CR LAURENCE CO., INC. TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-17 TESTING ON IW 8000 SINGLE HUNG REPORT NUMBER J2603.01-303-44 R3 TEST DATE(S) 01/15/19 - 01/28/19 ISSUE DATE REVISION DATE 02/06/19 03/25/19 RECORD RETENTION END DATE 02/06/22 PAGES 14 DOCUMENT CONTROL NUMBER ATI 00438 (07/24/17) RT-R-AMER-Test-2804 © 2017 INTERTEK

Upload: others

Post on 26-Feb-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CR LAURENCE CO., INC. TEST REPORT...CR LAURENCE CO., INC. TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-17 TESTING ON IW 8000 SINGLE HUNG REPORT NUMBER J2603.01-303-44 R3

CR LAURENCE CO., INC. TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-17 TESTING ON IW 8000 SINGLE HUNG REPORT NUMBER J2603.01-303-44 R3 TEST DATE(S) 01/15/19 - 01/28/19

ISSUE DATE REVISION DATE 02/06/19 03/25/19 RECORD RETENTION END DATE 02/06/22 PAGES 14 DOCUMENT CONTROL NUMBER ATI 00438 (07/24/17) RT-R-AMER-Test-2804 © 2017 INTERTEK

Page 2: CR LAURENCE CO., INC. TEST REPORT...CR LAURENCE CO., INC. TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-17 TESTING ON IW 8000 SINGLE HUNG REPORT NUMBER J2603.01-303-44 R3

25800 Commercentre Drive Lake Forest, California 92630

Telephone: 949-460-9600

Facsimile: 717-764-4129 www.intertek.com/building

TEST REPORT FOR CR LAURENCE CO., INC. Report No.: j2603.01-303-44 R3 Date: 02/06/19

This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this report. Only the Client is authorized to permit copying or distribution of this report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only to the sample(s) tested. This report by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.

Version: 07/24/17 Page 2 of 14 RT-R-AMER-Test-2804

REPORT ISSUED TO CR LAURENCE CO.,INC. 2100 East 38th Street Vernon, California 90058 SECTION 1 SCOPE Intertek Building & Construction (B&C) was contracted by CR Laurence Co., Inc. 2100 East 38th Street Vernon, California 90058 to perform testing in accordance with AAMA/WDMA/CSA 101/I.S.2/A440-17, NAFS 2017 - North American Fenestration Standard/Specification for Windows, Doors, and Skylights, on their IW8000 Single Hung. Results obtained are tested values and were secured by using the designated test method(s). Testing was conducted at Intertek testing facility in Lake Forest, California. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. SECTION 2 SUMMARY OF TEST RESULTS

TITLE RESULTS

AAMA/WDMA/CSA 101/I.S.2/A440 -17 Class CW – PG80: Size Tested 1526 x 2318 mm (60 x 91-1/4 in) – Type H

Design Pressure ±3840 Pa (±80.20 psf)

Air Infiltration @ 1.57 psf 0.2 L/s/m2 (0.03 cfm/ft2)

Air Infiltration @ 6.27 psf 0.6 L/s/m2 (0.12 cfm/ft2)

Air Exfiltration @ 1.57 psf <0.1 L/s/m2 (<0.01 cfm/ft2)

Air Exfiltration @ 6.27 psf 0.6 L/s/m2 (0.12 cfm/ft2)

Water Penetration Resistance Test Pressure 580 Pa (12.11 psf)

For INTERTEK B&C:

COMPLETED BY: Aaron Baker REVIEWED BY: Jarod Hardman

TITLE:

Technician – Building & Construction TITLE: Operations Manager

SIGNATURE:

SIGNATURE:

DATE: 03/22/19 DATE: 03/22/19 adb:ab

Page 3: CR LAURENCE CO., INC. TEST REPORT...CR LAURENCE CO., INC. TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-17 TESTING ON IW 8000 SINGLE HUNG REPORT NUMBER J2603.01-303-44 R3

