CONTROL PANEL WIRING SCHEMATICAND OPTION GUIDE
420 Third Street 83 West Drive, Bramton
Piqua, Ohio 45356 Ontario, Canada L6T 2J6
Phone: (937) 778-8947 Phone: (905) 457-6223
Fax: (937) 773-7157 Fax: (905) 457-2650
www.cranepumps.com Form No. 1448-Rev. D
ii
Other brand and product names are trademarks or registered trademarks of their respective holders.
® Barnes is a registered trademark of Crane Pumps & Systems, Inc
1986, 1997, 2003, 5/06, 9/06 Alteration Rights Reserved
INTRODUCTION
The intent of this manual is to familiarize the user with the symbols used for each of the
options on a control panel wiring schematic. The manual will detail the schematic diagram for
each of the options and attempt to provide an understanding for each of the functions of the
option. The manufacturer’s part number will be listed for each of the options, however, they are
subject to change due to specifi cation requirements or availability.
If you have any questions regarding the use of any of the options or its placement in the
schematic diagram please feel free to contact the factory.
iii
ELECTRICAL SYMBOLS
iii
iv
CONTENTSALARM COMPONENTS - Enclosure Mounted:
Part No Description ........................................................................................................................... Page
064672 Shielded Weatherproof Flashing Red Light ........................................................................... 1
064673 Weatherproof 4” Bell, Alarm Silencer and Red High Water Indicator Light. .......................... 1
064674 Weatherproof Alarm Horn, Alarm Silencer and Red High Water Indicator Light. ................... 2
073604 Dry Contacts for Remote Alarm Functions. ........................................................................... 2
075601 Dim Glow Alarm ..................................................................................................................... 3
Dim Glow Alarm with 064672 Light and 064673 Bell ............................................................. 3
Dim Glow Alarm with 064672 Light and 064673 Horn ........................................................... 4
PANEL MOUNTED OPTIONS:064675 Moisture Sensor Relay .......................................................................................................... 4
064681 Temperature Sensor Relay .................................................................................................... 5
085325 Moisture Sensor Test Circuit .................................................................................................. 6
064676 Elapsed Time Meter ............................................................................................................... 6
064677 Pump Sequence Selector Switch .......................................................................................... 6
064403 Intrinsically Safe Relay .......................................................................................................... 7
075629 Selector Switch, 2 Position .................................................................................................... 7
075630 Selector Switch, 3 or 4 Postion .............................................................................................. 8
075638 NEMA 4 Light ......................................................................................................................... 8
075637 NEMA 4 Push Button ............................................................................................................. 8
075636 Auxiliary Contacts - Relay DPDT ........................................................................................... 8
075635 Auxiliary Contacts - On Motor Control ................................................................................... 9
075631 Electronic Timer ..................................................................................................................... 9
075632 24 Hour Timer ........................................................................................................................ 9
075633 7 Day Timer ........................................................................................................................... 10
075634 .5 Hrs to 60 Hrs Timer - Motor Driven .................................................................................... 10
093504 Timer, Electronic, Lag Pump Delay ....................................................................................... 10
075639 Ammeter - Single Phase ........................................................................................................ 11
075640 Ammeter - Three Phase ........................................................................................................ 11
UTILITY TRANSFORMERS with OUTLET - Panel Mounted:079027 Utility Outlet, 115V & 230V, NEMA 1, No Transformer .......................................................... 12
064679 Utility Transformer, 1.5 KVA ................................................................................................... 12
075602 Utility Transformer, 3.0 KVA ................................................................................................... 12
075603 Utility Transformer, 5.0 KVA ................................................................................................... 12
064680 Utility Outlet, 115V & 230V, NEMA 3R, w/GFI ....................................................................... 13
SERVICE ENTRANCE OPTIONS - Panel Mounted:064683 Reconnect Relay - 115 Volt AC - 1 KVA Maximum ................................................................ 13
064684 Reconnect Relay - 200/230 Volt AC - 1 KVA Maximum ......................................................... 13
064685 Reconnect Relay - 460 Volt AC - 1 KVA Maximum ................................................................ 13
036189 Lighting Arrestor - Single Phase ............................................................................................ 14
058582 Lighting Arrestor - Three Phase ............................................................................................. 14
064688 Phase Failure / Under Voltage Sensor - 200/230 VAC, 3 Phase ........................................... 14
064689 Phase Failure / Under Voltage Sensor - 460 VAC, 3 Phase .................................................. 14
064686 Under Voltage Sensor - 115/120 Volt AC, Single Phase ........................................................ 15
079847 Under Voltage Sensor - 200 Volt AC, Single Phase .............................................................. 15
064687 Under Voltage Sensor - 230 Volt AC, Single Phase ............................................................. 15
MASTER CIRCUIT BREAKER- Panel Mounted No Operator:075605 Master Circuit Breaker - 115/230 VAC, 1 Phase - 7- Amp ..................................................... 15
075606 Master Circuit Breaker - 200/230 VAC, 3 Phase - 100 Amp .................................................. 15
075607 Master Circuit Breaker - 460 VAC, 3 Phase - 100 Amp ......................................................... 15
082140 Circuit Breaker - Single Phase, 230 VAC, 3.5 KVA, 2 Pole ................................................... 16
082141 Circuit Breaker - Single Phase, 460 VAC, 7 KVA, 2 Pole ...................................................... 16
FUSED DISCONNECTS with Door Mounted Operators:079029 Fused Disconnect, 115/230VAC, 1 Ph, 60A, NEMA 1 ........................................................... 16
