crowbar effect dfig

Upload: vgaruda

Post on 02-Jun-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/11/2019 Crowbar Effect DFIG

    1/6

    Analysis of the By-Pass Resistance of an Active

    Crowbar for Doubly-Fed Induction Generator Based

    Wind Turbines under Grid Faults

    Wei Zhang, Peng Zhou, Yikang He,Senior Member, IEEECollege of Electrical Engineering, Zhejiang University, China

    Email: [email protected], [email protected], [email protected]

    Abstract-The doubly-fed induction generator (DFIG) based

    wind turbines of today are often equipped with a crowbar, which

    can be used to limit the inrush rotor current and protect the ac

    excitation converter from damage via a set of resistors that are

    connected to the rotor windings of the DFIG. When the rotor

    current becomes too high due to the severe grid voltage dips on the

    transmission line, the crowbar is activated and the rotor sideconverter is disconnected from the rotor windings at the same

    time, which makes the DFIG behave as a squirrel cage induction

    generator with increased rotor resistance. This paper analyzes the

    influence of the crowbar resistors on the electrical behavior of the

    DFIG during the grid voltage dips. Approximate expression of the

    fault stator and rotor currents are deduced from mathematical

    analysis and verified by simulation. Different crowbar by-pass

    resistances and their impacts on the maximal fault currents and

    electromagnetic torque are examined by simulations with different

    parameter sets of the DFIG. Based on the simulation results, the

    appropriate crowbar by-pass resistance can be effectively

    predicted.

    Index Terms-Crowbar, by-pass resistance, doubly fed induction

    generator, wind turbine, grid voltage dip

    I. INTRODUCTION

    With the steadily increasing of wind turbines connected to the

    grid, the interaction between large scale wind farms and the

    regional power systems are becoming more and more

    remarkable. As the penetration of wind power increases, wind

    turbines are required to romaine connected during grid fault and

    contribute to system stability, according to the recent grid codes

    [1]. Since the doubly-fed induction generator (DFIG) has been

    widely used in wind energy conversion, the low voltage ride

    through (LVRT) technology of the DFIG has been investigated

    extensively in recent times [2-12].

    When the grid voltage dips occur, the power generated by the

    DFIG can not be transmitted to the grid in time, which will

    induce large fault currents in the stator and rotor windings.

    Various improved control strategies have been proposed to deal

    This work was supported by the National High Technology Research and

    Development of China (the 863 Program Number: 2007AA05Z419) and the

    National Natural Science Foundation of China (Project Number: 50577056).

    with the inrush over-currents [2-3]. However, these methods

    basically restrain the faulty rotor current at the expense of higher

    rotor control voltage and, thus, the control capability is

    restricted seriously by the limited capacity of the rotor side

    converter (RSC). In case of severe grid voltage dips, the most

    popular and reliable way to protect the RSC is to apply a

    crowbar to short circuit the rotor windings and bypass the faultrotor current [4-9], as shown in Fig. 1.

    Once the crowbar is activated, all of the IGBTs in the RSC are

    turned off simultaneously, then the DFIG operates as an

    asynchronous generator and the controllability over the DFIG

    will get lost. At this condition, the resistance of the by-pass

    resistors is of great importance on the dynamic behavior of the

    DFIG. Several papers have discussed the crowbar resistance and

    two main requirements are summarized [10-12]. Firstly, the

    resistance should be high enough to limit the inrush rotor

    current. Secondly, it should be sufficiently low to avoid high

    voltage on the rotor terminals, which can result in the

    breaking-down of isolation materials and the charging of dc bus

    capacitor through the antiparallel diodes in the RSC. However,

    some other factors should also be taken into consideration in

    order to determine the appropriate crowbar resistance, such as

    the maximum transient torque and the decaying speed of the

    fault currents, which have not been investigated and published

    in detail yet.

    In order to determine the crowbar resistance, the transient

    behavior of the DFIG during grid faults should be analyzed

    firstly. Several papers have discussed the dynamic response of

    the DFIG to grid voltage dips. A theoretical analysis of the

    DFIG under voltage dips was proposed in [13]. But the focus of

    the analysis was only on the transient rotor voltage, and the fault

    currents were not detailedly investigated. The short circuitcurrent of the DFIG was discussed in [14], and the Laplace

    transformation was applied to calculate the fault current.

