criteria to protect telecommunication cabling during a ......icea standard p-32-382 i t (a2s) iec...
TRANSCRIPT
![Page 1: Criteria to Protect Telecommunication Cabling During a ......ICEA standard P-32-382 i t (A2s) IEC 60950-1 DC Figure I.1 (A) 18 1.0237 82.7 64787 8881 4.99 19 0.9116 69.5 40745 5588](https://reader035.vdocument.in/reader035/viewer/2022081623/614a001c12c9616cbc692146/html5/thumbnails/1.jpg)
Presented by: Mick Maytum
ICT Surge Protection Consultant ictsp-essays.info
Criteria to Protect Telecommunication Cabling During a Power Cross Event
![Page 2: Criteria to Protect Telecommunication Cabling During a ......ICEA standard P-32-382 i t (A2s) IEC 60950-1 DC Figure I.1 (A) 18 1.0237 82.7 64787 8881 4.99 19 0.9116 69.5 40745 5588](https://reader035.vdocument.in/reader035/viewer/2022081623/614a001c12c9616cbc692146/html5/thumbnails/2.jpg)
Rational for this work
© M J Maytum 2016 2
• North American standards, UL 60950-1 and GR-1089-CORE, test for power fault wiring damage.
• International standards, IEC and ITU-T, don’t test for power fault wiring damage.
• This work created ITU-T Supplement 3 (2015): ITU-T K.20, K.21, K.45 and K.82 – Additional criteria to protect telecommunication cabling during a power cross event
![Page 3: Criteria to Protect Telecommunication Cabling During a ......ICEA standard P-32-382 i t (A2s) IEC 60950-1 DC Figure I.1 (A) 18 1.0237 82.7 64787 8881 4.99 19 0.9116 69.5 40745 5588](https://reader035.vdocument.in/reader035/viewer/2022081623/614a001c12c9616cbc692146/html5/thumbnails/3.jpg)
Just a piece of wire
© M J Maytum 2016 3
i
Area = pD2/4
Length = L
R = rL/(pD2/4)
Power Loss = P = i2R
Surface Area = SA = pDL
Surface power density = P/SA = 4i2r/(p2D3)
![Page 4: Criteria to Protect Telecommunication Cabling During a ......ICEA standard P-32-382 i t (A2s) IEC 60950-1 DC Figure I.1 (A) 18 1.0237 82.7 64787 8881 4.99 19 0.9116 69.5 40745 5588](https://reader035.vdocument.in/reader035/viewer/2022081623/614a001c12c9616cbc692146/html5/thumbnails/4.jpg)
Insulation damage sets temperature limit
© M J Maytum 2016 4
![Page 5: Criteria to Protect Telecommunication Cabling During a ......ICEA standard P-32-382 i t (A2s) IEC 60950-1 DC Figure I.1 (A) 18 1.0237 82.7 64787 8881 4.99 19 0.9116 69.5 40745 5588](https://reader035.vdocument.in/reader035/viewer/2022081623/614a001c12c9616cbc692146/html5/thumbnails/5.jpg)
DC fusing current of wires in free air (Preece)
© M J Maytum 2016 5
𝐼 = 𝐴 ∗ 𝑑1.5 Where I is the wire fusing current, d is the wire diameter and A is a constant, dependent of units system and the wire material. For a copper wire of diameter of d mm, the equation becomes: 𝐼 = 80 ∗ 𝑑1.5 For example, 32 AWG has a diameter of 0.2019 mm, making 𝐼 = 80 ∗ 0.20191.5 = 7.3 A.
Preece W. H., On the Heating Effects of Electric Currents, Proc. Royal Society 36, 464 ‐ 471 (1883). No. II, 43, 280 ‐ 295 (1887). No. III, 44, 109 ‐ 111 (1888). (Retrieved 2015-09 from www.ultracad.com/articles/reprints/preece.zip)
![Page 6: Criteria to Protect Telecommunication Cabling During a ......ICEA standard P-32-382 i t (A2s) IEC 60950-1 DC Figure I.1 (A) 18 1.0237 82.7 64787 8881 4.99 19 0.9116 69.5 40745 5588](https://reader035.vdocument.in/reader035/viewer/2022081623/614a001c12c9616cbc692146/html5/thumbnails/6.jpg)
DC Insulation damage current
© M J Maytum 2016 6
• MIL-STD-975 section 3.16 Wire and Cable Derating Criteria gives maximum currents for an ambient of 70 °C and various insulator maximum temperatures (Teflon at 200 °C down to types of PVC at 105 °C).
• For cable bunches, a derating factor of (28-N)/27 should be applied, where N is the number of conductors. The derating factor is taken as a constant value once the bundle exceeds fifteen conductors.
