contents · rc.per _ eussmann 5001/ac t1me-delay fuse fnq-10 low voltage, supplementary fuses 3...

16
r _ c.pER Eussmann 5001/ac T1ME-DELAY FUSE FNQ-10 Low voltage, supplementary fuses 3 Contents Description Fuse holder and block selection guide Cable limiters and welder limiters K cable limiters 600V UH cable limiters 250V 64000 and 68000 welder limiters . 600V 13/32 -x 1 1/2 - Fast-acting supplementary fuses BAF 250V 3-5 KTK 600V 3-5 KLM 600Vac/dc 3-6 13/32 - x 1 1/2 -Time-delay supplementary fuses FNM 250V 3-7 FNQ 500V 3-7 13/32 -x 1 3/8 - Fast-acting supplementary fuses BBS 600V 3-8 Pin indication fuses and actuator GBA 125V 3-8 GLD 125V 3-8 MIC 250V fast-acting 3-9 FNA 250V time-delay 3-9 MIS 600V 3-10 KAZ 600V 3-10 Limiters ANN . 125V fast-acting 3-10 ANL 80Vdc time-delay 3-10 4164 and 4164-FR fuse blocks .3-10 In-line size rejecting fuses and fuse holders GLQ 300V 3-11 GMQ 300V 3-11 In-line non-rejecting fuses and fuse holders GLR 300V 3-12 GMF 300V 3-12 GRF 300V 3-12 Automotive blade-type fuses ATC 32Vdc 3-13 ATC- _ID 32Vdc 3-13 ATM 32Vdc 3-13 ATM- _ID 32Vdc 3-13 ATM-LP 32Vdc 3-13 ATR micro 32Vdc 3-16 MAX 32Vdc 3-14 MAX- _ID 32Vdc 3-14 Automotive blade-type fuse holders HHC, HHD, HHF, HHG, ATC-FHID for ATC fuses . . 3-13 HHL, HHM, ATC-FHID for ATM fuses 3-14 HHX for MAX fuses 3-14 Page 3-2 3-4 3-4 3-4 RED indicates NEW information PCB fuseclips for ATC/ATM blade, 5mm, 1/4" and 13/32" diameter fuses 3-15 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.corn/bussmannseries 3.1 3-1 Low voltage supplementary fuses 3 Low voltage, supplementary fuses BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries Description Page Fuse holder and block selection guide 3-2 Cable limiters and welder limiters K cable limiters . . . . . . . . . . . . . . . 600V . . . . . . . . . . 3-4 UH cable limiters . . . . . . . . . . . . . . 250V . . . . . . . . . . 3-4 64000 and 68000 welder limiters . . 600V . . . . . . . . . . 3-4 13/32˝ x 1 1/2˝ Fast-acting supplementary fuses BAF . . . . . . . . . . . . . . . . . . . . . . 250V . . . . . . . . . . 3-5 KTK . . . . . . . . . . . . . . . . . . . . . . 600V . . . . . . . . . . 3-5 KLM . . . . . . . . . . . . . . . . . . 600Vac/dc . . . . . . . . . . 3-6 13/32˝ x 1 1/2˝ Time-delay supplementary fuses FNM . . . . . . . . . . . . . . . . . . . . . . 250V . . . . . . . . . . 3-7 FNQ . . . . . . . . . . . . . . . . . . . . . . . 500V . . . . . . . . . . 3-7 13/32˝ x 1 3/8˝ Fast-acting supplementary fuses BBS . . . . . . . . . . . . . . . . . . . . . . . 600V . . . . . . . . . . 3-8 Pin indication fuses and actuator GBA . . . . . . . . . . . . . . . . . . . . . . . 125V . . . . . . . . . . 3-8 GLD . . . . . . . . . . . . . . . . . . . . . . . 125V . . . . . . . . . . 3-8 MIC . . . . . . . . . . . . . . . 250V fast-acting . . . . . . . . . . 3-9 FNA . . . . . . . . . . . . . . . 250V time-delay . . . . . . . . . . 3-9 MIS . . . . . . . . . . . . . . . . . . . . . . . 600V . . . . . . . . . 3-10 KAZ . . . . . . . . . . . . . . . . . . . . . . . 600V . . . . . . . . . 3-10 Limiters ANN . . . . . . . . . . . . . . 125V fast-acting . . . . . . . . . 3-10 ANL . . . . . . . . . . . . . . 80Vdc time-delay . . . . . . . . . 3-10 4164 and 4164-FR . . . . . . . .fuse blocks . . . . . . . . . 3-10 In-line size rejecting fuses and fuse holders GLQ . . . . . . . . . . . . . . . . . . . . . . 300V . . . . . . . . . .3-11 GMQ . . . . . . . . . . . . . . . . . . . . . . 300V . . . . . . . . . . 3-11 In-line non-rejecting fuses and fuse holders GLR . . . . . . . . . . . . . . . . . . . . . . 300V . . . . . . . . . 3-12 GMF . . . . . . . . . . . . . . . . . . . . . . 300V . . . . . . . . . 3-12 GRF . . . . . . . . . . . . . . . . . . . . . . 300V . . . . . . . . . 3-12 Automotive blade-type fuses ATC . . . . . . . . . . . . . . . . . . . . . . 32Vdc . . . . . . . . . 3-13 ATC-_ID . . . . . . . . . . . . . . . . . . . 32Vdc . . . . . . . . . 3-13 ATM . . . . . . . . . . . . . . . . . . . . . . 32Vdc . . . . . . . . . 3-13 ATM-_ID . . . . . . . . . . . . . . . . . . . 32Vdc . . . . . . . . . 3-13 ATM-LP . . . . . . . . . . . . . . . . . . . .32Vdc . . . . . . . . . 3-13 ATR micro . . . . . . . . . . . . . . . . . 32Vdc . . . . . . . . . 3-16 MAX . . . . . . . . . . . . . . . . . . . . . . 32Vdc . . . . . . . . . 3-14 MAX-_ID . . . . . . . . . . . . . . . . . . . 32Vdc . . . . . . . . . 3-14 Automotive blade-type fuse holders HHC, HHD, HHF, HHG, ATC-FHID for ATC fuses . . . 3-13 HHL, HHM, ATC-FHID for ATM fuses . . . . . . . . . . . . 3-14 HHX for MAX fuses . . . . . . . . . . . . . . . . . . . . . . . . . 3-14 PCB fuseclips for ATC/ATM blade, 5mm, 1/4˝ and 13/32˝ diameter fuses . . . . . . . . . . . . . . . 3-15 Contents RED indicates NEW information

Upload: duongxuyen

Post on 19-May-2019

217 views

Category:

Documents


0 download

TRANSCRIPT

• r_c.pER Eussmann

5001/ac T1ME-DELAY

FUSE

FNQ-10

Low voltage, supplementary fuses 3

Contents Description Fuse holder and block selection guide

Cable limiters and welder limiters

K cable limiters 600V UH cable limiters 250V 64000 and 68000 welder limiters . 600V

13/32-x 1 1/2-Fast-acting supplementary fuses BAF 250V 3-5 KTK 600V 3-5 KLM 600Vac/dc 3-6

13/32-x 1 1/2-Time-delay supplementary fuses FNM 250V 3-7

FNQ 500V 3-7

13/32-x 1 3/8-Fast-acting supplementary fuses BBS 600V 3-8

Pin indication fuses and actuator GBA 125V 3-8 GLD 125V 3-8 MIC 250V fast-acting 3-9 FNA 250V time-delay 3-9 MIS 600V 3-10 KAZ 600V 3-10

Limiters

ANN . 125V fast-acting 3-10 ANL 80Vdc time-delay 3-10 4164 and 4164-FR fuse blocks .3-10

In-line size rejecting fuses and fuse holders GLQ 300V 3-11

GMQ 300V 3-11

In-line non-rejecting fuses and fuse holders GLR 300V 3-12 GMF 300V 3-12

GRF 300V 3-12

Automotive blade-type fuses ATC 32Vdc 3-13 ATC- _ID 32Vdc 3-13 ATM 32Vdc 3-13 ATM- _ID 32Vdc 3-13 ATM-LP 32Vdc 3-13 ATR micro 32Vdc 3-16 MAX 32Vdc 3-14 MAX- _ID 32Vdc 3-14

Automotive blade-type fuse holders HHC, HHD, HHF, HHG, ATC-FHID for ATC fuses . . 3-13 HHL, HHM, ATC-FHID for ATM fuses 3-14 HHX for MAX fuses 3-14

Page 3-2

3-4 3-4

3-4

RED indicates NEW information PCB fuseclips for ATC/ATM blade, 5mm, 1/4" and 13/32" diameter fuses 3-15

BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.corn/bussmannseries 3.1 3-1

Low voltage

supplementary

fuses

3Low voltage, supplementary fuses

BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries

Description PageFuse holder and block selection guide 3-2

Cable limiters and welder limitersK cable limiters . . . . . . . . . . . . . . . 600V . . . . . . . . . . 3-4UH cable limiters . . . . . . . . . . . . . . 250V . . . . . . . . . . 3-464000 and 68000 welder limiters . . 600V . . . . . . . . . . 3-4

13/32˝ x 1 1/2˝ Fast-acting supplementary fusesBAF . . . . . . . . . . . . . . . . . . . . . . 250V . . . . . . . . . . 3-5KTK . . . . . . . . . . . . . . . . . . . . . . 600V . . . . . . . . . . 3-5KLM . . . . . . . . . . . . . . . . . . 600Vac/dc . . . . . . . . . . 3-6

13/32˝ x 1 1/2˝ Time-delay supplementary fusesFNM . . . . . . . . . . . . . . . . . . . . . . 250V . . . . . . . . . . 3-7FNQ . . . . . . . . . . . . . . . . . . . . . . . 500V . . . . . . . . . . 3-7

13/32˝ x 1 3/8˝ Fast-acting supplementary fusesBBS . . . . . . . . . . . . . . . . . . . . . . . 600V . . . . . . . . . . 3-8

Pin indication fuses and actuatorGBA . . . . . . . . . . . . . . . . . . . . . . .125V . . . . . . . . . . 3-8GLD . . . . . . . . . . . . . . . . . . . . . . . 125V . . . . . . . . . . 3-8MIC . . . . . . . . . . . . . . . 250V fast-acting . . . . . . . . . . 3-9FNA . . . . . . . . . . . . . . . 250V time-delay . . . . . . . . . . 3-9MIS . . . . . . . . . . . . . . . . . . . . . . . 600V . . . . . . . . . 3-10KAZ . . . . . . . . . . . . . . . . . . . . . . . 600V . . . . . . . . . 3-10

LimitersANN . . . . . . . . . . . . . . 125V fast-acting . . . . . . . . . 3-10ANL . . . . . . . . . . . . . . 80Vdc time-delay . . . . . . . . . 3-104164 and 4164-FR . . . . . . . .fuse blocks . . . . . . . . . 3-10

In-line size rejecting fuses and fuse holdersGLQ . . . . . . . . . . . . . . . . . . . . . . 300V . . . . . . . . . .3-11GMQ . . . . . . . . . . . . . . . . . . . . . . 300V . . . . . . . . . .3-11

In-line non-rejecting fuses and fuse holdersGLR . . . . . . . . . . . . . . . . . . . . . . 300V . . . . . . . . . 3-12GMF . . . . . . . . . . . . . . . . . . . . . . 300V . . . . . . . . . 3-12GRF . . . . . . . . . . . . . . . . . . . . . . 300V . . . . . . . . . 3-12

Automotive blade-type fusesATC . . . . . . . . . . . . . . . . . . . . . . 32Vdc . . . . . . . . . 3-13ATC-_ID . . . . . . . . . . . . . . . . . . . 32Vdc . . . . . . . . . 3-13ATM . . . . . . . . . . . . . . . . . . . . . . 32Vdc . . . . . . . . . 3-13ATM-_ID . . . . . . . . . . . . . . . . . . . 32Vdc . . . . . . . . . 3-13ATM-LP . . . . . . . . . . . . . . . . . . . .32Vdc . . . . . . . . . 3-13ATR micro . . . . . . . . . . . . . . . . . 32Vdc . . . . . . . . . 3-16MAX . . . . . . . . . . . . . . . . . . . . . . 32Vdc . . . . . . . . . 3-14MAX-_ID . . . . . . . . . . . . . . . . . . . 32Vdc . . . . . . . . . 3-14

Automotive blade-type fuse holdersHHC, HHD, HHF, HHG, ATC-FHID for ATC fuses . . . 3-13HHL, HHM, ATC-FHID for ATM fuses . . . . . . . . . . . .3-14HHX for MAX fuses . . . . . . . . . . . . . . . . . . . . . . . . .3-14PCB fuseclips for ATC/ATM blade, 5mm, 1/4˝ and 13/32˝ diameter fuses . . . . . . . . . . . . . . . 3-15

Contents

RED indicates NEW information

FWAHL
SmallO

HM250 CH Safety JTM' Modular Type

JM600 HM600

• . -

• •

C.,

OPM-1038R and CH 0 PM-1038RSW

HPC-D

alma HPM

HEB HPF

HEX and HEY

NDNF1-WH BCM CCP Class CC

JP 4164 and 4164-FR

Modular knifeblade

OPM-NG-SC3

• 0

3 Low voltage, supplementary fuses Holders and blocks for low voltage supplementary fuses

Limiters

Catalog number Volts Page K 600V 3-4 u11 250V 3-4 68000 600V 3-4 64000 600V 3-4 ANN fast-acting limiter 125Vac/80Vdc 3-10 ANL time-delay limiter 80Vdc 3-10

Holders • CH Class J modular 1- to 3-pole, panel/DIN-Rail mount 9-11 • Safety JTM' modular holders, panel/DIN-Rail mount 9-14

Blocks • Modular type fuse blocks 250/600V, panel mount 9-41 • HM250 1- to 3-pole 250V, panel/DIN-Rail mount 9-24 • HM600 1- to 3-pole 600V, panel/DIN-Rail mount 9-24

