countries supported by the solaredge inverters€¦ · countries supported by the solaredge...
TRANSCRIPT
Last update: Nov. 2016
1
Countries Supported by the SolarEdge Inverters
The SolarEdge inverters can be used in many different countries. This document details countries where SolarEdge approves
installation of its inverters. Installation should always be done in compliance with local regulations, and in case of a conflict
between local regulations and this document, local regulations apply.
Summary
The SolarEdge inverters may be installed in the following countries. Unless stated otherwise, the approval refers to low voltage
installations. For medium voltage installations, please contact SolarEdge support. Please refer to the country details below for
more information, as in some countries not all grids are supported or not all inverter models are supported.
In supported countries, connection of supported inverters to non-supported grids is permitted through a transformer, if the
secondary connection (transformer connection to the inverter) is identical to a supported grid.
NOTE
Transformer procurement, installation, maintenance and support are the responsibility of the installer. Damage to the inverter due to
incorrect transformer installation or use of a transformer that is incompatible with the SolarEdge system will render the SolarEdge
warranty invalid.
NOTE
Prior to purchasing a StorEdge system verify battery availablity and service in the country. Availability of SolarEdge StorEdge products
does not guarantee battery availabllity.
A country listed in bold indicates that StorEdge inverters with backup are approved for installation in that country.
Aruba
Australia
Austria
Barbados
Belarus
Belgium
Bermuda
Botswana
Bulgaria
Canada
Cape Verde
China
Costa Rica
Croatia
Curacao
Cyprus
Czech Republic
Denmark
Dubai
El Salvador
Estonia
Finland
France
Germany
Ghana
Greece
Grenada
Guatemala
Hungary
India
Indonesia
Ireland
Israel
Italy
Jamaica
Japan
Jordan
Kenya
Kuwait
Latvia
Lithuania
Luxembourg
Malaysia
Malta
Mauritius
Mexico
Namibia
The Netherlands
New Zealand
Norway
Panama
Philippines
Poland
Portugal
Romania
Seychelles
Singapore
Slovakia
Slovenia
South Africa
Spain
Sri Lanka
St. Lucia
St. Vincent
Sweden
Switzerland
Tahiti
Taiwan
Thailand
Turkey
Ukraine
United Kingdom
USA
Zimbabwe
For installation in countries or with grids not detailed in this document, contact SolarEdge support: [email protected]
2
Detailed Information per Country
The table below details for each of the above countries:
1. Supported inverters: which SolarEdge inverters may be used in the country
2. Inverter country setting: to what country setting the inverter should be configured in order to comply with the local
grid requirements. Some countries have a submenu that should be used; sub-entries are indicated with the following
symbol: ->
3. Frequency: the nominal inverter AC frequency for the corresponding country setting
4. Comments: additional information about the inverter and grid support
3
Supported inverters Inverter country setting Frequency Comments
Aruba
SE3000A-US –
SE11400A-US
Caribbean -> Aruba 60Hz Available from CPU v2.07xx
Can be connected to the following grid: 127/220V (L-L
connection)
SE3800A-US limited to 3.5kW AC
SE6000A-US limited to 5.5kW AC
SE11400A-US approved only for installations with no
LVRT (low voltage ride through) requirement; if required
– contact SolarEdge support
SE9kUS Caribbean -> Aruba 60Hz Available from CPU v2.07xx
Can be connected to the following grid: 127/220V
Australia
SE2200 - SE6000,
SE5k - SE27.6k
Australia -> Australia
Australia -> Queensland
Australia -> Victoria
50Hz Use Queensland setting when QLD wider voltage range
is required; available from CPU v2.0496
Victoria setting available from CPU v3.19xx
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Australia -> Australia
Australia -> Queensland
Australia -> Victoria
50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
StorEdge with
backup power:
SE5000-AUS -
SE6000-AUS
Australia -> Australia
Australia -> Queensland
Australia -> Victoria
50Hz Available from CPU v3.18xx
Austria
SE2200 - SE6000,
SE2200H – SE3680H,
SE4k - SE27.6k
Austria 50Hz
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Austria 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Barbados
SE3000A-US -
SE11400A-US
Caribbean -> Barbados
230V No N
50Hz Available from CPU v2.0496
Can be connected to the following grids:
115/230V split phase or 3-wire (L-L connection)
230/400V WYE (L-N connection)
SE9KUS Caribbean -> Barbados
115V
50Hz Available from CPU v2.09xx / v3.12xx
Can be connected to the following grid: 115/200V WYE
4
Supported inverters Inverter country setting Frequency Comments
SE10kUS - SE20kUS Caribbean -> Barbados
230V (No N)
50Hz Supported in inverters shipped from Jan. 10 2014 that
have DSP1 v1.13.321; for other inverters contact
SolarEdge support.
