ITS ENTIRETY INCLUDING ASSOCIATED PIPING

11 REMOVE SINK IN ITS ENTIRETY INCLUDING ASSOCIATED PIPING

1111

8

9

8

9

8

9

8

9

12 REMOVE GWB CEILING AND FRAMING IN ITS ENTIRETY

12 12

8

9

13 REMOVE CARD READER AND ASSOCIATED MAGNETIC LOCK AND RETURNTO OWNER IN GOOD WORKING CONDITION.

13

13

MATC

HLIN

E - A

REA

AMA

TCHL

INE

- ARE

A B

MATC

HLIN

E - A

REA

AMA

TCHL

INE

- ARE

A B

DEMOLITION KEY NOTES

14 SAW CUT CONCRETE SLAB TO EXTENTS SHOWN - USE WET SAW TOMINIMIZE DUST - SEE STRUCTURAL. LOCATE EXISTING CONDUIT PRIORTO DEMOLITION AND PROTECT FROM DAMAGE.

14

4' - 0"

39' -

3 7/8"

1

15' - 6"

15' -

6"

1415' - 6"

15' -

6"

1414

14 14 14

6

6

55/ A

11.1

5' - 1

9/16

"

1

1 15

9

9

215

15 REMOVE HM WINDOW FRAME IN ITS ENTIRETY

2

EXISTING UPS

EXISTINGN UPS ROOM MUST BE SEALED(INCLUDING AHU'S SERVING THIS ROOM)AND PROTECTED FROM DUST DURING ALLDEMOLITION AND CONSTRUCTION

Arch

itect

ure

Eng

inee

ring

Pla

nnin

g In

terio

rs

©

, DLR

Gro

up in

c., a

Neb

rask

a co

rpor

atio

n, A

LL R

IGH

TS R

ESER

VED

KEY PLAN

BA

NORTH

Revis

i ons

5/8/

2017

2:3

0:06

PM

C:\R

evit\

10-1

6206

-00_

AR_2

016_

Cen

tral_

sbur

gess

.rvt

10-1

6206

-00

5/08

/17

STAT

E O

F N

EBR

ASKA

501

BU

ILD

ING

REN

OVA

TIO

ND

EMO

LITI

ON

PLA

N, L

OW

ER L

EVEL

-AR

EA B

DA

1.0B

2017

PRIN

TSH

OP

BUIL

D O

UT

& ST

RU

CTU

RAL

DEF

ICIE

NC

Y R

ENO

VATI

ON

NORTHSCALE: 1/8" = 1'-0"DEMOLITION PLAN, LOWER LEVEL -AREA B

Page 6: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

REF

.

UP

UP

CART STORAGE022A

HALL023

WOMEN'S024

MEN'S025

JAN026

BREAK ROOM027

FUTURE UPS028

ELECTRICAL029

CORRIDOR041

CORRIDOR022

CG

CG

CG

CG

CG

CR

PHASE No 1 SCOPE OF WORKWORK TO COMMENCE JUNE 1, 2017AND BE COMPLETE DECEMBER 1, 2017

PHASE No. 2 SCOPE OF WORKWORK TO COMMENCE DECEMBER 2, 2017 AND BECOMPLETE JUNE 1, 2018

MATC

HLIN

E - A

REA

AMA

TCHL

INE

- ARE

A B

MATC

HLIN

E - A

REA

AMA

TCHL

INE

- ARE

A B

122 SF

RECORDS STORAGE007

130 SF

CART STORAGE004

780 SF

MECHANICAL009

262 SF

RECEPTION006

138 SF

OFFICE010

475 SF

CONFERENCE012

59 SF

FILES008C

1998 SF

PRE-PRESS/DIGITAL GRAPHICS016

688 SF

OPEN OFFICE008

519 SF

CORRIDOR001

1878 SF

SECURED PRINT020

684 SF

COLOR COPY019

251 SF

SECURED STORAGE021

332 SF

HALL005

117 SF

OFFICE014

138 SF

OFFICE008A

67 SF

SCHED.017

94 SF

OFFICE018

120 SF

HALL008B

158 SF

OFFICE011

117 SF

OFFICE015

110 SF

CART STORAGE002

72 SF

ELEC/DATA003

4467 SF

FUTURE031

NEW SECURE PRINT ROOM TOBE COMPLETED AND FULLYOPERATIONAL PRIOR TODEMO'ING ITS CURRENTLOCATION

PHASING NOTES & KEY

AREA A / PHASE 1 - THIS AREA NEEDS TO BE COMPLETED BEFORE DECEMBER 1, 2017 AND PRIOR TO DEMOLITION OF AREA B.

AREA B / PHASE 2- THIS AREA WORK TO COMMENCE DECEMBER 2, 2017 AND BE COMPLETE BY JUNE 1 2018.

Arch

itect

ure

Eng

inee

ring

Pla

nnin

g In

terio

rs

©

, DLR

Gro

up in

c., a

Neb

rask

a co

rpor

atio

n, A

LL R

IGH

TS R

ESER

VED

KEY PLAN

BA

NORTH

Revis

i ons

5/8/

2017

2:3

0:08

PM

C:\R

evit\

10-1

6206

-00_

AR_2

016_

Cen

tral_

sbur

gess

.rvt

10-1

6206

-00

5/08

/17

STAT

E O

F N

EBR

ASKA

501

BU

ILD

ING

REN

OVA

TIO

NLO

WER

LEV

EL P

HAS

ING

PLA

N, L

OW

ER L

EVEL

- AR

EAS

A& B

PH1.

1

2017

PRIN

TSH

OP

BUIL

D O

UT

& ST

RU

CTU

RAL

DEF

ICIE

NC

Y R

ENO

VATI

ON

NORTHSCALE: 1" = 10'-0"PHASING PLAN, LOWER LEVEL - AREAS A & B

Page 7: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

REF

.

UP

UP

CART STORAGE022A

HALL023

WOMEN'S024

MEN'S025

JAN026

BREAK ROOM027

FUTURE UPS028

ELECTRICAL029

CORRIDOR041

CORRIDOR022

CG

CG

CG

CG

CG

CR

MATC

HLIN

E - A

REA

AMA

TCHL

INE

- ARE

A B

MATC

HLIN

E - A

REA

AMA

TCHL

INE

- ARE

A B

LUMP SUM BASE BID A:BREAK OUT No. A1: PROVIDE THE COST FOR THE WORK ASSOCIATED WITH BREAK ROOM 027.

122 SF

RECORDS STORAGE007

130 SF

CART STORAGE004

780 SF

MECHANICAL009

262 SF

RECEPTION006

138 SF

OFFICE010

475 SF

CONFERENCE012

59 SF

FILES008C

1998 SF

PRE-PRESS/DIGITAL GRAPHICS016

688 SF

OPEN OFFICE008

519 SF

CORRIDOR001

1878 SF

SECURED PRINT020

684 SF

COLOR COPY019

251 SF

SECURED STORAGE021

332 SF

HALL005

117 SF

OFFICE014

138 SF

OFFICE008A67 SF

SCHED.017

94 SF

OFFICE018

120 SF

HALL008B

158 SF

OFFICE011

117 SF

OFFICE015

110 SF

CART STORAGE002

72 SF

ELEC/DATA003

FUTURE031

LUMP SUM BASE BID B:BREAK OUT No. B2: PROVIDE THE COST FOR THE WORK ASSOCIATED WITH THE STRUCTURAL DEFICIENCY IN AREA B, EXCLUDINGBREAK ROOM/027, WOMEN'S RESTROOM/024, MEN'S RESTROOM/025, AND JANITOR ROOM/026.

LUMP SUM BASE BID B:BREAK OUT No. B2: PROVIDE THE COST FOR THE WORK ASSOCIATED WITH THE ADA UPGRADES IN RESTROOMS 024, 025, AND JANITOR 026

BREAK OUT COST LEGEND:

NOTE: BREAK OUT COSTS ASSOCIATED WITH THE LUMP SUM BASE BIDS. SEE SPECIFICATION SECTION 004113PROPOSAL FORM.

EXISTING PRINT SHOP

LUMP SUM BASE BID B:BREAK OUT No. B3: PROVIDE THE COST FOR THE WORK ASSOCIATED WITH THE HVAC IN AREA A.

Arch

itect

ure

Eng

inee

ring

Pla

nnin

g In

terio

rs

©

, DLR

Gro

up in

c., a

Neb

rask

a co

rpor

atio

n, A

LL R

IGH

TS R

ESER

VED

KEY PLAN

BA

NORTH

Revis

i ons

5/8/

2017

2:3

0:09

PM

C:\R

evit\

10-1

6206

-00_

AR_2

016_

Cen

tral_

sbur

gess

.rvt

10-1

6206

-00

5/08

/17

STAT

E O

F N

EBR

ASKA

501

BU

ILD

ING

REN

OVA

TIO

NBR

EAK

OU

T C

OST

PLA

N, L

OW

ER L

EVEL

- AR

EAS

A &

BPH

1.2

2017

PRIN

TSH

OP

BUIL

D O

UT

& ST

RU

CTU

RAL

DEF

ICIE

NC

Y R

ENO

VATI

ON

NORTHSCALE: 1/16" = 1'-0"COST BREAK OUT PLAN, LOWER LEVEL - AREAS A & B

Page 8: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

BA C C.1

5/8" GYPSUM WALL BOARD

3 5/8" METAL STUD

16 GAUGE STEEL MESH

DEMOUNTABLE WALL PANELOWNER PROVIDED/OWNER INSTALLED

5/8" GYPSUM WALL BOARD

3 5/8" METAL STUD

SOUND BATT INSULATION @ C.1SOUND BATT INSULATION

4 7/8"

5"2 1/2"

D

5/8" GYPSUM WALL BOARD

3 5/8" METAL STUD

E

(2) LAYERS 5/8" GYPSUM WALL BOARD BOTH SIDES

3 5/8" METAL STUD

SOUND BATT INSULATION @ C.1

6 1/8"

F

5/8" GYPSUM WALL BOARD

6" COLD FORMED METAL STUD

SOUND BATT INSULATION

7 1/4"

G

5/8" GYPSUM WALL BOARD

6" METAL STUD

SOUND BATT INSULATION

7 9/16

"

16 GAUGE STEEL MESH

ROOM FINISH SCHEDULE GENERAL NOTES

A. ROOM FINISH SCHEDULE GENERAL NOTES APPLY TOALLROOM FINISH SCHEDULE SHEETS.

B. SEE SPECIFICATIONS FOR PAINTING OF ITEMS NOT NOTED INTHE ROOM FINISH SCHEDULE.

C. EXPOSED CONCRETE FLOOR SLABS NOT SCHEDULED TORECEIVE A FINISH SHALL RECEIVE A CURING AND SEALINGCOMPOUND UNLESS OTHERWISE NOTED.

D. ALL GYPSUM WALLBOARD BULKHEADS SHALL BE PAINTED P-3UNLESS OTHERWISE NOTED.

E. CEILING HEIGHTS, AS NOTED ON THE REFLECTED CEILING,PLANS ARE MEASURED FROM THE FINISH FLOOR OF THEROOM.

F. CONTRACTOR SHALL FURNISH AND INSTALL WALL BASEAROUND CASEWORK AND MILLWORK.

G. WHERE FLOOR FINISH CHANGES FROM ONE ROOM TOANOTHER, SET JOINT OF THE MATERIALS AT THE CENTER OFTHE COMMUNICATING DOOR.

H. SEE REFLECTED CEILING PLANS FOR CEILING TYPES ANDHEIGHT.

METAL DECK

STEEL JOISTSEE STRUCTURAL

SEALANT ATPENETRATIONS

GWB, SEE WALLTYPES FORTHICKNESS ANDNUMBER OFLAYERSMETAL STUDS,SEE WALLTYPESFOR SIZE ANDGAUGE

SCRIBE TO IRREGULARITIES OF DECK

1"

BOTTOM OF METAL DECKOR FLOOR

16 GA RECEIVERCHANNEL CONT W/2 1/2" MIN LEGS

NO CONNECTION BETWEENCHANNEL AND TRACK

3/16" DIA x 1 1/4" SCREWANCHORS @ FLOORS, NO8x18 SCREWS @ ROOF @2'-8" OC MAX

STABILIZE STUDS AT TOPW/ CONT CHANNEL ANDBRIDGE CLIP AT EACH STUD

GWB

FIN CLG - SEE ROOM FINISH SCHEDULESCHEDULE FOR HEIGHT

1"4"

MIN

ROOM FINISH SCHEDULE SPECIFIC NOTES(these notes are referenced in the “comments” column of the roomfinish schedules)

FLOOR NOTES:

F1. REFER TO FLOOR PLAN SHEETS FOR SPECIFIC FLOOR FINISHLOCATIONS.

F2. CARPET PROVIDED BY OWNER.

F3. REFER TO FLOOR PLAN SHEETS FOR FLOOR FINISH TILEDIRECTION.

F4. THIN-SET CERAMIC TILE FLOORS.

WALL NOTES:

W1. REFER TO FLOOR PLAN SHEETS FOR SPECIFIC WALL FINISHLOCATIONS.

W2. RESILIENT WALL COVERING WAINSCOT TO 3'-6" ABOVE FINISHFLOOR.

W3. REFER TO A11 SERIES SHEET FOR WALL TILE ELEVATION.

W4. INTEGRAL ERF COVE BASE.

METAL DECK

STEEL JOISTSEE STRUCTURAL

FIRE-RATED SEALANTAT PENETRATIONS

GWB, SEE WALLTYPES FORTHICKNESS ANDNUMBER OFLAYERSMETAL STUDS,SEE WALLTYPESFOR SIZE ANDGAUGE

GENERAL NOTES

A. GENERAL NOTES APPLY TO ALL SHEETS.B. DIMENSIONS ARE ACTUAL AND ARE TO FACE OF STUDS, FACE

OF CONCRETE WALLS, FACE OF CMU WALLS, FACE OF FRAMESOR CENTERLINE OF COLUMNS, UNLESS NOTED OTHERWISE.

C. NOT USED.D. WALL TYPES SHALL BE DESIGNATED ON FLOOR PLANS THUS

x . SEE SHEET A0.1 FOR WALL TYPES.E. INTERIOR STUD WALLS SHALL EXTEND TO UNDERSIDE OF

FLOOR OR ROOF DECK ABOVE UNLESS NOTED OTHERWISE.SEE REFLECTED CEILING PLAN NOTES.

F. PROVISIONS SHALL BE MADE AT FULL HEIGHT NONBEARINGWALLS FOR 1-INCH VERTICAL MOVEMENT OF BUILDINGSTRUCTURE WITHOUT TRANSFER OF COMPRESSIVE LOADS TOWALL. FILL IRREGULARITIES BETWEEN TOP OF WALL AND DECKABOVE WITH FIRE SAFING INSULATION OR FIRE STOPPINGMATERIALS AS REQUIRED TO MEET FIRE RATING OFRESPECTIVE WALLS. SEE DETAILS ON SHEET A0.1.

G. SEE SHEET CP1.1 FOR LOCATION OF FIRE-RESISTANCE-RATEDWALLS. WALLS OF FIRE-RESISTANCE-RATED CONSTRUCTIONSHALL EXTEND TO UNDERSIDE OF FLOOR OR ROOF DECKABOVE. SEE DETAIL 41/A0.1 FOR HEAD TO DECK CONNECTION.

H. SEAL PENETRATIONS THROUGH FIRE-RESISTANCE-RATEDCONSTRUCTIONS WITH THROUGH- PENETRATION FIRESTOPMATERIAL AS REQUIRED TO ACHIEVE RESPECTIVE FIRE-RESISTIVE RATING AND SMOKE STOPPAGE.

I. SEE STRUCTURAL DRAWINGS FOR BRACING OF NONLOADBEARING MASONRY WALLS.

J. FURNISH AND INSTALL FIRE-RETARDANT-TREATED WOODBLOCKING OR METAL BACKING PLATE IN STEEL STUDPARTITIONS FOR PROPER ANCHORAGE OF WALL ATTACHEDITEMS; I.E. TOILET ACCESSORIES, TOILET PARTITIONS,CASEWORK, MILLWORK, WALL-MOUNTED FIXTURES,MARKERBOARDS, TACKBOARDS, DOOR STOPS, AUDIO VISUALBRACKETS, ETC.

K. GYPSUM BOARD AND PLASTER SURFACES SHALL BE ISOLATEDWITH CONTROL JOINTS WERE INDICATED ON DRAWINGSAND/OR AS DESCRIBED IN THE SPECIFICATIONS.

L. MASONRY CONTROL JOINTS (CJ) AND CONTROL JOINTS ABOVE(CJA) SHALL BE LOCATED AS INDICATED ON FLOOR PLANS ANDBUILDING ELEVATIONS, AND WHERE LARGE PLUMBING VENTSOR RISERS OCCUR IN SINGLE WYTHE MASONRY WALLS, ANDWHERE MASONRY WALLS BEARING ON CONCRETE FLOORSLABS ABUT MASONRY WALLS BEARING ON CONCRETEFOOTINGS OR AS INDICATED ON DRAWINGS.

M. THE OWNER SHALL FURNISH AND CONSTRACTOR SHALLINSTALL THE FOLLOWING: 1. CARPET.

N. INCLUDE OWNER-FURNISHED AND INSTALLED ITEMS ANDOWNER FURNISHED AND CONTRACTOR INSTALLED ITEMS INTHE CONSTRUCTION SCHEDULE, AND COORDINATE WITHOWNER TO ACCOMMODATE THESE ITEMS.

O. COORDINATE MECHANICAL CHASE SIZES WITH MECHANICALCONTRACTOR.

P. COORDINATE WITH MECHANICAL AND ELECTRICALCONTRACTORS SIZE AND LOCATION OF EQUIPMENT PADSINDICATED ON FLOOR PLANS.

Q. “MBD AND TBD” INDICATE MARKERBOARDS AND TACKBOARDSON FLOOR PLANS. LENGTH PRECEDES THE DESIGNATION(EXAMPLE 16’ MBD). BOARDS ARE 48 INCHES TALL. SEE WALLELEVATIONS OR SPECIFICATIONS FOR MOUNTING HEIGHT.

R. NOT USED.S. EXTEND FURRING CHANNELS AND GYPSUM BOARD UP MINIMUM

4 INCHES ABOVE FINISHED CEILING ON CMU WALLS.T. FIRE-RATED ENCLOSURES AROUND STEEL COLUMNS SHALL BE

CONTINUOUS FROM FLOOR TO UNDERSIDE OF FLOOR OR ROOFDECK ABOVE FOR EACH LEVEL.

U. SCRIBE GYPSUM BOARD OF WALL AND PARTITIONS TOIRREGULARITIES OF DECK ABOVE. SEAL TIGHTLY AROUNDPENETRATIONS.

6"

1' - 1"

AT GWB WALL

GWB/METAL STUD WALL - SEE PLANSFOR WALL TYPE

6"

10 1/2" RO

1' - 1"

2 1/2"

4" R

O

6 1/2"

TO MAINTAIN A 1-HOUR RATING BEHINDFEC'S AT AN 8" CMU WALL, EITHERPROVIDE A 4" SOLID BLOCK OR AN 8"CUT CMU W/ 2" SOAPS AND ALL VOIDSGROUTED SOLID

NOTE:VERIFY ROUGH OPENING DIMENSIONWITH CABINET MFR - TOP OF RO @ 4'-8" AFF

AT CMU WALL

6 1/2"

2 1/2"

4" R

O

10 1/2" RO

3 5/8" x 20GA METAL STUD BRACING@ 32" O.C.

3 5/8" x 20GA METALSTUDS @ 16" O.C.

5/8" GWB

SUSP APC

FINISH CEILINGAS SCHEDULED

4"4"

3 5/8" x 20GA METAL STUD BRACING@ 32" O.C.

3 5/8" x 20GA METALSTUDS @ 16" O.C.

5/8" GWB

SUSP APC

FINISH CEILINGAS SCHEDULED

4"4"

FINISH CEILINGAS SCHEDULED

INTERIOR FINISH ABBREVIATIONSABBREV. DESCRIPTIONCPT CARPETCT-1 CERAMIC TILE - 1ERF-1 EPOXY RESIN FLOOR - 1HPC-1 HIGH PERFORMANCE COATING - 1LVT-1 LUXURY VINYL TILE - 1 P-1 PAINT -1P-3 PAINT - 3P-4 PAINT - 4PT-1 PORCELAIN TILE - 1RB-1 RUBBER (WALL) BASE - 1RWC-1 RESISTANT (ABUSE) WALL COVERING - 1SEAL CONC SEALED CONCRETEVWC-1 VINYL WALL COVERING - 1

D

F

F

EXISTING COLUMN

CONTINUOUS WALL GUARD

Arch

itect

ure

Eng

inee

ring

Pla

nnin

g In

terio

rs

©

, DLR

Gro

up in

c., a

Neb

rask

a co

rpor

atio

n, A

LL R

IGH

TS R

ESER

VED

Revis

i ons

5/8/

2017

2:2

9:45

PM

C:\R

evit\

10-1

6206

-00_

AR_2

016_

Cen

tral_

sbur

gess

.rvt

10-1

6206

-00

5/08

/17

STAT

E O

F N

EBR

ASKA

501

BU

ILD

ING

REN

OVA

TIO

NR

OO

M F

INIS

H S

CH

EDU

LE, G

ENER

AL N

OTE

S, W

ALL

TYPE

S &

DET

AILS

A0.

1

2017

PRIN

TSH

OP

BUIL

D O

UT

& ST

RU

CTU

RAL

DEF

ICIE

NC

Y R

ENO

VATI

ON

_ROOM FINISH SCHEDULE_BP1

ROOMFLOOR FINISH BASE FINISH

WALLCeiling Finish COMMENTSNUMBER NAME MATERIAL NORTH EAST SOUTH WEST

001 CORRIDOR ERF-1/LVT-1 -/RB-1 GWB/CMU RWC-1 RWC-1/VWC-1 RWC-1 RWC-1 - F1, F3, W1,W2, W4002 CART STORAGE ERF-1 - GWB/CMU RWC-1/P-1 RWC-1/P-1 RWC-1/P-1 RWC-1/P-1 - W2, W4003 ELEC/DATA SEAL CONC RB-1 GWB/CMU P-1 P-1 P-1 P-1 -004 CART STORAGE ERF-1 - GWB/CMU RWC-1/P-1 RWC-1/P-1 RWC-1/P-1 RWC-1/P-1 - W2, W4005 HALL SEAL CONC RB-1 GWB HPC-1 HPC-1 HPC-1/VWC-1 HPC-1 - W1006 RECEPTION CPT RB-1 GWB P-1 P-1 P-1 P-1 - F2007 RECORDS STORAGE CPT RB-1 GWB/CMU P-1 P-1 P-1 P-1 - F2008 OPEN OFFICE CPT RB-1 GWB P-1 P-1 P-1 P-1 - F2

008A OFFICE CPT RB-1 GWB P-1 P-1 P-1 P-1 - F2008B HALL CPT RB-1 GWB P-1 P-1 P-1 P-1 - F2008C FILES CPT RB-1 GWB P-1 P-1 P-1 P-1 - F2009 MECHANICAL SEAL CONC RB-1 GWB/CMU P-1 P-1 P-1 P-1 -010 OFFICE CPT RB-1 GWB/CMU P-1 P-1 P-1 P-1 - F2011 OFFICE CPT RB-1 GWB/CMU P-1 P-1 P-1 P-1 - F2012 CONFERENCE CPT RB-1 GWB/CMU P-1 P-1 P-1 P-1 - F2014 OFFICE CPT RB-1 GWB P-1 P-1 P-1 P-1 - F2015 OFFICE CPT RB-1 GWB P-1 P-1 P-1 P-1 - F2016 PRE-PRESS/DIGITAL GRAPHICS SEAL CONC RB-1 GWB/CMU HPC-1 HPC-1 HPC-1/VWC-1 HPC-1/VWC-1 - W1017 SCHED. SEAL CONC RB-1 GWB P-1 P-1 P-1 P-1 -018 OFFICE CPT RB-1 GWB P-1 P-1 P-1 P-1 - F2019 COLOR COPY SEAL CONC RB-1 GWB/CMU P-1 P-1 P-1 P-1 -020 SECURED PRINT SEAL CONC RB-1 GWB/CMU HPC-1 HPC-1 HPC-1 HPC-1 -021 SECURED STORAGE SEAL CONC RB-1 GWB/CMU P-1 P-1 P-1 P-1 -022 CORRIDOR ERF-1 - EXIST RWC-1/P-1 RWC-1/P-1 RWC-1/P-1 RWC-1/P-1 - W2, W4

022A CART STORAGE ERF-1 - EXIST/GWB RWC-1/P-1 RWC-1/P-1 RWC-1/P-1 RWC-1/P-1 - W2, W4023 HALL ERF-1 - EXIST HPC-1 HPC-1 HPC-1 HPC-1 - W4024 WOMEN'S PT-1 PB-1 GWB CT-1/P-1 CT-1/P-1 CT-1/P-1 CT-1/P-1 P-3 F3, F4,W3025 MEN'S PT-1 PB-1 GWB CT-1/P-1 CT-1/P-1 CT-1/P-1 CT-1/P-1 P-3 F3, F4, W3026 JAN SEAL CONC RB-1 GWB P-1 P-1 P-1 P-1 -027 BREAK ROOM LVT-1/CPT RB-1 GWB P-1 P-4 P-1 P-1/CT-1 - F1, F2, F3,W1028 FUTURE UPS SEAL CONC RB-1 GWB/EXIST P-1 P-1 P-1 P-1 -029 ELECTRICAL SEAL CONC RB-1 GWB/EXIST P-1 P-1 P-1 P-1 -031 FUTURE041 CORRIDOR ERF-1 - GWB HPC-1 HPC-1 HPC-1 HPC-1 - W4

SCALE: 1 1/2" = 1'-0"WALL TYPES

SCALE: 1 1/2" = 1'-0"A0.131 NON RATED WALL TO DECK CONNECTION

SCALE: 1 1/2" = 1'-0"A0.132 NON-RATED STUD SLIP CONNECTION

21A0.1

SCALE: 1 1/2" = 1'-0"A0.141 GWB FIRESMOKE STOP

NO SCALEA0.1

42 FEC DETAILS

SCALE: 1 1/2" = 1'-0"A0.151 GWB BULKHEAD

SCALE: 1 1/2" = 1'-0"A0.152 GWB BULKHEAD

SCALE: 1 1/2" = 1'-0"A0.143 PLAN DETAIL

Page 9: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

CR

CR

CR

CR

CR

UP

RECORDSSTORAGE

007

CART STORAGE004

MECHANICAL009

RECEPTION006

OFFICE010

CONFERENCE012

FILES008C

PRE-PRESS/DIGITALGRAPHICS

016

OPEN OFFICE008

CORRIDOR001

SECUREDPRINT

020

COLOR COPY019

SECUREDSTORAGE

021

17' -

5 1/8"

16' -

9 7/8"

003

004

006

007

009

011

012

005

019

016

021

HALL005

CG

CG

C.1

AAA

A

A

A

C.1

C.1

C.1C.1

B

B

OFFICE014

OFFICE008A

44' -

1 13/1

6"10

' - 0" 25' - 0"

OFFICE018

A

A A

C

G

HALL008B

014018CG

CG

FILE

S

FILE

S VWC-

1FU

LL H

GT

VWC-1FULL HGT

11' -

8 7/8"

OFFICE011

16' - 0" 14' - 0" 12' - 0"

10' - 0" 7' - 0" 6' - 4 1/2" 12' - 0" 12' - 0" 13' - 10 7/8" 15' - 10 3/4" 7' - 10 7/8"

015

010

008B

14' -

9"39

' - 9"

C.1

A

A

D

5'-0" HGTPARTITION

FD

30' -

0"7'

- 8 7/

8"10

' - 0"

6' - 4

7/8"

15' - 8 3/4"

FEC

FEC

FECFEC

OFFICE015

REPAIR AND PATCH GWB WALL READYFOR FINISH MATERIAL

005A

MATC

HLIN

E - A

REA

AMA

TCHL

INE

- ARE

A B

MATC

HLIN

E - A

REA

AMA

TCHL

INE

- ARE

A B

SCHED.017

C.1

AIR SHAFT OPEN TO ABOVE

23' - 0"

7' - 6

"

4" CONCHOUSEKEEPINGPAD

001

002

CART STORAGE002

ELEC/DATA003

CONT WALL GUARD

A

A

ERF

LVT

LVT

DIR.

CG020

2' - 4"

EXISTING PRINTSHOP

A0.142

A0.142

A0.142

A0.142

4' - 1"

3' - 0"

D8" CMU

REPAIR GWB WALL AFTER DEMOLITIONOF HIGH DENSITY STORAGE UNIT

C

C

C

CC

C

B

43' - 1 1/8"

24' - 10 7/8"

E

10' -

9"

8' - 1 1/4"

5' - 1

1/4"

1' - 2"2' - 11 11/16"

G

4" STL TUBE

4" STLTUBE

Arch

itect

ure

Eng

inee

ring

Pla

nnin

g In

terio

rs

©

, DLR

Gro

up in

c., a

Neb

rask

a co

rpor

atio

n, A

LL R

IGH

TS R

ESER

VED

KEY PLAN

BA

NORTH

Revis

i ons

5/8/

2017

2:2

9:47

PM

C:\R

evit\

10-1

6206

-00_

AR_2

016_

Cen

tral_

sbur

gess

.rvt

10-1

6206

-00

5/08

/17

STAT

E O

F N

EBR

ASKA

501

BU

ILD

ING

REN

OVA

TIO

NFL

OO

R P

LAN

, LO

WER

LEV

EL -A

REA

AA1

.0A

2017

PRIN

TSH

OP

BUIL

D O

UT

& ST

RU

CTU

RAL

DEF

ICIE

NC

Y R

ENO

VATI

ON

NORTHSCALE: 1/8" = 1'-0"LOWER LEVEL PLAN -AREA A

FURNITUREBY OWNER

Page 10: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

CR

CR

CR

REF

.

UP

CART STORAGE022A

HALL023

WOMEN'S024

MEN'S025

JAN026

BREAK ROOM027

FUTURE UPS028

ELECTRICAL029

CORRIDOR041

VENDVENDVEND

CORRIDOR022

029029A028028A

030A

024

025

026

033

CG

CG

CG

CG

C.1

C.1

C.1

C.1C.1

C.1

C.1

C.1C

C.1

C.1

C

C

C

CG

A11.151

030

28' -

0"

CPT

LVT

CPTLVT

3' - 0" 15' - 0 3/4"

39' - 7" 6' - 0 5/8"

25/ A

11.1

35/ A

11.1

35/ A

11.1

REV

FEC

FEC

EXISTING MECH

EXISTING UPS

EXISTINGELEVEQUIP

EXISTINGMECH

EXISTINGELEC

EXISTINGELEC

EXISTINGELEC

027

CONCRETE HOUSEKEEPING PADCOORDINATE WITH ELEC

MATC

HLIN

E - A

REA

AMA

TCHL

INE

- ARE

A B

MATC

HLIN

E - A

REA

AMA

TCHL

INE

- ARE

A B

7' - 0

"3'

- 11 5

/8"

022A

16' -

1 1/8"

6' - 6

"17

' - 9 1

/4"5'

- 5"

WALL GUARD

CONT. WALL GUARD

CG

CONT WALL GUARD

LVT

DIR.

PT DIR.

PT DIR.

LVT

DIR.

CT-1

P-4

F

F

27' - 11"

CGCG

CG

CG

CGCG

CG CG

CGCG

CG

CG

CGCG

CG

CG

CGCG

CG

55/ A

11.1

7' - 4 1/4" 17' - 0"

15' -

7 1/4"

9' - 9

3/8"

10' -

6"E

E

CONT

WAL

L GUA

RD

A0.142

A0.142

D D

DD

D

D

D

FUTURE031

A11.121

8' - 2

1/4"

A11.112

030B

3' - 3 5/8"

8' - 2

3/8"

FUTURE ROOMBY OWNER

FUTURE ROOMBY OWNER

FUTURE ROOMBY OWNER

FUTURE ROOMBY OWNER

FUTURE ROOMBY OWNER

FUTURE ROOMBY OWNER

A0.143

CONT. WALL GUARD

Arch

itect

ure

Eng

inee

ring

Pla

nnin

g In

terio

rs

©

, DLR

Gro

up in

c., a

Neb

rask

a co

rpor

atio

n, A

LL R

IGH

TS R

ESER

VED

KEY PLAN

BA

NORTH

Revis

i ons

5/8/

2017

2:2

9:48

PM

C:\R

evit\

10-1

6206

-00_

AR_2

016_

Cen

tral_

sbur

gess

.rvt

10-1

6206

-00

5/08

/17

STAT

E O

F N

EBR

ASKA

501

BU

ILD

ING

REN

OVA

TIO

NFL

OO

R P

LAN

, LO

WER

LEV

EL -A

REA

BA

1.0B

2017

PRIN

TSH

OP

BUIL

D O

UT

& ST

RU

CTU

RAL

DEF

ICIE

NC

Y R

ENO

VATI

ON

NORTHSCALE: 1/8" = 1'-0"LOWER LEVEL PLAN -AREA B

Page 11: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

6

7

5

4

3

2

1

HA B C D E F G

8

9

10

EXP STR

EXP STR EXP STR

EXP STR

APC8' - 8"

APC8' - 8"

APC8' - 6"

APC8' - 8"

APC8' - 8"

APC8' - 8"

APC8' - 8"

APC8' - 6"

MATC

HLIN

E - A

REA

AMA

TCHL

INE

- ARE

A B

MATC

HLIN

E - A

REA

AMA

TCHL

INE

- ARE

A B

APC8' - 6"

APC8' - 8" APC

8' - 8"

52A0.1

52A0.1

51A0.1

52A0.1

REFLECTED CEILING PLAN NOTES:

A. REFLECTED CEILING PLAN GENERAL NOTES APPLY TO ALLREFLECTED CEILING PLAN SHEETS.

B. ALL CEILING GRIDS/PANELS SHALL BE CENTERED IN EACHROOM UNLESS NOTED OTHERWISE.

C. CEILING HEIGHTS ARE AS NOTED ON THE REFLECTEDCEILING PLAN UNLESS NOTED OTHERWISE.

D. ALL ELECTRICAL FIXTURES, SPEAKERS, SMOKE ANDTHERMAL DETECTORS, MECHANICAL GRILLES, SPRINKLERHEADS, ETC.. SHALL BE CENTERED BETWEEN CEILINGGRIDS UNLESS NOTED OTHERWISE. SPRINKLER HEADSSHALL BE WITHIN A 3" RADIUS CENTERED BETWEENCEILING GRIDS.

E. IN ACOUSTICAL CEILING PANELS WITH SCORE IN THECENTER, CENTER DEVICES REFERENCED IN NOTED, INONE HALF OF THE TILE. DO NOT LOCATE ON THE SCORE.FOR APC WITH MULTIPLE SCORED PATTERNS,COORDINATE LOCATION WITH ARCHITECT.

F. PROVIDE SUSPENSION SYSTEM AROUND ELECTRICALFIXTURES, MECHANICAL GRILLES, DIFFUSERS, ETC. ATACOUSTICAL PANEL CEILINGS.

G. ALL DIMENSIONS ON REFLECTED CEILING PLANS AREACTUAL AND ARE TO THE FOLLOWING UNLESS NOTEDOTHERWISE:

1. FACE OF FINISHED WALL2. FACE OF FINISHED BULKHEADS3. CENTERLINE OF COLUMNS4. CENTERLINE OF TEES

H. IN AREAS WITH EXPOSED STRUCTURE CEILINGS,COORDINATE EXACT LOCATIONS OF MECHANICAL GRILLES,DIFFUSERS, DUCTWORK, AND ELECTRICAL FIXTURES WITHEACH RESPECTIVE SUBCONTRACTOR.

I. ALL WALLS EXTEND TO UNDERSIDE OF DECK EXCEPTTHOSE SHOWN SHADED IN WHICH GYPSUM BOARD ORMASONRY EXTENDS MIN. 4" ABOVE FINISHED CEILING. ALLMETAL STUDS EXTEND TO UNDERSIDE OF STRUCTURE.

Arch

itect

ure

Eng

inee

ring

Pla

nnin

g In

terio

rs

©

, DLR

Gro

up in

c., a

Neb

rask

a co

rpor

atio

n, A

LL R

IGH

TS R

ESER

VED

KEY PLAN

BA

NORTH

Revis

i ons

5/8/

2017

2:2

9:51

PM

C:\R

evit\

10-1

6206

-00_

AR_2

016_

Cen

tral_

sbur

gess

.rvt

10-1

6206

-00

5/08

/17

STAT

E O

F N

EBR

ASKA

501

BU

ILD

ING

REN

OVA

TIO

NR

EFLE

CTE

D C

EILI

NG

PLA

N, L

OW

ER L

EVEL

-AR

EA A

A3.0

A

2017

PRIN

TSH

OP

BUIL

D O

UT

& ST

RU

CTU

RAL

DEF

ICIE

NC

Y R

ENO

VATI

ON

NORTHSCALE: 1/8" = 1'-0"REFLECTED CEILING PLAN, LOWER LEVEL -AREA A

Page 12: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

S

SS S

S

SS

S3S3

S

S

SS

S

S3

SOS

S 3

S3 S3

S

S

S

S3

S3

OS

OS

OS

OS

ER

ER

ER

ER

ER ER

ER

S3

OS

OS

SS

S

OSOSOS

OS

OS

OS

OS

OS

OS

OS

S3

S

6

7

5

4

3

2

1

H I J K L M

8

EXP STR

EXP STREXP STR

APC8' - 8"

APC8' - 6"

APC8' - 8"

APC8' - 8"

APC8' - 8"

GWB8' - 8"

GWB8' - 8"

APC8' - 8"

GWB8' - 8"

MATC

HLIN

E - A

REA

AMA

TCHL

INE

- ARE

A B

MATC

HLIN

E - A

REA

AMA

TCHL

INE

- ARE

A B

GWB8' - 8"

GWB8' - 8"

51A0.1

51A0.1

51A0.1

COORDINATE CEILING GRIDLAYOUT WITH OWNER PRIORTO INSTALLATION

Arch

itect

ure

Eng

inee

ring

Pla

nnin

g In

terio

rs

©

, DLR

Gro

up in

c., a

Neb

rask

a co

rpor

atio

n, A

LL R

IGH

TS R

ESER

VED

KEY PLAN

BA

NORTH

Revis

i ons

5/8/

2017

2:2

9:53

PM

C:\R

evit\

10-1

6206

-00_

AR_2

016_

Cen

tral_

sbur

gess

.rvt

10-1

6206

-00

5/08

/17

STAT

E O

F N

EBR

ASKA

501

BU

ILD

ING

REN

OVA

TIO

NR

EFLE

CTE

D C

EILI

NG

PLA

N, L

OW

ER L

EVEL

-AR

EA B

A3.

0B

2017

PRIN

TSH

OP

BUIL

D O

UT

& ST

RU

CTU

RAL

DEF

ICIE

NC

Y R

ENO

VATI

ON

NORTHSCALE: 1/8" = 1'-0"REFLECTED CEILING PLAN, LOWER LEVEL -AREA B

PRIOR TO INSTALLING NEW CEILINGS,ADDRESS /CORRECT WATER LEAKSCOMING FROM ABOVE

Page 13: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

1

SEE

SCHE

D

SEE SCHED

7' - 0

"2"

7' - 2

"

3' - 4" 2' - 0"5' - 4"

2"

2

4"2'

- 2"

4"4'

- 2"

2"

CTG

4' - 10" 6' - 0" 4' - 10"

15' - 8"

10"

7' - 4

"2"

8' - 4

"

CTG

3LOCK AND BOLT BYFRAMELESS MFR.GC TO PROVIDE CYLINDER

ALUM BASE

ALUM HEAD

1/2"GLASS -TYP

CTG

CTG

RECESSED MAGNETIC LOCK

.SLIDE

COUNTERTOP

SLIDING WINDOW TIED TOSMOKE DETECTION TOCLOSE AUTOMATICALLY

4' - 8

"

5' - 8"

EQ EQ

4

HM FRAME

HM HM ALUM STEEL

CTG CTG

A B

SEE

SCHE

D

SEE SCHED

3' - 6

"2'

- 8"

10"

SEE SCHED

BY DOOR MFR

SEALANT - BOTHSIDES

HOLLOW METALFRAME

DOOR

GYPSUM BOARDON METAL STUDFRAMING

JAMB ANCHOR

4"

WALL WHEREOCCURS

TILE WHEREOCCURS

WALL WHEREOCCURS

SEALANT - BOTHSIDES

HOLLOW METALFRAME

DOOR

METAL STUD HEADER - SEEDETAIL 1 THIS SHEET

GYPSUM BOARD

TILE WHERESCHEDULED

++

++

++

1(MIN.)1

11(MIN.)

OPENING WIDTHHEADER SCHEDULE

2 - 12" x 18 GA.

HEADER SIZE2 - 3-5/8" x 20 GA.

2 - 10" x 20 GA.2 - 8" x 20 GA.

15-1" TO 20'-0"

0 TO 5'-0"

NOTES:

10'-1" TO 15'-0"5'-1" TO 10'-0"

1. HEADERS SHALL BE UNPUNCHED AND OF THESIZE AND GAUGE LISTED.

2. PROVIDE BRACES TO STRUCTURE FOROPENINGS OVER 15'-0"

3. HEADERS SHALL BE FILLED WITH SOUNDDEADENING INSULATION MATERIAL.

4. SEE STRUCTURAL DRAWINGS FOR HEADERCONSTRUCTION AT EXTERIOR STUD WALLS.

JOIST OR BEAM - SEESTRUCTURAL DRAWINGS

SEE STRUCTURAL DETAILSFOR RATED AND NON-RATEDCONNECTION TO STRUCTUREGYPSUM BOARD NOT SHOWNFOR CLARITY

ATTACH METAL STUDS TOSTEEL ANGLE WITH (2) #10SELF-TAPPING SCREWS

4" X 4" X 12 GA. X 4" LONGSTEEL ANGLE WITH POWDERACTUATED FASTENER(2 PINS) AT EACH BRACE.

3-5/8" X 20 GA. BRACE AT 4'-0"O.C. PROVIDE 2 #10 AT EACHBRACE

METAL STUD-SEEHEADER SCHEDULEFOR SIZE

# 10 SELF-TAPPINGSCREWS AT 16" O.C.EACH SIDE - TOP ANDBOTTOM

METAL JACK STUDS

METAL RECEIVER CHANNELS

CONTROL JOINT LOCATIONS

TOP TRACK

CRIPPLE STUDS ABOVE HEADERTOP TRACK - SEE NOTE BELOW

HEADER - SEE STRUCTURAL

STIFFENER STUDS - SEE STRUCTURAL

BEARING STUD - SEE STRUCTURAL

BOTTOM TRACK

NOTE: SEESTRUCTURAL FORTYPICAL METALSTUD FRAMINGDETAILS

NOTE: ABOVE HEADER, PROVIDE 1/2"MIN CLEAR SPACE BETWEEN CRIPPLESTUDS AND STIFFENER STUDS BOTHSIDES OF ALL DOOR OPENINGS

TYP METAL STUD FRAMING AT DOOR OPENINGA

xBAX.X

TYP GWB CONTROL JOINT ABOVEB

GWB/METAL STUD WALL -SEE PLAN FOR WALL TYPE

DOOR FRAME BELOW

CONTROL JOINT

CRIPPLE STUDS @ 16" OC

STIFFENER STUDS - SEE STRUCTURAL

NOTE:AT DOUBLE LAYER GWB LOCATIONSMAINTAIN 1/2" CLEAR SPACE ATFIRST LAYER AND CONTROL JOINTAT SECOND LAYER

DOOR AND WINDOW FRAME SCHEDULE GENERAL NOTES

A. ALL HOLLOW METAL FRAMES IN MASONRY WALLS SHALL BEGROUTED SOLID.

B. HOLLOW METAL FRAMES IN METAL STUD WALLS SHALL BEFILLED WITH MINERAL WOOL INSULATION.

C. INSTALL EXTERIOR FRAMES WITH 1/4 INCH SHIM AND JOINTSEALANT AROUND PERIMETER OF FRAME.

D. MASONRY LINTELS AND STEEL LINTELS ARE INDICATED ONSTRUCTURAL DRAWINGS.

E. GLASS TYPES FOR FRAMES ARE INDICATED ON FRAMEELEVATIONS.

F. FRAME MANUFACTURER SHALL COORDINATE LOCATIONS OFCONCEALED CONDUIT AND J-BOXES REQUIRED FORSECURITY SYSTEM HARDWARE PRIOR TO MANUFACTURINGOF HOLLOW METAL FRAMES AND COORDINATE WITHSECURITY HARDWARE AND DEVICES.

G. SEE SPECIFICATIONS 087100 HARDWARE FOR HARDWARESET NOTED IN DOOR SCHEDULE.

METAL STUD WALL - SEE PLANS FORWALL TYPES

DOUBLE EGRESS HOLLOW METALFRAME - SEE DOOR AND FRAMESCHED.

DOOR - SEE DOOR AND FRAMESCHED.

SEALANT BOTH SIDES, TYP

FILL FRAME WITH MINERAL WOOLINSULATION

1/2" 1/2"STEEL FRAME

GLAZING

HEADER - SEE METAL STUDFRAMING DETAILS

METAL STUD WALL - SEE PLANS FORWALL TYPE

STEEL FRAME

METAL STUD WALL - SEE PLANS FORWALL TYPE

SSTL COUNTER

GLAZING

4"

METAL STUD WALL - SEE PLANS FORWALL TYPES

HOLLOW METAL FRAME - SEE SCHED.

GLAZING

SEALANT BOTH SIDES, TYP

FILL FRAME WITH MINERAL WOOLINSULATION

1/2" 1/2"4"

WALL WHERE OCCURS

APPLIED STOP

6" x 20GA METAL STUD BRACING @32" O.C.

6" x 20GA METALSTUDS @ 16" O.C.