25800 Commercentre Drive Lake Forest, California 92630

Telephone: 949-460-9600

Facsimile: 717-764-4129 www.intertek.com/building

TEST REPORT FOR CR LAURENCE CO., INC. Report No.: j2603.01-303-44 R3 Date: 02/06/19

Version: 07/24/17 Page 3 of 14 RT-R-AMER-Test-2804

SECTION 3 TEST METHOD(S) The specimens were evaluated in accordance with the following:

AAMA/WDMA/CSA 101/I.S.2/A440-17, NAFS 2017 - North American Fenestration Standard/Specification for Windows, Doors, and Skylights

ASTM E283-04(2012), Standard Test Method for Determining Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen

ASTM E330/E330M-14, Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air Pressure Difference

ASTM E331-00(2016), Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference

ASTM E987-88(2009), Standard Test Methods for Deglazing Force of Fenestration Products

ASTM E2068-00(2016), Standard Test Method for Determination of Operating Force of Sliding Windows and Doors1

ASTM F588-14, Standard Test Methods for Measuring the Forced Entry Resistance of Window Assemblies, Excluding Glazing Impact

SECTION 4 MATERIAL SOURCE/INSTALLATION Test specimen was provided by the client. Representative samples of the test specimen will be retained by Intertek B&C for a minimum of four years from the test completion date. The specimen was installed into a Douglas Fir wood buck. The rough opening allowed for a 1/4" shim space. The exterior and interior perimeter of the door was sealed with silicone sealant. Installation of the tested product was performed by the client.

LOCATION ANCHOR DESCRIPTION ANCHOR LOCATION

Through Frame #10 x 2-1/2” Flat Head Phillips Wood Screws

3” from corner at head and sill 12” o/c; 4” from corners at jambs and 12” o/c.

Page 4: CR LAURENCE CO., INC. TEST REPORT...CR LAURENCE CO., INC. TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-17 TESTING ON IW 8000 SINGLE HUNG REPORT NUMBER J2603.01-303-44 R3

25800 Commercentre Drive Lake Forest, California 92630

Telephone: 949-460-9600

Facsimile: 717-764-4129 www.intertek.com/building

TEST REPORT FOR CR LAURENCE CO., INC. Report No.: j2603.01-303-44 R3 Date: 02/06/19

Version: 07/24/17 Page 4 of 14 RT-R-AMER-Test-2804

SECTION 5 LIST OF OFFICIAL OBSERVERS

NAME COMPANY

Garrett Osterode CR Laurence Co., Inc.

Aaron Baker Intertek B&C

Jarod Hardman Intertek B&C

SECTION 6 TEST SPECIMEN DESCRIPTION Product Type: Single Hung Series/Model: IW8000 Product Size(s):

OVERALL AREA: WIDTH HEIGHT

3.5 m² (38.07 ft2) millimeters inches millimeters inches

Overall Size 1526 60 2311 91

Interior Sash 1472 58 762 30

Frame Construction:

FRAME MEMBER MATERIAL DESCRIPTION

Head Aluminum Part No. SH812, See attached Drawings Section 10.

Jambs Aluminum Part No. SH814, See attached Drawings Section 10.

Sill Aluminum Part No. SH813, See attached Drawings Section 10.

Fixed Interlock Aluminum Part No. SH866, Secured through frame jambs with two #8 x 1” Phillip Hex Head fasteners into screw bosses. See Attached Drawings Section 10

Sill PVC Part No. WH811, snapped onto center leg. See attached Drawings Section 10.

Jambs PVC Part No. WH809 snapped onto jambs. See Attached drawings Section 10.

Page 5: CR LAURENCE CO., INC. TEST REPORT...CR LAURENCE CO., INC. TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-17 TESTING ON IW 8000 SINGLE HUNG REPORT NUMBER J2603.01-303-44 R3

25800 Commercentre Drive Lake Forest, California 92630

Telephone: 949-460-9600

Facsimile: 717-764-4129 www.intertek.com/building

TEST REPORT FOR CR LAURENCE CO., INC. Report No.: j2603.01-303-44 R3 Date: 02/06/19

Version: 07/24/17 Page 5 of 14 RT-R-AMER-Test-2804

FRAME MEMBER MATERIAL DESCRIPTION

Head PVC Part No. WH808, snapped onto center leg, See attached Drawings Section 10.

