    Operators Manual

    SC400Lubrication Controller

  • 7/24/2019 Controlador Bijur Delimon SC400

    2/24

    2 35979 R18/11

    Table of Contents

    GENERAL....................................................................................................................................3

    SAFETY

    .......................................................................................................................................

    3

    APPLICATION..............................................................................................................................4

    TECHNICALDATA.......................................................................................................................5

    PROGRAMMINGRANGES..........................................................................................................5

    DIMENSIONSANDMOUNTING..................................................................................................5

    WIRING:QUICKGUIDE...............................................................................................................6

    WIRING:SC400POWER.............................................................................................................7

    WIRING:VALVEAANDVALVEBOUTPUTS................................................................................8

    WIRING:AUTOFILLPUMPOUTPUT...........................................................................................8

    WIRING:INPUTS(GENERAL)......................................................................................................8

    WIRING:INPUT(DETAILS)........................................................................................................10

    WIRING:FAULTSIGNALS..........................................................................................................10

    PROGRAMMING:FIRSTTIMESTARTUP/SYSTEMSETUP.........................................................11

    PROGRAMMING:ENGINEERINGPARAMETERS.......................................................................11

    ADVANCEDFUNCTIONS...........................................................................................................13

    PROGRAMMINGMODEOPERATORLEVEL(TIMINGSETUP)...................................................13

    PROGRAMMINGSINGLELINEPROGRESSIVE...........................................................................13

    PROGRAMMINGSINGLE

    LINE

    INJECTORS

    ................................................................................

    15

    PROGRAMMINGDUALLINEHYDRAULIC.................................................................................16

    PROGRAMMINGDUALLINEELECTRIC.....................................................................................18

    PROGRAMMINGCONTINUOUS...............................................................................................20

    SYSTEMMESSAGES..................................................................................................................20

    WARNINGCONDITIONS...........................................................................................................20

    FAULTCONDITIONS.................................................................................................................21

    APPENDIX:SYSTEMEXAMPLES................................................................................................22

    TECHDATASHEETLIST.............................................................................................................24

    SERVICEPARTS.........................................................................................................................24

    SC400 Lubrication Control

    BIJURDELIMONINTERNATIONAL

    (252)5276001 LOCAL

    (800)2271063 TOLLFREE

    (252)5279232 FAX

    WWW.BIJURDELIMON.COM2100GatewayCentreBlvd.,Suite109

    Morrisville,NC27560

    35979

    R18/11

  • 7/24/2019 Controlador Bijur Delimon SC400

    3/24

    3 35979 R18/11

    GENERAL

    Prior to start up, we recommend reading these operating

    instructions carefully. We do not assume any liability for

    damages and operating issues resulting from failing to

    followthese

    operating

    instructions.

    Any use beyond the applications described in these

    operatinginstructionsisconsideredtobenotinaccordance

    with the products intended purpose. The manufacturer is

    nottobeheldresponsibleforanydamagesresultingfrom

    this:theuseralonebearsthecorrespondingrisk.

    Astofiguresandindicationsintheseoperatinginstructions

    wereservetherighttomaketechnicalchangeswhichmight

    becomenecessaryforimprovements.

    The copyright on these operating instructions is kept

    reservedbythecompanyBIJURDELIMON.Theseoperating

    instructions

    are

    intended

    for

    the

    erecting,

    operating

    and

    supervising personnel. They contain regulations and

    drawingsof technicalnaturewhichmustnotcompletely

    orpartially bedistributednorusednorcommunicatedto

    otherswithoutauthorization.

    SAFETY

    These operating instructions contain fundamental

    instructions which are to be observed during erection,

    operation and maintenance. Therefore it is absolutely

    necessary for the installer and the competent qualified

    staff/user to read these operating instructions before

    installation and startup. The operating instructions must

    be

    available

    at

    all

    times

    at

    the

    place

    of

    use

    of

    the

    machine/system.

    Not only the general safety instructions stated under this

    mainpointsafetyaretobeobserved,butalsotheother

    specific safety instructions stated under the other main

    points.

    Identification of safety warnings in the

    operating instructions

    The safety warnings contained in these operating

    instructions which, if not observed, may cause dangers to

    people,arespeciallymarkedwithgeneraldangersymbols

    safety symbol according to DIN 4844,

    warningaboutadangerspot,

    safety symbol according to DIN 4844,

    warning about dangerous electric

    voltage.

    In case of safety instructions which, if not observed, may

    causedamagetothemachineanditsfunction,

    theword isinserted.

    Instructionsthataredirectlyattachedtothemachinemust

    beobservedatalleventsandmaintained ina fully legible

    condition.

    Note: There is an increased skid risk in case of

    spilled/leaked out lubricants. They are to be removed,

    properlyandimmediately.

    Safety sign according to DIN 4844,

    warningaboutskidrisk.

    Personnel qualification and training

    The operating, maintaining, inspecting and erecting

    personnelmusthavetheappropriatequalificationforsuch

    work. The scope of responsibility, competence and

    supervision of the personnel shall to be regulated by the

    user. If the personnel do not have the necessary

    knowledge, they must be trained and given instructions.

    This can be assisted, if necessary, by the

    manufacturer/supplier on behalf of the user of the

    machine. Furthermore, the user shall make sure that the

    contentsoftheoperating instructionsarefullyunderstood

    bythepersonnel.

    Dangers in case of nonobservance of the

    safety instructions

    Thenonobservanceofthesafety instructionsmayresultin

    hazards to persons, to the environment and to the

    machine.Thenonobservanceofthesafetyinstructionsmay

    lead to the loss of any claims for damages. In detail, the

    nonobservance may for instance lead to the following

    hazards:

    Failure of important functions of the

    machine/system

    Failure of prescribed methods for maintenance

    andrepair

    Hazard to persons by electrical, mechanical and

    chemicalinfluences

    Hazard to the environment by the leakage of

    dangeroussubstances

    Safety conscious working

    The safety instructions stated in these operating

    instructions, the existing national regulations related to

    accident prevention, as well as possible internal working,

    operatingandsafetyrulesoftheuseraretobeobserved.

  • 7/24/2019 Controlador Bijur Delimon SC400

    4/24

    4 35979 R18/11

    Safety instructions for the

    user/operator

    If hot or cold machine parts lead to dangers,

    thesepartsshallbeprotectedagainsttouch.

    Protection

    against

    touch

    for

    moving

    parts

    (e.

    g.

    coupling) must not be removed when the

    machineisinoperation.

    Leakages (e.g.fromtheshaftseal)ofhazardous

    goodstobedelivered(e.g.explosive,toxic,hot)

    aretoberemoved insuchawaythatthereisno

    danger to persons and environment. Legal rules

    aretobeobserved..