5/8" GWB

SUSP APC

FINISH CEILINGAS SCHEDULED

4X4 STEEL ANGLE - SEE STR

ENTRY SYSTEM HEADER TUBE

ALUM RAIL

16 GA STEEL MESH

SOUND BATTS

3/4" PLYWOOD

GLAZING WHERE - SEE FRAME TYPES

ALUM RAIL

EXISTING CONC SLAB

FLOORING - SEE ROOM FINISH SCHED

SOUND BATT INSULATION

SEE PLAN FOR WALL TYPE

GLAZING

WALL WHERE OCCURS

SEALANT

16 GA STEEL MESH

4"2"

STUD WALL - SEE PLANS FOR WALLTYPE

SEE STRUCTURAL FOR JAMB DETAILS

WALL WHERE OCCURS

SEALANT BOTH SIDES - TYP

DOUBLE EGRESS HM FRAME - GROUTSOLID

Arch

itect

ure

Eng

inee

ring

Pla

nnin

g In

terio

rs

©

, DLR

Gro

up in

c., a

Neb

rask

a co

rpor

atio

n, A

LL R

IGH

TS R

ESER

VED

Revis

i ons

5/8/

2017

2:2

9:57

PM

C:\R

evit\

10-1

6206

-00_

AR_2

016_

Cen

tral_

sbur

gess

.rvt

10-1

6206

-00

5/08

/17

STAT

E O

F N

EBR

ASKA

501

BU

ILD

ING

REN

OVA

TIO

ND

OO

R A

ND

FR

AME

SCH

EDU

LEA

9.1

2017

PRIN

TSH

OP

BUIL

D O

UT

& ST

RU

CTU

RAL

DEF

ICIE

NC

Y R

ENO

VATI

ON

SCALE: 1/4" = 1'-0"INTERIOR FRAME ELEVATIONS -BP-1

SCALE: 1/4" = 1'-0"DOOR TYPES BP-1

_DOOR AND FRAME SCHEDULE -BP-1

NUMBER

DOOR PANEL FRAME

FIRE RATING HARDWARE SET

DETAILS

COMMENTS Door SecurityNO. OF PANELS WIDTH HEIGHT THICKNESS MATERIAL GLAZING TYPE DEPTH MATERIAL TYPE HEADJAMBLEFT JAMB RIGHT SILL

001 2 4' - 0" 8' - 0" 1 3/4" HM A 7 1/8" HM 1 90 MIN 4.0 21/A9.1 32/A9.1 32/A9.1 DOUBLE EGRESS002 2 3' - 6" 8' - 0" 1 3/4" HM A 5 3/4" HM 1 13.0 13/A9.1 11/A9.1 11/A9.1 SMOKE GASKETING003 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 1 17.0 13/A9.1 11/A9.1 11/A9.1 SMOKE GASKETING004 2 3' - 6" 8' - 0" 1 3/4" HM A 5 3/4" HM 1 13.0 13/A9.1 11/A9.1 11/A9.1 SMOKE GASKETING005 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 14.0 13/A9.1 11/A9.1 12/A9.1 SMOKE GASKETING005A 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 1 18.0 13/A9.1 11/A9.1 11/A9.1006 1 3' - 0" 7' - 0" 1 3/4" Glass CTG 4 1/2" ALUM 3 2.0 33/A9.1 43/A9.1 43/A9.1 53/A9.1 FRAMELESS, SMOKE GASKETING, PREP FRAME HEAD FOR FLUSH MAG

LOCKNo

007 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 1 10.0 13/A9.1 11/A9.1 11/A9.1008B 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 15.0 13/A9.1 11/A9.1 12/A9.1009 2 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 1 20.0 13/A9.1 11/A9.1 11/A9.1010 1 3' - 0" 7' - 0" 1 3/4" HM 3 1/2" HM 1.0 FFE OWNER PROVIDED OWNER INSTALLED011 1 3' - 0" 7' - 0" 1 3/4" HM 3 1/2" HM 1.0 FFE OWNER PROVIDED OWNER INSTALLED012 1 3' - 0" 7' - 0" 1 3/4" HM 3 1/2" HM 1.0 FFE OWNER PROVIDED OWNER INSTALLED014 1 3' - 0" 7' - 0" 1 3/4" HM 3 1/2" HM 1.0 FFE OWNER PROVIDED OWNER INSTALLED015 1 3' - 0" 7' - 0" 1 3/4" HM 3 1/2" HM 1.0 FFE OWNER PROVIDED OWNER INSTALLED016 2 3' - 6" 8' - 0" 1 3/4" HM CTG B 5 3/4" HM 1 21 13/A9.1 11/A9.1 11/A9.1 HALF LIGHT018 1 3' - 0" 7' - 0" 1 3/4" HM 3 1/2" HM 1.0 FFE OWNER PROVIDED OWNER INSTALLED019 2 3' - 0" 8' - 0" 1 3/4" HM CTG B 5 3/4" HM 1 21.0 13/A9.1 11/A9.1 11/A9.1 HALF LIGHT020 2 3' - 0" 8' - 0" 1 3/4" HM CTG B 5 3/4" HM 1 3.0 13/A9.1 11/A9.1 11/A9.1 HALF LIGHT021 2 3' - 0" 8' - 0" 1 3/4" HM A 5 3/4" HM 1 20.0 13/A9.1 11/A9.1 11/A9.1022A 2 3' - 6" 8' - 0" 1 3/4" HM A 5 3/4" HM 1 13.0 13/A9.1 11/A9.1 11/A9.1 SMOKE GASKETING024 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 1 19.0 13/A9.1 11/A9.1 11/A9.1025 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 1 19.0 13/A9.1 11/A9.1 11/A9.1026 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 1 16.0 13/A9.1 11/A9.1 11/A9.1027 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 6.0 13/A9.1 11/A9.1 12/A9.1 SMOKE GASKETING028 2 3' - 0" 8' - 0" 1 3/4" HM A 8 1/4" HM 1 12.0 13/A9.1 11/A9.1 11/A9.1 SMOKE GASKETING028A 1 3' - 0" 8' - 0" 1 3/4" HM A 8 1/4" HM 1 5.0 13/A9.1 11/A9.1 11/A9.1 SMOKE GASKETING029 1 3' - 0" 8' - 0" 1 3/4" HM A 8 1/4" HM 1 5.0 13/A9.1 11/A9.1 11/A9.1 SMOKE GASKETING029A 2 3' - 0" 8' - 0" 1 3/4" HM A 8 1/4" HM 1 12.0 13/A9.1 11/A9.1 11/A9.1 SMOKE GASKETING030 1 3' - 0" 7' - 0" 1 3/4" HM A 5 3/4" HM 2 7.0 13/A9.1 11/A9.1 11/A9.1 SMOKE GASKETING030A 2 3' - 6" 8' - 0" 1 3/4" HM A 8 1/4" HM 1 9.0 13/A9.1 11/A9.1 11/A9.1 SMOKE GASKETING033 2 3' - 0" 8' - 0" 1 3/4" HM A 5 3/4" HM 1 8.0 13/A9.1 11/A9.1 11/A9.1 SMOKE GASKETING

SCALE: 1 1/2" = 1'-0"A9.111 JAMB

SCALE: 1 1/2" = 1'-0"A9.113 HEAD

SCALE: 1" = 1'-0"A9.141 TYPICAL PARTITION HEADER

SCALE: 1 1/2" = 1'-0"A9.151 GWB CONTROL JOINTS @ DOOR FRAMES

34A9.1

44A9.1

SCALE: 1 1/2" = 1'-0"A9.121 HEAD @ DOUBLE EGRESS DOOR

SCALE: 1 1/2" = 1'-0"A9.122 INT. SLIDING WINDOW HEAD

SCALE: 1 1/2" = 1'-0"A9.123 INT. SLIDING WINDOW JAMB

SCALE: 1 1/2" = 1'-0"A9.112 HEAD / JAMB / SILL @ WINDOW

SCALE: 1 1/2" = 1'-0"A9.133 HEAD

SCALE: 1 1/2" = 1'-0"A9.153 SILL

SCALE: 1 1/2" = 1'-0"A9.143 JAMB

_WINDOW SCHEDULE_

FRAMEFIRE RATING

DETAILSCOMMENTSNUMBER TYPE MATERIAL DEPTH HEAD JAMB LEFT JAMB RIGHT SILL

030B 4 STEEL 5 3/4" SMOKE 22/A9.1 23/A9.1 23/A9.1 53/A11.1 SMOKE DETECTOR ACTIVATED - SEE SECTION 088000

SCALE: 1 1/2" = 1'-0"A9.132 JAMB-DBL EGRESS

Page 14: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

13' - 7"2' - 0" 3' - 6" 2' - 0" 3' - 0" 3' - 0"

MICROWAVE

2' - 0" 3' - 6" 2' - 0" 3' - 0" 3' - 0"

COFF

2' - 1

0"1'

- 8"

2' - 6

"

1' - 3

"

4' - 6

"1'

- 3"

CABINETS: PL-1COUNTERTOPS: 1/2" CORIAN OVER3/4" MARINE GRADE PLYWOOD

CT-1

FILLER PNL1"

FILLER PNL1"

MIRROR

34A11.1

CABINET: PL-1COUNTERTOP: SS-1

SS-1

PL-1

2' - 1

0"4"

3' - 6

"

8' - 0"

UNO

IN C

ASEW

ORK

ELE V

ATIO

NS2'

- 10 1

/2"SE

E EL

EVAT

IONS

SEE

ELEV

ATIO

NS

2' - 0"

RESILIENT BASE

COUNTERTOP AND BACKSPLASH, SEEELEVATIONS FOR FINISH MATERIAL

DRAWER WHERE OCCURS, SEEELEVATIONS

ADJUSTABLE SHELF

ADJUSTABLE SHELF

1' - 2"

3"

4"

SEE PLAN FOR WALL TYPE

1/2" SOLID SURFACE COUNTER OVER3/4" MARINE GRADE PLYWDSUSBSTRATE (TYP)

UNDERMOUNT SINK- SEE PLUMBING

FAUCET- SEE PLUMBING

RAKKS MADE TO ORDER EHV-VANITYSUPPORTS WITH PLAM REMOVABLEACCESS PANEL, ATTACH TO FURRINGSTRIPS, WHERE OCCURS

MIRROR

1' - 1

"1'

- 4"

5"

7"

WALL TILE AS SCHED.(TO UNDERSIDEOF COUNTERTOP)

9"

6" MIN

2' - 3

"

7" MAX 6" MAX 11" MIN

1' - 5" MIN

2' - 1

0"

STEEL ANGLE

RAKKS COUNTER SUPPORTBRACKET, FLUSH MOUNTINSTALLATION

BLOCKING AS REQUIRED

4"

MILLWORK GENERAL NOTES

A. MILLWORK GENERAL NOTES APPLY TO ALL MILLWORKSHEETS.

B. ELEVATIONS DENOTED AS MILLWORK ARE SPECIFIEDUNDER DIVISION 06.

C. BASE AND TALL STORAGE CABINETS: 24 INCHES DEEP,UNLESS NOTED OTHERWISE.

D. WALL CABINETS: 14 INCHES DEEP, UNLESS NOTEDOTHERWISE.

E. PROVIDE ADJUSTABLE SHELVING IN MILLWORK, UNLESSNOTED OTHERWISE.

F. WHERE ELECTRICAL DEVICES ARE LOCATED IN MILLWORK,MILLWORK CONTRACTOR SHALL PROVIDE FINISHEDOPENINGS. COORDINATE LOCATION AND QUANTITY WITHELECTRICAL CONTRACTOR.

G. PROVIDE JOINT SEALANT AT PERIMETER JOINTS WHERECOUNTERTOPS, BACK AND SIDE SPLASHES, MILLWORKABUT WALLS.

H. FIELD VERIFY DIMENSIONS OF CABINET LOCATIONS INBUILDING PRIOR TO FABRICATION.

I. PROVIDE FINISHED ENDS AT ALL EXPOSED ENDS OFMILLWORK.

J. ALL EXPOSED SURFACES IN OPEN SHELVING SHALL BEPLASTIC LAMINATE COVERED.

K. TYPICAL PLASTIC LAMINATE COUNTERTOP DETAIL, SEE14/A11.1

SIDE SPLASH AT SIDE WALLS

PARTICLEBOARD CORE TYP

1"4" 3/4"

VARIES

PLASTIC LAMINATE

BALANCING BACKER SHEET TYP

FACE OF BASE CABINET

3 MM PVC

1/4" X 1/2" PINE SCRIBE ATBACKSPLASH, SIDE SPLASHAND AT SIDE SPLASH FRONT EDGE

1/2"

P-1

CT-1

SEE FLOOR PLANVARIES

8' - 8

"

4' - 0

"

WALL GUARD

VINYL WALL COVERING

PAINT P-1

FLOOR LINE

2' - 1

0"8"

3' - 6

"

RESILIENT BASE

4"

1"

1' - 6"

2"14 GA STAINLESS STEELCOUNTER TOP

RADIUS FRONT EDGEOF COUNTER - SEE PLANS

2-LAYERS OF 3/4" PLYWOOD

3/4" PARTICLEBOARD SUB-TOP ANDCABINET BOTTOM. PLAM ON EXPOSEDSURFACE. PVC EDGE BAND ON FRONTEDGE3/4" ADJUSTABLE PARTICLEBOARDSHELF. PROVIDE PVC EDGE BANDFRONT AND BACK. PLAMALL SURFACES

1/2" PARTICLEBOARD BACK SET BACK7/8" AND FULLY HOUSED INTO CABINETSIDES, TOP AND BOTTOM - PLAM ALLEXPOSED SURFACES

3/4" PARTICLEBOARD CABINET ENDS.PL ALL EXPOSED SURFACES.PVC EDGE BAND ON FRONT EDGE.

3/4" THICK HANG RAILS

SEPARATE 3/4" EXT GRADE PLYWOODSUB-BASE - LADDER TYPECONSTRUCTION

T.O. SS COUNTER3'-6" AFF

SLIDING GLASS WINDOW

3' - 6

"

2x2 STL ANGLE

3"

2 3/4"

4"

3' - 6

"

.

4"1'

- 2"

10 1/

2" 1' - 0

"

3' - 2"8' - 0"

SLIDE

53A11.1

CABINET FRONTS PL-1

TTD

TTD

TTD

TTD

TTD

TTD

TTD

GB-3GB-1

GB-2

WR

US

WR

SND

SND

SND

SND

TTD

TTDSND

GB-3

GB-1

GB-2

1' - 8

"5'

- 0"

2' - 1

1"2'

- 11"

2' - 1

1"2'

- 6"

2' - 1

0"2'

- 11"

2' - 1

1"5'

- 0"

1' - 6

"

MR

SD

SD

MR

35/ A

11.1

CG

CG

CG

C

C.1

C.1

C

D

C

025

024

026

CLEA

R6'

- 6"

3' - 0"15' - 0 3/4"

A11.1

26

26

26

26

A11.1

26

26

26

26 C.1

DRINKINGFOUNTAINS

1' - 6 5/8"

CONTINUOUSWALL GUARD

CONTINUOUSWALL GUARD

C.1

24x24 ACCESS PANEL

24X24 ACCESSPANEL

4' - 9

3/8"

12' -

0"3'

- 0"

3' - 1

0 7/8"

10' -

5 3/8"

5' - 2

1/4"

C.1

D

MEN'S025

WOMEN'S024

JAN026

PTD

PTD

SD

SD

TOILET ACCESORIES SCHEDULEABBREV. DESCRIPTION MOUNTING HEIGHTGB-1 GRAB BAR (SIDE WALL) 2'-10" TO CENTER LINEGB-2 GRAB BAR (BACK WALL) 2'-10" TO CENTER LINEGB-3 GRAB BAR (VERTICAL) 3'-4" TO BOTTOMMR MIRROR 3'-2" TO BOTTOMPTD PAPER TOWEL DISPENSER 4'-3" TO TOP (ADA COMPLIANT)SD SOAP DISPENSERSND SANITARY NAPKIN DISPOSAL 2'-6" TO TOP (ADA COMPLIANT)TTD TOILET TISSUE DISPENSER 2'-6" TO TOP (ADA COMPLIANT)US UTILITY SHELF 6'-0" TO CENTER LINEWR WASTE RECEPTACLE (RECESSED) 3'-9" TO TOP (ADA COMPLIANT)

BREAK ROOM027

3' - 0

"5'

- 4"

2' - 0

"7 1

/2"

REFR(NIC)

CPT

LVT

CPTLVT

LVT

DIR

LVT

DIR

25/A

11.1

C.1

C.1

C.1B

FUTURE031

ELECTRICAL029

CORRIDOR041

55/A

11.1 030B

Arch

itect

ure

Eng

inee

ring

Pla

nnin

g In

terio

rs

©

, DLR

Gro

up in

c., a

Neb

rask

a co

rpor

atio

n, A

LL R

IGH

TS R

ESER

VED

Revis

i ons

5/8/

2017

2:3

0:01

PM

C:\R

evit\

10-1

6206

-00_

AR_2

016_

Cen

tral_

sbur

gess

.rvt

10-1

6206

-00

5/08

/17

STAT

E O

F N

EBR

ASKA

501

BU

ILD

ING

REN

OVA

TIO

NC

ASEW

OR

K, L

ARG

E SC

ALE

PLAN

S &

INTE

RIO

R E

LEVA

TIO

NS

A11

.1

2017

PRIN

TSH

OP

BUIL

D O

UT

& ST

RU

CTU

RAL

DEF

ICIE

NC

Y R

ENO

VATI

ON

SCALE: 1/4" = 1'-0"A11.125 CASEWORK ELEVATION

SCALE: 1/4" = 1'-0"A11.135 CASEWORK ELEVATION

SCALE: 1 1/2" = 1'-0"A11.154 TYP. BASE CABINET W/ UPPER

SCALE: 1 1/2" = 1'-0"A11.134 COUNTER LAV DETAIL- SOLID SURFACE

SCALE: 3" = 1'-0"A11.114 COUNTERTOP BACKSPLASH

SCALE: 1/4" = 1'-0"A11.126 RESTROOM WALL TILE ELEV.

SCALE: 1/4" = 1'-0"A11.145 TYP WALL GUARD ELEVATION

SCALE: 1 1/2" = 1'-0"A11.153 COUNTERTOP AT SLIDING WINDOW 030B

SCALE: 1/4" = 1'-0"A11.155 CASEWORK ELEVATION

SCALE: 1/4" = 1'-0"A11.151 LARGE SCALE FLOOR PLAN

SCALE: 1/4" = 1'-0"A11.121 Large Scale Plan-Break Room

SCALE: 1/4" = 1'-0"A11.112 LARGE SCALE FLOOR PLAN

Page 15: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

F O U N D A T I O N N O T E S

S T R U C T U R A L N O T E S

F R A M I N G N O T E S

CODE:

2012 INTERNATIONAL BUILDING CODE (2012 IBC)

GENERAL NOTES:1. THE DRAWINGS REPRESENT THE FINISHED STRUCTURE, NOT THE METHOD OF

CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECTTHE STRUCTURE DURING CONSTRUCTION INCLUDING, BUT NOT LIMITED TO, BRACING, SHORING FOR CONSTRUCTION LOADS AND EQUIPMENT, ETC. THE ARCHITECT-ENGINEER IS NOTRESPONSIBLE FOR THE CONTRACTOR'S MEANS AND METHODS, SEQUENCES OFCONSTRUCTION, OR THE SAFETY PROGRAM. OBSERVATION VISITS TO THE SITE BY THEARCHITECT-ENGINEER WILL NOT INVOLVE REVIEW OF THESE ITEMS.

2. CONTRACTOR IS TO ESTABLISH AND VERIFY OPENINGS AND INSERTS FOR ITEMS TO BEINSTALLED BY OTHER TRADES PRIOR TO SUBMITTAL OF SHOP DRAWINGS AND CONSTRUCTION.

3. CONSTRUCTION MATERIAL AND EQUIPMENT PLACED ON FRAMED CONSTRUCTIONS SHALL BESUCH THAT THE LOAD DOES NOT EXCEED THE DESIGN LIVE LOAD OF THE CONSTRUCTION.PROVIDE SHORING OF CONSTRUCTIONS WHERE NECESSARY FOR LOADS.

4. DETAILS THAT ARE NOTED AS "TYP." ON DETAIL TITLES ARE TO BE APPLIED TO THE PROJECTCONSTRUCTION AS GENERAL CONSTRUCTION METHODS UNLESS NOTED OTHERWISE. THESEDETAILS ARE NOT CUT AT ALL LOCATIONS THEY OCCUR AND MAY NOT BE CUT AT ALL. WHERENO SPECIFIC DETAILS ARE SHOWN CONSTRUCTION SHALL CONFORM TO SIMILAR CONDITIONSELSE WHERE ON THE PROJECT.

5. DO NOT SCALE DRAWINGS

6. THESE NOTES SHALL SUPPLEMENT THE PROJECT SPECIFICATIONS, WHICH SHALL BE REFERREDTO FOR ADDITIONAL REQUIREMENTS.

7. WHERE DISCREPANCIES OCCUR BETWEEN GENERAL NOTES, PLANS, DETAILS, ANDSPECIFICATIONS, THE MOST STRINGENT REQUIREMENTS SHALL GOVERN, UNLESS VERIFIED OTHERWISE BY THE ARCHITECT AND ENGINEER.

8. THESE DOCUMENTS SHALL NOT BE CONSTRUED AS STAND-ALONE DOCUMENTS.CONTRACTOR SHALL COORDINATE WITH ALL OTHER CONSULTANTS WORK.

9. SEE ARCHITECTURAL DRAWINGS FOR MISCELLANEOUS STEEL NOT SHOWN ON THESTRUCTURAL DRAWINGS. THIS INCLUDES BUT IS NOT LIMITED TO, STEEL AT ROOF DRAINS,EMBED PLATES AND STEEL ASSOCIATED WITH ARCHITECTURAL DETAILS.

10. SEE ARCHITECTURAL DRAWINGS FOR COMPLETE STRUCTURAL DIMENSIONS.

11. CONSTRUCTION DOCUMENTS SHALL NOT BE REPRODUCED FOR USE OF SHOP DRAWINGSSUBMITTALS OR ANY OTHER PROJECT WITHOUT WRITTEN CONSENT BY DLR GROUP.

12. IF THE STRUCTURAL ENGINEER'S SEAL AND SIGNATURE IS NOT AFFIXED TO THESE DRAWINGS,THESE DRAWINGS ARE INTENDED FOR PRELIMINARY PURPOSES ONLY AND SHALL NOT BE USEDFOR CONSTRUCTION.

DESIGN DEAD LOADS:EXISTING ROOF: 25 PSF (1986 CONSTRUCTION)

EXISTING FLOORS: 68 PSF (1986 CONSTRUCTION)

DESIGN LIVE LOADS:ROOF: SNOW LOADS IN ACCORD WITH INTERNATIONAL BUILDING CODE SECTION 1608,

INCLUDING DRIFT LOADS. Pf = Ce x Ct l x Pg Ce = 1.0 Ct = 1.0 l = 1.1 Pg = 30 PSF Pf = 23 PSF DRIFTING SNOW LOADS - DRIFT LOADS SHALL BE COMBINED WITH OTHER LOADS NOTED IN

ACCORDANCE WITH BUILDING CODE PRESCRIBED COMBINATIONS

FLOORS: THE BUILDING WAS ORIGINALLY DESIGNED FOLLOWING THE 1985 UNIFIED BUILDING CODE:

SNOW = 30 PSF (1986 CONSTRUCTION)FLOORS LIVE LOAD = 100 PSF (1986 CONSTRUCTION)DOCK = 250 PSF (1986 CONSTRUCTION)

NEW DESIGN LOADS FOLLOWING GOVERNING CODE IBC 2009:50 PSF (OFFICE)80 PSF (CORRIDORS ABOVE FIRST FLOOR)100 PSF (CORRIDORS / STAIRS / EXIT WAYS)125 PSF (STORAGE ROOMS)250 PSF (DATA CENTER)250 PSF (DOCK)

INCLUDE 15 PSF PARTITION LOAD FOR FLOORS WITH LIVE LOADS LESS THAN 80 PSF.

WIND LOAD:BASIC WIND SPEED (3-SECOND GUST), V = 120 MPH

EXPOSURE "C" IMPORTANCE FACTOR, Iw = 1.00 (RISK CATEGORY III PER TABLE 1604.5)

INTERNAL PRESSURE COEFFICIENT, GCpi = +/-0.18 (ENCLOSED BUILDING)

SEISMIC LOAD: SEISMIC DESIGN IS IN ACCORD WITH IBC, OCCUPANCY CATEGORY PER TABLE 1604.5 IS

CATEGORY III, S1 = .045 SS = 0.077 I = 1.25 SITE CLASS = D R = 2.0; Ωo = 2.5 Cd = 1.75 ORDINARY REINFORCED MASONRY SHEAR WALLS

SEISMIC DESIGN CATEGORY 'A'DESIGN BASE SHEAR: V = 0.01W

LATERAL LOAD RESISTANCE SYSTEM:1. LATERAL LOAD SYSTEM CONSISTS OF ROOF AND FLOOR DIAPHRAGMS TRANSFERRING

LATERAL LOADS TO MASONRY SHEAR WALLS. ORIGINAL LOAD RESISTANCE SYSTEM ISMAINTAINED.

FOUNDATIONS:1. FOUNDATION DESIGN IS BASED ON GEOTECHNICAL INVESTIGATION PERFORMED BY ALFRED

BENESCH & COMPANY JOB NO. 00111543.00, DATED JANUARY, 20, 2017. A COPY OF THEGEOTECHNICAL INVESTIGATION REPORT ARE INCLUDED IN THE PROJECT SPECIFICATIONS.BASED ON THE GEOTECHNICAL REPORT, THE FOLLOWING HAS BEEN ASSUMED:

- MINIMUM FROST DEPTH = 40"- ALLOWABLE SOIL BEARING PRESSURE = 3,000 PSF-

2. SUBGRADE SHALL BE PREPARED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS.CONTRACTOR SHALL READ AND FAMILIARIZE HIMSELF WITH THE GEOTECHNICAL REPORT. IFDISCREPANCIES EXIST BETWEEN PROJECT SPECIFICATIONS AND GEOTECHNICAL REPORT, THEMOST STRINGENT REQUIREMENTS SHALL GOVERN, UNLESS DETERMINED OTHERWISE BY THEENGINEER.

3. BACKFILLING AGAINST FOUNDATION WALLS WHERE GRADE IS PRESENT ON BOTH SIDES SHALL BE PERFORMED SUCH THAT THE DIFFERENCE IN SOIL HEIGHT ON EACH SIDE DOES NOT EXCEED 2 FEET.

4. TEMPORARY FROST PROTECTION SHALL BE PROVIDED DURING COLD WEATHER FOR ALLFOUNDATIONS.

5. CONTRACTOR SHALL PROVIDE FOR PROPER DEWATERING OF ALL EXCAVATIONS.

CONCRETE CONSTRUCTION:1. CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF ACI 301 AND

ACI 318.

2. PROVIDE A FORMED CONSTRUCTION KEYWAY BETWEEN ALL HORIZONTAL AND VERTICALPOUR EDGES EXCEPT CONCRETE TOPPING SLABS. PROVIDE WATERSTOPS FOR ALLCONSTRUCTION JOINTS BELOW WATER TABLE AND WHERE INTERIOR SLAB-ON-GRADE ISBELOW EXTERIOR GRADE.

3. CONCRETE SHALL BE MECHANICALLY CONSOLIDATED IN ACCORD WITH ACI 309.

4. CONTROL (CONTRACTION OR CONSTRUCTION) JOINTS SHALL BOUND ALL CONCRETESLABS ON GRADE AS SHOWN ON THE DRAWINGS. WHERE NOT SHOWN ON THEDRAWINGS, CONTROL JOINTS SHALL BE LOCATED SUCH THAT THE ENCLOSED AREA ISRELATIVELY SQUARE AND DOES NOT EXCEED 100 SQUARE FEET. REFERENCE TYPICALCONTROL JOINT LAYOUT DETAIL ON SHEET S3.1. GENERAL CONTRACTOR SHALL SUBMITCONTROL JOINT SHOP DRAWING FOR APPROVAL. KEYED JOINTS NEED ONLY TO OCCURAT CONSTRUCTION JOINTS. ALL CONTRACTION JOINTS MAY BE SAWCUT. DO NOT PROVIDECONTROL JOINTS IN STRUCTURAL CONCRETE SLABS AND CONCRETE TOPPINGS UNLESSSPECIFICALLY SHOWN ON THE STRUCTURAL DRAWINGS.

CONCRETE REINFORCEMENT:1. REINFORCING STEEL SHALL BE ASTM A615, GRADE 60. REINFORCING STEEL TO BE WELDED

SHALL BE ASTM A706, GRADE 60.

2. CONCRETE COVER REQUIREMENTS FOR CAST-IN-PLACE, NON-PRESTRESSED CONCRETEUNLESS OTHERWISE NOTED ON DETAILS:a. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3"b. FORMED CONCRETE EXPOSED TO EARTH OR WEATHER:

#6 BARS AND LARGER: 2"#5 BARS AND SMALLER: 1 1/2"

c. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH EARTH:SLABS, WALLS, AND JOISTS:#14 AND #18 BARS: 1 1/2"#11 BARS AND SMALLER: 1"

d. BEAMS, COLUMNS:PRIMARY REINFORCEMENT: 2”TIES, STIRRUPS, SPIRALS: 1 1/2"

3. REINFORCING BAR SPLICES SHALL BE IN ACCORD WITH THE REQUIREMENTS OF ACI 318-11AND THE REINFORCING SPLICE LENGTH TABLE SHOWN ON THE DRAWINGS. PROVIDE CLASS 'B' LAP SPLICE, UNO.

4. ALL REINFORCING SHALL BE PROPERLY CHAIRED BY THE CONTRACTOR.

5. LAP ALL WELDED WIRE REINFORCING AT LEAST ONE FULL WIRE SPACING PLUS 2 INCHES.

6. MECHANICAL COUPLERS SHALL BE TYPE 2 COUPLERS CAPABLE OF SUSTAINING 125% Fy.

CAST-IN-PLACE CONCRETE:1. PROPORTION EACH INDIVIDUAL CONCRETE MIX ACCORDING TO SPECIFICATIONS TO HAVE THE

FOLLOWING PROPERTIES: LOCATION 28 DAY F'c MIX TYP W/C RATIO

A FOOTING 3,000 PSI NWT 0.50 B FOUNDATION/RETAINING WALL 3,500 PSI NWT 0.45 C EXPOSED SLABS-ON-GRADE 4,000 PSI NWT 0.45 D SUSPENDED SLABS/TOPPINGS 4,000 PSI NWT 0.40

E SLABS WITH FLOOR COVERINGS 4,000 PSI NWT 0.40 F EXTERIOR CONCRETE AND 4,500 PSI NWT 0.45

PAVEMENT

NWT = NORMAL WEIGHT CONCRETE (UNIT WEIGHT = 145 PCF) * 6% ±1 1/2% AIR ENTRAINED CONCRETE AT ALL EXTERIOR CONDITIONS.

2. CONCRETE CONTAINING SUPERPLASTICIZING ADMIXTURE SHALL HAVE A SLUMP NOT EXCEEDING 3" PRIOR TO ADDING ADMIXTURE AND NOT EXCEEDING 8" AT PLACEMENT

3. THE ADDITION OF WATER TO A CONCRETE BATCH WITH INSUFFICIENT SLUMP SHALL NOT BEPERMITTED

4. SUBSTITUTION OF FLYASH FOR PORTLAND CEMENT IN SLABS ON GRADE AND STRUCTURALSLABSSHALL NOT BE PERMITTED.

MASONRY:1. THE MINIMUM 28-DAY COMPRESSIVE STRENGTH OF THE CONCRETE MASONRY UNITS SHALL BE

1,900 PSI ON THE NET AREA, PROVIDING A STRUCTURAL DESIGN COMPRESSIVE STRENGTH OF1,500 PSI PER THE INTERNATIONAL BUILDING CODE, TABLE 2105.2.2.1.2.

2. MORTAR SHALL BE TYPE 'S' FOR CONCRETE MASONRY UNITS AND TYPE 'N' FOR CLAY MASONRYVENEER IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE, TABLE 2103.8(1), MORTARPROPORTIONS, USING CEMENT LIME OR MORTAR CEMENT MIXES (MASONRY CEMENT IS NOTACCEPTABLE).

3. MINIMUM 28-DAY COMPRESSIVE STRENGTH OF GROUT SHALL BE THE GREATER OF 2,000 PSI ORTHE COMPRESSIVE STRENGTH OF THE MASONRY UNITS. AIR ENTRAINMENT AND OTHERADDITIVES ARE NOT ACCEPTABLE IN GROUT MIX. GROUT SHALL HAVE A SLUMP OF 8 TO 11INCHES.

4. GROUT SHALL BE MECHANICALLY CONSOLIDATED IN A MANNER TO FILL THE GROUT SPACE AND RECONSOLIDATED IN ACCORD WITH THE INTERNATIONAL BUILDING CODE.

5. PROVIDE GROUT AND MASONRY UNIT TESTING PRIOR TO AND DURING CONSTRUCTION INACCORD WITH THE INTERNATIONAL BUILDING CODE.

6. TESTING LABORATORY, IN ACCORD WITH IBC REQUIREMENTS, SHALL INSPECT REINFORCEMENT PLACEMENT, GROUT SPACES AND GROUTING OPERATION. MORTAR FINAL PROJECTION INTO

THE GROUT SPACE SHALL NOT EXCEED 1/2 INCH.

7. REFER TO TYPICAL DETAILS FOR MASONRY DETAILS AND REQUIREMENTS NOT SHOWN INSECTIONS OR PLANS.

STRUCTURAL STEEL:1. FABRICATOR SHALL BE AN "APPROVED FABRICATOR" IN ACCORDANCE WITH IBC SECTION 1704.2,

REGISTERED AND APPROVED BY THE LOCAL BUILDING DEPARTMENT. IN LIEU OF THE PREVIOUS,FABRICATOR SHALL INCLUDE IN THEIR BID THE SERVICES OF A SPECIAL INSPECTOR TO PROVIDEINSPECTION/TESTING SERVICES FOR IN-SHOP WORK TO MEET THE REQUIREMENTS OF IBCSECTION 1704.2.5 AND 1704.3. FINAL COSTS OF THESE SERVICES WILL BE AS REQUIRED BY THEOWNER'S SPECIAL INSPECTION AND TESTING AGENCY, WHO MAY OR MAY NOT BE HIRED AT THETIME OF BIDDING THE PROJECT. REFER TO IBC TABLE 1704.3 FOR A LIST OF THE MINIMUM CODEREQUIRED VERIFICATION AND INSPECTION REQUIREMENTS. ANY STEEL FABRICAT OR NOTMEETING THE REQUIREMENTS OF THE CONTRACT DOCUMENTS OR SPECIFICATIONS WILL BEREJECTED.

2. STRUCTURAL STEEL SHALL MEET ASTM A36 UNLESS NOTED OTHERWISE. STRUCTURAL STEELWIDE FLANGE SHAPES SHALL MEET ASTM A992 (GRADE 50).

3. STEEL TUBE SHALL MEET ASTM A500, GRADE B.

4. STEEL PIPE SHALL MEET ASTM A53, TYPE E OR S.

5. BOLTS AT STEEL TO STEEL CONNECTIONS SHALL BE 3/4-INCH DIAMETER, ASTM A325-N, ANDTIGHTENED TO THE SNUG TIGHT CONDITION AS DEFINED BY AISC UNLESS OTHERWISE NOTED.WHERE CONNECTIONS ARE NOTED TO BE ASTM A 325-SC, BOLTS SHALL BE TIGHTENED TO THEMINIMUM PRETENSION FOR FULLY TIGHTENED BOLTS BY ONE OF THE AISC APPROVED METHODS.

6. ANCHOR BOLTS IN CONCRETE OR MASONRY SHALL BE 3/4-INCH DIAMETER ASTM F1554 GRADE 36,UNLESS NOTED OTHERWISE.

7. FIELD BOLTING INSTALLATION SHALL BE INSPECTED IN ACCORD WITH THE BUILDING CODE ANDTHE AISC MANUAL.

8. ALL WELDING SHALL CONFORM TO THE PROVISIONS OF THE AMERICAN WELDING SOCIETY CODEAWS D1.1. ELECTRODES SHALL MATCH BASE METALS AS SPECIFIED IN IBC. ALL WELDING OF ASTMA706 REINFORCING STEEL TO STRUCTURAL STEEL SHALL BE IN ACCORD WITH AWS D1.4 USINGE70 ELECTRODES.

9. THE TESTING LABORATORY SHALL VISUALLY INSPECT ALL FIELD WELDING. ALL COMPLETEPENETRATION WELDS SHALL BE TESTED AND CERTIFIED BY AN INDEPENDENT TESTINGLABORATORY.

10. ALL BOLTS (HIGH STRENGTH, ANCHOR BOLTS, EXPANSION BOLTS, ADHESIVE ANCHORS, ETC.)SHALL BE INSTALLED WITH STEEL WASHERS.

11. ALL WELDS SHOWN ON THE DRAWINGS SHALL BE SHOP WELDS UNLESS NOTED OTHERWISE.CONTRACTOR MAY SUBSTITUTE FIELD WELDS FOR SHOP WELDS AT HIS DISCRETION. SHOPDRAWINGS SHALL CLEARLY NOTE SHOP AND FIELD WELDS.

12. CONTRACTOR IS RESPONSIBLE FOR THE STABILITY OF THE BUILDING SYSTEM AT ALL TIMES DURING THE ERECTION PROCESS. CONTRACTOR SHALL CONSIDER EFFECTS FROM WIND,

SEISMIC, AND OTHER LOADING DURING CONSTRUCTION.

13. COAT STEEL BELOW GRADE WITH COLD-APPLIED ASPHALT EMULSION PER ASTM D1187.

14. COORDINATE WITH ALL OTHER TRADES WHICH STEEL INTERACTS. THIS INCLUDES BUT IS NOTLIMITED TO COORDINATIN WITH MASONRY, PRECAST CONCRETE, CAST-IN-PLACE CONCRETE,JOIST, AND METAL DECK SUPPLIERS. WHERE MISALIGNMENT OF STEEL CONNECTIONS DUE TOIMPROPER COORDINATION OCCURS, THE CONTRACTOR SHALL HIRE AN ENGINEER LICENSED INTHE STATE WHICH THE PROJECT IS LOCATED TO PRODUCE A REPAIR AND SUBMIT THE REPAIRDETAIL WITH CALCULATIONS TO THE ENGINEER OF RECORD FOR REVIEW AND APPROVAL PRIORTO INSTALLATION.

STEEL JOISTS:1. FABRICATOR SHALL BE AN "APPROVED FABRICATOR" IN ACCORD WITH IBC SECTION 1704.2,

REGISTERED AND APPROVED BY THE LOCAL BUILDING DEPARTMENT.

2. ALL STEEL JOISTS SHALL BE DESIGNED, FABRICATED AND ERECTED IN ACCORD WITH IBCSECTION 2206, OPEN WEB STEEL JOISTS AND THE STANDARD SPECIFICATIONS FOR STEELJOIST, K-SERIES, LH-SERIES, DLH-SERIES AND JOIST GIRDERS, PUBLISHED BY THE STEEL JOISTINSTITUTE. TEMPORARY BRACING AND BRACING DESIGN REQUIRED FOR ERECTION ARE THERESPONSIBILITY OF THE FABRICATOR/INSTALLER.

3. SIZE, TYPE AND SPACING OF JOIST BRIDGING TO BE IN ACCORD WITH STEEL JOIST INSTITUTERECOMMENDATIONS. USE 'X'-BRIDGING AT DISCONTINUOUS ENDS OF BRIDGING. LOCATEBRIDGING TO AVOID MECHANICAL OPENINGS.

4. DESIGN JOISTS AND BRIDGING TO RESIST A NET UPLIFT OF 15 PSF. JOISTS WITHIN 10'-0" OFBUILDING EDGES AND RIDGES SHALL BE DESIGNED FOR A NET WIND UPLIFT LOAD OF 25 PSF.

5. JOIST SHOE DEPTH SHALL BE 2 1/2" AT K SERIES JOIST, 5" LH SERIES JOISTS, UNLESSOTHERWISE NOTED.

6. SPLICED JOIST SHOE DEPTH SHALL BE 2" AT K SERIES JOIST, 4 1/2" LH SERIES JOIST UNLESSOTHERWISE NOTED.

7. MANUFACTURER SHALL SUBMIT CALCULATIONS AND DRAWINGS SEALED BY A CIVIL ORSTRUCTURAL ENGINEER REGISTERED IN THE STATE IN WHICH THE PROJECT IS LOCATED FORALL JOISTS. CALCULATIONS SHALL INCLUDE DEFLECTION AND CAMBER REQUIREMENTS ANDCLEARLY SHOW ALL DESIGN LOADS. SHOP DRAWINGS SUBMITTED WITHOUT SIGNED ANDSEALED CALCULATIONS ARE GROUNDS FOR REJECTION.

8. LIVE LOAD DEFLECTIONS SHALL BE LIMITED TO SPAN/360 AT SIMPLE SPAN ROOF MEMBERS.

9. JOIST CANTILEVERS SHALL BE DESIGNED FOR ALL APPLICABLE DEAD, LIVE, AND WIND LOADS.LIMIT TOTAL DEFLECTION TO L/120 OF THE CANTILEVER LENGTH.

10. CAMBER JOISTS ACCORDING TO THE STANDARD SPECIFICATION FOR STEEL JOISTS. ATLOCATIONS WHERE TOP CHORD OR JOIST MUST MATCH TOP OF ADJACENT CONSTRUCTION ORWHERE TOP CHORDS OR JOISTS WITH DIFFERENT SPANS MUST MATCH, JOISTS SHALL HAVE NOCAMBER UNDER SELF WEIGHT.

11. ALL JOISTS SHALL BE DESIGNED, FABRICATED, AND ERECTED IN ACCORDANCE WITH THEAPPLICABLE U.L. LISTINGS PER THE ARCHITECTURAL DRAWINGS.

12. PROVIDE SLOPED AND/OR SLOPED AND SKEWED BEARING SEATS AS REQUIRED FOR ROOFSLOPE.

13. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND CALCULATIONS FOR REVIEW PRIOR TOFABRICATION.

14. REFER TO SNOW DRIFT DIAGRAM AND/OR LOADING PLAN FOR SNOW DRIFT LOADS. LOADSSHALL BE COMBINED WITH OTHER ROOF LOADS INDICATED IN ACCORDANCE WITH THE BUILDINGCODE. SNOW DRIFT LOADS SHALL BE DISTRIBUTED OVER THE TRIBUTARY WIDTH OF ROOFSUPPORTED BY THE JOIST.

15. DESIGN ALL JOIST CHORDS FOR BENDING BETWEEN PANEL POINTS WITH A TOP CHORD BENDCHECK LOAD OF 200 LBS AND A BOTTOM CHORD BEND CHECK LOAD OF 100 LBS. WHERECONCENTRATED LOADS EXCEED THESE LOADS, CONTRACTOR SHALL PROVIDE FIELDREINFORCEMENT PER TYPICAL JOIST REINFORCEMENT DETAIL.

16. COORDINATE EXACT MECHANICAL EQUIPMENT WEIGHT AND LOCATION WITH MECHANICALCONTRACTOR AND DESIGN JOISTS FOR TRIBUTARY LOADS. COORDINATE JOIST WEBS WHEREMECHANICAL DUCTS SHOWN ON MECHANICAL DRAWINGS ARE DESIGNED TO PENETRATETHROUGH JOIST WEBS.

FIRE RATINGS:1. FOR FIRE-RATING REQUIREMENTS AND METHODS, SEE ARCHITECTURAL DRAWINGS.

SUBMITTALS GENERAL1. THE CONTRACTOR SHALL DEVELOP AND SUBMIT A SUBMITTAL SCHEDULE CLEARLY INDICATING

THE NUMBER OF STEEL SHOP DRAWINGS, CONCRETE REINFORCING DRAWINGS, AND OTHERSHOP DRAWINGS TO BE SUBMITTED EACH WEEK OVER THE DURATION OF THE PROJECT.

2. THE SUBMITTAL SCHEDULE PROVIDED BY THE CONTRACTOR IS NECESSARY TO PROVIDEREASONABLE TIME TO STAFF APPROPRIATELY FOR THE SCHEDULED SUBMITTALS. THESUBMITTAL ENGINEER'S REVIEW SCHEDULE IS SUBJECT STRICTLY TO THE SUBMITTALSCHEDULE PROVIDED BY THE CONTRACTOR.

3. REVIEW OF SHOP DRAWINGS DOES NOT RELIEVE THE CONTRACTOR FROM CONFORMANCEWITH THE INTENT OF THE DRAWINGS. REVIEW DOES NOT IMPLY OR STATE THAT THEFABRICATOR HAS CORRECTLY INTERPRETTED THE CONSTRUCTION DOCUMENTS.

4. CONTRACTOR SHALL SUBMIT CALCULATIONS WITH THE SHOP DRAWINGS DESIGNATED ASDEFERRED SUBMITTALS, SIGNED AND SEALED BY THE ENGINEER, LICENSED IN THE STATEWHICH THE PROJECT IS LOCATED, RESPONSIBLE FOR THEIR PREPARATION WHEN REQUIRED INTHE SPECIFICATIONS (SEE ALSO 'DEFERRED SUBMITTALS').

5. COPIES OF THE CONTRACT DOCUMENTS SHALL NOT BE SUBMITTED AS SHOP DRAWINGS.CONTRACT DRAWINGS SHOW ONLY GENERAL DESIGN INTENT. FINAL SHOP DRAWING SECTIONSSHALL PROVIDE SIZES, LAYOUT, EXACT DIMENSIONS, ELEVATIONS, GRADES OF MATERIALS,ETC., SPECIFIC TO EACH LOCATION.

6. SHOP DRAWINGS SHALL BE REVIEWED AND STAMPED BY THE GENERAL CONTRACTOR ORCONSTRUCTION MANAGER PRIOR TO SUBMITTING TO DLR GROUP. REQUEST FOR INFORMATIONFOR ITEMS SUCH AS OVERALL BUILDING GEOMETRY, ELEVATIONS, ETC. SUBMITTED THROUGHSHOP DRAWAINGS SHALL BE DETERMINED BY THE CONTRACTOR. IF GEOMETRY CANNOT BEDETERMINED FROM THE DRAWINGS, THE CONTRACTOR SHALL SUBMIT AN RFI AND COORDINATETHE RESPONSE WITH ALL AFFECTED TRADES PRIOR TO FABRICATION.

DEFERRED SUBMITTALS:1. THE FOLLOWING ARE DEFERRED SUBMITTAL ITEMS:

- STEEL JOISTS

2. DEFERRED SUBMITTAL CALCULATIONS AND/OR SHOP DRAWINGS SHALL BE SIGNED ANDSEALED BY THE ENGINEER RESPONSIBLE FOR THEIR PREPARATION AND SHALL BE SUBMITTEDTO THE ENGINEER FOR REVIEW WITH THE SHOP DRAWING SUBMITTAL. ONCE REVIEWED,CONTRACTOR SHALL FORWARD TO THE BUILDING DEPARTMENT FOR APPROVAL. FABRICATIONAND/OR INSTALLATION OF DEFERRED SUBMITTAL ITEMS SHALL NOT OCCUR UNTIL APPROVAL OFTHE BUILDING DEPARTMENT IS RECEIVED.

3. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

SPECIAL STRUCTURAL INSPECTIONS:1. IN ACCORD WITH IBC, SECTION 1704, AS NOTED BELOW. TESTING AND INSPECTION SHALL BE

BY AN INDEPENDENT TESTING/INSPECTION FIRM UNDER THE SUPERVISION OF A LICENSEDENGINEER EMPLOYED BY THAT FIRM. THIS ENGINEER SHALL BE DEEMED THE DESIGNATEDENGINEER OF RECORD FOR SPECIAL INSPECTIONS PERFORMED BY HIS FIRM OR HISCONSULTANTS. INSPECTORS SHALL BE ICBO CERTIFIED AND APPROVED BY THE BUILDINGOFFICIAL.

2. THE DESIGNATED ENGINEER OF RECORD FOR SPECIAL INSPECTIONS SHALL BE RESPONSIBLEFOR DEFINING THE ACTIVITIES OF THE INSPECTORS, FOR CERTIFYING THE QUALIFICATIONS OFTHE INSPECTORS WITH THE BUILDING OFFICIAL, AND TO ATTEND THE PRECONSTRUCTIONMEETING TO DEFINE THEIR SCOPE OF SERVICES AND THE TESTING OR TEST PROCEDURESTHAT ARE REQUIRED AS OUTLINED IN THE INTERNATIONAL BUILDING CODE.

3. SPECIAL INSPECTION IS TO BE PROVIDED IN ADDITION TO THE INSPECTIONS CONDUCTED BYTHE LOCAL DEPARTMENT OF BUILDING SAFETY AND SHALL NOT BE CONSTRUED TO RELIEVETHE OWNER OR HIS AUTHORIZED AGENT FROM REQUESTING THE PERIODIC AND CALLEDINSPECTIONS REQUIRED BY SECTION 109 OF THE INTERNATIONAL BUILDING CODE.

4. CONCRETE: PER SECTION 1704.4 WITH EXCEPTIONS. THE FOLLOWING ITEMS REQUIRE SPECIALINSPECTION: ALL CONCRETE EXCEPT SLAB-ON-GRADE.