Blocks • Modular knifeblade fuse blocks 250/600V, panel mount 9-17 • Modular type fuse blocks 600V, panel mount 9-41 • JM600 panel/DIN-Rail mount 9-24 • JP pyramid blocks, panel mount 9-31 • BH modular-style open blocks, panel mount 9-41

Limiter blocks - ANN and ANL • Blocks for 4164 and 4164-FR 3-10

13/32-X 1 112-Fuses

Catalog number Volts Page BAF 250V 3-5 KTK 600V 3-5 KLM 600Vac/dc 3-6 FN M 250V 3-7 FNQ 500V 3-7

Holders • OPM-NG-SC3 3-pole, panel/DIN-Rail mount 9-12 • OPM-1038R 3-pole, panel/DIN-Rail mount 9-11 • OPM-1038RSW 3-pole w/ switch, panel/DIN-Rail mount 9-10 • CH global 1- to 3-pole, DIN-Rail mount 9-2 • HPG panel mount fuse holder 9-53 • HPC-D panel mount fuse holder 9-54 • HPM panel mount fuse holder 9-54 • HPS panel mount fuse holder 9-53 • HPF panel mount fuse holder 9-53 • HEB 1-pole in-line fuse holder 9-46 • HEX and HEY 2-pole in-line fuse holders 9-45 • NDNF1-WH fuse holding rail mount terminal block 9-58 • Compact Circuit Protector (CCP) Class CC 1-, 2-, 3-pole

disconnect switch. 12-2

Blocks • BCM panel/DIN-Rail with adapters 9-32 • 4421 and 4515 single-pole fuse blocks 9-57

3-2 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.corn/bussmannseries 3-2 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries

3 Low voltage, supplementary fusesHolders and blocks for low voltage supplementary fuses

13/32˝ X 1 1/2˝ Fuses

Catalog number Volts PageBAF . . . . . . . . . . . . . . . . . . . . . . . 250V . . . . . . . . . . . . . . . . . . . . . 3-5KTK . . . . . . . . . . . . . . . . . . . . . . . 600V . . . . . . . . . . . . . . . . . . . . . 3-5KLM. . . . . . . . . . . . . . . . . . . . . . . 600Vac/dc . . . . . . . . . . . . . . . . . 3-6FNM . . . . . . . . . . . . . . . . . . . . . . 250V . . . . . . . . . . . . . . . . . . . . . 3-7FNQ . . . . . . . . . . . . . . . . . . . . . . . 500V . . . . . . . . . . . . . . . . . . . . . 3-7

Holders• OPM-NG-SC3 3-pole, panel/DIN-Rail mount . . . . . . . . . . . . . . . . . . .9-12• OPM-1038R 3-pole, panel/DIN-Rail mount . . . . . . . . . . . . . . . . . . . . 9-11• OPM-1038RSW 3-pole w/ switch, panel/DIN-Rail mount . . . . . . . . . .9-10• CH global 1- to 3-pole, DIN-Rail mount . . . . . . . . . . . . . . . . . . . . . . .9-2• HPG panel mount fuse holder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-53• HPC-D panel mount fuse holder . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-54• HPM panel mount fuse holder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-54• HPS panel mount fuse holder. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-53• HPF panel mount fuse holder. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-53• HEB 1-pole in-line fuse holder. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-46• HEX and HEY 2-pole in-line fuse holders . . . . . . . . . . . . . . . . . . . . .9-45• NDNF1-WH fuse holding rail mount terminal block . . . . . . . . . . . . . .9-58• Compact Circuit Protector (CCP) Class CC 1-, 2-, 3-pole disconnect switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12-2

Blocks• BCM panel/DIN-Rail with adapters . . . . . . . . . . . . . . . . . . . . . . . . . . .9-32• 4421 and 4515 single-pole fuse blocks . . . . . . . . . . . . . . . . . . . . . . .9-57

OPM-NG-SC3 CH

CH

JM600

JP BH 4164 and 4164-FR

Safety J™ ModularType

HM250

HM600

OPM-1038R and OPM-1038RSW

Limiters

Catalog number Volts PageK . . . . . . . . . . . . . . . . . . . . . . . . . 600V . . . . . . . . . . . . . . . . . . . . . 3-4UH . . . . . . . . . . . . . . . . . . . . . . . . 250V . . . . . . . . . . . . . . . . . . . . . 3-468000 . . . . . . . . . . . . . . . . . . . . . 600V . . . . . . . . . . . . . . . . . . . . . 3-464000 . . . . . . . . . . . . . . . . . . . . . 600V . . . . . . . . . . . . . . . . . . . . . 3-4ANN fast-acting limiter . . . . . . . . . 125Vac/80Vdc . . . . . . . . . . . . . 3-10ANL time-delay limiter . . . . . . . . . 80Vdc . . . . . . . . . . . . . . . . . . . 3-10

Holders• CH Class J modular 1- to 3-pole, panel/DIN-Rail mount. . . . . . . . . . .9-11• Safety J™ modular holders, panel/DIN-Rail mount . . . . . . . . . . . . . . .9-14

Blocks• Modular type fuse blocks 250/600V, panel mount. . . . . . . . . . . . . . . .9-41• HM250 1- to 3-pole 250V, panel/DIN-Rail mount . . . . . . . . . . . . . . . .9-24• HM600 1- to 3-pole 600V, panel/DIN-Rail mount . . . . . . . . . . . . . . . .9-24

Blocks• Modular knifeblade fuse blocks 250/600V, panel mount . . . . .9-17• Modular type fuse blocks 600V, panel mount . . . . . . . . . . . . . . . . . . .9-41• JM600 panel/DIN-Rail mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-24• JP pyramid blocks, panel mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-31• BH modular-style open blocks, panel mount . . . . . . . . . . . . . . . . . . . 9-41

Limiter blocks - ANN and ANL• Blocks for 4164 and 4164-FR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-10

HPGHPC-D HPM

HPS HPF HEB

HEX andHEY

NDNF1-WH BCM

Modular knifeblade

CCPClass CC

FWAHL
SmallO

1/4"X 1 1/4"fuse catalog numbers Volts Page GBA 1/4" X 1 1/4" 125V 3-8 GLD 1/4" X 1 1/4" 125V 3-8 MIC 13/32" X 1 1/2" 250V 3-9 FNA 13/32" X 1 1/2" 250V 3-9 MIS 13/32" X 2" 600V 3-10

KAZ 13/32" X 2' 600V 3-10 *Not a fuse. Pin actuator only.

Holders

Catalog numbers Volts Page ATC 32Vdc 3-13 ATM 32Vdc 3-13 MAX 32Vdc 3-14

Holders • ATC: HHC, HHD, HHF, HHG and ATC-FHID In-line holders 3-13 • ATM: HHL, HHM and ATM-FHID In-line holders 3-14 • MAX: HHX, MAX-FHID In-line holders 3-14

In-line rejecting and non-rejecting fuses

Catalog number Volts Page GLQ rejecting fuse 300V 3-11 GMQ rejecting fuse 300V 3-11 GLR non-rejecting fuse 300V 3-12 GMF non-rejecting fuse 300V 3-12 GRF non-rejecting fuse 300V 3-12

Holders • GLQ and GMQ: HLQ rejection holder 3-11 • GLR, GMF and GRF: HLR and HLR-2A non-rejection holders 3-12

easylDTm HHC, HHD, HHF HHL and

HHX illuminating holders and HHG HHM

11. HLQ3 fuse holders HLR fuse holder

Holders and blocks for low voltage supplementary fuses

3 13132" X 1 318" Fuses

Catalog numbers Volts Page BBS 600V 3-8

Holder • HPS-L panel mount holder 9-53 ,,,„ . :::.k_. 1.,. 4 .

) A

Blocks • BCM panel/DIN-Rail with adapters 9-32 HPS-L BCM

• 4421 and 4515 single-pole fuse blocks 9-57

Pin indicating fuses

• 1/4" X 1/4": HLD panel mount visual indication 9-52 FEW HK • 1/4" X 1/4": HK panel mount lamp indicating 9-52

Blocks • 1/4" X 1 1/4": 8000 for visual indication 9-55 • 13/32" X 1 1/7: 4-pole signal block cat # 3839

(not shown in catalog)* • 13/32" X 2": 1-pole signal block cat # 2778

(not shown in catalog)* • 13/37 X 2": 2-pole signal block cat # 2837

(not shown in catalog)* • 13/32" X 2": 3-pole signal block cat # 2838

(not shown in catalog)*

Automotive blade-type fuses

BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.corn/bussmannseries 3-3 3-3

Low voltage

supplementary

fuses

3Low voltage, supplementary fusesHolders and blocks for low voltage supplementary fuses

BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries

In-line rejecting and non-rejecting fuses

Catalog number Volts PageGLQ rejecting fuse . . . . . . . . . . . . . . . . . . . 300V . . . . . . . . . . . . . . . 3-11GMQ rejecting fuse . . . . . . . . . . . . . . . . . . 300V . . . . . . . . . . . . . . . 3-11GLR non-rejecting fuse . . . . . . . . . . . . . . . 300V . . . . . . . . . . . . . . . 3-12GMF non-rejecting fuse . . . . . . . . . . . . . . . 300V . . . . . . . . . . . . . . . 3-12GRF non-rejecting fuse . . . . . . . . . . . . . . . 300V . . . . . . . . . . . . . . . 3-12

Holders• GLQ and GMQ: HLQ rejection holder . . . . . . . . . . . . . . . . . . . . . . . . 3-11• GLR, GMF and GRF: HLR and HLR-2A non-rejection holders . . . . . . . 3-12

13/32˝ X 1 3/8˝ Fuses

Catalog numbers Volts PageBBS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 600V . . . . . . . . . . . . . . . 3-8

Holder• HPS-L panel mount holder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-53

Blocks• BCM panel/DIN-Rail with adapters . . . . . . . . . . . . . . . . . . . . . . . . . . 9-32• 4421 and 4515 single-pole fuse blocks . . . . . . . . . . . . . . . . . . . . . . 9-57

Automotive blade-type fuses

Catalog numbers Volts PageATC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Vdc . . . . . . . . . . . . . . 3-13ATM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Vdc . . . . . . . . . . . . . . 3-13MAX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Vdc . . . . . . . . . . . . . . 3-14

Holders• ATC: HHC, HHD, HHF, HHG and ATC-FHID In-line holders . . . . . . . . 3-13• ATM: HHL, HHM and ATM-FHID In-line holders . . . . . . . . . . . . . . . . 3-14• MAX: HHX, MAX-FHID In-line holders . . . . . . . . . . . . . . . . . . . . . . . 3-14

Pin indicating fuses

1/4˝ X 1 1/4˝ fuse catalog numbers VoltsPageGBA 1/4" X 1 1/4" . . . . . . . . . . . . . . . . . . . 125V . . . . . . . . . . . . . . . 3-8GLD 1/4" X 1 1/4" . . . . . . . . . . . . . . . . . . . 125V . . . . . . . . . . . . . . . 3-8MIC 13/32" X 1 1/2" . . . . . . . . . . . . . . . . . 250V . . . . . . . . . . . . . . . 3-9FNA 13/32" X 1 1/2˝ . . . . . . . . . . . . . . . . . 250V . . . . . . . . . . . . . . . 3-9MIS 13/32" X 2˝ . . . . . . . . . . . . . . . . . . . . 600V . . . . . . . . . . . . . . . 3-10

KAZ 13/32" X 2˝* . . . . . . . . . . . . . . . . . . . 600V . . . . . . . . . . . . . . . 3-10*Not a fuse. Pin actuator only.

Holders• 1/4" X 1/4": HLD panel mount visual indication . . . . . . . . . . . . . . . . 9-52• 1/4" X 1/4": HK panel mount lamp indicating. . . . . . . . . . . . . . . . . . . 9-52

Blocks• 1/4" X 1 1/4": 8000 for visual indication . . . . . . . . . . . . . . . . . . . . . 9-55• 13/32" X 1 1/2": 4-pole signal block cat. # 3839 (not shown in catalog)*

• 13/32" X 2˝: 1-pole signal block cat. # 2778 (not shown in catalog)*

• 13/32" X 2˝: 2-pole signal block cat. # 2837 (not shown in catalog)*

• 13/32" X 2˝: 3-pole signal block cat. # 2838 (not shown in catalog)*

HPS-L BCM

HLD

HK

8000

HHC, HHD, HHFand HHG

easy ID™illuminating holders

HHX

HLQ3 fuse holders HLR fuse holder

HHL andHHM

FWAHL
SmallO

3 Low voltage, supplementary fuses Cable limiters and welder limiters

K 600V UH 250V

250kcmil KCH

350kcmil KGJ',2

500kcmil KCM'"'"

600kcmil KCV

750kcmil KCR' '

1000kcmil KCS

KFT 250kcmil KFM'

750kcmil

2/OAWG 4/OAWG UHA

UHJ-M 3/OAWG 250kcmil

350kcmil 500kcmil UHJ-T

600kcmil 800kcmil UHJ-W

■ 64000 and 68000

Specifications: Description: Welder limiters.

Ratings:

Volts — 600Vac (or less) IR — 200kA RMS Sym.

Catalog numbers Catalog Fuse holder Nominal

type amp rating

Class H

300

Class H

600

64200 Class J 200

64300 Class J 300

KCF

*Tubular terminal and offset bolt-type terminal KQV #12 KDD 2/0

KQT #10 KDE 3/0

KFZ #8 KDF 4/0

KIG #6 KDH 250kcmil

KDY #4 KDJ• 350kcmil

KDA #2 KDM 1,S 500kcmil

KDB #1 KDU 600kcmil

KDC 1/0 750kcmil

*Compression connector rod and tubular terminals KEX 4/0 KQO 350kcmil

KFH-A 250kcmil KDT 500kcmil

**Center bolt-type terminal and off-set bolt-type terminal KPF 4/0 KDP' 500kcmil

KEW 350kcmil

Copper conductors only. **Copper or aluminum conductors.

