corrientes en los momentos de conexión

Upload: mansilla316

Post on 10-Apr-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/8/2019 Corrientes en los momentos de conexin

    1/12

    http://www.epcos.com

    Damping of Inrush Currentin Low-Voltage PFC EquipmentLow-Voltage PFC

    Application Note 2001

  • 8/8/2019 Corrientes en los momentos de conexin

    2/122 EPCOS AG

    Power Quality

    Contents

    General 3

    The risks of high inrush current 4

    Single capacitor connection, inrush current calculation 6

    Parallel capacitor connection, inrush current calculation 7

    Various solutions for limiting inrush current serial aircoils 7

    Detuning reactors, connection cable selection 8

    Capacitor contactors with damping resistorsFunctionality / comparison 9

    Comparison 10

    Capacitor bank switching under various conditions 11

  • 8/8/2019 Corrientes en los momentos de conexin

    3/123EPCOS AG

    Damping of Inrush Currentin Low-Voltage PFC EquipmentGeneral

    The market trend to reduce lossesin modern low-voltage power-factor-correction capacitors (LV-PFCs)and the requirement for highoutput density result in reducedohmic resistance in PFC capacitors.Especially the switching of capa-citors in parallel to others of thebank, already energized, causesextremely high inrush current,up to 200 times the rated current,and limited only by the ohmicresistance of the capacitor itself.According to the formula ( Eq1),such a capacitors AC resistance isvery low and thus contributes tohigh inrush current.

    LV-PFC capacitor bank

    Inrush current (pulse) is a factor of:

    a Remaining capacitor voltagedue to fast switching in auto-matic capacitor banks

    a Shortcircuit power of supplytransformer

    a Output of capacitor switchedin parallel to others alreadyenergized

    aFault level of supply network

    a Output of capacitors alreadyenergized

    a Ohmic resistance of capacitoritself and distribution switchgear, connection cables or con-ductors

    KLK1709-W

    25kVAr

    25kVAr

    25kVAr

    25kVAr

    25kVAr

    25kVAr

    12.5

    kVAr

    25kVAr

    M3~

    187,5 kVAr

    Automatic capacitor bankwith 6 capacitors in parallel

    High inrush current for grid,high balancing currents for capacitors

    xc =1

    2**f*c

    Eq1:

    Switching operation: f xc0 200 * Ir

  • 8/8/2019 Corrientes en los momentos de conexin

    4/124 EPCOS AG

    Inrush Current by ConnectingCapacitor in Parallel (Energization)

    The risks of high inrush current

    Connecting LV-PFC capacitors with-out damping to an AC grid stressesthe capacitor like a shortcircuit.To avoid negative effects and toimprove a capacitors life time, ade-quate damping of inrush current ishighly recommended.

    Influence of high inrush currentand resulting distortion:

    a High stress on the capacitor reduced lifetime

    a Welding or fast wearing out ofthe main contacts of contactors

    a Negative effects on powerquality (eg.voltage transients)

    a Overvoltage: insulation problems

    defects of electronic equipment

    production stop

    a Undervoltage/voltage zerocrossing measurement failure problems with numerical

    control equipment

    production stop due tocomputer failure

    a High cost of maintenance andproduction standstill

    73.2 73.8 74.5 75.1 75.7 76.3 77.0 77.6 t (ms)

    4000

    3000

    2000

    1000

    0

    -1000

    -2000

    -3000

    Current(A)

    Capacitor inrush current

    ONOFF 5th capacitor connected

    Peak current occurrence

    i = 157* IN = 157*21 = 3300 Ai

    i

    Capacitor connection:IN

    =rated current= 21A

  • 8/8/2019 Corrientes en los momentos de conexin

    5/12

    0 10 20 30 40 50 60 70 80 90 100t (ms)

    1500

    1000

    500

    0

    -500

    -1000

    -1500

    Voltage(V)

    1st step on 2nd step on 3rd step on 4th step on 5th step on 6th step on

    1

    1

    High peak voltage (transients) occurrence

    1 12

    2

    > UINS risk of shortcircuit 0 V results in wrong measurementscausing control failures

    1

    2

    5EPCOS AG

    Inrush Measurementof Capacitor Steps

    Switching of power factor correc-tion (PFC) capacitors is not onlyrelated to high currents but alsoto high voltage transients (ref.capacitor switching-on steps 16),causing degradation ofpowerquality, if the negative influenceis not prevented by damping.