5. ANCHOR BOLTS INSTALLED IN CONCRETE: PER TABLE 1704.4.

6. REINFORCING PER TABLE 1704.4 WITH EXCEPTION FOR CONCRETE NOT REQUIRING SPECIALINSPECTION.

7. WELDING: PER SECTION 1704.3 WITH EXCEPTIONS. PROVIDE INSPECTION OF ALL SHOPWELDING AT CONTRACTOR'S EXPENSE IF WELDING IS NOT DONE IN AN APPROVEDFABRICATOR'S SHOP.

8. HIGH STRENGTH BOLTING: PER SECTION 1704.3.3.

9. STRUCTURAL MASONRY: PER SECTION 1704.5 AND TABLES 1704.5.1 AND 1704.5.3

10. GRADING, EXCAVATION AND FILLING: PER SECTION 1704.7. SEE CIVIL DRAWINGS ANDSPECIFICATION DIVISION 2.

11. EXPANSION BOLT, SCREW ANCHOR AND ADHESIVE ANCHOR INSTALLATION TO VERIFYINSTALLATION IN ACCORD WITH ICBO REPORTS NOTED PREVIOUSLY OR APPROVED EQUAL.

12. THE INSPECTOR SHALL OBSERVE THE WORK ASSIGNED TO BE CERTAIN IT CONFORMS TO THEAPPROVED DESIGN DRAWINGS AND SPECIFICATIONS.

13. THE INSPECTOR SHALL FURNISH DAILY INSPECTION REPORTS ON THE WORK TO THE BUILDINGOFFICIAL AND TO THE ENGINEER. ALL DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATEATTENTION OF THE CONTRACTOR FOR CORRECTION, AND, IF UNCORRECTED, TO THE ENGINEERAND THE BUILDING OFFICIAL.

14. THE TESTING/INSPECTION FIRM'S ENGINEER SHALL COMPLETE, SIGN AND SEAL A FINALREPORT CERTIFYING THAT TO THE BEST OF HIS KNOWLEDGE, THE WORK IS IN CONFORMANCEWITH THE CONTRACT DOCUMENTS.

15. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE CONSTRUCTION SCHEDULEWITH THE OWNER'S SPECIAL INSPECTION REPRESENTATIVE IN A TIMELY MANNER AND SHALLNOT PROCEED WITH CONSTRUCTION OF COMPONENTS THAT MAY INTERFERE WITH THEINSPECTORS ABILITY TO PERFORM CODE REQUIRED INSPECTIONS. ANY COST INCURREDASSOCIATED WITH REMOVAL OF WORK TO PERFORM INSPECTIONS WILL BE BORNE BY THECONTRACTOR.

1. ARCHITECTURAL FINISHED FLOOR ELEVATION XX'-X” EQUAL SITE SURVEY ELEVATION XXXX.XX'.

2. FOOTING WIDTH SHOWN THUS 0'-0. IF NO WIDTH IS INDICATED SEE NOTE NO. 3.

3. TOP OF FOOTING ELEVATION = 99'-4”, OTHERWISE SHOWN THUS

4. INDICATES FOOTING TYPE. REFER TO FOOTING SCHEDULE ON SHEET S3.1

5. SEE SHEET S3.1 FOR REINFORCING SPLICE LENGTH TABLE.

6. SEE ARCHITECTURAL DRAWINGS FOR LOCATION OF THICKENED, SLOPED, RAISED, ORDEPRESSED SLABS.

7. PROVIDE AT LEAST 2' - 0" OR 1/2 THE FOOTING'S WIDTH OF GRANULAR STRUCTURAL FILL BELOWTHE FOOTING AND WIDEN EXCAVATION AS SPECIFIED IN SECTION 312000 "EARTH MOVING"

8. PROVIDE AT LEAST X' - X" OF STRUCTURAL FILL BELOW FLOOR SLAB AS SPECIFIED IN SECTION312000 "EARTH MOVING"

1. JOIST BEARING ELEVATION SHOWN THUS (0'-0) ON PLAN.

2. TOP OF STEEL ELEVATION SHOWN THUS (TOS = 0'-0) ON PLAN.

3. BOTTOM OF LINTEL ELEVATION SHOWN THUS (BOL = 0'-0) ON PLAN.

4. PROVIDE 3x3x1/4 ANGLE FRAMING AT ALL OPENINGS 12” OR LARGER IN METAL ROOF DECK UNLESS NOTED OTHERWISE. MEMBERS PERPENDICULAR TO JOISTS SHALL SPAN FROM JOIST TO

JOIST. SEE TYPICAL DETAIL.

5. PROVIDE L5X3X3/8 FRAMING AT ALL OPENINGS 12" OR LARGER IN FLOOR DECK UNLESS NOTEDOTHERWISE. MEMBERS PERPENDICULAR TO BEAMS SHALL SPAN FROM BEAM TO BEAM. SEETYPICAL DETAIL.

6. FRAMING FOR MECHANICAL UNITS IS FOR THE UNITS AS SPECIFIED. COORDINATE AND VERIFY THE EXACT FRAMING AND DIMENSION REQUIRED. VERIFY ALL ROOF PENETRATION SIZES AND

LOCATIONS.

7. JOIST MANUFACTURER TO DESIGN JOISTS FOR ALL APPLICABLE DEAD, LIVE, AND WIND LOADS.COORDINATE MECHANICAL EQUIPMENT LOADS WITH APPROPRIATE MANUFACTURERS.

8. DISCONTINUE JOIST BRIDGING WHERE MECHANICAL DUCTS RUN BETWEEN THE JOISTS. SEE DETAIL FOR BRIDGING. BRIDGING RUNS SHALL NOT ATTACH TO NON-LOAD BEARING WALLS.

9. PROVIDE TOP AND BOTTOM PLATES, DEFORMED BAR ANCHORS, AND T-PLATES AS SHOWN ONPLANS. IF NOT INDICATED ON PLANS, SEE TYPICAL DETAILS.

10. JOIST BRIDGING SHALL BE DESIGNED BY THE STEEL JOIST MANUFACTURER.

11. ANGLE STEEL SHOWN THUS ( ) ON PLANS. ALSO SEE ARCHITECTURAL ANDSTRUCTURAL DETAILS.

0

XX'-X"TOF

FX

ABBREVIATIONS:ABBREVIATIONS ARE AS SHOWN IN THE CONTRACT DOCUMENTS WITH THE FOLLOWING EXCEPTIONS:

BOL BOTTOM OF LINTELBOS BOTTOM OF STEELBRG BEARINGCJP COMPLETE JOINT PENETRATIONDBA DEFROMED BAR ANCHORDT DOUBLE TEEEE EACH ENDEW EACH WAYHC PRESTRESSED PRECAST HOLLOW COREHS HEADED ANCHOR STUDLLH LONG LEG HORIZONTALLLV LONG LEG VERTICALSTD STANDARDTOCB TOP OF CONCRETE BLOCKOUTTOCW TOP OF CONCRETE WALLTOF TOP OF FOOTINGTOGB TOP OF GRADE BEAMTOM TOP OF MASONRYTOP TOP OF PIERTOS TOP OF STEELTOW TOP OF WALLTYP TYPICALUNO UNLESS NOTED OTHERWISE

POST-INSTALLED ANCHORS:

1. ALL POST INSTALLED ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'SRECOMMENDATIONS AND ICC EVALUATION REPORTS CORRRESPONDING TO THAT ANCHOR.

2. MASONRY:EXPANSION ANCHORS: SIMPSON STRONG-TIE WEDGE-ALL ANCHORS (ICC ESR-1396)

HILTI KWIK BOLT 3 MASONRY ANCHORS (ICC ESR-1385)

ADHESIVE ANCHORS: SIMPSON STRONG-TIE SET ADHESIVE ANCHORS (ICC ESR-1772)HILTI HIT-HY 70 MAX ADHESIVE ANCHORS (ICC ESR-2682 & ICC ESR-3342)

SCREW ANCHORS: SIMPSON STRONG-TIE TITEN HD ANCHORS (ICC ESR-1056)HILTI KWIK HUS-EX ANCHORS (ICC ESR-3056)

3. CONCRETE:EXPANSION ANCHORS: SIMPSON STRONG-BOLT WEDGE ANCHORS (ICC ESR-1771)

HILTI KWIK BOLT TZ CONCRETE ANCHORS (ICC ESR-1917)

ADHESIVE ANCHORS: SIMPSON STRONG-TIE SET-XP ADHESIVE ANCHORS (ICC ESR-2508)HILTI HIT-HY 200 ADHESIVE ANCHORS (ICC ESR-3197; SAFESET INSTALLATION ALLOWED WITH HOLLOW DRILL BIT)

SCREW ANCHORS: SIMPSON STRONG-TIE TITEN HD ANCHORS (ICC ESR-2713)HILTI KWIK HUS-EZ ANCHORS (ICC ESR-3027)

4. MASONRY CELLS SHALL BE FULLY GROUTED FOR INSTALLATION OF POST-INSTALLED ANCHORS.

5. POST-INSTALLED ANCHORS ARE NOT TO BE INSTALLED UNTIL CONCRETE OR GROUT HAS REACHEDITS DESIGN STRENGTH.DEMOLITION:

1. DEMOLITION OF EXISTING STRUCTURE TO BE REMOVED SHALL BE PERFORMED BY THECONTRACTOR USING MEANS NECESSARY TO PREVENT DAMAGE TO THE EXISTING STRUCTURE TOREMAIN. DAMAGE TO THE EXISTING STRUCTURE TO REMAIN SHALL BE REPAIRED AT THECONTRACTOR'S EXPENSE USING METHODS REVIEWED BY THE STRUCTURAL ENGINEER. IFEXISTING CONDITIONS DIFFER FROM THOSE SHOWN IN THE CONTRACT DOCUMENTS CONTACT THEARCHITECT PRIOR TO PREOCEEDING WITH WORK.

EXISTING CONDITIONS:1. CONTRACTOR IS TO FIELD VERIFY EXISTING CONDITIONS PRIOR TO BIDDING. ALL WORK AND

MATERIALS NECESSARY TO INSTALL NEW WORK IN EXISTING BUILDING SHALL BE INCLUDED.

2. DISCREPANCIES: CONTRACTOR SHALL NOTIFY ARCHITECT/ENGINEER IMMEDIATELY IF EXISTINGCONDITIONS DO NOT MATCH, OR SEEM IN CONFLICT WITH, INFORMATION SHOWN ON DRAWINGS.

3. EVERY EFFORT SHALL BE MADE TO MINIMIZE DISRUPTION TO OWNER'S OPERATIONS AND TOPROVIDE PATRON, FACILITY STAFF AND WORKER SAFETY.

4. EXCESSIVE NOISE AND VIBRATION SHALL BE PRE-APPROVED AND COORDINATED WITH THEOWNER'S REPRESENTATIVE.

5. PROVIDE PROTECTION FOR ALL EXISTING BUILDING MATERIALS AND EQUIPMENT TO REMAIN FROMDAMAGE DUE TO DEMOLITION OR CONSTRUCTION OPERATIONS PERFORMED UNDER THISCONTRACT.

6. THE SEQUENCE OF CONSTRUCTION SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND HESHALL BE RESPONSIBLE FOR PROVIDING ALL TEMPORARY GUYS, BRACING, AND OTHER SUPPORTSAS NEED TO SAFELY RESIST ALL LOADS TO WHICH THE STRUCTURE MAY BE SUBJECTED,INCLUDING LOADS ERECTION EQUIPMENT AND ERECTION OPERATIONS, AND WIND OR SEISMICFORCES COMPARABLE IN INTENSITY FOR WHICH TEH STRUCTURE AS DESIGNED.

7. ALL ERECTION AND CONSTRUCTION PROCEDURES SHALL MEET THE REQUIREMENTS OF ALLAPPLICABLE CODES AND ORDINANCES.

8. ALL FRAMING CONNECTION TO EXISTING STRUCTURE SHALL BE FIELD VERIFIED PRIOR TO SHOPDRAWING PRODUCTION AND FABRICATION.

9. ALL FURNITURE AND EQUIPMENT SHALL BE REMOVED FROM THE FLOOR STRUCTURE TO BERETROFITTED BEFORE THE NEW STEEL IS INSTALLED.

10. JACK EXISTING BEAMS UP AS REQUIRED TO ALLOW FOR INSTALLATION OF NEW STEEL ON EXISTINGBEAMS. THE STRUCTURAL INTEGRITY OF THE BUUILDING SHALL NOT BE COMPROMISE DURINGTHIS PROCESS.

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

Rev

isio

ns

5/1

2/2

017 2

:29:1

3 P

M

C:\R

evit\1

0-1

6206-0

0_S

T_2016_C

entr

al_

gla

rsen.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

ST

RU

CT

UR

AL N

OT

ES

S0.1

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

Page 16: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

UP

6

7

5

4

3

2

1

HA B C D E F G

8

9

10

3' - 0"

L

1

2

3

4

5

6

7

A B C D E F G

8

9

10

3 1/2"16' - 0 3/4"

HSS4X4X1/441

S3.1

ON

WA

LL

CE

NT

ER

PO

ST

8' -

1"

18' -

1"

6' -

0"

18' -

0"

24' -

0"

24' -

10"

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

BA

NORTH

Rev

isio

ns

5/1

2/2

017 2

:29:1

4 P

M

C:\R

evit\1

0-1

6206-0

0_S

T_2016_C

entr

al_

gla

rsen.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

FO

UN

DA

TIO

N P

LA

N, B

AS

EM

EN

T L

EV

EL -

AR

EA

AS1.0A

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

SCALE: 1/8" = 1'-0"S1.0A

1 FOUNDATION PLAN, BASEMENT LEVEL - AREA A

Page 17: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

RE

F.

6

7

5

4

3

2

1

H M N O P Q

8

10

3' - 0"

14' -

11

5/8"

FUTURE MECHANICAL

L M N O P Q

1

2

3

4

5

6

7

8

10

TYP2' - 0"

SPREAD FOOTINGREINFORCEMENT

1' - 0"

AROUND1' - 6"

AROUND1' - 6"

AROUND1' - 6"

2' -

0"

EXISTING FOOTING.11' - 6" SQUARE(FIELD VERIFY)

EXISTING FOOTING.10' - 6" SQUARE(FIELD VERIFY)

EXISTING FOOTING.10' - 6" SQUARE(FIELD VERIFY)

EXISTING FOOTING.11' - 6" SQUARE(FIELD VERIFY)

EXISTING FOOTING.10' - 6" SQUARE(FIELD VERIFY

EXISTING FOOTING.9' - 9" SQUARE(FIELD VERIFY)

EXISTING FOOTING.10' - 6" SQUARE(FIELD VERIFY)

EXISTING FOOTING.11' - 0" SQUARE(FIELD VERIFY)

EXISTING FOOTING.11' - 6" SQUARE(FIELD VERIFY)

31

S3.1 TYP

TOF 77' - 0"

EXISTING U.N.O

TOF 78' - 0"

EXISTING

TOF 78' - 0"

EXISTING

TOF 78' - 0"

EXISTINGTOF 79' - 0"

EXISTING

34

S3.1TYP

HSS4X4X1/4

MC

8x20

MC

8x20

MC

8x20

MC

8x20

MC

8x20

MC

8x20

MC

8x20

6' - 0"

10"

TO

S =

92'

-0"

TY

P(V

ER

IFY

)

10 1/2"

6' - 10"51

S3.1TYP

44

S3.1

42

S3.1

HSS 4x4x1/2 POSTTYP

25

S3.1

16

S3.1

ON

WA

LL

CE

NT

ER

PO

ST

28' - 2" 28' - 0" 28' - 0" 24' - 0" 18' - 8"

8' -

1"

18' -

1"

6' -

0"

18' -

0"

24' -

0"

24' -

10"

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

BA

NORTH

Rev

isio

ns

5/1

2/2

017 2

:29:1

6 P

M

C:\R

evit\1

0-1

6206-0

0_S

T_2016_C

entr

al_

gla

rsen.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

FO

UN

DA

TIO

N P

LA

N, B

AS

EM

EN

T L

EV

EL -

AR

EA

BS1.0B

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

SCALE: 1/8" = 1'-0"S1.0B

1 FOUNDATION PLAN, BASEMENT LEVEL- AREA B

Page 18: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

STL JST STL JST

STL JST

L M N O P Q

1

2

3

4

5

6

7

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

14K1

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

18K3

EXIST. JST

18K3

EXIST. JST

20K3

EXIST. JST

20K3

EXIST. JST

20K3

19 3/4K-SP

20K3

20K3

20K3

W36

x135

EX

IST

W33

x141

EX

IST

W33

x141

EX

IST

W30

x108

EX

IST

W21

x68

EX

IST

W21

x62

EX

IST

W21

x44

EX

IST

W24

x76

EX

IST

W24

x62

EX

IST

W21

x62

EX

IST

W18

x40

EX

IST

W24

x68

EX

IST

W24

x55

EX

IST

W18

x55

EX

IST

W18

x35

EX

IST

W21

x68

EX

IST

W16

x26

EX

IST

W16x26EXIST

W12x22EXIST

W16x26EXIST

W12

x14

EX

IST

W24x68EXIST

W24x68EXIST

W24x68EXIST

W24x68EXIST

W24x68EXIST

W24x68EXIST

W24x68EXIST

W24x68EXIST

W24x68EXIST

W24x68EXIST

W24x68EXIST

W24x68EXIST

W24x68EXIST

W16x31EXIST

W16x31EXIST

W16x31EXIST

W12x14EXIST

W21

EW

21C

W21

A

W24

AW

21B

W18

A

W24

B

12

S3.1TYP

24

S3.1

21

S3.1

A

TYP

22

S3.1TYP

21

S3.1

A 21

S3.1

B

W18

A

W33

AW

33A

28' - 2" 28' - 0" 28' - 0" 24' - 0" 18' - 8"

8' -

1"

18' -

1"

6' -

0"

18' -

0"

24' -

0"

24' -

10"

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

BA

NORTH

Rev

isio

ns

5/1

2/2

017 2

:29:1

8 P

M

C:\R

evit\1

0-1

6206-0

0_S

T_2016_C

entr

al_

gla

rsen.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

FR

AM

ING

PLA

N, F

IRS

T L

EV

EL -

AR

EA

BS2.1B

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

SCALE: 1/8" = 1'-0"S2.1B

1 FRAMING PLAN, FIRST LEVEL - AREA B

Page 19: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

L M N O P Q

1

2

3

4

5

6

7

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

22K4 SPLICED

W21

x68

W18

X60

W21

x44

EX

IST

ING

EX

IST

ING

EX

IST

ING

ALT

ER

NA

TE

# 1

12

S3.1

W18

AW

21E

W21

A

22

S3.1

TYP

21

S3.1

A

TYP

TYP

35

S3.1TYP

28' - 2" 28' - 0" 28' - 0" 24' - 0" 18' - 8"

8' -

1"

18' -

1"

6' -

0"

18' -

0"

24' -

0"

24' -

10"

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

BA

NORTH

Rev

isio

ns

5/1

2/2

017 2

:29:2

0 P

M

C:\R

evit\1

0-1

6206-0

0_S

T_2016_C

entr

al_

gla

rsen.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

FR

AM

ING

PLA

N, S

EC

ON

D L

EV

EL -

AR

EA

BS2.2B

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

SCALE: 1/8" = 1'-0"S2.2B

1 FRAMING PLAN, SECOND LEVEL - AREA B

Page 20: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

CL

CL

BEAM SIZE WT SIZE ANGLE

W18X40W18x60

WT12x31

W21x44

W21x62

W21x68

W24x62W24x68

N/A

STEEL BEAM REINFORCEMENT SCHEDULE

WT, SEESCHEDULE

EXISTING STEEL BEAM

SEESCHED

W24x76

MARK WELD SIZE

3/16"

3/16"

3/8"

3/16"

3/16"

3/16"

SECTION

ASECTION A

A

A

A

A

A

B

WT12x31 N/A

WT12x31 N/A

WT12x38 N/A

WT12x31 N/A

WT12x38 2 - L6x3 1/2x1/2

WT, SEESCHEDULE

EXISTING STEEL BEAM

SEESCHED

BSECTION B

ANGLE, SEE SCHEDULE

SEESCHED

3/8"B WT12x38 2 - L6x3 1/2x1/2

W18A

W21A

W21B

W21E

W24A

W24B

W33x141 3/8"A WT12x38 N/AW33A

W21x62W21C

EXISTING METAL DECK

STEEL SPLICE FIELD-BOLTED JOIST

EXISTING STEEL BEAM

MATCH EXISTING

T.O. JOIST EL

3/16 3"

JOIS

T S

EA

T

2 1/

4" D

EE

P

SHIM PLATE 1/4"x6"x0'-8"CENTERED ON JOIST SEAT

NOTES:1. FIELD VERIFY JOIST SPAN DIMENSIONS2. AFTER INSTALLATION OF STEEL JOIST, A 1/4-INCH THICK STEEL PLATE

SHALL BE INSTALLED BENEATH THE JOIST SEAT TO PROVIDE A TIGHTCONNECTION AGAINST THE METAL DECK.

3. ATTACH METAL DECK TO STEEL JOIST WITH No.12 SCREWS AT EVERYOTHER DECK RIB.

4. DISCONTINUE ANY BRIDGING ELEMENT TO ALLOW INSTALLATION OF NEWJOIST. AFTER INSTALLATION, RESTORE CONTINUOUS BRIDGING ELEMENTS.

No. 12 CONCRETE SCREW

MIN1' - 0"

No.12 CONCRETE SCREWAT EVERY OTHERDECK RIB

EXISTING METALDECK WITHCONCRETE TOPPING

EXISTING JOISTS

NEW STEEL JOIST,SEE PLAN

COLUMN SIZEPLATE

THICKNESS

W12x72 3/8''

W12x79

W14x90

STEEL COLUMN REINFORCEMENT SCHEDULE

EXISTING STEEL COLUMN

SEESCHED

MARK SECTION

ASECTION A

A

A

A

3/8''

3/8''

C12A

C12B

C14A

1/2" TYP

PLATE, SEESCHEDULE

WELD SIZE

3/16"

3/16"

1/4"

CJP

ASECTION

L3x2x1/2 TYP

1" TYP

WT

EXISTING STIFFENERPLATE, FIELD VERIFY

EXISTINGSTEEL BEAM

EXISTINGSTEEL COLUMN

EXISTINGSTEEL COLUMN

EACH WAY 2' - 6'' MIN

A

1/4TYP

3/4" STEEL ROD (50 ksi)

EXTEND OF STEEL ROD

TOP OF PIER EL(EXISTING)

FIELD VERIFY

TOF EL(EXISTING)

FIELD VERIFY

EXISTINGCONCRETEPIER

#6x2'-6'' EPOXY DOWELREINFORCEMENT, EMBED 6'' INTOEXISTING COLUMN - ONE AT EACHFACE

EXISTING COLUMN

CLR2"

EPOXY BAR WITH 90 DEG STD ENDHOOK AT 10" OC ON BOTH DIRECTIONS,EMBED 6" INTO EXISTING FOOTING

3" CLR

NEW FTGSEE PLANS SEE PLANS AND FIELD VERIFY

EXISTING FOOTING NEW FTGSEE PLANS

#6 BARS EA WAY WITH 90 DEGSTD END HOOKAT 10" OC

3" C

LR

#6 EPOXY DOWELS WITH 90 DEG STDEND HOOK AT 12" OC, EMBED 8" INTOEXISTING FOOTING

#3 CLOSED STIRRUPS AT 12" OC

1' -

0"

2 1/

2"

2 #6 TOP, MIDDLE AND BOTTOM

PROCEDURES:

1. EXCAVATE AROUND EXISTING FOOTING.2. ROUGHEN ALL SURFACE OF EXISTING FOOTING TO

A FULL AMPLITUDE OF 1/4 IN.3. INSTALL ALL EPOXY DOWELS AND FASTEN ALL NEW

REBAR USING STEEL WIRES.4. COAT THE EXISTING FOOTING WITH BONDING AGENT.5. POUR NEW CONCRETE WITH SHRINKAGE REDUCTION

ADMIXTURE.

6"

TYP 1' - 0"

NEW OPENING AT EXISTING WALL.AFTER INSTALLING STEEL CHANNELAND PLATE AT HEADER, CAREFULLYREMOVE EXISTING CONCRETE FORNEW OPENING

STEEL CHANNEL

CONCRETEWALL

A

3"6"

C12x20.7 W/2-3/4" A325N THRUBOLTS AT 12" OC

PL 1/2"x12"

DRILL HOLES ANDGROUT HOLESCOMPLETELY AFTERBOLTS ARE IN PLACE

A

EXISTING METAL DECK

STEEL SPLICE FIELD-BOLTED JOIST

EXISTING STEEL BEAM

MATCH EXISTING

T.O. JOIST EL

3/16 3"

SHIM PLATE 1/4"x6"x0'-8"CENTERED ON JOIST SEAT

NOTES:1. FIELD VERIFY JOIST SPAN DIMENSIONS2. AFTER INSTALLATION OF STEEL JOIST, A 1/4-INCH THICK STEEL PLATE

SHALL BE INSTALLED BENEATH THE JOIST SEAT TO PROVIDE A TIGHTCONNECTION AGAINST THE METAL DECK.

3. ATTACH METAL DECK TO STEEL JOIST WITH No.12 SCREWS AT EVERYOTHER DECK RIB.

4. DISCONTINUE ANY BRIDGING ELEMENT TO ALLOW INSTALLATION OF NEWJOIST. AFTER INSTALLATION, RESTORE CONTINUOUS BRIDGING ELEMENTS.

No. 12 CONCRETE SCREW

FV 4'-0''

1"

1' - 6" x 1/2" Ø EPOXY DOWEL INTOEXISTING SLAB ON GRADE WITH6" EMBEDMENT

EXISTING SLABNEW 4" SLAB ON GRADE

6x6 - W.21xW2.1 WWF

OPENING

HSS8X4X1/4

HS

S4X

4X1/

4 U

NO

HS

S4X

4X1/

4 U

NO

LEVEL EL = 82'-0"

LEVEL

S3.1

43

S3.1

44

42

S3.1

BOS ELE. = 90'-6"

L7x4x3/8(LLV) AT EA SIDEOF THE TUBE W/ 13/16"x3" VERT.SLOTTED HOLE.

1-3/4"Ø A325N THRU BOLTAND WASHERS. FINGER TIGHTENNUT. BACK OF 1/2 TURN & UPSETTHREATS

STEEL POST

1 1/2"5"

1 1/2"

1/2"Ø EXPANSION ANCHOR BOLTWITH 3 1/4" MIN. EMBEDMENT

1"

1/2"

BOS ELEVATION

PL 9"x4 1/2"

STEEL POST

1/4

1/4

HSS MEMBER NOTCHEDAT ENDS

1/2"

1"1"

3"

1 1/2" 4" 2 1/2"

2 1/

2"

1/4

BASE PL 1/2"x5"x0'-8"W/ 2-5/8" EXP ANCHORSW/ 3" EMBEDMENT

OPENING EDGE

NOTE: SEE DETAIL 44/S3.1 FORTHICKENED SLAB SUPPORT

1 1/

2"

1' -

2"

6' - 0"

SEE PLANS

STEEL CHANNEL

1 1/2" x 22GA COMPOSITEMETAL DECK

LIGHT WEIGHT CONCRETE

ELECTRICAL CONDUITS

(PARALLEL TO WALL)

UN

O2'

- 0

"

BEARING PL1/2"x7"x0'-7"UNO ON PLANS

FILL ALL CELLS WITH GROUT INSHADED AREA.

2-3/4"Øx1'-0" EPOXY BOLTSAND WASHERS

PROVIDE 3" LONG SLOTTEDHOLES IN BEAM FLANGE

1" NON-SHRINKGROUT MINIMUM

FINGER TIGHTEN AND UPSETTHREADS. TYPICAL UNOSTEEL BEAM

UNO8" BEARING

2' - 0"

CREATE POCKET TO RECEIVE NEWBEAM AND GROUT FULLY AFTERINSTALLATION

26

S3.1

FINGER TIGHTEN NUTS ANDUPSET THREADS - TYPICALUNO

BEARING PLATE 1/2"x7"x0'-9"UNO ON PLANS CENTER ONWALL UNO

STEEL BEAM3 1/2" BEARING

1" NON-SHRINKGROUT MIN

FILL ALL CELLS WITHGROUT IN SHADED AREA

2-3/4"Ø x1'-0" EPOXY BOLTSAND WASHERS. PROVIDE 3"LONG SLOTTED HOLES INBEAM FLANGE

(PERPENDICULAR WALL)

1' - 4" MIN1'-4"MIN

2'-0

" U

NO

1/4

BARSIZE

LAPCLASS

1ABABABABABABABABAB

#3

#4

#5

#6

#7

#8

#9

#10

#11

COMPRESSIONLAP SPLICES

2 3 4 5 6 1 2 3 4 5 6

TOP BARSCATEGORY

OTHER BARSCATEGORY

TENSION LAP SPLICES

1621

1621

1621

1621

1621

1621

2330

2228

2228

2228

2228

2228

3646

2937

2735

2735

2735

2735

5065

4052

3546

3242

3242

3242

6989

5571

4863

3950

3849

3849

90117

7294

6382

5166

4559

43564863

5774

6483

80104

91119

114148

5876

7394

81106

102132

116151

145188

7193

89116

100130

125162

142185

178231

1316

1316

1316

1316

1316

1316

1823

1722

1722

1722

1722

1722

2736

2229

2127

2127

2127

2127

3950

3140

2735

2532

2532

2532

5369

4255

3748

3039

2938

2938

7090

5672

4963

3951

3545

3343

88114

7091

6280

4964

4457

3748

112145

89116

78102

6381

5673

4558

137178

110142

96125

77100

6989

5571

14

17

21

27

30

34

38

44

49

STRUCTURALELEMENT

BEAMS, COLUMNS,AND INNER LAYEROF WALLS OR SLABS

ALL OTHERS

CONCRETECOVER

CATEGORY, ACCORDING TOCENTER-TO-CENTER SPACING

≤ 3db> 3db< 4db

≥ 6db≥ 4db< 6db

≤db

> db ≤ db> db,< 2db

≥ 2db

11

13

15

26

111

133

135

246

NOTES:1. CATEGORIES 1 THROUGH 6 DEPEND ON THESTRUCTURAL ELEMENT, CONCRETE COVER, AND THECTR-TO-CTR SPACING OF BARS, AS SHOWN IN TABLE.2. TOP BARS ARE HORIZONTAL BARS WITH MORE THAN12 INCHES OF CONCRETE CAST BELOW THE BARS.3. USE LAP CLASS B U.N.O.4. FOR LIGHTWEIGHT AGGREGRATE, MULTIPLY THEVALUES BY 1.3.

5. #11 AND SMALLER EDGE BARS WITH CENTER -TO-CENTER SPACING NOT LESS THAN 6d ARE ASSUMED TO HAVE ASIDE COVER NOT LESS THAN 2.5d. OTHERWISE CATEGORY 5 APPLIES RATHER THAN CATEGORY 6.6. FOR SPLICE OF BARS WITH DIFFERENT SIZE, USE VALUE REQUIRED FOR LARGER BAR.

4-#6 EACH WAY

FIN FL EL

SEE PLANS

(AT STEEL POST

SE

E P

LAN

SLA

B T

HIC

KN

ES

S

1' - 0" 3' - 0" 1' - 0" .3" C

LR

8"

STEEL COLUMN AND BASEPLATE

CL

OF

BE

AM

LOC

AT

E A

T C

LO

F W

ALL

UN

OO

N P

LAN

S

PROVIDE 3" LONG SLOTTEDHOLE IN CHANNEL FLANGE

BEARING PLATE

BOTTOM PLATE NOTES:1. STOP PLATE AT EDGE OF OPENING WHEN NO CONTROL JOINT.2. EXTEND PLATE TO END OF BEAM WHEN THERE IS AN OFFSETCONTROL JOINT ABOVE THE OPENING.

(AT CMU WALL)

STEELCHANNELBEAM

3"

GROUT CELLS MINIMUM OF 6"AROUND EXPANSION BOLTS

METAL DECK

L3x3x1/4 CONTINUOUS

GROUT 8" AROUND ANCHOR

MASONRY WALL

DECK BRG EL

SEE PLAN

(AT CMU WALL, 1 SIDE)

3/4"Ø EXPANSION BOLTSWITH 5" MINIMUM EMBEDMENT@ 2'-0" OC

5/8

SPACE AS REQ(D)FOR DIAPRAGMOR 1'-0 OC MAX

2"8"

2"

1/2"

1/8 2" MIN

3/16

EXIST CMU WALL

BENT PL 3/8"x1'-0" (4" HORIZ LEG) W/(4) 3/4"Ø ADHESIVE ANCHORS @8" OC(6" MIN EMBED)

3/8" GUSSET PLCENTERED ON BENT PL

NEW JOIST PER PLAN

EXISTING FLOOR

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

Rev

isio

ns

5/1

2/2

017 2

:29:2

4 P

M

C:\R

evit\1

0-1

6206-0

0_S

T_2016_C

entr

al_

gla

rsen.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

ST

RU

CT

UR

AL D

ET

AIL

SS3.1

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NO SCALES3.1

21 STEEL BEAM REINFORCEMENT SCHEDULE

NO SCALES3.1

12 STEEL JOIST TO EXISTING BEAMNO SCALES3.1

13 STEEL JOIST DETAIL AT EXISTING ROOFNO SCALES3.1

14 STEEL COLUMN REINFORCEMENT SCHEDULE

NO SCALES3.1

22 BEAM REINFORCEMENT OVER COLUMNS

NO SCALES3.1

31 SPREAD FOOTING REINFORCEMENT DETAIL

NO SCALES3.1

15 TYP LINTEL AT NEW OPENING

NO SCALES3.1

24 STEEL JOIST TO EXISTING BEAM

NO SCALES3.1

34 SLAB-ON-GRADE-DETAIL

NO SCALES3.1

41 EXTERIOR WALL OPENING ELEVATIONNO SCALES3.1

42 POST CONNECTION DETAILNO SCALES3.1

43 DETAILNO SCALES3.1

44 POST BASE PLATE

NO SCALES3.1

51 CONDUIT ENCASEMENT

TOP OF STEEL

NO SCALES3.1

25 TYP BEARING STEEL ON MASONRY

NO SCALES3.1

16 TYP BEARING STEEL ON MASONRY

NO SCALES3.1

1 CONCRETE REINFORCING LAP SPLICES

NO SCALES3.1

45 TYP THICKENED SLAB DETAIL

NO SCALES3.1

26 TYP STEEL BEAM BEARING DETAIL

NO SCALES3.1

2 DECK TO WALL DETAILNO SCALES3.1

35 JOIST TO EXIST CMU WALL DETAIL

Page 21: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

BAS BUILDING AUTOMATION SYSTEMB to B BACK TO BACKBBO BOILER BLOW OFFBC BALANCING COCKBCMU BURNISHED CONCRETE MASONRY UNITBD BOARDBD BACK DRAFT DAMPERBET BETWEENBFP BACKFLOW PREVENTERBFR BELOW FLOORBF BOILER FEEDBFV BUTTERFLY VALVEBHP BREAK HORSE POWERBKR BREAKERBL BUILDING LINEBLDG BUILDINGBLK BLOCKBLKG BLOCKINGBLKHD BULKHEADBM BEAMBM BENCH MARKBOD BOTTOM OF DUCTBOF BOTTOM OF FOOTINGBOTT BOTTOMBRDG BRIDGINGBRG BEARINGBRKT BRACKETBSMT BASEMENTBT BATH TUBBTU BRITISH THERMAL UNITBTUH BRITISH THERMAL UNIT PER HOURBUR BUILT UP ROOFINGBV BALL VALVE

C CONDENSER WATERC CONDUITCA COMBUSTION AIRCAB CABINETCANT CANTILEVERCAP CAPACITYCAS CASINGCBD CHALKBOARDCD CONDENSATE DRAINCCTV CLOSED CIRCUIT TELEVISIONCE COVER ELEVATIONCEM CEMENTCENT CENTRIFUGALCER CERAMICCF CUBIC FEETCFH CUBIC FEET PER HOURCFM CUBIC FEET PER MINUTECG CORNER GUARDCH CHANNELCI CAST IRONCI CURB INLETCIP CAST IN PLACECIP CAST IRON PIPECIRC CIRCULATINGCJ CONTROL JOINTCJA CONTROL JOINT ABOVECKT CIRCUITCKT BK CIRCUIT BREAKERCL CENTERLINECL CIRCUIT LINECLG CEILINGCLOS CLOSETCLR CLEARCM CEILING MOUNTEDCMP CORRUGATED METAL PIPECMU CONCRETE MASONRY UNITCO CLEAN OUTCO CONDUIT ONLYCO2 CARBON DIOXIDECOL COLUMNCOM COMMONCOMB COMBINATIONCOMM COMMUNICATIONSCOMP COMPOSITECOMP COMPRESSOR UNITCOMPR COMPRESSIBLECONC CONCRETECONF CONFERENCECONFIG CONFIGURATIONCONN CONNECTCONN CONNECTIONCONST CONSTRUCTIONCONT CONTINUOUS OR CONTINUATIONCONTR CONTRACTOR OR CONTRACTCONV CONVECTORCORR CORRIDORCP CONDENSER PUMPCP COVER PLATECPS CYCLES PER SECONDCPT CARPETCR CONDENSER WATER RETURN

CR CORROSION RESISTANTCS COUNTERSINKCS COMBINATION SEWERCS CONDENSER WATER SUPPLYCSK COUNTERSUNKCSMU CALCIUM SILICATE MASONRY UNITCSP COMBINATION STANDPIPECJ CONSTRUCTION JOINTCSWK CASEWORKCT COOLING TOWERCT CERAMIC TILECT CURRENT TRANSFORMERCTR CENTERCU COPPERCU CONDENSING UNITCU CUBICCU COMBINATION UNITCUH CABINET UNIT HEATERCW COLD WATERCV CONDOM VENDORCWR CHILLED WATER RETURNCWS CHILLED WATER SUPPLYCY CUBIC YARDCYL CYLINDER

D DRAIND DEPTHD DATADB DRY BULBDB DECIBELDBA DEFORMED BAR ANCHORDBL DOUBLEDC DIRECT CURRENTDC DUST COLLECTORDCJ DUMMY CONTROL JOINTd PENNY (AS NAIL 10D)DDC DIRECT DIGITAL CONTROLDE DEIONIZED WATERDEG DEGREEDEPR DEPRESS(ION)(ED)DEPT DEPARTMENTDET DETENTIONDF DRINKING FOUNTAINDFR DIESEL FUEL RETURNDFS DIESEL FUEL SUPPLYDFV DIESEL FUEL VENTDG DOOR GRILLEDH DUCT HEATERDI DISTILLED WATERDI DUCTILE IRONDIA DIAMETERDIAG DIAGONALDIFF DIFFUSERDIM DIMENSIONDISC SW DISCONNECT SWITCHDISC DISCONNECTDISCH DISCHARGEDISTR DISTRIBUTIONDL DEAD LOADDM DAMPER MOTORDMPR DAMPERDN DOWNDSN DOWNSPOUT NOZZLEDO OR " DITTODPFG DAMPROOFINGDPS DIFFERENTIAL PRESSURE SWITCHDR DOORDR DRAINDS DOWNSPOUTDS DISTILLED WATERDSP DRY STANDPIPEDTL DETAILDTR DUCT THRU ROOFDW DISHWASHERDWG DRAWINGDWL DOWELDWR DRAWERDXS DOUBLE EXTRA STRONG

E EASTEA EACHEA EXHAUST AIREAT ENTERING AIR TEMPERATUREEB EXPANSION BOLTEC ELECTRICAL CONTRACTOREDH ELECTRIC DUCT HEATEREE EACH ENDEER ENERGY EFFICIENCY RATIOEEW EMERGENCY EYEWASHEEWS EMERGENCY EYEWASH/SHOWEREF EACH FACEEF EXHAUST FANEFF EFFICIENCYEH ELECTRICAL HEATEREIFS EXTERIOR INSULATION AND FINISH SYSTEMEJ EXPANSION JOINTEL ELEVATIONELAS ELASTOMERICELEC ELECTRIC(AL)ELEV ELEVATOREMCS ENERGY MANAGEMENT CONTROL SYSTEMEMER EMERGENCYEMD ESTIMATED MAXIMUM DEMANDEMT ELECTRICAL METALLIC TUBINGEMV EMERGENCY MIXING VALVEENCL ENCLOSUREENTR ENTRANCEEOMD END OF MAIN DRIPEP ELECTRO-PNEUMATICEP EXPLOSION PROOFEPO EMERGENCY POWER OFFERF EPOXY RESIN FLOORINGEQ EQUALEQUIP EQUIPMENTER EXHAUST REGISTERES EMERGENCY SHOWERES EXTRA STRONGESP EXTERNAL STATIC PRESSUREEST ESTIMATEET EXPANSION TANKEW EACH WAYEWC ELECTRIC WATER COOLEREWH ELECTRIC WATER HEATEREWT ENTERING WATER TEMPERATUREEXC EXCAVATEEXH EXHAUSTEXIST EXISTINGEXP EXPANSIONEXP EXPOSEDEXPL EXPLOSIONEXT EXTERIOR

F FAHRENHEITF FIRELINEF FURNACEFA FIRE ALARMFAB FABRICATEDFB FACE BRICKFC FLUID COOLER

FC FOOT CANDLEFCMU FLUTED CONCRETE MASONRY UNITFCO FLOOR CLEAN OUTFCU FAN COIL UNITFD FIRE DAMPERFD FLOOR DRAINFDC FIRE DEPARTMENT CONNECTIONFDN FOUNDATIONFDNDR FOUNDATION DRAINFDR FEEDERFE FIRE EXTINGUISHERFEC FIRE EXTINGUISHER CABINETFF FINISH FLOORFH FILTER HOUSINGFH FIRE HYDRANTFHC FIRE HOSE CABINETFIG FIGUREFIN FINISHFIX FIXTUREFL FLOORFLASH FLASHINGFLEX FLEXIBLEFLUOR FLUORESCENTFLG FLOORINGFLM FULL LENGTH MIRRORFM FACTORY MUTUALFM FIRE MAINFMCS FACILITIES MANAGEMENT CONTROL SYSTEMFME FLOW MEASURING EQUIPMENTFO FACE OFFO FINISH OPENINGFOC FACE OF CONCRETEFOF FACE OF FINISHFOF FUEL OIL FILLFOM FACE OF MASONRYFOR FUEL OIL RETURNFOS FACE OF STUDFOS FUEL OIL SUPPLYFOV FUEL OIL VENTFOW FACE OF WALLFP FIREPROOFINGFPD FIRE PUMP DISCHARGEFPM FEET PER MINUTEFR FIRE RESISTIVEFR FRAMEFRP FIBERGLASS REINFORCED PANELFS FLOOR SINKFS FLOW SWITCHFSD FIRE/SMOKE DAMPERF.S.E.C. FOOD SERVICE EQUIPMENT CONTRFSS FOLDING SHOWER SEATFT FEET (FOOT)FT FIN TUBEFT FLOW TRANSMITTERFTG FOOTINGFUT FUTUREFVC FIRE VALVE CABINETFWC FABRIC WALL COVERING

G GRILLEG NATURAL GASGA GAUGEGAL GALLONGALV GALVANIZEDGB GRAB BARGC GENERAL CONTRACTORGCO GRADE CLEAN OUTGCMU GLAZED CONCRETE MASONRY UNITGD GARBAGE DISPOSALGEN GENERALGEN GENERATORGFA GROSS FLOOR AREAGFI GROUND FAULT INTERRUPTERGFRC GLASS FIBER REINFORCED CONCRETEGHR GLYCOL-WATER HEATING RETURNGHS GLYCOL-WATER HEATING SUPPLYGI GALVANIZED IRONGL GLUE LAMINATEDGL GLASSGMU GLASS MASONRY UNITGND GROUNDGOVT GOVERNMENTGPH GALLONS PER HOURGPM GALLONS PER MINUTEGR GUARD RAILGR GRADEGR GRILLEGRC GLAVANIZED RIGID CONDUITGRC GLASS REINFORCED CONCRETEGRGP GLASS REINFORCED GYPSUM PLASTERGRS GALVANIZED RIGID STEELGS GASOLINEGV GATE VALVEGV GREASE VENTGW GREASE WASTEGWB GYPSUM WALL BOARDGYP GYPSUM

H HEIGHTH 1E HOOK ONE ENDHB HOSE BIBHC HANDICAPHC HOLLOW COREHCB HANDICAP BENCHHCR HOT / CHILLED WATER RETURNHCS HOT / CHILLED WATER SUPPLYHD HAND DRYER OR HAIR DRYERHDBD HARDBOARDHDR HEADERHDWD HARDWOODHDWR HARDWAREHEV HOSE END VALVEHID HIGH INTENSITY DISCHARGEHM HOLLOW METALHOA HAND OFF AUTOMATICHORIZ HORIZONTALHP HEAT PUMPHP HIGH PRESSUREHP HORSEPOWERHPR HIGH PRESSURE STEAM RETURNHPS HIGH PRESSURE SODIUMHPS HIGH PRESSURE STEAM SUPPLYHR HANDRAILHR HOURHS HEADSTUDHSTR HIGH STRENGTHHT HEIGHTHTG HEATINGHTR HEATERHTWR HIGH TEMP HOT WATER RETURNHTWS HIGH TEMP HOT WATER SUPPLYHUM HUMIDIFIERHV HEATING VENTILATING UNITHVAC HEATING VENTILATING AND AIR CONDITIONINGHW DOMESTIC HOT WATERHWC DOMESTIC HOT WATER RECIRCULATINGHWR LOW TEMP HOT WATER RETURNHWS LOW TEMP HOT WATER SUPPLYHX HEAT EXCHANGERHZ HERTZ

JAN JANITORJB JUNCTION BOXJCT JUNCTIONJST JOISTJFB JOINT FILLER BOARDJT JOINT

KCJ KEYED CONSTRUCTION JOINTKCP KEENE'S CEMENT PLASTERKD KNOCKDOWNKH KITCHEN HOODKHE KITCHEN HOOD EXHAUST FANKHS KITCHEN HOOD SUPPLY FANKIT KITCHENKO KNOCKOUTKS KITCHEN SINKKV KILOVOLTKVA KILOVOLT AMPERESKVAR KILOVOLT AMPERES REACTIVEKW KILOWATTKWH KILOWATT HOUR

L ANGLEL LAVATORYLA LABORATORY COMPRESSED AIRLAB LABORATORYLAM LAMINATE(D)LAT LEAVING AIR TEMPERATURELAV LAVATORYLB POUNDLBR LUMBERLBS POUNDSLDG LOADINGLF LINEAR FOOT (FEET)LG LENGTH (LONG)LIN LINEARLINO LINOLEUMLKR LOCKERLL LIVE LOADLLH LONG LEG HORIZONTALLLV LONG LEG VERTICALLOC LOCATIONLONG LONGITUDINALLOX LIQUID OXYGENLPG LIQUEFIED PETROLEUM GASLPR LOW PRESSURE STEAM RETURNLPS LOW PRESSURE STEAM SUPPLYLR LIVING ROOMLS LAWN SPRINKLERLSC LIFE SAFETY CODELT LIGHTLTD LINED TRANSFER DUCTLTG LIGHTINGLV LOUVERLV LABORATORY VACUUMLW LONG WAYLWT LEAVING WATER TEMPERATURE