079030 Fused Disconnect, 460VAC, 3 Ph, 100A, NEMA 1 ................................................................ 16
075626 Door Interlock - Through Outer Door For Fused Disconnect ................................................. 17
075625 Door Interlock - Through Inner Door For Fused Disconnect .................................................. 17
v
Part No Description ........................................................................................................................... Page
CIRCUIT BREAKER - Door Interlocks:075627 Use with 230 VAC Circuit Breaker, NEMA 1 .......................................................................... 18
075628 Use with 460 VAC Circuit Breaker, NEMA 1 .......................................................................... 18
CONTROL CIRCUIT POWER OPTIONS:079841 24 Volt AC Control Circuit - No Other Options ....................................................................... 19
082137 24 Volt AC Control Circuit on Controls with Panel ................................................................. 19
079842 24 Volt AC Control Circuit on 115 VAC Controls Only Mounted 115 Volt AC Transformer .... 19
ENCLOSURE RELATED OPTIONS:066361 Dead Front Door with Inner Door - Simplex .......................................................................... 20
066362 Dead Front Door with Inner Door - Duplex ............................................................................ 20
064690 Enclosure Interior Service Light - Fluorescent ....................................................................... 21
064678 Panel Heater with Thermostat Control ................................................................................... 21
MANUAL TRANSFER SWITCH - Control Panel Mounted:075641 60 Ampere, 230/460VAC, 3 Phase ........................................................................................ 22
075642 100 Ampere, 230/460VAC, 3 Phase ...................................................................................... 22
075643 200 Ampere, 230/460VAC, 3 Phase ...................................................................................... 22
ENCLOSURES:064691 NEMA 3R Enclosure for Remote Alarm ................................................................................. 23
075615 NEMA 3R Enclosure, Oversize Simplex “A” - Steel, Gray ..................................................... 23
075616 NEMA 3R Enclosure, Oversize Duplex “A” - Steel, Gray ...................................................... 23
064682 NEMA 4 Enclosure, Simplex - Steel ...................................................................................... 23
075608 NEMA 4 Enclosure, Duplex - Steel ........................................................................................ 23
075617 NEMA 4 Enclosure, Oversize Simplex “A” - Steel, Gray ....................................................... 23
075618 NEMA 4 Enclosure, Oversize Duplex “A” - Steel, Gray ......................................................... 23
075609 NEMA 4X Enclosure, Simplex - Fiberglass ........................................................................... 23
075610 NEMA 4X Enclosure, Duplex- Fiberglass .............................................................................. 23
075619 NEMA 4X Enclosure, Oversize Simplex “A” - Fiberglass ..................................................... 23
074620 NEMA 4X Enclosure, Oversize Duplex “A” - Fiberglass ........................................................ 23
075611 NEMA 4X Enclosure, Simplex - Stainless Steel .................................................................... 23
075612 NEMA 4X Enclosure, Duplex - Stainless Steel ...................................................................... 23
075621 NEMA 4X Enclosure, Oversize Simplex “A” - Stailess Steel ................................................. 23
075622 NEMA 4X Enclosure, Oversize Duplex “A” - Stainless Steel ................................................. 23
075613 NEMA 12 Enclosure, Simplex - Steel .................................................................................... 23
075614 NEMA 12 Enclosure, Duplex - Steel ...................................................................................... 23
075623 NEMA 12/13 Enclosure, Oversize Simplex “A” - Steel ......................................................... 23
075624 NEMA 12/13 Enclosure, Oversize Duplex “A” - Steel ............................................................ 23
ENCLOSURE TYPES ............................................................................................................ 24
HEATER TABLE .................................................................................................................... 25
1
ALARM OPTIONS:064672 [0854]- HIGH WATER ALARM LIGHT, 90º MTD.
The alarm light is a 90 dgree mounted vapor-proof fi xture with a 40 watt fl ashing red light which gives a visual warning of high
water in the wet well. This light will not be turned off with the alarm off switch used in conjunction with an audible alarm, but will
keep fl ashing until the lowering of water in the wet well.
PARTLIST:
Light - RAB B100GG
Bulb - G. E.
Flasher - Superior 1008
Fuse Block - Littlefuse 350-329
Fuse - Littlefuse 3AB, 1-1/2 amp
Terminal Strip - Connectron KT3
HIGH WATER ALARM LIGHT, TOP MTD.
The alarm light is a Top Mounted vapor-proof molded unbreakable acrylic plastic fi xture with a 40 watt fl ashing red light which
gives a 360º visual warning of high water in the wet well. This light will not be turned off with the alarm off switch used in
conjunction with an audible alarm, but will keep fl ashing until the lowering of water in the wet well.Schematic same as 064672.
064673 [0855]- HIGH WATER ALARM BELL:
The alarm bell is a 4” vibrating bell which produces an 87db @ 10 foot audible warning of high water in the wet well. An alarm
off switch will silence the bell, but leave a small red light on to show that the high water condition still exists. The alarm will
automatically reset on lowering of water in the wet well. NOTE: The parts marked with * will not be supplied if you order a
064672 High Water Alarm Flashing Red Light with this alarm.
PARTS LIST:
Bell - W.L. Jenkins # 1005
Relay - Idec # RH2BUAC120V.
Socket - Idec # SH2B-05
Switch - McGill # 3190001 (Momentary)
* Light - Littelfuse # 961-8-04-91WRN
* Fuse block - Littelfuse # 350-329
* Fuse - Littelfuse 3AB, 1-1/2 Amp
* Terminal - Connectron # KT3
File: W64672.Dwg
File: W64673.Dwg
2
ALARM OPTIONS:
064674 [0856]- HIGH WATER ALARM HORN:
The alarm horn is a 4” square vibrating horn which produces an 92db @ 10 foot audible warning of high water in the wet well.
An alarm off switch will silence the horn, but leave a small red light on to show that the high water condition still exists. The
alarm will automatically reset on lowering of water in the wet well. NOTE: The parts marked with * will not be supplied if you
order a 064672 High Water Alarm Flashing Red Light with this alarm.
PARTS LIST:
Horn Wheelock 31-115AC-S 4” SQ. 92db.
Relay IDEC # RH2BUAC120V.
Socket IDEC #SH2B-05.
Switch McGill #3190001
* Light - Littelfuse # 961-8-04-91WRN
* Fuse block - Littelfuse # 350-329
* Fuse - Littelfuse 3AB, 1-1/2 Amp
* Terminal - Connectron # KT3
073604 [0868]- HIGH WATER ALARM DRY CONTACT:
The alarm dry contact is a D.P.D.T. relay rated at 10 amps, 250 volts. These contacts are not connected to a power source in
the control panel. These contacts are primarily used to operate telemetering and remote high water alarms.