    Capacitor sample,contact surface damagedby high inrush currents

    High inrush current occurrencesdue to insufficient dampingcaused high electromechanicalforces within the capacitor. Espe-cially the contact area betweenelectrodes (windings) and themetal-spray layer was extremelystressed by high current forces.

    The example shows that a fractionof metal-spray layer separatedfrom the windings. Even the MKKcapacitor with excellent pulsecurrent capability and enhancedcontactability due to wavy cut andheavy edge design of the filmshows that extensive power cancause failures.

    Voltage at 0.69 kV - busbar

    PFC capacitor cascade connection:High voltage transients occurrence due to no damping

    Example

    Metal-spray layerseparated from thecapacitor windings

  • 8/8/2019 Corrientes en los momentos de conexin

    6/126 EPCOS AG

    Inrush Current Calculation

    KLK1706-7

    Grid

    L 3

    L

    L 2

    1UN

    Connecting a single capacitor

    Circuit and formula

    Terms

    Result

    Peak inrush current i A Transformer shortcircuit power Sk kVA Rated capacitor output Q kVAr Rated capacitor current IN ARated voltage UN V

    Ohmic resistance = X C

    3 * UN2

    * (1/Q1+ 1/Q2)

    Grid impedance = XI o*L () including contactor fuse busbars

    Calculation example

    Given parameters:

    Grid connection of a single 50 kVArcapacitor, no other capacitor connected:a Grid 400 V/50 Hza Transformer shortcircuit voltage: 5%a Transformer output: 1600 kVAa Capacitor Q = 50 kVAr; IN = 72 A

    i = = 2575 A

    The inrush current is approximately35 times the rated current.

    Typical inrush currents are

    1040 times the rated current forsingle capacitors during connection.

    1600 kVA

    2* 0.05 *72 A50 kVAr

    i=2*Sk

    *INQ

    ^

    Eq 2

    ^

    ^

  • 8/8/2019 Corrientes en los momentos de conexin

    7/12

    Connection of a 50 kVAr capacitor, other300 kVAr capacitors are already connected:a Grid 400 V/50 Hza Transformer shortcircuit voltage: 6%a Transformer output: 630 kVAra Q1 = 50 kVAra Q2 = 300 kVAra IN = 72 A ; VN = 400 V ; f = 50 Hz

    aXC = 3 * U2N * ( + ) = 11.2

    a L /phase = 0.4 H (empirical)aXL= o * L = 2 * * f * L = 0.125 m

    i = = 15118.6 A

    The inrush current is approximately210 times the rated current.

    2*400 V

    11.2 *0.125*103

    1Q2

    1Q1

    7EPCOS AG

    Various Solutionsfor Limiting Inrush Current

    KLK1707-F

    3C

    1C

    2C

    C1

    1Q Q2

    C2 3

    C

    Capacitor

    Contactor

    Grid

    L 3

    L

    L 2

    1UN

    KLK1708-N

    nL

    Kn K

    L 2

    2

    1L

    K1

    2L

    L 1

    L 3 Grid

    Qn Q2 Q1

    UN

    Parallel connecting of capacitor: Serial air coils

    This example shows that cable turns in seriesbetween contactor and capacitor reduce theinrush current. Contactor suppliers recommendinductivity of 6 8 H for damping inrush current.To achieve this inductivity, the following table pro-vides tips for selecting the required turns, diame-ters and cross sections.

    Given parameters: Given parameters:

    Parallel connection of a 50 kVAr capacitorwith cable turns (serial aircoils) for damping,other 300 kVAr capacitors are already connect-ed, 400 V/50 Hz, shortcircuit power 10.5 MVA,rated capacitor current 72 A: damping withapprox. 6 H with turns.aXc = 11.2aXL1 = 2 * * f * L = 2 * * 50 * 6 H = 1.88 m

    aXL2 = 2 * *f *L =0.125 maXL total = 0.125 + 1.88 = 2 ma L /phase = 0.4 H (empirical value)1)

    i = = 3780 A

    The inrush current is approximately50 times the rated current. This means onlyabout a quarter compared to a capacitorwithout damping (turns).

    2*400 V

    11.2 *2 *103

    Typical inrush currents are

    100250 times rated current forsingle capacitors in parallel connectionto other capacitors in operation.

