csc 326 manual
TRANSCRIPT
CSC-326 Numerical Transformer
Protection Equipment Manual
CAUTION
1) This manual applies only to CSC-326.2) Please read the manual carefully and the specification of the installation,
adjustment, testing, operation and maintenance with the device.3) To prevent damage from equipment, don’t plug-hot-plug any unit of the
equipment, touching the chips and components in printed circuit board is inhibited.4) Please use the testing instruments which comply with the relevant standards for
test and detection.5) If any abnormity occurred in the equipment or unusual maintenance needed,
promptly contact with the agents or our service hotline.6) The operation password is: 8888.
WARNING
1) During operation of electrical equipment, certain parts of this equipment are under high voltage. Severe personal injury or significant equipment damage could result from improper behavior.2) Only qualified personnel should work on this equipment or in vicinity of the equipment. These persons must be familiar with warning & service procedure described in this manual, as well as with safety regulations.3) Prerequisites to proper & safety operation of the equipment are proper storage, setup, installation, operation & maintenance of the equipment.4) In particularly cases, the general rules & safety regulations according to relating standards (e.g. IEC, National standards or other International standards) for work with high voltage equipment must be observed.
COPYRIGHT
All rights reserved.
Registered trademark
® are registered trademark of Beijing Sifang Automation Co., Ltd..
CONTENTS
1. Introduction…………………………………………………………………..…………………….1
1.1 Application…………………………………………………………….…………..………………..1
1.2 Features…………………………………………………………………….………………………...2
1.3 Functions……………………………………………………………………………………………….3
2. Design………………………………...………………………………………………………………..4
2.1 Mechanical structure………………………………………………………………………….4
2.2 Dimensions………………………………………………………..…………………………………5
3. Technical data…………………………………………………..………………………………...6
3.1 General data……………………………………………………………………..………………….6
3.2 Function data……………………………………………………………………………………….9
3.2.1 Differential protection unit data………………………………………………………9
3.2.2 Restricted earth fault protection unit data…………..……………………….9
3.2.3 Overflux protection unit data………………………………….………………………10
3.2.4 Definite-time and IDMTL overcurrent protection unit data……..10
3.2.5 Definite-time and IDMTL neutral protection unit data…….……….11
3.2.6 Neutral displacement protection unit data…………………..…………….11
3.2.7 Thermal overload protection unit data………………………..……………...12
3.2.8 Pole discordance protection unit data………………………………………….12
3.2.9 Over-load protection unit data……………….………………….……….………...13
3.2.10 Negative phase sequence imbalance detection protection unit data……………………………………………………………………………13
4. Hardware functions…………………………….…………………………….……………..14
4.1 Hardware arrangements………………………………………….………………………14
4.2 Operations of complete units………………………………….………………………14
4.3 Front panel……………………………………………………………….…………………………15
5. Protection functions…………………………………………………….…………………..16
5.1 Differential protection unit (ANSI-87T)…………………….…………………16
5.2 Restricted earth fault protection unit (ANSI-87TN)…………….……24
5.3 Overflux protection unit (ANSI-24)………………………………………………27
5.4 Definite-time and IDMTL overcurrent protection unit…………..….31
5.5 Definite-time and IDMTL neutral protection unit……………………….35
5.6 Neutral displacement protection unit………………………………….……….39
5.7 Thermal overload protection unit………………………………………………...40
5.8 Pole discordance protection unit……………………………………….………….41
5.9 Other auxiliary protection unit……………….…………………….……………...42
5.10 VT failure……………………………………………………………….……………………………44
6. Operation……………………………………………………..…………………………………….44
6.1 Safety precautions……………………………………………..…………………………….44
6.2 Dialog with the equipment……………………………….…………………………….45
6.2.1 Menu frame…………………………………………………………………………………………45
6.2.2 Display flowing………………………………………………………………………………….48
6.3 Annunciations…………………………………………….……………………………………..49
6.3.1 Event report………………………………………………………..……………………………..49
6.3.2 Alarm report……………………………………………………………………………………….51
6.3.3 Operating report……………………………………………………..…………………………53
6.4 Testing and commissioning…………………………….…………………….………..54
6.5 Putting the equipment into operation…………………….…………….………54
6.6 Configuration of functions……………………………………………………….………54
6.6.1 Configuration of functions…………………………………………….…………………54
6.6.2 Setting-equipment parameters………………………………………………………54
6.6.3 Setting-protection settings……………………………………………………………..55
6.6.4 Setting-Control word setting………………………………..…………………………62
7. Installation and commissioning……………………………….…….………………68
7.1 Unpacking & repacking…………………………………………………………………….68
7.2 Mounting………………………………………………………………..……………………………68
7.3 Check before power on……………………………………….…………………………..68
7.4 Check with power on……………………………..………………………………………..69
8. Maintenance……………………………………………………………………………………….70
8.1 Routine checks………………………………………….……………………………………….70
8.2 Replacing the back-up battery……………………….………………………………70
8.3 Fault tracing…………………………………………….………………………………………..70
8.4 Repairs………………………………………………………………………………………………..70
9. Store……………………………………………….…………………………………………………..71
10. Ordering………………………………………………………………………………………………72
10.1 Ordering data……………………………………………….…………………………………….72
10.2 Ordering data sample……………………………………………………………………….72
11. Appendix………………………………………………………………………………………………73
11.1 Terminal diagrams…………………………………………….……………………………..73
11.2 Connection Examples……………………………………………………………………….74
11.3 Digital input module…….…………………………………………………………………..77
11.4 Digital output module………...…………………………………………………………..77
CSC-326 Numerical Transformer Protection Equipment Manual
-1-
1 Introduction
1.1 Application
CSC-326 numerical transformer protection equipment applies to small, medium and
large power transformers.