Can be connected to the following grid: 230/400V WYE
SE20kUS limited to 16.5kW AC
Belarus
SE2200 – SE6000,
SE4k - SE27.6k
Europe EN50438 50Hz Available from CPU v3.16xx
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Europe EN50438 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Belgium
SE2200 - SE5000,
SE2200H – SE3680H,
SE4k - SE27.6k
Belgium
50Hz Refer to the following note for more details about grid
compliance:
http://www.solaredge.com/files/pdfs/belgian-grids-
application-note.pdf
StorEdge without
backup power:
SE2200-SE5000,
SE3500 AC Coupled
Inverter
Belgium 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
StorEdge with
backup power:
SE5000-RWS
Belgium 50Hz Available from CPU v3.18xx
Bermuda
SE3000A-US -
SE11400A-US
USA -> Auto
USA -> 240V
USA -> 240V No Neutral
USA -> 208V
USA -> 208V No Neutral
60Hz Refer to the inverter datasheet for full inverter-grid
compatibility:
http://www.solaredge.us/files/pdfs/products/inverters/
se-single-phase-us-inverter-datasheet.pdf
SE9kUS USA -> 208V 60Hz 120/208V WYE grid only
SE10kUS – SE20kUS USA -> 277V 60Hz 277/480V WYE grid only
Botswana
SE2200 - SE6000,
SE2200H – SE3680H,
SE4k - SE27.6k
South Africa 50Hz
Bulgaria
SE2200 - SE6000,
SE2200H – SE3680H,
SE5k - SE27.6k
Bulgaria 50Hz
5
Supported inverters Inverter country setting Frequency Comments
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Bulgaria 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Canada
SE3000A-US-CAN -
SE11400A-US-CAN
USA -> Auto
USA -> 240V
USA -> 240V No Neutral
USA -> 208V
USA -> 208V No Neutral
60Hz Refer to the inverter datasheet for full inverter-grid
compatibility:
http://www.solaredge.us/files/pdfs/products/inverters/
se-single-phase-us-inverter-datasheet.pdf
SE9kUS-CAN,
SE14.4KUS
USA -> 208V 60Hz 120/208V WYE grid only
SE10kUS-CAN,
SE20kUS-CAN,
SE33.3KUS
USA -> 277V 60Hz 277/480V WYE grid only
Cape Verde
SE2200 – SE6000 Contact SolarEdge support 50Hz
SE4k – SE27.6k Cape Verde 50Hz Available from CPU version 3.18xx
China
SE2200 – SE6000,
SE5k - SE17k
China 50Hz All systems must be approved by SolarEdge; contact
SolarEdge Support for details
Costa Rica
SE3000A-US -
SE11400A-US
USA -> Auto
USA -> 240V
USA -> 240V No Neutral
USA -> 208V
USA -> 208V No Neutral
60Hz Refer to the inverter datasheet for full inverter-grid
compatibility:
http://www.solaredge.us/files/pdfs/products/inverters/
se-single-phase-us-inverter-datasheet.pdf
SE9kUS USA -> 208V 60Hz 120/208V WYE grid only
SE10kUS – SE20kUS USA -> 277V 60Hz 277/480V WYE grid only
Croatia
SE2200 - SE5000,
SE4k - SE27.6k
Croatia 50Hz Available from CPU v2.0496
StorEdge without
backup power:
SE2200-SE5000,
SE3500 AC Coupled
Inverter
Croatia 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Curacao
SE2200 – SE5000 Caribbean -> Curacao 50Hz Available from CPU v2.0637
Can be connected to the following grids:
6
Supported inverters Inverter country setting Frequency Comments
127/220V WYE (L-L connection)
110/220V split phase (L-L connection)
220/380V WYE (L-N connection)
SE4k - SE27.6k Caribbean -> Curacao 50Hz Available from CPU v2.0637
Can be connected to the following grid: 220/380V WYE
Systems 100kW and larger must be approved by
SolarEdge; contact SolarEdge Support for details
Cyprus
SE2200 – SE6000,
SE5k - SE27.6k
Cyprus
Cyprus 240V
50Hz
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Cyprus
Cyprus 240V
50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Czech Republic
SE2200 - SE6000,
SE2200H – SE3680H,
SE5k - SE17k
Czech Republic 50Hz
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Czech Republic 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Denmark
SE2200 - SE6000,
SE4k - SE27.6k
Denmark -> Denmark
Denmark -> Denmark
Residen.
