Last update: Nov. 2016 1 Countries Supported by the SolarEdge Inverters The SolarEdge inverters can be used in many different countries. This document details countries where SolarEdge approves installation of its inverters. Installation should always be done in compliance with local regulations, and in case of a conflict between local regulations and this document, local regulations apply. Summary The SolarEdge inverters may be installed in the following countries. Unless stated otherwise, the approval refers to low voltage installations. For medium voltage installations, please contact SolarEdge support. Please refer to the country details below for more information, as in some countries not all grids are supported or not all inverter models are supported. In supported countries, connection of supported inverters to non-supported grids is permitted through a transformer, if the secondary connection (transformer connection to the inverter) is identical to a supported grid. NOTE Transformer procurement, installation, maintenance and support are the responsibility of the installer. Damage to the inverter due to incorrect transformer installation or use of a transformer that is incompatible with the SolarEdge system will render the SolarEdge warranty invalid. NOTE Prior to purchasing a StorEdge system verify battery availablity and service in the country. Availability of SolarEdge StorEdge products does not guarantee battery availabllity. A country listed in bold indicates that StorEdge inverters with backup are approved for installation in that country. Aruba Australia Austria Barbados Belarus Belgium Bermuda Botswana Bulgaria Canada Cape Verde China Costa Rica Croatia Curacao Cyprus Czech Republic Denmark Dubai El Salvador Estonia Finland France Germany Ghana Greece Grenada Guatemala Hungary India Indonesia Ireland Israel Italy Jamaica Japan Jordan Kenya Kuwait Latvia Lithuania Luxembourg Malaysia Malta Mauritius Mexico Namibia The Netherlands New Zealand Norway Panama Philippines Poland Portugal Romania Seychelles Singapore Slovakia Slovenia South Africa Spain Sri Lanka St. Lucia St. Vincent Sweden Switzerland Tahiti Taiwan Thailand Turkey Ukraine United Kingdom USA Zimbabwe For installation in countries or with grids not detailed in this document, contact SolarEdge support: [email protected]

Upload: others

Post on 03-Jun-2020

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Countries Supported by the SolarEdge Inverters€¦ · Countries Supported by the SolarEdge Inverters The SolarEdge inverters can be used in many different countries. This document

Last update: Nov. 2016

1

Countries Supported by the SolarEdge Inverters

The SolarEdge inverters can be used in many different countries. This document details countries where SolarEdge approves

installation of its inverters. Installation should always be done in compliance with local regulations, and in case of a conflict

between local regulations and this document, local regulations apply.

Summary

The SolarEdge inverters may be installed in the following countries. Unless stated otherwise, the approval refers to low voltage

installations. For medium voltage installations, please contact SolarEdge support. Please refer to the country details below for

more information, as in some countries not all grids are supported or not all inverter models are supported.

In supported countries, connection of supported inverters to non-supported grids is permitted through a transformer, if the

secondary connection (transformer connection to the inverter) is identical to a supported grid.

NOTE

Transformer procurement, installation, maintenance and support are the responsibility of the installer. Damage to the inverter due to

incorrect transformer installation or use of a transformer that is incompatible with the SolarEdge system will render the SolarEdge

warranty invalid.

NOTE

Prior to purchasing a StorEdge system verify battery availablity and service in the country. Availability of SolarEdge StorEdge products

does not guarantee battery availabllity.

A country listed in bold indicates that StorEdge inverters with backup are approved for installation in that country.

Aruba

Australia

Austria

Barbados

Belarus

Belgium

Bermuda

Botswana

Bulgaria

Canada

Cape Verde

China

Costa Rica

Croatia

Curacao

Cyprus

Czech Republic

Denmark

Dubai

El Salvador

Estonia

Finland

France

Germany

Ghana

Greece

Grenada

Guatemala

Hungary

India

Indonesia

Ireland

Israel

Italy

Jamaica

Japan

Jordan

Kenya

Kuwait

Latvia

Lithuania

Luxembourg

Malaysia

Malta

Mauritius

Mexico

Namibia

The Netherlands

New Zealand

Norway

Panama

Philippines

Poland

Portugal

Romania

Seychelles

Singapore

Slovakia

Slovenia

South Africa

Spain

Sri Lanka

St. Lucia

St. Vincent

Sweden

Switzerland

Tahiti

Taiwan

Thailand

Turkey

Ukraine

United Kingdom

USA

Zimbabwe

For installation in countries or with grids not detailed in this document, contact SolarEdge support: [email protected]