    Hazards caused by electrical power are to be

    excluded (for details, please refer to local, state

    andfederalregulations).

    Safety instructions for maintenance,

    inspection and installation workThe user shall take care that all the maintenance,

    inspection and installationwork is executedbyauthorized

    and qualified skilled personnel who have informed

    themselves adequately by thoroughly studying these

    operatinginstructions.

    Installation, operation, and maintenance personnel shall

    conform to Federal, State, Local and internal safety

    regulations.

    Pumps or pump systems that deliver media being

    hazardoustohealthshallbedecontaminated.

    Immediately

    after

    completion

    of

    the

    work,

    all

    safety

    and

    protective equipments shall be reinstalled and/or

    reactivated.

    Advice: When working with compressed air, hydraulics, or

    electricity,wearPersonalProtectiveEquipment(PPE).

    (DIN4844Usebreathingmask)

    (DIN4844Usebreathingmask)

    (DIN

    4844

    Pull

    mains

    cord

    before

    opening)

    (DIN4844Deenergizebeforework)

    Before recommissioning, observe the points stated in

    sectioninitialstartup.

    Unauthorized conversion and

    manufacture of spare parts

    Conversion or modifications to the machine are only

    permitted when agreed to by the manufacturer. Original

    spareparts

    and

    accessories

    authorized

    by

    the

    manufacturer

    serve toensuresafety.The useofother partsmayrender

    theliabilityforconsequentiallossesnullandvoid.

    Unacceptable modes of operation

    The operational reliability of the machine supplied is only

    guaranteed if the machine is used in accordance with its

    intended purposes as per APPLICATION section of these

    operating instructions. The limiting values specified in the

    datasheetshallnotbeexceeded.

    APPLICATION

    TheSC400

    is

    afull

    featured

    lubrication

    control,

    operating

    in

    anyoffive(5)modes:

    SeriesProgressive

    SinglineInjector

    Dualine(HydraulicReversingValve)

    Dualine(ElectricReversingValve)

    Continuous

    Primaryfeaturesinclude:

    Spraysystemsupport

    Automaticfillpumpcontrol

    Four(4)languagessupported

    Two(2)zonesupport(notavailableforDLelectric

    orSpraysystems)

  • 7/24/2019 Controlador Bijur Delimon SC400

    5/24

    5 35979 R18/11

    TECHNICAL DATA

    InputVoltage 85to265VAC,50/60Hz

    Current

    Consumption

    80

    ma

    at

    115

    VAC

    (less

    load),

    40ma

    at

    230

    VAC

    (less

    load)

    PumpOutputRatings 8amp(85to265VAC)

    ValveA andValveBOutputRating 8amp(85to265VAC),Combinedtotalnottoexceed12A

    EnclosureRating IP56

    AmbientTemperatureRange(Operation) 14Fto131F(10Cto55C)

    Fault/WarningOutputs 5amp

    Vibration 2g atresonant(3axis)

    PermanentMemory FLASH

    FaultRelayContacts 5Amp

    Availablecurrent 500mA@24VDC

    NetWeight 5lb

    PROGRAMMING RANGESLubeCompletion CycleCounts 1to999

    Time(HH:MM:SS) 00:00:01to23:59:59

    Purgetime(MM:SS) 00:01to59:59

    ReversingValveHoldTime(MM:SS) 00:01to59:59

    IdlePeriod Time(DD.HH:MM:SS) 00.00:00:01to99.23:59:59

    MachineCycleCounts 1to999,999

    MachineWatchdogTimer(MM:SS) OFF,00:01to59:59

    CycleMonitorTime(HH:MM:SS) 00:00:01to23:59:59

    Overcount OFF,1to9

    CyclicPumping PulseOnTime 1to59Seconds

    PulseOffTime 1to59Seconds

    DIMENSIONS AND MOUNTINGINTERNALMOUNTING EXTERNALMOUNTING

  • 7/24/2019 Controlador Bijur Delimon SC400

    6/24

    6 35979 R18/11

    WIRING: QUICK GUIDE

  • 7/24/2019 Controlador Bijur Delimon SC400

    7/24

    7 35979 R18/11

    WIRING: SC400 POWER

    TheSC400ispoweredthroughpins1and2. Thecontrolshouldbeproperlygroundedatpin3andatthegroundingpointon

    theback

    panel.

    ShockHazard:DisconnectPowerfromcontrolpriortoanywiringormaintenance.

    FUSES

    Therearefour(4)fuseslocatedontheSC400controlboard.

    F1FuseforL1(incomingpower).(part#37317)

    F2FuseforL2(incomingpower).(part#37317)

    F3ProtectsSC400internalcircuitry.(part#37316)

    F4Fusefor24VDCpowersupply(part#37315)

    F1

    F2

    F3

    F4

    SC400MAINPOWERconnectio

    SC400POWERCIRCUITRYand

    FUSEDIAGRAM

    DCFUSELOCATION

    ACFUSELOCATIONS

  • 7/24/2019 Controlador Bijur Delimon SC400

    8/24

    8 35979 R18/11

    WIRING: VALVE A AND VALVE B OUTPUTSValveAandValveBaremultifunctionoutputs. Theoperationoftheseoutputsdependsupon

    themodeofoperation: ConnectthesystemsvalvestosolenoidstoValveA(pins6and7)and

    toValveB(pins8and9). Thetableindicateswherevalvesconnect,forvarioussystemtypes.

    MODE NumberofZones

    ValveA

    (pins6and7)

    ValveB

    (pins8and9)

    SERIES

    PROGRESSIVE

    Two(2)ZoneSystemVALVE,ZONEA

    ENABLE

    VALVE,ZONEB

    ENABLE

    One(1)Zone(2Interval) n/a AIRVALVE(OPT)

    SINGLINE

    INJECTOR

    Two(2)ZoneSystemVALVE,ZONEA

    ENABLE

    VALVE,ZONEB

    ENABLE

    SingleZone(2Interval) n/a AIRVALVE(OPT)

    DUALINE

    HYDRAULIC

    Two(2)ZoneSystemVALVE,ZONEA

    ENABLE

    VALVE,ZONEB

    ENABLE

    SingleZone(2Interval) n/a AIRVALVE(OPT)

    DUALINE

    ELECTRICSingleZone(2Interval)

    REVERSING VALVE,

    LINEA

    REVERSING VALVE, LINE

    B

    CONTINUOUS

    n/a

    n/a

    n/a

    WIRING: AUTOFILL PUMP OUTPUT

    Theautofilloutputoperatesanautomaticfillpump. Connectfillpumptopins10and11.