NOTE: This option should be used when a remote alarm is used.
PARTS LIST:
IDEC Relay #RH2BUAC120V.
IDEC Socket #SH2B-05
McGill Switch #3190001
Littelfuse Fuse Block #350329
Littelfuse Fuse 3AB, 1-1/2 amp
Connectron Terminals #KT3
File: W64674.Dwg
File: W73604a.Dwg
File: W73604.Dwg
With Panel Mounted Alarm
Without Panel Mounted Alarm
3
ALARM OPTIONS: 075601 [0857]- DIM GLOW ALARM:
The Dim Glow option is ordered separately with the 064672 H.W.A light. This option will cause the alarm light to glow dimly
during normal operations, but come to full brilliance and fl ash between dim and full power during high water conditions. The
light will revert to dim glow on lowering of the high water in the wet well.
NOTE: This Dim Glow option is used EXCLUSIVELY with the 064672 High Water Alarm Light.
PARTS LIST:
Dim Glow & Flasher 075601 with 064672 H.W.A. Light
1 Light RAB B100 GG
1 Bulb
1 AC-DC EFG2-120VAC, 25% Dim Glow & Flasher
1 Littelfuse Fuse Holder #305029
1 Littelfuse Fuse 3AG 1-1/2 amp #312
Dim Glow 075601 [0857] with 064672 Light and 064673 Bell:
The Bell is silent during normal operation and will ring at 87db during high water conditions. Pushing the alarm off switch
will silence the bell and leave the High Water Alarm Light on. The alarm bell relay and light will reset automatically with
lowering of the water level in the wet well.
When this option is used, add the following parts to the 075601 and 064672 parts list:
1 Bell - W.L. Jenkins # 1005
2 Relay - Idec # RH2BUAC120V.
2 Socket - Idec # SH2B-05
1 Switch - McGill # 3190001 (Momentary)
File: W75601.Dwg
File: W75601a.Dwg
4
ALARM OPTIONS: Dim Glow 075601 [0857] with 064672 Light and 064674 Horn:
The Horn is silent during normal operation and will ring at 92db during high water conditions. Pushing the alarm off switch
will silence the horn and leave the High Water Alarm Light on. The horn relay and light will reset automatically with lowering of
the water level in the wet well.
When this option is used, add the following parts to 075601 and 064672 parts list:
1 Horn Wheelock 31-115AC-S 4” SQ. 92db.
2 Relay IDEC # RH2BUAC120V.
2 Socket IDEC #SH2B-05.
1 Switch McGill #3190001
PANEL MOUNTED OPTIONS: 064675 [0861]- MOISTURE SENSOR RELAY:
This relay is connected to two sensing probes in the pump seal chamber. These probes will detect moisture in the pump and
operate a door mounted warning light on the control panel to indicate a failed seal. One required for simplex, two for duplex.
Rated for 25 Volt Amperes, 115 Volt Input, 500 Volt Output. Probs in Pumps are rated 1watt @ 330K Ohms, 500 Volts.
PARTS LIST:
Warrick relay #IDIEO
IDEC Light #APW-199
Connectron Terminal #KT3
File: W75601b.Dwg
File: W64675s.DwgSIMPLEX File: W64675d.DwgDUPLEX
5
PANEL MOUNTED OPTIONS: 064681 [0876] - TEMPERATURE SENSOR RELAY WITH LIGHT:
This relay is connected in series with the thermostat which is embedded in the pump motor windings. If the motor overheats,
the thermostat will open causing the relay to de-energize which will stop the pump motors and light a small red pilot light in the
control panel. The pump(s) will restart automatically when the thermostat cools.
IMPORTANT! - EACH CONTROL PANEL IS EQUIPPED AS STANDARD EQUIPMENT, WITH TERMINALS FOR TEMPERATURE SENSORS. THESE THERMOSTATS ARE WIRED IN LINE WITH WITH THE PUMP MOTOR
STARTER COIL AND WILL TURN THE MOTOR OFF WITH TEMPERATURE RISE. QUANTITY OF ONE REQUIRED FOR EACH PUMP.
PARTS LIST:
IDEC Relay #RH2BUAC120V
IDEC Socket #SH2B-05
Littelfuse Light #961-8-04-91WRN
Connectron Terminal #KT3
File: W64681s.Dwg
File: W64681d.Dwg
SIMPLEX
DUPLEX
6
PANEL MOUNTED OPTIONS:085325 [2661] - MOISTURE SENSOR TEST CIRCUIT:
A normally closed pusbutton and neon indicating lamp are provided as means of checking the moisture sensing components.
When the pushbutton is depressed, the indicating lamp will be illuminated to indicate (1) power is supplied to the control, (2)
the control is operative, and (3) wiring to the moisture sensing probes in the motor is intact. This option is used in conjuction
with 064676.
PARTS LIST:
IDEC Push-To-Test Button with Clear Neon Light # 1630AC
064676 [0865] - ELAPSED TIME METERS:
The elapsed time meter indicates pump running time in hours and tenths of hours to a total of 99999.9. This non-reset meter is
useful in determining when periodic maintenance should be performed on the pumps. One (1) required per pump.
PARTS LIST:
Engler #10NG7 or #02-010117-000.
064677 [0866] - PUMP SEQUENCE SELECTOR SWITCH:
The selector switch is provided to override the automatic alternator. This option is useful if it becomes necessary to remove
one pump from the duplex system. Either pump may be selected as the lead pump.
PARTS LIST:
Selector Switch Furnas #52SB2CAB OR
Selector Switch IDEC #ASW300-1
File: W85325.Dwg
File: W64676.Dwg
File: W64677.Dwg
7
PANEL MOUNTED OPTIONS:064403 [0867] - INTRINSICALLY SAFE RELAY:
The intrinsically safe relay is a reduced voltage power supply that produces a low voltage and current to the fl oat switches in
the wet well. If one of these fl oat switches were to break open and expose the control wiring, the applied voltage would not
cause a spark which could ignite explosive gases or combustible liquids that might happen to be in the wet well.
