Controlling boiler emissions in an industrial cluster-A case study

Prof. H S SyedAsst. Prof. of Env. Engg

L. D. College of Engg, Ahmedabad

November , 2011

Page 2: Controlling boiler emissions in an industrial cluster-A case study

Chimney, the stack attached to the boiler house.

• A symbol of progress and development in the past

• Now, a symbol of pollution and hence a concern

Page 3: Controlling boiler emissions in an industrial cluster-A case study

Heat requirements in the industry are satisfied by

steam generated at boiler house.

Boiler House - an important source of air pollution.

Different types of boilers, of different capacities using

different types of fuel with different operating conditions

are in use.

Page 4: Controlling boiler emissions in an industrial cluster-A case study

Case Study:

• Narol Industrial cluster of textile process houses

was identified as a major source of pollution by

Supreme Court appointed Environmental Pollution Control

Authority(EPCA) – Bhurelal Committee.

• Also identified by GPCB as major air polluter with reference to

CEPI (Comprehensive Environmental Pollution Index ) score

of MOEF .

Page 5: Controlling boiler emissions in an industrial cluster-A case study

Environmental Engg Department , L D College of

Enginering , Ahmedabad was approached by

Ahmedabad Textile Process Association (ATPA) to

study the problem and provide a solution to

pollution.

Page 6: Controlling boiler emissions in an industrial cluster-A case study

Case Study:

• Narol Industrial cluster of textile process houses

122 Process Houses

91 having Steam Boilers and Thermic Fluid Heaters

87 have been surveyed and data collected

Page 7: Controlling boiler emissions in an industrial cluster-A case study

Broad Classification Of Boilers Based On

Steam Generation Capacity

≤ 2 Ton/hr 35

5 – 7.5 Ton/hr 35

10 Ton/hr 14

≥ 10 Ton/hr 3

Page 8: Controlling boiler emissions in an industrial cluster-A case study

The Different Fuels Used In The BoilerSr No. Steam Generation Capacity Type of fuel No. of units

1 ≤ 2 T/hr Saw dust 2

Wood 33

Lignite 7

2 5 T/hr Saw dust 5

Lignite 19

Wood 8

Coal 3

3 10 T/hr Agro waste 1

Lignite 10

Coal 3

4 > 10 T/hr Agro waste 1

Lignite 2

Page 9: Controlling boiler emissions in an industrial cluster-A case study

The common fuels used are wood for ≤ 2 Ton/hr and lignite for ≥ 5

Ton/hr capacity boilers.

Proximate Analysis of Fuel

Proximate Analysis

Wood Indian CoalLignite

(MatanoMadh)Saw Dust

Moisture -- 5.98 11.71 37.98

Ash 0.10 38.63 20.05 1.63

Volatile Matter 76.40 34.69 41.70 81.22

Fix Carbon 23.50 20.70 26.20 17.15

The Proximate Analysis Of The Fuel

Page 10: Controlling boiler emissions in an industrial cluster-A case study

The common air pollutants encountered: PM,

SO2 & NOx

The air pollutants namely particulate matter (PM),

SO2 and NOx primarily depend on the fuel used

as well as on the operating conditions and

procedures adopted.

Page 11: Controlling boiler emissions in an industrial cluster-A case study

Based on the proximate analysis stoichometry calculation for

pollutants (50% Excess Air)

Parameters Lignite Saw Dust

PM, mg/m3 10,200 3950

SO2, ppm 500 --

Page 12: Controlling boiler emissions in an industrial cluster-A case study

Out of 87 - 30 selected units were monitored for air pollution

parameters.

Sr. No.

Steam Generation

Capacity

PM mg/Nm3 SO2 ppm NOx

Range Average Range Average Range Average

1 2 Ton/hr 225 – 698 450 9 – 308 120 0.5 – 8.0 4

2 5 Ton/hr 61 – 840 435 6 – 400 175 0.5 – 9.0 7

3 10 Ton/hr 500 – 2500 1500 12 -700 350 5-14 10

The Measured Concentration Of Pollutants

Page 13: Controlling boiler emissions in an industrial cluster-A case study

The present scenario: About pollutant control equipments/

systems;

Practically all boilers are equipped with multi cyclones

Not designed appropriately

Offers only 30- 35 % removal of PM

Page 14: Controlling boiler emissions in an industrial cluster-A case study

≤ 2 Ton/hr: No economizer or pre-heaters are installed to

control temperature

≥ 5 Ton/hr: Economizer or pre – heaters are installed for heat

recovery and hence temperature control

Bag filters are installed at practically all the units.

Under compulsion and directions of Bhurelal committee and

GPCB

Page 15: Controlling boiler emissions in an industrial cluster-A case study

The boilers with steam generation capacity ≥ 5 Ton/hr,

mostly use lignite as fuel.

Lignite generates PM and SO2.

Wood generates PM

However, no system is installed to control SO2 in

the flue gas.

Page 16: Controlling boiler emissions in an industrial cluster-A case study

The multi cyclones and bag filters installed are not

appropriately designed and hence are neither

adequate nor efficient

Result is gross non - compliance of the emission

standards.

Page 17: Controlling boiler emissions in an industrial cluster-A case study

Environmental Engineering Department of L.D. College,

Ahmedabad has proposed/ developed the scheme

Design Approach:

For ≤ 2 Ton/hr capacity wood/saw dust as fuel

Multi cyclone – Venturi Scrubber– Cyclone separator-Demistifer

For ≥ 5 Ton/hr capacity lignite as fuel

Multi cyclone – Bag Filter – Packed bed Alkali wet Scrubber

Page 18: Controlling boiler emissions in an industrial cluster-A case study

1 Venturi Scrubber 7. Filter Cloth

2 Cyclonic Separator 8. Mesh Pad Type Demister

3 ID fan 9. Alkali storage tank (powder / lye)

4Stack 10. Feeder

5Filter neutsch 11. Mixing tank

6Alkali Recirculatin Pump 12. Pump (Alkali Solution)

: The Proposed Air Pollution Control System for ≤ 2 TPH Lignite based Boiler

125

10

11

1

2

7

5

6

3 4

8

Page 19: Controlling boiler emissions in an industrial cluster-A case study

The Proposed Air Pollution Control System

≥ 5 Ton/hr capacity: Lignite as Fuel

Furnace

Pre Air Heater

Multi Cyclo

ne

Bag House

Cyclone

ID Fan Alkaline Wet Scrubb

er

Stack

Bypass

Page 20: Controlling boiler emissions in an industrial cluster-A case study

The Expected Results: When installed as per the

design and operated as directed the emissions

norms will be satisfied.

Page 21: Controlling boiler emissions in an industrial cluster-A case study