Page 2: Countries Supported by the SolarEdge Inverters€¦ · Countries Supported by the SolarEdge Inverters The SolarEdge inverters can be used in many different countries. This document

2

Detailed Information per Country

The table below details for each of the above countries:

1. Supported inverters: which SolarEdge inverters may be used in the country

2. Inverter country setting: to what country setting the inverter should be configured in order to comply with the local

grid requirements. Some countries have a submenu that should be used; sub-entries are indicated with the following

symbol: ->

3. Frequency: the nominal inverter AC frequency for the corresponding country setting

4. Comments: additional information about the inverter and grid support

Page 3: Countries Supported by the SolarEdge Inverters€¦ · Countries Supported by the SolarEdge Inverters The SolarEdge inverters can be used in many different countries. This document

3

Supported inverters Inverter country setting Frequency Comments

Aruba

SE3000A-US –

SE11400A-US

Caribbean -> Aruba 60Hz Available from CPU v2.07xx

Can be connected to the following grid: 127/220V (L-L

connection)

SE3800A-US limited to 3.5kW AC

SE6000A-US limited to 5.5kW AC

SE11400A-US approved only for installations with no

LVRT (low voltage ride through) requirement; if required

– contact SolarEdge support

SE9kUS Caribbean -> Aruba 60Hz Available from CPU v2.07xx

Can be connected to the following grid: 127/220V

Australia

SE2200 - SE6000,

SE5k - SE27.6k

Australia -> Australia

Australia -> Queensland

Australia -> Victoria

50Hz Use Queensland setting when QLD wider voltage range

is required; available from CPU v2.0496

Victoria setting available from CPU v3.19xx

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Australia -> Australia

Australia -> Queensland

Australia -> Victoria

50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

StorEdge with

backup power:

SE5000-AUS -

SE6000-AUS

Australia -> Australia

Australia -> Queensland

Australia -> Victoria

50Hz Available from CPU v3.18xx

Austria

SE2200 - SE6000,

SE2200H – SE3680H,

SE4k - SE27.6k

Austria 50Hz

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Austria 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Barbados

SE3000A-US -

SE11400A-US

Caribbean -> Barbados

230V No N

50Hz Available from CPU v2.0496

Can be connected to the following grids:

115/230V split phase or 3-wire (L-L connection)

230/400V WYE (L-N connection)

SE9KUS Caribbean -> Barbados

115V

50Hz Available from CPU v2.09xx / v3.12xx

Can be connected to the following grid: 115/200V WYE

Page 4: Countries Supported by the SolarEdge Inverters€¦ · Countries Supported by the SolarEdge Inverters The SolarEdge inverters can be used in many different countries. This document

4

Supported inverters Inverter country setting Frequency Comments

SE10kUS - SE20kUS Caribbean -> Barbados

230V (No N)

50Hz Supported in inverters shipped from Jan. 10 2014 that

have DSP1 v1.13.321; for other inverters contact

SolarEdge support.

Can be connected to the following grid: 230/400V WYE

SE20kUS limited to 16.5kW AC

Belarus

SE2200 – SE6000,

SE4k - SE27.6k

Europe EN50438 50Hz Available from CPU v3.16xx

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Europe EN50438 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Belgium

SE2200 - SE5000,

SE2200H – SE3680H,

SE4k - SE27.6k

Belgium

50Hz Refer to the following note for more details about grid

compliance:

http://www.solaredge.com/files/pdfs/belgian-grids-

application-note.pdf

StorEdge without

backup power:

SE2200-SE5000,

SE3500 AC Coupled

Inverter

Belgium 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

StorEdge with

backup power:

SE5000-RWS

Belgium 50Hz Available from CPU v3.18xx

Bermuda

SE3000A-US -

SE11400A-US

USA -> Auto

USA -> 240V

USA -> 240V No Neutral

USA -> 208V

USA -> 208V No Neutral

60Hz Refer to the inverter datasheet for full inverter-grid

compatibility:

http://www.solaredge.us/files/pdfs/products/inverters/

se-single-phase-us-inverter-datasheet.pdf

SE9kUS USA -> 208V 60Hz 120/208V WYE grid only

SE10kUS – SE20kUS USA -> 277V 60Hz 277/480V WYE grid only

Botswana

SE2200 - SE6000,

SE2200H – SE3680H,

SE4k - SE27.6k

South Africa 50Hz

Bulgaria

SE2200 - SE6000,

SE2200H – SE3680H,

SE5k - SE27.6k

Bulgaria 50Hz

Page 5: Countries Supported by the SolarEdge Inverters€¦ · Countries Supported by the SolarEdge Inverters The SolarEdge inverters can be used in many different countries. This document

5

Supported inverters Inverter country setting Frequency Comments

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Bulgaria 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Canada

SE3000A-US-CAN -

SE11400A-US-CAN

USA -> Auto

USA -> 240V

USA -> 240V No Neutral

USA -> 208V

USA -> 208V No Neutral

60Hz Refer to the inverter datasheet for full inverter-grid

compatibility:

http://www.solaredge.us/files/pdfs/products/inverters/

se-single-phase-us-inverter-datasheet.pdf

SE9kUS-CAN,

SE14.4KUS

USA -> 208V 60Hz 120/208V WYE grid only

SE10kUS-CAN,

SE20kUS-CAN,

SE33.3KUS

USA -> 277V 60Hz 277/480V WYE grid only

Cape Verde

SE2200 – SE6000 Contact SolarEdge support 50Hz

SE4k – SE27.6k Cape Verde 50Hz Available from CPU version 3.18xx

China

SE2200 – SE6000,

SE5k - SE17k

China 50Hz All systems must be approved by SolarEdge; contact

SolarEdge Support for details

Costa Rica

SE3000A-US -

SE11400A-US

USA -> Auto

USA -> 240V

USA -> 240V No Neutral

USA -> 208V

USA -> 208V No Neutral

60Hz Refer to the inverter datasheet for full inverter-grid

compatibility:

http://www.solaredge.us/files/pdfs/products/inverters/

se-single-phase-us-inverter-datasheet.pdf

SE9kUS USA -> 208V 60Hz 120/208V WYE grid only

SE10kUS – SE20kUS USA -> 277V 60Hz 277/480V WYE grid only

Croatia

SE2200 - SE5000,

SE4k - SE27.6k

Croatia 50Hz Available from CPU v2.0496

StorEdge without

backup power:

SE2200-SE5000,

SE3500 AC Coupled

Inverter

Croatia 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Curacao

SE2200 – SE5000 Caribbean -> Curacao 50Hz Available from CPU v2.0637

Can be connected to the following grids:

Page 6: Countries Supported by the SolarEdge Inverters€¦ · Countries Supported by the SolarEdge Inverters The SolarEdge inverters can be used in many different countries. This document

6

Supported inverters Inverter country setting Frequency Comments

127/220V WYE (L-L connection)

110/220V split phase (L-L connection)

220/380V WYE (L-N connection)

SE4k - SE27.6k Caribbean -> Curacao 50Hz Available from CPU v2.0637

Can be connected to the following grid: 220/380V WYE

Systems 100kW and larger must be approved by

SolarEdge; contact SolarEdge Support for details

Cyprus

SE2200 – SE6000,

SE5k - SE27.6k

Cyprus

Cyprus 240V

50Hz

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Cyprus

Cyprus 240V

50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Czech Republic

SE2200 - SE6000,

SE2200H – SE3680H,

SE5k - SE17k

Czech Republic 50Hz

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Czech Republic 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Denmark

SE2200 - SE6000,

SE4k - SE27.6k

Denmark -> Denmark

Denmark -> Denmark

Residen.

Denmark -> Denmark VDE

Denmark -> Denmark VDE

Res.

50Hz Use Residential settings to comply with 16Aac and 6kW

limits of residential systems

Use VDE settings for VDE-AR-N-4105 grid settings;

Available from CPU v2.0496

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Denmark -> Denmark

Denmark -> Denmark

Residen.

Denmark -> Denmark VDE

Denmark -> Denmark VDE

Res.