Denmark -> Denmark VDE
Denmark -> Denmark VDE
Res.
50Hz Use Residential settings to comply with 16Aac and 6kW
limits of residential systems
Use VDE settings for VDE-AR-N-4105 grid settings;
Available from CPU v2.0496
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Denmark -> Denmark
Denmark -> Denmark
Residen.
Denmark -> Denmark VDE
Denmark -> Denmark VDE
Res.
50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Dubai
SE2200 – SE6000 Dubai 50Hz Available from CPU v3.18xx
SE4k - SE27.6k Dubai 50Hz Available from CPU v3.18xx
El Salvador
SE3000A-US - USA -> Auto 60Hz
7
Supported inverters Inverter country setting Frequency Comments
SE11400A-US USA -> 240V
USA -> 240V No Neutral
Estonia
SE2200 - SE4000-
16A, SE4k-SE27.6k
Portugal 50Hz
StorEdge without
backup power:
SE2200-SE4000-16A,
SE3500 AC Coupled
Inverter
Portugal 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Finland
SE2200 – SE4000-
16A
Finland 50Hz Available from CPU v3.18xx
SE4k – SE27.6k Finland 50Hz Available from CPU v3.18xx
StorEdge without
backup power:
SE2200-SE4000-16A,
SE3500 AC Coupled
Inverter
Finland 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
France
SE2200 - SE6000,
SE2200H – SE3680H,
SE4k - SE27.6k
France 50Hz
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
France 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
StorEdge with
backup power:
SE5000-RWS -
SE6000-RWS
France 50Hz Available from CPU v3.18xx
Germany
SE2200 - SE5000,
SE2200H – SE3680H,
SE4k - SE12.5k
Germany 50Hz
SE15k-SE27.6k Germany -> Germany
Germany -> Germany
MVGC
50Hz These inverters are approved for connection to the
medium voltage grid according to the BDEW standard;
use Germany MVG
SE33.3K Germany -> MVGC 480 50Hz This inverter has a 277/480Vac output voltage and is
designed for connection to the medium voltage grid via
a transformer
StorEdge without Germany 50Hz Requires StorEdge-compatible inverter and installation
8
Supported inverters Inverter country setting Frequency Comments
backup power:
SE2200-SE5000,
SE3500 AC Coupled
Inverter
of StorEdge Interface; refer to application note.