    NOTE:THESC400CONTROLSFILLPUMPOPERATION. ITISHIGHLYRECOMMENDEDTHATCUSTOMER

    INSTALLWIRINGSUCHTHATFILLPUMPMAYBEDISABLEDFORMAINTENANCE. MANUALOPERATION

    ISNOTSUPPORTEDTHROUGHTHESC400CUSTOMERMUSTWIRETHISSEPARATELY.

    NOTE:FORFILLPUMPTOOPERATEPROPERLY,APPRORIATELEVELSIGNALSMUSTBECONNECTEDTO

    THESC400.

    ShockHazard:DisconnectPowerfromcontrolpriortoanywiringormaintenance.

    WIRING: INPUTS (GENERAL)

    TheSC400hasconnectionsforupto12inputs. Connectionsareclearly labeled,andofferconvenient24VDCpowerformost

    signals.

    NOTE:SC400offers500mAof24VDC,availabletopowerswitches.Supplyterminalsinclude:

    24VDC 15 18 21 24 42 45 48 51

    0V 17 20 23 26 44 47 50 53 28 30 55 57

    OutputWiring:OTHER

    (Power source = Extern

    Power)

    EXTERNALPOWER

    SOURCE:

    **Anyjumpers

    must

    be

    removed

    frompins35and

    37. Customer

    powershouldbe

    fused/protected

    toamaximumof

    12A

  • 7/24/2019 Controlador Bijur Delimon SC400

    9/24

    9 35979 R18/11

    Primary Inputs

    Eight(8) inputsmaybeconnectedtoanyswitchthatworkswith24VDC. NPN,PNPandmechanicalswitchesaresupported.

    Theseinputsinclude:

    OPERATION

    COMPLETE

    A

    OPERATION

    COMPLETE

    B

    MACHINECYCLE ALARM2

    LOW

    LEVEL

    HIGH

    LEVEL

    AUTOFILL

    START

    AUTOFILL

    STOP

    Secondary Inputs

    Four(inputs)maybeconnectedtomechanicalorNPNswitchesonly. Theseinputsinclude:

    JOG

    PAUSE

    INTERVAL

    SELECT

    LOW

    PRESSURE

  • 7/24/2019 Controlador Bijur Delimon SC400

    10/24

    10 35979 R18/11

    WIRING: INPUT (DETAILS)

    Usethetablebelowtohelpdeterminewhichinputsarerequiredforyoursystem:

    InputTerminal Input Description

    19

    OPERATIONCOMPLETEA Feedback signal for line A. Depending upon system type, this

    maybe:

    CycleSwitch

    Pressureswitch

    If the system has only one feedback switch, it should be

    connectedhere.

    22 OPERATIONCOMPLETEB Feedback signal for lineBor zone 2. Depending upon system

    type,thismaybe:

    CycleSwitch

    Pressureswitch

    16

    MACHINECYCLE Monitoringofmachinetobelubricated

    25 ALARM2 Highpressure,motortrip,ormisc.alarminput

    43

    LOWLEVEL

    Low

    level

    switch

    (reservoir)

    46

    HIGHLEVEL Highlevelswitch(reservoir)

    49 FILLSTART Fillstartsignal(reservoir)

    52 FILLSTOP Fillstopsignal(reservoir)

    27 JOG Momentary switch input that resets messages and initiates

    lubrication.

    29 PAUSE Maintained switch input that causes all lubrication to cease

    whileswitchisactive.

    54 INTERVALSELECT Maintainedswitch inputthatcausesSC400tousea2ndsetof

    lubricationparameters.

    56 LOWPRESSURE Lowpressureswitchfromairsupply(Spraysystems)

    WIRING: FAULT SIGNALS

    SC400hastwo(2)relays,eachwithN.O.andN.C.contacts.

    ThefirstrelayiscalledWARNING. ThisrelayactivatesuponANYmessage.

    ThesecondrelayiscalledFAULT. Thisrelayactivatesonlyforcatastrophiceventsthatforcelubricationtocease.

  • 7/24/2019 Controlador Bijur Delimon SC400

    11/24

    11 35979 R18/11

    PROGRAMMING: FIRST TIME START

    UP/SYSTEM SETUP

    There are two (2) programming sections for the SC400.

    Operation Parameters determine timing for the system.

    EngineeringParametersdefinethesystemitself.

    Engineering parameters should be programmed first,

    followedbyoperationparameters.

    Keypad Operation Programming)

    =MODECHANGEPressthisbuttontochangestate

    oftheSC400. Modesinclude:

    RUNMODE

    PROGRAMMINGMODEOPERATIONLEVEL

    PROGRAMMINGMODEENGINEERINGLEVEL

    =PREVIOUS

    /

    NEXT

    Parameter

    Thesebuttons are used to navigate forward and backward

    throughavailableparameters.

    =CHANGEPARAMETERVALUEPresseither

    ofthesebuttonstochangetheparameterbeingviewed.

    = DIGIT SELECT For parameters that are TIME

    based, Press DIGIT SELECT to choose the digit to modify.

    Also

    used

    to

    manually

    start

    and

    stop

    a

    lube

    event.

    NOTE:

    When

    the

    SC400

    is

    powered

    for

    the

    first

    time,

    thedisplay may show an alarm PARAMETERS LOST. This is

    normal.

    PROGRAMMING: ENGINEERING

    PARAMETERS

    To begin system setup, go to Engineering parameters by

    pressing twice. The display should briefly read

    programmingmode.Engineeringlevel.

    Language

    Set language for the system. Available languages are

    English, French, Spanish, and German. To select a

    language,press or . Oncetheproperselectionhas

    beenmade,press togotothenextparameter.

    System Type

    TheSC400

    will

    operate

    in

    any

    of

    five

    (5)

    operating

    modes:

    SinglineInjector

    SinglineProgressive

    DualineHydraulic

    DualineElectric

    Continuous

    Toselecttheoperatingmode,press or . Oncethe

    proper selection has been made, press to go to the

    next parameter. Some modes will require additional

    information. Seebelow.

    Secondary Function

    The

    SC400

    has

    the

    capability

    of

    offering

    two

    special

    functions: two zone operationand two interval operation.

    Onlyonesecondaryfunctionmaybeselected.

    2nd

    ZoneControloftwoindependentsystems

    2nd

    Interval Standard system. Timing

    parameters usedare determined bystatus of an

    intervalselectswitch(customersupplied).

    NoneStandardsystem. (Formostapplications

    noneshouldbeselected)

    Selectthedesiredsecondaryfunctionusing or . If

    nosecondaryfunctionisrequired,selectnone.press

    Spray System

    Whencontrollingaspraysystem,theSC400canoperatea

    separateairsolenoidforthespraynozzles. Ifyoursystemis

    a spray type, select yes using or . Otherwise

    selectno.press

    Spray system functionality is available in Progressive,

    InjectorandDualineHydraulicmodesonly. Spraysystemis

  • 7/24/2019 Controlador Bijur Delimon SC400

    12/24

    12 35979 R18/11

    not available for two zone systems or Dualine Electric

    Systems.