50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Dubai

SE2200 – SE6000 Dubai 50Hz Available from CPU v3.18xx

SE4k - SE27.6k Dubai 50Hz Available from CPU v3.18xx

El Salvador

SE3000A-US - USA -> Auto 60Hz

Page 7: Countries Supported by the SolarEdge Inverters€¦ · Countries Supported by the SolarEdge Inverters The SolarEdge inverters can be used in many different countries. This document

7

Supported inverters Inverter country setting Frequency Comments

SE11400A-US USA -> 240V

USA -> 240V No Neutral

Estonia

SE2200 - SE4000-

16A, SE4k-SE27.6k

Portugal 50Hz

StorEdge without

backup power:

SE2200-SE4000-16A,

SE3500 AC Coupled

Inverter

Portugal 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Finland

SE2200 – SE4000-

16A

Finland 50Hz Available from CPU v3.18xx

SE4k – SE27.6k Finland 50Hz Available from CPU v3.18xx

StorEdge without

backup power:

SE2200-SE4000-16A,

SE3500 AC Coupled

Inverter

Finland 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

France

SE2200 - SE6000,

SE2200H – SE3680H,

SE4k - SE27.6k

France 50Hz

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

France 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

StorEdge with

backup power:

SE5000-RWS -

SE6000-RWS

France 50Hz Available from CPU v3.18xx

Germany

SE2200 - SE5000,

SE2200H – SE3680H,

SE4k - SE12.5k

Germany 50Hz

SE15k-SE27.6k Germany -> Germany

Germany -> Germany

MVGC

50Hz These inverters are approved for connection to the

medium voltage grid according to the BDEW standard;

use Germany MVG

SE33.3K Germany -> MVGC 480 50Hz This inverter has a 277/480Vac output voltage and is

designed for connection to the medium voltage grid via

a transformer

StorEdge without Germany 50Hz Requires StorEdge-compatible inverter and installation

Page 8: Countries Supported by the SolarEdge Inverters€¦ · Countries Supported by the SolarEdge Inverters The SolarEdge inverters can be used in many different countries. This document

8

Supported inverters Inverter country setting Frequency Comments

backup power:

SE2200-SE5000,

SE3500 AC Coupled

Inverter

of StorEdge Interface; refer to application note.

Ghana

SE2200 - SE6000,

SE5k - SE27.6k

Ghana 50Hz Available from CPU v3.18xx

Greece

SE2200 - SE6000,

SE2200H – SE3680H,

SE4k - SE27.6k

Greece -> Greece

Continent

Greece -> Greece Islands

50Hz

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Greece -> Greece

Continent

Greece -> Greece Islands

50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Grenada

SE3000A-US -

SE11400A-US

Grenada 50Hz Available from CPU v3.18xx

Can be connected to the following grid: 230/400V WYE

(L-N connection)

SE9KUS Grenada 50Hz Available from CPU v3.18xx

Can be connected to the following grid: 230/400V WYE

SE10kUS - SE20kUS Grenada 50Hz Available from CPU v3.18xx

Can be connected to the following grid: 230/400V WYE

SE20kUS limited to 16.5kW AC

Guatemala

SE3000A-US –

SE5000A-US

USA -> Auto

USA -> 208V

USA -> 208V No Neutral

60Hz

SE9kUS USA -> 208V 60Hz

Hungary

SE2200 - SE6000,

SE2200H – SE3680H,

SE5k - SE27.6k

Hungary 50Hz Available from CPU v2.09xx / v3.12xx

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Hungary 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

India

SE2200 - SE6000,

SE4k - SE27.6k

India 50Hz

Page 9: Countries Supported by the SolarEdge Inverters€¦ · Countries Supported by the SolarEdge Inverters The SolarEdge inverters can be used in many different countries. This document

9

Supported inverters Inverter country setting Frequency Comments

SE33.3k India -> India MV 50Hz Available from CPU v3.19xx

This inverter has a 277/480Vac output voltage and is

designed for connection to the medium voltage grid via

a transformer

Indonesia

SE2200 - SE6000,

SE5K-SE17K

Indonesia 50Hz Available from CPU v3.16xx

Ireland

SE2200 - SE6000,

SE2200H – SE3680H,

SE4k - SE27.6k

Ireland 50Hz Available from CPU v2.0496

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Ireland 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Israel