    However, the calculation was too complicate to be adopted.

    Based on the transient equivalent circuit of the DFIG, reference

    [15] proposed a simpler method to calculate the short circuit

    current. But it is still hard to calculate the amplitude of the fault

    current because of the many unknown parameters in the

    expression of the current. In [11], the approximate equations for

    the maximum short circuit currents were determined and

    compared with the simulated results. Moreover, the crowbar

    2316

    Authorized licensed use limited to: Monash University. Downloaded on November 7, 2009 at 22:19 from IEEE Xplore. Restrictions apply.

  • 8/11/2019 Crowbar Effect DFIG

    2/6

  • 8/11/2019 Crowbar Effect DFIG

    3/6

    B. Faulty Stator and Rotor Currents

    In this section, the approximate equations of the faulty stator

    and rotor currents are deduced. Some assumptions are made

    primarily in order to simplify the analysis.

    The assumptions are: firstly, the DFIG rotor is short circuited

    by the crowbar as soon as the dip occurs. Secondly, the DFIG is

    rotating at the synchronous speed s when the dip occurs.

    Thirdly, the DFIG is producing the rated active power before thedip occurs. Finally, the three phase grid voltage drops to zero, i.e.

    p=0.

    Substituting (4) and (5) into (3), the faulty stator current can

    be obtained as [11]

    ' '/ ( ) /0( ) [ ]s s rt T j t t T ss

    t e e eL

    =

    I (6)

    where L is the sum of stator and rotor leakage inductances, i.e.

    s rL L L = + , and'

    s sT L R= ,

    '

    r rT L R= . And s0 is the

    initial value of the stator flux after the dip occurs, which can be

    expressed as0 0

    ( )s s s

    t j= U .

    According to (3), since the magnetizing inductance of the

    DFIG is much bigger than the leakage inductances, the stator

    and rotor current vectors possess approximately the same

    amplitude and opposite direction. Based on (6), the maximal

    faulty stator and rotor currents can be calculated as

    max max

    2 ss r

    s

    UI I

    L = (7)

    The amplitude of the simulated fault rotor current is shown in

    Fig. 4. DFIG 1 is used in this simulation and its parameters are

    tabulated in the appendix. As the total leakage inductance

    L=0.327, the maximal rotor current calculated from (7) is about6pu, which is highly close to the simulated result.

    When the crowbar is applied, the equivalent circuit of the

    DFIG can be drawn as in Fig. 5.

    Assuming that the by-pass resistance Rcrow is much bigger

    than the stator and rotor resistance, the stator and rotor side

    equivalent impedance can be calculated as

    2

    ( )

    ( )

    m s crows

    s crow

    r crow

    s L L sL RZ s

    sL R

    Z s sL R

    +=

    +

    = +

    (8)

    According to (8), the stator and rotor transient time constants

    are derived as

    2 2' 1

    2

    1

    '

    ( )

    crow ss

    s crow

    r crow

    R L LT

    L L R

    T L R

    +=

    =

    (9)

    Substituting (8) and (9) into (6) and (6) becomes

    '

    '/

    /0 0( ) ( )s

    s r

    t Tj t t Ts s rdc

    s r

    s crow

    j et t e e

    j L R L

    =

    I I (10)

    (

    )

    rI

    pu

    ( )t s0 0.05 0.1 0.15 0.2

    0

    1

    2

    3

    4

    5

    6

    Rcrow=0

    Rcrow=0.2 pu

    Rcrow=0.5 pu

    Rcrow=1 pu

    Rcrow=2 pu

    Fig. 4. The amplitude of the faulty rotor current with different crowbar

    resistances applied

    sR sL rLsI rR

    mL

    rI

    s rsd

    dt

    crowR

    sZ rZ

    Fig. 5. Equivalent circuit of the DFIG after the crowbar applied

    AsRcrowgrows bigger, Trwill become smaller than T

    s, which

    means that the second term on the right hand side of (10)

    attenuates faster than the first one, as shown in Fig. 4 when

    Rcrow=0.2pu. Therefore, the faulty stator and rotor currents are

    primarily determined by the first term in (10), so that the

    maximal faulty current can be deduced as

    2 2

    max max ( )s r s s crowI I U L R = + (11)