    Dualine Electric

    For Dualine Electric systems, two additional parameters

    describeoperation.

    ReversingValveFeedback

    Asettingisavailabletodescribethetypeofswitchusedto

    indicate that the cycle has completed. Options are Two

    SignalsorOneSignal. Wheneveraseparatefeedbacksignal

    (or pressure switch) is used for each line of a Dualine

    system,selecttwo signals. Forsomespecialtyswitches,

    onesignalmayberequired.

    Reversing Valve Hold Time (Set to 00:00, not used on

    standardsystems)

    To maintain pressure for an additional period (after

    pressure switch signal is received), a hold time may be

    selected. Setholdtimedesired.

    Pump Power

    SelecthowtheSC400shallpowerthepump. Whensystem

    utilizesanelectricdrivenorautomaticreciprocatingpump

    (drumpump),choosecontinuous. Ifpumprequiresaseries

    ofmomentarypulsestooperate,selectcyclic.(Cyclicused

    forTPtypepumpsonly)CyclicwillcauseSC400todelivera

    series of electrical pulses to the pump output. If cyclic

    operation ischosen,setpumpontimeandofftimeas

    required.

    Selectthedesiredfunctionusing or andpress

    togotothenextparameter.

    Input Functions

    The following parameters pertain to alarm inputs to the

    SC400.

    Select the desired functions below using or and

    press togotothenextparameter.

    LowLevelAlarm

    Whenthesystemindicatesalowlevelalarm,theSC400will

    reactinoneoftwoways:

    Stop pump All lubrication is halted until the reservoir is

    filledto

    aproper

    level.

    Message only A warning signal is activated, but

    lubricationcontinues.

    To prevent potential damage to the pump and to prevent

    airfromgettingintothelubricationlines,BDIrecommends

    choosingstoppumpforthisfunction. Ifmessageonly is

    selected,thecustomershouldtakeseparateprecautionsto

    preventthelubricationsystemfromrunningdry.

    LowLevelPolarity

    Select thestateofswitch that signifiesaLowLevelalarm.

    Options

    are

    alarm

    when

    open

    or

    alarm

    when

    closed.

    Note: If no low level switch is connected to the low level

    inputs,customershouldselectalarmwhenclosedforthis

    parameter.

    LowpressurePolarity

    Select the state of switch that signifies a Low Pressure

    Alarm. Options are Alarm when open or alarm when

    closed.

    Note: If no low pressure switch is connected to the Low

    Pressure inputs, customer should select alarm when

    closedforthisparameter.

    Alarm2Polarity

    Selectthe

    state

    of

    switch

    that

    signifies

    an

    alarm

    from

    the

    Alarm2 input. OptionsareAlarmwhenopenoralarm

    whenclosed.

    Note:IfnowiresareconnectedtoAlarm2inputs,customer

    shouldselectalarmwhenclosedforthisparameter.

    Alarm2Message

    Selectthemessagetobedisplayedwhenafaultoccursasa

    resultoftheAlarm2input. Optionsinclude:

    HighPressure

    MotorTrip

    ExternalAlarm2

    Alarm Polarity

    (for

    dry

    contacts)

    Customermaymonitoralarmsviatheuseoftwo(2)setsof

    dry (potential free) contacts. The Fault contact activates

    only for events that cause lubrication to be halted. The

    warningcontactactivateswithanymessage.

    Faultop.Polarity(Terminal12,13,14)

    Operationofthefaultrelaymaybeselectedas:

    Fault = Open (the relay coil is energized during

    normaloperation)

    Fault = Closed (the relay coil is energized during

    fault)

    Warningop.Polarity(Terminal39,40,41)

    Operationof

    the

    Warning

    relay

    may

    be

    selected

    as:

    Warning=Open(therelaycoilisenergizedduring

    normaloperation)

    Warning = Closed (the relay coil is energized

    duringwarning)

  • 7/24/2019 Controlador Bijur Delimon SC400

    13/24

    13 35979 R18/11

    ADVANCEDFUNCTIONSAREOPTIONSMOSTSYSTEMSWILL

    NOT USE. IF NOT REQUIRED PROCEED TO PROGRAMING

    MODEOPERATORLEVELBYPRESSING twice.

    ADVANCED FUNCTIONSInput Status

    Statusofanyinputmaybeviewedutilizingthisscreen.

    Output Force

    Any output may be energized using this screen. Caution:

    changingstatesonthisscreenwillcauseoutputstochange

    state. Only authorized personnel should utilize functions

    on this screen. Failure to follow safety procedures can

    resultinequipmentdamage,personalinjuryordeath.

    LCD Contrast

    LCDcontrast

    is

    modified

    via

    this

    parameter.

    The

    contrast

    hasbeenfactorysetforoptimumviewingmodifyonly if

    screenisdifficulttosee.

    Operator Password

    Operator password can be enabled or disabled from this

    screen. Enabling will prevent unauthorized users from

    modifyingtimingdatawithinoperationparameters.

    Engineer Password

    Engineer password can be enabled or disabled from this

    screen. Enabling will prevent unauthorized users from

    modifying timing data within operation parameters.

    Note: It is recommended that Engineeringpassword be

    enabled. Engineering parameters contain parameters

    critical to the operation of the SC400. Modification of

    theseparameters by unqualifiedpersonnel can result in

    equipmentdamage,personalinjuryordeath.

    Reset Lost Parameters

    Normally,no

    should

    be

    selected.

    If

    the

    SC400

    displays

    an

    alarm, SystemFault! Parameters Lost, then select yes.

    Thenexitengineeringparameters.

    Enter Factory Mode

    This function is for internal BDI use only. This parameter

    settingshouldremainatno.

    PROGRAMMING MODE OPERATOR LEVEL

    (TIMING SETUP)

    Operation

    parameters

    are

    used

    to

    set

    timing

    information

    for the system. Parameters will vary depending on the

    selections made within engineering parameters. The

    following sections provide the steps for programming

    Progressive, Injector, Dualine Hydraulic, Dualine Electric

    andContinuousmodes.

    PROGRAMMING SINGLE

    LINE PROGRESSIVE

    Pump Mode 1

    Select how the SC400 should

    determinewhenlubricationiscomplete. Optionsinclude:

    FixedCyclesLubricateforaspecifiednumberof

    switch cycles, as monitored from OP COMP A

    (terminals 18, 19, 20) input. When the specified

    valueisreached,lubricationwillcease.