'UL Listed (File E90818), 600Vac, 200k A I.R.. 'Available with shrink tube " V" suffix. •Available with molded rubber boots. Boot can be purchased separately, order Part# - BOOT-KCM.

Accessories Boots can be purchased separately.

For KCM BOOT-KCM For KDM BOOT-KDM

Installation tools can be purchased separately from Thomas and Betts

• Crimp Tool: TBM-14M • Die: 15506 KDM/15515 KDR

Data Sheet: 1042

Catalog numbers Center bolt-type terminal and off-set bolt-type terminal Catalog Copper cable Aluminum cable number size size

Features and benefits: • Current-limiting devices designed specially for use

on welder circuits only • Time-current characteristics are designed to hold

on the intermittent overloading encountered in welder operation, while providing short-circuit protection to the circuit and equipment

• Typical applications: • Welder circuits • Because welder limiters have special characteristics, they are

not intended for application on general-use circuits

Recommended fuse blocks for 68000 and 64000 limiters • See page 3-2

Data Sheet: 1045

Typical applications: • Protecting low voltage distribution and service entrance

cables against short-circuit currents. Catalog numbers

Catalog number

Typical applications: • Designed specifically for use in residental applications.

Catalog number

Cable size

*Tubular terminals KCY #4

KCZ #3

KCA #2

KCB #1

KCC 1/0

KCD1,2 2/0

KCE 3/0

4/0

Cable size

numbers 68300

68600

3-4 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.corn/bussmannseries

UHA

Cable . Limiter

UH.J.T ''.1.1110110if

1.10.0

Specifications: Description: Cable limiters.

Ratings:

Volts — up to 250Vac IR — 100kA RMS Sym.

Terminals: • Center bolt-to-offset bolt - copper or aluminum conductors.

Conductors: • Copper or aluminum conductors are permitted per the listed

cable size. Select the catalog symbol for the system conductor size. See data sheet 1042 for dimensions.

Specifications: Description: Cable limiters. Ratings:

Volts — 600Vac IR — 200kA RMS Sym.

600Vac Agency information: UL Listing: KDM, KDR, KDP and KFM, KCM, KCM-B and KCR.

Features and benefits: • Sizes and ratings available to

meet many applications.

3-4 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries

3 Low voltage, supplementary fusesCable limiters and welder limiters

K 600V

Specifications:Description: Cable limiters.Ratings:Volts — 600VacIR — 200kA RMS Sym.

@ 600VacAgency information: ULListing: KDM, KDR, KDP andKFM, KCM, KCM-B and KCR.

Features and benefits:• Sizes and ratings available tomeet many applications.

Typical applications:• Protecting low voltage distribution and service entrancecables against short-circuit currents.

Catalog numbersCatalog Cable Catalog Cablenumber size number size

*Tubular terminalsKCY #4 KCF 4/0

KCZ #3 KCH 250kcmil

KCA #2 KCJ1, 2 350kcmil

KCB #1 KCM1, 2, 3 500kcmil

KCC 1/0 KCV 600kcmil

KCD1, 2 2/0 KCR1, 2 750kcmil

KCE 3/0 KCS 1000kcmil

*Tubular terminal and offset bolt-type terminalKQV #12 KDD 2/0

KQT #10 KDE 3/0

KFZ #8 KDF 4/0

KIG #6 KDH 250kcmil

KDY #4 KDJ3 350kcmil

KDA #2 KDM1,3 500kcmil

KDB #1 KDU 600kcmil

KDC 1/0 KDR1,2 750kcmil

*Compression connector rod and tubular terminalsKEX 4/0 KQO 350kcmil

KFH-A 250kcmil KDT 500kcmil

**Center bolt-type terminal and off-set bolt-type terminalKPF 4/0 KDP1 500kcmil

KFT 250kcmil KFM1 750kcmil

KEW 350kcmil*Copper conductors only.**Copper or aluminum conductors.1UL Listed (File E90818), 600Vac, 200k A I.R..2Available with shrink tube “_V” suffix.3Available with molded rubber boots. Boot can be purchased separately, order Part# - BOOT-KCM.

AccessoriesBoots can be purchased separately.

For KCM BOOT-KCM For KDM BOOT-KDM

Installation tools can be purchased separately from Thomas and Betts• Crimp Tool: TBM-14M • Die: 15506 KDM/15515 KDR

Specifications:Description: Welder limiters.Ratings:Volts — 600Vac (or less)IR — 200kA RMS Sym.

Features and benefits:• Current-limiting devices designed specially for useon welder circuits only

• Time-current characteristics are designed to holdon the intermittent overloading encountered inwelder operation, while providing short-circuit protection to the circuit and equipment

• Typical applications:• Welder circuits• Because welder limiters have special characteristics, they arenot intended for application on general-use circuits

Catalog numbersCatalog Fuse holder Nominalnumbers type amp rating68300 Class H 300

68600 Class H 600

64200 Class J 200

64300 Class J 300

Data Sheet: 1042 Data Sheet: 1045

64000 and 68000

Recommended fuse blocks for 68000 and 64000 limiters• See page 3-2

UH 250V

Specifications:Description: Cable limiters.Ratings:Volts — up to 250VacIR — 100kA RMS Sym.

Terminals:• Center bolt-to-offset bolt – copper or aluminum conductors.

Conductors:• Copper or aluminum conductors are permitted per the listedcable size. Select the catalog symbol for the system conductor size. See data sheet 1042 for dimensions.

Typical applications:• Designed specifically for use in residental applications.

Catalog numbers

Center bolt-type terminal and off-set bolt-type terminalCatalog Copper cable Aluminum cablenumber size size

UHA 2/0AWG 4/0AWG

UHJ-M 3/0AWG 250kcmil

UHJ-T 350kcmil 500kcmil

UHJ-W 600kcmil 800kcmil

FWAHL
SmallO

KTK

Description:

Fast-acting supplemental fuse.

For superior protection, Eaton recommends upgrading to Bussmann series Low-PeakTM Class CC fuses. See data sheet # 1023.

Catalog symbol / color code:

• KTK - Black (600Vac maximum voltage)

Ratings:

Fuse amp range

600Vac UL CSA

1/10 to 30

100kA X X

Agency information:

• CE, RoHS compliant

• UL Listed, Std. 248-14, Guide JDYX, File E19180

• CSA Certified: C22.2 No. 248.14, Class 1422-01, File 53787, HRC-MISC

Catalog numbers (amps)

LE! 600Vac

FAST ACTAG FUSE

KTK-10

Interrupting rating Agency at rated voltage information

KTK-1/10

KTK-1/8

KTK-2/10

KTK-1/4

KTK-3/10

KTK-4/10

KTK-3/4

KTK-1

KTK-1-1/4

KTK-1-1/2

KTK-2

KTK-2-1/2

KTK-4

KTK-5

KTK-6

KTK-7

KTK-7-1/2

KTK-8

KTK-12

KTK-15

KTK-20

KTK-25

KTK-30

KTK-1/2 KTK-3 KTK-9

KTK-6/10 KTK-3-1/2 KTK-10

Low voltage, supplementary fuses

13/32" x 1 1/2" Fast-acting 3

BAF

Description:

Fast-acting, supplemental fuse.

For superior protection, Eaton recommends upgrading to Bussmann series Low-PeakTM Class CC fuses. See data sheet # 1023.

Catalog symbol — color code:

• BAF - Green (250Vac max 1/4 to 30A)

Ratings:

Interrupting rating Agency

at system voltage information

Fuse amp

250 125 range

Vac Vac UL CSA

1/4 to 1 35A 10kA X

1-1/2 to 2-1/2 100A 10kA X

3

100A 10kA X X

4 to 10 200A 10kA X X

12 to 15 750A 10kA X X

20 to 30 200A 10kA

Agency information:

• CE

• UL Listed, Std. 248-14, 250Vac (3 to 15A) Guide JDYX, File E19180

• CSA Certified, 250Vac (1/4 to 15A) Class 1422-01, File 53787

Catalog numbers (amps)

BAF-1/4 BAF-1-8/10 BAF-6 BAF-12

BAF-1/2 BAF-2 BAF-6-1/4 BAF-15

Features:

• Color coded green for 250Vac maximum voltage rating

• Fiber tube construction

• Nickel-plated brass endcaps.

Typical applications:

• General purpose circuits

• Lighting circuit protection

• Meter circuits

For superior electrical protection, Eaton recommends upgrading BAF fuse applications to Bussmann series Low-Peak LP-CC fuses See page 1-7.

Data Sheet: 2011 (0-30)

Features:

Color coded black for 600Vac voltage rating

• Fast-acting for resistive loads

• Melamine tube construction

• Nickel-plated bronze endcaps

Typical applications:

• Control circuits

• Lighting circuit protection

• Meter circuits

For superior electrical protection, Eaton recommends upgrading KTK fuse applications to Bussmann series Low-Peak LP-CC fuses See page 1-7.

Data Sheet: 1011

BAF-6/10 BAF-2-1/2 BAF-7 BAF-20

BAF-8/10 BAF-3 BAF-8 BAF-25

BAF-1

BAF-4

BAF-9

BAF-30

BAF-1-1/2 BAF-5

BAF-10

Recommended fuse blocks/fuse holders for 94 x 1 IC fuses • See page 3-2

BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.corn/bussmannseries 3-5 3-5

Low voltage

supplementary

fuses

3Low voltage, supplementary fuses13/32˝ x 1 1/2˝ Fast-acting

BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries

Recommended fuse blocks/fuse holders for 13⁄32˝ x 1 1⁄2˝ fuses• See page 3-2

Data Sheet: 1011Data Sheet: 2011 (0-30)

Description:

Fast-acting, supplemental fuse.

For superior protection, Eaton recommends upgrading to Bussmann series Low-Peak™ Class CC fuses. See data sheet # 1023.

Catalog symbol – color code:

• BAF - Green (250Vac max 1/4 to 30A)

Ratings:

Fuse amp range

Interrupting rating at system voltage

Agency information

250Vac

125Vac UL CSA

1/4 to 1 35A 10kA - X

1-1/2 to 2-1/2 100A 10kA - X

3 100A 10kA X X

4 to 10 200A 10kA X X

12 to 15 750A 10kA X X

20 to 30 200A 10kA - -

Agency information:• CE

• UL Listed, Std. 248-14, 250Vac (3 to 15A) Guide JDYX, File E19180

• CSA Certified, 250Vac (1/4 to 15A) Class 1422-01, File 53787

Catalog numbers (amps)

BAF-1⁄4 BAF-1-8⁄10 BAF-6 BAF-12

BAF-1⁄2 BAF-2 BAF-6-1⁄4 BAF-15

BAF-6⁄10 BAF-2-1⁄2 BAF-7 BAF-20

BAF-8⁄10 BAF-3 BAF-8 BAF-25

BAF-1 BAF-4 BAF-9 BAF-30

BAF-1-1⁄2 BAF-5 BAF-10

C

BAF

Description:

Fast-acting supplemental fuse.

For superior protection, Eaton recommends upgrading to Bussmann series Low-Peak™ Class CC fuses. See data sheet # 1023.

Catalog symbol / color code:

• KTK - Black (600Vac maximum voltage)

Ratings:

Fuse amp range

Interrupting rating at rated voltage

Agency information

600Vac UL CSA

1/10 to 30 100kA X X

Agency information:• CE, RoHS compliant

• UL Listed, Std. 248-14, Guide JDYX, File E19180

• CSA Certified: C22.2 No. 248.14, Class 1422-01, File 53787, HRC-MISC

Catalog numbers (amps)

KTK-1/10 KTK-3/4 KTK-4 KTK-12

KTK-1/8 KTK-1 KTK-5 KTK-15

KTK-2/10 KTK-1-1/4 KTK-6 KTK-20

KTK-1/4 KTK-1-1/2 KTK-7 KTK-25

KTK-3/10 KTK-2 KTK-7-1/2 KTK-30

KTK-4/10 KTK-2-1/2 KTK-8

KTK-1/2 KTK-3 KTK-9

KTK-6/10 KTK-3-1/2 KTK-10

Features:

• Color coded black for 600Vac voltage rating

• Fast-acting for resistive loads

• Melamine tube construction

• Nickel-plated bronze endcaps

Typical applications:

• Control circuits

• Lighting circuit protection

• Meter circuits

C

KTK

For superior electrical protection, Eaton recommends upgrading BAF fuseapplications to Bussmann series Low-Peak LP-CC fuses See page 1-7.

For superior electrical protection, Eaton recommends upgrading KTK fuseapplications to Bussmann series Low-Peak LP-CC fuses See page 1-7.

Features:

• Color coded green for 250Vac maximum voltage rating

• Fiber tube construction

• Nickel-plated brass endcaps.

Typical applications:

• General purpose circuits

• Lighting circuit protection

• Meter circuits

R

FWAHL
SmallO

3 Low voltage, supplementary fuses

13/32" x 1 1/2" Fast-acting

KLM

Description:

Fast-acting supplemental fuse.

For superior protection, Eaton recommends upgrading to Bussmann series Low-PeakTM Class CC fuses. See data sheet # 1023.

For protecting DC photovoltaic systems, Eaton recommends using Bussmann series PVM 10x3Omm PV fuses. See data sheet # 10121.

Catalog symbol / color code:

• KLM - Black (600Vac/dc maximum voltage)

Ratings:

600V FAsi.Arric

RAE

KLM-I5

Interrupting rating Agency

Fuse at rated voltage information

amp 600 600 range Vac Vdc UL CSA

1/10 to 30 100kA 50kA X X

Electrical characteristics:

% of amp rating Opening time

110% 4 Hours minimum

135% AC Opens within 1 hour

Agency information:

• CE, RoHS compliant

• UL Listed: Std. 248-14, Guide JDYX, File E19180

• CSA Certified, C22.2 No. 248. 14, Class 1422-01, File 53787

Catalog numbers (amps)

KLM-1/10 KLM-1 KLM-5 KLM-15

KLM-118 KLM-1-1/4 KLM-6 KLM-20

KLM-2/10 KLM-1-1/2 KLM-7 KLM-25

KLM-V4 KLM-2 KLM-8 KLM-30

KLM-3/10 KLM-2-12 KLM-9

KLM-12 KLM-3 KLM-10

KLM-3/4 KLM-4 KLM-12

Features:

• Color coded for 600Vac/dc

• A full range DC supplemental fuse

• Melamine tube construction

• Nickel-plated brass endcaps.