JOINERY TYPE DETAIL

All Corners Coped Secured through jambs with two #8 x 1” Hex Washer Head Screws into screw bosses.

Sash Construction:

SASH MEMBER MATERIAL DESCRIPTION

Interlock Aluminum Part No. SH854, See Attached Drawings Section 10

Stiles Aluminum Part No. SH855, See attached Drawings Section 10.

Bottom rail Aluminum Part No. SH852, See attached Drawings Section 10.

Interlock Aluminum Part No. SH858, See attached Drawings Section 10.

JOINERY TYPE DETAIL

All Corners Coped Secured through the stiles with four #8 x 1” Phillip Hex Head fasteners into screw bosses through balance catch clip.

Reinforcement: No reinforcement was utilized.

Weatherstripping:

DESCRIPTION QUANTITY LOCATION

Pile Gasket Triple Fin, 0.310” x 0.230”, W-027.

1 row Channel inserted full span of center leg of frame at sill and jambs.

Pile Gasket Triple Fin, 0.310” x 0.230”, W-027.

1 row Channel inserted full width of fixed and sash interlock.

Page 6: CR LAURENCE CO., INC. TEST REPORT...CR LAURENCE CO., INC. TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-17 TESTING ON IW 8000 SINGLE HUNG REPORT NUMBER J2603.01-303-44 R3

25800 Commercentre Drive Lake Forest, California 92630

Telephone: 949-460-9600

Facsimile: 717-764-4129 www.intertek.com/building

TEST REPORT FOR CR LAURENCE CO., INC. Report No.: j2603.01-303-44 R3 Date: 02/06/19

Version: 07/24/17 Page 6 of 14 RT-R-AMER-Test-2804

Glazing: No conclusions of any kind regarding the adequacy or inadequacy of the glass in any glazed test specimen(s) can be made.

GLASS TYPE

SPACER TYPE

INTERIOR LITE EXTERIOR LITE

GLAZING METHOD

1-1/4" IG

Aluminum Spacer -Dual Seal (A1-D)

3/16” Clear Heat Strengthened -0.060” PVB innerlayer-3/16” Clear Heat Strengthened

1/4” clear Tempered

Exterior set dry glazed with sponge gasket at interior face ( Part No. NP881), and Wedge Gasket (Part No. WH416) with exterior glass stop (Part No. SH884).

LOCATION QUANTITY DAYLIGHT OPENING GLASS BITE

millimeters inches

Fixed lite 1 1422 x 1426 56 x 56-1/8 1"

Sash 1 1346 x 638 53-25-1/8 1"

Drainage:

DRAINAGE METHOD SIZE QUANTITY LOCATION

Weep Hole w/ cover (Part No. WH276)

1-3/4" wide by 1/4" high

2 2-1/2” from jambs at exterior face of sill.

Hardware:

DESCRIPTION QUANTITY LOCATION

PC Guide, Part No. NP 942 1 Row Interior leg of frame at jambs and sill, see attached Drawings Section 10.

AmesBury – Balance, Part No. K29095

2 Midspan of Right and Left Jambs, see attached Drawings Section 10.

Latch, Part No. SH858 2 Inserted into bottom rail 16-1/2” from each end of sash, see attached Drawings Section 10.

Screen Construction: No screen was utilized.