    FixedTime Lubricate fora specified amountof

    time. When specified time has expired,

    lubricationwillcease.

    Pump Cycles 1IffixedCycles isselectedforPumpMode1,thenumber

    ofcyclesmustbespecified. Select thedesirednumberof

    cycles.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Pump Time 1

    IffixedTimeisselectedforPumpMode1,thelubrication

    time must be specified. Select the length of time for

    lubrication.

    Press to select desired time field, seconds: minutes:

    hours

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    NOTE:Iffixedtimeisselected,Monitortimeisnotused.

  • 7/24/2019 Controlador Bijur Delimon SC400

    14/24

    14 35979 R18/11

    Air Purge Time (When spray system has been

    selected

    in

    Engineering

    parameters)

    Forspraysystems,anairsolenoidisdrivenbytheSC400(in

    addition to the lubrication pump). This solenoid may be

    programmedtoremainonforaspecifiedperiodoftime

    after normal lubrication has completed. This time (called

    air purge time or afterblow time) should be set to the

    desiredvalue.

    Press toselectdesiredtimefield,seconds:minutes

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Monitor Time

    TheSC400willsignalafault if lubricationisnotcompleted

    as expected. OPCOMP_A (Terminals 18, 19, 20) is

    monitored

    for

    changes

    in

    state

    during

    lubrication.

    If

    there

    is no activity from the cycle switch within a specified

    timeframe (Monitor time),a faultoccurs. Monitor time is

    automatically reset upon each cycle switch transaction.

    Recommendedsetting is1.5timestheactualtimeneeded

    foronetransaction.

    Press to select desired time field, seconds: minutes:

    hours

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Overcount Cycles

    Inprogressivesystems,thecycleswitchmaybemonitored

    while system is idle. If required, a fault will occur if a

    specifiednumberofcyclesareobservedafterlubricationis

    completed. Setthisparametertothemaximumallowable

    cyclesacceptable,orselectDISABLED.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Idle Settings

    The idle period can be determined by one of two events:

    Timeor

    Machine

    cycles.

    When

    Time

    is

    selected,

    the

    system

    willremain inawaitstateforaspecifiedperiodoftime.

    IfMachineCyclesisselected,thesystemwillremaininthe

    wait state until a specified number of pulses are received

    fromthemachinecountinput(MACHCYC).

    IdleMode1

    Press tochangevaluetotimeormachinecycles.

    Press togotothenextparameter

    IdleTime1

    IfTimeisselectedforIdleMode1,thetimetowait(before

    nextlubeevent)mustbespecified.

    Press

    to

    select

    desired

    time

    field,

    seconds:

    minutes:

    hours:days

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    MachineCycles1

    IfMachineCyclesisselected,thenumberofpulses(before

    nextlubeevent)mustbespecified.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Machine

    Watchdog

    1If Machine cycles is selected for Idle Mode 1, the SC400

    may (optionally) monitor the machine cycle input for

    failure. If Machine Watchdog is enabled, the SC400 will

    monitor(MACHCYC)forchanges instate. Ifapulse isnot

    receivedwithinaspecifiedperiodoftime,afaultwilloccur.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    MachineWatchdogTime

    If Machine Watchdog has been activated, a time period

    mustbespecified. Ifthemachinecycleinputdoesnotcycle

    withinthe

    specified

    period

    of

    time,

    afault

    will

    occur.

    Press toselectdesiredtimefield,seconds:minutes

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    NOTE: For systems using secondary functions (2 interval

    or 2 zone systems), a second set of pump parameters are

    available. These parameters may be set appropriately for

    thesecondintervalorzoneusingtheaboveinstructions.

    Autofill Pump

    SelectEnabled

    to

    activate

    fill

    pump

    functionality.

    If

    the

    fill

    pump needs to be disabled (or if autofill system is not

    connected to the SC400) this parameter should be set as

    Disabled.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

  • 7/24/2019 Controlador Bijur Delimon SC400

    15/24

    15 35979 R18/11

    Autofill Timeout

    If the autofill pump is enabled, a time period must be

    specifiedforthefillpumptooperate. Thisperiodshouldbe

    set long enough to allow for adequate filling, but short

    enough topreventdamageto thefillpump incase thefill

    pumpisrundry.

    Press to select desired time field, seconds: minutes:

    hours

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Lube at Power Up

    Even after power loss, the SC400 retains memory of its

    currentstatewithinthelubecycle. Ifthecustomerprefers

    that lubrication occur immediately after the control

    receivespower,

    set

    this

    parameter

    to

    YES.

    If

    parameter

    is

    settoNO,theSC400willresumeactivityatthelastknown

    positionwithinthelubricationcycle.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Operation

    Onceparametersareset,press tochangesystemto

    runmode. Thesystemsetupisnowcomplete.

    PROGRAMMING SINGLE LINE INJECTORS

    Monitor Time

    TheSC400willsignalafaultiflubricationis

    not completed as expected. OPCOMP_A

    (Terminals 18, 19, 20) is monitored for

    changes in state during lubrication. If

    there is no activity from the pressure

    switch within a specified timeframe

    (Monitortime),afaultoccurs. Recommendedsettingis1.5

    timestheactualtimeneededforonecycle.

    Press to select desired time field, seconds: minutes:hours

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Idle Settings

    The idle period can be determined by one of two events:

    TimeorMachinecycles. WhenTimeisselected,thesystem

    willremain inawaitstateforaspecifiedperiodoftime.

    IfMachineCyclesisselected,thesystemwillremaininthe

    wait state until a specified number of pulses are received

    fromthemachinecountinput(MACHCYC).

    Idle

    Mode

    1

    Press tochangevaluetotimeormachinecycles.

    Press togotothenextparameter

    IdleTime1

    IfTimeisselectedforIdleMode1,thetimetowait(before

    nextlubeevent)mustbespecified.

    Press to select desired time field, seconds: minutes:

    hours:days

    Press tochangevalueofdesiredfield.

    Press

    togo

    to

    the

    next

    parameter

    MachineCycles1

    IfMachineCyclesisselected,thenumberofpulses(before

    nextlubeevent)mustbespecified.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    MachineWatchdog1

    If Machine cycles is selected for Idle Mode 1, the SC400

    may

    (optionally)

    monitor

    the

    machine

    cycle

    input

    for

    failure. If Machine Watchdog is enabled, the SC400 will

    monitor(MACHCYC)forchanges instate. Ifapulse isnot

    receivedwithinaspecifiedperiodoftime,afaultwilloccur.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    MachineWatchdogTime

    If Machine Watchdog has been activated, a time period

    mustbespecified. Ifthemachinecycleinputdoesnotcycle

    withinthespecifiedperiodoftime,afaultwilloccur.