Recommended fuse blocks/fuse holders for 952"x 1 W fuses • See page 3-2

Data Sheet: 2020

34 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.corn/bussmannseries 3-6 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries

3 Low voltage, supplementary fuses13/32˝ x 1 1/2˝ Fast-acting

Data Sheet: 2020

Description:

Fast-acting supplemental fuse.

For superior protection, Eaton recommends upgrading to Bussmann series Low-Peak™ Class CC fuses. See data sheet # 1023.

For protecting DC photovoltaic systems, Eaton recommends using Bussmann series PVM 10x30mm PV fuses. See data sheet # 10121.

Catalog symbol / color code:

• KLM - Black (600Vac/dc maximum voltage)

Ratings:

Fuse amp range

Interrupting rating at rated voltage

Agency information

600Vac

600Vdc UL CSA

1/10 to 30 100kA 50kA X X

Electrical characteristics:

% of amp rating Opening time

110% 4 Hours minimum

135% AC Opens within 1 hour

Agency information:

• CE, RoHS compliant

• UL Listed: Std. 248-14, Guide JDYX, File E19180

• CSA Certified, C22.2 No. 248. 14, Class 1422-01, File 53787

Catalog numbers (amps)

KLM-1⁄10 KLM-1 KLM-5 KLM-15

KLM-1⁄8 KLM-1-1⁄4 KLM-6 KLM-20

KLM-2⁄10 KLM-1-1⁄2 KLM-7 KLM-25

KLM-1⁄4 KLM-2 KLM-8 KLM-30

KLM-3⁄10 KLM-2-1⁄2 KLM-9

KLM-1⁄2 KLM-3 KLM-10

KLM-3⁄4 KLM-4 KLM-12

Features:

• Color coded for 600Vac/dc

• A full range DC supplemental fuse

• Melamine tube construction

• Nickel-plated brass endcaps.

T

KLM

Recommended fuse blocks/fuse holders for 13⁄32˝ x 1 1⁄2˝ fuses• See page 3-2

FWAHL
SmallO

3

250Vac

yyl 10

4s

Low voltage, supplementary fuses

13/32" x 1 1/2" Time-delay

FNM

Description:

Time-delay supplemental fuse.

For superior protection, Eaton recommends upgrading to Bussmann series Low-PeakTM Class CC fuses. See data sheet # 1023.

Catalog symbol / color code:

• FNM - Green (250Vac maximum voltage)

Ratings:

Fuse amp range

Interrupting rating at system voltage

Agency information

250Vac 125Vac UL CSA

1/10 to 1 35A 10kA X X

1-1/8 to 3-1/2 100A 10kA X X

4 to 10 200A 10kA X X

12 to 30 10kA X X

Agency information:

• CE, RoHS complaint

• UL Listed, Std. 248-14, Guide JDYX; File E19180

• CSA Certified, Class 1422-01, File 53787

Catalog numbers (amps)

FNM-1/10 FNM-8/ 0 FNM-2-1/2 FNM-6-1/4

FNM-1i8 FNM-1 FNM-2-8/ 0 FNM-7

FNM-151 00 FNM-1-1i8 FNM-3 FNM-8

FNM-2/10 FNM-1-1/4 FNM-3-2/10 FNM-9

FNM-1/4 FNM-1-41 FNM-3-1/2 FNM-10

FNM-31 FNM-1-1/2 FNM-4 FNM-12

FNM-41 FNM-1-61 FNM-4-1/2 FNM-15

FNM-1/2

FNM-1-8/ 0 FNM-5 FNM-20

FNM-61 0

FNM-2 FNM-5-61 FNM-25

F N M-3/4 FNM-2-1/4 FNM-6 FNM-30

Features:

• Color coded green for 250Vac maximum voltage rating

• Melamine tube construction

• Nickel-plated brass endcaps

Typical applications:

• Circuits with high inrush currents (motor/transformer loads)

• Supplemental protection for 125Vac and 250Vac inductive circuits.

FNQ

Description:

Time-delay supplemental fuse.

For superior protection, Eaton recommends upgrading to Bussmann series FNQ-R Class CC fuses. See data sheet # 1014.

Catalog symbol / color code:

• FNQ - Orange (500Vac maximum voltage)

Interrupting rating Agency at rated voltage information

UL CSA

1/10 to 30 10kA

Agency information:

• CE, RoHS compliant*

• UL Listed, Std. 248-14, Guide JDYX, File E19180

• CSA Certified: C22.2 No. 248.14, Class 1422-01, File 53787, HRC-MISC RoHS

FNQ-1/8 not RoHS compliant.

Catalog numbers (amps)

FNQ-1/10

FNQ-8/10 FNQ-3-2/10 FNQ-9

FNQ-1/8

F NO-1

FNQ-3-1/2 FNQ-10

FNQ-15/100 FNQ-1-1/8 FNQ-4

FNQ-12

FNQ-3/16 FNQ-1-1/4 FNQ-4-1/2 FNQ-14

FNQ-2/10 FNQ-1-1/2 FNQ-5

FNQ-15

FNQ-1/4

FNQ-1-6/10 FNQ-5-6/10 FNQ-20

FNQ-3/10 FNQ-2 FNQ-6 FNQ-25

FNQ-4/10 FNQ-2-1/4 FNQ-6-1/4 FNQ-30

FNQ-1/2 FNQ-2-1/2 FNQ-7

FNQ-6/10 FNQ-3 FNQ-8

Features:

• Color coded for 500Vac maximum voltage rating

• Fiber tube construction

• Nickel-plated brass endcaps

Typical applications:

• Motor control transformers

• Circuits with in-rush currents.

Carton quantity

Amps Qty.

Ratings:

Fuse amp range 500Vac

For superior electrical protection, Eaton recommends upgrading FNM and FNQ fuse applications to Bussmann series Low-Peak LP-CC fuses See page 1-7.

Recommended fuse blocks and fuse holders for

152-x 1 1,4" fuses • See page 3-2

Data Sheet: 2028

1/10 to 30 10

For superior electrical protection, Eaton recommends upgrading FNM and FNQ fuse applications to Bussmann series Low-Peak LP-CC fuses See page 1-7.

Recommended fuse blocks and fuse holders for

1%2" x 1 1,4" fuses • See page 3-2

Data Sheet: 1012

BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.corn/bussmannseries 3.7 3-7

Low voltage

supplementary

fuses

3Low voltage, supplementary fuses13/32˝ x 1 1/2˝ Time-delay

BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries

Data Sheet: 2028 Data Sheet: 1012

For superior electrical protection, Eaton recommends upgrading FNM and FNQ fuse applications to Bussmann series Low-Peak LP-CC fuses See page 1-7.

Recommended fuse blocks and fuse holders for 13⁄32˝ x 1 1⁄2˝ fuses • See page 3-2

For superior electrical protection, Eaton recommends upgrading FNM and FNQ fuseapplications to Bussmann series Low-Peak LP-CC fuses See page 1-7.

Recommended fuse blocks and fuse holders for 13⁄32˝ x 1 1⁄2˝ fuses • See page 3-2

FNM FNQ

Description:

Time-delay supplemental fuse.

For superior protection, Eaton recommends upgrading to Bussmann series Low-Peak™ Class CC fuses. See data sheet # 1023.

Catalog symbol / color code:

• FNM - Green (250Vac maximum voltage)

Ratings:

Fuse amp range

Interrupting rating at system voltage

Agency information

250Vac 125Vac UL CSA

1/10 to 1 35A 10kA X X

1-1/8 to 3-1/2 100A 10kA X X

4 to 10 200A 10kA X X

12 to 30 10kA - X X

Agency information:

• CE, RoHS complaint

• UL Listed, Std. 248-14, Guide JDYX; File E19180

• CSA Certified, Class 1422-01, File 53787

Catalog numbers (amps)

FNM-1⁄10 FNM-8⁄10 FNM-2-1⁄2 FNM-6-1⁄4

FNM-1⁄8 FNM-1 FNM-2-8⁄10 FNM-7

FNM-15⁄100 FNM-1-1⁄8 FNM-3 FNM-8

FNM-2⁄10 FNM-1-1⁄4 FNM-3-2⁄10 FNM-9

FNM-1⁄4 FNM-1-4⁄10 FNM-3-1⁄2 FNM-10

FNM-3⁄10 FNM-1-1⁄2 FNM-4 FNM-12

FNM-4⁄10 FNM-1-6⁄10 FNM-4-1⁄2 FNM-15

FNM-1⁄2 FNM-1-8⁄10 FNM-5 FNM-20

FNM-6⁄10 FNM-2 FNM-5-6⁄10 FNM-25

FNM-3⁄4 FNM-2-1⁄4 FNM-6 FNM-30

Features:

• Color coded green for 250Vac maximum voltage rating

• Melamine tube construction

• Nickel-plated brass endcaps

Typical applications:

• Circuits with high inrush currents (motor/transformer loads)

• Supplemental protection for 125Vac and 250Vac inductive circuits.

C

Description:

Time-delay supplemental fuse.

For superior protection, Eaton recommends upgrading to Bussmann series FNQ-R Class CC fuses. See data sheet # 1014.

Catalog symbol / color code:

• FNQ - Orange (500Vac maximum voltage)

Ratings:

Fuse amp range

Interrupting rating at rated voltage

Agency information

500Vac UL CSA

1/10 to 30 10kA X X

Agency information:

• CE, RoHS compliant*

• UL Listed, Std. 248-14, Guide JDYX, File E19180

• CSA Certified: C22.2 No. 248.14, Class 1422-01, File 53787, HRC-MISC

* FNQ-1/8 not RoHS compliant.

Catalog numbers (amps)

FNQ-1/10 FNQ-8/10 FNQ-3-2/10 FNQ-9

FNQ-1/8 FNQ-1 FNQ-3-1/2 FNQ-10

FNQ-15/100 FNQ-1-1/8 FNQ-4 FNQ-12

FNQ-3/16 FNQ-1-1/4 FNQ-4-1/2 FNQ-14

FNQ-2/10 FNQ-1-1/2 FNQ-5 FNQ-15

FNQ-1/4 FNQ-1-6/10 FNQ-5-6/10 FNQ-20

FNQ-3/10 FNQ-2 FNQ-6 FNQ-25

FNQ-4/10 FNQ-2-1/4 FNQ-6-1/4 FNQ-30

FNQ-1/2 FNQ-2-1/2 FNQ-7

FNQ-6/10 FNQ-3 FNQ-8

Features:

• Color coded for 500Vac maximum voltage rating

• Fiber tube construction

• Nickel-plated brass endcaps

Typical applications:

• Motor control transformers

• Circuits with in-rush currents.

Carton quantity

Amps Qty.1/10 to 30 10

FWAHL
SmallO

Low voltage, supplementary fuses 13/32" x 1 3/8" Fast-acting and pin indication

3 BBS

EMI 600Vac

600Vac 1/10 to 6A

250Vac

250Vac 7 to 10A

48Vac 12 to 30A

Description:

Fast-acting supplemental fuse.

For superior protection, Eaton recommends upgrading to Bussmann series Low-PeakTM Class CC fuses. See data sheet # 1023.

Catalog symbol / color code:

• BBS - Black (600Vac max voltage 1/10 to 6A) - Green (250Vac max voltage 7 to 10A) - Purple (48Vac max voltage 12 to 30A)

Ratings:

Fuse amp range

1/10 to 6 7 to 10

Interrupting rating at Agency system voltage information

600 250 48 Vac Vac Vac UL CSA

101<A

X

X

10I<A

X

X

12 to 30*

* For interrupting rating, contact factory.

Agency information:

• CE

• UL Listed, Std. 248-14 (1/10-6A©600Vac, 7-10A@250Vac), Guide JDYX, File E19180

• CSA Certified, C22.2 No. 248.14 (1/10-6A@600Vac, 7-10A@250Vac), Class 1422-01, File 53787

Catalog numbers (amps)

BBS-1/10 BBS-8/10 BBS-4 BBS-15

BBS-2/10 BBS-1 BBS-5 BBS-20

BBS-1/4 BBS-1-1/2 BBS-6 BBS-25

BBS-4/10 BBS-1-6/10 BBS-7 BBS-30 BBS-1/2 BBS-1-8/10 BBS-8

BBS-6/10 BBS-2 BBS-10

BBS-3/4 BBS-3 BBS-12

Features:

• Color coded for 600Vac (black) 250Vac (green) and 48Vac (purple) for maximum voltage ratings

• Fiber tube construction

• Nickel-plated brass endcaps.

Typical applications:

• Control circuits • Electronic circuits

• Gaseous vapor fixtures • Hand-held meters

• HID ballasts

GBA

GLD Specifications: Class: Supplemental

Description: Fast-acting, pin indication fuse.

Dimensions: 1/4""x 1 "A- (6.6 x 31.7mm) 3AG.

Ratings:

Volts — See Agency Info below

Amps — X-15A

IR — See Agency Info below

Agency information: CE, Std. 248-14, UL Listed, 0-5N125Vac, 10,000 AIC, Guide JDYX, File E19180, UL Recognized, 6N125Vac, 1000AIC 8-15A/50Vac/dc, 300 AIC Guide JDYX2, File E19180, CSA Certified: 0-5N125Vac, 10,000 AIC Class 1422-01, File 53787.

Features and benefits: • Type GBA has a "red" pin indicator providing

visual identification of failed circuits, resulting in faster troubleshooting (reduced circuit downtime).

• Type GLD has a plated pin to activate transmitting a electrical signal to indicate the location of opened circuits, resulting in reduced downtime.