SE2200 - SE6000,

SE4k - SE27.6k

Israel -> Israel

Israel -> Israel -

Commercial

50Hz Commercial setting for systems >50kW available from

CPU v2.07xx

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Israel -> Israel

50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Italy

SE2200 - SE6000,

SE4k - SE12.5k

Italy -> Italy

Italy -> Italy (No SPI)

50Hz

SE15k-SE27.6k Italy -> Italy

Italy -> Italy (No SPI)

50Hz These inverters are approved for connection to the

medium voltage grid according to the CEI 0-16 standard

SE33.3k Italy -> Italy 277V No SPI 50Hz This inverter has a 277/480Vac output voltage and is

designed for connection to the medium voltage grid via

a transformer

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Italy -> Italy

Italy -> Italy (No SPI)

50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

StorEdge with

backup power:

SE5000-RWS -

SE6000-RWS

Italy -> Italy 50Hz Available from CPU v3.18xx

Jamaica

Page 10: Countries Supported by the SolarEdge Inverters€¦ · Countries Supported by the SolarEdge Inverters The SolarEdge inverters can be used in many different countries. This document

10

Supported inverters Inverter country setting Frequency Comments

SE3000A-US -

SE11400A-US

Caribbean -> Jamaica ->

240V No Neutral

Caribbean -> Jamaica ->

220V No Neutral

50Hz Available from CPU v2.0496

Can be connected to the following grids:

110/220V split phase (L-L connection)

240/415V WYE (L-N connection)

220V delta (L-L connection)

SE10kUS - SE20kUS Caribbean -> Jamaica ->

240V (No N)

50Hz Supported in inverters shipped from Jan. 10 2014 that

have DSP1 v1.13.321; for other inverters contact

SolarEdge support.

Can be connected to the following grid: 240/415V WYE

SE20kUS limited to 17.3kW AC

Japan

SE25K-JP Japan -> Japan 380V 50Hz

Japan -> Japan 380V 60Hz

50/60Hz Available from CPU v3.19xx

SE33.3K-JP Japan -> Japan MV 480V

50Hz

Japan -> Japan MV 480V

60Hz

50/60Hz Available from CPU v3.16xx

Jordan

SE2200 - SE6000,

SE2200H – SE3680H,

SE4k - SE27.6k

United Kingdom -> UK

230V

50Hz

Kenya

SE2200 - SE6000,

SE4k - SE27.6k

Kenya 50Hz Available from CPU v3.19xx

Kuwait

SE2200 - SE6000,

SE4k - SE27.6k

Contact SolarEdge support 50Hz Available from CPU v2.10xx / v3.14xx

Latvia

SE2200 - SE4000-

16A, SE2200H –

SE3680H, SE5k -

SE27.6k

Latvia 50Hz Available from CPU v2.0549

StorEdge without

backup power:

SE2200-SE4000-16A,

SE3500 AC Coupled

Inverter

Latvia 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Lithuania

SE2200 - SE6000,

SE2200H – SE3680H,

SE4k - SE27.6k

Lithuania 50Hz

StorEdge without Lithuania 50Hz Requires StorEdge-compatible inverter and installation

Page 11: Countries Supported by the SolarEdge Inverters€¦ · Countries Supported by the SolarEdge Inverters The SolarEdge inverters can be used in many different countries. This document

11

Supported inverters Inverter country setting Frequency Comments

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

of StorEdge Interface; refer to application note.

Luxembourg

SE2200 - SE6000,

SE4k - SE27.6k

Europe EN50438 50Hz Available from CPU v3.16xx

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Europe EN50438 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Malaysia

SE2200 - SE6000,

SE4k - SE27.6k

Malaysia 50Hz Available from CPU v2.09xx / v3.12xx

Malta

SE2200 - SE6000,

SE4k - SE27.6k

United Kingdom -> UK

230V

50Hz

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

United Kingdom -> UK

230V

50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Mauritius

SE2200 - SE6000,

SE4k - SE27.6k

Mauritius 50Hz

Mexico

SE3000A-US -

SE11400A-US

Mexico -> 220V

Mexico -> 240V

60Hz Can be connected to the following grids:

110/220V split phase (L-L connection)