The Intrinsically Safe Relay is for Explosion Proof Applications, one (1) is required for simplex and two (2) for duplex
plus one for any alarm function.
PARTS LIST:
C.F. Warrick 27AIDO
075629 [0900] - SELECTOR SWITCH 2 POSITION:
Additional 2 position selector switch is oil tight and panel mounted. Standard with 1 Normally Open (NO) and 1 Normally
Closed (NC) contact, unless otherwise specifi ed. NOTE: USER MUST DEFINE THE OPERATION OF THIS OPTION.
PARTS LIST:
IDEC Switch #ASW200
File: W64403.Dwg
File: W75629.Dwg
8
PANEL MOUNTED OPTIONS:075630 [0901] - SELECTOR SWITCH 3 or 4 POSITION:
Additional 3 position selector switch is oil tight and panel
mounted. Standard with 2 Normally Open (NO) and 2
Normally Closed (NC) contact, unless otherwise specifi ed.
NOTE: USER MUST DEFINE THE OPERATION OF THIS
OPTION.
PARTS LIST:
IDEC 3 Position Switch #ASW300
IDEC 4 Position Switch #ASW400-1
075638 [0910] - NEMA 4 LIGHT:
115 volt control, oil tight panel mounted light. Amber (A),
Green (G), Red (R) or White (W).
NOTE: USER MUST DEFINE THE OPERATION OF THIS
OPTION.
PARTS LIST:
IDEC Light #APW199
075637 [0909] - NEMA 4 PUSH BUTTON:
Oil tight push button for manual control of a user defi ned
function. Oil tight panel mounted momentary contact button
may be wired as user directs when designing the control.
May be used as TEST button to exercise control functions,
reset button, or in any other circuit needing a momentary
contact closure.
NOTE: USER MUST DEFINE THE OPERATION OF THIS
OPTION.
PARTS LIST:
IDEC Push Button #ABW100
075636 [0907] - AUXILIARY CONTACTS - RELAY DPDT:
A general purpose relay, panel mounted, to provide 2 DPDT contacts to operate remote alarm, event recorder or other user
defi ned loads. May be energized from motor control circuit (s) or other user defi ned source.
NOTE: USER MUST DEFINE THE
OPERATION OF THIS OPTION.
PARTS LIST:
Normally Open (NO) Furnas
#49DZ21251
Normally Closed (NC) Furnas #
49DZ21252
File: W75630.Dwg
File: W75636.Dwg
File: W75638.Dwg
File: W75637.Dwg
9
PANEL MOUNTED OPTIONS:075635 [0906] - AUXILIARY CONTACTS - ON MOTOR CONTROL:
Provides user with one or more auxiliary contact on the motor starting device. To provide remote sensing of motor running time
or initiate other operations external or internal with motor operation.
PARTS LIST:
Normally Open (NO) Furnas # 49DZ2125001
Normally Closed (NC) Furnas #49D22125002
075631 [0902] - ELECTRONIC TIMER:
A general purpose time delay relay added to control. An electronic device with 2 Form “C” contacts to provide delay on start
of second motor, contact closure, verifi cation fl oat switches, or any other time related function in the control system. Also
available as a repeat cycle timer for repetitive system functions which are time related.
NOTE: USER MUST DEFINE THE OPERATION OF THIS OPTION.
PARTS LIST:
Timer IDEC #RTE-P12
Base IDEC #SR2P-05
075632 [0903] - 24 HOUR TIMER:
A panel mounted 24 hour timer to allow programming events in the system. May be used for once-a-day motor alternation, or
to run stand-by motor daily. NOTE: USER MUST DEFINE THE OPERATION OF THIS OPTION.
PARTS LIST:
AMF/Paragon Series 1015-S
File: W75635.Dwg
File: W75631.Dwg
File: W75632.Dwg
10
PANEL MOUNTED OPTIONS: 075633 [0904] - 7 DAY TIMER:
A panel mounted 7 day timer to allow programming events in the system. May be specifi ed with power loss carry-over.
NOTE: USER MUST DEFINE THE OPERATION OF THIS OPTION.
PARTS LIST:
AMF/Paragon Series EC7000
075634 [0905] - .5 Hrs to 60 Hrs. - MOTOR DRIVEN:
For adjustable timing of events such as accumulating running time on a motor load to a pre-set number of hours. Available with
ranges from one-half hour to 60 hours. NOTE: USER MUST DEFINE THE OPERATION OF THIS OPTION.
093504 [0923] - Timer, Electronic, Lag Pump Delay:
A user adjustable timer to prevent simultaneous starting of both pumps. Usfull to prevent high current draw after long power
outage. Recommended for single phase pump controls and duplex systems to be run on generator power (Duplex Only).
PARTS LIST:
Timer, #IDEC RTE-P11-120V
Base, #IDEC SR2P-05
File: W75633.Dwg
File: W93504.Dwg
File: ---------
11
PANEL MOUNTED OPTIONS:
075639 [0916] - AMMETER - SINGLE PHASE:
A panel mounted A.C. reading ammeter with panel mounted
current transformer. To indicate to the operator the amperage
load.
PARTS LIST:
Crompton Instruments Fiesta Type 02.
Weshler Current Transformer*
* Transformer Ratio selected to give 40 - 50% meter
reading at pump FLA.
075640 [0917] - AMMETER - THREE PHASE:
A panel mounted ammeter with current transformer for three
phase controls. To indicate to the operator the amperage load.
This option includes three current transformers and shorting
selector switch to monitor three phase systems.
PARTS LIST:
Crompton Instruments Fiesta Type 02
Electroswitch Ammeter Switch Series 24
Weshler Current Transformer*
* Transformer Ratio selected to give 40 - 50% meter
reading at pump FLA.
File: W75639.Dwg
File: W75640.Dwg
12
UTILITY TRANSFORMER WITH OUTLETSPANEL MOUNTED OPTIONS:
Options 1.5KVA thru 5.0KVA transformer and outlet require next larger size enclosure.
079027 [2632] - CONVENIENCE OUTLET
WITHOUT POWER TRANSFORMER:
A 115 volt duplex outlet with weather tight
cover is mounted on the side of the panel
enclosure for 15 amp max. utility use. NOTE:
A 200/240 volt, 3 phase 4-Wire service or
120/240 volt, Single phase 3-Wire service
which produces 115 volts to neutral is required
for this option.