MIL-STD-975M NASA, Standard Electrical, Electronic and Electromechnical (EEE) Parts List, 5 August 1994
![Page 7: Criteria to Protect Telecommunication Cabling During a ......ICEA standard P-32-382 i t (A2s) IEC 60950-1 DC Figure I.1 (A) 18 1.0237 82.7 64787 8881 4.99 19 0.9116 69.5 40745 5588](https://reader035.vdocument.in/reader035/viewer/2022081623/614a001c12c9616cbc692146/html5/thumbnails/7.jpg)
DC levels to avoid insulation damage
© M J Maytum 2016 7
Copper wire diameter - mm
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.5 21
De
rate
d c
urr
en
t -
A
0.4
0.50.60.70.80.9
1.5
2
3
4
56789
15
20
1
10
Single wire with 200 °C insulation
Single wire with 105 °C insulation
Single wire curve set to 1.3 A @ 0.4 mm
MIL-STD-975 derated current versus wire diameter
![Page 8: Criteria to Protect Telecommunication Cabling During a ......ICEA standard P-32-382 i t (A2s) IEC 60950-1 DC Figure I.1 (A) 18 1.0237 82.7 64787 8881 4.99 19 0.9116 69.5 40745 5588](https://reader035.vdocument.in/reader035/viewer/2022081623/614a001c12c9616cbc692146/html5/thumbnails/8.jpg)
Adiabatic (thermal capacity) conditions Onderdonk equation
© M J Maytum 2016 8
1
274**10*28.7 442 T
LOGdtI
Where I (A) is the wire current, d (mm) is the wire diameter, t (s) is the current flow time, and T is the temperature difference (°C) between the wire and ambient. For an ambient of 30 °C and the copper melting temperature of 1083 °C, the equation becomes: 442 *10*5 dtI
Adam J. & Brooks D., In Search for Preece and Onderdonk, 2015 (retrieved 2015-09 http://www.ultracad.com/articles/preece.pdf) ANSI/ICEA PUBLICATION P-32-382-2007, Short circuit characteristics of insulated cables
![Page 9: Criteria to Protect Telecommunication Cabling During a ......ICEA standard P-32-382 i t (A2s) IEC 60950-1 DC Figure I.1 (A) 18 1.0237 82.7 64787 8881 4.99 19 0.9116 69.5 40745 5588](https://reader035.vdocument.in/reader035/viewer/2022081623/614a001c12c9616cbc692146/html5/thumbnails/9.jpg)
Typical wire current-time curve
© M J Maytum 2016 9
Time
Curr
ent
ACCEPTABLE REGION
UNACCEPTABLE REGION
![Page 10: Criteria to Protect Telecommunication Cabling During a ......ICEA standard P-32-382 i t (A2s) IEC 60950-1 DC Figure I.1 (A) 18 1.0237 82.7 64787 8881 4.99 19 0.9116 69.5 40745 5588](https://reader035.vdocument.in/reader035/viewer/2022081623/614a001c12c9616cbc692146/html5/thumbnails/10.jpg)
Insulation damage limit current-time curve for 0.2 mm and 0.4 mm copper wire
© M J Maytum 2016 10
Based on the P-32-382 i2t values and the IEC 60950 equivalent DC values from Table I1 in Appendix I.
Time — s
0.01 0.1 1 10 100 1000
Cu
rre
nt
— A
1
10
100
0.2 mm diameter Cu wire
0.4 mm diameter Cu wire
![Page 11: Criteria to Protect Telecommunication Cabling During a ......ICEA standard P-32-382 i t (A2s) IEC 60950-1 DC Figure I.1 (A) 18 1.0237 82.7 64787 8881 4.99 19 0.9116 69.5 40745 5588](https://reader035.vdocument.in/reader035/viewer/2022081623/614a001c12c9616cbc692146/html5/thumbnails/11.jpg)
Parameters for 18 to 32 AWG
© M J Maytum 2016 11
Wire
AWG
Dia
(mm)
Preece
DC
Fusing
(A)
Onderdonk
transient
melting
i2t (A2s)
ICEA
standard
P-32-382
i2t (A2s)
IEC 60950-1
DC
Figure I.1
(A)
18 1.0237 82.7 64787 8881 4.99
19 0.9116 69.5 40745 5588 4.19
20 0.8118 58.4 25625 3516 3.53
21 0.7229 49.1 16116 2212 2.98
22 0.6438 41.2 10135 1392 2.51
23 0.5733 34.7 6374 876 2.13
24 0.5106 29.1 4009 551 1.81
25 0.4547 24.5 2521 347 1.54
26 0.4049 20.6 1586 218 1.32
27 0.3606 17.3 997 137 1.14
28 0.3211 14.5 627 86.3 0.98
29 0.2859 12.2 394 54.3 0.85
30 0.2546 10.3 248 34.2 0.73
31 0.2268 8.61 156 21.5 0.63
32 0.2019 7.24 98 13.5 0.53
![Page 12: Criteria to Protect Telecommunication Cabling During a ......ICEA standard P-32-382 i t (A2s) IEC 60950-1 DC Figure I.1 (A) 18 1.0237 82.7 64787 8881 4.99 19 0.9116 69.5 40745 5588](https://reader035.vdocument.in/reader035/viewer/2022081623/614a001c12c9616cbc692146/html5/thumbnails/12.jpg)