M THOUSANDMA MIXED AIRMA MEDICAL COMPRESSED AIRMAC MACHINEMAG MAGNETICMAINT MAINTENANCEMAN MANUALMAS MASONRYMATL MATERIALMAU MAKEUP AIR UNITMAV MANUAL AIR VENTMAX MAXIMUMMB MACHINE BOLTMBD MARKER BOARDMBH THOUSAND BTU PER HOURMC MECHANICAL CONTRACTORMC MEDICINE CABINETMCA MINIMUM CIRCUIT AMPSMCB MAIN CIRCUIT BREAKERJMCM THOUSAND CIRCULAR MILLSMD MOTORIZED DAMPERMDO MEDIUM DENSITY OVERLAYMECH MECHANICALMEMB MEMBRANEMET METALMEZZ MEZZANINEMFR MANUFACTURERMFRG MANUFACTURINGMG MOTOR GENERATORMH MANHOLEMH METAL HALIDEMH MOP HOLDERMIN MINIMUMMISC MISCELLANEOUSML MOTORIZED LOUVERMLDG MOLDINGMLO MAIN LUGS ONLYMLWK MILLWORKMO MASONRY OPENINGMPG MEDIUM PRESSURE GASMPR MEDIUM PRESSURE STEAM RETURNMPS MEDIUM PRESSURE STEAM SUPPLYMR MIRRORMR/S MIRROR WITH SHELFMS MAGNETIC STARTERMS MOP SINKMTD MOUNTEDMTG MOUNTINGMTL METALMTWR MEDIUM TEMP HOT WATER RETURNMTWS MEDIUM TEMP HOT WATER SUPPLYMUL MULLIONMV MERCURY VAPORMV MEDICAL VACUUMMW MARKER WALL

N NITROGENN NORTHN2O NITROUS OXIDEN/A NOT APPLICABLE

P PAINTP POLEP/T PRESSURE/TEMPERATURE TEST PORTP PUMPPA PUBLIC ADDRESSPAN B PANIC BOLTPAR PARALLELPB PARTICLE BOARDPB PULL BOXPB PUSH BUTTONPBS PUSH BUTTON STATIONPC PRECASTPC PUMPED CONDENSATEPCD PAPER CUP DISPENSERPCF POUNDS PER CUBIC FOOTPCT PORCELAIN CERAMIC TILEPD PRESSURE DROPPD PUMP DISCHARGEPDI PLUMBING & DRAINAGE INSTITUTEPENT PENTHOUSEPERF PERFORATEDPERP PERPENDICULARPF POWER FACTORPG PRESSURE GAGEPH PHASEPI POINT OF INTERSECTIONPI PRESSURE INDICATORPIC PORTABLE INSTRUMENT CONNECTIONPIV POST INDICATOR VALVEPL PLACE(S)PL PLATEPLAM PLASTIC LAMINATEPLAS PLASTERPLBG PLUMBINGPLYWD PLYWOODPNEU PNEUMATICPNL PANELPOC POINT OF CONNECTIONPORC PORCELAINPPM PARTS PER MILLIONPR PAIRPREFAB PREFABRICATEDPROJ PROJECTIONPRV PRESSURE REDUCING VALVEPS PIPE SUPPORTPS PROJECTION SCREENPSF POUNDS PER SQUARE FOOTPSI POUNDS PER SQUARE INCHPSID POUNDS PER SQUARE INCH PRESSURE DROPPSV PRESSURE SAFETY VALVEPT PLASTER TRAPPT POINTPT POTENTIAL TRANSFORMERPTD PAPER TOWEL DISPENSERPTD/R COMBINATION TOWEL DISPENSER/RECEPTACLEPTN PARTITIONPVC POLYVINYL CHLORIDEPVI POINT OF VERTICAL INTERSECTIONPVT POINT OF VERTICAL TANGENCYPWL SOUND POWER LEVELPWR POWER

QT QUARRY TILEQTR RND QUARTER ROUND

R RISERRA RETURN AIRRAD RADIATORRAD or R RADIUSRB RUBBER BASERC REMOVE CONTROLRCP REFLECTED CEILING PLANRCP REINFORCED CONCRETE PIPERCU RECIPROCATING CHILLER JOINTRD ROOF DRAINRD REFRIGERANT DISCHARGERECP RECEPTACLEREF REFERENCEREFL REFLECTEDREFR REFRIGERANTREFR REFRIGERATORREG REGISTERREINF REINFORCEMENTREM REMOVABLEREQ(D) REQUIRE(D)RESIL RESILIENTRET RETAINING (WALL)REV REVISIONSRF RETURN FANRF RUBBER FLOORRFM RECESSED FLOOR MATRH RELATIVE HUMIDITYRH RELIEF HOODRHC REHEAT COILRH ROBE HOOKRHG REFRIGERANT HOT GASRI&C ROUGH IN AND CONNECTRIJS RISE IN JOIST SPACERL REFRIGERANT LIQUIDRM ROOMRND ROUNDRO ROUGH OPENING

S SINKS SANITARY SEWERS SOAP DISHS SOUTHS SPRINKLER LINESA SHOCK ABSORBERSA SUPPLY AIRSAN SANITARY WASTESC SECURITYSC SOLID CORESC SHOWER CURTAINSC SPECIAL COATINGSCD SEAT COVER DISPENSERSCH SHOWER CURTAIN HOOKSSCHED SCHEDULESCR SHOWER CURTAIN RODSCT STRUCTURAL CLAY TILESCUT SCUTTLESCW SOFT COLD WATERSD SOAP DISPENSERSD SMOKE DAMPERSD SMOKE DETECTORSD STORM DRAINSE STEAM EXHAUST VENTSEC SECONDARYSEC SECONDSECT SECTIONSECY SECRETARYSENS SENSIBLESF SQUARE FOOTSF SUPPLY FANSFA SPRINKLER FLOW ALARMSFCMU SPLIT-FACED CONCRETE MASONRY UNITSFU STRUCTURAL FACING UNITSGL SINGLESH SHOWERSHEATH SHEATHINGSHM SECURITY HOLLOW METALSHT SHEETSHW SOFT HOT WATERSIM SIMILARSL SHORT LEGSLNT SEALANTSM SHEET METALSM SPRINKLER MAINSND SANITARY NAPKIN DISPOSALSNV SANITARY NAPKIN VENDORSP STAND PIPESP STATIC PRESSURESPEC SPECIFICATIONSSPK SPRINKLERSPL SOUND PRESSURE LEVELSPL SPECIALSPL BLK SPLASH BLOCKSQ SQUARESS SOLIDS SEPARATORSS STAINLESS STEELSSA STORM SHELTER AREASS SERVICE SINKSS SOLID SURFACEST STAIRST STORM SEWERSTAG'D STAGGEREDSTC SOUND TRANSMISSION CLASSSTD STANDARDSTE SINGLE TAPERED ENDSTGR STRINGERSTL STEELSTOR STORAGESTR STRUCTURAL - STRUCTURESUB SUBSTATIONSUBFL SUBFLOORSURF SURFACESUSP SUSPENDEDSV SHEET VINYLSV SOLENOID VALVESW SHORT WAYSW SWITCHSWBD SWITCH BOARDSWP STEAM WORKING PORESSURESYM SYMMETRICAL

T TEMPEREDT THERMOSTATT & B TOP & BOTTOMT& G TONGUE & GROOVET TREADTA TRANSFER AIRTAB TEST AND BALANCETAN TANGENTTB TERMINAL BOXTB TOWEL BARTBD TACK BOARDTC TEMPERATURE CONTROLTCC TEMPERATURE CONTROL CONTRACTORTC TIME CLOCKTD TRANSFER DUCTTD TRENCH DRAINTDH TOTAL DYNAMIC HEADTEL TELEPHONETEMP TEMPERED - TEMPORARYTEMP TEMPERATURETERR TERRAZZOTEXT TEXTUREDTGL TOGGLETH THRESHOLDTH TOWEL HOOKTHK THICK(NESS)TMR TILT MIRROR UNITTMV THERMOSTATIC MIXING VALVETOB TOP OF BEAMTOC TOP OF CONCRETETOF TOP OF FOOTINGTOIL TOILETTOP TOP OF PAVINGTOS TOP OF STEELTOW TOP OF WALLTPV TRAP PRIMER VALVETR TRIPTRANS TRANSVERSETRD TREADTS TEMPERATURE SENSORTS TUBE STEELTSP TOTAL STATIC PRESSURETT TEMPERATURE TRANSMITTERTT TERRAZZO TILETTD TOILET TISSUE DISPENSERTV TELEVISIONTW TACK WALLTYP TYPICAL

UBC UNIFORM BUILDING CODEUC UNIT COOLERUG UNDERGROUND

V VENTV VOLTV VACUUMVA VALVEVAC VACUUMVAV VARIABLE AIR VOLUMEVB VAPOR BARRIERVB VINYL BASEVBF VENT BELOW FLOORVCB VENTED COVE BASEVCP VITRIFIED CLAY PIPEVCT VINYL COMPOSITION TILEVD VOLUME DAMPER - MANUALVEL VELOCITYVENT VENTILATIONVENT VENTILATORVERT VERTICALVEST VESTIBULEVF VINYL FLOORVFD VARIABLE FREQUENCY DRIVEVM VOLTMETERVOL VOLUMEVP VENEER PLASTERVP VACUUM PUMPVSMC VARIABLE SPEED MOTOR CONTROLLERVT VINYL TILEVTR VENT THROUGH ROOFVWC VINYL WALLCOVERING

W WATER SERVICEW WIDE; WIDTHW WASTEW WATTW WESTW WIDE FLANGEW/ WITHW/O ITHOUTWB WET BULBWC WALL COVERINGWC WATER COLUMNWC WATER CLOSETWCC WATER COOLED CONDENSERWCL WATER CLOSET/LAVATORY COMBINATIONWCO WALL CLEAN OUTWD WOODWDW WINDOWWF WASH FOUNTAINWH WALL HYDRANTWFMD WATER FLOW MEASURING DEVICEWH WATER HEATERWHM WATT HOUR METERWI WROUGHT IRONWLR WATER LOOP RETURNWLS WATER LOOP SUPPLYWMG WATER MOTOR GONGWNSCT WAINSCOTWP WEATHERPROOFWPB WHIRLPOOL BATHWPF WATERPROOFWPFG WATERPROOFINGWR WATER RESISTANTWR WASTE RECEPTACLEWSP WET STAND PIPEWT WEIGHTWW WARM WHITEWWF WELDED WIRE FABRIC

XFMR TRANSFORMERXMTR TRANSMITTER

YD YARDYH YARD HYDRANT

Z IMPEDANCEZCV ZONE CONTROL VALVEZVB ZONE VALVE BOX

& AND@ ATi.e. THAT IS# NUMBER

CG CLEAR FLOAT GLASSCIG CLEAR INSULATING GLASSCTG CLEAR TEMPERED FLOAT GLASSCTIG CLEAR TEMPERED INSULATING GLASSLG LAMINATED GLASSPG PATTERN GLASSPIG PATTERN INSULATING GLASSSG SPANDREL GLASSTG TINTED FLOAT GLASSTIG TINTED INSULATING GLASSTTG TINTED TEMPERED FLOAT GLASSTTIG TINTED TEMPERED INSULATING GLASSWG POLISHED WIRE GLASS

THE FOLLOWING ABBREVIATIONSARE USED WITH GLAZING:

IAQ INDOOR AIR QUALITYIAW IN ACCORDANCE WITHIB INFRARED BURNERIC INTERCOMID INSIDE DIAMETERIE INVERT ELEVATIONIES ILLUMINATING ENGINEERING SOCIETYIF INSIDE FACEIG ISOLATED GROUNDIH INTAKE HOODIJ ISOLATION JOINTIJS IN JOIST SPACEIMC INTERMEDIATE METAL CONDUITIN INCHINC INCLUDE (ING)INSUL INSULATIONINT INTERIORIP IRON PIPEIW INDIRECT WASTE

O&M OPERATION AND MAINTENANCEO to O OUT TO OUTOA OVERALLOA OUTSIDE AIROBSC OBSCUREOC ON CENTEROD OUTSIDE DIAMETEROD OVERFLOW DRAINOF OUTSIDE FACEOVFL OVERFLOWOFCI OWNER FURNISHED CONTRACTOR INSTALLEDOFF OFFICEOFOI OWNER FURNISHED OWNER INSTALLEDOHP OVERHEAD POWEROHT OVERHEAD TELEPHONEOPNG OPENINGOPP OPPOSITEOSD OVERFLOW STORM DRAINOS&Y OUTSIDE SCREW AND YOKEOTCS OPEN TO CEILING SPACEOVHD OVERHEADOX OXYGEN

A/C AIR CONDITIONING(ER)A OR AMP AMPEREA COMPRESSED AIRAAP AREA ALARM PANELAAV AUTOMATIC AIR VENTAB ANCHOR BOLTABS ACRYLONITRILE-BUTADIENE-STYRENEAC ACOUSTICAL CEILINGAC ALTERNATING CURRENTACC AIR COOLED CONDENSERACCUAIR COOLED CONDENSING UNITACM ALUMINUM COMPOSITE MATERIALACST ACOUSTICAD ACCESS DOORAD AREA DRAINADDNADDITION OR ADDITIONALADJ ADJUSTABLEADJT ADJACENTADMIN ADMINISTRATIONA/E ARCHITECT/ENGINEERAF AIR FILTERAFF ABOVE FINISH FLOORAFG ABOVE FINISH GRADEAHJ AUTHORITY HAVING JURISDICTIONAHU AIR HANDLING UNITAI AREA INLETALT ALTERNATEALUMALUMINUMAMB AMBIENTANCHANCHORAP ACCESS PANELAPC ACOUSTICAL PANEL CEILINGAPPROX APPROXIMATEAR ACID RESISTINGARCHARCHITECTURALASB ASBESTOSASPHASPHALTAUTO AUTOMATICAV ACID VENTAV AIR VENTAVG AVERAGEAW ACID WASTEAWG AMERICAN WIRE GAUGEAWP ACOUSTICAL WALL PANEL

ABBREVIATIONSNC NOISE CRITERIANC NORMALLY CLOSEDNC NURSE CALLNEC NATIONAL ELECTRIC CODENEMA NATIONAL ELECTRICAL MANUFACTURERS ASSN.NEUT NEUTRALNIC NOT IN CONTRACTNO NORMALLY OPENNO NUMBERNO NITROUS OXIDENOM NOMINALNS NEUTRAL SENSORNTS NOT TO SCALE

RPM REVOLUTIONS PER MINUTERPBP REDUCED PRESSURE BACKFLOW PREVENTERRS REFRIGERANT SUCTIONRWL RAIN WATER LEADERS SENSOR

UGE UNDERGROUND ELECTRICALUGT UNDERGROUND TELEPHONEUH UNIT HEATERUL UNDERWRITERS LABORATORIESUNEX UNEXCAVATEDUNFIN UNFINISHEDUNO UNLESS NOTED OTHERWISEUR URINALURD UNDERGROUND RESIDENTIAL DISTRIBUTIONUS UTILITY SHELFUTIL UTILITYUV UNIT VENTILATOR

GENERAL SYMBOLS

(CONTINUOUS BLOCKING)

BATT INSULATION

RIGID INSULATION

CARPET (LARGE SCALE)

TILE (LARGE SCALE)

ACOUSTICAL TILE (LARGE SCALE)

PROTECTION BOARD

CONCRETE MASONRY UNIT

METAL STUDS

STEEL (LARGE SCALE)

(LARGE SCALE)GYPSUM WALL BOARD

PLYWOOD (LARGE SCALE)

BRICK VENEER

SHINGLES

STONE

GLASS

(TRIM/FINISH)WOOD

(NON-CONTINUOS BLOCKING)WOOD

GRAVEL/BALLAST

WOOD

GYM FLOOR

STEEL

PRECAST CONCRETE

CONCRETE

SAND

EARTH

AT ONE DETAIL NUMBER

SHEET ON WHICH DRAWN

REVISION NUMBER

WALL TYPE

WINDOW NUMBERDOOR NUMBER AND

ROOM NUMBER

COLUMN LINE

MULTIPLE ELEVATIONSCASEWORK ELEVATION WITH

LEGEND ORKEY NOTE

BUILDING ELEVATIONINTERIOR ELEVATION

DETAIL REFERENCE

DETAIL OR WALL SECTION

CROSS REFERENCE

DETAIL NUMBER

CASEWORKELEVATION

SIMILAR OR TYPICAL REFERENCE

SIMILAR OR TYPICAL REFERENCE

BUILDING SECTION

?

?

?

?

?

?

?

?

?

?

?

?

?

ROOM NAME

?

?

?

?

?

?

?

?

SIM

?

?

SIM

DIFFUSER (SUPPLY)

GRILLE (RETURN)

WALL REGISTER

SLOT DIFFUSER

SUPPLY ARROW

RETURN ARROW

EXHAUST ARROW

RECTANGULAR DIFFUSER INDICATIONSHOWING CFM

ROUND DIFFUSER INDICATIONSHOWING CFM

RECTANGULAR GRILLE INDICATIONSHOWING CFM

RECTANGULAR REGISTER INDICATIONSHOWING CFM

FIRE DAMPER

SMOKE DAMPER

FIRE/SMOKE DAMPER

BACKDRAFT DAMPER

GRAVITY DAMPER

MOTORIZED DAMPER

VOLUME DAMPER

SECURITY BAR

THERMOSTAT - WALL MOUNTED

THERMOSTAT - CEILING MOUNTED

CARBON MONOXIDE SENSOR - WALL MOUNTED

CARBON MONOXIDE SENSOR - CEILING MOUNTED

CARBON DIOXIDE SENSOR - WALL MOUNTED

HUMIDISTAT - WALL MOUNTED

HUMIDISTAT - CEILING MOUNTED

TEMPURATURE SENSOR - WALL MOUNTED

TEMPURATURE SENSOR - CEILING MOUNTEDS

S

H

H

CO2

CO

CO

T

T

BD

FS

S

F

R-112"x12"

200 CFM

G-112"x12"

200 CFM

D-112" Ø

200 CFM

D-112"x12"

200 CFM

HVAC

PIPING - HEATING

24"x12"TYPICAL DUCT - SIZE AS INDICATED(WIDTH / DEPTH) SIZE INDICATES FREE AREA

MITERED ELBOW WITH VANES

MITERED ELBOW WITHOUT VANES

RADIUS ELBOW

TEE WITH VANES

TEE WITH RADIUS

ROUND DUCT UP

SUPPLY DUCT UP

RETURN DUCT UP

EXHAUST DUCT UP

ROUND DUCT DOWN

SUPPLY DUCT DOWN

RETURN DUCT DOWN

EXHAUST DUCT DOWN

FLEXIBLE CONNECTION

TRANSFER DUCT

SUPPLY AIR - SINGLE LINE

RETURN AIR - SINGLE LINE

EXHAUST AIR - SINGLE LINE

OUTSIDE AIR - SINGLE LINE

SINGLE LINE REDUCER

SINGLE LINE FLEX DUCT

NEW TO EXISTING CONNECTION POINT

PLUMBING

SA

RA

EA

OA

CWS

CWR

HCS

HCR

CS

CR

WLS

WLR

RL

RS

RHG

RD

CD

G

SCW

SHW

T

DI

DE

CD

VAC

LV

MV

N

CO2

N2O

OX

LOX

A

LA

MA

LS

HWS

HWR

HTWS

HTWR

MTWS

MTWR

LPS

LPR

HPS

HPR

FOS

FOR

FOV

CW

110 HW

140 HW

110 HWC

140 HWC

SD

SD

OSD

OSD

V

VBF

AW

LOW TEMP HOT WATER SUPPLY

LOW TEMP HOT WATER RETURN

HIGH TEMP HOT WATER SUPPLY

HIGH TEMP HOT WATER RETURN

MEDIUM TEMP HOT WATER SUPPLY

MEDIUM TEMP HOT WATER RETURN

LOW PRESSURE STEAM SUPPLY

LOW PRESSURE STEAM RETURN

HIGH PRESSURE STEAM SUPPLY

HIGH PRESSURE STEAM RETURN

FUEL OIL SUPPLY

FUEL OIL RETURN

FUEL OIL VENT

CHILLED WATER SUPPLY

CHILLED WATER RETURN

HOT/CHILLED WATER SUPPLY

HOT/CHILLED WATER RETURN

CONDENSER WATER SUPPLY

CONDENSER WATER RETURN

WATER LOOP SUPPLY

WATER LOOP RETURN

REFRIGERANT LIQUID

REFRIGERANT SUCTION

REFRIGERANT HOT GAS

REFRIGERANT DISCHARGE

CONDENSATE DRAIN

GAS

SOFT COLD WATER

SOFT HOT WATER

TEMPERED

DISTILLED WATER

DEIONIZED WATER

CONDENSATE DRAIN

VACUUM

LABORATORY VACUUM

MEDICAL VACUUM

NITROGEN

CARBON DIOXIDE

NITROUS OXIDE

OXYGEN

LIQUID OXYGEN

COMPRESSED AIR

LABORATORY COMPRESSED AIR

MEDICAL COMPRESSED AIR

LAWN SPRINKER

DOMESTICE COLD WATERORDOMESTIC COLD WATER

110°F DOMESTIC HOT WATER

140°F DOMESTIC HOT WATER

DOMESTIC HOT WATER (GENERIC)

110°F DOMESTIC HOT WATER RECIRULATING

140°F DOMESTIC HOT WATER RECIRCULATING

DOMESTIC HOT WATER RECIRC (GENERIC)

STORM DRAIN ABOVE FLOOR

STORM DRAIN BELOW FLOOR

OVERFLOW STORM DRAIN ABOVE FLOOR

OVERFLOW STORM DRAIN ABOVE FLOOR

SANITARY WASTE ABOVE FLOOR

SANITARY WASTE BELOW FLOOR

VENT

VENT BELOW FLOOR

ACID WASTE BELOW FLOOR

XX

GCO

FCO

WCO

CO CLEAN OUT

WALL CLEAN OUT

FLOOR CLEAN OUT

FLOOR DRAIN / FLOOR SINK

ROOF DRAIN / OVERFLOW ROOF DRAIN

RISER ID

DOWNSPOUT NOZZLE

WALL HYDRANT

HOSE BIB

ALIGNMENT GUIDE

PIPE ANCHOR

EXPANSION JOINT

PIPE CAP

PIPE UP

PIPE DOWN

PIPE TEE, UP

PIPE TEE, DOWN

UNION

DIRECTION OF PIPE PITCH

AQUASTAT

WATER HAMMER ARRESTER

ANESTHESIA EVACUATION

MEDICAL COMPRESSED AIR OUTLET

DEINONIZED WATER OUTLET

DISTILLED WATER OUTLET

NATURAL GAS OUTLET

NITROGEN OUTLET

NITOUS OXIDE OUTLET

OXYGEN OUTLET

VACUUM OUTLET

NEW TO EXISTING CONNECTION POINT

FIRE PROTETION WATER SUPPLY

SPRINKLER MAIN

ALARM VALVE, WET

ALARM VALVE, DRY

FIRE PROTECTION RISER

FIRE DEPARTMENT CONNECTION

GRADE CLEAN OUT(DOUBLE CLEAN OUT)

X

A

A

D

D

G

N

N

V

O

S

E

F

SM

FS

PS

SPRINKLER HEAD, PENDANT

SPRINKLER HEAD, UPRIGHT

SPRINKLER HEAD, SIDE WALL

FLOW SWITCH

PRESSURE SWITCH

OS&Y VALVE

VALVES AND FITTINGSEXPANSION LOOP

BALANCING VALVE

BALANCING VALVEWITH METERING POINTS

BALL VALVE

BUTTERFLY VALVE

VALVE (GENERIC)

CHECK VALVE

CONCENTRIC REDUCER

ECCENTRIC REDUCER

STEAM TRAP

FLEXIBLE CONNECTION

FLOW DIRECTION

GATE VALVE

GLOBE VALVE

MANUAL AIR VENT

AUTOMATIC AIR VENT

PLUG VALVE

PRESSURE GAUGE

SOLENOID VALVE

ANGLE VALVE

AUTOMATIC CONTROL VALVE 2-WAY

AUTOMATIC CONTROL VALVE 3-WAY

AUTOMATIC FLOW CONTROL VALVE

STRAINER

PRESSURE AND TEMPURATURETEST PORT

THERMOMETER

PUMP (GENERIC)

PRESSURE REDUCING VALVE (WATER SYSTEMS)PRESSURE REGULATING VALVE (GAS SYSTEMS)

RELIEF VALVE

P T

MECHANICAL SYMBOLS

PIPING - A/C & REFR

FIRE PROTECTION

OS&Y VALVE (INDICATING)

AW ACID WASTE ABOVE FLOOR

M

GD

BARAMETRIC RELIEF DAMPERRD

VOLUME DAMPERVD

AIRFLOW MEASUREMENT STATIONAFMS

DIFFERENTIAL PRESSURE SENSOR(DUCT MOUNTED)

DP

STATIC PRESSURE SENSOR(DUCT MOUNTED)

SP

DUCT SMOKE DETECTOR

CARBON DIOXIDE SENSOR - CEILING MOUNTEDCO2

NITROGEN DIOXIDE SENSOR - WALL MOUNTEDNO2

NITROGEN DIOXIDE SENSOR - CEILING MOUNTEDNO2

OPPOSED DAMPER

PARALLEL DAMPER

AV ACID VENT

PRESSURE REDUCING DAMPERPR

FLOW MEASURING DEVICE

REDUCED PRESSURE ZONE BACKFLOW PREVENTER

TRANSFER AIR - SINGLE LINETA

LINED TRANSFER DUCTLTD

PRESSURE SENSOR - WALL MOUNTED

PRESSURE SENSOR - CEILING MOUNTEDP

P

W

W

PLUMBING NOTATIONPIPE SIZES SHOWN ON THE DRAWINGS CAN BE FOLLOWED BY PIPE SIZING CRITERIA. THIS CRITERIA CAN EITHER BE SQUARE FOOTAGE (FORSTORM DRAIN PIPING), FIXTURE UNIT VALUES (FOR DOMESTIC WATER PIPING, SANITARY WASTE PIPING, AND SANITARY VENT PIPING) OR INTHOUSAND'S OF BTUH - MBH (FOR NATURAL GAS PIPING). THE FOLLOWING LEGEND WILL AID IN UNDERSTANDING THE DRAWINGS.

FOR EXAMPLE:

1. 12" SD (32,000 SF): THIS IS A 12" STORM DRAIN PIPE CARRYING 32,000 SQUARE FEET OF ROOF AREA.

2. 3" CW (200 CFU): THIS IS A 3" COLD WATER PIPE CARRYING 200 COLD WATER FIXTURE UNITS.

3. 2" HW (50 HFU): THIS IS A 2" HOT WATER PIPE CARRYING 50 HOT WATER FIXTURE UNITS.

4. 1" HWC (5.0 GPM): THIS IS A 1" HOT WATER CIRCULATING PIPE CARRYING 5.0 GALLONS PER MINUTE FLOW.

5. 4" W (150 WFU): THIS IS A 4" SANITARY WASTE PIPE CARRYING 150 WASTE FIXTURE UNITS.

6. 2" V (20 VFU): THIS IS A 2" SANITARY VENT PIPE CARRYING 20 VENT FIXTURE UNITS.

8. 1-1/4" G (600 MBH): THIS IS A 1-1/4" NATURAL GAS PIPE CARRYING 600,000 BTUH.

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

Rev

isio

ns

5/8

/2017 3

:40:0

7 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

ME

CH

AN

ICA

L S

YM

BO

LS

AN

D A

BB

RE

VIA

TIO

NS

M0.0

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

Page 22: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

6

7

5

4

3

2

1

HA B C D E F G

8

9

10

EXISTINGRF-2EXISTING EXHAUST LOUVER

EXISTING RELIEF LOUVER

24"x16" SA 36"x16" SA 42"x18" SA 54"x18" SA 56"x24" SA20"x8" SA

8"x8" EA

8"x8" EA

14"x10" EA

60"x28" RA

EXISTINGAHU-2

66"x

24"

SA

64"x

24"

SA

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

BA

NORTH

Rev

isio

ns

5/8

/2017 3

:39:5

2 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

HV

AC

DE

MO

LIT

ION

PLA

N, LO

WE

R L

EV

EL -

AR

EA

AD

M1.0

A

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

HVAC DEMOLITION PLAN, LOWER LEVEL - AREA A

REMOVE EXISTING SUPPLY DUCTWORK AND DIFFUSERS

REMOVE EXISTING CRAC UNIT AND ASSOCIATED DUCTWORK AND DIFFUSERS

REMOVE DUCT TO THIS LOCATION AND CAP

A. MECHANICAL ITEMS INDICATED FULL TONE (DARK) AREITEMS TO BE SALVAGED FOR RE-USE OR DEMOLISHED.MECHANICAL ITEMS INDICATED HALF TONE (LIGHT) AREEXISTING ITEMS TO REMAIN. CONTRACTOR TO PROPERLYDISPOSE OF MATERIAL NOT RE-USED.

B. EXISTING MECHANICAL ITEMS HAVE BEEN INDICATED FROMTHE EXISTING PLANS AND VERIFIED TO THE EXTENT POSSIBLE.THE CONTRACTOR IS TO FIELD VERIFY ALL EXISTINGCONDITIONS PRIOR TO CONSTRUCTION AND REPORT ANYDISCREPANCIES THAT CHANGE THE SCOPE OF WORK TO THEARCHITECT/ENGINEER. (NOTE: ALL ITEMS MAY NOT BEINDICATED.)

C. DRAWINGS ARE OF SMALL SCALE, NOT ALL FITTINGS ANDOFFSETS ARE INDICATED.

D. FACILITY IS TO REMAIN OPERATIONAL DURINGCONSTRUCTION. ROOM TEMPERATURES IN CRITICAL ROOMSMUST REMAIN AT ACCEPTABLE LEVELS AT ALL TIMES. ANYSHUT DOWN OF EQUIPMENT OR INTERRUPTION OF HVACSERVICES TO NON-CRITICAL ROOMS MUST BE COORDINATEDWITH OWNER. COORDINATE WITH OWNER WHICH ROOMS ARETEMPERATURE CRITICAL.CHILLED WATER AND HEATING WATERPIPING TO BE REMOVED SHALL BE DONE WITHOUT SHUTTINGDOWN AND DRAINING RESPECTIVE SYSTEMS.

GENERAL NOTES

Page 23: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

6

7

5

4

3

2

1

H I J K L M

8 REMOVE EXISTING SUPPLY AND RETURN DUCTWORKAND ASSOCIATED TERMINAL BOXES AND DIFFUSERS

REMOVE EXISTING EXHAUST DUCTWORKAND GRILLES WHERE SHOW DASHED

66"x

24"

SA

64"x

24"

SA

REMOVE DUCT TO THISLOCATION AND CAP

REMOVE DUCT TO THISLOCATION AND COVER.PREPARE OPENING TOCONNECT WITH NEWEXHAUST DUCTWORK.

10

10

11

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

LEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET

BA

NORTH

Rev

isio

ns

5/8

/2017 3

:39:5

2 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

HV

AC

DE

MO

LIT

ION

PLA

N, LO

WE

R L

EV

EL -

AR

EA

BD

M1.0

B

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

HVAC DEMOLITION PLAN, LOWER LEVEL - AREA B

A. MECHANICAL ITEMS INDICATED FULL TONE (DARK) AREITEMS TO BE SALVAGED FOR RE-USE OR DEMOLISHED.MECHANICAL ITEMS INDICATED HALF TONE (LIGHT) AREEXISTING ITEMS TO REMAIN. CONTRACTOR TO PROPERLYDISPOSE OF MATERIAL NOT RE-USED.

B. EXISTING MECHANICAL ITEMS HAVE BEEN INDICATED FROMTHE EXISTING PLANS AND VERIFIED TO THE EXTENT POSSIBLE.THE CONTRACTOR IS TO FIELD VERIFY ALL EXISTINGCONDITIONS PRIOR TO CONSTRUCTION AND REPORT ANYDISCREPANCIES THAT CHANGE THE SCOPE OF WORK TO THEARCHITECT/ENGINEER. (NOTE: ALL ITEMS MAY NOT BEINDICATED.)

C. DRAWINGS ARE OF SMALL SCALE, NOT ALL FITTINGS ANDOFFSETS ARE INDICATED.

D. FACILITY IS TO REMAIN OPERATIONAL DURINGCONSTRUCTION. ROOM TEMPERATURES IN CRITICAL ROOMSMUST REMAIN AT ACCEPTABLE LEVELS AT ALL TIMES. ANYSHUT DOWN OF EQUIPMENT OR INTERRUPTION OF HVACSERVICES TO NON-CRITICAL ROOMS MUST BE COORDINATEDWITH OWNER. COORDINATE WITH OWNER WHICH ROOMS ARETEMPERATURE CRITICAL.CHILLED WATER AND HEATING WATERPIPING TO BE REMOVED SHALL BE DONE WITHOUT SHUTTINGDOWN AND DRAINING RESPECTIVE SYSTEMS.

GENERAL NOTES

Keynote Legend

KeyValue Keynote Text

1 FIRE PROTECTION MAINS ROUTED OVER THISAREA TO BE MOVED TO ACCOMMODATE NEWELECTRICAL AND FUTURE UPS ROOMS.

2 EXISTING AHU TO BE REBALANCED TOADJUST FOR AIRFLOW DEDUCTED FROMUNIT.

3 HATCHED AREA INDICATES WORK ABOVECEILING TO BE DONE AS PART OF BIDPACKAGE #2. WORK ASSOCIATED WITH BIDPACKAGE #2 SHALL BE COMPLETED PRIORTO CEILING GRID INSTALLATION.

4 NEW 6" CWS/CWR PIPING TO BE INSTALLEDAS PART OF BID PACKAGE #2 TO BE ROUTEDAS HIGH AS POSSIBLE TIGHT TOSTRUCTURE. COORDINATE ALL WORK INTHIS AREA WITH BID PACKAGE #2MECHANICAL CONTRACTOR.

5 NEW ELECTRICAL CONDUITS TO BEINSTALLED AS PART OF BID PACKAGE #2 TOBE ENCLOSED IN CONCRETE DUCT BANKOVER EXISTING RESTROOMS ANDCORRIDOR. COORDINATE ALL WORK IN THEAREA WITH THE BID PACKAGE #2ELECTRICAL CONTRACTOR.

6 CAP AND VALVE FOR FUTURE COILCONNECTIONS.

7 PROVIDE WALL TYPE THERMOSTAT, MOUNTTO CEILING. PROVIDE ADDITIONAL CONTROLWIRE TO ACCOMMODATE RELOCATION OFTHERMOSTAT AS SPACES ARE FITTED OUT.

9 BUILDING IS TO REMAIN OPERATIONALDURING RENOVATION. COORDINATE WITHOTHER DISCIPLINES TO MINIMIZE THESPRINKLER SYSTEM DOWN TIME. IN THEEVENT OF AN EXTENDED SHUT DOWN OFTHE SPRINKLER SYSTEM, CONTRACTOR TONOTIFY LOCAL FIRE DEPARTMENT AND FIRECODE OFFICIAL AND PROVIDE FIRE WATCHPER NFPA STANDARDS .

10 HVAC DEMOLITION IN THIS AREA IS LIMITEDTO EXISTING AIRSIDE COMPONENTS ONLY.CAREFULLY REMOVE COMPONENTSWITHOUT DISRUPTING SERVICE TO WATERLINES ROUTED ABOVE THE CORRIDOR.

11 REMOVE AND REINSTALL EXHAUSTDUCTWORK AND GRILLES IF NECESSARY TOCOMPLETE ELECTRICAL WORK ABOVERESTROOMS AND CORRIDOR.

12 RELOCATE EXISTING HUMIDIFIER TO EASTWALL OF MECHANICAL ROOM. SEE SHEETM2.0A FOR NEW LOCATION.

13 SHUT OFF SUPPLY AND RETURN VALVES TOBRANCH AND DRAIN DOWN TO ALLOW FORREMOVAL OF HOT WATER PIPING TOTERMINAL BOXES.

14 ENSURE HYDRONIC PIPING IS REMOVEDBACK TO THE CORRIDOR. NO EXISTING ORNEW WATER PIPING IS TO BE ROUTED OVERNEW ELECTRICAL SPACES.

15 PROVIDE LOW LEAKAGE OPPOSED BLADEVOLUME DAMPER.

Page 24: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

6

7

5

4

3

2

1

HA B C D E F G

8

9

EXISTINGRF-2

EXISTINGEF-2

EXISTINGEF-3

EXISTINGAHU-2

EXISTINGH-1

REMOVE EXISTING CHILLED WATER SUPPLYAND RETURN PIPING ASSOCIATED WITHCRAC UNIT BACK TO VALVES AND CAP.

REMOVE EXISTING HUMIDIFIER STEAM LINE. CAPAND VALVE CONNECTION TO DUCT MANIFOLD TOALLOW FOR RECONNECTION LATER.

3"3"

HW

R3"

3" H

WS

4"4"

CW

R4"

4" C

WS

1 1/2"1 1/2" CWS

1 1/2"1 1/2" CWR

3"3" HWR3"3" HWS

4"4" CWR4"4" CWS

12

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

BA

NORTH

Rev

isio

ns

5/8

/2017 3

:39:5

3 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

HV

AC

PIP

ING

DE

MO

LIT

ION

PLA

N, LO

WE

R L

EV

EL -

AR

EA

AD

M2.0

A

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

HVAC PIPING DEMOLITION PLAN, LOWER LEVEL - AREA A

A. MECHANICAL ITEMS INDICATED FULL TONE (DARK) AREITEMS TO BE SALVAGED FOR RE-USE OR DEMOLISHED.MECHANICAL ITEMS INDICATED HALF TONE (LIGHT) AREEXISTING ITEMS TO REMAIN. CONTRACTOR TO PROPERLYDISPOSE OF MATERIAL NOT RE-USED.

B. EXISTING MECHANICAL ITEMS HAVE BEEN INDICATED FROMTHE EXISTING PLANS AND VERIFIED TO THE EXTENT POSSIBLE.THE CONTRACTOR IS TO FIELD VERIFY ALL EXISTINGCONDITIONS PRIOR TO CONSTRUCTION AND REPORT ANYDISCREPANCIES THAT CHANGE THE SCOPE OF WORK TO THEARCHITECT/ENGINEER. (NOTE: ALL ITEMS MAY NOT BEINDICATED.)

C. DRAWINGS ARE OF SMALL SCALE, NOT ALL FITTINGS ANDOFFSETS ARE INDICATED.

D. FACILITY IS TO REMAIN OPERATIONAL DURINGCONSTRUCTION. ROOM TEMPERATURES IN CRITICAL ROOMSMUST REMAIN AT ACCEPTABLE LEVELS AT ALL TIMES. ANYSHUT DOWN OF EQUIPMENT OR INTERRUPTION OF HVACSERVICES TO NON-CRITICAL ROOMS MUST BE COORDINATEDWITH OWNER. COORDINATE WITH OWNER WHICH ROOMS ARETEMPERATURE CRITICAL.CHILLED WATER AND HEATING WATERPIPING TO BE REMOVED SHALL BE DONE WITHOUT SHUTTINGDOWN AND DRAINING RESPECTIVE SYSTEMS.

GENERAL NOTES

Keynote Legend

KeyValue Keynote Text

1 FIRE PROTECTION MAINS ROUTED OVER THISAREA TO BE MOVED TO ACCOMMODATE NEWELECTRICAL AND FUTURE UPS ROOMS.

2 EXISTING AHU TO BE REBALANCED TOADJUST FOR AIRFLOW DEDUCTED FROMUNIT.

3 HATCHED AREA INDICATES WORK ABOVECEILING TO BE DONE AS PART OF BIDPACKAGE #2. WORK ASSOCIATED WITH BIDPACKAGE #2 SHALL BE COMPLETED PRIORTO CEILING GRID INSTALLATION.

4 NEW 6" CWS/CWR PIPING TO BE INSTALLEDAS PART OF BID PACKAGE #2 TO BE ROUTEDAS HIGH AS POSSIBLE TIGHT TOSTRUCTURE. COORDINATE ALL WORK INTHIS AREA WITH BID PACKAGE #2MECHANICAL CONTRACTOR.

5 NEW ELECTRICAL CONDUITS TO BEINSTALLED AS PART OF BID PACKAGE #2 TOBE ENCLOSED IN CONCRETE DUCT BANKOVER EXISTING RESTROOMS ANDCORRIDOR. COORDINATE ALL WORK IN THEAREA WITH THE BID PACKAGE #2ELECTRICAL CONTRACTOR.

6 CAP AND VALVE FOR FUTURE COILCONNECTIONS.

7 PROVIDE WALL TYPE THERMOSTAT, MOUNTTO CEILING. PROVIDE ADDITIONAL CONTROLWIRE TO ACCOMMODATE RELOCATION OFTHERMOSTAT AS SPACES ARE FITTED OUT.

9 BUILDING IS TO REMAIN OPERATIONALDURING RENOVATION. COORDINATE WITHOTHER DISCIPLINES TO MINIMIZE THESPRINKLER SYSTEM DOWN TIME. IN THEEVENT OF AN EXTENDED SHUT DOWN OFTHE SPRINKLER SYSTEM, CONTRACTOR TONOTIFY LOCAL FIRE DEPARTMENT AND FIRECODE OFFICIAL AND PROVIDE FIRE WATCHPER NFPA STANDARDS .

10 HVAC DEMOLITION IN THIS AREA IS LIMITEDTO EXISTING AIRSIDE COMPONENTS ONLY.CAREFULLY REMOVE COMPONENTSWITHOUT DISRUPTING SERVICE TO WATERLINES ROUTED ABOVE THE CORRIDOR.

11 REMOVE AND REINSTALL EXHAUSTDUCTWORK AND GRILLES IF NECESSARY TOCOMPLETE ELECTRICAL WORK ABOVERESTROOMS AND CORRIDOR.

12 RELOCATE EXISTING HUMIDIFIER TO EASTWALL OF MECHANICAL ROOM. SEE SHEETM2.0A FOR NEW LOCATION.

13 SHUT OFF SUPPLY AND RETURN VALVES TOBRANCH AND DRAIN DOWN TO ALLOW FORREMOVAL OF HOT WATER PIPING TOTERMINAL BOXES.

14 ENSURE HYDRONIC PIPING IS REMOVEDBACK TO THE CORRIDOR. NO EXISTING ORNEW WATER PIPING IS TO BE ROUTED OVERNEW ELECTRICAL SPACES.

15 PROVIDE LOW LEAKAGE OPPOSED BLADEVOLUME DAMPER.

Page 25: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

6

7

5

4

3

2

1

H I J K L M

8

REMOVE EXISTING HOT WATER SUPPLY ANDRETURN TO THIS LOCATION. CAP AND VALVE.

3"3" HWR3"3" HWS

4"4" CWR4"4" CWS

8"8" CS

8"8" CR

8"8" CWS

8"8" CWR2"2" HWS2"2" HWR

8"8"

CW

S

8"8"

CW

R

2"2"

HW

R2"

2" H

WS

8"8" C

R

8"8" C

S

6"6" C

R

6"6"

CW

S6"

6" C

WR

2"2" CWR2"2" CWS

2"2" CWS2"2" CWR

8"8" CS

6"6" CS

6"6" CR

6"6" CW

R

6"6" CW

S

2"2"

CW

S2"

2" C

WR

2"2" CWS2"2" CWR

6"6" CWS6"6" CWR

13

14 14

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

LEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET

BA

NORTH

Rev

isio

ns

5/8

/2017 3

:39:5

4 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

HV

AC

PIP

ING

DE

MO

LIT

ION

PLA

N, LO

WE

R L

EV

EL -

AR

EA

BD

M2.0

B

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

HVAC PIPING DEMOLITION PLAN, LOWER LEVEL - AREA B

A. MECHANICAL ITEMS INDICATED FULL TONE (DARK) AREITEMS TO BE SALVAGED FOR RE-USE OR DEMOLISHED.MECHANICAL ITEMS INDICATED HALF TONE (LIGHT) AREEXISTING ITEMS TO REMAIN. CONTRACTOR TO PROPERLYDISPOSE OF MATERIAL NOT RE-USED.

B. EXISTING MECHANICAL ITEMS HAVE BEEN INDICATED FROMTHE EXISTING PLANS AND VERIFIED TO THE EXTENT POSSIBLE.THE CONTRACTOR IS TO FIELD VERIFY ALL EXISTINGCONDITIONS PRIOR TO CONSTRUCTION AND REPORT ANYDISCREPANCIES THAT CHANGE THE SCOPE OF WORK TO THEARCHITECT/ENGINEER. (NOTE: ALL ITEMS MAY NOT BEINDICATED.)

C. DRAWINGS ARE OF SMALL SCALE, NOT ALL FITTINGS ANDOFFSETS ARE INDICATED.

D. FACILITY IS TO REMAIN OPERATIONAL DURINGCONSTRUCTION. ROOM TEMPERATURES IN CRITICAL ROOMSMUST REMAIN AT ACCEPTABLE LEVELS AT ALL TIMES. ANYSHUT DOWN OF EQUIPMENT OR INTERRUPTION OF HVACSERVICES TO NON-CRITICAL ROOMS MUST BE COORDINATEDWITH OWNER. COORDINATE WITH OWNER WHICH ROOMS ARETEMPERATURE CRITICAL.CHILLED WATER AND HEATING WATERPIPING TO BE REMOVED SHALL BE DONE WITHOUT SHUTTINGDOWN AND DRAINING RESPECTIVE SYSTEMS.

GENERAL NOTES

Keynote Legend

KeyValue Keynote Text

1 FIRE PROTECTION MAINS ROUTED OVER THISAREA TO BE MOVED TO ACCOMMODATE NEWELECTRICAL AND FUTURE UPS ROOMS.

2 EXISTING AHU TO BE REBALANCED TOADJUST FOR AIRFLOW DEDUCTED FROMUNIT.

3 HATCHED AREA INDICATES WORK ABOVECEILING TO BE DONE AS PART OF BIDPACKAGE #2. WORK ASSOCIATED WITH BIDPACKAGE #2 SHALL BE COMPLETED PRIORTO CEILING GRID INSTALLATION.

4 NEW 6" CWS/CWR PIPING TO BE INSTALLEDAS PART OF BID PACKAGE #2 TO BE ROUTEDAS HIGH AS POSSIBLE TIGHT TOSTRUCTURE. COORDINATE ALL WORK INTHIS AREA WITH BID PACKAGE #2MECHANICAL CONTRACTOR.

5 NEW ELECTRICAL CONDUITS TO BEINSTALLED AS PART OF BID PACKAGE #2 TOBE ENCLOSED IN CONCRETE DUCT BANKOVER EXISTING RESTROOMS ANDCORRIDOR. COORDINATE ALL WORK IN THEAREA WITH THE BID PACKAGE #2ELECTRICAL CONTRACTOR.

6 CAP AND VALVE FOR FUTURE COILCONNECTIONS.

7 PROVIDE WALL TYPE THERMOSTAT, MOUNTTO CEILING. PROVIDE ADDITIONAL CONTROLWIRE TO ACCOMMODATE RELOCATION OFTHERMOSTAT AS SPACES ARE FITTED OUT.

9 BUILDING IS TO REMAIN OPERATIONALDURING RENOVATION. COORDINATE WITHOTHER DISCIPLINES TO MINIMIZE THESPRINKLER SYSTEM DOWN TIME. IN THEEVENT OF AN EXTENDED SHUT DOWN OFTHE SPRINKLER SYSTEM, CONTRACTOR TONOTIFY LOCAL FIRE DEPARTMENT AND FIRECODE OFFICIAL AND PROVIDE FIRE WATCHPER NFPA STANDARDS .

10 HVAC DEMOLITION IN THIS AREA IS LIMITEDTO EXISTING AIRSIDE COMPONENTS ONLY.CAREFULLY REMOVE COMPONENTSWITHOUT DISRUPTING SERVICE TO WATERLINES ROUTED ABOVE THE CORRIDOR.