Ghana
SE2200 - SE6000,
SE5k - SE27.6k
Ghana 50Hz Available from CPU v3.18xx
Greece
SE2200 - SE6000,
SE2200H – SE3680H,
SE4k - SE27.6k
Greece -> Greece
Continent
Greece -> Greece Islands
50Hz
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Greece -> Greece
Continent
Greece -> Greece Islands
50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Grenada
SE3000A-US -
SE11400A-US
Grenada 50Hz Available from CPU v3.18xx
Can be connected to the following grid: 230/400V WYE
(L-N connection)
SE9KUS Grenada 50Hz Available from CPU v3.18xx
Can be connected to the following grid: 230/400V WYE
SE10kUS - SE20kUS Grenada 50Hz Available from CPU v3.18xx
Can be connected to the following grid: 230/400V WYE
SE20kUS limited to 16.5kW AC
Guatemala
SE3000A-US –
SE5000A-US
USA -> Auto
USA -> 208V
USA -> 208V No Neutral
60Hz
SE9kUS USA -> 208V 60Hz
Hungary
SE2200 - SE6000,
SE2200H – SE3680H,
SE5k - SE27.6k
Hungary 50Hz Available from CPU v2.09xx / v3.12xx
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Hungary 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
India
SE2200 - SE6000,
SE4k - SE27.6k
India 50Hz
9
Supported inverters Inverter country setting Frequency Comments
SE33.3k India -> India MV 50Hz Available from CPU v3.19xx
This inverter has a 277/480Vac output voltage and is
designed for connection to the medium voltage grid via
a transformer
Indonesia
SE2200 - SE6000,
SE5K-SE17K
Indonesia 50Hz Available from CPU v3.16xx
Ireland
SE2200 - SE6000,
SE2200H – SE3680H,
SE4k - SE27.6k
Ireland 50Hz Available from CPU v2.0496
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Ireland 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Israel
SE2200 - SE6000,
SE4k - SE27.6k
Israel -> Israel
Israel -> Israel -
Commercial
50Hz Commercial setting for systems >50kW available from
CPU v2.07xx
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Israel -> Israel
50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Italy
SE2200 - SE6000,
SE4k - SE12.5k
Italy -> Italy
Italy -> Italy (No SPI)
50Hz
SE15k-SE27.6k Italy -> Italy
Italy -> Italy (No SPI)
50Hz These inverters are approved for connection to the
medium voltage grid according to the CEI 0-16 standard
SE33.3k Italy -> Italy 277V No SPI 50Hz This inverter has a 277/480Vac output voltage and is
designed for connection to the medium voltage grid via
a transformer
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Italy -> Italy
Italy -> Italy (No SPI)
50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
StorEdge with
backup power:
SE5000-RWS -
SE6000-RWS
Italy -> Italy 50Hz Available from CPU v3.18xx
Jamaica
10
Supported inverters Inverter country setting Frequency Comments
SE3000A-US -
SE11400A-US
Caribbean -> Jamaica ->
240V No Neutral
Caribbean -> Jamaica ->
220V No Neutral
50Hz Available from CPU v2.0496
Can be connected to the following grids:
110/220V split phase (L-L connection)
240/415V WYE (L-N connection)
220V delta (L-L connection)
SE10kUS - SE20kUS Caribbean -> Jamaica ->
240V (No N)
50Hz Supported in inverters shipped from Jan. 10 2014 that
have DSP1 v1.13.321; for other inverters contact
SolarEdge support.
Can be connected to the following grid: 240/415V WYE
SE20kUS limited to 17.3kW AC
Japan
SE25K-JP Japan -> Japan 380V 50Hz
Japan -> Japan 380V 60Hz
50/60Hz Available from CPU v3.19xx
SE33.3K-JP Japan -> Japan MV 480V
50Hz
Japan -> Japan MV 480V
60Hz
50/60Hz Available from CPU v3.16xx
Jordan
SE2200 - SE6000,
SE2200H – SE3680H,
SE4k - SE27.6k
United Kingdom -> UK
230V
50Hz
Kenya
SE2200 - SE6000,
SE4k - SE27.6k
Kenya 50Hz Available from CPU v3.19xx
Kuwait
SE2200 - SE6000,
SE4k - SE27.6k
Contact SolarEdge support 50Hz Available from CPU v2.10xx / v3.14xx
Latvia
SE2200 - SE4000-
16A, SE2200H –
SE3680H, SE5k -
SE27.6k
Latvia 50Hz Available from CPU v2.0549
StorEdge without
backup power:
SE2200-SE4000-16A,
SE3500 AC Coupled
Inverter
Latvia 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Lithuania
SE2200 - SE6000,
SE2200H – SE3680H,
SE4k - SE27.6k
Lithuania 50Hz
StorEdge without Lithuania 50Hz Requires StorEdge-compatible inverter and installation
11
Supported inverters Inverter country setting Frequency Comments
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
of StorEdge Interface; refer to application note.