Page 7: CR LAURENCE CO., INC. TEST REPORT...CR LAURENCE CO., INC. TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-17 TESTING ON IW 8000 SINGLE HUNG REPORT NUMBER J2603.01-303-44 R3

25800 Commercentre Drive Lake Forest, California 92630

Telephone: 949-460-9600

Facsimile: 717-764-4129 www.intertek.com/building

TEST REPORT FOR CR LAURENCE CO., INC. Report No.: j2603.01-303-44 R3 Date: 02/06/19

Version: 07/24/17 Page 7 of 14 RT-R-AMER-Test-2804

SECTION 7 TEST RESULTS The temperature during testing was 19 °C (66°F). The results are tabulated as follows:

TITLE OF TEST RESULTS ALLOWED NOTE

Operating Force, per ASTM E2068

Initiate Motion: 240 N (54 lbf) 280 N (62.95 lbf) max

Maintain Motion: 200 N (45 lbf) 200 N (44.96 lbf) max

Latches: 8.90 N (2 lbf) 100 N (22.5 lbf) max

Air Leakage, Infiltration per ASTM E283 at 75 Pa (1.57 psf)

0.2 L/s/m2 (0.03 cfm/ft2)

1.5 L/s/m2 (0.3 cfm/ft2) max. 1, 2

Air Leakage, Infiltration per ASTM E283 at 300 Pa (6.27 psf)

0.6 L/s/m2 (0.12 cfm/ft2)

1.5 L/s/m2 (0.3 cfm/ft2) max. 1, 2

Air Leakage, Exfiltration per ASTM E283 at 75 Pa (1.57 psf)

<0.1 L/s/m2 (<0.01 cfm/ft2)

1.5 L/s/m2 (0.3 cfm/ft2) max. 1, 2

Air Leakage, Exfiltration per ASTM E283 at 300 Pa (6.27 psf)

0.6 L/s/m2 (0.12 cfm/ft2)

1.5 L/s/m2 (0.3 cfm/ft2) max. 1, 2

Water Penetration, per ASTM E331 at 580 Pa (12.11 psf)

Pass No leakage

Uniform Load Deflection, per ASTM E330 Deflections taken at interlock +3840 Pa (+80.20 psf) -3840 Pa (-80.20 psf)

5.33 mm (0.21") 5.08 mm (0.20")

7.87 mm (0.31") max. 7.87 mm (0.31") max. 3, 4

Uniform Load Structural, per ASTM E330 Permanent set taken at interlock +5760 Pa (+120.30 psf) -5760 Pa (-120.30 psf)

0.25 mm (0.01") 0.25 mm (0.01")

7.62 mm (0.30") max. 7.62 mm (0.30") max. 3, 4

Forced Entry Resistance, per ASTM F588, Type: A - Grade: 10 Pass No entry

Page 8: CR LAURENCE CO., INC. TEST REPORT...CR LAURENCE CO., INC. TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-17 TESTING ON IW 8000 SINGLE HUNG REPORT NUMBER J2603.01-303-44 R3

25800 Commercentre Drive Lake Forest, California 92630

Telephone: 949-460-9600

Facsimile: 717-764-4129 www.intertek.com/building

TEST REPORT FOR CR LAURENCE CO., INC. Report No.: j2603.01-303-44 R3 Date: 02/06/19

Version: 07/24/17 Page 8 of 14 RT-R-AMER-Test-2804

TITLE OF TEST RESULTS ALLOWED NOTE

Deglazing, per ASTM E987 Operating direction, 320 N (70 lbf) Pass Meets as stated Remaining direction, 230 N (50 lbf) Pass Meets as stated

Note 1: The tested specimen meets (or exceeds) the performance levels specified in AAMA/WDMA/CSA 101/I.S.2/A440 for air leakage resistance. Note 2: Test Date 01/28/19 / Time: 9:00 AM Note 3: Loads were held for 10 seconds. Note 4: Tape and film were used to seal against air leakage during structural testing. In our opinion, the tape and film did not influence the results of the test. SECTION 8 ALTERATIONS No alterations were required.