    This example shows that some cable

    turns in series with the capacitorcontribute to reducing inrush current(to 50 times rated current).This improves capacitor life cycle.

    i=2*UN

    Xc*XLi=

    2*UN

    Xc*(XL1+XL2)^ ^

    Eq 3 Eq 4

    ^^

    1) For switch gear and connected cables

  • 8/8/2019 Corrientes en los momentos de conexin

    8/128 EPCOS AG

    Damping as described is a possiblesimple solution, but this methoddeals with two contradicting effects:

    a Longer (or additional) cablescause electrical losses higherlosses cause higher inherenttemperature within the capacitor.

    a On the other hand, cable turnsreduce the inrush current andincrease the life cycle of capaci-tors and contactors.

    Plus, you must make sure that thecapacitor works below its maximumoperating temperature.

    Detuning reactors(series anti-harmonic reactors)

    In detuned capacitor banks theinductivity of filter circuit reactorsprovides an excellent dampingeffect for limiting inrush current.The following diagrams showthe connection of a detuned andnon-detuned (reactor and capac-itor) system.

    The peak current of a conventionalcapacitor is higher than 4000 A.The peak current of detuned capac-itors is only approx. 500 A. Thepurpose of filter circuit reactors isof course not the damping ofinrush current, but this exampleshows that in the case of detunedcapacitors no additional damp-ing measures are required.

    Examples for detunedcapacitor banks (ref. page 2)

    Selection table for connection cables

    Detuned capacitorwith series reactors

    Various Solutions forLimiting Inrush Current

    Capacitor Turns Approx. Cablerating diameter cross-section

    5 kVAr 10 100 mm 2.5 mm2

    10 kVAr 10 100 mm 4 mm2

    12.5 kVAr 10 100 mm 4 mm2

    16.7 kVAr 7 100 mm 6 mm2

    25 kVAr 7 100 mm 10 mm2

    33 kVAr 7 100 mm 25 mm2

    50 kVAr 7 100 mm 35 mm2

    Fig. 1: 25 kVAr (21A /690 V)vertical: 2000 A /divhorizontal: 0.625ms /div

    Fig. 2: 25 kVAr (21A / 690 V)vertical: 200 A / divhorizontal: 10 ms / div

    Because of the high inductance inthe circuit, the breaking qualityof the contactor is important toavoid restriking during switch-off.Especially large contactors (over-sized motor contactors) may betoo slow and are therefore critical.

    > 4000 A

    = 190 * IN

    i = 500 A

    = 24 * IN

    This table should help to find the appropriate cable and required turns.

    Our PFC-CDROM (available upon request) contains calculation softwarewhich enhances precise calculation of the application (capacitors andswitch gear).

    Conventional capacitorwithout damping

  • 8/8/2019 Corrientes en los momentos de conexin

    9/129EPCOS AG

    Capacitor contactors with damping resistors

    How does it work?

    The series damping resistors areswitched by socalled precontactsor auxiliary contacts. The precon-tact closes before main contactsand preloads the capacitor.

    a Reduced voltage differences.

    a The peak current is limited.

    a The resistor is temporarily in thecircuit and has no thermal losses.

    a The total resistance of the resistorwires is mainly ohmic in nature,its inductance can be neglected.The coiling up of the dampingresistors is only a matter of con-struction.

    a During operation (main contactsare closed) the resistor wires aredisconnected or shorted out, anddo not cause any permanentlosses at all. Due to the very shortoperation time (a few milliseconds

    only) during switch-on of thecontactor, a long life cycle of thedamping resistors is ensured.

    Auxiliary switchedcontact with serialresistor (precontacts)

    Capacitor contactor(main contacts)

    Capacitor

    Main contacts

    Precontacts2...10 ms

    on

    Grid/Mains

    onoff

    onoff

    Functional diagram

    i=C*dVdt

    ^

    Note:Due to pre-loading via aux.contacts the capacitorsvoltage difference will bereduced. Consequentlyalso the capacitor currentaccording to the formula:

    Damping

    resistor

    Pre-switching

    aux. contacts

    Eq 5

  • 8/8/2019 Corrientes en los momentos de conexin

    10/1210 EPCOS AG

    With

    damping resistors

    Without

    damping resistors

    The following two diagrams showthe difference between a capa-citors inrush current without andwith damping series resistorswhen a capacitor is switched inparallel to an already energizedcapacitor bank/unit:

    Comparison

    Facts and conclusion

    a Rated current of a 12.5 kVar/400 V capacitor is 18 A

    a Peak inrush current without series resistors is 1200 A

    a Peak inrush current with series resistors is only 260 A

    a 1200 A is equal to 66 times the rated current

    a Inrush current with series resistors is only one fifthof that of the standard contactor

    a Substantial difference also in terms of power(integrated area)

    a Superior switching behavior of contactor with seriesresistors compared with a standard contactor, results inextended life cycle of contactors as well as of capacitors

    a Improved power quality ensures trouble-free and safeoperation of the PFC system and application

    Fig.3 : 12.5 kVAr (18 A/400 V)

    vertical: 250 A/divhorizontal: 0.5 ms/div

    Fig.4 : 12.5 kVAr (18 A/400 V)

    vertical: 250 A/divhorizontal: 0.5 ms/div

    i = 1200 A

    i = 260 A

  • 8/8/2019 Corrientes en los momentos de conexin

    11/1211EPCOS AG

    Without precontacts

    (detuned capacitor)

    With precontacts

    (detuned capacitor)

    Without precontacts

    (non-detuned capacitor)

    ComparisonCapacitor bank switching under various conditions

    Facts and conclusion

    The peak current during switching without using precontacts(Fig.5) exceeds 4000 A

    If capacitors are detuned (Fig. 6) the peak is only 500 A

    The latter case shows the influence of inductivity andprecontacts of a capacitor contactor, the peak current

    (Fig.7) is reduced to approx. 200 A

    Fig. 5: 25 kVAr (21A /690 V)

    vertical: 2000 A/divhorizontal: 0.625 ms/div

    Fig. 6: 25 kVAr (21 A/690 V)

    vertical: 200 A/divhorizontal: 10 ms/div

    Fig. 7: 25 kVAr (21 A/690 V)

    vertical: 200 A/divhorizontal: 10 ms/div

    i > 4000 A i = 500 A

    i < 200 A

  • 8/8/2019 Corrientes en los momentos de conexin

    12/12

    Herausgegeben von EPCOS AG, Marketing Kommunikation

    Postfach 801709, 81617 Mnchen, DEUTSCHLAND

    (089) 636-09, FAX (089) 636-2 2689

    EPCOS AG 2000. Alle Rechte vorbehalten. Vervielfltigung, Verffentlichung, Verbreitung und Verwertung dieser

    Broschre und ihres Inhalts ohne ausdrckliche Genehmigung der EPCOS AG nicht gestattet.

    Mit den Angaben in dieser Broschre werden die Bauelemente spezifiziert, keine Eigen-schaften zugesichert. Bestellungen

    unterliegen den vom ZVEI empfohlenen Allgemeinen Lieferbedingungen fr Erzeugnisse und Leistungen der

    Elektroindustrie, soweit nichts anderes vereinbart wird. Diese Broschre ersetzt die vorige Ausgabe. Fragen ber Technik,

    Preise und Liefermglichkeiten richten Sie bitte an den Ihnen nchstgelegenen Vertrieb der EPCOS AG oder an unsere

    Vertriebsgesellschaften im Ausland. Bauelemente knnen aufgrund technischer Erfordernisse Gefahrstoffe enthalten.

    Ausknfte darber bitten wir unter Angabe des betreffenden Typs ebenfalls ber die zustndige Vertriebsgesellschaft

    einzuholen.

    Published by EPCOS AG, Marketing Communications

    P.O.B. 801709, 81617 Munich, GERMANY

    ++49 89 636-09, FAX (089) 636-2 2689

    EPCOS AG 2000. All Rights Reserved. Reproduction, publication and dissemination of this brochure and the information

    contained therein without EPCOS prior express consent is prohibited.

    The information contained in this brochure describes the type of component and shall not be considered as guaranteed

    characteristics. Purchase orders are subject to the General Conditions for the Supply of Products and Services of the

    Electrical and Electronics Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers

    Association), unless otherwise agreed. This brochure replaces the previous edition. For questions on technology, prices and

    delivery please contact the Sales Offices of EPCOS AG or the international Representatives. Due to technical requirementscomponents may contain dangerous substances. For information on the type in question please also contact one of our

    Sales Offices.

    EPCOS AG