Luxembourg
SE2200 - SE6000,
SE4k - SE27.6k
Europe EN50438 50Hz Available from CPU v3.16xx
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Europe EN50438 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Malaysia
SE2200 - SE6000,
SE4k - SE27.6k
Malaysia 50Hz Available from CPU v2.09xx / v3.12xx
Malta
SE2200 - SE6000,
SE4k - SE27.6k
United Kingdom -> UK
230V
50Hz
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
United Kingdom -> UK
230V
50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Mauritius
SE2200 - SE6000,
SE4k - SE27.6k
Mauritius 50Hz
Mexico
SE3000A-US -
SE11400A-US
Mexico -> 220V
Mexico -> 240V
60Hz Can be connected to the following grids:
110/220V split phase (L-L connection)
127/220V WYE (L-L connection)
240/420V WYE (L-N connection)
SE9kUS, SE14.4KUS Mexico -> 220V 60Hz 127/220V WYE grid only
SE10kUS, SE20kUS,
SE33.3KUS
Mexico -> 240V
Mexico -> 277V
60Hz Can be connected to the following grids:
240/420V WYE; when connected to this grid the
SE10kUS is limited to 8.6kW AC, the SE20kUS is limited
to 17.3kW AC and the SE33.3KUS is limited to 28.6kW
AC
277/480V WYE
Namibia
SE2200 - SE6000,
SE2200H – SE3680H,
SE4k - SE27.6k
South Africa 50Hz
12
Supported inverters Inverter country setting Frequency Comments
The Netherlands
SE2200 - SE6000,
SE2200H – SE3680H,
SE4k - SE27.6k
Netherlands 50Hz
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Netherlands 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
New Zealand
SE2200 - SE6000,
SE5k - SE27.6k
New Zealand -> Vector
Australia -> Australia
50Hz
New Zealand setting available from CPU v3.16xx
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
New Zealand -> Vector
Australia -> Australia
50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
StorEdge with
backup power:
SE5000-AUS -
SE6000-AUS
New Zealand -> Vector
Australia -> Australia
50Hz Available from CPU v3.18xx
Norway
SE2200 - SE6000,
SE2200H – SE3680H,
SE4k – SE27.6k
Norway 50Hz Available from CPU v2.10xx / v3.14xx
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Norway 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Panama
SE3000A-US -
SE11400A-US,
SE9kUS, SE10kUS,
SE20kUS
Contact SolarEdge support
Philippines
SE2200 - SE6000 Philippines 60Hz Can be connected to the following grids:
115/230V split phase (L-L connection)
220/380V WYE (L-N connection)
230/400V WYE (L-N connection)
240/420V WYE (L-N connection)
SE5k - SE27.6k Philippines 60Hz Can be connected to the following grids:
13
Supported inverters Inverter country setting Frequency Comments
220/380V WYE
230/400V WYE
240/420V WYE
SE33.3k Philippines -> Philippines
MV
50Hz Available from CPU v3.19xx
This inverter has a 277/480Vac output voltage and is
designed for connection to the medium voltage grid via
a transformer
SE17k - SE27.6K Philippines -> 230V L-L No
N
60Hz Can be connected to the following grid: 230V True Delta
(requires inverter adjustment; contact SolarEdge
support)
SE17k limited to 10kW AC
SE25K limited to 14.7kW AC
SE27.6K limited to 16.2kW AC
Available from CPU v3.16xx
Poland
SE2200 - SE6000,
SE2200H – SE3680H,
SE5k - SE27.6k
Poland 50Hz
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Poland 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Portugal
SE2200 - SE6000,
SE2200H – SE3680H,
SE4k - SE27.6k
Portugal 50Hz
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Portugal 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Romania
SE2200 - SE6000,
SE4k - SE27.6k
Romania 50Hz
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Romania 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Seychelles