Page 9: CR LAURENCE CO., INC. TEST REPORT...CR LAURENCE CO., INC. TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-17 TESTING ON IW 8000 SINGLE HUNG REPORT NUMBER J2603.01-303-44 R3

25800 Commercentre Drive Lake Forest, California 92630

Telephone: 949-460-9600

Facsimile: 717-764-4129 www.intertek.com/building

TEST REPORT FOR CR LAURENCE CO., INC. Report No.: j2603.01-303-44 R3 Date: 02/06/19

Version: 07/24/17 Page 9 of 14 RT-R-AMER-Test-2804

SECTION 9 LOCATION OF AIR SEAL The air seal between the test specimen and the test wall is detailed below. The seal is made of foam weatherstripping and is attached to the edge of the test specimen buck. The test specimen buck is placed against the test wall and clamped in place, compressing the weatherstripping and creating a seal.

Test Specimen Buck

Air seal between test buck and test

wall (typically foam weatherstripping)

Test Specimen

Air seal between test specimen

and test buck (typically silicone)

Test Wall

Page 10: CR LAURENCE CO., INC. TEST REPORT...CR LAURENCE CO., INC. TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-17 TESTING ON IW 8000 SINGLE HUNG REPORT NUMBER J2603.01-303-44 R3

25800 Commercentre Drive Lake Forest, California 92630

Telephone: 949-460-9600

Facsimile: 717-764-4129 www.intertek.com/building

TEST REPORT FOR CR LAURENCE CO., INC. Report No.: j2603.01-303-44 R3 Date: 02/06/19

Version: 07/24/17 Page 10 of 14 RT-R-AMER-Test-2804

SECTION 10 DRAWINGS The test specimen drawings have been reviewed by Intertek B&C and are representative of the test specimen(s) reported herein. Test specimen construction was verified by Intertek B&C per the drawings included in this report. Any deviations are documented herein or on the drawings.

Page 11: CR LAURENCE CO., INC. TEST REPORT...CR LAURENCE CO., INC. TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-17 TESTING ON IW 8000 SINGLE HUNG REPORT NUMBER J2603.01-303-44 R3

1

2

2

2

3

2

4

3

5

3

58" x 58-1/8"

55" x 26-7/8"

GLA

ZIN

GH

AR

DW

AR

E

PART DESCRIPTIONITEM PT. NO.