PARTS LIST:
Hubbel Receptacle #GE4065
Reddot Cover #CCD
Littelfuse Fuse Block #350329
Littelfuse Fuse 3AB 15amp
CONVENIENCE OUTLET WITH TRANSFORMER:
064679 [0862] - 1.5KVA
075602 [0863] - 3KVA
075603 [0864] - 5KVA
A 115 volt duplex outlet with weather tight
cover is mounted on the side of the panel
enclosure. For 15 amp utility use. The option
is standard with 1.5KVA power transformer
connected to the primary line with fused
secondary.
PARTS LIST:
Part No. 064679:
Micron transformer #ENX1K5PU1519HI
Hubbel Receptacle #GE4065
Reddot Cover #CCD
Littelfuse Fuse Block #350329
Littelfuse Fuse 3AB 15amp
Part No. 075602:
Micron Transformer #EN3KPU1519
Hubbel Receptacle #GE4065
Reddot Cover #CCD
Littelfuse Fuse Block #350329
Littelfuse Fuse 3AB 15amp
Part No. 075603:
Micron Transformer #EN5KPU1519
Hubbel Receptacle #GE4065
Reddot Cover #CCD
Littelfuse Fuse Block #350329
Littelfuse Fuse 3AB 15amp
File: W79027.Dwg
File: W64679.Dwg
13
UTILITY TRANSFORMER WITH OUTLETSPANEL MOUNTED OPTIONS:
Options 1.5KVA thru 5.0KVA transformer and outlet require next larger size enclosure.
064680 [2634] - GROUND FAULT CONVENIENCE OUTLET:
A 115 volt ground fault receptacle to be used on the convenience outlet option.
PARTS LIST:
Bryant receptacle #GFR83-1
Littelfuse Fuse Block #350329
LIttelfuse Fuse 3AB 15 amp
SERVICE ENTRANCE - PANEL MOUNTED OPTIONS:
The following options require additional enclosure volume and may require larger enclosures.
CONTROL CIRCUIT RECONNECT RELAY:
064683 [0850] - 115 Volt, 1KVA max.
064684 [0851] - 230 Volt, 1KVA max.
064685 [0853] - 460 Volt, 1KVA max.
The reconnect relay will transfer the control voltage from the “Pump 1” circuit breaker to the “Pump 2” circuit breaker in the
event of the “Pump 1” circuit breaker tripping. This relay will hold the control voltage on the “Pump 2” circuit breaker until the
“Pump 1” circuit breaker is reset.
PARTS LIST:
Part No. 064683:
1 IDEC Relay #RR2PUAC120V
1 IDEC Base # SR2P-05
Part No. 064684:
1 IDEC Relay #RR2PUAC230V
1 IDEC Base # SR2P-05
Part No. 064685:
1 Furnas Relay #MT4640H
File: W64680.Dwg
File: W64683.Dwg
14
SERVICE ENTRANCE - PANEL MOUNTED OPTIONS:The following options require additional enclosure volume and may require larger enclosures.
LIGHTNING ARRESTOR:
036189 [0859] - Single Phase
058582 [0860] - Three Phase
The lightning arrestor is connected to the incoming power lines and panel ground. This arrestor will reduce the chances of
pump and control panel damage from voltage transient caused by lightning.
PARTS LIST: PARTS LIST:
Part No. 036189: Part No. 058582:
Delta #LA302R, 300volt, 1 Phase. Delta #LA603, 600volt, 3 Phase.
PHASE FAILURE RELAY:
064688 [ ] - 230V, 3 Phase
064689 [0874] - 460V, 3 Phase
This relay is connected
to the primary power service to detect phase loss, improper phase rotation and under-voltage on one or all phases of the
service. This relay will automatically start and stop the pump motors under these conditions.
PARTS LIST:
064688:
Furnas Relay #47VA32G
USD Fuse Block #11425
Buss Fuse 1 amp #KTK
IDEC relay #RH2BUAC120V
IDEC base #SH2B-05
064689:
Furnas Relay #47VA32H
USD Fuse Block #11425
Buss Fuse 1 amp #KTK
IDEC relay #RH2BUAC120V
IDEC base #SH2B-05
File: W58582.Dwg
File: W64688.Dwg
File: W36189.Dwg
15
SERVICE ENTRANCE - PANEL MOUNTED OPTIONS:The following options require additional enclosure volume and may require larger enclosures.
UNDER VOLTAGE RELAY:
064686 [0869] - 115/120V, Single Phase
064687 [0871] - 230V, Single Phase
079847 [0870] - 200V, Single Phase
This relay is connected to the primary service to detect under-voltage. This relay will automatically start and stop the pump
motor under this condition.
PARTS LIST:
064686 - Diversifi ed Elec. UOA-120-ALA
064687 - Diversifi ed Elec. UOA-230-ALA
079847 - Diversifi ed Elec. UOA-208-ALA
USD Fuse Block #11425
Buss Fuse 1 amp #KTK
IDEC relay #RH2BUAC120V
IDEC base #SH2B-05
MASTER CIRCUIT BREAKER - PANEL MOUNTED OPTION (No Operator)
Circuit Breakers count as one (1) PANEL MOUNTED option, when added to control.
MASTER CIRCUIT BREAKER:
075605 [0877] - 115/230V, 1 Phase, 70 Amp max.
075606 [2608] - 200/230V, 3 Phase, 100 Amp max.
075607 [2609] - 460V, 3 Phase, 100 Amp max.
The master breaker is a single point line connection and line disconnect for the duplex controls. The breaker is sized
to handle the two pump motor circuit breakers and any external heating and lighting load the panel may be asked to deliver.
PARTS LIST:
075605 - G.E. #THQC2100WL
075606 - G.E. #THQC3200WL
075607 - G.E. #TED134000WL
File: W64686.Dwg
File: W75606.DwgFile: W75605.Dwg
16
CONTROL CIRCUIT BREAKERPANEL MOUNTED OPTION (No Operator)
Circuit Breakers count as one (1) PANEL MOUNTED option, when added to control. No External Operator.