SE2200 - SE6000,
SE4k - SE27.6k
Mauritius 50Hz
14
Supported inverters Inverter country setting Frequency Comments
Singapore
SE2200 - SE6000,
SE2200H – SE3680H,
SE4k - SE27.6k
Singapore 50Hz
Slovakia
SE2200 - SE6000,
SE2200H – SE3680H,
SE5k - SE27.6k
Slovakia -> Slovakia ZSED
Slovakia -> Slovakia SSED
Slovakia -> Slovakia VSD
50Hz Available from CPU v3.1961
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Slovakia -> Slovakia ZSED
Slovakia -> Slovakia SSED
Slovakia -> Slovakia VSD
50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Slovenia
SE2200H – SE3680H,
SE4k - SE27.6k
Slovenia 50Hz
South Africa
SE2200 - SE6000,
SE2200H – SE3680H,
SE4k - SE27.6k
South Africa 50Hz
SE33.3k South Africa -> South
Africa MV
50Hz Available from CPU v3.19xx
This inverter has a 277/480Vac output voltage and is
designed for connection to the medium voltage grid via
a transformer
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
South Africa 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
StorEdge with
backup power:
SE5000-ZAS -
SE6000-ZAS
South Africa 50Hz Available from CPU v3.18xx
Spain
SE2200 - SE6000,
SE2200H – SE3680H,
SE4k - SE27.6k
Spain 50Hz
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Spain 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Sri Lanka
15
Supported inverters Inverter country setting Frequency Comments
SE3500, SE5000 –
SE6000, SE2200H –
SE3680H
Sri Lanka 50Hz
St. Lucia
SE3000A-US -
SE11400A-US
Caribbean -> St. Lucia 50Hz
St. Vincent
SE2200 – SE4000-
16A, SE4k - SE10k
United Kingdom -> UK
230V
50Hz
Sweden
SE2200 - SE6000,
SE4k - SE27.6k
Sweden 50Hz
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Sweden 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Switzerland
SE2200-SE6000,
SE4k - SE27.6k
Switzerland 50Hz
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Switzerland 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Tahiti
SE2200 - SE6000,
SE4k - SE27.6k
Tahiti 60Hz Available from CPU v2.09xx / v3.12xx
Taiwan
SE2200 - SE6000,
SE4k - SE27.6k
Taiwan 60Hz
SE33.3k Taiwan -> Taiwan MV 60Hz Available from CPU v3.19xx
This inverter has a 277/480Vac output voltage and is
designed for connection to the medium voltage grid via
a transformer
Thailand
SE5000, SE10K,
SE25K, SE27.6K
Thailand -> Thailand MEA
Thailand -> Thailand PEA
50Hz Available from CPU v3.16xx
Turkey
SE2200 - SE6000,
SE2200H – SE3680H,
SE4k – SE27.6K
Turkey -> Turkey
Turkey -> N. Cyprus
50Hz
16
Supported inverters Inverter country setting Frequency Comments
SE33.3k Turkey -> Turkey MV 50Hz Available from CPU v3.19xx
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Turkey -> Turkey
Turkey -> N. Cyprus
50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
Ukraine
SE2200 – SE6000,
SE4k - SE27.6k
Europe EN50438 50Hz Available from CPU v3.16xx
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
Europe EN50438 50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
United Kingdom
SE2200 - SE6000,
SE2200H – SE3680H,
SE4k - SE27.6k
United Kingdom -> GBR
United Kingdom -> N.
Ireland
50Hz N. Ireland setting available from CPU v2.10xx / v3.14xx
GBR setting available from CPU v3.16xx; in earlier
versions use UK 230V
SE33.3k United Kingdom -> UK 480 50Hz This inverter has a 277/480Vac output voltage and is
designed for connection to the medium voltage grid via
a transformer
StorEdge without
backup power:
SE2200-SE6000,
SE3500 AC Coupled
Inverter
United Kingdom -> GBR
United Kingdom -> N.
Ireland
50Hz Requires StorEdge-compatible inverter and installation
of StorEdge Interface; refer to application note.