11 REMOVE AND REINSTALL EXHAUSTDUCTWORK AND GRILLES IF NECESSARY TOCOMPLETE ELECTRICAL WORK ABOVERESTROOMS AND CORRIDOR.

12 RELOCATE EXISTING HUMIDIFIER TO EASTWALL OF MECHANICAL ROOM. SEE SHEETM2.0A FOR NEW LOCATION.

13 SHUT OFF SUPPLY AND RETURN VALVES TOBRANCH AND DRAIN DOWN TO ALLOW FORREMOVAL OF HOT WATER PIPING TOTERMINAL BOXES.

14 ENSURE HYDRONIC PIPING IS REMOVEDBACK TO THE CORRIDOR. NO EXISTING ORNEW WATER PIPING IS TO BE ROUTED OVERNEW ELECTRICAL SPACES.

15 PROVIDE LOW LEAKAGE OPPOSED BLADEVOLUME DAMPER.

Page 26: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

UP

M

T

T

T

T

T

T T

T

T

T

T

SS

Unoccupied

Unoccupied12331.18 SF

CONFERENCE

012

475.22 SF

SECUREDPRINT

0201877.81 SF

MECHANICAL

009

780.43 SF

CORRIDOR

001

519.15 SF

CART STORAGE

004130.23 SF

Unoccupied

Unoccupied

148.87 SF

Unoccupied

Unoccupied139.73 SF

AREA TO BE SERVED BY EXISTING PRINT SHOP AHU

AHU-A009

OPEN OFFICE

008688.12 SF

OFFICE

014

116.69 SF OFFICE

008A138.41 SF

OFFICE

015

116.69 SF

OFFICE

011

157.65 SF

OFFICE

01893.66 SF

COLOR COPY

019

684.29 SF

SECUREDSTORAGE

021250.50 SF

RECORDSSTORAGE

007121.63 SF

40"x24" SA

44"x24" RA

36"x20" SA

30"x20" RA

20"x14" EA

18"x10" EA

20"x

20"

EA

OFFICE

010

137.81 SF

RECEPTION

006261.68 SF

10"x10" EA

24"x20" SA

18"x

12"

EA

18"x16" SA16"x

14"

SA

10"x

14"

SA

8"x8" EA 8"x8" EA

12"x

10"

EA

18"x

10"

EA

8"x8" EA 8"x8" EA

14"x

14"

SA10"x14" SA

20"x

14"

SA

8"ø SA

12"x8" SA

10"x8" SA

14"x10" SA

8"x8" SA

8"x8" SA

6"ø SA

10"x10" EA

10"x10" EA

16"x16" SA

14"ø SA

10"x10" SA

10"x

14"

SA

16"x14" SA

10"x

14"

SA

16"ø SA

16"ø SA

16"ø SA

10"x14" SA 16"x14" SA 18"x16" SA

6" ø145 CFM

D-1

TYP 4

6" ø40 CFM

D-1

12" ø340 CFM

D-1

TYP 16

12" ø260 CFM

D-1

TYP 2

12" ø400 CFM

D-1

TYP 8

6" ø120 CFM

D-1

6" ø120 CFM

D-1

6" ø120 CFM

D-1

6" ø140 CFM

D-1

6" ø120 CFM

D-16" ø

120 CFM

D-1

8" ø200 CFM

D-1

6" ø50 CFM

D-1

TYP 2

6" ø95 CFM

D-1

6" ø140 CFM

D-1

6" ø160 CFM

D-1

G-124" x 24"6" ø

150 CFM

D-1

G-124" x 24"

G-124" x 24"

G-124" x 24"

G-124" x 24"

G-124" x 24"

G-124" x 24"

G-124" x 24"

G-124" x 24"

G-124" x 24"

G-124" x 24"

VA

V-0

03

VAV-008

VAV-014

VA

V-0

10

VA

V-0

12

VAV-016

VAV-017

VAV-019VAV-020A

VAV-020B

VAV-020C

8" ø225 CFM

D-1

TYP 2

38"x

26"

RA

38"x

26"

RA

60"x28" RA

G-224" x 24"275 CFM

TYP 4

G-224" x 24"340 CFM

G-224" x 24"375 CFM

TYP 3

30"x

14"

OA

H-A009

EXISTINGAHU-2

40"x20" RA

40"x20" RA

EF-A009

20"x

20"

EA

EXISTINGRF-2

48"x

32"

RA

H-1

30"x20" RA UPOPEN TO PLENUM

G-124" x 24"

G-124" x 24"

G-124" x 24"

G-124" x 24"

36"x30" LOUVER EXHAUSTING TOLEVEL ONE PARKING GARAGE

EXISTING EXHAUST LOUVER

EXISTING EXHAUST LOUVER

EXISTING RELIEF LOUVER

G-310" x 8"

300 CFM

10"x10" TA

10"ø SA6"ø SA 6"ø SA

16"ø SA

ELEC/DATA

00372 SF

CART STORAGE

002110 SF

10"x10" TA

10"x10" TA

10"x10" TA

10"x10" TA

10"x10" TA

10"x10" TA

TERMINATE OA DUCT IN AREA WELL.PROVIDE INSECT SCREEN OVEROPENING AND SECURITY BARS INDUCTWORK AT EXTERIOR WALL

14"x10" EA

ROUTE OUTDOOR DUCTINTO SPACE BETWEENTWIN T STUCTURALSUPPORTS. ROUTEOVER NEW ANDEXISTING RETURNDUCTWORK . MODIFYEXISTING DUCTSUPPORTS ASNECCESSARY.

G-38" x 6"

50 CFM

G-124" x 24"

2

16"x8" EA22

"x16

" R

A

VAV-001

SA-A009

10"x

10" S

A

8"x6" SA

8"x6

" S

A

10"ø SA

10"x10" EA

18"x16" SA

10"x10" TA

14"x

10"

TA

14"x

10"

RA 8"

x8"

RA

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

LEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET

BA

NORTH

Rev

isio

ns

5/8

/2017 3

:40:1

0 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

HV

AC

PLA

N, LO

WE

R L

EV

EL -

AR

EA

AM

1.0

A

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

SCALE: 1/8" = 1'-0"M1.0A

1 HVAC FLOOR PLAN - LOWER LEVEL AREA A

Keynote Legend

KeyValue Keynote Text

1 FIRE PROTECTION MAINS ROUTED OVER THISAREA TO BE MOVED TO ACCOMMODATE NEWELECTRICAL AND FUTURE UPS ROOMS.

2 EXISTING AHU TO BE REBALANCED TOADJUST FOR AIRFLOW DEDUCTED FROMUNIT.

3 HATCHED AREA INDICATES WORK ABOVECEILING TO BE DONE AS PART OF BIDPACKAGE #2. WORK ASSOCIATED WITH BIDPACKAGE #2 SHALL BE COMPLETED PRIORTO CEILING GRID INSTALLATION.

4 NEW 6" CWS/CWR PIPING TO BE INSTALLEDAS PART OF BID PACKAGE #2 TO BE ROUTEDAS HIGH AS POSSIBLE TIGHT TOSTRUCTURE. COORDINATE ALL WORK INTHIS AREA WITH BID PACKAGE #2MECHANICAL CONTRACTOR.

5 NEW ELECTRICAL CONDUITS TO BEINSTALLED AS PART OF BID PACKAGE #2 TOBE ENCLOSED IN CONCRETE DUCT BANKOVER EXISTING RESTROOMS ANDCORRIDOR. COORDINATE ALL WORK IN THEAREA WITH THE BID PACKAGE #2ELECTRICAL CONTRACTOR.

6 CAP AND VALVE FOR FUTURE COILCONNECTIONS.

7 PROVIDE WALL TYPE THERMOSTAT, MOUNTTO CEILING. PROVIDE ADDITIONAL CONTROLWIRE TO ACCOMMODATE RELOCATION OFTHERMOSTAT AS SPACES ARE FITTED OUT.

9 BUILDING IS TO REMAIN OPERATIONALDURING RENOVATION. COORDINATE WITHOTHER DISCIPLINES TO MINIMIZE THESPRINKLER SYSTEM DOWN TIME. IN THEEVENT OF AN EXTENDED SHUT DOWN OFTHE SPRINKLER SYSTEM, CONTRACTOR TONOTIFY LOCAL FIRE DEPARTMENT AND FIRECODE OFFICIAL AND PROVIDE FIRE WATCHPER NFPA STANDARDS .

10 HVAC DEMOLITION IN THIS AREA IS LIMITEDTO EXISTING AIRSIDE COMPONENTS ONLY.CAREFULLY REMOVE COMPONENTSWITHOUT DISRUPTING SERVICE TO WATERLINES ROUTED ABOVE THE CORRIDOR.

11 REMOVE AND REINSTALL EXHAUSTDUCTWORK AND GRILLES IF NECESSARY TOCOMPLETE ELECTRICAL WORK ABOVERESTROOMS AND CORRIDOR.

12 RELOCATE EXISTING HUMIDIFIER TO EASTWALL OF MECHANICAL ROOM. SEE SHEETM2.0A FOR NEW LOCATION.

13 SHUT OFF SUPPLY AND RETURN VALVES TOBRANCH AND DRAIN DOWN TO ALLOW FORREMOVAL OF HOT WATER PIPING TOTERMINAL BOXES.

14 ENSURE HYDRONIC PIPING IS REMOVEDBACK TO THE CORRIDOR. NO EXISTING ORNEW WATER PIPING IS TO BE ROUTED OVERNEW ELECTRICAL SPACES.

15 PROVIDE LOW LEAKAGE OPPOSED BLADEVOLUME DAMPER.

Page 27: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

RE

F.

FSFS

S

S

T

T

T

T T T

S

FUTURE MECHANICAL

CORRIDOR

001519.15 SF

CART STORAGE

004

130.23 SFUnoccupied

Unoccupied152.97 SF

Unoccupied

Unoccupied91.22 SF

CORRIDOR

0221572.36 SF

JAN

02620.11 SF

FUTURE

0314467.11 SF

Unoccupied

Unoccupied1259.75 SF

Unoccupied

Unoccupied423.04 SF

Unoccupied

Unoccupied334.38 SF

Unoccupied

Unoccupied312.63 SF

Unoccupied

Unoccupied

310.50 SF

Unoccupied

Unoccupied107.48 SF

Unoccupied

Unoccupied59.14 SF

Unoccupied

Unoccupied125.20 SF

Unoccupied

Unoccupied198.98 SF

Unoccupied

Unoccupied95.67 SF

AHU-A009

RECORDSSTORAGE

007121.63 SF

12"x10" RA

30"x

20"

RA

WOMEN'S

024230 SF

MEN'S

025247 SF

CART STORAGE

022A88 SF

FUTURE UPS

028267 SF

ELECTRICAL

029586 SF

CORRIDOR

041459 SF

HALL

023245 SF

RECEPTION

006261.68 SF

8" ø200 CFM

D-1

6" ø50 CFM

D-1

TYP 2

6" ø160 CFM

D-1

ELEC/DATA

00372 SF

CART STORAGE

002110 SF

30"x20" SA

20"x

16"

SA

8"ø SA

12"ø SA 14"x12" SA

10"x

10"

SA

18"x

14"

SA

12"x

10"

SA

10"x10" SA

8"x1

0" S

A

12"x8" SA12"x8" SA

8"x8

" S

A

8"x8

" S

A

8"ø SA10"x10" SA

6" ø140 CFM

D-1

TYP 6

8" ø250 CFM

D-1

TYP 2

6" ø85 CFM

D-1

TYP 3

6" ø85 CFM

D-1

TYP 3

8" ø250 CFM

D-1

TYP 2

8" ø260 CFM

D-1

TYP 2

G-124" x 24"

G-124" x 24"

G-124" x 24"

14"x

10"

EA

10"x

8" E

A

8"x8" EA

10"x8" EA

G-212" x 12"250 CFM

G-212" x 12"50 CFM

G-212" x 12"250 CFM

14"x10" EA

30"x20" SA

VAV-B032

VAV-B027

VAV-B030

VAV-B034

VAV-B035VAV-B038

G-38" x 6"

50 CFM

77 7

8"x6

" S

A

10"x

10" S

A8"

x6"

SA

8"x8

" R

A

PROVIDE NEW PRESSURE SENSOR AT THIS LOCATION

1515

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

LEGEND NOTESLEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET

BA

NORTH

Rev

isio

ns

5/8

/2017 3

:40:1

1 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

HV

AC

PLA

N, LO

WE

R L

EV

EL -

AR

EA

BM

1.0

B

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

SCALE: 1/8" = 1'-0"M1.0B

1 HVAC FLOOR PLAN - LOWER LEVEL AREA B

Page 28: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

T

T

T

T

T

T T

T

T

T

T

6

7

5

4

3

2

1

HA B C D E F G

8

9

10

AHU-A009

SECUREDSTORAGE

021250.50 SF

SECUREDPRINT

0201877.81 SF

COLOR COPY

019684.29 SF

CONFERENCE

012

475.22 SF

CONFERENCE

012Redundant Space

OFFICE

011157.65 SF

OPEN OFFICE

008

688.12 SF

MECHANICAL

009780.43 SF

RECEPTION

006261.68 SF

RECORDSSTORAGE

007121.63 SF

CART STORAGE

004130.23 SF

OFFICE

008A138.41 SF

OFFICE

014116.69 SF

OFFICE

015116.69 SF

SCHED.

01767.40 SF

CORRIDOR

001519.15 SF

Unoccupied

Unoccupied

144.11 SF

OFFICE

010137.81 SF

?

??

MEN'S

025247 SF

WOMEN'S

024230 SF

JAN

02620 SF

?

??

3"3" CWR3"3" CWS

2 1/2"2 1/2" HWR2 1/2"2 1/2" HWS

VAV-020C

VAV-020B

VAV-020A

VAV-019

VAV-017

VAV-016

VAV-014

VAV-008VAV-010VAV-012

EXISTINGAHU-2

H-1

H-A

009

OFFICE

018

93.66 SF

1"1" HWS1"1" HWR

1"1" HWS

1 1/4"1 1/4" HWS1 1/4"1 1/4" HWR

1 1/2"1 1/2" HWS1 1/2"1 1/2" HWR

2"2" HWS2"2" HWR

1"1" HWR

1"1" HWS

1"1" HWR

3/4"3/4" HWR3/4"3/4" HWS

1"1" HWS1"1" HWR

3/4"3/4" HWS

3/4"3/4" HWR

1"1" HWS

1"1" HWR

1 1/4"1 1/4" HWS1 1/4"1 1/4" HWR

3/4"3/4" HWR3/4"3/4" HWS

3/4"3/4" HWS3/4"3/4" HWR

1"1" HWS1"1" HWR

3/4"3/4" HWS3/4"3/4" HWR

3/4"3/4" HWR3/4"3/4" HWS

3/4"3/4" HWS

3/4"3/4" HWR

3"3" HWS

4"4" CWS

HUMIDIFIER STEAM LINEUP TO DUCT MANIFOLD

3"3"

HW

R3"

3" H

WS

4"4"

CW

R4"

4" C

WS

EXISTINGSUMP

EXISTINGRF-2

EXISTINGEF-3

EXISTINGEF-2

VAV-003

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

LEGEND NOTESLEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET

BA

NORTH

Rev

isio

ns

5/8

/2017 3

:40:1

3 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

HV

AC

PIP

ING

PLA

N, LO

WE

R L

EV

EL -

AR

EA

AM

2.0

A

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

SCALE: 1/8" = 1'-0"M2.0A

1 HVAC PIPING PLAN - LOWER LEVEL AREA A

Page 29: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

T

6

7

5

4

3

2

1

H I J K L M

8

EXISTINGFAN COIL

EXISTING CHILLEDWATER PUMPS

EXISTING CONDENSERWATER PUMPS

EXISTING CHILLERS

EXISTING HEATEXCHANGER

AIR COMPRESSOR

EXISTINGEXPANSION TANK

2"2" HWR2"2" HWS

8"8" CWS

AHU-A009

RECEPTION

006

261.68 SF

RECORDSSTORAGE

007

121.63 SF

CART STORAGE

004

130.23 SF

CORRIDOR

001

519.15 SF

Unoccupied

Unoccupied

144.11 SF

BREAK ROOM

027

448 SF

MEN'S

025

247 SF

WOMEN'S

024

230 SF

JAN

026

20 SF

?

?

?

CORRIDOR

041

459 SFELECTRICAL

029

586 SF

FUTURE UPS

028

267 SF

CORRIDOR

022

1571 SF

8"8" CWR

VAV-B027 VAV-B030

VAV-B034

VAV-B032

VAV-B035VAV-B038

3/4"3/4" HWS3/4"3/4" HWR

3/4"3/4" HWS

3/4"3/4" HWR

3/4"3/4" HWS3/4"3/4" HWR

3/4"3/4" HWS

3/4"3/4" HWR

1"1" HWS

1"1" HWR

3/4"3/4" HWR

3/4"3/4" HWS

1"1" HWS1"1" HWR

1"1" HWS

1"1" HWR

1 1/4"1 1/4" HWR1 1/4"1 1/4" HWS

8"8" CR

8"8" CS

EXISTING AIRSEPERATOR

6"6"

CW

S6"

6" C

WR

8"8"

CW

R

8"8"

CW

S

8"8" C

S

8"8" C

R

4"4" CWR4"4" CWS

3"3" HWS3"3" HWR

4"4" CWS4"4" CWR

2"2"

CW

R2"

2" C

WS

6"6" CWS

6"6" CWR

2"2" CWS

2"2" CWR

6"6" CR

6"6" CS

8"8" CS

6"6" C

R

8"8"

CW

S

8"8"

CW

R

2"2"

HW

R2"

2" H

WS

2"2" CWR2"2" CWS

2"2" CWS2"2" CWR

3"3"

HW

R3"

3" H

WS

4"4"

CW

R4"

4" C

WS

3

3 4

5

6

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

LEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET

BA

NORTH

Rev

isio

ns

5/1

1/2

017 9

:12:2

8 A

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

HV

AC

PIP

ING

PLA

N, LO

WE

R L

EV

EL -

AR

EA

BM

2.0

B

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

SCALE: 1/8" = 1'-0"M2.0B

1 HVAC PIPING PLAN - LOWER LEVEL AREA B

Keynote Legend

KeyValue Keynote Text

1 FIRE PROTECTION MAINS ROUTED OVER THISAREA TO BE MOVED TO ACCOMMODATE NEWELECTRICAL AND FUTURE UPS ROOMS.

2 EXISTING AHU TO BE REBALANCED TOADJUST FOR AIRFLOW DEDUCTED FROMUNIT.

3 HATCHED AREA INDICATES WORK ABOVECEILING TO BE DONE AS PART OF BIDPACKAGE #2. WORK ASSOCIATED WITH BIDPACKAGE #2 SHALL BE COMPLETED PRIORTO CEILING GRID INSTALLATION.

4 NEW 6" CWS/CWR PIPING TO BE INSTALLEDAS PART OF BID PACKAGE #2 TO BE ROUTEDAS HIGH AS POSSIBLE TIGHT TOSTRUCTURE. COORDINATE ALL WORK INTHIS AREA WITH BID PACKAGE #2MECHANICAL CONTRACTOR.

5 NEW ELECTRICAL CONDUITS TO BEINSTALLED AS PART OF BID PACKAGE #2 TOBE ENCLOSED IN CONCRETE DUCT BANKOVER EXISTING RESTROOMS ANDCORRIDOR. COORDINATE ALL WORK IN THEAREA WITH THE BID PACKAGE #2ELECTRICAL CONTRACTOR.

6 CAP AND VALVE FOR FUTURE COILCONNECTIONS.

7 PROVIDE WALL TYPE THERMOSTAT, MOUNTTO CEILING. PROVIDE ADDITIONAL CONTROLWIRE TO ACCOMMODATE RELOCATION OFTHERMOSTAT AS SPACES ARE FITTED OUT.

9 BUILDING IS TO REMAIN OPERATIONALDURING RENOVATION. COORDINATE WITHOTHER DISCIPLINES TO MINIMIZE THESPRINKLER SYSTEM DOWN TIME. IN THEEVENT OF AN EXTENDED SHUT DOWN OFTHE SPRINKLER SYSTEM, CONTRACTOR TONOTIFY LOCAL FIRE DEPARTMENT AND FIRECODE OFFICIAL AND PROVIDE FIRE WATCHPER NFPA STANDARDS .

10 HVAC DEMOLITION IN AREA ABOVE THECORRIDOR LIMITED TO EXISTING AIRSIDECOMPONENTS ONLY. CAREFULLY REMOVECOMPONENTS WITHOUT DISRUPTINGSERVICE TO WATER LINES ROUTED ABOVETHE CORRIDOR.

11 REMOVE AND REINSTALL EXHAUSTDUCTWORK AND GRILLES IF NECESSARY TOCOMPLETE ELECTRICAL WORK ABOVERESTROOMS AND CORRIDOR.

12 RELOCATE EXISTING HUMIDIFIER TO EASTWALL OF MECHANICAL ROOM. SEE SHEETM2.0A FOR NEW LOCATION.

13 SHUT OFF SUPPLY AND RETURN VALVES TOBRANCH AND DRAIN DOWN TO ALLOW FORREMOVAL OF HOT WATER PIPING TOTERMINAL BOXES.

14 ENSURE HYDRONIC PIPING IS REMOVEDBACK TO THE CORRIDOR. NO EXISTING ORNEW WATER PIPING IS TO BE ROUTED OVERNEW ELECTRICAL SPACES.

15 PROVIDE LOW LEAKAGE OPPOSED BLADEVOLUME DAMPER.

Page 30: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

NOTE:1) DAMPER MUST BE U.L. APPROVED & INSTALLED AS PER

MANUFACTURER U.L. RECOMMENDATIONS. UL555, UL555A & UL55C.2) PROVIDE ACCESS PANELS IN WALLS OR CHASES.

DUCT

MOUNTING ANGLE14 GA

DAMPER ACTUATOR(SMOKE & FIRE/SMOKE DAMPERS)

MOUNTING ANGLE14 GA

14 GA SLEEVE

FIRE, SMOKE, OR COMBINATIONFIRE/SMOKE DAMPER

BREAKDOWN JOINT

ALLOW FOR 1/8" EXP OF SLEEVE INSETTING ANGLES. ANGLES TO LAPSTRUCTURE A MIN. OF 1" AROUNDENTIRE OPENING.

DAMPERACCESS

WALL ORPARTITION

VD

DIFFUSER

ROUND DUCT WRAP INSULATION

CEILING

SUPPLY MAIN WRAP INSULATION

45° ENTRY TAP RECTANGULAR TOROUND

FLEX CONNECTION NO BENDS MAX.5'-0" LONG

4" MAX 4". 4". 4". 4" MAX

4" M

AX

4".

4" M

AX

SECURITY BARRIER WIDTH

SE

CU

RIT

Y B

AR

RIE

R H

EIG

HT

2"x1 1/4"x3/16" STEEL ANGLE(TOP AND BOTTOM)

3/4" ROUND STEEL BARS (TYP)

3/16"x2" FLAT BAR (BOTH SIDES)

SECURITY BARRIER ELEVATIONA

OU

TS

IDE

WA

LLIN

AR

EA

WE

LL

INS

IDE

WA

LL

2".

6".

PROVIDE 3/4"Ø x 5" EXPANSIONANCHORS IN WALL AT 16" O.C.SPACING

MIN 6"x3"x3/16" ANGLE IRON ALLAROUND SLEEVE

10 GUAGE STEEL SLEEVE (GALV)

PROVIDE 2" LONG FILLET WELD @ 12"O.C. ALONG PERIMETER OF ANGLEIRON SLEEVE

SECURELY FASTEN DUCTWORK TO SLEEVE

WALL STRUCTURE

SECURITY BARRIER @ DUCT OPENINGB

SECURITY BARS

BUILDING WALL INTERIOR

RIVET (TYP)

RECTANGULAR DUCTWORK

SEAL ALL WALL PENETRATIONS (TYP)

PIPING & INSULATION

GALV. STEEL DRAWBANDTYPE ESCUTCHEON, 3" WIDE

ROUND DUCTWORK

SATIN FINISH OR ALUMINUMSPLIT-TYPE ESCUTCHEON

SLEEVE IN MASONRY WALL (TYP)

CONCEALED DUCTWORK& PIPING

EXPOSED DUCTWORK& PIPING IN FINSHED SPACES

HANGER CLAMP OR BAND

BOLT

STRAP OR ANGLE

NUT

ANGLE

ROD

DUCT

NOTES:1. DO NOT EXCEED ALLOWABLE LOAD LIMITS OF ANY OR ALL OF THE INDIVIDUAL TRAPEZE PARTS.2. DO NOT PENETRATE DUCT OR DUCT INSULATION VAPOR BARRIER WHEN SECURING HANGERS TO

DUCTWORK. EVENTUALLY THE PENETRATIONS WILL LEAK.3. USE HANGER CLAMPS OR BANDS FOR ROUND DUCTS AS ROUND DUCT TENDS TO DEFORM ON TRAPEZE

HANGERS.4. TEARS, PUNCTURES, ETC. SHALL BE REPAIRED WITH TAPE OR MASTIC TO MAINAIN THE INTEGRITY OF

THE VAPOR BARRIER.5. DO NOT USE ANY STRAP HANGERS WITH SCREWS ON ANY DUCTWORK THAT IS EXTERNALY WRAPPED.

SUPPORT RODS DOWN FROMSTRUCTURE (TYP OF 4)

VIBRATION ISOLATORS, SEESPECIFICATIONS

NEOPRENE VIBRATION ISOLATORS(TYP OF 4)

FLEXIBLE DUCT CONNECITON (TYP)

IN-LINE EXHAUST FAN

REFER TO PLANS FOR CONTINUATIONOF DUCTWORK AND SIZES

M

RELIEF AIR LOUVER - REFER TOMECHANICAL DRAWINGS FORLOCATION AND ARCHITECTURALDRAWINGS FOR SPECIFICATIONS ANDSIZES AND INSTALLATION

BACKDRAFT DAMPER WHEREINDICATED ON PLANS

CONNECT DUCTWORK FULL SIZE TOLOUVER CONNECTION

RELIEF DUCT CONNECTIONS, SEEPLANS FOR SIZE AND LOCATION

FULL SIZE PLENUM FOR BRANCHDUCT CONNECTIONS

EXTERIOR WALL

1" ACCOUSTICAL DUCT LINER

WALL

1" ACCOUSTICAL DUCT LINER

W W * 1.5

HWS

HWR

5/8"Ø SUPPORT RODS DOWN FROMSTRUCTURE (TYP OF 4). REFER TOSTRUCTURAL DRAWINGS FORCONNECTION DETAILS

PRIMARY AIR DUCT FROM RTAC UNIT

SHEET METAL DUCT (TYP)

2 POSITION CONTROL VALVE

AIRFLOW

FLEXIBLE BRAIDED STAINLESS STEELHOSE KIT

VAV TERMINAL UNIT

X"

Y"

INSTALL ADDITIONAL VENT ATINTERVALS OF 10' WHEN PIPINGDOWNSTREAM OF TRAP EXCEEDS15'

FLOOR DRAIN

CLEAN OUT

1" AIR GAP

PITCH DOWN TOWARD DRAIN

OPEN END

CLEAN OUT

DRAIN LINE SHALL BE AT LEAST THESAME SIZE AS THE NIPPLE ON THEDRAIN PAN

EQUIP MUST BE MOUNTED HIGHENOUGH VIA HOUSEKEEPING PADAND/OR EQUIPMENT RAILS TO ENSUREX AND Y DIMENSIONS

NOTES:1. ON DRAW-THRU UNITS, THE (X) DIMENSION (IN INCHES) SHALL BE 1.5 TIMES THE AIR HANDLING-UNITS

SUCTION PRESSURE AT OPERATING CONDITIONS, BUT IN NO CASE LESS THAN 2-INCHES.2. ON BLOW-THRU UNITS, THE (X) DIMENSION (IN INCHES) CAN BE AS SMALL AS 2 INCHES, BUT THE (Y)

DIMENSION (IN INCHES) SHALL BE 1.5 TIMES THE AIR HANDLING UNITS TOTAL STATIC PRESSURE BUTIN NO CASE LESS THAN 2 INCHES.

X=DISTANCE BETWEEN THE DRAIN PAN OUTLET AND THE TRAPY=TRAP DEPTH

3/4" BALL VALVE W/HOSE END THREADCONNECTION

THREAD PIPE CAP DO NOT SEAL WELD

LOW POINT

WELDOLET

SOCKET WELD

PITCH DOWNTO DRAIN

HVAC PIPING LOW POINT DRAINA

3/4" LEAD FREE BALL VALVE W/HOSEEND THREAD CONNECTION CAP ANDCHAIN

LOW POINT

PITCH DOWNTO DRAIN

PLUMBING PIPING LOW POINT DRAINB

PROVIDE A SECTION OF HIGHCOMPRESSION STRENGTHINSULATION AT EACH HANGER POINT.INSULATION MAY BE HALF ROUND ORFULL ROUND AND EXTENDED 2"BEYOND GALVANIZED SHIELD EACHWAY.

HANGER ROD WITH CLEVIS HANGER

PIPE

UNI-STRUT CHANNEL

GALV. IRON SHEET SHIELD (12" LONG)

INSULATION

PIPE

NOTES:

1. ATTACH SUPPORTS FOR ALL PIPING SUSPENDED FROM THE STEELSTRUCTURE TO THE TOP CHORD OF JOISTS OR BEAM.

2. PROVIDE COPPER OR PLASTIC COATED HANDERS FOR NON-INSULATED COPPER PIPE.

HWS

HWS

HWRHWR

X'-X" MINIMUM ACOUSTICALLYLINED DUCT

HOT WATER COIL

AIR INLET DUCT

VARIABLE AIR VOLUME BOX

CONTROL VALVE

SHUT-OFF VALVE (TYP)

P/T PORT

UNION (TYP)

INSULATE OVER COIL AND COILHEADER TO PREVENTCONDENSATION WHEN IN COOLINGMODE

MANUAL AIR VENT

STRAINER

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

Rev

isio

ns

5/8

/2017 3

:40:1

8 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

ME

CH

AN

ICA

L D

ET

AIL

SM

4.1

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NO SCALEM4.1

1 COMBO FIRE/SMOKE DAMPERNO SCALEM4.1

2 DIFF DUCT CONN HORIZ FLEXNO SCALEM4.1

3 DUCT SECURITY BARRIERNO SCALEM4.1

4 DUCT/PIPE WALL PENETRATIONS

NO SCALEM4.1

5 DUCTWORK HANGING DETAILNO SCALEM4.1

6 EXHAUST FAN - IN-LINENO SCALEM4.1

7 LOUVER CONN - RELIEF

NO SCALEM4.1

9 TRANSFER DUCT 2

NO SCALEM4.1

10 VAV BOX - SEISMICNO SCALEM4.1

11 CONDENSATE DRAIN P-TRAP

NO SCALEM4.1

12 LOW POINT DRAIN

NO SCALEM4.1

13 PIPE INSULATION AT HANGERS

NO SCALEM4.1

14 VAV REHEAT PIPING

Page 31: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

TERMINAL BOX - HOT WATER REHEAT

CFM OPERATING MAX RADIATED MAX DISCHARGE HOT WATER REHEAT COIL DATA MECH

MARK TYPE MAX MINSTATIC PRESSURE

INLET DIA NC AT NC AT CFM MIN CAP GPM WPD APD ROWS EWT LWT EAT LAT BASIS OF DESIGN

NOTES

(TB-X) (IN WG) (IN) INLET STATIC INLET STATIC (MBH) (FT WG) (IN WG) (°F) (°F) (°F) (°F)

VAV-001 REHEAT 310 145 0.75 8 25 25 145 5.5 1 0.7 0.1 1 200 189.038 55 90 TITUS DESV 1,2

VAV-003 REHEAT 300 80 0.75 6 25 25 80 3.0 1 0.5 0.1 1 200 193.952 55 90 TITUS DESV 1,2

VAV-008 REHEAT 675 230 0.75 10 25 25 230 8.7 2 0.7 0.1 1 200 191.306 55 90 TITUS DESV 1,2

VAV-010 REHEAT 240 80 0.75 6 25 25 80 3.0 1 0.5 0.1 1 200 193.952 55 90 TITUS DESV 1,2

VAV-012 REHEAT 250 80 0.75 6 25 25 80 3.0 1 0.5 0.1 1 200 193.952 55 90 TITUS DESV 1,2

VAV-014 REHEAT 240 80 0.75 6 25 25 80 3.0 1 0.5 0.1 1 200 193.952 55 90 TITUS DESV 1,2

VAV-016 REHEAT 1,600 450 0.75 14 25 25 450 17.0 2 0.5 0.1 1 200 182.99 55 90 TITUS DESV 1,2

VAV-017 REHEAT 1,870 580 0.75 16 25 25 580 21.9 2 1 0.1 1 200 178.076 55 90 TITUS DESV 1,2

VAV-019 REHEAT 450 145 0.75 8 25 25 145 5.5 1 0.7 0.1 1 200 189.038 55 90 TITUS DESV 1,2

VAV-020A REHEAT 2,000 580 0.75 16 25 25 580 21.9 3 1 0.1 1 200 185.384 55 90 TITUS DESV 1,2

VAV-020B REHEAT 2,000 580 0.75 16 25 25 580 21.9 3 1 0.1 1 200 185.384 55 90 TITUS DESV 1,2

VAV-020C REHEAT 2,000 580 0.75 16 25 25 580 21.9 3 1 0.1 1 200 185.384 55 90 TITUS DESV 1,3

VAV-027 REHEAT 520 145 0.75 8 25 25 145 5.5 1 0.7 0.1 1 200 189.038 55 90 TITUS DESV 1,2

VAV-030 REHEAT 915 325 0.75 12 25 25 325 12.3 2 0.9 0.1 1 200 187.715 55 90 TITUS DESV 1,2

VAV-032 REHEAT 500 145 0.75 8 25 25 145 5.5 1 0.7 0.1 1 200 189.038 55 90 TITUS DESV 1,2

VAV-034 REHEAT 500 145 0.75 8 25 25 145 5.5 1 0.7 0.1 1 200 189.038 55 90 TITUS DESV 1,2

VAV-035 REHEAT 255 80 0.75 6 25 25 80 3.0 1 0.5 0.1 1 200 193.952 55 90 TITUS DESV 1,2

VAV-038 REHEAT 255 80 0.75 6 25 25 80 3.0 1 0.5 0.1 1 200 193.952 55 90 TITUS DESV 1,2

MECHANICAL NOTES:

1. ROOM NC LEVEL SHOWN INCLUDES ATTENUATION TRANSFER FUNCTIONS OBTAINED FROM TABLES IN ARI STANDARD 885-90.

2. SOUND DATA SHALL BE OBTAINED FROM TESTS CONDUCTED IN ACCORDANCE WITH ARI STANDARD 880-94.

MODULAR AIR HANDLING UNIT SCHEDULE

MARK

AHU-A009

MECHANICAL NOTES:

1. PROVIDE CLASS 2 SUPPLY & RETURN FANS.

2. SEE PLANS & SECTIONS FOR AHU SIZE & CONFIGURATION.

3. PROVIDE DOUBLE SLOPED STAINLESS STEEL DRAIN PANS FOR COOLING COIL SECTIONS.

4. ALL VARIABLE FREQUENCY DRIVES SHALL BE UNIT MOUNTED AND WIRED AT THE FACTORY.

5. PROVIDE 1 EXTRA SET OF PRE AND FINAL FILTERS.

6. UNIT WILL NOT HAVE CONCRETE EQUIPMENT PAD.MANUFACTURER AND CONTRACTOR TO COORDINATE CONDENSATE OUTLET/PIPING PRIOR TO ORDERING UNIT.

7. PROVIDE SINGLE POINT POWER CONNECTION - 460 V / 3 PH / 29 A FLA / 30 A MCA.

8. UNIT SHALL BREAK DOWN TO FIT IN BUILDING FREIGHT ELEVATOR.

LOCATION

A009

FAN

SECTION

SUPPLY

RETURN

FAN WALL SECTION DATA

WHEEL

TYPE

CENTRIFUGAL

CENTRIFUGAL

NUMBER

OF FANS

4

2

WHEEL

DIA

(IN)14

22

BLADE

TYPE

AIRFOIL

AIRFOIL

TOTAL

MAX

CFM13,000

10,300

ESP

(IN WG)2.50

1.00

Kw/

Fan3.7

3.4

V

460

460

PH

3

3

VFD

YES

YES

SUPPLY/RETURN

DISCHARGE PLENUM

YES

YES

BLENDER

NO

ECONOMIZER

SECTION

NO

FILTER

PRE/FINAL

2" MERV 8 PRE

4" MERV 11 FINAL

HEATING

COIL MARK

HC-A009

COOLING

COIL MARK

CC-A009

MIN

OA

CFM

2,700

UNIT

WEIGHT

9,869

BASIS OF DESIGN

TEMPTROL

MECH

NOTES

1,2,3,4,5,6,7,8

COIL - CHILLED WATER SCHEDULE

MARK

CC-A009

MECHANICAL NOTES:

1. MAX FACE VELOCITY AND AIR PRESSURE DROP IS FOR MAXIMUM CFM. SEE AIR HANDLING UNIT SCHEDULE.

2. ALL OTHER INFORMATION IS FOR MINIMUM CFM AS LISTED ON THIS SCHEDULE.

SERVES

AHU-A009

CFM

13,000

NUMBER

COILS

2

MAX

FACE

VEL

(FPM)500

MAX

AIR

PD

(IN)0.80

TOTAL

CAP

COIL

(MBH)470

SENSIBLE

CAP

COIL

(MBH)350

EAT

(°F)78.0

LAT

(°F)52.5

GPM

93.8

MAX

WATER

PD

(FT)6.2

EWT

(°F)45

LWT

(°F)55

MIN

NO

ROWS

6

MAX

FINS PER

INCH

10

BASIS OFDESIGN

DAIKIN

MECH

NOTES

1,2

COIL - HOT WATER SCHEDULE

MARK

HC-A009

MECHANICAL NOTES:

1. MAX FACE VELOCITY AND AIR PRESSURE DROP IS FOR MAXIMUM CFM. SEE AIR HANDLING UNIT SCHEDULE.

2. ALL OTHER INFORMATION IS FOR MINIMUM CFM AS LISTED ON THIS SCHEDULE.

SERVES

AHU-A009

CFM

13,000

NUMBER

COILS

1

MAX

FACE

VEL

(FPM)500

MAX

AIR

PD

(IN)0.10

TOTAL

CAP

COIL

(MBH)522

EAT

(°F)59.2

LAT

(°F)89.1

GPM

54.0

MAX

WATER

PD

(FT)3.4

EWT

(°F)200

LWT

(°F)180

MIN

NO

ROWS

1

MAX

FINS PER

INCH

10

BASIS OF DESIGN

DAIKIN

MECH

NOTES

1,2

LOUVER SCHEDULE

MARK

(LV-X)

LV-2

MECHANICAL NOTES:

1. PROVIDE WITH BIRDSCREEN.

2. PROVIDE MOUNTING ACCESSORIES AND EXTENDED SILL MOUNTING.

3. PROVIDE RUSKIN FLUROPON FINISH. COLOR TO BE SELECTED BY A/E.

4. PROVIDE WITH THERMALLY INSULATED, LOW LEAKAGE RUSKIN CDTI-50 DAMPER OR APPROVED EQUAL.

SERVES

EF-A009

FUNCTION

EXHAUST AIR

CFM

3,000

TOTAL LOUVER

FREE AREA

(SQ. FT.)

9.26

FREE AREA

VELOCITY

(FPM)

700

MAX PD

(IN WG)

0.1

W

(IN)

30

SIZE

H

(IN)

30

D

(IN)

4

BASIS OF DESIGN

RUSKIN ELF375DXD

MECH

NOTES

1,2,3,4

DIFFUSER, REGISTER & GRILLE SCHEDULE

MARK

D-1

D-2

D-3

G-1

G-2

GENERAL NOTES:

1. NC VALUES ARE BASED ON A ROOM ABSORPTION OF 10 db, re 10-12 WATTS.

2. SEE PLANS FOR NECK SIZE AND CFM.

MECHANICAL NOTES:

1. PROVIDE WITH OPPOSED BLADE BALANCING DAMPER.

2. PROVIDE WITH FLANGED BORDER.

3. SET VERTICAL DEFLECTION TO 22.5 DEG DOWN UNLESS OTHERWISE NOTED ON THE DRAWINGS.

SERVES

SUPPLY AIR

SUPPLY AIR

SUPPLY AIR

RETURN/EXHAUST/TRANSFER AIR

RETURN/EXHAUST/TRANSFER AIR

FRAME TYPE

LAY-IN

LAY-IN

DUCT MOUNTED

LAY-IN

SURFACE

MATERIAL

STEEL

STEEL

STEEL

ALUMINUM

ALUMINUM

FACE SIZE

(INCHES)

24 x 24

12x12

SEE PLANS

SEE PLANS

SEE PLANS

PANEL SIZE

(INCHES)

24 X 24

12x12

- - - - -

- - - - -

- - - - -

NECK SIZE

(INCHES)

SEE PLANS

SEE PLANS

SEE PLANS

SEE PLANS

SEE PLANS

FINISH

WHITE

WHITE

BRITISH-WHITE

BRITISH-WHITE

BRITISH-WHITE

MAX

TOT PD

(IN WG)

0.1

0.1

0.1

0.08

0.08

MAX NC

@ Pd SHOWN

30

30

30

30

30

MANUFACTURER

& MODEL NUMBER

NAILOR RNSA

NAILOR RNSA

TITUS 300RL

TITUS 50F

TITUS 50F

MECH

NOTES

3

2

FAN SCHEDULE

MARK

EF-A009

MECHANICAL NOTES:

1. FAN SELECTION WITH THE FOLLOWING PARAMETER: NOT ALLOWED TO OPERATE IN MOTOR SAFETY FACTOR.

2. PROVIDE WITH SOLID STATE SPEED CONTROLLER FOR FAN BALANCING, SHIPPED LOOSE FOR FIELD WIRING BY ELECTRICAL CONTRACTOR.

3. PROVIDE WITH FACTORY MOUNTED DISCONNECT SWITCH AND NEMA-4X ENCLOSURE.

LOCATION

PRINT SHOP

FAN

TYPE

INLINE

WHEEL

DIA

(IN)

BLADE

TYPE

BI

FAN DATA

CFM

3000

ESP

(IN WG)

0.5

FAN

RPM

1099

DRIVE

TYPE

BELT

HP

[WATTS]

3/4

ELECTRICAL DATA

V

115

PH

1

HZ

60

MAX

SONES

12

UNIT

WEIGHT

(LBS)

11

BASIS OF DESIGN

COOK 165SQNB

MECH

NOTES

1,2,3

SOUND ATTENUATOR SCHEDULE

MARK

SA-A009

MECHANICAL NOTES:

1. VELOCITY SHOWN IS +(FORWARD FLOW) OR -(REVERSE FLOW) AS DEFINED BY ASTM E477-13.

2. PRESSURE DROP, DYNAMIC INSERTION LOSS AND SELF GENERATED NOISE PER ASTM E477-13.

3. MAXIMUM PRESSURE DROP WITH SYSTEM EFFECTS = SILENCER PRESSURE DROP PER ASTM E477-13 + SYSTEM EFFECTS FOR NEARBY DUCT ELEMENTS.

4. TYPE - RECTANGULAR DISSAPATIVE.

SERVES

EF-A009

FUNCTION

SUPPLY AIR

CFM

13,000

FREE AREA

VELOCITY

(FPM)

1950

MAX PD

(IN WG)

0.22

W

(IN)

40

SIZE

H

(IN)

24

D

(IN)

36

BASIS OF DESIGN

VIBRO-ACOUSTICS RD-HV-F6-L20313

MECH

NOTES

1,2,3,4

63

3

125

4

250

7

500

13

1000

18

2000

14

4000

10

8000

6

MINIMUM DYNAMIC INSERTION LOSS, Db

OCTAVE BAND CENTER FREQUENCY, HZ

LOUVER SCHEDULE

MARK

(LV-X)

H-A009

SERVES

AHU-A009

TYPE

STEAM

CFM

13,000

STEAMCAPACITY

(LBS/HR)

91.2

HEATERQUANTITY

6

STAGES

2

kW

32

ELECTRICAL DATA

V

480

PH

3

BASIS OF DESIGN

DRISTEEM VAPORSTREAM 32-2

MECH

NOTES

--

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

Rev

isio

ns

5/8

/2017 3

:40:1

9 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

ME

CH

AN

ICA

L S

CH

ED

ULE

SM

5.1

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

Page 32: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

6

7

5

4

3

2

1

HA B C D E F G

8

9

10

REMOVE FLOOR DRAINS AND CAP.

2"2" W 2"2" W 2"2" W

2"2" W

4"4" W

4"4" W

2"2" W2"2" W

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

LEGEND NOTES

BA

NORTH

Rev

isio

ns

5/8

/2017 3

:39:5

5 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

UN

DE

RG

RO

UN

D P

LU

MB

ING

DE

MO

LIT

ION

PLA

N -

AR

EA

AD

P0.1

A

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

UNDERGROUND PLUMBING DEMOLITION PLAN - AREA A

GENERAL NOTES

A. MECHANICAL ITEMS INDICATED FULL TONE (DARK) AREITEMS TO BE SALVAGED FOR RE-USE OR DEMOLISHED.MECHANICAL ITEMS INDICATED HALF TONE (LIGHT) AREEXISTING ITEMS TO REMAIN. CONTRACTOR TO PROPERLYDISPOSE OF MATERIAL NOT RE-USED.

B. EXISTING MECHANICAL ITEMS HAVE BEEN INDICATEDFROM THE EXISTING PLANS AND VERIFIED TO THEEXTENT POSSIBLE. THE CONTRACTOR IS TO FIELDVERIFY ALL EXISTING CONDITIONS PRIOR TOCONSTRUCTION AND REPORT ANY DISCREPANCIES THATCHANGE THE SCOPE OF WORK TO THEARCHITECT/ENGINEER. (NOTE: ALL ITEMS MAY NOT BEINDICATED.)

C. DRAWINGS ARE OF SMALL SCALE, NOT ALL FITTINGSAND OFFSETS ARE INDICATED.

D. FACILITY IS TO REMAIN OPERATIONAL DURINGCONSTRUCTION. ROOM TEMPERATURES IN CRITICALROOMS MUST REMAIN AT ACCEPTABLE LEVELS AT ALLTIMES. ANY SHUT DOWN OF EQUIPMENT ORINTERRUPTION OF HVAC SERVICES TO NON-CRITICALROOMS MUST BE COORDINATED WITH OWNER.COORDINATE WITH OWNER WHICH ROOMS ARETEMPERATURE CRITICAL. CHILLED WATER AND HEATINGWATER PIPING TO BE REMOVED SHALL BE DONE WITHOUTSHUTTING DOWN AND DRAINING RESPECTIVE SYSTEMS.

Page 33: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

6

7

5

4

3

2

1

H I J K L M

8

REMOVE FLOOR DRAINS AND CAP AT FLOOR

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

LEGEND NOTES

BA

NORTH

Rev

isio

ns

5/8

/2017 3

:39:5

7 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

UN

DE

RG

RO

UN

D P

LU

MB

ING

DE

MO

LIT

ION

PLA

N -

AR

EA

BD

P0.1

B

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

UNDERGROUND PLUMBING DEMOLITION PLAN - AREA B

GENERAL NOTES

A. MECHANICAL ITEMS INDICATED FULL TONE (DARK) AREITEMS TO BE SALVAGED FOR RE-USE OR DEMOLISHED.MECHANICAL ITEMS INDICATED HALF TONE (LIGHT) AREEXISTING ITEMS TO REMAIN. CONTRACTOR TO PROPERLYDISPOSE OF MATERIAL NOT RE-USED.

B. EXISTING MECHANICAL ITEMS HAVE BEEN INDICATEDFROM THE EXISTING PLANS AND VERIFIED TO THEEXTENT POSSIBLE. THE CONTRACTOR IS TO FIELDVERIFY ALL EXISTING CONDITIONS PRIOR TOCONSTRUCTION AND REPORT ANY DISCREPANCIES THATCHANGE THE SCOPE OF WORK TO THEARCHITECT/ENGINEER. (NOTE: ALL ITEMS MAY NOT BEINDICATED.)