Evolution of North American wiring simulators
© M J Maytum 2016 12
• ANSI/TIA/EIA-571 and ANSI/TIA/EIA-571A
• UL 1459-1998
• UL 60950-1
• GR-1089-CORE, Issue 6
• Stub links and block cable
![Page 13: Criteria to Protect Telecommunication Cabling During a ......ICEA standard P-32-382 i t (A2s) IEC 60950-1 DC Figure I.1 (A) 18 1.0237 82.7 64787 8881 4.99 19 0.9116 69.5 40745 5588](https://reader035.vdocument.in/reader035/viewer/2022081623/614a001c12c9616cbc692146/html5/thumbnails/13.jpg)
EIA-571(A), 1992 (1999), Telecommunications User Premises Equipment Environmental Considerations – current division
© M J Maytum 2016 13
(a)
Feed
571 Branches
i2t = 400 A2se.g. 40 A for 0.25 s
i2t = 45 A2se.g. 13.3 A for 0.25 s
TerminalEquipment
TerminalEquipment
TerminalEquipment
i2t = 45 A2se.g. 13.3 A for 0.25 s
i2t = 45 A2se.g. 13.3 A for 0.25 s
(b)
571-A Branches
i2t = 100 A2se.g. 20 A for 0.25 s
i2t = 100 A2se.g. 20 A for 0.25 s
Feed
i2t = 400 A2se.g. 40 A for 0.25 s
TerminalEquipment
TerminalEquipment
![Page 14: Criteria to Protect Telecommunication Cabling During a ......ICEA standard P-32-382 i t (A2s) IEC 60950-1 DC Figure I.1 (A) 18 1.0237 82.7 64787 8881 4.99 19 0.9116 69.5 40745 5588](https://reader035.vdocument.in/reader035/viewer/2022081623/614a001c12c9616cbc692146/html5/thumbnails/14.jpg)
EIA-571(A), 1992 (1999), Telecommunications User Premises Equipment Environmental Considerations – I-t curves
© M J Maytum 2016 14
Duration – s0.01 0.1 1 10 100 1000
Cu
rre
nt
– A
rm
s
1
10
100
500-type 'phone
'phone line cord
modular jack
26 AWG riser cable
![Page 15: Criteria to Protect Telecommunication Cabling During a ......ICEA standard P-32-382 i t (A2s) IEC 60950-1 DC Figure I.1 (A) 18 1.0237 82.7 64787 8881 4.99 19 0.9116 69.5 40745 5588](https://reader035.vdocument.in/reader035/viewer/2022081623/614a001c12c9616cbc692146/html5/thumbnails/15.jpg)
UL 1459 (1995): UL standard for safety - telephone equipment
© M J Maytum 2016 15
UL 60950-1: Information Technology Equipment - Safety - Part 1: General Requirements used an MDL-2 fuse
![Page 16: Criteria to Protect Telecommunication Cabling During a ......ICEA standard P-32-382 i t (A2s) IEC 60950-1 DC Figure I.1 (A) 18 1.0237 82.7 64787 8881 4.99 19 0.9116 69.5 40745 5588](https://reader035.vdocument.in/reader035/viewer/2022081623/614a001c12c9616cbc692146/html5/thumbnails/16.jpg)
GR-1089-CORE, Issue 6, 2011, Electromagnetic Compatibility and Electrical Safety - Generic Criteria for Network Telecommunications Equipment
© M J Maytum 2016 16
TIME (Seconds)
10-2 10-1 100 101 102 103
CU
RR
EN
T (A
mp
ere
s)
2
3
4
5
6
7
20
30
40
50
60
70
100
101
102
UNACCEPTABLE REGION
ACCEPTABLE REGION
TIME (Seconds)
0.01 0.1 1 10 100 1000
CU
RR
EN
T (
Am
pe
res)
1
10
100
70
20
60
50
40
30
76
5
4
3
2
ACCEPTABLE REGION
UNACCEPTABLE REGION
ACCEPTABLE REGION LIMITS
CURRENT(A)60307
2.2
MAXIMUM TIME(s)
0.0130.065
2.5900
![Page 17: Criteria to Protect Telecommunication Cabling During a ......ICEA standard P-32-382 i t (A2s) IEC 60950-1 DC Figure I.1 (A) 18 1.0237 82.7 64787 8881 4.99 19 0.9116 69.5 40745 5588](https://reader035.vdocument.in/reader035/viewer/2022081623/614a001c12c9616cbc692146/html5/thumbnails/17.jpg)
Stub links and block cable
© M J Maytum 2016 17
![Page 18: Criteria to Protect Telecommunication Cabling During a ......ICEA standard P-32-382 i t (A2s) IEC 60950-1 DC Figure I.1 (A) 18 1.0237 82.7 64787 8881 4.99 19 0.9116 69.5 40745 5588](https://reader035.vdocument.in/reader035/viewer/2022081623/614a001c12c9616cbc692146/html5/thumbnails/18.jpg)
Closing Remarks
© M J Maytum 2016 18
• All simulations are based on an i2t limitation for adiabatic times and a fixed current value for thermal equilibrium times.
• The derivation of Norther American simulation curves are based on testing.
• Simulation curves based on insulation temperature rise are more conservative. Example, 26 AWG has a North American fixed current limit of 2.2 A, but in IEC safety standards it is 1.3 A.