Equipments included in the CSC-326 series see table1 and 2.
Table 1: CSC-326 series equipments
Type Application
CSC-326(Model 1) For two-winding transformer
CSC-326(Model 2) For three-winding transformer or auto transformer
Table 2: Main function and arrangement
TypeFunctions and arrangement
CSC-326(Model1) CSC-326(Model2)
Main protection
Instantaneous differential
protection
√ √
Inrush inhibit with 2nd harmonic
Fuzzy recognition of inrushbased on waveform
selective selective
Differential
protection
Over-flux inhibit √ √
Restricted earth fault protection for HV √ √
Over-flux (definite and inverse ) for HV √ √
Restricted earth fault protection for MV Χ √
Over-flux (definite and inverse ) for MV Χ √
Restricted earth fault protection for LV configurable Χ
Backup protection in HV (high voltage)
side
Thermal overload protection √ √
Definite and IDMTL overcurrent protection (withselective direction)
√ √
Definite and IDMTL earth fault protection (withselective direction)
√ √
Phase-to-phase distance protection Configurable configurable
Phase-to-earth distance protection Configurable configurable
Neutral displacement protection Configurable configurable
IDMTL Neutral current protection for HV √ √
Overload protection √ √
Overcurrent blocking voltage regulation
protection
√ √
Backup protection in MV(middle voltage)
side
Only for three-winding transformer
or auto transformer
Definite and IDMTL overcurrent protection(withselective direction)
Χ √
Definite and IDMTL earth fault protection(withselective direction)
Χ √
Phase-to-phase distance protection Χ Configurable
CSC-326 Numerical Transformer Protection Equipment Manual
-2-
Phase-to-earth distance protection Χ Configurable
Neutral displacement protection Χ √
IDMTL Neutral current protection for MV Χ √
Overload protection Χ √
Overcurrent blocking voltage regulation
protection
Χ √
Backup protection in LV(low voltage) side
Definite and IDMTL overcurrent protection √ √Definite and IDMTL earth fault protection (withselective direction)
√ √
Neutral displacement protection √ √
Overload protection √ √
Overload for LV winding (inside delta) configurable configurable
Backup protection for Breakers
Pole discordance protection for HV CB1 √ √
Pole discordance protection for HV CB2 √ √
Pole discordance protection for MV CB Χ √
Other auxiliary protection
Negative phase sequence imbalance detection √ √
CB status supervision √ √
Disturbance records √ √
1.2 Features
The equipment has characteristics as follows:
• The microprocessor combined 32 bits DSP with MCU, high performance hardware systemensures the parallel real-time calculation in all components of the equipment.
• Protective functions man-machine interface and also communications functions arecompletely independent in equipment. This improves the reliability and makes debugginginstallation, maintenance easier.
• Internal module is designed in such a way that a comprehensive real-time self-monitoring is performed.
• Dual A/D sampling in analog circuit, performing real time self-testing.
• The equipment provides periodical automatic testing.
• Disturbance recorder with large capacity (memory up to 4M bytes), can record more than24 records. Optional event format or wave format is provided when the records need to beprinted. Fault wave disturbance records can be easily extracted through serial port orethernet port and saved in COMTRADE format.
• 1000 event records which are date and time tagged are stored in none volatile memory
CSC-326 Numerical Transformer Protection Equipment Manual
-3-
to ensure the data or not lost when DC supply fails.
• The relay can record protection operating process, logic flow and various calculatedvalues. Our CSPC software can be used for viewing the above and also the recorded faultdata and for analyzing disturbance records via RS 232 serial port on the relay front facia.
• 2-channel high speed reliable electric Ethernet ports (optional optical fiber Ethernetports), 2-channel LonWorks ports, RS-485 port and series printing port are provided; theuser can select any of these according to the requirements. The protocol supportsIEC60870-5-103, IEC61850 or CSC-2000 of Sifang Company, for interface with substationautomatic system and protection management information system.