CIRCUIT BREAKER ON PRIMARY CONTROL:
082140 [2607] - 230 Volt,3.5KVA max, 2 Pole
082141 [ ] - 460 Volt, 7KVA max, 2 Pole
Circuit breaker on the primary of the control transformer.
The two pole breaker isolates the control circuit from the pump
breakers. 2 Pole Circuit Breaker size varies according to size of
transformer.
FUSED DISCONNECTS WITH DOOR MOUNTED OPERATORS: Options replacing existing circuit breakers require no additional enclosure space. Option chosen to be Master Fused
Disconnect adds one option space to the enclosure.
FUSED DISCONNECT:
079029 - 115/230V, 1 Phase 250 volt.
079029 - 200/230V, 3 Phase 250 volt.079030 - 460V, 3 Phase 600 volt.
A fused disconnect is to replace the motor circuit breaker which
is sized for motor load and voltage with rotary disconnect handle.
PARTS LIST:
079029 - G.E. #THMR3121
079030 - G.E. # THMR3161
File: W82140.Dwg
File: W79030.DwgFile: W79029.Dwg
17
FUSED DISCONNECTS WITH DOOR MOUNTED OPERATORS:Options replacing existing circuit breakers require no additional enclosure space. Option chosen to be Master Fused
Disconnect adds one option space to the enclosure.
075626 - DOOR INTERLOCK - THROUGH OUTER DOOR FOR FUSED DISCONNECT:
Mounted through the outer door for operation of panel mounted fused disconnect. Mechanical interlock prevents unauthorized
opening of enclosure when handle is “ON”. Also locking hasp accommodates up to three padlocks. One (1) required for each
disconnect.
075625 - DOOR INTERLOCK - THROUGH INNER DOOR FOR FUSED DISCONNECT:
Mounted through the inner door for operation of panel mounted fused disconnect. Mechanical interlock prevents unauthorized
opening of enclosure when handle is “ON”. Also locking hasp accommodates up to three padlocks. One required for each
disconnect.
File: P75626
File: P75627
18
CIRCUITE BREAKER - DOOR INTERLOCKS:
NEMA 1 option, maybe self standing or used with sub door option.
075628 - DOOR INTERLOCK - THROUGH OUTER DOOR FOR CIRCUIT BREAKERS:
Mounted through the outer door for operation of panel mounted circuit breaker. Mechanical interlock prevents unauthorized
opening of enclosure when handle is “ON”. Also locking hasp accommodates up to three padlocks. One (1) required for
each breaker.
075627 - DOOR INTERLOCK - THROUGH INNER DOOR FOR CIRCUIT BREAKER:
Mounted through the inner door for operation of panel mounted circuit breaker. Mechanical interlock prevents unauthorized
opening of enclosure when handle is “ON”. Also locking hasp accommodates up to three padlocks. One required for each
breaker.
File: P75626
File: P75627
19
CONTROL CIRCUIT POWER OPTIONS:
079841 [2604] - 24 VOLT CONTROL CIRCUIT w/Control Equipment @ 24 VAC.
Cover 24 volt A.C. control voltage with all control equipment at 24 volts A.C.
082137 [2606] - 24 VOLT CONTROL FOR 115 VOLT: For 065400 & 065600 Control Panels ONLY.
This option will allow you to operate the wet well fl oat switches and other panel controls at 24 volts A.C. with the addition of a
24 volt A.C. control transformer to 065400 and 065600, 1/2 HP, 115 volt, Single phase control panels. (Duplex Shown)
PARTS LIST:
Simplex - Micron Transformer #C075LP7
Littelfuse Fuse 3AG 2 amp
Duplex - Micron Transformer #C150LP7
Littelfuse Fuse 3AG 4 amp
079842 [2605] - 24 VOLT CONTROL CIRCUIT w/Control Equipment @ 115 Volt AC:
Covers 24 volt A.C. control voltage with control equipment at 115 volts A.C. which requires an extra transformer. This option
has a 100 VA transformer 115V to 24 V AC. This is to control fl oats only at 24 Volts A.C.EXAMPLES of 115 Volt Equipment:
Panel Heater, Convience Outlets, Ground Fault, Dim Glow Alarm, 24 Hr Timer and 7 Day Timer.
File: W79841.Dwg
File: W82137.Dwg
File: W79842.Dwg
20
ENCLOSURE RELATED OPTIONS:
DEAD FRONT DOOR WITH INNER DOOR:
066361 [0880] - Simplex
066362 [0881] - Duplex
The inner door is a hinged aluminum sub-door which is mounted beneath the enclosure’s weather tight door. The circuit
breaker operating handles, hand-off-auto selector switches and pump run lights and optional alarm silence switch
extend through this sub-door.
File: PGSPANEL
File: PGDPANEL
Inner Door
SIMPLEX
Sub Panel NOT USED
with inner door option
DUPLEX
Inner Door
Sub Panel NOT USED
with inner door option
21
ENCLOSURE RELATED OPTIONS:064678 [0858] - PANEL HEATER:
Panel mounted heater 100 watts with thermostat and over-temperature control.
PARTS LIST:
Chromalox heater #SCB100.
Thermodisc Thermostat #36T26
Thermodisc Overtemp #36T21
064690 [2635] - SERVICE LIGHT:
This option consists of a light socket controlled by a door switch, providing interior panel illumination during service work. Due
to the fact that the power for this light comes from the control circuit, it is necessary for the circuit breaker to be turned on after
the door is opened.
PARTS LIST:
Micro door switch #MC2711
Paulding ceramic base #50714
G.E. Light Bulb 25 watt.
File: W64678.Dwg
File: W64690.Dwg
22
MANUAL GENERATOR TRANSFER SWITCH, PANEL MOUNTED: 075641 [0924] - 60 amp, 460V, 3 Phase.
075642 [ ] - 100 amp, 460V, 3 Phase.
075643 [ ] - 200 amp, 460V, 3 Phase.