    The maximal faulty rotor current obtained from simulationand (11) are shown in Fig. 6. As can be seen, the simulated

    results are highly close to the calculated ones for crowbar

    resistance above a certain value (about 0.5pu). When Rcrow is

    relatively small, the errors between the simulated and calculated

    results come from rdc0, which has been ignored in (11).

    max

    (

    )

    rI

    p

    u

    ( )crowR pu0 0.5 1 1.5 2 2.5 3

    0

    1

    2

    3

    4

    5

    6

    Calculated Results by (11)

    Rotor speed 0.7 pu

    Rotor speed 1 pu

    Rotor speed 1.3 pu+

    Simulated Results

    Calculated Results by (12)

    Fig. 6. The maximal fault rotor current versus the crowbar resistance

    2318

    Authorized licensed use limited to: Monash University. Downloaded on November 7, 2009 at 22:19 from IEEE Xplore. Restrictions apply.

  • 8/11/2019 Crowbar Effect DFIG

    4/6

    C. Factors that Affect the Faulty Currents

    In section B, some important assumptions are made so as to

    simplify the transient state analysis of the DFIG. However, these

    assumptions are not always valid for a wind turbine driven

    DFIG. So that some factors should be taken into account in order

    to make the analytical results more veracious.

    Firstly, the rotor speed r at the instant of voltage dip is

    examined. Generally, the rotor speed of a DFIG is within therange of 0.3pu around the synchronous speed. Based on the

    simulation results, it is found that the higher the rotor speed is,

    the bigger the maximal faulty currents are. The relationship

    between rand the maximal faulty currents can be expressed as

    max max 2 2( )

    srs r

    s r crow

    UI I

    L R

    =

    +

    (12)

    Fig. 6 shows the maximum fault rotor current obtained from

    simulation and calculating by using (12). As can be seen, these

    two results agree with each other very well when Rcrow is big

    enough.

    Secondly, the pre-fault operation condition of the DFIG isconsidered. During the above analysis, it is assumed that the

    DFIG produces the rated active power and zero reactive power

    before the dip occurs. When this operation condition changes,

    the dc rotor flux rdc0, rather than the forced rotor flux rf0, will

    change accordingly. However, the impact of rdc0 can be

    neglected ifRcrowis big enough, so that the pre-fault operation

    condition does not play an important role in the DFIG transient

    behavior during the dip when the crowbar is applied.

    Finally, if the voltage does not drop to zero, the case will

    become more complicated. Besides the attenuated dc flux, there

    will be non-attenuated ac component in the stator flux [16], as

    expressed in (4). As a result, the faulty currents can likewise beseparated into attenuated and non-attenuated components, and

    the amplitude of the faulty currents can be expressed as

    '/

    2 2[(1 ) cos( )]

    ( )

    st Tsrs r s

    s r crow

    UI I p e p t

    L R

    = + +

    +

    (13)

    where is the angle related to the pre-fault operation condition

    of the DFIG.

    Fig. 7 shows the amplitude of the simulated faulty rotor

    current when the rotor speed is fixed at 1.3pu. It is clearly shown

    that when the grid voltage does not drop to zero, there will be a

    non-attenuated component with the frequency of 50Hz existingin the faulty current, which is induced by the remaining grid

    voltage after the dip. As p grows bigger, the maximal faulty

    current will become smaller, which means that the largest faulty

    current will appear when a short circuit occurs right at the

    terminals of the DFIG.

    III. SELECTION OF THE CROWBAR BY-PASS RESISTANCE

    A. Appropriate Value of the Crowbar Resistance

    As mentioned in the introduction, the by-pass resistance of the

    crowbar should be high enough to limit the fault currents and

    low enough to avoid over-voltages on the rotor terminals. Based

    on these two considerations, an appropriate range of the crowbar

    resistance can be acquired.

    Firstly, the fault currents should be limited in a safe range.

    Based on the analysis of last section, the largest faulty current

    will appear when the grid voltage drops to zero and the pre-fault

    rotor speed is the highest, i.e. 1.3pu. According to (12), thefollowing expression can be described

    2 2( )

    srsafe

    s r crow

    UI

    L R