C. DRAWINGS ARE OF SMALL SCALE, NOT ALL FITTINGSAND OFFSETS ARE INDICATED.

D. FACILITY IS TO REMAIN OPERATIONAL DURINGCONSTRUCTION. ROOM TEMPERATURES IN CRITICALROOMS MUST REMAIN AT ACCEPTABLE LEVELS AT ALLTIMES. ANY SHUT DOWN OF EQUIPMENT ORINTERRUPTION OF HVAC SERVICES TO NON-CRITICALROOMS MUST BE COORDINATED WITH OWNER.COORDINATE WITH OWNER WHICH ROOMS ARETEMPERATURE CRITICAL. CHILLED WATER AND HEATINGWATER PIPING TO BE REMOVED SHALL BE DONE WITHOUTSHUTTING DOWN AND DRAINING RESPECTIVE SYSTEMS.

Page 34: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

6

7

5

4

3

2

1

HA B C D E F G

8

9

10

REMOVE FLOOR DRAINS AND CAP.

EXISTINGH-1

EXISTINGAHU-2

EXISTINGCRAC

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

LEGEND NOTES

BA

NORTH

Rev

isio

ns

5/8

/2017 3

:39:5

8 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

PLU

MB

ING

DE

MO

LIT

ION

PLA

N, LO

WE

R L

EV

EL A

RE

A A

DP

1.0

A

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

PLUMBING DEMOLITION PLAN, LOWER LEVEL - AREA A

GENERAL NOTES

A. MECHANICAL ITEMS INDICATED FULL TONE (DARK) AREITEMS TO BE SALVAGED FOR RE-USE OR DEMOLISHED.MECHANICAL ITEMS INDICATED HALF TONE (LIGHT) AREEXISTING ITEMS TO REMAIN. CONTRACTOR TO PROPERLYDISPOSE OF MATERIAL NOT RE-USED.

B. EXISTING MECHANICAL ITEMS HAVE BEEN INDICATEDFROM THE EXISTING PLANS AND VERIFIED TO THEEXTENT POSSIBLE. THE CONTRACTOR IS TO FIELDVERIFY ALL EXISTING CONDITIONS PRIOR TOCONSTRUCTION AND REPORT ANY DISCREPANCIES THATCHANGE THE SCOPE OF WORK TO THEARCHITECT/ENGINEER. (NOTE: ALL ITEMS MAY NOT BEINDICATED.)

C. DRAWINGS ARE OF SMALL SCALE, NOT ALL FITTINGSAND OFFSETS ARE INDICATED.

D. FACILITY IS TO REMAIN OPERATIONAL DURINGCONSTRUCTION. ROOM TEMPERATURES IN CRITICALROOMS MUST REMAIN AT ACCEPTABLE LEVELS AT ALLTIMES. ANY SHUT DOWN OF EQUIPMENT ORINTERRUPTION OF HVAC SERVICES TO NON-CRITICALROOMS MUST BE COORDINATED WITH OWNER.COORDINATE WITH OWNER WHICH ROOMS ARETEMPERATURE CRITICAL. CHILLED WATER AND HEATINGWATER PIPING TO BE REMOVED SHALL BE DONE WITHOUTSHUTTING DOWN AND DRAINING RESPECTIVE SYSTEMS.

Page 35: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

6

7

5

4

3

2

1

H I J K L M

8

REMOVE FLOOR DRAINS AND CAP AT FLOOR

REMOVE VENT PIPING AND WASTE PIPE AND CAP AT FLOOR

REMOVE ALL PLUMBING FIXTURES INEXISTING BATHROOM. REMOVE VENTPIPING AND CAP WASTE LINES AT FLOOR

1"1" CW

1"1" CW 1"1" CW

EXISTINGWH-1

REMOVE WASTELINE SERVING FDON LEVEL ONE

REMOVE CW TOTHIS LOCATION.CAP AND VALVE.

REMOVE CW TOTHIS LOCATION.CAP AND VALVE.

REMOVE DOMESTICWATER LINES SERVINGEXISTING RESTROOMS

EXISTING WATERHEATER TO REMAIN

REMOVE ALL DOMESTIC WATERPIPING ABOVE CEILING. REMOVEEXISTING WATER HEATER.

COORDINATE EXISTING DOMESTIC WATER,WASTE AND VENT PIPE ABOVE RESTROOMSWITH NEW ELECTRICAL DUCT BACK. RE-ROUTEPIPING WHEN NECESSARY.

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

LEGEND NOTES

BA

NORTH

Rev

isio

ns

5/8

/2017 3

:40:0

0 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

PLU

MB

ING

DE

MO

LIT

ION

PLA

N, LO

WE

R L

EV

EL A

RE

A B

DP

1.0

B

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

PLUMBING DEMOLITION PLAN, LOWER LEVEL - AREA B

GENERAL NOTES

A. MECHANICAL ITEMS INDICATED FULL TONE (DARK) AREITEMS TO BE SALVAGED FOR RE-USE OR DEMOLISHED.MECHANICAL ITEMS INDICATED HALF TONE (LIGHT) AREEXISTING ITEMS TO REMAIN. CONTRACTOR TO PROPERLYDISPOSE OF MATERIAL NOT RE-USED.

B. EXISTING MECHANICAL ITEMS HAVE BEEN INDICATEDFROM THE EXISTING PLANS AND VERIFIED TO THEEXTENT POSSIBLE. THE CONTRACTOR IS TO FIELDVERIFY ALL EXISTING CONDITIONS PRIOR TOCONSTRUCTION AND REPORT ANY DISCREPANCIES THATCHANGE THE SCOPE OF WORK TO THEARCHITECT/ENGINEER. (NOTE: ALL ITEMS MAY NOT BEINDICATED.)

C. DRAWINGS ARE OF SMALL SCALE, NOT ALL FITTINGSAND OFFSETS ARE INDICATED.

D. FACILITY IS TO REMAIN OPERATIONAL DURINGCONSTRUCTION. ROOM TEMPERATURES IN CRITICALROOMS MUST REMAIN AT ACCEPTABLE LEVELS AT ALLTIMES. ANY SHUT DOWN OF EQUIPMENT ORINTERRUPTION OF HVAC SERVICES TO NON-CRITICALROOMS MUST BE COORDINATED WITH OWNER.COORDINATE WITH OWNER WHICH ROOMS ARETEMPERATURE CRITICAL. CHILLED WATER AND HEATINGWATER PIPING TO BE REMOVED SHALL BE DONE WITHOUTSHUTTING DOWN AND DRAINING RESPECTIVE SYSTEMS.

Page 36: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

6

7

5

4

3

2

1

HA B C D E F G

8

9

10

RECORDSSTORAGE

007

122 SF

CART STORAGE

004130 SF

CORRIDOR

001519 SF

MECHANICAL

009780 SF

RECEPTION

006262 SF

OFFICE

010

138 SF

CONFERENCE

012475 SF

FILES

008C59 SF

PRE-PRESS/DIGITALGRAPHICS

0161998 SF

OPEN OFFICE

008688 SF

SECUREDPRINT

0201878 SF

COLOR COPY

019684 SF

SECUREDSTORAGE

021251 SF

OFFICE

014117 SF

OFFICE

008A138 SF

SCHED.

017

67 SF

OFFICE

011

158 SF

2"2" W 2"2" W

4"4" W

4"4" W

2"2" W2"2" W

2"2" W

2"2" W

2"2" W

4"4" W

OFFICE

015117 SF

OFFICE

01894 SF

CART STORAGE

002110 SF

ELEC/DATA

00372 SF

S-3

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

LEGEND NOTES

BA

NORTH

Rev

isio

ns

5/8

/2017 3

:40:2

2 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

UN

DE

RG

RO

UN

D P

LU

MB

ING

PLA

N, LO

WE

R L

EV

EL A

RE

A A

P0.1

A

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

UNDERGROUND PLUMBING PLAN - AREA A

Page 37: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

6

7

5

4

3

2

1

H I J K L M

8

RECORDSSTORAGE

007122 SF

CART STORAGE

004130 SF

CORRIDOR

001519 SF

HALL

023245 SF

BREAK ROOM

027

448 SF

FUTURE UPS

028267 SF

ELECTRICAL

029586 SF

CORRIDOR

041459 SF

CORRIDOR

0221572 SF

RECEPTION

006

262 SF

CART STORAGE

002110 SF

ELEC/DATA

00372 SF

4"4" W

2"2" W

2"2" W

2"2" W4"4"

W4"4"

W4"4"

W

2"2" W

4"4" W

2"2" W

4"4" W4"4" W

4"4" W

2"2" W

2"2" W

2"2" W

FD-2

FD-2

WC-1

WC-1

S-1

L-1

L-1

L-1

L-1

L-1

L-1

WC-1

WC-1

WC-1

WC-1

WC-1

WC-1

WC-1

WC-1

WC-1

UR-1

UR-1

MS-1

WOMEN'S

024230 SF

MEN'S

025247 SF

FUTURE

0314467 SF

2"2" W

2"2" W

2"2" W

4"4" W

4"4" W

4"4" W

4"4" W

2"2" W

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

LEGEND NOTES

BA

NORTH

Rev

isio

ns

5/8

/2017 3

:40:2

4 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

UN

DE

RG

RO

UN

D P

LU

MB

ING

PLA

N, LO

WE

R L

EV

EL A

RE

A B

P0.1

B

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

UNDERGROUND PLUMBING PLAN - AREA B

Page 38: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

6

7

5

4

3

2

1

HA B C D E F G

8

9

10

RECORDSSTORAGE

007122 SF

CART STORAGE

004130 SF

CORRIDOR

001

519 SF

MECHANICAL

009780 SF

RECEPTION

006

262 SF

OFFICE

010138 SF

CONFERENCE

012475 SF

?

?

?

FILES

008C59 SF

PRE-PRESS/DIGITALGRAPHICS

016

1998 SF

OPEN OFFICE

008

688 SF

SECUREDPRINT

0201878 SF

COLOR COPY

019684 SF

SECUREDSTORAGE

021251 SF

OFFICE

014117 SF

OFFICE

008A

138 SF

SCHED.

01767 SF

OFFICE

011158 SF

OFFICE

015117 SF

OFFICE

01894 SF

CART STORAGE

002110 SF

ELEC/DATA

00372 SF

S-2

2"2" V

2"2" V

2"2" V

FD-1

3/4"3/4" 110-HW

3/4"3/4" CW

3/4"3/4" CW

1/2"

1/2"

CW

6"6" W2"2" V

1"1" W

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

LEGEND NOTES

BA

NORTH

Rev

isio

ns

5/8

/2017 3

:40:2

7 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

PLU

MB

ING

PLA

N, LO

WE

R L

EV

EL A

RE

A A

P1.0

A

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

PLUMBING PLAN LOWER LEVEL - AREA A

Page 39: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

6

7

5

4

3

2

1

H I J K L M

8

RECORDSSTORAGE

007122 SF

CART STORAGE

004130 SF

CORRIDOR

001

519 SF

HALL

023245 SF

BREAK ROOM

027

448 SF

FUTURE UPS

028

267 SF

ELECTRICAL

029586 SF

CORRIDOR

041459 SF

CORRIDOR

0221572 SF

RECEPTION

006

262 SF

CART STORAGE

002

110 SF

ELEC/DATA

003

72 SF

2"2" W

2 1/

2"2

1/2"

V

2"2" V 3"3" V

2 1/2"2 1/2" V

2"2" V

2"2" V

WC-1

WC-1

WC-1

WC-1

WC-1

WC-1

WC-1

WC-1

WC-1

UR-1

UR-1

MS-1

L-1

L-1

L-1

L-1

L-1

L-1

S-12"2" V

2"2" V

8"8" S

D

4"W DN2" W UP

2" W UPTO FD

3"3" CW

3"3" CW

6"6" Fire Protection Wet

6"6" CW

WATER AND FIRESERVICE ENTERANCE

DUPLEX BOOSTER PUMP

EXISTINGWH-1

EXISTINGWH-1

ROUTE NEW VENTLINE TO EXISTINGVENT STACK

2"2"

CW

2"2" CW1 1/4"1 1/4" CW

2"2" CW

2"2" CW

1 1/2"1 1/2" CW

1 1/4"1 1/4" CW

3/4"3/4" 110-HW

1"1" CW

2"2" V

1"1" 110-HW3/4"3/4" CW

3/4"3/4" 110-HW

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

LEGEND NOTES

Rev

isio

ns

5/8

/2017 3

:40:3

0 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

PLU

MB

ING

PLA

N, LO

WE

R L

EV

EL A

RE

A B

P1.1

B

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

PLUMBING PLAN, LOWER LEVEL - AREA B

Page 40: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

6

7

5

4

3

2

1

HA B C D E F G

8

9

10

REMOVE EXISTING SPRINKLER HEADS TO ACCOMMODATE NEW SPACE LAYOUT

9

9

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

LEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET

BA

NORTH

Rev

isio

ns

5/8

/2017 3

:39:5

1 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

FIR

E P

RO

TE

CT

ION

DE

MO

LIT

ION

, LO

WE

R L

EV

EL -

AR

EA

AD

FP

1.0

A

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

FIRE PROTECTION DEMOLITION PLAN, LOWER LEVEL - AREA A

Keynote Legend

KeyValue Keynote Text

1 FIRE PROTECTION MAINS ROUTED OVER THISAREA TO BE MOVED TO ACCOMMODATE NEWELECTRICAL AND FUTURE UPS ROOMS.

2 EXISTING AHU TO BE REBALANCED TOADJUST FOR AIRFLOW DEDUCTED FROMUNIT.

3 HATCHED AREA INDICATES WORK ABOVECEILING TO BE DONE AS PART OF BIDPACKAGE #2. WORK ASSOCIATED WITH BIDPACKAGE #2 SHALL BE COMPLETED PRIORTO CEILING GRID INSTALLATION.

4 NEW 6" CWS/CWR PIPING TO BE INSTALLEDAS PART OF BID PACKAGE #2 TO BE ROUTEDAS HIGH AS POSSIBLE TIGHT TOSTRUCTURE. COORDINATE ALL WORK INTHIS AREA WITH BID PACKAGE #2MECHANICAL CONTRACTOR.

5 NEW ELECTRICAL CONDUITS TO BEINSTALLED AS PART OF BID PACKAGE #2 TOBE ENCLOSED IN CONCRETE DUCT BANKOVER EXISTING RESTROOMS ANDCORRIDOR. COORDINATE ALL WORK IN THEAREA WITH THE BID PACKAGE #2ELECTRICAL CONTRACTOR.

6 CAP AND VALVE FOR FUTURE COILCONNECTIONS.

7 PROVIDE WALL TYPE THERMOSTAT, MOUNTTO CEILING. PROVIDE ADDITIONAL CONTROLWIRE TO ACCOMMODATE RELOCATION OFTHERMOSTAT AS SPACES ARE FITTED OUT.

9 BUILDING IS TO REMAIN OPERATIONALDURING RENOVATION. COORDINATE WITHOTHER DISCIPLINES TO MINIMIZE THESPRINKLER SYSTEM DOWN TIME. IN THEEVENT OF AN EXTENDED SHUT DOWN OFTHE SPRINKLER SYSTEM, CONTRACTOR TONOTIFY LOCAL FIRE DEPARTMENT AND FIRECODE OFFICIAL AND PROVIDE FIRE WATCHPER NFPA STANDARDS .

10 HVAC DEMOLITION IN THIS AREA IS LIMITEDTO EXISTING AIRSIDE COMPONENTS ONLY.CAREFULLY REMOVE COMPONENTSWITHOUT DISRUPTING SERVICE TO WATERLINES ROUTED ABOVE THE CORRIDOR.

11 REMOVE AND REINSTALL EXHAUSTDUCTWORK AND GRILLES IF NECESSARY TOCOMPLETE ELECTRICAL WORK ABOVERESTROOMS AND CORRIDOR.

12 RELOCATE EXISTING HUMIDIFIER TO EASTWALL OF MECHANICAL ROOM. SEE SHEETM2.0A FOR NEW LOCATION.

13 SHUT OFF SUPPLY AND RETURN VALVES TOBRANCH AND DRAIN DOWN TO ALLOW FORREMOVAL OF HOT WATER PIPING TOTERMINAL BOXES.

14 ENSURE HYDRONIC PIPING IS REMOVEDBACK TO THE CORRIDOR. NO EXISTING ORNEW WATER PIPING IS TO BE ROUTED OVERNEW ELECTRICAL SPACES.

15 PROVIDE LOW LEAKAGE OPPOSED BLADEVOLUME DAMPER.

Page 41: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

6

7

5

4

3

2

1

H I J K L M

8

REMOVE FIRE SPRINKLER HEADS AND PIPING AS NECESSARYTO ACCOMMODATE NEW SPACE LAYOUT. CROSSHATCHEDAREA INDICATES THE EXTENTS OF RENOVATED AREA

9

9

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

LEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET

BA

NORTH

Rev

isio

ns

5/8

/2017 3

:39:5

1 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

FIR

E P

RO

TE

CT

ION

DE

MO

LIT

ION

, LO

WE

R L

EV

EL -

AR

EA

BD

FP

-1.0

B

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

FIRE PROTECTION DEMOLITION PLAN, LOWER LEVEL - AREA B

Keynote Legend

KeyValue Keynote Text

1 FIRE PROTECTION MAINS ROUTED OVER THISAREA TO BE MOVED TO ACCOMMODATE NEWELECTRICAL AND FUTURE UPS ROOMS.

2 EXISTING AHU TO BE REBALANCED TOADJUST FOR AIRFLOW DEDUCTED FROMUNIT.

3 HATCHED AREA INDICATES WORK ABOVECEILING TO BE DONE AS PART OF BIDPACKAGE #2. WORK ASSOCIATED WITH BIDPACKAGE #2 SHALL BE COMPLETED PRIORTO CEILING GRID INSTALLATION.

4 NEW 6" CWS/CWR PIPING TO BE INSTALLEDAS PART OF BID PACKAGE #2 TO BE ROUTEDAS HIGH AS POSSIBLE TIGHT TOSTRUCTURE. COORDINATE ALL WORK INTHIS AREA WITH BID PACKAGE #2MECHANICAL CONTRACTOR.

5 NEW ELECTRICAL CONDUITS TO BEINSTALLED AS PART OF BID PACKAGE #2 TOBE ENCLOSED IN CONCRETE DUCT BANKOVER EXISTING RESTROOMS ANDCORRIDOR. COORDINATE ALL WORK IN THEAREA WITH THE BID PACKAGE #2ELECTRICAL CONTRACTOR.

6 CAP AND VALVE FOR FUTURE COILCONNECTIONS.

7 PROVIDE WALL TYPE THERMOSTAT, MOUNTTO CEILING. PROVIDE ADDITIONAL CONTROLWIRE TO ACCOMMODATE RELOCATION OFTHERMOSTAT AS SPACES ARE FITTED OUT.

9 BUILDING IS TO REMAIN OPERATIONALDURING RENOVATION. COORDINATE WITHOTHER DISCIPLINES TO MINIMIZE THESPRINKLER SYSTEM DOWN TIME. IN THEEVENT OF AN EXTENDED SHUT DOWN OFTHE SPRINKLER SYSTEM, CONTRACTOR TONOTIFY LOCAL FIRE DEPARTMENT AND FIRECODE OFFICIAL AND PROVIDE FIRE WATCHPER NFPA STANDARDS .

10 HVAC DEMOLITION IN THIS AREA IS LIMITEDTO EXISTING AIRSIDE COMPONENTS ONLY.CAREFULLY REMOVE COMPONENTSWITHOUT DISRUPTING SERVICE TO WATERLINES ROUTED ABOVE THE CORRIDOR.

11 REMOVE AND REINSTALL EXHAUSTDUCTWORK AND GRILLES IF NECESSARY TOCOMPLETE ELECTRICAL WORK ABOVERESTROOMS AND CORRIDOR.

12 RELOCATE EXISTING HUMIDIFIER TO EASTWALL OF MECHANICAL ROOM. SEE SHEETM2.0A FOR NEW LOCATION.

13 SHUT OFF SUPPLY AND RETURN VALVES TOBRANCH AND DRAIN DOWN TO ALLOW FORREMOVAL OF HOT WATER PIPING TOTERMINAL BOXES.

14 ENSURE HYDRONIC PIPING IS REMOVEDBACK TO THE CORRIDOR. NO EXISTING ORNEW WATER PIPING IS TO BE ROUTED OVERNEW ELECTRICAL SPACES.

15 PROVIDE LOW LEAKAGE OPPOSED BLADEVOLUME DAMPER.

Page 42: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

6

7

5

4

3

2

1

HA B C D E F G

8

9

10

RECORDSSTORAGE

007122 SF

CART STORAGE

004130 SF

MECHANICAL

009780 SF

RECEPTION

006262 SF

OFFICE

010138 SF

CONFERENCE

012475 SF

FILES

008C59 SF

PRE-PRESS/DIGITALGRAPHICS

0161998 SF

OPEN OFFICE

008688 SF

CORRIDOR

001519 SF

SECUREDPRINT

0201878 SF

COLOR COPY

019684 SF

SECUREDSTORAGE

021251 SF

OFFICE

014117 SF

OFFICE

008A138 SF

SCHED.

01767 SF

OFFICE

011158 SF

CART STORAGE

022A88 SF

WOMEN'S

024230 SF

MEN'S

025

247 SF

JAN

026

20 SF

OFFICE

01894 SF

OFFICE

015117 SF

CART STORAGE

002110 SF

ELEC/DATA

00372 SF

9

9

9

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

LEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET

BA

NORTH

Rev

isio

ns

5/8

/2017 3

:40:0

0 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

FIR

E P

RO

TE

CT

ION

, LO

WE

R L

EV

EL -

AR

EA

AF

P-1

.0A

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

FIRE PROTECTION PLAN, LOWER LEVEL - AREA A

ADJUST FIRE SPRINKLER PIPING AND HEAD LOCATIONS TO ACCOMMODATE NEW ROOM AND EQUIPMENTLAYOUT. COORDINATE WITH OTHER DISCIPLINES TO AVOID DUCT, PIPING, AND CONDUIT CONFLICTS.

Keynote Legend

KeyValue Keynote Text

1 FIRE PROTECTION MAINS ROUTED OVER THISAREA TO BE MOVED TO ACCOMMODATE NEWELECTRICAL AND FUTURE UPS ROOMS.

2 EXISTING AHU TO BE REBALANCED TOADJUST FOR AIRFLOW DEDUCTED FROMUNIT.

3 HATCHED AREA INDICATES WORK ABOVECEILING TO BE DONE AS PART OF BIDPACKAGE #2. WORK ASSOCIATED WITH BIDPACKAGE #2 SHALL BE COMPLETED PRIORTO CEILING GRID INSTALLATION.

4 NEW 6" CWS/CWR PIPING TO BE INSTALLEDAS PART OF BID PACKAGE #2 TO BE ROUTEDAS HIGH AS POSSIBLE TIGHT TOSTRUCTURE. COORDINATE ALL WORK INTHIS AREA WITH BID PACKAGE #2MECHANICAL CONTRACTOR.

5 NEW ELECTRICAL CONDUITS TO BEINSTALLED AS PART OF BID PACKAGE #2 TOBE ENCLOSED IN CONCRETE DUCT BANKOVER EXISTING RESTROOMS ANDCORRIDOR. COORDINATE ALL WORK IN THEAREA WITH THE BID PACKAGE #2ELECTRICAL CONTRACTOR.

6 CAP AND VALVE FOR FUTURE COILCONNECTIONS.

7 PROVIDE WALL TYPE THERMOSTAT, MOUNTTO CEILING. PROVIDE ADDITIONAL CONTROLWIRE TO ACCOMMODATE RELOCATION OFTHERMOSTAT AS SPACES ARE FITTED OUT.

9 BUILDING IS TO REMAIN OPERATIONALDURING RENOVATION. COORDINATE WITHOTHER DISCIPLINES TO MINIMIZE THESPRINKLER SYSTEM DOWN TIME. IN THEEVENT OF AN EXTENDED SHUT DOWN OFTHE SPRINKLER SYSTEM, CONTRACTOR TONOTIFY LOCAL FIRE DEPARTMENT AND FIRECODE OFFICIAL AND PROVIDE FIRE WATCHPER NFPA STANDARDS .

10 HVAC DEMOLITION IN THIS AREA IS LIMITEDTO EXISTING AIRSIDE COMPONENTS ONLY.CAREFULLY REMOVE COMPONENTSWITHOUT DISRUPTING SERVICE TO WATERLINES ROUTED ABOVE THE CORRIDOR.

11 REMOVE AND REINSTALL EXHAUSTDUCTWORK AND GRILLES IF NECESSARY TOCOMPLETE ELECTRICAL WORK ABOVERESTROOMS AND CORRIDOR.

12 RELOCATE EXISTING HUMIDIFIER TO EASTWALL OF MECHANICAL ROOM. SEE SHEETM2.0A FOR NEW LOCATION.

13 SHUT OFF SUPPLY AND RETURN VALVES TOBRANCH AND DRAIN DOWN TO ALLOW FORREMOVAL OF HOT WATER PIPING TOTERMINAL BOXES.

14 ENSURE HYDRONIC PIPING IS REMOVEDBACK TO THE CORRIDOR. NO EXISTING ORNEW WATER PIPING IS TO BE ROUTED OVERNEW ELECTRICAL SPACES.

15 PROVIDE LOW LEAKAGE OPPOSED BLADEVOLUME DAMPER.

Page 43: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

6

7

5

4

3

2

1

H I J K L M

8

ADJUST FIRE SPRINKLER PIPING AND HEAD LOCATIONS TO ACCOMMODATE NEW ROOM AND EQUIPMENTLAYOUT. COORDINAT WITH OTHER DISCIPLINES TO AVOID DUCT, PIPING, AND CONDUIT CONFLICTS.

RECORDSSTORAGE

007122 SF

CART STORAGE

004

130 SF

RECEPTION

006262 SF

CORRIDOR

001519 SF

CORRIDOR

0221572 SF

CORRIDOR

0221572 SF

CART STORAGE

022A88 SF

HALL

023245 SF

WOMEN'S

024230 SF

MEN'S

025247 SF

JAN

026

20 SF

BREAK ROOM

027448 SF

FUTURE UPS

028267 SF

ELECTRICAL

029586 SF

CORRIDOR

041459 SF

CORRIDOR

022

1572 SF

FUTURE

0314467 SF

1

CART STORAGE

002110 SF

9

9

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

LEGEND NOTES ARE COMMON TO ALLSOME NOTES MAY NOT APPLY TO THIS SHEET

BA

NORTH

Rev

isio

ns

5/8

/2017 3

:40:0

1 P

M

C:\R

evit\1

0-1

6206-0

0_M

P_2016_C

entr

al_

mm

art

z.r

vt

10-1

6206-0

0

5/0

8/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

FIR

E P

RO

TE

CT

ION

, LO

WE

R L

EV

EL -

AR

EA

BF

P-1

.0B

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

FIRE PROTECTION PLAN, LOWER LEVEL - AREA B

Keynote Legend

KeyValue Keynote Text

1 FIRE PROTECTION MAINS ROUTED OVER THISAREA TO BE MOVED TO ACCOMMODATE NEWELECTRICAL AND FUTURE UPS ROOMS.

2 EXISTING AHU TO BE REBALANCED TOADJUST FOR AIRFLOW DEDUCTED FROMUNIT.

3 HATCHED AREA INDICATES WORK ABOVECEILING TO BE DONE AS PART OF BIDPACKAGE #2. WORK ASSOCIATED WITH BIDPACKAGE #2 SHALL BE COMPLETED PRIORTO CEILING GRID INSTALLATION.

4 NEW 6" CWS/CWR PIPING TO BE INSTALLEDAS PART OF BID PACKAGE #2 TO BE ROUTEDAS HIGH AS POSSIBLE TIGHT TOSTRUCTURE. COORDINATE ALL WORK INTHIS AREA WITH BID PACKAGE #2MECHANICAL CONTRACTOR.

5 NEW ELECTRICAL CONDUITS TO BEINSTALLED AS PART OF BID PACKAGE #2 TOBE ENCLOSED IN CONCRETE DUCT BANKOVER EXISTING RESTROOMS ANDCORRIDOR. COORDINATE ALL WORK IN THEAREA WITH THE BID PACKAGE #2ELECTRICAL CONTRACTOR.

6 CAP AND VALVE FOR FUTURE COILCONNECTIONS.

7 PROVIDE WALL TYPE THERMOSTAT, MOUNTTO CEILING. PROVIDE ADDITIONAL CONTROLWIRE TO ACCOMMODATE RELOCATION OFTHERMOSTAT AS SPACES ARE FITTED OUT.

9 BUILDING IS TO REMAIN OPERATIONALDURING RENOVATION. COORDINATE WITHOTHER DISCIPLINES TO MINIMIZE THESPRINKLER SYSTEM DOWN TIME. IN THEEVENT OF AN EXTENDED SHUT DOWN OFTHE SPRINKLER SYSTEM, CONTRACTOR TONOTIFY LOCAL FIRE DEPARTMENT AND FIRECODE OFFICIAL AND PROVIDE FIRE WATCHPER NFPA STANDARDS .

10 HVAC DEMOLITION IN THIS AREA IS LIMITEDTO EXISTING AIRSIDE COMPONENTS ONLY.CAREFULLY REMOVE COMPONENTSWITHOUT DISRUPTING SERVICE TO WATERLINES ROUTED ABOVE THE CORRIDOR.

11 REMOVE AND REINSTALL EXHAUSTDUCTWORK AND GRILLES IF NECESSARY TOCOMPLETE ELECTRICAL WORK ABOVERESTROOMS AND CORRIDOR.

12 RELOCATE EXISTING HUMIDIFIER TO EASTWALL OF MECHANICAL ROOM. SEE SHEETM2.0A FOR NEW LOCATION.

13 SHUT OFF SUPPLY AND RETURN VALVES TOBRANCH AND DRAIN DOWN TO ALLOW FORREMOVAL OF HOT WATER PIPING TOTERMINAL BOXES.

14 ENSURE HYDRONIC PIPING IS REMOVEDBACK TO THE CORRIDOR. NO EXISTING ORNEW WATER PIPING IS TO BE ROUTED OVERNEW ELECTRICAL SPACES.

15 PROVIDE LOW LEAKAGE OPPOSED BLADEVOLUME DAMPER.

Page 44: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

ML

GB

DP

FAA

D

SF

RT

P

I

F

##

F

F

##

WP

F

F

FS

TS

###

PTZ

LW

DID

S

S

S

S

S

S

S

S

S

S

3

4

K

P

D

LV

MC

EP

OS

LC

OS

RD

SL

M

DL

IC

SSP

ACC

DCP

(#,#,#)C

CBA

CR

T

R

MD

ID

K

ELECTRICAL SYMBOLSSOME SYMBOLS SHOWN MAY NOT APPLY TO THIS PROJECT

FACP

LIGHTING FIXTURE

STRIP LIGHTING FIXTURE

CEILING LIGHTING FIXTURE (SURFACE, RECESSED OR PENDANT)

WALLWASH LIGHTING FIXTURE

WALL LIGHTING FIXTURE, BRACKET MOUNTED

WALL MOUNTED STRIP LIGHTING FIXTURE

TRACK HEAD FIXTURE, SURFACE, PENDANT, TRACK, OR CABLE

POLE MOUNTED AREA LIGHTING

BOLLARD LIGHTING FIXTURES

IN-GRADE LIGHTING FIXTURES

LIGHTING FIXTURE ON EMERGENCY SYSTEM

STRIP FIXTURE ON EMERGENCY SYSTEM

CEILING FIXTURE ON EMERGENCY SYSTEM

SELF CONTAINED EMERGENCY LIGHTING FIXTURE

EXIT LIGHT FIXTURE, SINGLE FACE, CEILING OR WALL MOUNTED, DIRECTIONALARROW AS INDICATED ON PLANS (SHADED AREA INDICATES FACES)

EXIT LIGHT FIXTURE, DOUBLE FACE, CEILING OR WALL MOUNTED, DIRECTIONALARROW AS INDICATED ON PLANS (SHADED AREA INDICATES FACES)

SWITCH, SINGLE POLE

SWITCH, 3-WAY

SWITCH, 4-WAY

SWITCH, KEY OPERATED

SWITCH, WITH PILOT LIGHT

SWITCH, WALL DIMMER CONTROL

SWITCH, WITH INTEGRATED OCCUPANCY SENSOR

SWITCH, LOW VOLTAGE, MULTI-BUTTON TYPE, SEE SPECIFICATION

SWITCH, LOW VOLTAGE, SINGLE-BUTTON TYPE ON/OFF, CONTROL ZONE ASINDICATED ON PLAN

SWITCH, MOMENTARY CONTACT

SWITCH, EXPLOSION PROOF

OCCUPANCY SENSOR

WALL MOUNT OCCUPANCY SENSOR

PHOTOSENSOR

LIGHTING CONTACTOR

THEATRICAL CONTROL STATION

EMERGENCY LIGHTING RELAY

LOW VOLTAGE LIGHTING RELAY PANEL

INTERCOM CALL STATION

INTERCOM SPEAKER, CEILING MOUNTED(WP:WEATHER PROOF)

INTERCOM SPEAKER, WALL MOUNTED

SPEAKER/HORN, WALL MOUNTED

SPEAKER/HORN, CEILING MOUNTED

VOLUME CONTROL, WALL MOUNTED

INTERCOM OFF TIMER SWITCH

SOUND REINFORCEMENT SPEAKER, CEILING MOUNTED

SOUND REINFORCEMENT SPEAKER, WALL MOUNTED

MICROPHONE OUTLET WITH DEVICE, WALL MOUNTED

MICROPHONE OUTLET WITH DEVICE, FLOOR MOUNTED

DIRECTOR'S HEADSET

CLOCK (ANALOG)

CLOCK (DIGIAL)

CLOCK - DIGITAL, DOUBLE FACED

COMM OUTLET WITH DEVICES, WALL MOUNTED(C: CEILING MOUNTED DEVICE)(#: INDICATES QUANTITY OF CABLES. VOICE, DATA, VIDEO)

COMM OUTLET WITH DEVICES, WALL MOUNTED, ABOVE COUNTER

WIRELESS ACCESS POINT TERMINATION(#: INDICATES QUANTITY OF CABLES. VOICE, DATA, VIDEO)

WALL PHONE(#: INDICATES QUANTITY OF CABLES. VOICE, DATA, VIDEO)

COMM OUTLET WITH DEVICES, FLOOR MOUNTED(#: INDICATES QUANTITY OF CABLES. VOICE, DATA, VIDEO)

COMPUTER VIDEO OUTLET(#: INDICATES QUANTITY OF CABLES. VOICE, DATA, VIDEO)

TEACHER WORKSTATION(#: INDICATES QUANTITY OF CABLES. VOICE, DATA, VIDEO)

TELEVISION OUTLET, WALL MOUNTED(#: INDICATES QUANTITY OF CABLES. VOICE, DATA, VIDEO)

TELEVISION OUTLET, CEILING MOUNTED(#: INDICATES QUANTITY OF CABLES. VOICE, DATA, VIDEO)

BUZZER

CHIME

CELLULAR ANTENNA SYSTEM - ANTENNA

CABLE TRAY (WIDTH AS INDICATED)

SLEEVE WITH BUSHINGS

CONDUIT UP

CONDUIT DOWN

ALARM PUSH BUTTON

DOOR CONTROL PANEL

ACCESS CONTROL COMPUTER

SECURITY SYSTEMS PANEL

VEHICLE LOOP DETECTOR

SOUND DETECTOR ALARM

GLASS BREAK

DOOR FRAME CONDUIT ROUGH-IN

P

LIGHTING

S

S

F

T

POWER

M

CIRCUIT HOME RUN

CONDUIT TURNING UP

CONDUIT TURNING DOWN

CONDUIT STUB-UP

CONDUIT SLEEVE

CONDUIT CONCEALED IN CEILING OR WALLS

CONDUIT CONCEALED IN FLOOR OR UNDERGROUND

TRANSFORMER

BRANCH CIRCUIT PANEL BOARD

DISTRIBUTION PANEL BOARD

EQUIPMENT CABINET, AS NOTED

SWITCHBOARD

CURRENT TRANSFORMER ENCLOSURE

METER

GENERATOR

AUTOMATIC TRANSFER SWITCH

SYSTEM GROUND ELECTRODE

THERMOSTAT

MUSHROOM SWITCH

ELECTRICAL MANHOLE

ELECTRICAL HAND HOLE

MECHANICAL EQUIPMENT CONNECTION, SEE SCHEDULES

SWITCH W/ FUSE

TIMER SWITCH

MOTOR RATED TOGGLE SWITCH

THERMOSTAT (MECH)

HUMIDISTAT (MECH)

SENSOR (MECH)

SWITCH, PUSHBUTTON, SINGLE

SWITCH, PUSHBUTTON, DOUBLE

SWITCH, PUSHBUTTON, TRIPLE

SINGLE RECEPTACLE

DUPLEX RECEPTACLE

DUPLEX RECEPTACLE, ABOVE COUNTER, SEE DETAIL

DUPLEX RECEPTACLE, GFCI

DUPLEX RECEPTACLE, GFCI, ABOVE COUNTER, SEE DETAIL

DUPLEX RECEPTACLE ON ROOF, GFCI, WP COVER

DUPLEX RECEPTACLE, USB

FOURPLEX RECEPTACLE

FOURPLEX RECEPTACLE, USB

DUPLEX RECEPTACLE, CEILING MOUNTED

DUPLEX RECEPTACLE, HORIZONTALLY MOUNTED

DUPLEX RECEPTACLE, HORIZONTALLY MOUNTED, USB

DUPLEX RECEPTACLE, EMERGENCY

FOURPLEX RECEPTACLE, EMERGENCY

DUPLEX RECEPTACLE, LOWER SWITCH

DUPLEX RECEPTACLE, SWITCHED

RANGE RECEPTACLE, MOUNT 8 INCHES AFF

SPECIAL RECEPTACLE, IN DEEP BOX

FLOOR BOX

FLOOR BOX WITH DUPLEX RECEPTACLE

FLOOR BOX WITH DUPLEX AND TELECOM OUTLETS

MULTI-OUTLET ASSEMBLY

DIVIDED SURFACE RACEWAY

FLUSH JUNCTION BOX, CEILING MOUNTED

FLUSH JUNCTION BOX, WALL MOUNTED

SURFACE JUNCTION BOX, CEILING MOUNTED

SURFACE JUNCTION BOX, WALL MOUNTED

FLUSH JUNCTION BOX FOR HAND DRYER

PULL BOX

EQUIPMENT ELECTRICAL CONNECTION

MECHANICAL EQUIPMENT ELECTRICAL CONNECTION

SM

T

XXX

XXX

XXX

CT

GEN

ATS

T

MH

HH

M

T

H

CO2

J

J

J

J

PB

COMMUNICATIONS SYSTEMS

IC

S

S

H

V

SR

M

M

D

D

DS

SR

DOOR INTRUSION SWITCH(D: TIME DELAY WHERE INDICATED)

MOTION DETECTOR(L: LONG RANGE)(W: WIDE RANGE)

INTRUSION RECEIVER

INTRUSION TRANSMITTER

KEYPAD(A: MASTER)(B: ZONE)(C: SUB-ZONE)

VIDEO INTERCOM CALL STATION

VIDEO INTERCOM MASTER STATION

VIDEO INTERCOM SUB-MASTER STATION

CARD ACCESS READER

CCTV CAMERA, WALL MOUNTED(PTZ: PAN/TILT/ZOOM WHERE INDICATED)

CCTV CAMERA, CEILING MOUNTED

ELECTRIC DOOR LOCK

MONITORED DOOR

ELECTRIC DOOR LOCK - SLIDER

ROLL - UP DOOR OUTLET

DOOR POSITION SWITCH

MOTOR OPERATED ELECTRIC DOOR LOCK

FACILITY INTERCOM

CALL BUTTON

CV

TV

TV

(#,#,#)

H

(#,#,#)

TW(#,#,#)

(#,#,#)

(#,#,#)

(#,#,#)AP

C

SAFETY

FIRE ALARM MANUAL PULL STATION

FIRE ALARM SPEAKER NOTIFICATION(WP: WEATHER PROOF)

FIRE ALARM SPEAKER WITH VISUAL WARNING(##:CANDELA RATING)

FIRE ALARM VISUAL WARNING(##: CANDELA RATING)

FIRE ALARM HORN(WP: WEATHER PROOF)

FIRE ALARM HORN WITH VISUAL WARNING(##: CANDELA RATING)

FIRE ALARM NOTIFICATION DEVICE - CEILING MOUNTED

FIRE ALARM BELL

FIRE ALARM SMOKE DETECTOR-IONIZATION

FIRE ALARM SMOKE DETECTOR-PHOTOELECTRIC

FIRE ALARM SMOKE DETECTOR, UNDERFLOOR

FIRE ALARM SMOKE DETECTOR, WALL MOUNTED

FIRE ALARM SMOKE DUCT DETECTOR-PHOTOELECTRIC(HVAC AIR DUCT TYPE WITH SAMPLING TUBE)

FIRE ALARM HEAT DETECTOR, RATE-OF-RISE & FIXEDTEMPERATURE, (135°)

FIRE ALARM HEAT DETECTOR, FIXED TEMPERATURE, (200°)

FIRE ALARM HEAT DETECTOR, RATE-OF-RISE & FIXEDTEMPERATURE (200°)

FIRE ALARM BEAM SMOKE DETECTOR(T: TRANSMITTER, R: RECEIVER)

VOICE EVACUATION SPEAKER, CEILING MOUNTED

VOICE EVACUATION HORN, WALL MOUNTED

VOICE EVACUATION HORN, CEILING MOUNTED

FIRE RISER TAMPER SWITCH CONNECTION

FIRE RISER WATER FLOW SWITCH CONNECTION

FIRE ALARM MAGNETIC DOOR RELEASE DEVICE

FIRE ALARM CONTROL PANEL

FIRE ALARM ANNUNCIATOR PANEL

REMOTE INDICATOR LAMP & TEST STATION

MONITOR MODULE

RELAY MODULE

POST INDICATOR VALVE CONNECTION

SUPPLEMENTAL NOTIFICATION APPLIANCE CIRCUITPOWER SUPPLY

SECURITY

ER

A

SZ#

XXX

PC

STS

L

M

R

PIV

D

F

WP

F

HF

HF

P

SNAC

##

WP

OS

T

XX

HD

###

VIC

VM

VS

R

U

##

F

C

(#,#,#)

MOUNTING HEIGHT SCHEDULE__________________________________________________________

CENTERLINE OF BOXDEVICE ABOVE FINISHED

FLOOR U.N.O.__________________________________________________________

1. SWITCH 42 INCHES

2. RECEPTACLE 18 INCHES3. DOOR PUSHBUTTON 42 INCHES4. DISCONNECT SWITCH 54 INCHES5. MOTOR STARTER 54 INCHES6. PANELBOARD 72 INCHES TO TOP

7. PULL STATION 42 INCHES8. FIRE HORN WITH VISUAL WARNING* 90 INCHES9. VISUAL WARNING LIGHT* 90 INCHES10. FIRE SPEAKER WITH VISUAL WARNING* 90 INCHES11. FIRE SPEAKER HORN (WALL MOUNT) 144 INCHES12. FIRE ALARM CONTROL PANEL 72 INCHES TO TOP13. FIRE ALARM ANNUNCIATOR PANEL 60 INCHES TO TOP14. DOOR HOLDER 74 INCHES

15. TV OUTLET 65 INCHES16. COMMUNICATIONS OUTLET 18 INCHES17. WALL PHONE 52 INCHES18. MICROPHONE OUTLET 18 INCHES19. VOLUME CONTROL 42 INCHES20. SPEAKERS (WALL MOUNT) 94 INCHES OR

12 INCHES BELOW CEILING21. CARD READER 42 INCHES22. DOOR SECURITY RELEASE PUSHBUTTON 42 INCHES23. SECURITY KEYPAD 52 INCHES26. AUDIO-VIDEO CONTROLLER 52 INCHES27. AUDIO-VIDEO OUTLET 18 INCHES28. CHIME 84 INCHES

* MOUNT AT HEIGHTS INDICATED OR 6 INCHES BELOW CEILING WHICHEVER IS LOWER.

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

Rev

isio

ns

5/8

/2017 4

:28:5

3 P

M

C:\R

evit\1

0-1

6206-0

0_E

L_2016_C

entr

al_

ekam

in.r

vt

10-1

6206-0

1

3/2

9/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

ELE

CT

RIC

AL S

YM

BO

LS

AN

D A

BB

RE

VIA

TIO

NS

E0.0

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

Page 45: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

S

S

S

S3

S2S

S3

S S S S

SS

SS

SSS

SS

S

SD

DD

CR

CR

CR

F

30

F

110

30

F

15

F

F

75

F

75

F

75 15

F

F

75

75

F

F

15

P

P

PP

P

P

P

P

P PP

P

P P

P PP

P

P

P

PD

PD

P

SS

SA

A

A

C

S

GH

XFMR G

GL

GA

D7

MA

TC

HLI

NE

- A

RE

A A

MA

TC

HLI

NE

- A

RE

A B

MCPD2

D18

D19

D19

D19 D19

D19

D6

DOCUTECD7

D20

MA

TC

HLI

NE

- A

RE

A A

MA

TC

HLI

NE

- A

RE

A B

42"42"42"42"42"

42"

42"

42" 42" 42" 42"

D21

D21

42"

D22 D23

D24

D24

D2

D25

D26

(TYPICAL ALL DEMOLITION SHEETS):

1. DEVICES SHOWN FULL TONE OR NOTED ELSEWHERE IN THEDOCUMENTS TO BE REMOVED OR DEMOLISHED SHALL BE REMOVED ASFOLLOWS: ALL WIRING BACK TO CONTROL DEVICE, PANELBOARD, ORNEAREST J-BOX TO REMAIN. ALL CONDUIT (ABOVE GRADE) BACK TOCONTROL DEVICE OR NEAREST J-BOX TO REMAIN. AT J-BOXES WHERECONDUIT HAS BEEN REMOVED, PROVIDE KNOCKOUT PLUGS. IF CONDUITORIGINATES AT A PANELBOARD, STUB-UP FROM PANELBOARD TO NEARESTCOUPLER OR J-BOX AND LABEL CIRCUIT BREAKER AS A SPARE, UNLESSNOTED OTHERWISE.

2. DEVICES AND LIGHT FIXTURES TO BE REMOVED SHALL BE TURNEDOVER TO THE OWNER (AT OWNER'S REQUEST). ALL DEVICES, LIGHTFIXTURES, CONDUIT AND CONDUCTORS NOT REQUESTED TO BE RETAINEDBY THE OWNER SHALL BE PROPERLY DISPOSED OF OFF THE SITE.

3. EXISTING CONDUIT MAY REMAIN IF ALL THE FOLLOWING ARE TRUE:A. IT CAN BE REUSED TO FEED DEVICES INSTALLED UNDER THIS

CONTRACT.B. DOES NOT INTERFERE WITH OTHER TRADES.C. MEETS PROJECT SPECIFICATIONS.D. WILL NOT BE EXPOSED IN A FINISHED AREA (UNO).

4. CONDUITS CONCEALED IN MASONRY WALLS OR UNDER CONCRETESLABS MAY BE CUT BACK, SEALED AND ABANDONED.

5. PROVIDE BLANK COVERPLATES ON ALL ABANDONED BOXES TOREMAIN IN EXISTING MASONRY OR STUD WALLS.

6. DEVICES SHOWN HALF TONE ARE EXISTING TO REMAIN.

7. MAINTAIN POWER TO END-OF-LINE OR DOWNSTREAM DEVICES THATARE TO REMAIN. PROVIDE RACEWAYS, BOXES, CONDUCTORS AND ALLOTHER NECESSARY MATERIALS AS REQUIRED TO RE-ESTABLISH DAMAGEDOR INTERRUPTED FEEDERS AND BRANCH CIRCUITS. INTERCEPT EXISTINGFEEDERS OR BRANCH CONDUCTORS AT NEAREST ACCESSIBLE SPACE ORDEVICE AND RECONNECT TO ORIGINAL FEEDER OR BRANCH CIRCUITSOURCE.