This transfer switch is built into the control panel using two circuit breakers and a mechanical walking beam interlock which
keeps the two circuit breakers from being turned on together. The incoming power line is wired to one breaker and the
generator power receptacle is wired to the other breaker. With loss of the primary power line, the operator opens the panel
door and turns the line circuit breaker off and the generator circuit breaker on. The generator can then be connected to the
receptacle and the station power.
NOTE: This option adds a minimum of 18” to the control panel height. Must use an oversize enclosure.
The following parts will be used unless otherwise specifi ed.
PARTS LIST:
075641:
Hubbell Generator Receptacle 60 amp, #26410
Hubbell Generator Plug #26419
G.E. Circuit Breaker #TED13400WL
G.E. Walking Beam Interlock
075642:
Hubbell Generator Receptacle 100 amp, #4100R7W
Hubbell Generator Plug #4100P7W
G.E. Circuit Breaker #TED13400WL
G.E. Walking Beam Interlock
075643:
Crouse-Hinds Generator Receptacle 200 amp, #AR2031
Crouse-Hinds Generator Plug AR20357
G.E. Circuit Breaker #TED13400WL
G.E. Walking Beam Interlock
File: W75641.Dwg
NOTE: Suggest a remote MANUAL TRANSFER
SWITCH be supplied as part of the generator
package, by whomever supplies the generator.
23
NEMA 3R ENCLOSURES: Standard enclosures will accept up to 4 Panel Mounted options.
For 5 to 8 Panel Mounted options, use enclosures marked as Oversize “A”.
For 9 to 11 Panel Mounted options, use Oversize “B” enclosures.
For more than 12 Panel Mounted options, call for special size.
The NEMA 3R enclosure is formed of 16 or 14 gauge, G-90 galvanized steel, with all surfaces phosphatized, then fi nished
inside and out with ANSI 61 gray polyester powder fi nish. A full width drip shield is formed into the top cap to prevent standing
water from dripping into the interior when the door is opened. This drip shield and the formed edges of the enclosure provide
a seating surface for the full door gasket. The door is equipped with two galvanized hinges with stainless steel hing pins. Two
padlockable draw-pull latches will hold the door closed. Weld nuts support the removable steel componet mounting panel. The
removable panel is to be white enamel and will be drilled and tapped for component mounting.The enclosure shall have
external mounting tabs for wall mounting. The enclosure is rated NEMA 3R RAINTIGHT and is suited for outdoor mounting.
064691 [2408] - NEMA 3R Enclosure for Remote Alarms
075615 [2614] - NEMA 3R Enclosure, Oversize Simplex “A” - Steel, Gray
[2616] - NEMA 3R Enclosure, Oversize Simplex “B” - Steel, Gray
[2612] - NEMA 3R Enclosure, Replacement for Simplex Std. - Steel, Gray
075616 [2615] - NEMA 3R Enclosure, Oversize Duplex “A” - Steel, Gray
[2617] - NEMA 3R Enclosure, Oversize Duplex “B” - Steel, Gray
[2613] - NEMA 3R Enclosure, Replacement for Duplex Std. - Steel, Gray
NEMA 4 ENCLOSURES: Standard enclosures will accept up to 4 Panel Mounted options.
For 5 to 8 Panel Mounted options, use enclosures marked as Oversize “A”.
For 9 to 11 Panel Mounted options, use Oversize “B” enclosures.
For more than 12 Panel Mounted options, call for special size.
064682 [0882] - NEMA 4 Enclosure, Simplex - Steel
075608 [0883] - NEMA 4 Enclosure, Duplex - Steel
075617 [2622] - NEMA 4 Enclosure, Oversize Simplex “A” - Steel, Gray
[2624] - NEMA 4 Enclosure, Oversize Simplex “B” - Steel, Gray
075618 [2623] - NEMA 4 Enclosure, Oversize Duplex “A” - Steel, Gray
[2625] - NEMA 4 Enclosure, Oversize Duplex “B” - Steel, Gray
075609 [0884] - NEMA 4X Enclosure, Simplex - Fiberglass
075610 [0885] - NEMA 4X Enclosure, Duplex- Fiberglass
075619 [2628] - NEMA 4X, 3, 12 Enclosure, Oversize Simplex “A” - Fiberglass
[2630] - NEMA 4X, 3, 12 Enclosure, Oversize Simplex “B” - Fiberglass
074620 [2629] - NEMA 4X, 3, 12 Enclosure, Oversize Duplex “A” - Fiberglass
[2631] - NEMA 4X, 3, 12 Enclosure, Oversize Duplex “B” - Fiberglass
075611 [0886] - NEMA 4X Enclosure, Simplex - Stainless Steel
075612 [0887] - NEMA 4X Enclosure, Duplex - Stainless Steel
075621 [2673] - NEMA 4X Enclosure, Oversize Simplex “A” - Stailess Steel
[2641] - NEMA 4X Enclosure, Oversize Simplex “B” - Stailess Steel
075622 [2642] - NEMA 4X Enclosure, Oversize Duplex “A” - Stainless Steel
[2643] - NEMA 4X Enclosure, Oversize Duplex “B” - Stailess Steel
075613 [0888] - NEMA 12 Enclosure, Simplex - Steel
075614 [0889] - NEMA 12 Enclosure, Duplex - Steel
075623 [2618] - NEMA 12/13 Enclosure, Oversize Simplex “A” - Steel
[2620] - NEMA 12/13 Enclosure, Oversize Simplex “B” - Steel
075624 [2619] - NEMA 12/13 Enclosure, Oversize Duplex “A” - Steel
[2621] - NEMA 12/13 Enclosure, Oversize Duplex “B” - Steel
24
NEMA TYPE 1 - Enclosures are intended for indoor use
primarily to provide a degree of protection against contact
with the enclosed equipment or locations where unusual
service conditions do not exist. The enclosure shall meet the
rod entry and rust resistance design tests.
NEMA TYPE 3 - Enclosures are intended for outdoor use
primarily to provide a degree of protection against windblown
dust, rain and sleet; undamaged by the formation of ice on
the enclosure. They shall meet rain, external icing, dust and
rust resistance design tests. They are not intended to provide
protection against conditions such as internal condensation
or internal icing.