Typical applications: • Control circuits • Electronic circuits

GLD catalog numbers (amps) GLD-1,4 GLD-2 GLD-6

GLD 3/

GLD-3 GLD-10

GLD-1

GLD-4 GLD-12

GLD-1-1,4

GLD-5 GLD-15

GBA catalog numbers (amps) GBA-1,4 GBA-2 GBA-8

GBA-3%

GBA-3 GBA-10

GBA-1

GBA-4 GBA-15

GBA-1-1,4 GBA-5

Recommended fuse blocks/fuse holders for Wx 1 %-indicating fuses • Page 3-3

Data Sheet: 2012

Recommended fuse blocks/fuse holders for 94 x 1 fuses • Page 3-3

Data Sheet: 2010 (0-30A)

34 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.cornibussmannseries 3-8 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries

3 Low voltage, supplementary fuses13/32˝ x 1 3/8˝ Fast-acting and pin indication

Data Sheet: 2010 (0-30A)

Recommended fuse blocks/fuse holders for 13⁄32˝ x 1 3⁄8˝ fuses• Page 3-3

BBS

Description:

Fast-acting supplemental fuse.

For superior protection, Eaton recommends upgrading to Bussmann series Low-Peak™ Class CC fuses. See data sheet # 1023.

Catalog symbol / color code:

• BBS - Black (600Vac max voltage 1/10 to 6A) - Green (250Vac max voltage 7 to 10A) - Purple (48Vac max voltage 12 to 30A)

Ratings:

Fuse amp range

Interrupting rating at system voltage

Agency information

600Vac

250Vac

48Vac UL CSA

1/10 to 6 10kA - - X X

7 to 10 - 10kA - X X

12 to 30* - - - - -

* For interrupting rating, contact factory.

Agency information:• CE

• UL Listed, Std. 248-14 (1/10-6A@600Vac, 7-10A@250Vac), Guide JDYX, File E19180

• CSA Certified, C22.2 No. 248.14(1/10-6A@600Vac, 7-10A@250Vac), Class 1422-01, File 53787

Catalog numbers (amps)

BBS-1/10 BBS-8/10 BBS-4 BBS-15

BBS-2/10 BBS-1 BBS-5 BBS-20

BBS-1/4 BBS-1-1/2 BBS-6 BBS-25

BBS-4/10 BBS-1-6/10 BBS-7 BBS-30

BBS-1/2 BBS-1-8/10 BBS-8

BBS-6/10 BBS-2 BBS-10

BBS-3/4 BBS-3 BBS-12

Features:

• Color coded for 600Vac (black) 250Vac (green) and 48Vac (purple) for maximum voltage ratings

• Fiber tube construction

• Nickel-plated brass endcaps.

Typical applications:

• Control circuits

• Gaseous vapor fixtures

• HID ballasts

C

600Vac1/10 to 6A

250Vac7 to 10A

48Vac12 to 30A

• Electronic circuits

• Hand-held meters

Specifications:Class: SupplementalDescription: Fast-acting, pin indicationfuse.Dimensions: 1⁄4˝ x 1 1⁄4˝ (6.6 x 31.7mm) 3AG.Ratings:Volts — See Agency Info belowAmps — 1⁄2-15A

IR — See Agency Info belowAgency information: CE,Std. 248-14, UL Listed, 0-5A/125Vac, 10,000 AIC,Guide JDYX, File E19180, UL Recognized,6A/125Vac, 1000AIC 8-15A/50Vac/dc, 300 AICGuide JDYX2, File E19180, CSA Certified: 0-5A/125Vac, 10,000 AIC Class 1422-01, File 53787.

Features and benefits:• Type GBA has a “red” pin indicator providing visual identification of failed circuits, resulting infaster troubleshooting (reduced circuit downtime).

• Type GLD has a plated pin to activate transmittinga electrical signal to indicate the location of openedcircuits, resulting in reduced downtime.

Typical applications:• Control circuits• Electronic circuits

GLD catalog numbers (amps)GLD-1⁄2 GLD-2 GLD-6

GLD-3⁄4 GLD-3 GLD-10

GLD-1 GLD-4 GLD-12

GLD-1-1⁄2 GLD-5 GLD-15

GBA catalog numbers (amps)GBA-1⁄2 GBA-2 GBA-8

GBA-3⁄4 GBA-3 GBA-10

GBA-1 GBA-4 GBA-15

GBA-1-1⁄2 GBA-5

Data Sheet: 2012

GBA

GLD

Recommended fuse blocks/fuse holders for 1⁄4˝ x 1 1⁄4˝

indicating fuses

• Page 3-3

FWAHL
SmallO

3

250Vac

rm-2

AM&

250Vac 1/10 to 6A

'Ma* Ina

FNA-F2

, r -

Dual-tube construction 12A and up

32 Vac

250 Vac

35A

100A

200A

UL CSA

X

X

X

15 750A X

MIC

Description:

Fast-acting supplemental fuse.

Catalog symbol / color code:

• MIC - Green (250Vac max 1 to 15A) - Grey (32Vac max 20 to 30A)

250Vac 32Vac 1 to 15A

Ratings: 20 to 30A

Fuse amp range

1

2 to 3

5 to 10

Interrupting rating Agency at voltage rating information

250Vac

'Am

32Vac

FNA-1/10 FNA-1 FNA-3 FNA-9

FNA-1/8

F NA-15/100

FNA-2/10

FNA-1/4

FNA-3/10

FNA-4/10

FNA-1/2

FNA-1-1/8

FNA-1-1/4

FNA-1-4/10

FNA-1-1/2

FNA-1-6/10

FNA-1-8/10

FNA-2

FNA-3-2/10

FNA-3-1/2

FNA-4

FNA-4-1/2

FNA-5

FNA-5-6/10

FNA-6

FNA-10

FNA-12

F NA-15

FNA-20

FNA-25

FNA-30

FNA-6/10 FNA-2-1/4 FNA-6-1/4

FNA-3/4 FNA-2-1/2 FNA-7

FNA-8/10 FNA-2-8/10 FNA-8

Features:

Color coded by maximum voltage rating

• Pin indication for visual indication of open fuse condition

• Dual-element, time-delay performance permits close sizing on control transformers and relays

• Silver-plated pin for positive, electrical signal activation

• 12 amp and more versions are dual-tube construction

Recommended signal block for 'Yu" x 1 W indicating fuses • Page 3-3

Data Sheet: 2029

Low voltage, supplementary fuses

Pin indication

20 to 30 10kA

Electrical characteristics:

% of fuse rating Opening time

110% Indefinitely

135% 1 hour max.

Agency information:

• CE

• UL Listed, Std. 248-14, 1-15A, Guide JDYX, File E19180

Agency information:

• CE

• UL Listed 1/10 to 8/10A @ 125/250Vac, 1-15A @ 125Vac, Guide JDYX, File E19180

• CSA Certified 1/10 to 10A © 125Vac, Class 1422-01, File 53787

Catalog numbers (amps)

FNA Description:

Pin indicating time-delay supplemental fuse.

Catalog symbol / color code:

• FNA - Green (250Vac max voltage 1/10 to 6A) - Blue (125Vac max voltage 6-1/4 to 15A) - Grey (32Vac max voltage 20 to 30A)

Ratings:

Interrupting rating at Agency

Fuse system voltage information

amp

250 125 32 range Vac Vac Vac UL CSA

1/10 to

35A 10kA - X X 8/10

1 to 6 200A 10kA

6-1/4 to 15 - 101(A

20 to 30 - 11(A

Features:

Color coded by maximum voltage rating

Pin indication for visual indication of open fuse condition

Silver-plated pin for positive, electrical signal activation

Fiber tube construction

Nickel-plated bronze endcaps

Typical applications:

• Power electronic circuits in which fuse opening must be quickly apparent

• Control circuits

• PLC Circuits

Catalog numbers (amps)

MIC-1 MIC-8 MIC-25

MIC-2 MIC-10 MIC-30

MIC-3 MIC-15

MIC-5 MIC-20

Recommended signal block for, 'Yu" x 1 W indicating fuses • Page 3-3

Data Sheet: 10246

BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.corn/bussmannseries 3-9 3-9

Low voltage

supplementary

fuses

3Low voltage, supplementary fusesPin indication

BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries

Data Sheet: 2029Data Sheet: 10246

Recommended signal block for, 13⁄32˝ x 1 1⁄2˝ indicating fuses• Page 3-3

Recommended signal block for 13⁄32˝ x 1 1⁄2˝ indicating fuses • Page 3-3

MIC

Description:

Fast-acting supplemental fuse.

Catalog symbol / color code:

• MIC - Green (250Vac max 1 to 15A) - Grey (32Vac max 20 to 30A)

Ratings:

Fuse amp range

Interrupting rating at voltage rating

Agency information

250Vac

32Vac UL CSA

1 35A - X -

2 to 3 100A - X -

5 to 10 200A - X -

15 750A - X -

20 to 30 - 10kA - -

Electrical characteristics:

% of fuse rating Opening time110% Indefinitely

135% 1 hour max.

Agency information:• CE

• UL Listed, Std. 248-14, 1-15A, Guide JDYX, File E19180

Features:

• Color coded by maximum voltage rating

• Pin indication for visual indication of open fuse condition

• Silver-plated pin for positive, electrical signal activation

• Fiber tube construction

• Nickel-plated bronze endcaps

Typical applications:

• Power electronic circuits in which fuse opening must be quickly apparent

• Control circuits

• PLC Circuits

Catalog numbers (amps)

MIC-1 MIC-8 MIC-25

MIC-2 MIC-10 MIC-30

MIC-3 MIC-15 –

MIC-5 MIC-20 –

C

250Vac1 to 15A

32Vac20 to 30A

FNA

Description:

Pin indicating time-delay supplemental fuse.

Catalog symbol / color code:

• FNA - Green (250Vac max voltage 1/10 to 6A) - Blue (125Vac max voltage 6-1/4 to 15A) - Grey (32Vac max voltage 20 to 30A)

Ratings:

Fuseamprange

Interrupting rating at system voltage

Agency information

250Vac

125Vac

32Vac UL CSA

1/10 to 8/10

35A 10kA - X X

1 to 6 200A 10kA - X X

6-1/4 to 15 - 10kA - X X

20 to 30 - - 1kA - -

Agency information:

• CE

• UL Listed 1/10 to 8/10A @ 125/250Vac, 1-15A @ 125Vac, Guide JDYX, File E19180

• CSA Certified 1/10 to 10A @ 125Vac, Class 1422-01, File 53787

Catalog numbers (amps)

FNA-1/10 FNA-1 FNA-3 FNA-9

FNA-1/8 FNA-1-1/8 FNA-3-2/10 FNA-10

FNA-15/100 FNA-1-1/4 FNA-3-1/2 FNA-12

FNA-2/10 FNA-1-4/10 FNA-4 FNA-15

FNA-1/4 FNA-1-1/2 FNA-4-1/2 FNA-20

FNA-3/10 FNA-1-6/10 FNA-5 FNA-25

FNA-4/10 FNA-1-8/10 FNA-5-6/10 FNA-30

FNA-1/2 FNA-2 FNA-6

FNA-6/10 FNA-2-1/4 FNA-6-1/4

FNA-3/4 FNA-2-1/2 FNA-7

FNA-8/10 FNA-2-8/10 FNA-8

Features:

• Color coded by maximum voltage rating

• Pin indication for visual indication of open fuse condition

• Dual-element, time-delay performance permits close sizing on control transformers and relays

• Silver-plated pin for positive, electrical signal activation

• 12 amp and more versions are dual-tube construction

C

250Vac1/10 to 6A

Dual-tubeconstruction12A and up

FWAHL
SmallO

3

3 Low voltage, supplementary fuses Pin indication fuse, actuator and limiters

ANN and ANL Limiters

Specifications: Description: Circuit limiters. ANN: Very fast-acting limiter.

ANL: Non-time-delay limiter.

Dimensions: Vx 3 3/6" (22.2 x 81.0mm).

Ratings:

ANN:

Volts — 125Vac — 80Vdc

Amps — 10-800A

IR — 2500A @ 125Vac — 2700A @ 80Vdc

ANL:

Volts — 80Vdc

Amps — 35-750A

IR — 2700A @ 80Vdc Agency information:

ANN: 35-400A @ 125Vac, IR=2500A and 500A @ 80Vdc, IR=2700A: UL Recognized Guide JFHR2, File E56412; CSA Certified Class 1422-30, File 53787, CE for 35-400A. ANL: UL Recognized, CSA Certified, 35-750A @ 80Vdc, IR = 2700A, Guide JFHR2, File E56412, Class 1422-30, File 53787, SAE J1171.

Features and benefits: • Fast-acting circuit protection (ANN). • Time-delay sizing for inductive circuits (ANL). • Window shows limiter status.

Typical applications: • Fork lifts, marine, aviation

ANN catalog numbers (amps) ANN-10

ANN-90

ANN-225

ANN-400

ANN-35

ANN-100

ANN-250

ANN-500

ANN-40

ANN-125

ANN-275

ANN-600

ANN-50

ANN-150

ANN-300

ANN-700

ANN-60

ANN-175

ANN-325

ANN-800

ANN-80

ANN-200

ANN-350

MIS

Specifications: Class: Supplemental Description: Non time-delay pin indication fuse. Dimensions: 13,42-x

(10.3 x 50.8mm).

Ratings:

Volts — 600Vac Amps — 1-12A

IR — 200kA

Features and benefits: • Type MIS has a pin

indicator providing visual identification of failed circuits, resulting in faster troubleshooting (reduced circuit downtime).

• Type MIS can be used in circuits rated 600V or less.

• Type MIS has an interrupting rating of 200kA.

Typical applications: • 480V control circuits • PLC circuits

Catalog numbers (amps) MIS-1

MIS-4

MIS-10

MIS-2

MIS-5

MIS-12

MIS-3

MIS-8

Test specifications Fuse Load Opening time All

110% 4 hrs. (min.)

1-5A 150% 6 min. (max.)

6-12A

150% 12 min. (max.)

Recommended signal block for 1%2" x 2" indicating fuses

• Page 3-3

Data Sheet: 2021

KAZ

Specifications: Description: Non-fuse actuator. Dimensions: 13,42-x

(10.3 x 50.8mm).