8. ITEMS INDICATED ON DEMOLITION PLANS ARE BASED ON AS-BUILTDRAWINGS AND FIELD OBSERVATIONS AND ARE INTENDED TO GIVE THEBIDDER A GENERAL REPRESENTATION OF EXISTING CONDITIONS.DEMOLISH ADDITIONAL ITEMS WHICH MUST BE REMOVED TO COMPLETETHE PROJECT EVEN IF NOT SHOWN ON DRAWINGS.

9. PROVIDE ELECTRICAL DEMOLITION ASSOCIATED WITH MECHANICALEQUIPMENT TO BE REMOVED. IN ADDITION TO DEVICES SHOWN, REFER TOMECHANICAL AND ARCHITECTURAL DEMOLITION SHEETS TO DETERMINEEQUIPMENT TO BE REMOVED.

10. UNLESS OTHERWISE NOTED, MAINTAIN FUNCTIONALITY OF ALLEXISTING LOW VOLTAGE SYSTEMS INCLUDING, BUT NOT LIMITED TO, FIREALARM, INTERCOM, TELECOM CABLING NETWORKS, AND SECURITY DURINGALL PHASES OF CONSTRUCTION. PROVIDE TEMPORARYINTERCONNECTIONS AS REQUIRED TO ACCOMMODATE CONSTRUCTIONSCHEDULE.

11. CUT BACK CONDUITS BELOW GRADE FOR ELECTRICAL DEVICES ATISLANDS OR STAND-ALONE WORKSTATIONS TO BE REMOVED. COORDINATEWITH OTHER TRADES TO PREPARE FOR FLOOR COVERING.

DEMO NOTE:

DUE TO THE CRITICAL NATURE OF THE 501 BUILDING OPERATIONS,CONTRACTOR TO DEMO AND DECONSTRUCT IN A MANNER SO AS TONOT AFFECT THE CONTINUITY OF OPERATIONS IN AREAS NOT APART OF RECONSTRUCTION. SEE SPECS FOR "PROCEDURES ANDGUIDELINES FOR WORKING IN AN ACTIVE DATA CENTER."

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

BA

NORTH

Rev

isio

ns

5/8

/2017 4

:28:4

7 P

M

C:\R

evit\1

0-1

6206-0

0_E

L_2016_C

entr

al_

ekam

in.r

vt

10-1

6206-0

1

3/2

9/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

ELE

CT

RIC

AL D

EM

OLIT

ION

PLA

N, LO

WE

R L

EV

EL -

AR

EA

AD

E1.0

A

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

SCALE: 1/8" = 1'-0"

ELECTRICAL DEMOLITION PLAN, LOWER LEVEL - AREA A

KEYED NOTES

KEY

VALUE KEY TEXT

D2 COORDINATE EXTENT OF DEMOLITION WITH NEW WORKSCOPE. SEE NEW WORK FLOOR PLANS FOR ADDITIONALINFORMATION.

D6 SALVAGE EXISTING PHOTOELECTRIC DETECTORS FORREINSTALLATION ON NEW CEILING. DEVICES TO BEREINSTALLED IN NEAREST LOCATION ACCORDING TONEW WORK DRAWINGS. TYPICAL UNO.

D7 REMOVE PANEL. REUSE EXISTING FEEDERS AND BRANCHCIRCUITS AS NECESSARY FOR RELOCATION OF PANEL INNEW WORK SCOPE.

D18 REROUTE ALL CONDUIT ON EXISTING WALL TO BEDEMOLISHED.

D19 SALVAGE 208V RECEPTACLES FOR REUSE ANDINSTALLATION TO SERVE EQUIPMENT IN NEW LOCATIONINDICATED ON E2.0A.

D20 RELOCATE EXISTING PENDANT RECEPTACLE ASINDICATED ON E2.0A. DEMO EXISTING CIRCUIT BACK TOPANEL.

D21 DEMO EQUIPMENT AND WIRING BACK TO SOURCE

D22 SALVAGE CELLULAR ANTENNA SYSTEM FORREINSTALLATION (TYPICAL).

D23 SALVAGE PA SYSTEM FOR REINSTALLATION (TYPICAL).

D24 DOOR BELL, CHIME, AND LIGHT TO BE SALVAGED FORREINSTALLATION.

D25 SALVAGE POWER POLE FOR REINSTALLATION.

D26 REMOVE CONNECTION TO HUMIDIFIER. SEE SHEET E2.0AFOR NEW LOCATION.

Page 46: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

S

SSS

S

SS

S3

S3

S

S

S

SS

S

S

S

SbS

c

S S

S

S

SS

S

SS

SS

S

S

S

S

S

S3

SOS

S3

S

CR

CR

CR

D

D

D

CR

D

SS

CR

S

CR

CR

S

F

F

75

F

15

F

15

F

15

F

15

F

15

F

30

F

15

F

F

30

F

30

F

30

15

F

F

F

110

110

F

F

30

30

F

F

110

F

75

SN

AC

F

15

F

15

F

75

F

F

15

15

F

15

F

F

15

P

P PP

P

P

P

P PP

PPP

P

P

P

PP

P

P

P

PP

P

P

P

PP

P

P

P

P P

PP

P P

P

P

S

S

BB

D7

MA

TC

HLI

NE

- A

RE

A A

MA

TC

HLI

NE

- A

RE

A B

EXISTING 750kVA UPS

POWER POLE

D6

2000 GAL. UNDERGROUNDGENERATOR FUEL TANK

D13

FLEX DROP CORD

D25

D25

DEMO NOTE:

DUE TO THE CRITICAL NATURE OF THE 501 BUILDING OPERATIONS,CONTRACTOR TO DEMO AND DECONSTRUCT IN A MANNER SO AS TONOT AFFECT THE CONTINUITY OF OPERATIONS IN AREAS NOT APART OF RECONSTRUCTION. SEE SPECS FOR "PROCEDURES ANDGUIDELINES FOR WORKING IN AN ACTIVE DATA CENTER."

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

BA

NORTH

Rev

isio

ns

5/8

/2017 4

:28:4

9 P

M

C:\R

evit\1

0-1

6206-0

0_E

L_2016_C

entr

al_

ekam

in.r

vt

10-1

6206-0

1

3/2

9/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

ELE

CT

RIC

AL D

EM

OLIT

ION

PLA

N, LO

WE

R L

EV

EL -

AR

EA

BD

E1.0

B

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

SCALE: 1/8" = 1'-0"

ELECTRICAL DEMOLITION PLAN, LOWER LEVEL - AREA B

KEYED NOTES

KEY

VALUE KEY TEXT

D6 SALVAGE EXISTING PHOTOELECTRIC DETECTORS FORREINSTALLATION ON NEW CEILING. DEVICES TO BEREINSTALLED IN NEAREST LOCATION ACCORDING TONEW WORK DRAWINGS. TYPICAL UNO.

D7 REMOVE PANEL. REUSE EXISTING FEEDERS AND BRANCHCIRCUITS AS NECESSARY FOR RELOCATION OF PANEL INNEW WORK SCOPE.

D13 DEMOLISH AND REPLACE EXISTING CONDUIT ANDCABLING THAT CONFLICTS WITH INSTALLATION OF NEWJOISTS. SEE FRAMING PLANS FOR LOCATIONS. EXACTSCOPE OF WORK IS NOT SHOWN, FIELD VERIFY DURINGPRE-BID CONFERENCE. IF CONDUIT OR CABLE SERVES ACRITICAL FUNCTION, CONTACT ENGINEER PRIOR TODEMO. SEE GENERAL DEMO NOTE THIS SHEET.

D25 SALVAGE POWER POLE FOR REINSTALLATION.

Page 47: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

IC

CR

IC

CR

S S S S SS S

SS

SSSS

CR

K

CR

CR SSS S

F

15

F

F

15

15

F

15

F

F

110

F

F

110

F

110

75

F

F

75

F

F

F

15

75

F

30

F

P

P

P

PP

PPP

P P P

PP

PP

P PP P

P

P

F

F

CR

CR

CR

CR F

PP

CR

CRCR

CR

CR

P

F

S

IC

P

P

P

P

P P

P

P

P

P

P

CR

FACP

SS

S

S

P

P

S

CR

CR

J

ALTERNATE S1D1

MA

TC

HLI

NE

- A

RE

A A

MA

TC

HLI

NE

- A

RE

A B

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

Rev

isio

ns

5/8

/2017 4

:28:5

1 P

M

C:\R

evit\1

0-1

6206-0

0_E

L_2016_C

entr

al_

ekam

in.r

vt

10-1

6206-0

1

3/2

9/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

ELE

CT

RIC

AL D

EM

OLIT

ION

PLA

N, F

IRS

T F

LO

OR

DE

1.1

B

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

SCALE: 1/8" = 1'-0"

ELECTRICAL DEMOLITION PLAN, FIRST LEVEL

KEYED NOTES

KEY

VALUE KEY TEXT

D1 REMOVE ALL LIGHT FIXTURES AND CEILING MOUNTEDDEVICES TO FACILITATE STRUCTURAL NEW WORK INALTERNATE S1. DEVICES SHALL BE SALVAGED FORREINSTALLATION.

Page 48: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

S

S

SS

SS

SSS

SS

S

S

Sa

S

S

S

S

OSOS

OS

OS

OS

SS

S3

SER

OS

S

SS

S3

S

OS

OS

OS

OS

OS

S

ER

OSOS

OS

OS

OS

OS

OS

OS

OS

OS

OSOS

ER

ER

ER

S3S4

OS

OS

S

OS

OS

OS

OS

S

ER

S3

OS ERER

ERER

ER

Sb

R3bGA2- 5a

R3bEM- 18a

R3bGA2- 5a

R3bGA2- 5a

R3bEM- 18a

R3bGA2- 5a

R3bGA2- 5b

R3bGA2- 5b

R2aEM- 18

R2aGA2- 1

R2aGA2- 1

R2aEM- 18

R2aBB1- 32

R3aGA2- 7

R3aGA2- 7

R3bGA2- 7

R3bEM- 18

R3bGA2- 7

R3bGA2- 7

R3bGA2- 7

R3bGA2- 7

R3bGA2- 7

R3bEM- 18

R3bGA2- 7

R3bGA2- 7

R3bGA2- 7

R3bEM- 18

R3bGA2- 7

R3bGA2- 7

R3bGA2- 5b

R3bGA2- 5

R3bGA2- 5

R3bEM- 18

R3aGA2- 7

R3aGA2- 7

R3aGA2- 7

R3aEM- 18

R2aGA2- 3

R2aGA2- 3

R2bEM- 18

R2bEM- 18

R2bGA2- 3

R2bGA2- 3

R2bEM- 18

R2bGA2- 3

R2bEM- 18

R2bGA2- 3

R2bEM- 18

R2bGA2- 3

R2bGA2- 1

R2bGA2- 3

R2bGA2- 3

R2bGA2- 3

R2bGA2- 3

R2bGA2- 3

R2aGA2- 3

R2aEM- 18

R2bEM- 18

R2bGA2- 9

R2bEM- 18

R2bGA2- 1

R2bGA2- 1

R2bGA2- 1

R2bGA2- 9

R2bGA2- 9

R2bGA2- 9

R2bEM- 18

R2bGA2- 1

R2aGA2- 7

R2bGA2- 1

R2bGA2- 1

R2bGA2- 1

R2bGA2- 1

R2bEM- 18

R2bGA2- 1

R2bEM- 18

R2bGA2- 1

R2bGA2- 1

R2bGA2- 1

R2bEM- 18

R2bGA2- 1

R2bGA2- 1

R2bGA2- 1

R2bGA2- 1

R2aGA2- 1

R2bGA2- 7

R2bEM- 18

R2bBB1- 32

R2bBB1- 32R2a

EM- 16

R2aBB1- 32

R2aBB1- 32

R2aEM- 16

R2aBB1- 32

P1aBB1- 32

P1aEM- 16

P1aBB1- 32

P1aBB1- 32

RECORDSSTORAGE

007

CART STORAGE

004

MECHANICAL

009

RECEPTION

006

OFFICE

010

CONFERENCE

012

PRE-PRESS/DIGITALGRAPHICS

016

OPEN OFFICE

008

CORRIDOR

001

SECUREDPRINT

020

COLOR COPY

019

SECUREDSTORAGE

021HALL

005R2aEM- 18X1

EM- 18

P1aP1aP1a P1a

R2bGA2- 9

R2bGA2- 9

R2bEM- 18

R2bGA2- 9

R2aGA2- 3

R2bGA2- 3

R2bGA2- 3

R2bGA2- 3

R2bGA2- 3

R2bGA2- 3

R2bGA2- 1

R2bGA2- 1

R2bGA2- 1

R2bGA2- 1

R2bGA2- 1

R2bGA2- 3

R2bGA2- 3

R2bGA2- 3

R2bGA2- 9

R2bGA2- 3

R2bGA2- 3

R2bGA2- 3

R2bGA2- 3

R2bGA2- 3

R2bGA2- 9

R2aGA2- 7

R2aGA2- 7

R2bGA2- 1

R2bGA2- 1

R2bGA2- 1

R2bGA2- 1

R2bGA2- 1

R2bGA2- 1

R2aGA2- 3

R2aGA2- 3

R2aGA2- 3

R2aGA2- 3

R2aGA2- 3

MA

TC

HLI

NE

- A

RE

A A

MA

TC

HLI

NE

- A

RE

A B

R2aEM- 18

R3aGA2- 7

R3aEM- 18

R2bGA2- 9

R3bEM- 18

R3bGA2- 5

R3bGA2- 5

R3bGA2- 5

R3bGA2- 5

R3bGA2- 5b

R3aGA2- 7

R3aEM- 18

R3aGA2- 7

R2bGA2- 1

R3bGA2- 7

R3bGA2- 7

R3bGA2- 7

R3bGA2- 7

OFFICE

014

OFFICE

011

X1EM- 18

W1

X1EM- 16

OFFICE

015

GA2 GA1

X1EM- 18

X1EM- 16

X1EM- 18

L1

L4

L5

FILES

008C

OFFICE

008A

HALL

008B

L6

L6

L5

MOUNT AT 9'-0" AFF

SCHED.

017

CART STORAGE

002

ELEC/DATA

003

R3bGA2- 7

R3bGA2- 7

R3bEM- 18

R3bGA2- 7

MOUNT AT 9'-0'' AFF. (TYP)

L13

X1EM- 18

X1EM- 18

X1EM- 18

MA

TC

HLI

NE

- A

RE

A A

MA

TC

HLI

NE

- A

RE

A B

CART STORAGE

022A

JAN

026

OFFICE

018

L5

LIGHTING NOTES(TYPICAL ALL LIGHTING SHEETS)

1. TYPICAL LIGHTING NOMENCLATURE:

FIXTURE TYPEPANEL-CIRCUIT #SWITCH OR ZONE

2. IF SWITCHING IS NOT DESIGNATED, THEN ALL FIXTURES IN THATROOM SHALL BE SWITCHED TOGETHER, UNLESS NOTED OTHERWISE.

3. IF CIRCUITING IS NOT INDICATED, THEN THE FIXTURE SHALL BECONNECTED TO THE CIRCUIT SHOWN SERVING THAT ROOM.

4. MOUNTING HEIGHT REFERS TO THE DISTANCE AFF TO BOTTOM OFFIXTURE, UNLESS INDICATED OTHERWISE.

5. NL INDICATES FIXTURE IS NOT SWITCHED AND SERVES AS A NIGHTLIGHT.

6. SEE SPECIFICATION SECTION 260533 (PART 3) FOR LIMITATIONS ONUSE OF FLEXIBLE CONDUIT, TO INCLUDE FIXTURE WHIPS. TANDEMWIRING FROM FIXTURE TO FIXTURE IS UNACCEPTABLE. ALL FIXTUREWHIPS SHALL ORIGINATE FROM A LOCAL, ACCESSIBLE, JUNCTION BOX.

7. COMMISSIONING OF WALL SWITCH AND CEILING MOUNTEDOCCUPANCY SENSORS FOR LIGHTING CONTROL: UTILIZEMANUFACTURER'S RECOMMENDATIONS AND OWNER INPUT TO ADJUSTAND SET BOTH TIME DELAYS AND LIGHT LEVEL SENSORS ACCORDINGTO AREA BEING SERVED. RECORD SETTINGS AND TURN OVER TOOWNER. DO NOT LEAVE SENSORS ON FACTORY DEFAULTS. PROVIDEFINAL WALK-THRU WITH OWNER UPON COMPLETION TO VERIFYACCURACY OF SETTINGS.

8. OCCUPANCY SENSORS: SENSORS ON PLANS ARE SCHEMATIC.SYSTEM TO BE DESIGNED BY APPROVED MANUFACTURER.ELECTRICAL CONTRACTOR TO COORDINATE ALL LOCATIONS,QUANTITIES, AND ROUGH-INS WITH REVIEWED SHOP DRAWINGS. SEESPECIFICATION SECTION 260923 FOR ADDITIONAL INFORMATION. SEEDETAIL FOR WIRING DIAGRAM. POWER PACKS ARE NOT SHOWN ONPLANS.

9. WHERE LUMINAIRES ARE SHOWN TO BE CONNECTED TO ANEXISTING CIRCUIT, COORDINATE WITH FIELD CONDITIONS ANYNECESSARY CONDUIT MODIFICATIONS. DO NOT ASSUME ALL EXISTINGCONDUIT MAY BE REUSED AND NEW CONDUIT IS NOT REQUIRED.

10. EXPOSED STRUCTURE: IN SPACES WITHOUT A CEILING (EXPOSEDSTRUCTURE), SUSPEND LIGHT FIXTURES FROM UNISTRUT AT TOP CORDOF JOISTS UNLESS NOTED OTHERWISE.

GENERAL NOTE:

PHASE 2 WORK IS COMPOSED OF NEW ELECTRICALSERVICE, GENSETS, AND CHILLED WATER PIPING FOR THEDATA CENTER AND BUILDING.

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

BA

NORTH

Rev

isio

ns

5/8

/2017 4

:28:5

6 P

M

C:\R

evit\1

0-1

6206-0

0_E

L_2016_C

entr

al_

ekam

in.r

vt

10-1

6206-0

1

3/2

9/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

LIG

HT

ING

PLA

N, LO

WE

R L

EV

EL -

AR

EA

AE

1.0

A

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

LIGHTING PLAN, LOWER LEVEL - AREA A

KEYED NOTES

KEY

VALUE KEY TEXT

L1 LIGHT FIXTURE TO BE CONNECTED TO CIRCUIT SERVINGTHIS ROOM. (TYPICAL).

L4 ALL FIXTURES THIS ROOM TO BE SWITCHED TOGETHER.

L5 SWITCH CONTROLS ALL FIXTURES IN ROOM 005, 016 AND017.

L6 3-WAY SWITCH CONTROLS ALL FIXTURES IN ROOM 006,008, 008A, 008B, AND 008C.

L13 HOMERUN TO SPARE 20A/1P BREAKER IN PANEL EM.

Page 49: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

RE

F.

S

SSS

S

SS

S3

S3

S

S

S

S

S

S3

SOS

S3

S3 S3

S

S

S

S3

S3

OS

OS

OS

OS

ER

ER

ER

ER

ER ER

ER

S3

S

S

OSOSOS

OS

OS

OS

OS

OS

OS

OS

S3

S

R3aBB1- 32

R3aEM- 16

R3aBB1- 32

R3aBB1- 32

R3aBB1- 32

R3aEM- 16

R2aEM- 16

R2aBB1- 32

R2aBB1- 32

R2aEM- 16

R2aEM- 16

R2aBB1- 32

R2aBB1- 32

R2aEM- 16

R2aBB1- 32

R2aBB1- 32

R2aEM- 16

R2aBB1- 32

R2aBB1- 32

R2aEM- 16

R2aBB1- 32

R2aBB1- 32

R2aEM- 16

R2aBB1- 32

R2aBB1- 32

R2aEM- 16

R2aBB1- 32

R2aBB1- 32

R2aEM- 16

R2aBB1- 32

R2aBB1- 32

R2aEM- 16

R1BB1- 32

R1EM- 16

R1BB1- 32

R1BB1- 32

R1EM- 16

R1BB1- 32

R2aBB1- 30

R2aBB1- 30

R2aBB1- 30

W3EM- 19

W3EM- 19

W3EM- 19

W3EM- 19

W3EM- 19

P1bEM- 19

P1bEM- 19

P1bEM- 19

P1aEM- 19

P1aEM- 19

P1aEM- 19 P1a

EM- 19

R2bEM- 16

R2bBB1- 28

R2bBB1- 28

R2bBB1- 28

R2bBB1- 28

R2bBB1- 28

X2EM- 16

X1EM- 16

X1EM- 16

X1EM- 16

CART STORAGE

022A

HALL

023

WOMEN'S

024

MEN'S

025

JAN

026

BREAK ROOM

027

FUTURE UPS

028

ELECTRICAL

029

CORRIDOR

041

CORRIDOR

022

X1EM- 16

X1EM- 16

P1aBB1- 32

W1BB1- 32

D1EM- 16

MA

TC

HLI

NE

- A

RE

A A

MA

TC

HLI

NE

- A

RE

A B

X1EM- 16

X2EM- 16

X1EM- 16

X1EM- 16

X1EM- 16

BB1

R2aEM- 16

EM

L8

L8

P1aEM- 19

P1aBB1- 32

MOUNT AT 9'-0" AFF. (TYP)

MOUNT AT 9'-0" AFF. (TYP)

L13

L13P1aEM- 19

P1aEM- 19

AB

X1EM- 16

R2aEM- 16

R2aBB1- 30

R2aBB1- 30

R2bBB1- 30

R2aBB1- 30

R2aBB1- 30

R2aBB1- 30

R2bBB1- 28

R2bBB1- 28

R2bBB1- 28

R2bBB1- 28

FUTURE

031

R2bBB1- 30

R2bBB1- 30

R2bBB1- 30

R2bBB1- 30

R2bBB1- 30

R2bBB1- 30

R2bBB1- 30

R2bBB1- 30

R2bBB1- 30

R2bBB1- 30

R2bBB1- 30

R2bEM- 16

R2bBB1- 30

R2bBB1- 30

R2bBB1- 30

R2bEM- 16

R2bBB1- 30

R2bBB1- 30

R2bBB1- 30

R2bBB1- 30

R2bBB1- 28

R2bBB1- 28

R2bBB1- 28

R2bBB1- 28

R2bEM- 16

R2bBB1- 28

R2bBB1- 28

R2bBB1- 28

R2bBB1- 28

R2bBB1- 28

R2bEM- 16

R2bBB1- 28

R2bBB1- 28

R2bBB1- 28

R2bBB1- 28

R2bBB1- 28

R2bBB1- 28

R2bBB1- 28

R2bBB1- 28

L14

MA

TC

HLI

NE

- A

RE

A A

MA

TC

HLI

NE

- A

RE

A B

L15

D2BB1- 32

D2BB1- 32

D2BB1- 32

D2BB1- 32

GENERAL NOTE:

PHASE 2 WORK IS COMPOSED OF NEW ELECTRICALSERVICE, GENSETS, AND CHILLED WATER PIPING FOR THEDATA CENTER AND BUILDING.

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

BA

NORTH

Rev

isio

ns

5/8

/2017 4

:29:0

0 P

M

C:\R

evit\1

0-1

6206-0

0_E

L_2016_C

entr

al_

ekam

in.r

vt

10-1

6206-0

1

3/2

9/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

LIG

HT

ING

PLA

N, LO

WE

R L

EV

EL -

AR

EA

BE

1.0

B

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

LIGHTING PLAN, LOWER LEVEL - AREA B

KEYED NOTES

KEY

VALUE KEY TEXT

L8 3-WAY SWITCH CONTROLS ALL FIXTURES IN ROOM 031.

L13 HOMERUN TO SPARE 20A/1P BREAKER IN PANEL EM.

L14 SWITCH TO CONTROL ALL FIXTURES IN CORRIDOR 001,022, 023, AND 041.

L15 COORDINATE TIMING OF THE INSTALLATION OF ALLELECTRICAL RACEWAYS AND EQUIPMENT IN DENOTEDAREA WITH THE MECHANICAL AND ELECTRICAL WORK OFPHASE 2 CONSTRUCTION.

Page 50: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

T

T

T

T

T

T T

T

T

T

T

S

17A

16B

15A 14B

28B

27

26

20

21

28A

16A

34

17B

15B 14A

C

J

J

J

J

J

J

J

S

S SS

S

A

A

GB

GD

GE GF

XFMR G

GH

GL

GC

MCP

RECORDSSTORAGE

007

CART STORAGE

004

MECHANICAL

009

RECEPTION

006

OFFICE

010

CONFERENCE

012

PRE-PRESS/DIGITALGRAPHICS

016

OPEN OFFICE

008

CORRIDOR

001

SECUREDPRINT

020

COLOR COPY

019

SECUREDSTORAGE

021

GA1HALL

005

MA

TC

HLI

NE

- A

RE

A A

MA

TC

HLI

NE

- A

RE

A B

OFFICE

014

OFFICE

018

E4

E6

GA2

E7

E2

EF-A009

AHU-A009POWER POLE

POWER POLE

FILES

008C

OFFICE

011

OFFICE

015

78"30

78"30

L14-30R32,34

E6.1

32

CIRCUIT ELECTRICALDEVICES THIS ROOMTO PANEL GA1.

30

30

19

DOCUTEC - 19DOCUTEC - 10

DOCUTEC - 9

GA2 - 4

GA2 - 2

GA2 - 12

GA2 - 6

GA2 - 16

GA2 - 14

GA1 - 22

GA1 - 10

GA1 - 8

GA1 - 20

H-A009

GA1 - 11

GA1 - 9

GA1 - 5

GA1 - 13

GA1 - 3 GA1 - 28

OFFICE

008ASCHED.

017

HALL

008B

CART STORAGE

002

ELEC/DATA

003

XFMRDOCUTEC

GA1 - 36

GA2 - 18

GA2 - 8

GA2 - 10

GA1 - 23

DOCUTEC

E13

E7

E14

E15

GA1 - 7

MA

TC

HLI

NE

- A

RE

A A

MA

TC

HLI

NE

- A

RE

A B

60"

E16

36"

E17

E18

GA1 - 15

60"

POWER NOTES(TYPICAL ALL POWER SHEETS)

1. LOCATE SWITCHES FOR CONTROL OF FANS AND LIGHTS IN 2-GANGBOXES WITH LIGHT SWITCH WHERE APPLICABLE. PROVIDE A DIVIDERWITHIN BOX AS NECESSARY.

2. VERIFY OWNER'S PREFERENCE FOR PANEL DIRECTORIES.DIRECTORIES SHALL REFLECT OWNER'S NUMBERING SCHEME AND NOTTHE ARCHITECTURAL NUMBERING SCHEME. OBTAIN REQUIRED INPUTFROM OWNER PRIOR TO FABRICATION OF TYPED PANEL DIRECTORIES.

3. PROVIDE MINIMUM OF 24-INCHES SEPARATION BETWEEN BOXESLOCATED BACK-TO-BACK AT ALL FIRE-RATED WALLS.

4. PROVIDE POWER FROM DESIGNATED 20/1P BREAKER IN NEARESTPANEL TO EACH SMOKE DAMPERS IN AREA. WIRE THRU FIRE ALARMSYSTEM RELAYS.

5. SEE SCHEDULE SHEETS FOR CONNECTIONS TO ALL MECHANICALEQUIPMENT, INCLUDING DISCONNECTS & STARTERS PROVIDED BYDIVISION 26. COORDINATE MOUNTING OF DISCONNECTS AND STARTERSWITH SURROUNDING EQUIPMENT AND PROVIDE ADEQUATECLEARANCES AS REQUIRED BY NEC.

6. SEE MECHANICAL AND PLUMBING DRAWINGS TO CONFIRMLOCATIONS OF ALL HVAC EQUIPMENT, WATER HEATERS, PUMPS,EXHAUST FANS, DAMPERS, THERMOSTATS, HUMIDISTATS, SENSORS,CONTROL DEVICES, CONTROL PANELS, ETC.

PRINT EQUIPMENT GENERAL NOTES:1. COORDINATE FINAL ELECTRICAL ROUGH-INS WITH OWNER.2. REUSE EXISTING CONNECTIONS TO PRINT EQUIPMENT

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

BA

NORTH

Rev

isio

ns

5/8

/2017 4

:29:0

3 P

M

C:\R

evit\1

0-1

6206-0

0_E

L_2016_C

entr

al_

ekam

in.r

vt

10-1

6206-0

1

3/2

9/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

PO

WE

R P

LA

N, LO

WE

R L

EV

EL -

AR

EA

AE

2.0

A

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

POWER PLAN, LOWER LEVEL - AREA A

KEYED NOTES

KEY

VALUE KEY TEXT

E2 PROVIDE JUNCTION BOX EXTENSION WHERE STUDWALLS ARE BEING CONSTRUCTED OVER EXISTING WALLSTO ALLOW DEVICE TO BE LOCATED IN EXISTINGLOCATION.

E4 REROUTE CONDUIT ON WALL TO ALLOW NEW DUCT TO BEEXHAUSTED THROUGH WALL. SEE MECHANICALDRAWINGS FOR EXACT LOCATION OF DUCT. COORDINATEWITH MECHANICAL CONTRACTOR.

E6 NEW PANEL GA. EXTEND EXISTING FEEDER AND BRANCHCIRCUITS.

E7 PROVIDE (4)- 3/4" SPARE CONDUIT TO ABOVE APC.

E13 NEW PANEL DOCUTEC. EXTEND EXISTING FEEDER ANDBRANCH CIRCUITS.

E14 RELOCATED PENDANT RECEPTACLE.

E15 SEE MECHANICAL PLANS FOR RELOCATION OFHUMIDIFIER. EXTEND ELECTRICAL CONNECTION TO UNIT.

E16 CIRCUIT LOCAL DOOR LOCKS IN AREA A TO SPARE 20A/1PBREAKER IN DOCUTEC PANEL. COORDINATE ABOVECEILING LOCATION WITH OWNER SECURITYCONTRACTOR.

E17 INSTALL SALVAGED DOOR BELL AND BUZZER.

E18 RELOCATE EXISTING DUPLEX IF NECESSARY FORINSTALLATION OF NEW DOOR.

PRINT EQUIPMENT CONNECTION SCHEDULE

MARK NO. DESCRIPTION VOLTAGE POLES

RECEPTACLE/

DISCONNECT

EQUITMENT

CIRCUIT SIZE

MOUNTING

HEIGHT PANEL

CIRCUIT

NUMBER NOTES

14A XEROX DOCPRINT 135 208 V 2 NEMA 6-50R 6 - 10 - 3/4" DOCUTEC 11,13

14B XEROX DOCPRINT 135 208 V 2 NEMA 6-50R 6 - 10 - 3/4" DOCUTEC 15,17

15A XEROX DOCUTECH 180 208 V 2 NEMA 6-30R 10 - 10 - 1/2" DOCUTEC 2,4

15B XEROX DOCUTECH 180 208 V 2 NEMA 6-50R 6 - 10 - 3/4" DOCUTEC 6,8

16A XEROX NUVERA 288 208 V 2 NEMA 6-50R 6 - 10 - 3/4" DROP CORD DOCUTEC 12,14

16B XEROX NUVERA 288 208 V 2 NEMA 6-50R 6 - 10 - 3/4" DROP CORD DOCUTEC 16,18

17A XEROX DOCUTECH 180 HLC 208 V 2 NEMA 6-30R 10 - 10 - 1/2" DOCUTEC 1,3

17B XEROX DOCUTECH 180 HLC 208 V 2 NEMA 6-50R 6 - 10 - 3/4" DOCUTEC 5,7

20 XEROX 700i 208 V 2 NEMA 6-20R 12 - 12 - 1/2" DOCUTEC 25,27

21 EPSON STYLUS PRO 9900 208 V 2 NEMA 6-20R 12 - 12 - 1/2" DOCUTEC 21,23

26 AB DICK DPM 2000 208 V 2 NEMA 6-15R 12 - 12 - 1/2" GA1 2,4

27 MITSUBISHI VDP CF3070 208 V 2 NEMA 6-20R 12 - 12 - 1/2" GA1 12,14

28A AGFA ACENTO IIE 208 V 2 NEMA 6-20R 12 - 12 - 1/2" GA1 16,18

28B AGFA AZURA C85 208 V 2 NEMA 6-15R 12 - 12 - 1/2" GA1 24,26

34 EPSON SURECOLOR 120 V 1 NEMA 5-20R 12 - 12 - 1/2" GA1 6

Page 51: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

FSFS

S

S

T

T

T

T T T

S

J

J

J

J

J

J

A S

EM

FUTURE 750kVA UPS-B

CART STORAGE

022A

HALL

023

WOMEN'S

024

MEN'S

025

JAN

026BREAK ROOM

027

FUTURE UPS

028

ELECTRICAL

029

CORRIDOR

041

CORRIDOR

022

60"

42" 42" 42"

BB1

60"

MA

TC

HLI

NE

- A

RE

A A

MA

TC

HLI

NE

- A

RE

A B

EXISTING 750kVA UPS

E5

60"

LAB

LAB - 5 LAB - 3 LAB - 1

42" 42"

42"

42"

42"

42"

42"

42"

MASTER GROUNDBAR

E10

E11

BB1 - 9 BB1 - 11 BB1 - 13

BB1 - 27

BB1 - 19

BB1 - 23

BB1 - 21

BB1 - 15

BB1 - 25

BB1 - 17

BB1 - 14

BB1 - 12

BB1 - 16

BB1 - 10

LAB - 7

BB1 - 20

BB1 - 18

BB1 - 22

FUTURE

031

MA

TC

HLI

NE

- A

RE

A A

MA

TC

HLI

NE

- A

RE

A B

EWC

E19E19

BB1 - 26

E19

MLB

BB1 - 24

E9

E12

E12

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

BA

NORTH

Rev

isio

ns

5/8

/2017 4

:29:0

6 P

M

C:\R

evit\1

0-1

6206-0

0_E

L_2016_C

entr

al_

ekam

in.r

vt

10-1

6206-0

1

3/2

9/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

PO

WE

R P

LA

N, LO

WE

R L

EV

EL -

AR

EA

BE

2.0

B

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

KEYED NOTES

KEY

VALUE KEY TEXT

E5 NEW PANEL BB. EXTEND EXISTING FEEDER AND BRANCHCIRCUITS TO NEW LOCATION FROM ABOVE APC.

E9 NEW CONCRETE ENCASED GROUNDING ELECTRODE.BOND TO REBAR AND ROUTE #3/0 TO MASTER GROUNDBUS BAR IN ROOM 029.

E10 DOOR CHIME. LOCATE TRANSFORMER ABOVE APC.MOUNT AT 84" AFF.

E11 SWITCHGEAR INSTALLED AND CONNECTED UNDER BIDPACKAGE #2 SERVICES AND GENSET CONDUITS ANDCONDUCTORS UNDER BID PACKAGE #2.

E12 POWER FOR AUTOMATIC FAUCET AND SOAPDISPENSERS. COORDINATE FINAL LOCATION WITHAPPROVED SUBMITTAL.

E19 CIRCUIT LOCAL DOOR LOCKS IN AREA B TO SPARE 20A/1PBREAKER IN LAB PANEL. COORDINATE ABOVE CEILINGLOCATION WITH OWNER SECURITY CONTRACTOR.

NORTHSCALE: 1/8" = 1'-0"

POWER PLAN, LOWER LEVEL - AREA B

Page 52: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

SS

D

DC

R

P

PD

PD

P

AP

AP

AP

AP

AP

AP

AP

AP

P

P

P

P

PP

AP

FC 75

FC

75

FC

75

FC

75

FC

75

FC

15F

C

15

FC

15

FC

30

FC

75

F

75

FC

15

FC

30

FC

30F

C

15

P

P

P

P

P

P

P

P

P

P

FC

30

CR

CR

CR

PD

PD

D

D

C

CR

P

CR

J

J

J

J

J

J

J

S

S SS

S

A

A

R

P

0, 2, 0

0, 2, 0

0, 2, 0

RECORDSSTORAGE

007

CART STORAGE

004

MECHANICAL

009

RECEPTION

006

OFFICE

010

CONFERENCE

012

PRE-PRESS/DIGITALGRAPHICS

016

OPEN OFFICE

008

CORRIDOR

001

SECUREDPRINT

020

COLOR COPY

019

SECUREDSTORAGE

021

HALL

005

E6.1

42

E6.1

41

S4

MA

TC

HLI

NE

- A

RE

A A

MA

TC

HLI

NE

- A

RE

A B

0, 1, 0

0, 2, 0 0, 2, 0

OFFICE

014

OFFICE

008A

OFFICE

018

0, 2, 0

0, 2, 0

0, 1, 0

0, 1, 0

0, 1, 0

0, 2, 0

0, 2, 0

0, 2, 0

0, 2, 0

0, 2, 0

0, 2, 0

0, 2, 0

0, 2, 0

0, 2, 060"

S3

1, 0, 0

1, 0, 0

1, 0, 0

FILES

008C

HALL

008B

OFFICE

011

OFFICE

015

0, 2, 0

0, 2, 00, 1, 0

0, 1, 0

0, 1, 0 0, 1, 0 0, 1, 0 0, 1, 0

0, 1, 0

0, 1, 0

0, 1, 0

0, 1, 0

0, 1, 0

0, 1, 0

0, 2, 0

12" CABLE TRAY

12" CABLE TRAY

S10

SU

PP

LY

RE

TU

RN

S11

0, 2, 0

0, 2, 0

0, 2, 0

S12

S12S12

MA

TC

HLI

NE

- A

RE

A A

MA

TC

HLI

NE

- A

RE

A B

S15 S16

S17

0, 2, 00, 2, 060"

SPECIAL SYSTEMS NOTES(TYPICAL ALL SPECIAL SYSTEMS SHEETS)

1. OUTLETS FOR TELECOM, FIRE ALARM, SECURITY, ACCESSCONTROL, AND ALL OTHER LOW VOLTAGE CABLING: PROVIDEINSULATED BUSHINGS ON ALL CONDUIT STUB-UPS, INCLUDING UNUSEDSTUB-UPS OR STUB-UPS INDICATED FOR FUTURE USE.

2. SLEEVES FOR LOW VOLTAGE CABLES: PROVIDE SLEEVES PERSECTION 270500. COORDINATE WITH PATH OF DUCTWORK AND PIPESTO ENSURE ACCESSIBILITY. INSTALL ALL SLEEVES 12" ABOVE HIGHERCEILING OF TWO ADJACENT SPACES (REFER TO ROOM FINISHSCHEDULES AND REFLECTED CEILING PLANS FOR CEILING HEIGHTS).STUB SLEEVES INTO JOIST SPACE OF FINISHED ROOMS WITH EXPOSEDSTRUCTURE. PROVIDE INSULATED BUSHINGS ON BOTH ENDS OF EMTSLEEVES, INCLUDING UNUSED SLEEVES. PROVIDE GROUT TO SECURESLEEVES TO WALL. FIRESTOP AT ALL FIRE-RATED WALLS WHEREREQUIRED FOR UL LISTING OF FIRE-RATED WALL CABLE PATHWAYASSEMBLY.

3. COMMUNICATIONS OUTLET RACEWAYS SHALL BE ROUTED UP WITHSWEEP BENDS UNLESS SHOWN AS UGC.

4. EXPOSED CABLES IN FINISHED SPACES: PROVIDE 3/4 INCH MINIMUMCONDUIT FOR ALL LOW-VOLTAGE CABLES IN EXPOSED STRUCTUREAREAS. PAINT ALL CONDUIT, BOXES, AND ASSOCIATED MOUNTINGHARDWARE TO MATCH ADJACENT FINISHES.

5. CABLE TRAY SHALL BE INSTALLED OVER/UNDER OR AROUNDOBSTRUCTIONS TO MAINTAIN ACCESS AND CLEARANCES. SIDES OFCABLE TRAY SHALL NOT BE CUT TO REDUCE HEIGHT. PROVIDEEQUIVALENT SIZED SLEEVES WHERE CABLE TRAY CAN NOT BEINSTALLED WITH CLEARANCES SPECIFIED. SEE SECTION 270528.36.

6. INSTALL SLEEVES FOR INSTALLATION OF ALL LOW VOLTAGECABLING. FOLLOW INDUSTRY STANDARDS TO MAINTAIN 40% FILLREQUIREMENTS IN ALL SLEEVES. PROVIDE ADDITIONAL SLEEVES(MEETING REQUIREMENTS) AS REQUIRED.

7. ROUTE ALL LOW VOLTAGE CABLING INSTALLED IN LOCATIONS WITHNO CEILINGS (EXPOSED STRUCTURE) IN MINIMUM 3/4" CONDUIT TOACCESSIBLE SPACE ABOVE NEAREST LAY-IN CEILING.

8. DO NOT INSTALL CABLES ABOVE STRUCTURAL MEMBERS IN ROOFDECK SPACES.

9. CABLE TRAY AND SLEEVES SHALL BE FIRESTOPPED AND SMOKESTOPPED THROUGH FIRE/SMOKE-RATED WALLS PER MFR'SRECOMMENDATIONS AND MATERIALS SPECIFIED IN DIVISION 7. USEREMOVABLE PILLOWS OR NON-HARDENING PUTTY.

12. S OR FS - SMOKE OR FIRE/SMOKE DAMPER SYMBOL.PROVIDE CONNECTION TO FIRE ALARM SYSTEM. PROVIDE FA RELAY ANDDUCT DETECTOR WITH REMOTE INDICATOR LAMP AND TEST SWITCHFOR ACTUATION OF DAMPER. DETECTION AND ACTUATION SHALL BECOMPLIANT WITH IBC 2012 SECTION 717.3.3 TYPICAL FOR EACH DAMPERSHOWN.

13. PROVIDE RELAY(S) FOR FAN SHUTDOWN OF MECHANICALEQUIPMENT WITHIN 3FT OF EACH MECH UNIT. (REFER TO HVAC PLANSFOR EQUIPMENT LOCATION AND DUCTS). COORDINATE EFFORT WITHDIVISION 23.

14. FIRE ALARM SYSTEM SHALL CONNECT DIRECTLY TO MECHANICALUNITS SHOWN ON SCHEDULE AND SHUT-DOWN CORRESPONDING UNITSUPON ACTIVATION OF COMMON DUCTED DETECTION AS SPECIFIED.

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

BA

NORTH

Rev

isio

ns

5/8

/2017 4

:29:0

9 P

M

C:\R

evit\1

0-1

6206-0

0_E

L_2016_C

entr

al_

ekam

in.r

vt

10-1

6206-0

1

3/2

9/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

SP

EC

IAL S

YS

TE

MS

PLA

N, LO

WE

R L

EV

EL -

AR

EA

AE

3.0

A

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

SPECIAL SYSTEMS, LOWER LEVEL - AREA A

KEYED NOTES

KEY

VALUE KEY TEXT

S3 ALL HARDWARE AND CABLING TO BE OWNER PROVIDEDAND INSTALLED. WIRELESS ACCESS POINTS ARE SHOWNFOR REFERENCE ONLY.

S4 J HOOKS TO SUPPORT EXISTING COMMUNICATIONCABLES TO REMAIN. SUPPORT J HOOKS FROMSTRUCTURE.

S10 ROUGH-IN ONLY (TYPICAL).

S11 (5) - 2" C WITH BUSHINGS

S12 (2) - 2" C WITH BUSHINGS

S15 REINSTALL SALVAGED SPEAKER (TYPICAL).

S16 REINSTALL SALVAGED ANTENNA (TYPICAL).

S17 FIRE/SMOKE DAMPER CONTROLS (TYPICAL).

Page 53: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

FSFS

S

S

S

CR

D

D

D

CR

D

CR

CR

CR

F

75

F

15

F

15

F

15

F

15

F

30

F

15

F

F

30

F

30

F

30

15

F

F

75

SN

AC

F

P

P PP

PPP

P

P

P

P

PPP

P

P

P

P

P

P

P

P

P P

P

AP

AP

AP

AP

APAP

P

P

P

P

P

P

P

P

CR

J

F

30

FC

75

FC

75

FC

75F

C

75

FC

75

FC

30

F

30

F

30

FC

15F

C

15

FC

15

FC

15

FC

15

FC

15

FC

15

FC

15

R

D

F

FC

15

FC

15

FC

75

P

P

FC

15

J

J

J

J

J

A S

E6.1

43

E6.1

44

S4

MA

TC

HLI

NE

- A

RE

A A

MA

TC

HLI

NE

- A

RE

A B

0, 4, 0

0, 4, 0

S3

S2

CART STORAGE

022A

HALL

023

WOMEN'S

024

MEN'S

025

JAN

026

BREAK ROOM

027

FUTURE UPS

028

ELECTRICAL

029

CORRIDOR

041

CORRIDOR

022

0, 1, 0

0, 2, 060"

0, 2, 060"

12" CABLE TRAY

S9

S13

S14

FUTURE

031

MA

TC

HLI

NE

- A

RE

A A

MA

TC

HLI

NE

- A

RE

A B

S15S16

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

KEY PLAN

BA

NORTH

Rev

isio

ns

5/8

/2017 4

:29:1

0 P

M

C:\R

evit\1

0-1

6206-0

0_E

L_2016_C

entr

al_

ekam

in.r

vt

10-1

6206-0

1

3/2

9/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

SP

EC

IAL S

YS

TE

MS

PLA

N, LO

WE

R L

EV

EL -

AR

EA

BE

3.0

B

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

NORTHSCALE: 1/8" = 1'-0"

SPECIAL SYSTEMS, LOWER LEVEL - AREA B

KEYED NOTES

KEY

VALUE KEY TEXT

S2 SALVAGED PHOTOELECTRIC DETECTOR FORREINSTALLATION. TYPICAL UNO.

S3 ALL HARDWARE AND CABLING TO BE OWNER PROVIDEDAND INSTALLED. WIRELESS ACCESS POINTS ARE SHOWNFOR REFERENCE ONLY.

S4 J HOOKS TO SUPPORT EXISTING COMMUNICATIONCABLES TO REMAIN. SUPPORT J HOOKS FROMSTRUCTURE.

S9 FIRE ALARM RELAY FOR CONNECTION TO SMOKEACTIVATED HORIZONTAL SLIDING WINDOW. LOCATERELAY ABOVE APC AND CONNECT TO WINDOW CLOSER.PROGRAM TO CLOSE BY AREA DETECTION ON EITHERSIDE OF OPENING.

S13 (3) - 2" C WITH BUSHINGS. COORDINATE PENETRATIONWITH EXISTING SLEEVES INTO DATA ROOM.

S14 (4) - 4" C. COORDINATE ELEVATION WITH FUTURE PHASE 2CONCRETE ENCASED DUCT BANK LOCATED ABOVECEILING.

S15 REINSTALL SALVAGED SPEAKER (TYPICAL).

S16 REINSTALL SALVAGED ANTENNA (TYPICAL).