FR

AM

E &

S

AS

H C

OM

PO

NE

NT

S

AutoCAD SHX Text
SERIES IW8000 SGL. HUNG ELEVATION
AutoCAD SHX Text
3/8 MIN
AutoCAD SHX Text
3/8 MIN
AutoCAD SHX Text
3/8 MIN
AutoCAD SHX Text
3/8 MIN
AutoCAD SHX Text
3/8 MIN
AutoCAD SHX Text
3/8 MIN
AutoCAD SHX Text
3/8 MIN
AutoCAD SHX Text
3/8 MIN
AutoCAD SHX Text
1/4" TEMP X 1/2" AIR X (3/16" HS X .060 PVB X 3/16" HS)
AutoCAD SHX Text
INSULATED GLASS
AutoCAD SHX Text
- ALUMINUM SPACER
AutoCAD SHX Text
- DUAL GLAZED
AutoCAD SHX Text
H2
AutoCAD SHX Text
G1
AutoCAD SHX Text
S1
AutoCAD SHX Text
S2
AutoCAD SHX Text
G3
AutoCAD SHX Text
G5
AutoCAD SHX Text
G6
AutoCAD SHX Text
SH812
AutoCAD SHX Text
HEAD EXTRUSION
AutoCAD SHX Text
C1
AutoCAD SHX Text
G2
AutoCAD SHX Text
G4
AutoCAD SHX Text
H1
AutoCAD SHX Text
SH852
AutoCAD SHX Text
VENT EXTRUSION
AutoCAD SHX Text
C2
AutoCAD SHX Text
VENT EXTRUSION
AutoCAD SHX Text
C3
AutoCAD SHX Text
WH808
AutoCAD SHX Text
HEAD THERMAL ISOLATOR
AutoCAD SHX Text
C4
AutoCAD SHX Text
SH855
AutoCAD SHX Text
VENT STILE
AutoCAD SHX Text
C5
AutoCAD SHX Text
SH854
AutoCAD SHX Text
VENT HEAD EXTRUSION
AutoCAD SHX Text
C6
AutoCAD SHX Text
NP881
AutoCAD SHX Text
SPONGE GASKET-EDPM
AutoCAD SHX Text
WH416
AutoCAD SHX Text
WEDGE GASKET-EDPM
AutoCAD SHX Text
SB811
AutoCAD SHX Text
SETTING BLOCK
AutoCAD SHX Text
W-027
AutoCAD SHX Text
DUST GASKET
AutoCAD SHX Text
10X1HWSMS
AutoCAD SHX Text
#10 X 1" HEX WASHER HEAD SCREWS
AutoCAD SHX Text
10X212FHPWS
AutoCAD SHX Text
#10 X 2-1/2" FLAT HEAD PHILLIPS WOOD SCREWS
AutoCAD SHX Text
EF12C
AutoCAD SHX Text
CRL 3/8" CLOSED CELL BACKER ROD
AutoCAD SHX Text
795BL
AutoCAD SHX Text
DOW CORNING-795 SILICONE BUILDING SEALANT
AutoCAD SHX Text
SH866
AutoCAD SHX Text
SH814
AutoCAD SHX Text
JAMB EXTRUSION
AutoCAD SHX Text
WH809
AutoCAD SHX Text
ISOLATOR STRUT
AutoCAD SHX Text
SH813
AutoCAD SHX Text
SILL EXTRUSION
AutoCAD SHX Text
SH884
AutoCAD SHX Text
GLAZING STOP
AutoCAD SHX Text
WH811
AutoCAD SHX Text
ISOLATOR STRUT
AutoCAD SHX Text
C7
AutoCAD SHX Text
C8
AutoCAD SHX Text
C9
AutoCAD SHX Text
C10
AutoCAD SHX Text
C11
AutoCAD SHX Text
H4
AutoCAD SHX Text
WH3807
AutoCAD SHX Text
KEEPER
AutoCAD SHX Text
H5
AutoCAD SHX Text
WH276
AutoCAD SHX Text
WEEP HOLE COVER
AutoCAD SHX Text
NP942
AutoCAD SHX Text
PC GUIDE
AutoCAD SHX Text
G7
AutoCAD SHX Text
SB882
AutoCAD SHX Text
SETTING BLOCK
AutoCAD SHX Text
SH858
AutoCAD SHX Text
INTERLOCK
AutoCAD SHX Text
C12
AutoCAD SHX Text
H3
AutoCAD SHX Text
K29095K
AutoCAD SHX Text
AMESBURY - BALANCE HARDWARE
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
SHT
AutoCAD SHX Text
1
AutoCAD SHX Text
OF
AutoCAD SHX Text
3
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
01.02.2018
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
GDO
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
PTC464017
AutoCAD SHX Text
JOB #:
AutoCAD SHX Text
C.R.LAURENCE CO.
AutoCAD SHX Text
C
AutoCAD SHX Text
O
AutoCAD SHX Text