    Press toselectdesiredtimefield,seconds:minutes

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    NOTE: For systems using secondary functions (2 interval

    or 2 zone systems), a second set of pump parameters are

    available. These parameters may be set appropriately for

    thesecondintervalorzoneusingtheaboveinstructions.

  • 7/24/2019 Controlador Bijur Delimon SC400

    16/24

    16 35979 R18/11

    Autofill Pump

    SelectEnabledtoactivatefillpumpfunctionality. Ifthefill

    pump needs to be disabled (or if autofill system is not

    connected

    to

    the

    SC400)

    this

    parameter

    should

    be

    set

    as

    Disabled.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Autofill Timeout

    If the autofill pump is enabled, a time period must be

    specifiedforthefillpumptooperate. Thisperiodshouldbe

    set long enough to allow for adequate filling, but short

    enough topreventdamageto thefillpump incase thefill

    pumpisrundry.

    Press to select desired time field, seconds: minutes:

    hours

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Lube at Power Up

    Even after power loss, the SC400 retains memory of its

    currentstatewithinthelubecycle. Ifthecustomerprefers

    that lubrication occur immediately after the control

    receivespower,setthisparametertoYES. Ifparameter is

    settoNO,theSC400willresumeactivityatthelastknown

    position

    within

    the

    lubrication

    cycle.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Operation

    Onceparametersareset,press tochangesystemto

    run mode. The system setup is now complete.

    PROGRAMMING DUAL LINE HYDRAULIC

    Pump Mode 1

    Select how the SC400 should

    determine when lubrication is

    complete. Optionsinclude:

    Full Cycle (Used for

    standard DR45 type

    Dual Line Systems) Lubricate for exactly two (2)

    transitions of the OPCOMP_A (terminals 18, 19,

    20) input. After two transitions (in and out),

    lubricationwillcease.

    Half

    Cycle (Used for standard DR45 type Dual

    Line Systems) Lubricate for exactly one (1)

    transition of the OPCOMP_A (terminals 18, 19,

    20)

    input.

    After

    one

    transition

    (in

    or

    out),

    lubricationwillcease.

    FixedCyclesLubricateforaspecifiednumberof

    switch cycles, as monitored from OP COMP A

    (terminals 18, 19, 20) input. When the specified

    valueisreached,lubricationwillcease.

    FixedTimeLubricateforaspecifiedamountof

    time. When specified time has expired,

    lubricationwillcease.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    If Full Cycle or Half Cycle has been selected, proceed to

    MonitorTime

    (below).

    Pump Cycles 1

    IffixedCycles isselectedforPumpMode1,thenumber

    ofcyclesmustbespecified. Select thedesirednumberof

    cycles.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Pump Time 1

    IffixedTimeisselectedforPumpMode1,thelubrication

    time

    must

    be

    specified.

    Select

    the

    length

    of

    time

    for

    lubrication.

    Press to select desired time field, seconds: minutes:

    hours

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    NOTE:Iffixedtimeisselected,Monitortimeisnotused.

    Monitor Time

    TheSC400

    will

    signal

    afault

    if

    lubrication

    is

    not

    completed

    as expected. OPCOMP_A (Terminals 18, 19, 20) is

    monitoredforchanges instateduring lubrication. Ifthere

    is no activity from the cycle switch within a specified

    timeframe (Monitor time),a faultoccurs. Monitor time is

    automatically reset upon each cycle switch transaction.

    Recommendedsetting is1.5times theactualtimeneeded

    foronetransaction.

  • 7/24/2019 Controlador Bijur Delimon SC400

    17/24

    17 35979 R18/11

    Press to select desired time field, seconds: minutes:

    hours

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Idle Settings

    The idle period can be determined by one of two events:

    TimeorMachinecycles. WhenTimeisselected,thesystem

    willremain inawaitstateforaspecifiedperiodoftime.

    IfMachineCyclesisselected,thesystemwillremaininthe

    wait state until a specified number of pulses are received

    fromthemachinecountinput(MACHCYC).

    IdleMode1

    Press tochangevaluetotimeormachinecycles.

    Press

    togo

    to

    the

    next

    parameter

    IdleTime1

    IfTimeisselectedforIdleMode1,thetimetowait(before

    nextlubeevent)mustbespecified.

    Press to select desired time field, seconds: minutes:

    hours:days

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    MachineCycles1

    IfMachine

    Cycles

    is

    selected,

    the

    number

    of

    pulses

    (before

    nextlubeevent)mustbespecified.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    MachineWatchdog1

    If Machine cycles is selected for Idle Mode 1, the SC400

    may (optionally) monitor the machine cycle input for

    failure. If Machine Watchdog is enabled, the SC400 will

    monitor(MACHCYC)forchanges instate. Ifapulseisnot

    receivedwithinaspecifiedperiodoftime,afaultwilloccur.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    MachineWatchdogTime

    If Machine Watchdog has been activated, a time period

    mustbespecified. Ifthemachinecycleinputdoesnotcycle

    withinthespecifiedperiodoftime,afaultwilloccur.

    Press toselectdesiredtimefield,seconds:minutes

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    NOTE: For systems using secondary functions (2 interval

    or2zone

    systems),

    asecond

    set

    of

    pump

    parameters

    are

    available. These parameters may be set appropriately for

    thesecondintervalorzoneusingtheaboveinstructions.

    Autofill Pump

    SelectEnabledtoactivatefillpumpfunctionality. Ifthefill

    pump needs to be disabled (or if autofill system is not

    connected to the SC400) this parameter should be set as

    Disabled.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Autofill Timeout

    If the autofill pump is enabled, a time period must be

    specifiedforthefillpumptooperate. Thisperiodshouldbe

    set long enough to allow for adequate filling, but short

    enoughtopreventdamagetothe fillpump incasethe fill

    pumpisrundry.

    Press to select desired time field, seconds: minutes:

    hours

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Lube at Power Up

    Even after power loss, the SC400 retains memory of its

    currentstatewithinthelubecycle. Ifthecustomerprefers

    that lubrication occur immediately after the control

    receivespower,setthisparametertoYES. Ifparameter is

    settoNO,theSC400willresumeactivityatthelastknown

    positionwithinthelubricationcycle.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Operation

    Onceparameters

    are

    set,

    press

    to

    change

    system

    to

    runmode. Thesystemsetupisnowcomplete.

  • 7/24/2019 Controlador Bijur Delimon SC400

    18/24

    18 35979 R18/11

    PROGRAMMING DUAL LINE ELECTRIC

    Pump Mode 1

    Select

    how

    the

    SC400

    should

    determine

    when lubrication is complete. Options

    include:

    FullCycleLubricateforexactly

    two (2) transitions of the

    OPCOMP_A (terminals 18, 19, 20) input. After

    twotransitions(inandout),lubricationwillcease.