Page 54: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

UTIL XFRM-X12470/480 3PH1000KVA; 3%Z; 36.5KAICXFMR VAULT

1600AF

MSB-X, ELECTRICAL ROOM480/277V 1600A, 3PH, 4W32 KAIC

G

GENERATOR700 KW, 277/480 3PH, 4W

PANEL1B

PANELBB

PANEL2B

PANEL3B

PANEL4B

PANELAB

MOTOR CONTROL CENTER, MCB600A, 480VMAIN ELECTRICAL ROOMSQUARE D, MODEL 5

DISTRIBUTION PANEL, MX1600A, 480V, 30KAICMAIN ELECTRICAL ROOM

E.ELEVATOR

DISTRIBUTION PANEL, 1CA600A, 480V, 18KAIC1ST FLOOR ELEC ROOM

DISTRIBUTION PANEL MLX800A, 120/208V, 65KAICMAIN ELECTRICAL ROOM

DISTRIBUTION PANEL 2CA600A, 480V, 18KAIC2ND FLOOR ELEC ROOM

MOTOR CONTROL CENTER, MCX600A, 480V, 30KAICMAIN ELECTRICAL ROOM

XFMR-MLX480-208Y/120V

225 KVA

1600

AF

600A

450A

F

SPARESPARESPARESPARESPARE

FREIGHTELEVATOR

SPARE

WESTELEVATOR

400A

F

200A

F

UTIL XFMR-B12470/480 3PH1000KVA; 3%; 36.5KAICXFMR VAULT

GEN. PANEL

MOTOR CONTROL CENTER, MCG600A, 480VMAIN ELECTRICAL ROOM

XFMR-EM480-208Y/120V

30 KVA

PANELEM

ATS-1200A3P

ATS-21600A3P

MTS-X600A3P

DISTRIBUTION PANEL, GH400A, 480V, 25KAICPRINT SHOP

XFMR-G480-208Y/120V225 KVA

DISTRIBUTION PANEL, GL800A, 120/208V, 22KAICPRINT SHOPSQUARE D, I-LINE

PANELGF

PANELGA

PANELGE

PANELGB

PANELGD

PANELGC

100A

100A

100A

100A

200A

200A

200A

200A

1600

AF

200A480VFUSED @200A

DISTRIBUTION PANEL 1CP600A, 480V, 18KAIC1ST FLOOR ELECTRICAL ROOMSQUARE D, I-LINE

XFMR-2MPU480-208Y/120V300 KVA

PANEL 2MPU1200A, 208V, 22KAIC2ND FLOOR ELEC. RM.SQUARE D, I-LINE

PDU8150kVA(3)-84 POLE1ST FLOOR DATACENTER

PDU9150kVA(3)-84 POLE1ST FLOOR DATACENTER

DISTRIBUTION PANEL 2CP600A, 480V, 18KAIC2ND FLOOR ELECTRICAL ROOMSQUARE D, I-LINE

CPU4CA

CPU3CA

POWER PANEL UX1200A, 277/480V, 30KAICUPS ROOM

UPS-A750 KVA

SS

2500A

2500A

1200

A

600A

1200

A

600A

POWER PANEL BP1200A, 277/480V, 30KAICUPS ROOM

DOCUTECPANEL

XFMR-DOCUTECH480-208Y/120V

75 KVA

1200

A

1200

A

1200

A

MSB-B, ELECTRICAL ROOM480/277V 1600A, 3PH, 4W32 KAIC

225A42 POLE

225A42 POLE

225A84 POLE

225A42 POLE

225A84 POLE

225A84 POLE

225A42 POLE

225A42 POLE

200A

225A

200A

200A

200A

225A

200A

200A

200A

225ASPACE

350A

50A

30A

15A

60A

110A

60A

3A7A 15A

400A

50A

225A

50A

125A

225A

225A

225A

15A

20A

20A

30A

60A

30A

150A

50A

400A

200A

200A

200A

200A

200A

200A

225ASPACE

80A

50A

50A

40A

40A

200A

350A

HEIDELBERGSPEEDMASTER

100ASPACE

225ASPACE

100A

100A

400A

400A

600A 400A

SPACE 400A

600A

1200

A

600A

50A

50A

225A

100ASPACE

100ASPACE

AHU-2(SF-2)

AHU-2(RF-2)

SEWAGEEJECTOR

SUMPPUMP

ENGR.LIEBERT AC

1600AF1200AT

225ASPACE

225ASPACE

SPARE

225A84 POLE

CHILLERC-1B

PUMPCP-1B

PUMPCWP-1B

PUMPHWP-1B

COOLINGTOWERCT-1B

AHU-1(SF-1)

AHU-1(RF-1)

EX. FANEF-2

EX. FANEF-1

SPARE

TEMP.CHILLER

PUMP

TEMP.CHILLER

400ASPACE

SPARE

TEMP.CONTROLAIR COMP.

SPARE

PUMPHWP-1A

COOLINGTOWERCT-1A

PUMPCWP-1A

PUMPCP-1C

PUMPCP-1A

CHILLERC-1A

225ASPACE

225ASPACE

600kWBATT. CABS

100ASPACE

LESUTILITY

LESUTILITY

1600ATIE

MLB-1 MLB-2 MLB-3 MLB-4 MLB-5 MLB-6 MLB-7 MLB-8 MLB-9 MLB-10 MLB-11 MLB-12MCB-1 MCB-2 MCB-3 MCB-4 MCB-5 MCB-6 MCB-7 MCB-8 MCB-9 MCB-10

2CP-1 2CP-2 2CP-3 2CP-4 2CP-5 2CP-6 2CP-7 2CP-8 1CP-51CP-41CP-31CP-21CP-1

MCX-1

GL-1 GL-2 GL-3 GL-4 GL-5 GL-6 GL-7 GL-8 GL-9 GL-10

MCP-1 MCP-2 MCP-3 MCP-4 MCP-5 MCP-6

MCG-3 MCG-2 MCG-1 GH-2 GH-1 GH-3 GH-4 GH-5

MX-1 MX-2 MX-3 MX-4 MX-5 MX-9 MX-10 MX-6 MX-7 MX-11 MX-8

BP-3BP-2 BP-1

100A30 POLE

200A

S

400A

S

1600

AS

600A

S

600A

S

15A

MCG-4

7A

MCG-5

20A

MCG-6

NEMA-2 NEMA-1

NEMA-2 NEMA-2

NEMA-1NEMA-1 NEMA-2NEMA-2

MCX-2 MCX-3 MCX-4 MCX-5 MCX-6 MCX-8 MCX-9 MCX-10MCX-7

SPARE SPARE

PANELBX

PANEL1X

PANEL2X

PANEL3X

PANEL4X

PANEL4HX

100A18 POLE

225A42 POLE

100A12 POLE

150A

150A

150A

150A

150A

200A

225A42 POLE

225A42 POLE

225A42 POLE

SPARE

MLX-9MLX-8MLX-7MLX-6MLX-5MLX-4

150A

225A42 POLE

225A42 POLE

225A42 POLE

225A42 POLE

UX-2

UX-1 UX-3

UX-4

SPARE

30A

1CP-6

225A

225A

225A

2MPU-1

225A

2MPU-2

225A

2MPU-3

225A

2MPU-4

225A

2MPU-5

225A

2MPU-6

SPARE SPARE

SOUTH9027

SOUTH9027

TEMP.PORT.

COOLERS

100ASPACE

MCP-6

40A

HUMIDIFIERH-1

2000 GAL.UNDERGROUNDFUEL TANK

200 400 1600

600

450

600

1600

250A/3 250A/3

PDU1150kVA(3)-84 POLE1ST FLOOR DATACENTER

250A/3

PDU3150kVA(3)-84 POLE2ND FLOOR DATACENTER

250A/3

PDU2150kVA(3)-84 POLE2ND FLOOR DATACENTER

250A/3

PDU 4B150kVA(3)-84 POLE2ND FLOOR DATACENTER

250A/3

150A80A

80A

80A

80A

1CA-1

80A

80A

80A

80A

50A

50A

1CA-2 1CA-3 1CA-4 1CA-5 1CA-6

20A

1CA-7

2CA-1 2CA-2 2CA-3 2CA-4 2CA-5 2CA-6 2CA-7

80A

80A

80A

80A

80A

2CA-8 2CA-9 2CA-10 2CA-11

CRAHUNIT 3

AC 1 CRAHUNIT 1

CRAHUNIT 4

80A

2CA-12

CHIL 2 CHIL 1 AC 11 AC 12 AC 5 AC 9AC 10 AC 6 AC 8 AC 7

BUSS

80A

1CA-9

CRAHUNIT 2

2CA-13

25A

2CA-14

REHEAT FORCONSOLE

AREA

2CA-15

25A

2CA-16

REHEAT FOROFFICES

SPACE SPACE

225ASPACE

225ASPACE

O2

O2

SPARE

PDU4150kVA(3)-84 POLE2ND FLOOROFFICE

250A/3

O3

O2

O1

MOTOR CONTROL CENTER, MCP600A, 480V, 25KAICAHU ROOMSQUARE D, MODEL 5

RADIATORFAN

EX. FANEF-5

FAN COILUNIT FCU-1

BOOSTERPUMP BP-1

DISTRIBUTION PANEL, MLB1200A, 120/208V, 22KAICMAIN ELECTRICAL ROOMSQUARE D, QED

XFMR-B480-208Y/120V300 KVA

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

Rev

isio

ns

5/8

/2017 4

:29:1

3 P

M

C:\R

evit\1

0-1

6206-0

0_E

L_2016_C

entr

al_

ekam

in.r

vt

10-1

6206-0

1

3/2

9/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

DE

MO

ON

E-L

INE

DIA

GR

AM

E5.1

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

KEYED NOTES

KEY

VALUE KEY TEXT

O1 SEE SHEET DE1.0A FOR RELOCATION OF HUMIDIFIER.EXTEND ELECTRICAL CONNECTION TO UNIT AS NOTEDON SHEET E2.0A.

O2 EXISTING PANELBOARD TO BE DEMOLISHED. FEEDERSAND BRANCH WIRING TO BE EXTENDED TO NEWLOCATION.

O3 COORDINATE DEMOLITION WITH MECHANICALDRAWINGS.

SCALE: 12" = 1'-0"

DEMO ELECTRICAL ONE-LINE DIAGRAM

Page 55: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

UTIL XFRM-X12470/480 3PH1000KVA; 3%Z; 36.5KAICXFMR VAULT

1600AF

MSB-X, ELECTRICAL ROOM480/277V 1600A, 3PH, 4W32 KAIC

G

GENERATOR700 KW, 277/480 3PH, 4W

DISTRIBUTION PANEL, MLB1200A, 120/208V, 22KAICMAIN ELECTRICAL ROOMSQUARE D, QED

PANEL1B

PANELBB

PANEL2B

PANEL3B

PANEL4B

PANELAB

XFMR-B480-208Y/120V300 KVA

MOTOR CONTROL CENTER, MCB600A, 480VMAIN ELECTRICAL ROOMSQUARE D, MODEL 5

E.ELEVATOR

DISTRIBUTION PANEL MLX800A, 120/208V, 65KAICMAIN ELECTRICAL ROOM

MOTOR CONTROL CENTER, MCX600A, 480V, 30KAICMAIN ELECTRICAL ROOM

XFMR-MLX480-208Y/120V

225 KVA

1600

AF

600A

450A

F

SPARESPARESPARESPARESPARE

FREIGHTELEVATOR

SPARE

WESTELEVATOR

400A

F

200A

F

UTIL XFMR-B12470/480 3PH1000KVA; 3%; 36.5KAICXFMR VAULT

GEN. PANEL

MOTOR CONTROL CENTER, MCG600A, 480VMAIN ELECTRICAL ROOM

XFMR-EM480-208Y/120V

30 KVA

PANELEM

ATS-1200A3P

ATS-21600A3P

MTS-X600A3P

DISTRIBUTION PANEL GH400A, 480VPRINT SHOP

XFMR-G480-208Y/120V225 KVA

PANELGF

PANELGA1

PANELGE

PANELGB

PANELGD

PANELGC

100A

100A

100A

100A

200A

200A

200A

200A

1600

AF

200A480VFUSED @200A

XFMR-2MPU480-208Y/120V300 KVA

PDU8150kVA(3)-84 POLE1ST FLOOR DATACENTER

PDU9150kVA(3)-84 POLE1ST FLOOR DATACENTER

DISTRIBUTION PANEL 2CP600A, 480V, 18KAIC2ND FLOOR ELECTRICAL ROOM

CPU4CA

CPU-4 CPU3CA

POWER PANEL UX1200A, 277/480V, 30KAICUPS ROOM

UPS-A750 KVA

SS

2500A

2500A

1200

A

600A

1200

A

600A

POWER PANEL, BP1200A, 277/480V, 30KAICUPS ROOM

MOTOR CONTROL CENTER, MCP600A, 480V, 25KAICAHU ROOMSQUARE D, MODEL 5

DOCUTECPANEL

XFMR-DOCUTEC480-208Y/120V

75 KVA

1200

A

1200

A

1200

A

MSB-B, ELECTRICAL ROOM480/277V 1600A, 3PH, 4W32 KAIC

225A42 POLE

225A42 POLE

225A84 POLE

225A42 POLE

225A84 POLE

225A84 POLE

225A42 POLE

200A

225A

200A

200A

200A

225A

200A

200A

200A

225ASPACE

350A

50A

30A

15A

60A

110A

60A

3A7A 15A

400A

50A

225A

50A

125A

225A

225A

225A

15A

20A

20A

30A

60A

30A

150A

50A

400A

200A

200A

200A

200A

200A

200A

225ASPACE

80A

50A

50A

40A

50A

200A

350A

HEIDELBERGSPEEDMASTER

100ASPACE

225ASPACE

100A

100A

400A

400A

600A 400A

SPACE 400A

600A

1200

A

600A

50A

50A

225A

100ASPACE

100ASPACE

AHU-2(SF-2)

AHU-2(RF-2)

SEWAGEEJECTOR

SUMPPUMP

1600AF1200AT

225ASPACE

225ASPACE

SPARE

225A84 POLE

CHILLERC-1B

PUMPCP-1B

PUMPCWP-1B

PUMPHWP-1B

COOLINGTOWERCT-1B

AHU-1(SF-1)

AHU-1(RF-1)

EX. FANEF-2

EX. FANEF-1

SPARE

TEMP.CHILLER

PUMP

TEMP.CHILLER

400ASPACE

SPARE

TEMP.CONTROLAIR COMP.

SPARE

PUMPHWP-1A

COOLINGTOWERCT-1A

PUMPCWP-1A

PUMPCP-1C

PUMPCP-1A

CHILLERC-1A

225ASPACE

225ASPACE

600kWBATT. CABS

100ASPACE

RADIATORFAN

LESUTILITY

LESUTILITY

1600ATIE

MLB-1 MLB-2 MLB-3 MLB-4 MLB-5 MLB-6 MLB-7 MLB-8 MLB-9 MLB-10 MLB-11 MLB-12MCB-1 MCB-2 MCB-3 MCB-4 MCB-5 MCB-6 MCB-7 MCB-8 MCB-9 MCB-10

2CP-1 2CP-2 2CP-3 2CP-4 2CP-5 2CP-6 2CP-7 2CP-8 1CP-51CP-41CP-31CP-21CP-1

MCX-1

GL-1 GL-2 GL-3 GL-4 GL-5 GL-6 GL-7 GL-8 GL-9 GL-10

MCP-1 MCP-2 MCP-3 MCP-4 MCP-5 MCP-6

MCG-3 MCG-2 MCG-1 GH-2 GH-1 GH-3 GH-4 GH-5

MX-1 MX-2 MX-3 MX-4 MX-5 MX-9 MX-10 MX-6 MX-7 MX-11 MX-8

BP-3BP-2 BP-1

100A30 POLE

200A

S

400A

S

1600

AS

600A

S

600A

S

15A

EX. FANEF-5

MCG-

7A

FAN COILUNIT FCU-1

MCG-

20A

BOOSTERPUMP BP-1

MCG-

NEMA-2 NEMA-1

NEMA-2 NEMA-2

NEMA-1NEMA-1 NEMA-2NEMA-2

MCX-2 MCX-3 MCX-4 MCX-5 MCX-6 MCX-8 MCX-9 MCX-10MCX-7

SPARE SPARE

PANELBX

PANEL1X

PANEL2X

PANEL3X

PANEL4X

PANEL4HX

100A18 POLE

225A42 POLE

100A12 POLE

150A

150A

150A

150A

150A

200A

225A42 POLE

225A42 POLE

225A42 POLE

SPARE

MLX-9MLX-8MLX-7MLX-6MLX-5MLX-4

150A

225A42 POLE

225A42 POLE

225A42 POLE

225A42 POLE

UX-2

UX-1 UX-3

UX-4

SPARE

30A

1CP-6

225A

225A

225A

2MPU-1

225A

2MPU-2

225A

2MPU-3

225A

2MPU-4

225A

2MPU-5

225A

2MPU-6

SPARE SPARE

SOUTH9027

SOUTH9027

TEMP.PORT.

COOLERS

MCP-7

40A

HUMIDIFIERH-1

2000 GAL.UNDERGROUNDFUEL TANK

200 400 1600

600

450

600

1600

250A/3 250A/3

PDU1150kVA(3)-84 POLE1ST FLOOR DATACENTER

250A/3

PDU3150kVA(3)-84 POLE2ND FLOOR DATACENTER

250A/3

PDU2150kVA(3)-84 POLE2ND FLOOR DATACENTER

250A/3

PDU 4B150kVA(3)-84 POLE2ND FLOOR DATACENTER

250A/3

150A80A

80A

80A

80A

1CA-1

80A

80A

80A

80A

50A

50A

1CA-2 1CA-3 1CA-4 1CA-5 1CA-6

20A

1CA-7

2CA-1 2CA-2 2CA-3 2CA-4 2CA-5 2CA-6 2CA-7

80A

80A

80A

80A

80A

2CA-8 2CA-9 2CA-10 2CA-11

CRAHUNIT 3

AC 1 CRAHUNIT 1

CRAHUNIT 4

80A

2CA-12

CHIL 2 CHIL 1 AC 11 AC 12 AC 5 AC 9AC 10 AC 6 AC 8 AC 7

BUSS

80A

1CA-9

CRAHUNIT 2

2CA-13

25A

2CA-14

REHEAT FORCONSOLE

AREA

2CA-15

25A

2CA-16

REHEAT FOROFFICES

SPACE SPACE

225ASPACE

PANELGA2

225A42 POLE

200A

200

N1

200 225

N1

LAB

225A42 POLE

225

HUMIDIFIERH-A009

40A

AHU-A009

VFD BYDIV 23

N3

225A42 POLE N1

DISTRIBUTION PANEL, 1CA600A, 480V, 18KAIC1ST FLOOR ELEC ROOM

DISTRIBUTION PANEL 2CA600A, 480V, 18KAIC2ND FLOOR ELEC ROOM

DISTRIBUTION PANEL, GH400A, 480V, 25KAICPRINT SHOP

DISTRIBUTION PANEL, GL800A, 120/208V, 22KAICPRINT SHOPSQUARE D, I-LINE

DISTRIBUTION PANEL 1CP600A, 480V, 18KAIC1ST FLOOR ELECTRICAL ROOMSQUARE D, I-LINE

PANEL 2MPU1200A, 208V, 22KAIC2ND FLOOR ELEC. RM.SQUARE D, I-LINE

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

Rev

isio

ns

5/8

/2017 4

:29:1

6 P

M

C:\R

evit\1

0-1

6206-0

0_E

L_2016_C

entr

al_

ekam

in.r

vt

10-1

6206-0

1

3/2

9/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

NE

W O

NE

-LIN

E D

IAG

RA

ME

5.2

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

KEYED NOTES

KEY

VALUE KEY TEXT

N1 EXTEND EXISTING FEEDER AND BRANCH CIRCUITS TOPANELS NEW LOCATION. EXISTING BRANCH CIRCUITS TOBE EXTENDED ARE INDICATED ON PANEL SCHEDULE.

N3 COORDINATE FEEDER ROUTING FROM 2ND FLOOR ELECROOM TWO FLOORS ABOVE EXISTING UPS.

SCALE: 12" = 1'-0"

NEW WORK ELECTRICAL ONE-LINE DIAGRAM

Page 56: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

P

F

75

PP

4"

8"

BACKSPLASH & COUNTERTOP

COUNTERTOPWITHOUTBACKSPLASH

SEE ARCHITECTURALCASEWORK DETAILS

CABLE TRAY TO SLEEVE TRANSITIONSAT EQUAL ELEVATION

STACKED SLEEVESEXAMPLE

HORIZONTALSLEEVES EXAMPLES

CABLE TRAYWIDTH PLUS 4"MAXIMUM

CENTERMOUNTSUPPORT(TYP)

BOLTEDTO WALL

45 DEGMAX

SLEEVES (FIRE/SMOKESEAL AFTER CABLEINSTALLATION

WALL MOUNTSUPPORT (TYP)

BOND CABLE TRAYTHROUGH SLEEVESWITH #6 E.G.C.

CABLE TRAY TO SLEEVE TRANSITIONSWITH ELEVATION CHANGE

2" M

AX

2" M

AX

4" M

AX6" MIN

SEE POWER PLANFOR DEVICE TYPE

INSULATING BUSHINGS.B-LINE SB-1153 OREQUAL

ALIGN DEVICESBETWEEN RACKS

ELECTRICALLY INSULATERACEWAY AND JUNCTION BOXFROM CABLE RUNWAY

FRONT OFCABLE RUNWAY

EQUIPMENT RACK.SEE DIVISION 27.

REAR OF CABLE RUNWAY,NOT CABLE TRAY

DEVICES, CABLING,FACEPLATES ANDINSERTS BY DIVISION27. SEE PLANS FORQUANTITY AND TYPE

SINGLE GANG EXTENSION RINGFOR LOCATION INSTALLED(CMU/GYP)

REAM ALL CONDUIT PENETRATIONS TOMAINTAIN CONDUIT DIAMETER THROUGHBOX

1" EMT (TYP)

STUB OUT TO ACCESSIBLE CEILINGWITH INSULATING BUSHINGS (TYP)

SWEEP BENDS TYPICALOF COMM CONDUITS

4-11/16"x4-11/16"x2-1/8" DEEP BOXSTEEL CITY #72171 OR EQUAL

CONDUITS DOWNONLY WHERE INDICATED

TELECOM ROOM:TE1, TE2, ETC.

PATCH PANEL ID(A-Z)

PATCH PANELPORT NUMBER(1-48)

TIA

-606

FO

RM

AT

US

ING

ST

AN

DA

RD

LAB

ELI

NG

WIN

DO

WS

TE1-C26 TE1-C25

TE1-C16 TE1-C17

EMER LOAD

NORMAL LOAD

EMRELAY

1

2345 6

OCC.SENSOR

EMERGENCY

N

NORMAL

N

EMERGENCY RELAY TERMINALS:1. UNSWITCHED HOT (NORMAL)2. SWITCHED HOT (NORMAL)3. NEUTRAL (NORMAL)4. NEUTRAL (EMERGENCY)5. LOAD (EMERGENCY)6. UNSWITCHED HOT (EMERGENCY)

POWERPACK

PANEL L1A120/208V, 3PH, 4W

FED FROM T1A10KAIC, 1-20-2011

CABLE COLOR CODE:PHASE A: BLACKPHASE B: REDPHASE C: BLUENEUTRAL: WHITEGROUND: GREEN

SWITCHBOARD, DISTRIBUTION PANEL ANDPANELBOARD EXAMPLE.

SAFETY SWITCH OR ENCLOSED CIRCUITBREAKER EXAMPLE.

120/208V, 3PH, 4WFED FROM T1A

FEEDS PANEL L1A

LABELING DETAIL NOTES:

1. LABEL SHALL BE BLACK OR WHITE LAMINATED ACRYLIC OR MELAMINE WITH ENGRAVED LETTERING AND SELF-ADHESIVE BACK.

2. LETTERING SHALL BE WHITE ON BLACK OR BLACK ON WHITE BACKGROUND AND 3/8-INCH HIGH MINIMUM.

3. PROVIDE THE FOLLOWING INFORMATION ON SWITCHBOARD LABELS:SWITCHBOARD TAGSYSTEM VOLTAGE, PHASE, WIRESHORT CIRCUIT RATING, DATECONDUCTOR COLORS

4. PROVIDE THE FOLLOWING INFORMATION ON DISTRIBUTION PANELBOARD AND PANELBOARD LABELS:DISTRIBUTION PANELBOARD OR PANELBOARD TAGSYSTEM VOLTAGE, PHASE, WIREFED FROMSHORT CIRCUIT RATING, DATECONDUCTOR COLORS

5. PROVIDE THE FOLLOWING INFORMATION ON SWITCHBOARD AND DISTRIBUTION PANELBOARD BRANCH SWITCHES:BRANCH SWITCH TAG (LOAD BEING SERVED)

6. PROVIDE THE FOLLOWING INFORMATION ON TRANSFORMER LABELS:TRANSFORMER TAGSYSTEM PRIMARY AND SECONDARY VOLTAGE, WYE, DELTA, OR SINGLE PHASEFED FROM

7. PROVIDE THE FOLLOWING INFORMATION ON SAFETY SWITCH OR CIRCUIT BREAKER ENCLOSURE LABELS:SYSTEM VOLTAGE, PHASE, WIREFED FROMFEEDS (LOAD BEING SERVED)

8. CONDUCTOR COLORS SHALL ALSO FOLLOW REQUIREMENTS LISTED IN SPECIFICATIONS SECTION 260553.

OCCUPANCYSENSOR

OCCUPANCYSENSOR

NUMBER OFSENSORSPER PLANS

NUMBER OFSWITCHESPER PLAN

LOAD

LOAD

LOAD

SWITCH "a"

SWITCH "b"

SWITCH "c"

POWERPACK

LINE

NEUTRAL

3' -

6"

2' -

4"

12" CABLE RUNWAYAT 7'-6" AFF (TYP)

C4C1

C3C12C6

MOUNT BELOW CABLE RUNWAY.

E6.1

51

E6.1

22

E6.1 53

1"5/

8"

4" T

YP

2 HOLE IRREVERSIBLECOMPRESSION CONNECTOR.

CONNECTIONS PERDRAWINGS ANDSPECIFICATIONS

ISOLATIONBUSHING

COPPERGROUND BAR

MOUNTINGBRACKET

FRONT VIEW

SIDE VIEW

48-PORT PATCH PANEL

6" VERTICAL CABLEMANAGMENT

LIU. FIBER BACKBONE TOTE0B

C7

EXISTING 48-PORT SWITCH

EXISTING 48-PORT PATCHPANELS

EXISTING HORIZONTALCABLE MANAGEMENT

EXISTING FIBERRELOCATED EXISTING MODEMSHELF

RELOCATED EXISTINGBANDPASS FILTER

NEW LIU. BACKBONE TOTE0A

NEW 48-PORT PATCH PANEL FORHORIZONTAL CABLE IN AREA B.

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

Rev

isio

ns

5/8

/2017 4

:29:2

1 P

M

C:\R

evit\1

0-1

6206-0

0_E

L_2016_C

entr

al_

ekam

in.r

vt

10-1

6206-0

1

3/2

9/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

ELE

CT

RIC

AL D

ET

AIL

SE

6.1

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

SCALE: 12" = 1'-0"E6.1

21 ABOVE COUNTER RECEPTACLES

SCALE: 3" = 1'-0"E6.1

31 TYPICAL CABLE TRAY SLEEVESSCALE: 12" = 1'-0"E6.1

32 CABLE RUNWAY RECEPTACLESSCALE: 3" = 1'-0"E6.1

33 COMM OUTLETSCALE: 1/2" = 1'-0"E6.1

34 COMM OUTLET LABELING

SCALE: 1/2" = 1'-0"E6.1

12 EMERGENCY LIGHTING RELAY WITH OCCUPANCY SENSOR

SCALE: 12" = 1'-0"E6.1

23 EQUIPMENT LABELING

SCALE: 3/8" = 1'-0"E6.1

11 OCCUPANCY SENSOR WIRING DIAGRAM

SCALE: 3/8" = 1'-0"E6.1

42 TE0A CABLE TRAYSCALE: 3/8" = 1'-0"E6.1

41 TE0A LARGE SCALESCALE: 3/8" = 1'-0"E6.1

44 TE0B CABLE TRAYSCALE: 3/8" = 1'-0"E6.1

43 TE0B LARGE SCALE

SCALE: 3" = 1'-0"E6.1

22 GROUND BUS

SCALE: 1/2" = 1'-0"E6.1

51 TEOA ELEVATIONSCALE: 1/2" = 1'-0"E6.1

53 TEOB ELEVATION

KEYED NOTES

KEY

VALUE KEY TEXT

C1 PROVIDE CABLE DROP-OUTS AT EACH VERTICAL CABLEMANAGEMENT.

C3 PROVIDE VERTICAL RUNWAY FOR SUPPORT OF CABLESUP TO SLEEVES (TYPICAL).

C4 PROVIDE RADIUS CORNER BRACKETS FOR ALL CABLERUNWAY CORNERS (TYPICAL).

C6 PLYWOOD FROM 0'-4" TO 8'-4" ON ALL 4 WALLS.

C7 12 STRAND OS2 ARMORED. 12 STRAND OM4 ARMORED.

C12 SLEEVES THROUGH WALL. STACK AND ALIGN WITH CABLERUNWAY.

Page 57: CONSTRUCTION DOCUMENTS REVIEW SET · construction documents review set 5/08/2017 501 south 14th street ... large scale plans & interior elevations ... dia diameter diag diagonal diff

Arc

hite

ctu

re E

ngin

eering

P

lan

nin

g In

teriors

©

,

DL

R G

rou

p inc., a

Ne

bra

ska

co

rpo

ratio

n, A

LL

RIG

HT

S R

ES

ER

VE

D

Rev

isio

ns

5/8

/2017 4

:29:2

4 P

M

C:\R

evit\1

0-1

6206-0

0_E

L_2016_C

entr

al_

ekam

in.r

vt

10-1

6206-0

1

3/2

9/1

7

ST

AT

E O

F N

EB

RA

SK

A 5

01 B

UIL

DIN

G R

EN

OV

AT

ION

ELE

CT

RIC

AL S

CH

ED

ULE

SE

7.1

20

17

PR

INT

SH

OP

BU

ILD

OU

T &

ST

RU

CT

UR

AL D

EF

ICIE

NC

Y R

EN

OV

AT

ION

EMD CURRENT: 66 A

CONNECTED CURRENT: 68 A

Motor 1656 VA 100.00% 1656 VA ESTIMATED DEMAND: 23606 VA

Appliance 11220 VA 100.00% 11220 VA CONNECTED LOAD: 24336 VA

Receptacle 11460 VA 93.63% 10730 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 70 A 66 A 68 A

TOTAL LOAD: 8380 VA 7876 VA 8080 VA

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 SPARE 20 A 1 0 VA 1080 VA 1 20 A RECEPT-016 36

33 EXIST. RECEPT CENTER SO. REVENUE 20 A 1 0 VA 0 VA -- -- -- 34

31 SPARE 20 A 1 0 VA 0 VA 2 20 A RECEPT-DATA 003 UPS 32

29 SPARE 20 A 1 0 VA 720 VA 1 20 A RECEPT-DATA 003 30

27 SPARE 20 A 1 0 VA 900 VA 1 20 A RECEPT-RECEPTION 006 28

25 SPARE 20 A 1 0 VA 180 VA -- -- -- 26

23 RECEPT-CART STORAGE 002,003,007 20 A 1 720 VA 180 VA 2 15 A 28B-AGFA ACENTO IIE 24

21 EF-A009 20 A 1 1656 VA 180 VA 1 20 A RECEPT-PRE PRESS WORKSTATION... 22

19 RECEPT-DATA RM 003 20 A 1 1200 VA 180 VA 1 20 A RECEPT-PRE PRESS WORKSTATION EAST 20

17 EXIST. RECEPT. NORTH REVENUE 20 A 1 0 VA 1000 VA -- -- -- 18

15 RECEPT-CONFERENCE 012 20 A 1 900 VA 1000 VA 2 20 A 28A-AGFA ACENTO IIE 16

13 RECEPT-OPEN OFFICE 008 COPIER 20 A 1 1000 VA 2400 VA -- -- -- 14

11 RECEPT-OFFICE 010 20 A 1 720 VA 2400 VA 2 50 A 27-MITSUBISHI VDP 12

9 RECEPT-OFFICE 011 20 A 1 720 VA 180 VA 1 20 A RECEPT-PRE PRESS SOUTH WEST 10

7 RECEPT-OFFICE 013 20 A 1 1080 VA 180 VA 1 20 A RECEPT-PRE PRESS SOUTH 8

5 RECEPT-OFFICE 014 20 A 1 900 VA 360 VA 1 20 A 34-EPSON SURECOLOR 6

3 RECEPT-OFFICE 015 20 A 1 900 VA 1440 VA -- -- -- 4

1 RECEPT-OFFICE 018 20 A 1 720 VA 1440 VA 2 30 A 26-AB DICK 2

CKT CIRCUIT DESCRIPTION

BKR

TRIP POLES A B C POLES

BKR

TRIP CIRCUIT DESCRIPTION CKT

Type 1

NOTES: ALL CIRCUITS MARKED 'EXIST' SHALL BE RECIRCUITED TO NEW PANEL LOCATION.

MAIN BREAKER: 225 A WIRES: 4 SCCR: 7 kA

BUS RATING: 225 A PHASES: 3 FED FROM: SEE ONE-LINE

LOCATION: VOLTS: 120/208 Wye MOUNTING: FLUSH

PANEL: GA1

Spare 720 VA 50.00% 360 VA EMD CURRENT: 56 A

Other 114 VA 100.00% 114 VA CONNECTED CURRENT: 55 A

Appliance 6740 VA 100.00% 6740 VA ESTIMATED DEMAND: 20222 VA

Receptacle 8820 VA 100.00% 8820 VA CONNECTED LOAD: 19744 VA

Lighting 3350 VA 125.00% 4188 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 58 A 67 A 43 A

TOTAL LOAD: 6739 VA 7840 VA 5160 VA

83 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 84

81 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 82

79 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 80

77 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 78

75 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 76

73 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 74

71 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 72

69 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 70

67 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 68

65 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 66

63 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 64

61 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 62

59 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 60

57 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 58

55 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 56

53 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 54

51 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 52

49 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 50

47 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 48

45 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 46

43 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 44

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 720 VA 1 20 A FIRE/SMOKE DAMPERS 34

31 SPARE 20 A 1 0 VA 1379 VA 1 20 A LTG-CORRIDOR, JANITOR, BATHROOM,... 32

29 SPARE 20 A 1 0 VA 1040 VA 1 20 A LTG-FUTURE LOGISTICS NORTH 30

27 RECEPT-BREAK RM EAST 20 A 1 900 VA 1040 VA 1 20 A LTG-FUTURE LOGISTICS SOUTH 28

25 RECEPT-BREAK RM NORTH 20 A 1 360 VA 900 VA 1 20 A RECEPT-CORRIDOR 26

23 (G) RECEPT-REFRIGERATOR 20 A 1 800 VA 720 VA 1 20 A (G) WATER COOLER - HALL 023 24

21 RECEPT-BREAK RM COUNTERTOP #2 20 A 1 360 VA 1260 VA 1 20 A RECEPT-BATHROOM, JANITOR 22

19 (G) RECEPT-MICROWAVE 20 A 1 1500 VA 720 VA 1 20 A RECEPT-LOGISTICS 030 EAST 20

17 RECEPT-GARBAGE DISPOSER 20 A 1 180 VA 720 VA 1 20 A RECEPT-LOGISTICS 030 EAST 18

15 RECEPT-BREAK RM COUNTERTOP #1 20 A 1 360 VA 1500 VA 1 20 A RECEPT-LOGISTICS 030 COPIER 16

13 (G) RECEPT-VENDING 20 A 1 800 VA 1080 VA 1 20 A RECEPT-LOGISTICS 030 COLUMNS 14

11 (G) RECEPT-VENDING 20 A 1 800 VA 900 VA 1 20 A RECEPT-LOGISTICS 030 SOUTH 12

9 (G) RECEPT-VENDING 20 A 1 800 VA 900 VA 1 20 A RECEPT-LOGISTICS 030 WEST 10

7 EXIST. WOMENS RM HAND DRYER 20 A 1 0 VA 0 VA 1 20 A EXIST. FPB GEORGE RM 8

5 EXIST. MENS RM HAND DRYER 20 A 1 0 VA 0 VA 1 20 A EXIST. FPB NORTHEAST 6

3 EXIST. WATER HEATER NW BATHROOM 20 A 1 0 VA 0 VA 1 20 A EXIST. FPB BATH & WORK AREA 4

1 EXIST. DISTILLER 20 A 1 0 VA 0 VA 1 20 A EXIST. WATER HEATER BY DARK RM 2

CKT CIRCUIT DESCRIPTION

BKR

TRIP POLES A B C POLES

BKR

TRIP CIRCUIT DESCRIPTION CKT

Type 1

NOTES: ALL CIRCUITS MARKED 'EXIST' SHALL BE RECIRCUITED TO NEW PANEL LOCATION.

MAIN BREAKER: 225 A WIRES: 4 SCCR: 10 kA

BUS RATING: 225 A PHASES: 3 FED FROM: SEE ONE-LINE

LOCATION: LOGISTICS 030 VOLTS: 120/208 Wye MOUNTING: SURFACE

PANEL: BB1

EMD CURRENT: 24 A

CONNECTED CURRENT: 21 A

Other 180 VA 100.00% 180 VA ESTIMATED DEMAND: 8716 VA

Receptacle 2700 VA 100.00% 2700 VA CONNECTED LOAD: 7549 VA

Lighting 4669 VA 125.00% 5836 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 32 A 19 A 14 A

TOTAL LOAD: 3706 VA 2175 VA 1668 VA

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 720 VA 1 20 A RECEPT-COLOR COPY 019 18

15 SPARE 20 A 1 0 VA 180 VA 1 20 A RECEPT-COLOR COPY SOUTH EAST 16

13 SPARE 20 A 1 0 VA 360 VA 1 20 A RECEPT-COLOR COPY WEST 14

11 SPARE 20 A 1 0 VA 180 VA 1 20 A RECEPT-POWER POLE SOUTH 12

9 LTG-COLOR COPY 20 A 1 400 VA 180 VA 1 20 A RECEPT-UNDER PANEL GA2 10

7 LTG-OPEN OFFICE NORTH 20 A 1 1181 VA 720 VA 1 20 A RECEPT-020,021 8

5 LTG-OFFICE SOUTH 20 A 1 588 VA 180 VA 1 20 A RECEPT-COLOR COPY NORTH EAST 6

3 LTG-SECURED PRINT 20 A 1 1235 VA 180 VA 1 20 A RECEPT-PENDANT 4

1 LTG-DIGITAL GRAPHICS 20 A 1 1265 VA 180 VA 1 20 A RECEPT-POWER POLE NORTH 2

CKT CIRCUIT DESCRIPTION

BKR

TRIP POLES A B C POLES

BKR

TRIP CIRCUIT DESCRIPTION CKT

Type 1

NOTES:

MAIN BREAKER: 225 A WIRES: 4 SCCR: 7 kA

BUS RATING: 225 A PHASES: 3 FED FROM: SEE ONE-LINE

LOCATION: VOLTS: 120/208 Wye MOUNTING: SURFACE

PANEL: GA2

AHU CONNECTION SCHEDULE

MARK NO. VOLTAGE POLES VA MCA MOCP STARTER DISCONNECT

BRANCH CIRCUIT

P/N - G - C PANEL CIRCUIT NOTES

AHU-A009 480 V 3 9446 VA 37 A 40 A BY DIV 23 BY DIV 23 8 - 10 - 3/4" MCP 7 SEE ONE-LINEDIAGRAM

EXHAUST FAN CONNECTION SCHEDULE

VOLTAGE POLES HP VA FLA MCA MOCP STARTER DISCONNECT

BRANCH CIRCUIT

P/N - G - C PANEL CIRCUIT NOTES

EF-A009 120 V 1 3/4 1656 VA 13.8 A 17 A 20 A NEMA 0 BY DIV 23 12 - 12 - 3/4" GA1 21

EMD CURRENT: 6 A

CONNECTED CURRENT: 6 A

ESTIMATED DEMAND: 2220 VA

CONNECTED LOAD: 2220 VA

Receptacle 2220 VA 100.00% 2220 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 10 A 4 A 4 A

TOTAL LOAD: 1220 VA 500 VA 500 VA

41 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 42

39 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 RECEPT-ELECTRICAL RM, UPS RM 20 A 1 720 VA 0 VA 1 20 A SPARE 8

5 RECEPT-FUTURE LOGISTICS 20 A 1 500 VA 0 VA 1 20 A SPARE 6

3 RECEPT-FUTURE LOGISTICS 20 A 1 500 VA 0 VA 1 20 A SPARE 4

1 RECEPT-FUTURE LOGISTICS 20 A 1 500 VA 0 VA 1 20 A SPARE 2

CKT CIRCUIT DESCRIPTION

BKR

TRIP POLES A B C POLES

BKR

TRIP CIRCUIT DESCRIPTION CKT

Type 1

NOTES:

MAIN BREAKER: 225 A WIRES: 4 SCCR: 11 kA

BUS RATING: 225 A PHASES: 3 FED FROM: SEE ONE-LINE

LOCATION: LOGISTICS 030 VOLTS: 120/208 Wye MOUNTING: SURFACE

PANEL: LAB

HUMIDIFIER CONNECTION SCHEDULE

MARK NO. LOCATION VOLTAGE POLES VA FLA MCA MOCP

BRANCH CIRCUIT

P - N - G PANEL CIRCUIT NOTES

H-A009 A009 480 V 3 10660 VA 38.5 A 48 A 50 A 6 - 10 - 1" MCP 5 SEE ONE-LINEDIAGRAM

LIGHT FIXTURE SCHEDULETYPE MANUFACTURER MODEL LAMP LOAD VOLTAGE STYLE DESCRIPTION

D1 GOTHAM EVO LED 1500LM4000K

18 VA UNV RECESSED ROUND GRIDDOWNLIGHT

6" DIAMETER DOWNLIGHT. GALVANIZED STEEL HOUSING WITH FLUSH WHITE TRIM.MEDIUM DISTRIBUTION, SEMI-SPECULAR FINISH

D2 GOTHAM EVO LED 1500LM4000K

18 VA UNV RECESSED ROUND FLANGEDDOWNLIGHT

SAME SPECS AS D1, EXCEPT FLANGE MOUNT.

P1a LITHONIA ZL1D LED 5000LM4000K

42 VA 120 LINEAR STRIP PENDANT 4' LOW PROFILE LINEAR STRIP FIXTURE. SNAP ON CLEAR DIFFUSER. WHITE COLDROLLED STEEL HOUSING. AIRCRAFT CABLE MOUNTED.

P1b LITHONIA ZL1D LED 7000LM4000K

67 VA 120 LINEAR STRIP PENDANT SAME SPECS AS FIXTURE P1A, EXCEPT LUMEN OUTPUT.

R1 LITHONIA GTL4 LED 3300LM4000K

35 VA 120 1X4 RECESSED FLANGEDTROFFER

COLD ROLLED STEEL HOUSING WITH WHITE FLUSH STEEL DOOR. PRISMATIC #12PATTERN ACRYLIC, 0.125" THICK LENS. BAKED WHITE ENAMEL FINISH.

R2a LITHONIA 2GTL2 LED 3300LM4000K

35 VA 120 2X2 RECESSED LENSED GRIDTROFFER

COLD ROLLED STEEL HOUSING WITH WHITE FLUSH STEEL DOOR. PRISMATIC #12PATTERN ACRYLIC, 0.125" THICK LENS. BAKED WHITE ENAMEL FINISH.

R2b LITHONIA 2GTL2 LED 4000LM4000K

40 VA 120 2X2 RECESSED LENSED GRIDTROFFER

SAME SPECS AS R1a, EXCEPT LUMEN OUTPUT

R3a LITHONIA 2FSL2 LED 3300LM4000K

35 VA 120 2X2 RECESSED GRID VOLUMETRIC COLD ROLLED STEEL COATED POLYESTER, PAINTED AFTER FABRICATION, SATINWHITE ACRYLIC DIFFUSER. 0-10V DIMMING.

R3b LITHONIA 2FSL2 LED 4000LM4000K

42 VA 120 2X2 RECESSED GRID VOLUMETRIC SAME SPECS AS R3a, EXCEPT LUMEN OUTPUT.

W1 LITHONIA ZL1D LED 5000LM4000K

42 VA 120 WALL MOUNT LINEAR STRIP SAME SPECS AS FIXTURE P1A, EXCEPT WALL MOUNTED. MOUNT AT 8'-0" UNO.

W3 LITHONIA ELM2 LED 4000K 6 VA 3.6 TWIN HEAD EMERGENCY LIGHT TWO LED LAMP HEADS. IMPACT RESISTANT THERMOPLASTIC HOUSING.INTEGRATED TEST SWITCH/PILOT LIGHT. HIGH-OUTPUT NI-CAD BATTERY. WHITEFINISH. WALL MOUNT AT 8'-0" UNO.

X1 LITHONIA LE-S-W-1-G LED 10 VA 120 SINGLE-SIDED EXIT SIGN UNIVERSAL MOUNT EXIT SIGN, AC POWER ONLY, DIE-CAST ALUMINUMCONSTRUCTION. SINGLE FACE, GREEN LETTERS, WHITE FINISH.

X2 LITHONIA LE-S-W-2-G LED 10 VA 120 DOUBLE-SIDED EXIT SIGN UNIVERSAL MOUNT EXIT SIGN, AC POWER ONLY, DIE-CAST ALUMINUMCONSTRUCTION. DOUBLE FACE, GREEN LETTERS, WHITE FINISH.

EMD CURRENT: 12 A

CONNECTED CURRENT: 12 A

ESTIMATED DEMAND: 4480 VA

Appliance 3400 VA 100.00% 3400 VA CONNECTED LOAD: 4480 VA

Receptacle 1080 VA 100.00% 1080 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

TOTAL AMPS: 14 A 15 A 10 A

TOTAL LOAD: 1620 VA 1700 VA 1160 VA

41 0 VA 1 20 A SPARE 42

39 EXIST. UPS RM MONITOR POWER 20 A 1 0 VA 0 VA 1 20 A SPARE 40

37 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32

29 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 30

27 -- -- -- 180 VA 0 VA 1 20 A SPARE 28

25 20-XEROX 700i 20 A 2 180 VA 0 VA 1 20 A SPARE 26

23 -- -- -- 80 VA 0 VA 1 20 A SPARE 24

21 21-EPSON STYLUS PRO 9900 20 A 2 80 VA 0 VA 1 20 A SPARE 22

19 14-CONTROLLER 20 A 1 360 VA 0 VA 1 20 A SPARE 20

17 -- -- -- 180 VA 180 VA -- -- -- 18

15 14B-DOCPRINT 135 50 A 2 180 VA 180 VA 2 50 A 16B-NUVERA 288 16

13 -- -- -- 180 VA 180 VA -- -- -- 14

11 14A-DOCPRINT 135 30 A 2 180 VA 180 VA 2 50 A 16A-NUVERA 288 12

9 17-CONTROLLER 20 A 1 360 VA 360 VA 1 20 A 15-CONTROLLER 10

7 -- -- -- 180 VA 180 VA -- -- -- 8

5 17B-DOCUTECH 180 HLC 50 A 2 180 VA 180 VA 2 50 A 15B-DOCUTECH 180 6

3 -- -- -- 180 VA 180 VA -- -- -- 4

1 17A-DOCUTECH 180 HLC 30 A 2 180 VA 180 VA 2 30 A 15A-DOCUTECH 180 2

CKT CIRCUIT DESCRIPTION

BKR

TRIP POLES A B C POLES

BKR

TRIP CIRCUIT DESCRIPTION CKT

Type 1

NOTES: ALL CIRCUITS MARKED 'EXIST' SHALL BE RECIRCUTED TO NEW PANEL LOCATION

MAIN BREAKER: 225 A WIRES: 4 SCCR: 4 kA

BUS RATING: 225 A PHASES: 3 FED FROM: SEE ONE-LINE

LOCATION: VOLTS: 120/208 Wye MOUNTING: FLUSH

PANEL: DOCUTEC