M
AutoCAD SHX Text
P
AutoCAD SHX Text
A
AutoCAD SHX Text
N
AutoCAD SHX Text
Y
AutoCAD SHX Text
D
AutoCAD SHX Text
E
AutoCAD SHX Text
I
AutoCAD SHX Text
F
AutoCAD SHX Text
I
AutoCAD SHX Text
T
AutoCAD SHX Text
R
AutoCAD SHX Text
E
AutoCAD SHX Text
C
AutoCAD SHX Text
ISO9000
AutoCAD SHX Text
www.crlaurence.com
AutoCAD SHX Text
2100 E. 38TH Street, Los Angeles, CA 90058
AutoCAD SHX Text
ARCHITECTURAL PRODUCTS
AutoCAD SHX Text
Glazing Contractor:
AutoCAD SHX Text
Job Name:
AutoCAD SHX Text
XX
AutoCAD SHX Text
SERIES IW8000
AutoCAD SHX Text
HURRICANE RESISTANT
AutoCAD SHX Text
SINGLE HUNG WINDOW
aaron.baker
J2603-R0
Page 12: CR LAURENCE CO., INC. TEST REPORT...CR LAURENCE CO., INC. TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-17 TESTING ON IW 8000 SINGLE HUNG REPORT NUMBER J2603.01-303-44 R3
AutoCAD SHX Text
1'-0"=1'-0"
AutoCAD SHX Text
SECTION DETAIL AT SILL
AutoCAD SHX Text
3
AutoCAD SHX Text
ARCH REF: N/A
AutoCAD SHX Text
1'-0"=1'-0"
AutoCAD SHX Text
SECTION DETAIL AT MEETING
AutoCAD SHX Text
2
AutoCAD SHX Text
ARCH REF: N/A
AutoCAD SHX Text
1'-0"=1'-0"
AutoCAD SHX Text
SECTION DETAIL AT HEAD
AutoCAD SHX Text
1
AutoCAD SHX Text
ARCH REF: N/A
AutoCAD SHX Text
EXTERIOR
AutoCAD SHX Text
EXTERIOR
AutoCAD SHX Text
INTERIOR
AutoCAD SHX Text
EXTERIOR
AutoCAD SHX Text
S2
AutoCAD SHX Text
S1
AutoCAD SHX Text
C1
AutoCAD SHX Text
H2
AutoCAD SHX Text
C5
AutoCAD SHX Text
G2
AutoCAD SHX Text
G1
AutoCAD SHX Text
G3
AutoCAD SHX Text
C9
AutoCAD SHX Text
C7
AutoCAD SHX Text
G2
AutoCAD SHX Text
G1
AutoCAD SHX Text
G3
AutoCAD SHX Text
C9
AutoCAD SHX Text
G6
AutoCAD SHX Text
G3
AutoCAD SHX Text
C9
AutoCAD SHX Text
G1
AutoCAD SHX Text
G7
AutoCAD SHX Text
G6
AutoCAD SHX Text
G2
AutoCAD SHX Text
C4
AutoCAD SHX Text
C12
AutoCAD SHX Text
C8
AutoCAD SHX Text
96
AutoCAD SHX Text
S2
AutoCAD SHX Text
S1
AutoCAD SHX Text
H5
AutoCAD SHX Text
G6
AutoCAD SHX Text
C10
AutoCAD SHX Text
G1
AutoCAD SHX Text
G3
AutoCAD SHX Text
G2
AutoCAD SHX Text
G6
AutoCAD SHX Text
G5
AutoCAD SHX Text
C9
AutoCAD SHX Text
C3
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
SHT
AutoCAD SHX Text
2
AutoCAD SHX Text
OF
AutoCAD SHX Text
3
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
01.02.2018
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
GDO
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
PTC464017
AutoCAD SHX Text
JOB #:
AutoCAD SHX Text
C.R.LAURENCE CO.
AutoCAD SHX Text
C
AutoCAD SHX Text
O
AutoCAD SHX Text
M
AutoCAD SHX Text
P
AutoCAD SHX Text
A
AutoCAD SHX Text
N
AutoCAD SHX Text
Y
AutoCAD SHX Text
D
AutoCAD SHX Text
E
AutoCAD SHX Text
I
AutoCAD SHX Text
F
AutoCAD SHX Text
I
AutoCAD SHX Text
T
AutoCAD SHX Text
R
AutoCAD SHX Text
E
AutoCAD SHX Text
C
AutoCAD SHX Text
ISO9000
AutoCAD SHX Text
www.crlaurence.com
AutoCAD SHX Text
2100 E. 38TH Street, Los Angeles, CA 90058
AutoCAD SHX Text
ARCHITECTURAL PRODUCTS
AutoCAD SHX Text
Glazing Contractor:
AutoCAD SHX Text
Job Name:
AutoCAD SHX Text
XX
AutoCAD SHX Text
SERIES IW8000
AutoCAD SHX Text
HURRICANE RESISTANT
AutoCAD SHX Text
SINGLE HUNG WINDOW
aaron.baker
J2603-R0
Page 13: CR LAURENCE CO., INC. TEST REPORT...CR LAURENCE CO., INC. TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-17 TESTING ON IW 8000 SINGLE HUNG REPORT NUMBER J2603.01-303-44 R3
AutoCAD SHX Text
1'-0"=1'-0"
AutoCAD SHX Text
SECTION DETAIL AT JAMB
AutoCAD SHX Text
4
AutoCAD SHX Text
ARCH REF: N/A
AutoCAD SHX Text
1'-0"=1'-0"
AutoCAD SHX Text
SECTION DETAIL AT JAMB
AutoCAD SHX Text
5
AutoCAD SHX Text
ARCH REF: N/A
AutoCAD SHX Text
EXTERIOR
AutoCAD SHX Text
EXTERIOR
AutoCAD SHX Text
G1
AutoCAD SHX Text
G6
AutoCAD SHX Text
C11
AutoCAD SHX Text
G2
AutoCAD SHX Text
C2
AutoCAD SHX Text
G4
AutoCAD SHX Text
G3
AutoCAD SHX Text
C9
AutoCAD SHX Text
S1
AutoCAD SHX Text
S2
AutoCAD SHX Text
H2
AutoCAD SHX Text
H2
AutoCAD SHX Text
S1
AutoCAD SHX Text
S2
AutoCAD SHX Text
G4
AutoCAD SHX Text
97
AutoCAD SHX Text
G1
AutoCAD SHX Text
G3
AutoCAD SHX Text
C9
AutoCAD SHX Text
G6
AutoCAD SHX Text
C11
AutoCAD SHX Text
C2
AutoCAD SHX Text
H3
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
SHT
AutoCAD SHX Text
3
AutoCAD SHX Text
OF
AutoCAD SHX Text
3
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
01.02.2018
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
GDO
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
AS SHOWN
AutoCAD SHX Text
PTC464017
AutoCAD SHX Text
JOB #:
AutoCAD SHX Text
C.R.LAURENCE CO.
AutoCAD SHX Text
C
AutoCAD SHX Text
O
AutoCAD SHX Text
M
AutoCAD SHX Text
P
AutoCAD SHX Text
A
AutoCAD SHX Text
N
AutoCAD SHX Text
Y
AutoCAD SHX Text
D
AutoCAD SHX Text
E
AutoCAD SHX Text
I
AutoCAD SHX Text
F
AutoCAD SHX Text
I
AutoCAD SHX Text
T
AutoCAD SHX Text
R
AutoCAD SHX Text
E
AutoCAD SHX Text
C
AutoCAD SHX Text
ISO9000
AutoCAD SHX Text
www.crlaurence.com
AutoCAD SHX Text
2100 E. 38TH Street, Los Angeles, CA 90058
AutoCAD SHX Text
ARCHITECTURAL PRODUCTS
AutoCAD SHX Text
Glazing Contractor:
AutoCAD SHX Text
Job Name:
AutoCAD SHX Text
XX
AutoCAD SHX Text
SERIES IW8000
AutoCAD SHX Text
HURRICANE RESISTANT
AutoCAD SHX Text
SINGLE HUNG WINDOW
aaron.baker
J2603-R0
Page 14: CR LAURENCE CO., INC. TEST REPORT...CR LAURENCE CO., INC. TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-17 TESTING ON IW 8000 SINGLE HUNG REPORT NUMBER J2603.01-303-44 R3

25800 Commercentre Drive Lake Forest, California 92630

Telephone: 949-460-9600

Facsimile: 717-764-4129 www.intertek.com/building

TEST REPORT FOR CR LAURENCE CO., INC. Report No.: j2603.01-303-44 R3 Date: 02/06/19

Version: 07/24/17 Page 14 of 14 RT-R-AMER-Test-2804

SECTION 11 REVISION LOG

REVISION # DATE PAGES REVISION

0 02/06/19 N/A Original Report Issue

1 03/22/19 2, 7 Addition of exfiltration air results

2 03/22/19 1-4 Revise NAFS 2011 to 2017

3 03/25/19 2, 7 Include additional testing air infiltration values.