Ratings:

Volts — 600Vac Amps — N/A

IR — 200kA

Agency information: CE, UL Listed, Guide JDVS, File E58836.

Features and benefits: • Bussmann series signal

blocks 2778, 2837 or 2838 with KAZ actuators mounted in parallel with fuses having a rating of 50A or larger to provide blown fuse dropout of shunt-trip fused switches.

• Type KAZ can be used in circuits rated 600V or less.

• Type KAZ has an interrupting rating of 200kA.

Typical applications: • Large, shunt-trip fused switches • Fuse protected circuits rated 50A or

larger with shunt-trip devices.

Catalog number: KAZ

Recommended signal block for 1%2" x T indicating fuses

• Page 3-3

Data Sheet: 2021

4164 and 4164-FR limiter blocks ANL catalog numbers (amps) ANL-35

ANL-125 ANL-250 ANL-500

ANL-40

ANL-130 ANL-275 ANL-600 ANL-50

ANL-150 ANL-300 ANL-675

ANL-60

ANL-175 ANL-325 ANL-750

ANL-80

ANL-200 ANL-350

ANL-100

ANL-225 ANL-400

Data Sheets: 2023 (ANN), 2024 (ANL)

Specifications Description: Limiter fuse blocks for ANL and ANN.

• 4164 furnished with nylon inserted locknuts • 4164-FR furnished with standard hex nuts Dimensions: Length: 3.38"

Width: 0.95" Height: 1.62"

Studs center to center: 2.43"

Data Sheet: 2133

Ratings:

Volts — 125Vac

— 80Vdc

— 32Vdc (self certified)

Amps — 10-800A

Poles: 1 - stud terminal

3-10 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries 3-10 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries

3 Low voltage, supplementary fusesPin indication fuse, actuator and limiters

Data Sheet: 2133

ANN and ANL Limiters

Specifications:Description: Circuit limiters.ANN: Very fast-acting limiter.ANL: Non-time-delay limiter.Dimensions: 7⁄8˝ x 3 3⁄16˝ (22.2 x 81.0mm).Ratings:ANN:Volts — 125Vac

— 80VdcAmps — 10-800A

IR — 2500A @ 125Vac— 2700A @ 80Vdc

ANL:Volts — 80VdcAmps — 35-750A

IR — 2700A @ 80VdcAgency information:ANN: 35-400A @ 125Vac, IR=2500Aand 500A @ 80Vdc, IR=2700A: ULRecognized Guide JFHR2, File E56412;CSA Certified Class 1422-30, File53787, CE for 35-400A.ANL: UL Recognized, CSA Certified,35-750A @ 80Vdc, IR = 2700A, GuideJFHR2, File E56412, Class 1422-30,File 53787, SAE J1171.

Features and benefits:• Fast-acting circuit protection (ANN).• Time-delay sizing for inductive circuits (ANL).• Window shows limiter status.

Typical applications:• Fork lifts, marine, aviation

ANN catalog numbers (amps)ANN-10 ANN-90 ANN-225 ANN-400

ANN-35 ANN-100 ANN-250 ANN-500

ANN-40 ANN-125 ANN-275 ANN-600

ANN-50 ANN-150 ANN-300 ANN-700

ANN-60 ANN-175 ANN-325 ANN-800

ANN-80 ANN-200 ANN-350

ANL catalog numbers (amps)ANL-35 ANL-125 ANL-250 ANL-500

ANL-40 ANL-130 ANL-275 ANL-600

ANL-50 ANL-150 ANL-300 ANL-675

ANL-60 ANL-175 ANL-325 ANL-750

ANL-80 ANL-200 ANL-350

ANL-100 ANL-225 ANL-400

4164 and 4164-FR limiter blocks

SpecificationsDescription: Limiter fuse blocks for ANL and ANN.• 4164 furnished with nylon inserted locknuts• 4164-FR furnished with standard hex nutsDimensions: Length: 3.38˝

Width: 0.95˝Height: 1.62˝

Studs center to center: 2.43˝

Ratings:Volts — 125Vac

— 80Vdc— 32Vdc (self certified)

Amps — 10-800A

Poles: 1 - stud terminal

KAZ

Specifications:Description: Non-fuse actuator.Dimensions: 13⁄32˝ x 2˝ (10.3 x 50.8mm).

Ratings:Volts — 600VacAmps — N/A

IR — 200kAAgency information:CE, UL Listed, GuideJDVS, File E58836.

Features and benefits:• Bussmann series signalblocks 2778, 2837 or 2838 with KAZ actuators mounted in parallel with fuses having a rating of 50A or larger to provide blown fuse dropout of shunt-trip fused switches.

• Type KAZ can be used in circuits rated600V or less.

• Type KAZ has an interrupting rating of200kA.

Typical applications:• Large, shunt-trip fused switches• Fuse protected circuits rated 50A orlarger with shunt-trip devices.

Catalog number: KAZ

MIS

Specifications:Class: SupplementalDescription: Non time-delay pin indication fuse.Dimensions: 13⁄32˝ x 2˝(10.3 x 50.8mm).

Ratings:Volts — 600VacAmps — 1-12A

IR — 200kAFeatures and benefits:• Type MIS has a pin indicator providing visualidentification of failed circuits, resulting in faster troubleshooting (reducedcircuit downtime).

• Type MIS can be used in circuits rated600V or less.

• Type MIS has an interruptingrating of 200kA.

Typical applications:• 480V control circuits• PLC circuits

Catalog numbers (amps)MIS-1 MIS-4 MIS-10MIS-2 MIS-5 MIS-12MIS-3 MIS-8

Test specificationsFuse Load Opening timeAll 110% 4 hrs. (min.)

1-5A 150% 6 min. (max.)

6-12A 150% 12 min. (max.)

Data Sheet: 2021

Data Sheets: 2023 (ANN), 2024 (ANL)

Recommended signal block for13⁄32˝ x 2˝ indicating fuses

• Page 3-3

Recommended signal block for 13⁄32˝ x 2˝ indicating fuses

• Page 3-3

Data Sheet: 2021

FWAHL
SmallO

Low voltage, supplementary fuses In-line size rejecting fuses and fuse holders

3 GLQ

Specifications: Class: Supplemental Description: Fast-acting, size-rejecting in-line fuse.

Construction: Glass tube. Ratings:

Volts — 300Vac (or less) Amps — 1-10A

IR — 10kA

Agency information: CE, UL Listed Std. 248-14, (Guide JDYX, File E19180), CSA Certified C22.2 No. 248.14, (Class 1422-01,File 53787).

Features and benefits: • In-line, fast-acting circuit protection. • Rejection feature prevents overfusing.

Typical applications: • In-line lighting ballast protection

Catalog numbers (amps) and rejection holders Fuse Holder'', 2

Fuse Holder'', 2

GLQ-1 HLQ-1-%

GLQ-3 HLQ-3-%

GLQ-1-1h HLQ-1-%

GLQ-4 HLQ-5

GLQ-1-% HLQ-1-%

GLQ-5 HLQ-5

GLQ-2 HLQ-3-%

GLQ-9 HLQ-10

GLQ-2 -16 HLQ-3

GLQ-10 HLQ-10

1) Carrier is UL Recognized, Guide IZLT2, File E14853 and CSA Certified, Class 6225-01, File 47235 10A, 300Vac.

2) Units can be panel-mounted either in a knockout hole with a separate steel clip (BK/A-104) or in a keyhole punch using separate mounting clip #6374 for panels of thickness 0.043"to 0.062" or #4909 for thickness 0.030" to 0.042".

• Do not put tension on line (rear) terminal of fuse holder.

Data Sheet: 2033

GMQ

Specifications: Class: Supplemental

Description: Time-delay, size-rejecting in-line fuse.

Construction: Ceramic tube.

Ratings:

Volts — 300Vac (or less)

Amps — IA-61/4A

IR — 10kA

Agency information: CE, UL Listed Std. 248-14, (Guide JDYX, File E19180), CSA Certified, (Class 1422-01, File 53787)

Features and benefits: • In-line, fast-acting circuit protection. • Rejection feature prevents overfusing.

Typical applications: • In-line lighting ballast protection

Catalog numbers (amps) and rejection holders Fuse Holders'', 2 Fuse Holders% 4 GMQ-1A HLQ-1A GMQ-2-1A HLQ-3-3So

GMQ- o HLQ-1-Vo GMQ-3 HLQ-3-350

GMQ -Yo HLQ-1-Vo GMQ-3 -Yo HLQ-3-3So

GMQ-1 HLQ-1-Vo GMQ-4 HLQ-5

GMQ-1-% HLQ-1-Vo GMQ-5 HLQ-5

GMQ-1-Vo HLQ-1-Vo GMQ-6-'''A HLQ-8

GMQ-2 HLQ-3

1) Carrier is UL Recognized, Guide IZLT2, File El 4853 and CSA Certified, Class 6225-01, File 47235 10A, 300Vac.

2) Units can be panel-mounted either in a knockout hole with a separate steel dip (BK/A-104) or in a keyhole punch using separate mounting dip #6374 for panels of thickness 0.043"to 0.062" or #4909 for thickness 0.030" to 0.042"

• Do not put tension on line (rear) terminal of fuse holder.

Data Sheet: 2030

H LQ3 fuse holders for both GLQ and GMQ fuses.

BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.corn/bussmannseries 3.11

GMQ

Specifications:Class: Supplemental

Description: Time-delay,size-rejecting in-line fuse.Construction: Ceramic tube.Ratings:Volts — 300Vac (or less)Amps — 1⁄2-61⁄4A

IR — 10kAAgency information: CE, UL Listed Std. 248-14, (GuideJDYX, File E19180), CSA Certified, (Class 1422-01, File 53787)

Features and benefits:• In-line, fast-acting circuit protection.• Rejection feature prevents overfusing.

Typical applications:• In-line lighting ballast protection

Catalog numbers (amps) and rejection holdersFuse Holders1, 2 Fuse Holders3, 4

GMQ-1⁄2 HLQ-1⁄2 GMQ-2-1⁄2 HLQ-3-2⁄10

GMQ-6⁄10 HLQ-1-6⁄10 GMQ-3 HLQ-3-2⁄10

GMQ-8⁄10 HLQ-1-6⁄10 GMQ-3-2⁄10 HLQ-3-2⁄10

GMQ-1 HLQ-1-6⁄10 GMQ-4 HLQ-5

GMQ-1-1⁄4 HLQ-1-6⁄10 GMQ-5 HLQ-5

GMQ-1-6⁄10 HLQ-1-6⁄10 GMQ-6-1⁄4 HLQ-8

GMQ-2 HLQ-3-2⁄101) Carrier is UL Recognized, Guide IZLT2, File E14853 and CSA Certified, Class 6225-01, File 47235

10A, 300Vac.2) Units can be panel-mounted either in a knockout hole with a separate steel clip (BK/A-104) or in a

keyhole punch using separate mounting clip #6374 for panels of thickness 0.043”to 0.062” or #4909for thickness 0.030” to 0.042”

• Do not put tension on line (rear) terminal of fuse holder.

3-11

3Low voltage, supplementary fusesIn-line size rejecting fuses and fuse holders

BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries

Data Sheet: 2030Data Sheet: 2033

HLQ3 fuse holders

for both GLQ and GMQ fuses.

GLQ

Specifications:Class: SupplementalDescription: Fast-acting,size-rejecting in-line fuse.Construction: Glass tube.Ratings:Volts — 300Vac (or less)Amps — 1-10A

IR — 10kAAgency information: CE, UL Listed Std. 248-14, (GuideJDYX, File E19180), CSA Certified C22.2 No. 248.14, (Class 1422-01,File 53787).

Features and benefits:• In-line, fast-acting circuit protection.• Rejection feature prevents overfusing.

Typical applications:• In-line lighting ballast protection

Catalog numbers (amps) and rejection holdersFuse Holder1, 2 Fuse Holder1, 2

GLQ-1 HLQ-1-6⁄10 GLQ-3 HLQ-3-2⁄10GLQ-1-1⁄2 HLQ-1-6⁄10 GLQ-4 HLQ-5GLQ-1-6⁄10 HLQ-1-6⁄10 GLQ-5 HLQ-5GLQ-2 HLQ-3-2⁄10 GLQ-9 HLQ-10GLQ-2-1⁄2 HLQ-3 -2⁄10 GLQ-10 HLQ-10

1) Carrier is UL Recognized, Guide IZLT2, File E14853 and CSA Certified, Class 6225-01, File 4723510A, 300Vac.

2) Units can be panel-mounted either in a knockout hole with a separate steel clip (BK/A-104) or in akeyhole punch using separate mounting clip #6374 for panels of thickness 0.043”to 0.062” or #4909for thickness 0.030” to 0.042”.

• Do not put tension on line (rear) terminal of fuse holder.

Low voltage

supplementary

fuses

FWAHL
SmallO

3 Low voltage, supplementary fuses In-line non-rejecting fuses and fuse holders

GLR

Specifications: Class: Supplemental

Description: Fast-acting, non-rejection, in-line fuse.

Construction: Glass tube.

Ratings:

Volts — 300Vac (or less)

Amps — 346-15A

IR — 10kA

Agency information: CE, UL Listed Std. 248-14, 0-15A/300Vac (Guide JDYX, File E19180), CSA Certified C22.2, No. 248-14, 0-10A/300V (Class 1422-01, File 53787).

Features and benefits: • In-line, fast-acting circuit protection.

Typical applications: • In-line lighting ballast protection

Catalog numbers (amps) and non-rejection holders Fuse Holder'', 2* Fuse Holder'', 2* GLR-1 HLR GLR-6 HLR GLR-1 HLR GLR-7 HLR GLR-1-1h HLR GLR-8 HLR GLR-1 -13Ao HLR GLR-9 HLR GLR-2 HLR GLR-10 HLR GLR-3 HLR GLR-12 HLR GLR-4 HLR GLR-15 HLR-2A GLR-5 HLR

1) Carrier is UL Recognized, Guide IZLT2, File E14853 and CSA Certified, Class 6225-01, File 47235 12A, 300Vac.