127/220V WYE (L-L connection)

240/420V WYE (L-N connection)

SE9kUS, SE14.4KUS Mexico -> 220V 60Hz 127/220V WYE grid only

SE10kUS, SE20kUS,

SE33.3KUS

Mexico -> 240V

Mexico -> 277V

60Hz Can be connected to the following grids:

240/420V WYE; when connected to this grid the

SE10kUS is limited to 8.6kW AC, the SE20kUS is limited

to 17.3kW AC and the SE33.3KUS is limited to 28.6kW

AC

277/480V WYE

Namibia

SE2200 - SE6000,

SE2200H – SE3680H,

SE4k - SE27.6k

South Africa 50Hz

Page 12: Countries Supported by the SolarEdge Inverters€¦ · Countries Supported by the SolarEdge Inverters The SolarEdge inverters can be used in many different countries. This document

12

Supported inverters Inverter country setting Frequency Comments

The Netherlands

SE2200 - SE6000,

SE2200H – SE3680H,

SE4k - SE27.6k

Netherlands 50Hz

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Netherlands 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

New Zealand

SE2200 - SE6000,

SE5k - SE27.6k

New Zealand -> Vector

Australia -> Australia

50Hz

New Zealand setting available from CPU v3.16xx

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

New Zealand -> Vector

Australia -> Australia

50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

StorEdge with

backup power:

SE5000-AUS -

SE6000-AUS

New Zealand -> Vector

Australia -> Australia

50Hz Available from CPU v3.18xx

Norway

SE2200 - SE6000,

SE2200H – SE3680H,

SE4k – SE27.6k

Norway 50Hz Available from CPU v2.10xx / v3.14xx

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Norway 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Panama

SE3000A-US -

SE11400A-US,

SE9kUS, SE10kUS,

SE20kUS

Contact SolarEdge support

Philippines

SE2200 - SE6000 Philippines 60Hz Can be connected to the following grids:

115/230V split phase (L-L connection)

220/380V WYE (L-N connection)

230/400V WYE (L-N connection)

240/420V WYE (L-N connection)

SE5k - SE27.6k Philippines 60Hz Can be connected to the following grids:

Page 13: Countries Supported by the SolarEdge Inverters€¦ · Countries Supported by the SolarEdge Inverters The SolarEdge inverters can be used in many different countries. This document

13

Supported inverters Inverter country setting Frequency Comments

220/380V WYE

230/400V WYE

240/420V WYE

SE33.3k Philippines -> Philippines

MV

50Hz Available from CPU v3.19xx

This inverter has a 277/480Vac output voltage and is

designed for connection to the medium voltage grid via

a transformer

SE17k - SE27.6K Philippines -> 230V L-L No

N

60Hz Can be connected to the following grid: 230V True Delta

(requires inverter adjustment; contact SolarEdge

support)

SE17k limited to 10kW AC

SE25K limited to 14.7kW AC

SE27.6K limited to 16.2kW AC

Available from CPU v3.16xx

Poland

SE2200 - SE6000,

SE2200H – SE3680H,

SE5k - SE27.6k

Poland 50Hz

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Poland 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Portugal

SE2200 - SE6000,

SE2200H – SE3680H,

SE4k - SE27.6k

Portugal 50Hz

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Portugal 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Romania

SE2200 - SE6000,

SE4k - SE27.6k

Romania 50Hz

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Romania 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Seychelles

SE2200 - SE6000,

SE4k - SE27.6k

Mauritius 50Hz

Page 14: Countries Supported by the SolarEdge Inverters€¦ · Countries Supported by the SolarEdge Inverters The SolarEdge inverters can be used in many different countries. This document

14

Supported inverters Inverter country setting Frequency Comments

Singapore

SE2200 - SE6000,

SE2200H – SE3680H,

SE4k - SE27.6k

Singapore 50Hz

Slovakia

SE2200 - SE6000,

SE2200H – SE3680H,

SE5k - SE27.6k

Slovakia -> Slovakia ZSED

Slovakia -> Slovakia SSED

Slovakia -> Slovakia VSD

50Hz Available from CPU v3.1961

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Slovakia -> Slovakia ZSED

Slovakia -> Slovakia SSED

Slovakia -> Slovakia VSD

50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Slovenia

SE2200H – SE3680H,

SE4k - SE27.6k

Slovenia 50Hz

South Africa

SE2200 - SE6000,

SE2200H – SE3680H,

SE4k - SE27.6k

South Africa 50Hz

SE33.3k South Africa -> South

Africa MV

50Hz Available from CPU v3.19xx

This inverter has a 277/480Vac output voltage and is

designed for connection to the medium voltage grid via

a transformer

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

South Africa 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

StorEdge with

backup power:

SE5000-ZAS -

SE6000-ZAS

South Africa 50Hz Available from CPU v3.18xx

Spain

SE2200 - SE6000,

SE2200H – SE3680H,

SE4k - SE27.6k

Spain 50Hz

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Spain 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Sri Lanka

Page 15: Countries Supported by the SolarEdge Inverters€¦ · Countries Supported by the SolarEdge Inverters The SolarEdge inverters can be used in many different countries. This document

15

Supported inverters Inverter country setting Frequency Comments

SE3500, SE5000 –

SE6000, SE2200H –

SE3680H

Sri Lanka 50Hz

St. Lucia

SE3000A-US -

SE11400A-US

Caribbean -> St. Lucia 50Hz

St. Vincent

SE2200 – SE4000-

16A, SE4k - SE10k

United Kingdom -> UK

230V

50Hz

Sweden

SE2200 - SE6000,

SE4k - SE27.6k

Sweden 50Hz

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Sweden 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Switzerland

SE2200-SE6000,

SE4k - SE27.6k

Switzerland 50Hz

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Switzerland 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Tahiti

SE2200 - SE6000,

SE4k - SE27.6k

Tahiti 60Hz Available from CPU v2.09xx / v3.12xx

Taiwan

SE2200 - SE6000,

SE4k - SE27.6k

Taiwan 60Hz

SE33.3k Taiwan -> Taiwan MV 60Hz Available from CPU v3.19xx

This inverter has a 277/480Vac output voltage and is

designed for connection to the medium voltage grid via

a transformer

Thailand

SE5000, SE10K,

SE25K, SE27.6K

Thailand -> Thailand MEA

Thailand -> Thailand PEA

50Hz Available from CPU v3.16xx

Turkey

SE2200 - SE6000,

SE2200H – SE3680H,

SE4k – SE27.6K

Turkey -> Turkey

Turkey -> N. Cyprus

50Hz

Page 16: Countries Supported by the SolarEdge Inverters€¦ · Countries Supported by the SolarEdge Inverters The SolarEdge inverters can be used in many different countries. This document

16

Supported inverters Inverter country setting Frequency Comments

SE33.3k Turkey -> Turkey MV 50Hz Available from CPU v3.19xx

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Turkey -> Turkey

Turkey -> N. Cyprus

50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

Ukraine

SE2200 – SE6000,

SE4k - SE27.6k

Europe EN50438 50Hz Available from CPU v3.16xx

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

Europe EN50438 50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

United Kingdom

SE2200 - SE6000,

SE2200H – SE3680H,

SE4k - SE27.6k

United Kingdom -> GBR

United Kingdom -> N.

Ireland

50Hz N. Ireland setting available from CPU v2.10xx / v3.14xx

GBR setting available from CPU v3.16xx; in earlier

versions use UK 230V

SE33.3k United Kingdom -> UK 480 50Hz This inverter has a 277/480Vac output voltage and is

designed for connection to the medium voltage grid via

a transformer

StorEdge without

backup power:

SE2200-SE6000,

SE3500 AC Coupled

Inverter

United Kingdom -> GBR

United Kingdom -> N.

Ireland

50Hz Requires StorEdge-compatible inverter and installation

of StorEdge Interface; refer to application note.