United States (including Guam, Puerto Rico and US Virgin Islands, excluding Hawaii and New York)
SE3000A-US -
SE11400A-US
USA -> Auto
USA -> 240V
USA -> 240V No Neutral
USA -> 208V
USA -> 208V No Neutral
Rule 21 -> Auto
Rule 21 -> 240V
Rule 21 -> 240V No Neutral
Rule 21 -> 208V
Rule 21 -> 208V No Neutral
60Hz Refer to the inverter datasheet for full inverter-grid
compatibility:
http://www.solaredge.us/files/pdfs/products/inverters/
se-single-phase-us-inverter-datasheet.pdf
Rule 21 setting available from CPU v3.16xx
SE9kUS, SE14.4kUS USA -> 208V
Rule 21 -> 208V
60Hz 120/208V WYE grid or 208V Delta grid (SE9kUS delta
grid support for inverters with part number SE9K-
US228NNU4)
Rule 21 setting available from CPU v3.16xx
SE10kUS, SE20KUS,
SE33.3kUS
USA -> 277V 60Hz 277/480V WYE grid only
17
Supported inverters Inverter country setting Frequency Comments
Rule 21 -> 277V
Puerto Rico 277V
Rule 21 setting available from CPU v3.16xx
Puerto Rico setting available from CPU v3.19xx
SE7600A-USS
(StorEdge inverter)
USA -> Auto
USA -> 240V
60Hz Available from CPU v3.18xx
United States (Hawaii only)
SE3000A-US -
SE11400A-US
Hawaii -> XXX Auto
Hawaii -> XXX 240V
Hawaii -> XXX 240V No
Neutral
Hawaii -> XXX 208V
Hawaii -> XXX 208V No
Neutral
XXX = Hawaii / Kauai /
Molokai and Lanai
60Hz Refer to the inverter datasheet for full inverter-grid
compatibility:
http://www.solaredge.us/files/pdfs/products/inverters/
se-single-phase-us-inverter-datasheet.pdf
Use Hawaii settings for HECO grid settings
Molokai and Lanai setting available from CPU v2.10xx /
v3.14xx
SE9kUS, SE14.4KUS Hawaii -> XXX 208V
XXX = Hawaii / Kauai /
Molokai and Lanai
60Hz 120/208V WYE grid or 208V Delta grid (SE9kUS delta
grid support for inverters with part number SE9K-
US228NNU4)
Use Hawaii settings for HECO grid settings
Molokai and Lanai setting available from CPU v2.10xx /
v3.14xx
SE10kUS, SE20KUS,
SE33.3kUS
Hawaii -> XXX 277V
XXX = Hawaii / Kauai /
Molokai and Lanai
60Hz 277/480V WYE grid only
Use Hawaii settings for HECO grid settings
Molokai and Lanai setting available from CPU v2.10xx /
v3.14xx
SE7600A-USS
(StorEdge inverter)
Hawaii -> XXX Auto
Hawaii -> XXX 240V
Hawaii -> XXX 240V No
Neutral
XXX = Hawaii / Kauai /
Molokai and Lanai
60Hz Use Hawaii settings for HECO grid settings
Available from CPU v3.18xx
United States (New York only)
SE3000A-US -
SE11400A-US
NY -> New-York Auto
NY -> New-York 240V
NY -> New-York 240V No
Neutral
NY -> New-York 208V
NY -> New-York 208V No
Neutral
60Hz Refer to the inverter datasheet for full inverter-grid
compatibility:
http://www.solaredge.us/files/pdfs/products/inverters/
se-single-phase-us-inverter-datasheet.pdf
Available from CPU v2.10xx / v3.14xx
SE9kUS, SE14.4KUS NY -> New-York 208V 60Hz 120/208V WYE grid or 208V Delta grid (SE9kUS delta
grid support for inverters with part number SE9K-
US228NNU4)
Available from CPU v2.10xx / v3.14xx
18
Supported inverters Inverter country setting Frequency Comments
SE10kUS, SE20KUS,
SE33.3kUS
NY -> New-York 277V 60Hz 277/480V WYE grid only
Available from CPU v2.10xx / v3.14xx
SE7600A-USS
(StorEdge inverter)
NY -> New-York Auto
NY -> New-York 240V
NY -> New-York 240V No
Neutral
60Hz Available from CPU v3.18xx
Zimbabwe
SE2200 - SE6000,
SE4k – SE27.6k
Zimbabwe 50Hz Available from CPU v3.16xx