2) Units can be panel-mounted either in a knockout hole with a separate steel clip (BK/A-104) or in a keyhole punch using separate mounting clip #6374 for panels of thickness 0.043"to 0.062" or #4909 for thickness 0.030" to 0.042".

• For two leads (one each for line and loadside) order HLR-2A, 15A, 300V

• An alternative to the HLR fuse holder is the A fuse holder. The A fuse holder comes WITHOUT leads. The customer inserts #18 insulated solid copper wire into the line side receptacle as well as into the load side receptacle. It has the same body dimensions, utilizes the same mounting hole, and takes the same mounting clips as the HLR. The A fuse holder is UL Recognized, 10A, 300Vac, Guide IZLT2, File E14853 and CSA Certified, 10A, 300Vac, Class 6225-01, File 47235.

• Do not put tension on line (rear) terminal of fuse holder.

Data Sheet: 2032

GMF

GRF

Specifications: Class: Supplemental

Description: Time-delay, non-rejection, in-line fuse.

Construction: Glass tube.

Ratings:

Volts — 300Vac (or less)

Amps — 3/0-10A

IR — 10kA

Agency information: CE, UL Listed Std. 248-14 0-10A, (Guide JDYX, File E19180), CSA Certified, (Class 1422-01, File 53787).

Features and benefits: • In-line, time-delay circuits protection.

Typical applications: • In-line lighting ballast protection

Catalog numbers (amps) and non-rejection holders Fuse Holder'', 2* Fuse Holder'', 2* GMF-3A0 HLR GMF-3 HLR GMF-1 HLR GMF-3-2Ao HLR GMF-°Ao HLR GMF-4 HLR GMF-8A0 HLR GMF-5 HLR GMF-1 HLR GMF-6-14 HLR GMF-1 '/a HLR GMF-7 HLR GMF-1 -% HLR GRF-8 HLR GMF-2 HLR GMF-10 HLR GMF-2-1/6 HLR GRF-10 HLR GMF-2-8Ao HLR

1) Carrier is UL Recognized, Guide IZLT2, File E14853 and CSA Certified, Class 6225-01, File 47235 12A, 300Vac.

2) Units can be panel-mounted either in a knockout hole with a separate steel clip (8K/A-104) or in a keyhole punch using separate mounting clip #6374 for panels of thickness 0.043"to 0.062" or #4909 for thickness 0.030" to 0.047.

*For two leads order HLR-2A, 15A, 300V

• An alternative to the HLR fuse holder is the A fuse holder. The A fuse holder comes WITHOUT leads. The customer inserts #18 insulated solid copper wire into the line side receptacle as well as into the load side receptacle. It has the same body dimensions, utilizes the same mounting hole, and takes the same mounting clips as the HLR. The A fuse holder is UL Recognized, 10A, 300Vac, Guide IZLT2, File 814853 and CSA Certified, 10A, 300Vac, Class 6225-01, File 47235.

• Do not put tension on line (rear) terminal of fuse holder.

Data Sheet: 2031

HLR-2A fuse holder HLR fuse holder

3-12 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.corn/bussmannseries 3-12 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries

3 Low voltage, supplementary fusesIn-line non-rejecting fuses and fuse holders

GLR

Specifications:Class: SupplementalDescription: Fast-acting,non-rejection, in-line fuse.Construction: Glass tube.Ratings:Volts — 300Vac (or less)Amps — 3⁄16-15A

IR — 10kAAgency information: CE, UL Listed Std. 248-14, 0-15A/300Vac (Guide JDYX, File E19180), CSA CertifiedC22.2, No. 248-14, 0-10A/300V (Class 1422-01, File 53787).

Features and benefits:• In-line, fast-acting circuit protection.

Typical applications:• In-line lighting ballast protection

Catalog numbers (amps) and non-rejection holdersFuse Holder1, 2* Fuse Holder1, 2*

GLR-1⁄2 HLR GLR-6 HLRGLR-1 HLR GLR-7 HLRGLR-1-1⁄2 HLR GLR-8 HLRGLR-1-6⁄10 HLR GLR-9 HLRGLR-2 HLR GLR-10 HLRGLR-3 HLR GLR-12 HLRGLR-4 HLR GLR-15 HLR-2AGLR-5 HLR

1) Carrier is UL Recognized, Guide IZLT2, File E14853 and CSA Certified, Class 6225-01,File 47235 12A, 300Vac.

2) Units can be panel-mounted either in a knockout hole with a separate steel clip (BK/A-104) or in a keyhole punch using separate mounting clip #6374 for panels ofthickness 0.043”to 0.062” or #4909 for thickness 0.030˝ to 0.042˝.

* For two leads (one each for line and loadside) order HLR-2A,15A, 300V

• An alternative to the HLR fuse holder is the A fuse holder. The A fuse holder comesWITHOUT leads. The customer inserts #18 insulated solid copper wire into the line sidereceptacle as well as into the load side receptacle. It has the same body dimensions,utilizes the same mounting hole, and takes the same mounting clips as the HLR. The Afuse holder is UL Recognized, 10A, 300Vac, Guide IZLT2, File E14853 and CSACertified, 10A, 300Vac, Class 6225-01, File 47235.

• Do not put tension on line (rear) terminal of fuse holder.

GMF

GRF

Specifications:Class: SupplementalDescription: Time-delay, non-rejection, in-line fuse.Construction: Glass tube.Ratings:Volts — 300Vac (or less)Amps — 3⁄10-10A

IR — 10kAAgency information: CE, UL Listed Std. 248-14 0-10A,(Guide JDYX, File E19180), CSA Certified, (Class 1422-01, File53787).

Features and benefits:• In-line, time-delay circuits protection.

Typical applications:• In-line lighting ballast protection

Catalog numbers (amps) and non-rejection holdersFuse Holder1, 2* Fuse Holder1, 2*

GMF-3⁄10 HLR GMF-3 HLRGMF-1⁄2 HLR GMF-3-2⁄10 HLRGMF-6⁄10 HLR GMF-4 HLRGMF-8⁄10 HLR GMF-5 HLRGMF-1 HLR GMF-6-1⁄4 HLRGMF-1-1⁄4 HLR GMF-7 HLRGMF-1-6⁄10 HLR GRF-8 HLRGMF-2 HLR GMF-10 HLRGMF-2-1⁄2 HLR GRF-10 HLRGMF-2-8⁄10 HLR

1) Carrier is UL Recognized, Guide IZLT2, File E14853 and CSA Certified, Class 6225-01, File 4723512A, 300Vac.

2) Units can be panel-mounted either in a knockout hole with a separate steel clip (BK/A-104) or in akeyhole punch using separate mounting clip #6374 for panels of thickness 0.043”to 0.062” or #4909for thickness 0.030˝ to 0.042˝.

*For two leads order HLR-2A, 15A, 300V

• An alternative to the HLR fuse holder is the A fuse holder. The A fuse holder comes WITHOUT leads.The customer inserts #18 insulated solid copper wire into the line side receptacle as well as into theload side receptacle. It has the same body dimensions, utilizes the same mounting hole, and takesthe same mounting clips as the HLR. The A fuse holder is UL Recognized, 10A, 300Vac, GuideIZLT2, File E14853 and CSA Certified, 10A, 300Vac, Class 6225-01, File 47235.

• Do not put tension on line (rear) terminal of fuse holder.

Data Sheet: 2032 Data Sheet: 2031

HLR fuse holderHLR-2A fuse holder

FWAHL
SmallO

Available with

indication

LED indicator

Low voltage, supplementary fuses Automotive blade-type fuses and holders

3 ATC fuse

(actual size)

Specifications: Description: Fast-acting blade fuse.

Construction: Colored plastic housing with zinc fuse element.

Ratings:

Volts — 32Vdc

Amps — 1-40A

IR — 1000A

Agency information: UL Recognized, (1-40A) (Guide JFHR2, File E56412), SAE Standard J1284.

Features and benefits: • Color coded plastic housing for

easy identification of fuse ratings Typical applications: • Automotive

Catalog numbers (amps)

Non-indicating *Indicating Color

ATC-1

Black

ATC-2

ATC-3

ATC-31D

ATC-4

ATC-5

ATC-5ID

ATC-7-1/2 ATC-7-1/21D Brown

ATC-1 0 ATC-101D Red

ATC-15 ATC-151D Blue

ATC-20 ATC-201D Yellow

ATC-25 ATC-251D Clear

ATC-30 ATC-301D Green

ATC-35

ATC-351D Blue-Green

ATC-40 ATC-401D

Orange

*Call Eaton customer satisfaction for ordering information.

Data Sheet: 2009

HHA, HHC, HHD, HHF, HHG, HHR, HHS and ATC-FHID

easylDTM' LED indicating holder

Specifications:

Description: In-line fuse holders for ATC- blade-type fuses.

Dimensions: See dimensions illustration.

Ratings:

Volts: — 32Vdc

Amps: — 80% continuous of fuse rating. See catalog numbers table for individual fuses sizes.

Catalog numbers Catalog Fuse holder

Fuse Electrical

numbers description amps connection

1-40 #16 red leadwire

1-20 #16 black leadwire

1-30 #12 yellow leadwire

1-20 #16 yellow leadwire

1-30 #12 yellow leadwire

1-30 #12 red leadwire

1-20 #18 to 14 black leadwire

1-20 #16 black leadwire

A fuse must be properly and fully inserted into the holder to provide a solid connection. Poor or improper insertion of the fuse can result in failure of the fuse and holder, thus not protecting the device for which it was intended.

HHC and HHD dimensions - in

Data Sheet: 2107

ATM fuse

Available with

indication

(actual size) ATM

ATM-LP

Specifications: Description: Fast-acting blade fuse.

Construction: Colored plastic housing with zinc fuse element.

Ratings:

Volts — 32Vdc

Amps — 1-30A

IR — 1000A

Agency information: UL Listed Guide FHXT, File AU 169 (2-30A non-indicating ATM).

Features and benefits: • Color coded plastic housing for easy

identification of fuse ratings Typical applications: • Automotive

Catalog numbers (amps)

Non-indicating *Indicating Low-profile Color

ATM-1

ATM-2

ATM-3

ATM-31D

ATM-4

ATM-5

ATM-5ID

ATM-5LP

ATM-7-'/

ATM-7-'/ID

ATM-7-'/LP

ATM-10

ATM-101D

ATM-10LP

ATM-15

ATM-15ID

ATM-15LP

ATM-20

ATM-201D

ATM-20LP

ATM-25

ATM-251D

ATM-25LP

ATM-30

ATM-301D

ATM-30LP

*Call Eaton customer satisfaction for ordering information.

Data Sheet: 2048 (ATM), 2050 (ATM-LP)

Gray

Violet

Pink

Tan

ATC-FHID

HHA

HHC

HHD

HHF

HHG

HHR

HHS

Black w/ cover

Yellow

Black

Black w/ cover

Black w/ cover

Black w/ cover

Blue w/ cover

Indicating holder Black w/ cover

Black

Gray

Violet

Pink

Tan

Brown

Red

Blue

Yellow

Clear

Green

BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.corn/bussmannseries 3-13 3-13

Low voltage

supplementary

fuses

3Low voltage, supplementary fusesAutomotive blade-type fuses and holders

BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries

Specifications:Description: Fast-acting blade fuse.Construction: Colored plastichousing with zinc fuse element.Ratings:Volts — 32VdcAmps — 1-40A

IR — 1000AAgency information: ULRecognized, (1-40A) (GuideJFHR2, File E56412), SAE StandardJ1284.

Features and benefits:• Color coded plastic housing foreasy identification of fuse ratings

Typical applications:• Automotive

Catalog numbers (amps)

Data Sheet: 2048 (ATM), 2050 (ATM-LP)Data Sheet: 2009

(actual size)

ATC fuse ATM fuse

Specifications:Description: Fast-acting blade fuse.Construction: Colored plastic housingwith zinc fuse element.Ratings:Volts — 32VdcAmps — 1-30A

IR — 1000AAgency information: UL Listed GuideFHXT, File AU 169 (2-30A non-indicatingATM).

Features and benefits:• Color coded plastic housing for easyidentification of fuse ratings

Typical applications:• Automotive

Catalog numbers (amps)

ATM(actual size)

ATM-LP

Non-indicating *Indicating Color

ATC-1 — Black

ATC-2 — Gray

ATC-3 ATC-3ID Violet

ATC-4 — Pink

ATC-5 ATC-5ID Tan

ATC-7-1/2 ATC-7-1/2ID Brown

ATC-10 ATC-10ID Red

ATC-15 ATC-15ID Blue

ATC-20 ATC-20ID Yellow

ATC-25 ATC-25ID Clear

ATC-30 ATC-30ID Green

ATC-35 ATC-35ID Blue-Green

ATC-40 ATC-40ID Orange

Availablewith

indication

Availablewith

indication

Non-indicating *Indicating Low-profile Color

ATM-1 — — Black

ATM-2 — — Gray

ATM-3 ATM-3ID — Violet

ATM-4 — — Pink

ATM-5 ATM-5ID ATM-5LP Tan

ATM-7-1/2 ATM-7-1/2ID ATM-7-1/2LP Brown

ATM-10 ATM-10ID ATM-10LP Red

ATM-15 ATM-15ID ATM-15LP Blue

ATM-20 ATM-20ID ATM-20LP Yellow

ATM-25 ATM-25ID ATM-25LP Clear

ATM-30 ATM-30ID ATM-30LP Green0.78"

0.91"0.5"

0.38" 0.30"

4.0" + 0.25" 4.0" + 0.25"1.125"

0.364"

0.25"

Data Sheet: 2107

Specifications:Description: In-line fuse holders forATC™ blade-type fuses.Dimensions: See dimensionsillustration.Ratings:Volts: — 32VdcAmps:— 80% continuous of fuse

rating. See catalog numberstable for individual fuses sizes.