United States (including Guam, Puerto Rico and US Virgin Islands, excluding Hawaii and New York)

SE3000A-US -

SE11400A-US

USA -> Auto

USA -> 240V

USA -> 240V No Neutral

USA -> 208V

USA -> 208V No Neutral

Rule 21 -> Auto

Rule 21 -> 240V

Rule 21 -> 240V No Neutral

Rule 21 -> 208V

Rule 21 -> 208V No Neutral

60Hz Refer to the inverter datasheet for full inverter-grid

compatibility:

http://www.solaredge.us/files/pdfs/products/inverters/

se-single-phase-us-inverter-datasheet.pdf

Rule 21 setting available from CPU v3.16xx

SE9kUS, SE14.4kUS USA -> 208V

Rule 21 -> 208V

60Hz 120/208V WYE grid or 208V Delta grid (SE9kUS delta

grid support for inverters with part number SE9K-

US228NNU4)

Rule 21 setting available from CPU v3.16xx

SE10kUS, SE20KUS,

SE33.3kUS

USA -> 277V 60Hz 277/480V WYE grid only

Page 17: Countries Supported by the SolarEdge Inverters€¦ · Countries Supported by the SolarEdge Inverters The SolarEdge inverters can be used in many different countries. This document

17

Supported inverters Inverter country setting Frequency Comments

Rule 21 -> 277V

Puerto Rico 277V

Rule 21 setting available from CPU v3.16xx

Puerto Rico setting available from CPU v3.19xx

SE7600A-USS

(StorEdge inverter)

USA -> Auto

USA -> 240V

60Hz Available from CPU v3.18xx

United States (Hawaii only)

SE3000A-US -

SE11400A-US

Hawaii -> XXX Auto

Hawaii -> XXX 240V

Hawaii -> XXX 240V No

Neutral

Hawaii -> XXX 208V

Hawaii -> XXX 208V No

Neutral

XXX = Hawaii / Kauai /

Molokai and Lanai

60Hz Refer to the inverter datasheet for full inverter-grid

compatibility:

http://www.solaredge.us/files/pdfs/products/inverters/

se-single-phase-us-inverter-datasheet.pdf

Use Hawaii settings for HECO grid settings

Molokai and Lanai setting available from CPU v2.10xx /

v3.14xx

SE9kUS, SE14.4KUS Hawaii -> XXX 208V

XXX = Hawaii / Kauai /

Molokai and Lanai

60Hz 120/208V WYE grid or 208V Delta grid (SE9kUS delta

grid support for inverters with part number SE9K-

US228NNU4)

Use Hawaii settings for HECO grid settings

Molokai and Lanai setting available from CPU v2.10xx /

v3.14xx

SE10kUS, SE20KUS,

SE33.3kUS

Hawaii -> XXX 277V

XXX = Hawaii / Kauai /

Molokai and Lanai

60Hz 277/480V WYE grid only

Use Hawaii settings for HECO grid settings

Molokai and Lanai setting available from CPU v2.10xx /

v3.14xx

SE7600A-USS

(StorEdge inverter)

Hawaii -> XXX Auto

Hawaii -> XXX 240V

Hawaii -> XXX 240V No

Neutral

XXX = Hawaii / Kauai /

Molokai and Lanai

60Hz Use Hawaii settings for HECO grid settings

Available from CPU v3.18xx

United States (New York only)

SE3000A-US -

SE11400A-US

NY -> New-York Auto

NY -> New-York 240V

NY -> New-York 240V No

Neutral

NY -> New-York 208V

NY -> New-York 208V No

Neutral

60Hz Refer to the inverter datasheet for full inverter-grid

compatibility:

http://www.solaredge.us/files/pdfs/products/inverters/

se-single-phase-us-inverter-datasheet.pdf

Available from CPU v2.10xx / v3.14xx

SE9kUS, SE14.4KUS NY -> New-York 208V 60Hz 120/208V WYE grid or 208V Delta grid (SE9kUS delta

grid support for inverters with part number SE9K-

US228NNU4)

Available from CPU v2.10xx / v3.14xx

Page 18: Countries Supported by the SolarEdge Inverters€¦ · Countries Supported by the SolarEdge Inverters The SolarEdge inverters can be used in many different countries. This document

18

Supported inverters Inverter country setting Frequency Comments

SE10kUS, SE20KUS,

SE33.3kUS

NY -> New-York 277V 60Hz 277/480V WYE grid only

Available from CPU v2.10xx / v3.14xx

SE7600A-USS

(StorEdge inverter)

NY -> New-York Auto

NY -> New-York 240V

NY -> New-York 240V No

Neutral

60Hz Available from CPU v3.18xx

Zimbabwe

SE2200 - SE6000,

SE4k – SE27.6k