    Half

    Cycle Lubricateforexactlyone(1)transition

    of the OPCOMP_A (terminals 18, 19, 20) input.

    After one transition (in or out), lubrication will

    cease.

    Press tochangevaluetoFullCycleorHalfCycle.

    Press

    togo

    to

    the

    next

    parameter

    Monitor time

    TheSC400willsignalafault if lubricationisnotcompleted

    as expected. OPCOMP_A (Terminals 18, 19, 20) &

    OPCOMP_B (Terminals 21, 22, 23) are monitored for

    changes in state during lubrication. If there is no activity

    from the cycle or pressure switch within a specified time

    (Monitortime),afaultoccurs.

    Press to select desired time field, seconds: minutes:

    hours

    Press

    tochange

    value

    of

    desired

    field.

    Press togotothenextparameter

    Idle Settings

    The idle period can be determined by one of two events:

    TimeorMachinecycles. WhenTimeisselected,thesystem

    willremain inawaitstateforaspecifiedperiodoftime.

    IfMachineCyclesisselected,thesystemwillremaininthe

    wait state until a specified number of pulses are received

    fromthemachinecountinput(MACHCYC).

    IdleMode1

    Press tochangevaluetotimeormachinecycles.

    Press togotothenextparameter

    IdleTime1

    IfTimeisselectedforIdleMode1,thetimetowait(before

    nextlubeevent)mustbespecified.

    Press to select desired time field, seconds: minutes:

    hours:days

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    MachineCycles1

    IfMachine

    Cycles

    is

    selected,

    the

    number

    of

    pulses

    (before

    nextlubeevent)mustbespecified.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    MachineWatchdog1

    If Machine cycles is selected for Idle Mode 1, the SC400

    may (optionally) monitor the machine cycle input for

    failure. If Machine Watchdog is enabled, the SC400 will

    monitor(MACHCYC)forchanges instate. Ifapulse isnot

    receivedwithinaspecifiedperiodoftime,afaultwilloccur.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    MachineWatchdogTime

    If Machine Watchdog has been activated, a time period

    mustbespecified. Ifthemachinecycleinputdoesnotcycle

    withinthespecifiedperiodoftime,afaultwilloccur.

    Press toselectdesiredtimefield,seconds:minutes

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    NOTE: For systems using secondary functions (2 interval

    only), a second set of pump parameters are available.

    Theseparametersmaybesetappropriatelyforthesecond

    intervalusingtheaboveinstructions.

    AutofillPump

    SelectEnabledtoactivatefillpumpfunctionality. Ifthefill

    pump needs to be disabled (or if autofill system is not

    connected to the SC400) this parameter should be set as

    Disabled.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    AutofillTimeout

    If the autofill pump is enabled, a time period must be

    specifiedforthefillpumptooperate. Thisperiodshouldbe

    set long enough to allow for adequate filling, but short

    enoughtopreventdamagetothe fillpump incasethe fill

    pumpisrundry.

  • 7/24/2019 Controlador Bijur Delimon SC400

    19/24

    19 35979 R18/11

    Press to select desired time field, seconds: minutes:

    hours

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    LubeatPowerUp

    Even after power loss, the SC400 retains memory of its

    currentstatewithinthelubecycle. Ifthecustomerprefers

    that lubrication occur immediately after the control

    receivespower,setthisparametertoYES. Ifparameter is

    settoNO,theSC400willresumeactivityatthelastknown

    positionwithinthelubricationcycle.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Operation

    Onceparametersareset,press tochangesystemto

    runmode. Thesystemsetupisnowcomplete.

  • 7/24/2019 Controlador Bijur Delimon SC400

    20/24

    20 35979 R18/11

    PROGRAMMING CONTINUOUS

    Monitor Time

    TheSC400willsignalafaultiflubricationisnotproceeding

    as

    expected.

    OPCOMP_A

    (Terminals

    18,

    19,

    20)

    is

    monitoredforchanges instateduring lubrication. Ifthere

    is no activity from the cycle switch within a specified

    timeframe(Monitortime),afaultoccurs.

    Press to select desired time field, seconds: minutes:

    hours

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Autofill Pump

    SelectEnabledtoactivatefillpumpfunctionality. Ifthefill

    pump needs to be disabled (or if autofill system is not

    connected

    to

    the

    SC400)

    this

    parameter

    should

    be

    set

    as

    Disabled.

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Autofill Timeout

    If the autofill pump is enabled, a time period must be

    specifiedforthefillpumptooperate. Thisperiodshouldbe

    set long enough to allow for adequate filling, but short

    enough topreventdamageto thefillpump incase thefill

    pumpisrundry.

    Press to select desired time field, seconds: minutes:

    hours

    Press tochangevalueofdesiredfield.

    Press togotothenextparameter

    Lube at Power Up

    Even after power loss, the SC400 retains memory of its

    currentstatewithinthelubecycle. Ifthecustomerprefers

    that lubrication occur immediately after the control

    receives power, set this parameter to Enabled. If

    parameterissettodisabled,theSC400willresumeactivity

    atthelastknownpositionwithinthelubricationcycle.

    Press

    tochange

    value

    of

    desired

    field.

    Press togotothenextparameter

    Operation

    Onceparametersareset,press tochangesystemto

    run mode. The system setup is now complete.

    SYSTEM MESSAGES

    Duringoperation, theSC400sLCDwilldisplay information

    relatingtolubrication. Multiplemessagesmaybeinqueue,

    so

    messages

    will

    cycle

    periodically.

    Message

    information

    includes:

    Timing/Cycledata

    Monitortimeremaining

    Systemspecificdata

    Inaddition,otherinformationisavailable. Pressing will

    cause the display to the next message. If is pressed

    multipletimes,additionalscreenswillbedisplayed:

    Softwarerevision

    Daysofoperation

    Cyclescompleted

    Inputstatus

    (all

    external

    inputs)

    Outputstatus(pump,solenoids,etc)

    WARNING CONDITIONS

    Warning conditions are those events that require user

    attention, but are minor in nature. These events do not

    stoplubrication. WarningsareindicatedbyasolidredLED

    on the SC400. Warnings also cause activation of the

    Warningrelay. Warningsareselfclearingoncetheuse

    has rectified the problem, the warning will clear.

    High Level

    If an input signal is received from the high level input, a

    message,Warning!High lubricant levelwillbedisplayed.

    The reservoir has been overfilled. Stop fill pump

    immediately.

    Call Service

    Inapplicableregions,theSC400offersanotificationtothe

    user when regular system maintenance is required.