NEMA TYPE 3R - Enclosures are intended for outdoor
use primarily to provide a degree of protection against
falling rain; and to be undamaged by the formation of ice
on the enclosure. They shall meet rod entry, rain, external
icing and rust resistance test. They are not intended to
provide protection against conditions such as dust, internal
condensation, or internal icing.
NEMA TYPE 4 - Enclosures are intended for indoor or
outdoor use primarily to provide a degree of protection
against windblown dust and rain, splashing water, and
hose-directed water; undamaged by the formation of ice on
the enclosure. They shall meet the hosedown, external icing
and rust resistance design tests. They are not intended
to provide protection against conditions such as internal
condensation, or internal icing.
NEMA TYPE 4X - Enclosures are intended for indoor
or outdoor use primarily to provide a degree of protection
against corrosion, windblown dust and rain, splashing water,
and hose-directed water; undamaged by the formation of ice
on the enclosure. They shall meet the hosedown, external
icing and rust resistance design tests. They are not intended
to provide protection against conditions such as internal
condensation, or internal icing.
NEMA TYPE 6 - Enclosures are intended for indoors or
outdoors use primarily to provide a degree of protection
against the entry of water during occasional temporary
submersion at a limited depth. NEMA 6P Enclosures are,
same as above, except, protection against the entry of water
during prolonged submersion at a limited depth.
NEMA TYPE 7 - Enclosures are for indoor use in locations
classifi ed as Class I, Groups A,B,C or D, as defi ned in the
National Electrical Code... [Explosive gas-air mixtures.]
NEMA TYPE 9 - Enclosures are intended for indoor use in
locations classifi ed as Class II, Group E or G, as defi ned
in the National Electrical Code... [Explosive gas-air mixtures.]
NEMA TYPE 12 - Enclosures are intended for indoor use
primarily to provide a degree of protection against dust, falling
dirt, and dripping noncorrosive liquids.
NEMA TYPE 13 - Enclosures are intended for indoor use
primarily to provide a degree of protection against dust,
spraying of water, oil, and noncorrosive coolant.
The preceding descriptions are not intended to be complete
representations of National Electrical Manufactures
Association standards for enclosures. Data courtesy of
National Electrical Manufactures Association [NEMA]
from Standards Publication 250-1985, Enclosures for
Electrical Equipment (1000 Volts maximum), Copyright 1985
by NEMA or equivalent.
SOURCES of STANDARDS:
NEMA National Electrical Manufactures Association
2101 L Street Northwest
Washington, D.C. 20037
EEMAC Electrical/Electronic Mfgs Assoc. of Canada
10 Carlson Court
Suite 500
Rexdale (Toronto), Ontario
Canada M9W 6L2
UNDERWRITERS LABORATORIES INC.
333 Pfi ngsten Road
Northbrook, IL 60062
UL 508 Industrial Control Equipment
JOINT INDUSTRY COUNCIL
7901 Westpark Drive
McLean, VA. 22101
CANADIAN STANDARDS ASSOCIATION
178 Rexdale Blvd.
Rexdale (Toronto), Ontario,
Canada M9W IR3
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
1430 Broadway
New York, NY 10018
ANSI Z55.1-1967 Gray Finishes for Industrial Apparatus and
Equipment.
ENCLOSURE TYPES
25
Furnas Type “K” Heater Element Table
PART NO FURNAS NO.
032215 K-21
032216 K-22
032217 K-23
032218 K-24
032219 K-26
032220 K-27
032221 K-28
032222 K-29
032223 K-31
032224 K-32
032225 K-33
032226 K-34
032227 K-36
032228 K-37
032229 K-39
032230 K-41
032231 K-42
032232 K-43
032233 K-49
032234 K-50
032235 K-52
032236 K-53
032237 K-54
032238 K-55
032239 K-56
032240 K-57
032241 K-58
032242 K-60
032243 K-61
032244 K-62
032245 K-63
032246 K-64
032247 K-67
032248 K-68
032249 K-69
032250 K-70
032251 K-72
032252 K-73
032253 K-74
032254 K-75
032255 K-76
032256 K-77
032257 K-78
032258 K-80
032259 K-85
032260 K-86
26
030000036189 ..........................14
050000058582 ..........................14
060000063735 ..........................Not Shown
063736 ..........................Not Shown
063737 ..........................Not Shown
064403 ..........................7
064672 ..........................1
064673 ..........................1
064674 ..........................2
064675 ..........................4
064676 ..........................6
064677 ..........................6
064678 ..........................21
064679 ..........................12
064680 ..........................13
064681 ..........................5
064682 ..........................23
064683 ..........................13
064684 ..........................13
064685 ..........................13
064686 ..........................15
064687 ..........................15
064688 ..........................14
064689 ..........................14
064690 ..........................21
064691 ..........................23
066361 ..........................20
066362 ..........................20
070000073604 ..........................2
075601 ..........................3 & 4
075602 ..........................12
075603 ..........................12
075605 ..........................15
075606 ..........................15
075607 ..........................15
075608 ..........................23
075609 ..........................23
075610 ..........................23
075611 ...........................23
075612 ..........................23
075613 ..........................23
075614 ..........................23
075615 ..........................23
075616 ..........................23
075617 ..........................23
075618 ..........................23
075619 ..........................23
075620 ..........................23
075621 ..........................23
075622 ..........................23
075623 ..........................23
075624 ..........................23
075625 ..........................17
075626 ..........................17
075627 ..........................18
075628 ..........................18
075629 ..........................7
075630 ..........................8
075631 ..........................9
075632 ..........................9
075633 ..........................10
075634 ..........................10
075635 ..........................9
075636 ..........................8
075637 ..........................8
075638 ..........................8
075639 ..........................11
075640 ..........................11
075641 ..........................22
075642 ..........................22
075643 ..........................22
079027 ..........................12
079029 ..........................16
079030 ..........................16
079841 ..........................19
079842 ..........................19
079847 ..........................15
080000082137 ..........................19
082140 ..........................16
082141 ..........................16
085325 ..........................6
090000093504 ..........................10
INDEX