control station - atex - emergency stop - red mushroom pushbutton (pull) - walsall lcp131
TRANSCRIPT
Cornwallis Road, West Bromwich, West Midlands, B70 7DX, UKTel: +44 (0)121 500 6161 ~ Fax: +44 (0)121 500 6300Web: www.walsall-ltd.com ~ Email: [email protected]
Walsall Middle EastRAK Free Trade Zone, P. O. Box 10559 Ras Al Khaimah, United Arab EmiratesTel: +971 (0) 7 2660039Fax: +971 (0) 7 2660242Email: [email protected]: [email protected]
Walsall North America 11490 Westheimer, Suite 850Houston 77077Texas, USATel: +1 (713) 425 6361Fax: +1 (713) 783 0067
Walsall Asia Pacific10 Upper Aljunied Link,York International Industrial Building #02-05 Singapore 367904Tel: +65 (0) 6858-5259Fax: +65 (0) 6858-6560Email: [email protected]
Walsall South AmericaAv Nilo Pecanha, 50.Sala 1709. Centro, Rio De Janeiro,RJ, Brazil.CEP, 20020-906.Tel: +55 (21) 2025 1059Fax: +55 (21) 3084-1446
Local Control Station - Glass Reinforced Polyester Enclosure
Material Box Carbon loaded anti-static glass reinforced polyester UL94/V0
Finish Moulded black
Weight Empty 0.7Kg
Cover Fixing M6 Stainless Steel hexagon head screws
Gasket 1.2 mm one piece solid nitrile rubber
Earthing Internal Ex e brass clamps on base
Entries 1x20mm threaded hole in face A, fitted with a nylon Ex e stopping plug. 1x20mm threaded hole in face B, fitted with a nylon Ex e cable gland. 25mm entries are available as an option.
Mounting Through 7mm holes moulded into base
ENCLOSURE SPECIFICATION
LCP130 - Ex ed Single Emergency Pushbutton
Description Action Contacts Labelling Product Code
Red LatchingMushroom Pushbutton
Pull release
8
5
E
1
4
Emergency stop LCP131
Red LatchingMushroom Pushbutton
Key Release
8
5
E
1
4
Emergency stop LCP132
ORDERING INFORMATION
Notes - For 25mm entries add/25 to Product Code e.g. LCP132/25
HAZARDOUS AREA SPECIFICATION
Marking to 94/9/EC II 2 GD
Type of Protection Ex edm IIC T* GbEx tb IIIC T**°C Db
Ambient Temp.°C Gas Temperature Class (T*C)
Dust Temperature Class (T**)(°C)Min Max
-20* +55 T6 85
* -40°C when used with a plug and gland rated to -40°C
Ingress Protection IP66 to EN60529:1992
Area Classification Zones 1,2,21,22
Certification No. SIRA03ATEX3293, GOST-R POCC GB.Mл14.B00074
ELECTRICAL SPECIFICATION
Walsall Ex de IIC switch. Certification No. SIRA03ATEX1269U
Operating Voltage Operating Current Conductor Size
Volts Max Amps mm² Max
420 20 2.5
110
125
99 121
78110
A
B
C D
7
All Dimensions in mm.