    Low Level

    Low level is user selectable as a warning or as a fault.

    When

    selectedas

    awarning,

    system

    lubrication

    continues

    normally. Customershouldtakesecondaryprecautionsto

    prevent the system from operating without lubricant.

  • 7/24/2019 Controlador Bijur Delimon SC400

    21/24

    21 35979 R18/11

    FAULT CONDITIONSFault conditions are thoseevents that cause the SC400 to

    ceasenormaloperation. Theseeventsarecriticalinnature

    andrequireimmediateattention. Faultsareindicatedbya

    blinking

    red

    LED

    on

    the

    SC400.

    Faults

    also

    cause

    activation

    ofboththeFaultandWarningrelays.

    Low Pressure

    If an input signal is received from the low pressure input

    (LOWPRES)whilelubricationisactive,aFaultwilloccurand

    Fault!Lowpressurewillbedisplayed. Airsystemshould

    beverifiedforproperfunction. Toclearthefault,press

    (orremotejogifconnected).

    AL2 High Pressure

    An inputsignalhasbeenreceivedfromtheAlarm2 input.

    Whena High pressureswitch is connected to theAlarm2

    input,aFault

    will

    occur

    and

    Fault!

    AL2

    High

    Pressure

    will

    be displayed. This indicates excessive pressure was

    detectedwithin thesystem. Inspect system forblockages

    and verify pump is operating properly. Once the high

    pressurecondition isrectified,thefaultmaybeclearedby

    pressing (orremotejogifconnected).

    AL2 - External Alarm 2

    An inputsignalhasbeenreceivedfromtheAlarm2 input.

    Rectify situation that caused input to trigger alarm. Once

    the issue isresolved, the faultmaybeclearedbypressing

    (orremotejogifconnected).

    AL2 Motor Trip

    An inputsignalhasbeenreceivedfromtheAlarm2 input.

    Whenamotorthermalcircuit isconnectedtotheAlarm2

    input,aFaultwilloccurandFault!AL2 MotorTripwillbe

    displayed. This indicates motor thermal had deactivated

    motor starter. Inspect motor and system for conditions

    that could cause motor to draw excessive current. Reset

    MotorThermalunitasrequired. Oncetheissueisresolved,

    the faultmay be cleared by pressing (or remotejog if

    connected).

    Parameters Lost

    The SC400 continuously verifies parameter settings to

    assure

    safe

    operation.

    In

    the

    event

    of

    memory

    failure,

    a

    faultwilloccurandSystemfault!Parameters lostwillbe

    displayed. To recommission the system, all parameters

    need to be verified by qualified personnel. Once all

    parametersareproperlyset,gotoreset lostparameters

    withinengineeringparameters. Selectyes,thenreturnto

    runmode. Faultwillautomaticallyreset.

    Verifycontrolpower iscleanandnearbyequipment isnot

    creatingelectricalnoise.

    Low Lubricant Level

    Low level isuserselectableasawarningorafault. When

    selectedasafault,systemlubricationceasesoncelowlevel

    isreachedandFault!Lowlubricantlevelisdisplayed. To

    resume operation, fill reservoir with fluid. Fault will

    automaticallyclearoncelevelreachesappropriatelevel.

    Monitor Timeout

    During lubrication, a feedback signal (pressure or cycle

    switch) is expected to change state within a specified

    period of time (Monitor time). A monitor timeout occurs

    when lubrication has not seen this signal change as

    expected. Typicalcausesare:

    Lack of lubricant flow (Air in lubrication line,

    pumpmalfunction,emptyreservoir,etc)

    Electrical failure (cycle switch failure, poor

    electricalconnection,blownfuse,etc)

    Watchdog Timeout

    When selected, SC400 counts pulses from customers

    equipment during idle period. If a pulse is not received

    withinaspecifiedperiodoftime(WatchdogTime),aFault

    occurs and watchdog Timeout is displayed. Examine

    customers equipment for cause of failure and rectify.

    Oncecompleted,press (orremotejog ifconnected)to

    resetfault.

    Overcount

    When selected, SC400 counts pulses from cycle switch

    during idle period. If pulses received is greater than the

    specified limit(Overcountcycles),afaultoccursandFault

    Overcount

    is

    displayed.

    Rectify

    problem

    andpress

    (orremotejog ifconnected) toresetfault. Typicalcauses

    include poor electrical connection to cycle switch and

    malfunctioningsolenoidvalve/motorstarter(topump).

    EEPROM

    Periodically,theSC400willperformacheckon its internal

    EEprom (memory). This is performed to assure safe and

    reliableoperation. IntheunlikelyeventofEEpromfailure,

    a fault will occur and System Fault! EEPROM will be

    displayed. The fault may be cleared by pressing (or

    remotejogifconnected). Iffaultrepeatsorisunabletobe

    cleared,theSC400circuitboardmustbereplaced.

    Autofill Failure

    Whenfillpump isrunning,SC400expectsthefluid levelof

    thereservoirtorise. Iffluidlevelhasnotincreasedwithin5

    minutes (or Autofill time, if less than 5 minutes), a fault

    occursandFault!Autofillfailureisdisplayed.

    Torectify,replacefluidinfillpump. Oncecompleted,press

    (or remotejog if connected) to reset fault. Autofill

    pumpwillrestartautomatically.

  • 7/24/2019 Controlador Bijur Delimon SC400

    22/24

    22 35979 R18/11

    APPENDIX: SYSTEM EXAMPLES

    Series Progressive Systems

    SingleZone Two(2)Zone

    Single Line Injector Parallel) Systems

    SingleZone Two(2)Zone

  • 7/24/2019 Controlador Bijur Delimon SC400

    23/24

    23 35979 R18/11

    Dualine Systems w/ Hydraulic Reversing Valve)

    Single Zone Two (2) Zone

    Dualine Systems w/ Electric Reversing Valve)

    w/ 2 Pressure Switches( or SGA valve) w/ PC5 Pressure Switch(old style Denco)

  • 7/24/2019 Controlador Bijur Delimon SC400

    24/24

    TECH DATA SHEET LIST

    Foradditionalinformationrefertothewebsiteforthefollowingdatasheets:

    35682

    SC400

    Two

    Individual

    Pump

    System

    Wiring

    Guide35683 SC400AutofillProgrammingandInstallationGuide

    35684 SC400AdvancedWiringGuide

    35685 SC400ConvertingSS4500userstoSC400

    SERVICE PARTS

    EnclosurewithDoorandKeypad.Part#37376

    Footmountingkitonly.Part#37275

    PCBBoardonly(doesnotincludeLCDboard).Part#37274

    LCDdisplayboardonly....Part#37274LCD