Catalog numbersCatalog Fuse holder Fuse Electricalnumbers description amps connection

HHA Black w/ cover 1-40 #16 red leadwire

HHC Yellow 1-20 #16 black leadwire

HHD Black 1-30 #12 yellow leadwire

HHF Black w/ cover 1-20 #16 yellow leadwire

HHG Black w/ cover 1-30 #12 yellow leadwire

HHR Black w/ cover 1-30 #12 red leadwire

HHS Blue w/ cover 1-20 #18 to 14 black leadwire

ATC-FHIDIndicating holder

1-20 #16 black leadwireBlack w/ cover

A fuse must be properly and fully inserted into the holder toprovide a solid connection. Poor or improper insertion of thefuse can result in failure of the fuse and holder, thus notprotecting the device for which it was intended.

HHC and HHD dimensions - in

HHA, HHC, HHD, HHF,HHG, HHR, HHS and ATC-FHID

easy ID™ LED indicating holder

LED indicator

*Call Eaton customer satisfaction for ordering information.

*Call Eaton customer satisfaction for ordering information.

FWAHL
SmallO

LED indicator

Available with

indication

3 Low voltage, supplementary fuses Automotive blade-type fuses and holders

HHH, HHL, HHLP, HHM and ATM-FHID

easylDTM' LED indicating holder

Specifications:

Description: In-line fuse holders for ATM Fuses.

Ratings:

Volts: — 32Vdc

Amps: — 80% continuous of fuse rating. See catalog numbers table for individual fuses sizes.

Catalog numbers Catalog Fuse holder Fuse Electrical numbers description amps connection HHH Black w/ cover 1-30 #16 black le-edwire,

5- length

HHL Black w/ cover 1-20 #16 black leadwire, 4" length stripped to '/,,-

HHLP Black w/ cover 1-30 #16 black le-edwire,

5- length

HHM Black w/ cover 1-30 #12 red leadwire, 4" length stripped to 1/4-

HHU Black w/ cover 1-30 #16 black le-edwire,

Indicating holder ATM-FHID

1-20 #16 black le-edwire Black w/ cover

A fuse must be properly and fully inserted into the holder to provide a solid connection. Poor or improper insertion of the fuse can result in failure of the fuse and holder, thus not protecting the device for which it was intended.

HHL and HHM dimensions - in

156"

MAX Maxi-fuse

(actual size)

Specifications: Description: Fast-acting blade fuse.

Construction: Colored plastic housing with zinc fuse element.

Ratings:

Volts — 32Vdc

Amps — 20-80A (non-indicating) 20-100A (indicating)

IR — 1000A

Features and benefits: • Color coded plastic housing for easy

identification of fuse ratings Typical applications: • Automotive

Catalog numbers (amps)

Non-indicating *Indicating Color

MAX-20 MAX-201D Yellow

MAX-25 — Gray

MAX-30 MAX-301D Green

MAX-35 — Brown

MAX-40 MAX-401D Orange

MAX-50 MAX-501D Red

MAX-60 MAX-601D Blue

MAX-70 MAX-701D Tan

MAX-80 MAX-801D Clear

— MAX-1001D Purple

*Cal I Eaton customer satisfaction for ordering information.

HHX, MAX-FHID

Specifications:

Description: In-line fuse holders for MAXI Fuses.

Ratings:

Volts: — 32Vdc

Amps: — 80% continuous of fuse rating. See catalog numbers table for individual fuses sizes.

Catalog numbers Catalog Fuse holder Fuse Electrical numbers description amps connection HHX Black w/ cover 20-60 #6 red leadwire,

5 with blunt ends MAX-FHID Indicator black 20-60 #6 red leadwire,

w/ cover 5-with blunt ends

A fuse must be properly and fully inserted into the holder to provide a solid connection. Poor or improper insertion of the fuse can result in failure of the fuse and holder, thus not protecting the device for which it was intended.

Dimensions - in

s.s5"

0— J 6 70" 6 7014

1.37"

265" DIA. HOLE

(le ED III—,

// 25.

4.75"

4.75

Data Sheet: 2128

Recommended in-line fuse holder for

blade type fuses

• Page 3-15 Data Sheet: 2129

3-14 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.corn/bussmannseries 3-14

Data Sheet: 2129Data Sheet: 2128

Specifications:Description: In-line fuse holders forATM Fuses.Ratings:Volts: — 32VdcAmps: — 80% continuous of fuse

rating. See catalog numberstable for individual fuses sizes.

Catalog numbersCatalog Fuse holder Fuse Electricalnumbers description amps connectionHHH Black w/ cover 1-30 #16 black leadwire,

5˝ length

HHL Black w/ cover 1-20 #16 black leadwire,

4˝ length stripped to 1/4˝

HHLP Black w/ cover 1-30 #16 black leadwire,

5˝ length

HHM Black w/ cover 1-30 #12 red leadwire,

4˝ length stripped to 1/4˝

HHU Black w/ cover 1-30 #16 black leadwire,

ATM-FHIDIndicating holder

1-20 #16 black leadwireBlack w/ cover

A fuse must be properly and fully inserted into the holder toprovide a solid connection. Poor or improper insertion of thefuse can result in failure of the fuse and holder, thus notprotecting the device for which it was intended.

HHL and HHM dimensions - in

Specifications:Description: In-line fuse holders forMAXI Fuses.Ratings:Volts: — 32VdcAmps: — 80% continuous of fuse

rating. See catalog numberstable for individual fuses sizes.

Catalog numbersCatalog Fuse holder Fuse Electricalnumbers description amps connectionHHX Black w/ cover 20-60 #6 red leadwire,

5˝ with blunt ends

MAX-FHID Indicator black 20-60 #6 red leadwire,

w/ cover 5˝ with blunt ends

A fuse must be properly and fully inserted into the holder toprovide a solid connection. Poor or improper insertion of thefuse can result in failure of the fuse and holder, thus notprotecting the device for which it was intended.

Dimensions - in

HHX, MAX-FHIDHHH, HHL, HHLP, HHMand ATM-FHID

1.56"

4.75" 4.75" .25" .25"

.59"

.41"

3.35"

6.70" 6.70"

1.37"

.265" DIA. HOLE

easy ID™ LED indicating holder

LED indicator(actual size)

MAX Maxi–fuse

Specifications:Description: Fast-acting blade fuse.Construction: Colored plastic housingwith zinc fuse element.Ratings:Volts — 32VdcAmps — 20-80A (non-indicating)

20-100A (indicating)IR — 1000A

Features and benefits:• Color coded plastic housing for easy identification of fuse ratings

Typical applications:• Automotive

Catalog numbers (amps)

Recommended in-line fuse holder for

blade type fuses

• Page 3-15

Availablewith

indication

Non-indicating *Indicating Color

MAX-20 MAX-20ID Yellow

MAX-25 — Gray

MAX-30 MAX-30ID Green

MAX-35 — Brown

MAX-40 MAX-40ID Orange

MAX-50 MAX-50ID Red

MAX-60 MAX-60ID Blue

MAX-70 MAX-70ID Tan

MAX-80 MAX-80ID Clear

— MAX-100ID Purple

BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries

3 Low voltage, supplementary fusesAutomotive blade-type fuses and holders

*Call Eaton customer satisfaction for ordering information.

FWAHL
SmallO

T-

FUSECLIPS

8.64 0.340

, 7 0.144

I

1.65 .0.05 0.065 .0.002 DIA. HOLE (TYP-4)

MOUNTING LAYOUT

r 3.66 4.47 3.66 0.1767 0.144 7

ATR-25

ATR-30

Clear

Green

DIA. HOLE 2.54 .0.05 0.100 .0.002

(TYP-4)

MOUNTING LAYOUT

4.06 0.160

Low voltage, supplementary fuses Automotive blade-type fuses and PCB fuseclips

3 ATR micro fuse

Specifications: Description: Fast-acting color coded 2-leg micro blade fuse.

Construction: Colored plastic housing with zinc fuse element. Ratings:

Volts - 32Vdc

Amps - 5-30A IR - 1000A

Features and benefits: • Space-savings size • Industry standard color coding for

easy identification of fuse ratings Typical applications: • Automotive

Catalog numbers - (amps)

Catalog numbers Color ATR-5 Tan

ATR-7-1/2 Brown

ATR-10 Red

ATR-15 Blue

ATR-20 Yellow

ATC fuses (0 to 20 amps) 1A5600

Dimensional data

Catalog Clip Number Mat* Finish

1A5600 Cart. Satin Brass Finish Tin

Data Sheet: 2131

1A5780 Dimensional data

3.18 0.125

- BASE 6.88 0.27 FUSECLIPS

SPECIFICATIONS

FUSECLIPS BRASS, NICKEL PLATED

BASE MATERIAL GLASS FILLED NYLON, UL RATED 94V-0

CURRENT RATING 15 AMPS

VOLTAGE RATING 500V AC

TEMPERATURE RATING -50°C TO 145°C -58°F 292°F

*Spg. Br. - spring bronze; BeCu - beryllium copper; cart. brass -cartridge brass

'Tor RoHS compliant version add "-R" option code suffix to part number.

r

5.08 0.200

5.08 0.200

ATM fuses - 1A5778 Dimensional data

3.66 0.144

4.47 3.66 0.176 0.144

1.57 0.062

1.57 0.062 y

0.086

T

1.65x0.05 DIA. HOLE 0.065 x 0.002 (TYP-4)

MOUNTING LAYOUT FOR 2 CLIPS

MATERIAL BRASS, NICKEL PLATED,072 THICK

Data Sheet: 2131

1A5779

11.18 6.440

1.90 0.075

3.96 0.156

r 14.68 7 1.24 0.578 raw

fi 4.75 0.187

"-BASE

3.18 0.125

1.57 0.062

SPECIFICATIONS

FUSECLIPS BRASS, NICKEL PLATED

BASE MATERIAL GLASS FILLED NYLON, UL RATED 94V-0

CURRENT RATING 15 AMPS

VOLTAGE RATING 500V AC ° TEMPERATURE RATING 50°C TO

4 °F 145 C

1.45 0.057

.295" (7.49mm)

330" (8.38mm)

(3.81mm)

0.08" ± 0.01" (2.03 ± 0.25mm)

-.090" (2.29mm)

4.45 0.175

19.30 0.760

11.10 0.437

6.35 0.250

1.27 0.050

.053" (1.35mm)

(5.08mm)

3.66 0.144

2.54 0.100

3-15

Low voltage

supplementary

fuses

3Low voltage, supplementary fusesAutomotive blade-type fuses and PCB fuseclips

BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries

Data Sheet: 2131

Data Sheet: 2131

Data Sheet: 2131

Catalog ClipNumber Mat.* Finish

1A5600 Cart. Satin Brass Finish Tin

ATC fuses (0 to 20 amps)1A5600

Dimensional data

ATM fuses - 1A5778Dimensional data

1A5779

1A5780Dimensional data

.150"(3.81mm)

.330"(8.38mm)

.295"(7.49mm)

.200"(5.08mm)

.053"(1.35mm)

0.08" ± 0.01"(2.03 ± 0.25mm)

.090" (2.29mm)

MOUNTING LAYOUT FOR 2 CLIPS

0.0120.30MATERIAL: BRASS, NICKEL PLATED, THICK

1.900.075

0.1563.96

0.44011.18

4.980.196

0.1253.18

1.570.062

0.0621.57

2.180.086

3.660.144

(TYP-4)

1.65 ± 0.050.065 ± 0.002 DIA. HOLE

0.1443.66

0.1764.47 3.66

0.144

BASE

FUSECLIPS

14.680.578

4.750.187

1.450.057

1.240.049

0.3408.64

0.1002.54

03.660.144

3.180.125

1

0.0621.573

MOUNTING LAYOUT

(TYP-4)

1.65 ± 0.050.065 ± 0.002 DIA. HOLE

0.1443.66

0.1764.47 3.66

0.144

SPECIFICATIONS

. .

. . . . .

. . . . .

. . . . . . . . . . . . .

UL RATED 94V-0

BRASS, NICKEL PLATEDGLASS FILLED NYLON,

500V AC15 AMPS

145ºC292ºFTO-50ºC

-58ºFTEMPERATURE RATING

VOLTAGE RATING CURRENT RATING

FUSECLIPS BASE MATERIAL

292ºF-58ºF

SPECIFICATIONS

. .

. . . . .

. . . . .

. . . . . . . . . . . . .

MOUNTING LAYOUT

UL RATED 94V-0

BRASS, NICKEL PLATEDGLASS FILLED NYLON,

500V AC15 AMPS

145ºCTO-50ºCTEMPERATURE RATING

VOLTAGE RATING CURRENT RATING

FUSECLIPS BASE MATERIAL

19.300.760

3.180.125

5.080.200

BASE

FUSECLIPS

4.450.175

6.350.250

0.2716.88

0.43711.10

0.0501.27

(TYP-4)

2.54 ± 0.050.100 ± 0.002 DIA. HOLE

0.2005.08

0.1604.06

*Spg. Br. - spring bronze; BeCu - beryllium copper; cart. brass - cartridge brass

***For RoHS compliant version add “-R” option code suffix to part number.

Data Sheet: 2131

ATR micro fuse

Specifications:Description: Fast-acting color coded 2-leg micro blade fuse.Construction: Colored plastic housing with zinc fuse element.Ratings:Volts — 32VdcAmps — 5-30A

IR — 1000A

Features and benefits:• Space-savings size• Industry standard color coding for easy identification of fuse ratings

Typical applications:• Automotive

Catalog numbers - (amps)

Catalog numbers Color

ATR-5 Tan

ATR-7-1/2 Brown

ATR-10 Red

ATR-15 Blue

ATR-20 Yellow

ATR-25 Clear

ATR-30 Green

FWAHL
SmallO

// •• //) Fuses Made Simple'

Control circuit fuses AIP

a

The easiest and fastest way to select and specify the right control circuit fuse.

E:7•111 Powering Business Worldwide

346 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.corn/bussmannseries 3-16 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries

The easiest and fastest way to select and specify the right control circuit fuse.

Fuses Made Simple™Control circuit fuses