• Liquid crystal display with backlight is provided to display various messages such ascurrent, voltage, power, frequency, strip state, setting zones etc. The menu is easy tooperate. Four shortcut keys are provided to finish operation with one key for local operator.
1.3 Functions
The following protection functions are available in the relay: Differential protection (Including: Treble slope percent differential protection;
Instantaneous differential protection and Inrush inhibit and over-flux inhibit etc.)
Restricted Earth Fault protection for HV, MV and LV sides
Over-flux protection for HV and MV sides
Definite and IDMTL overcurrent protection for HV, MV and LV sides (with selective
direction)
Definite and IDMTL neutral current protection for HV, MV and LV sides (with selective
direction)
Neutral displacement protection for HV, MV and LV sides
Pole discordance protection for HV and MV circuit breaker
Overload protection for HV, MV and LV sides and LV winding inside delta
Thermal overload protection for HV side
Overcurrent blocking voltage regulation protection for HV and MV sides
Negative phase sequence imbalance detection for HV, MV and LV side
Circuit breaker status supervision for every side
Disturbance records.
CSC-326 Numerical Transformer Protection Equipment Manual
-4-
2 Design
2.1 Mechanical structure
The enclosure for equipment is 19 inches in width and 4U in height according to
IEC 60297-3.
The equipment is flush mounting with panel cutout and cabinet mounting.
Connection terminals to other system are on the rear.
The front panel of equipment is aluminum alloy by founding in integer and overturn
downwards. LCD, LED s and setting keys are mounted on the panel. There is a serial
interface on the panel suitable for connecting a PC.
Draw-out modules for serviceability are fixed by lock component.
The modules can be combined through the bus on the rear board. Both the
equipment and the other system can be combined through the rear interfaces.
Fig.1: CSC-326 transformer protection equipment view
CSC-326 Numerical Transformer Protection Equipment Manual
-5-
2.2 Dimensions
Dimension drawings for CSC-326 are shown in Fig 2.
Fig. 2: Flush-mounted enclosure of CSC-326 with panel cutout (dimensions in mm)
CSC-326 Numerical Transformer Protection Equipment Manual
-6-
3 Technical data
3.1 General data
3.1.1 Analog input and output
Input circuits Rated current IN
Rated voltage UN
Rated frequency fNThermal overload capability
In voltage circuit, continuousIn current circuit, continuous
≤ 1s ≤ 10sPower consumption
In voltage circuit at UN=100VIn current circuit at IN = 1A
at IN = 5A
1 or 5A63.5V (Ph-N) or 110V AC(Ph-Ph)50Hz
1.2×UN AC2×IN
80×IN
10×IN
less than 0.5VAless than 1VAless than 1VA
3.1.2 Power supply
DC voltage supply Rated auxiliary voltage Uaux
Permissible tolerance at ratedauxiliary voltagePower consumption
at energized stateat quiescent state
220V DC; 110V DC-30% to +14%
max. 50Wmax. 30W
3.1.3 Binary inputs and outputs
Binary inputs Binary inputs for 110/220V DCBinary inputs for 24V DCCurrent consumption for eachinput
1292mA~5mA
Binary outputs Potential-free trip/command+signaling contacts (Binaryoutput)Switching capacity make BreakPermissible current ,Continuous 0.5sSwitching voltageIndication contactsSwitching capacity make/breakPermissible currentSwitching voltage
32 Potential-free trip/commandcontacts +16 signaling contacts
1250VA(AC), 150W(DC)5A30A250V DC161250VA(AC), 150W(DC)5A250V DC
3.1.4 Communications interfaces
Communications
interfaces
2 RS485 and 2 Ethernetinterfaces1 serial interface
Rear boardOn the front panel
CSC-326 Numerical Transformer Protection Equipment Manual
-7-
3.1.5 Other general data
Other General data of the equipment see table 3.
Table 3: General data of the equipment
No. Item Class/rated According
to standards
Note
1 Environment conditions
1.1 Ambient temperature -10ºC ~+55ºC1.2 Extreme range of ambient
temperature-25ºC ~+70ºC
1.3 Atmospheric pressure 80~110kPa1.4 Operative ranges of
auxiliary energizingquantities
80% ~110% UN
1.5 Relative humidity ≤75%1.6 Storage temperature -10ºC~+40ºC
IEC 60255-6:1988 (GB/T14047-1993, IDT)
2 Rated parameters
2.1 Rated value of voltage 110V or 220V2.2 Rated value of current 1A or 5A2.3 Rated value of frequency 50Hz3 Burden
3.1 rated burden• AC current circuit:≤ 1VA
• AC voltage circuit::≤0.5VA• DC power supply
circuit: ≤50W
DL/T 478-2001
4 Thermal property
4.1 Thermal of short and longtime
• AC current circuit:2IN -continuously:10IN -10s;80IN -1s;
• AC voltage circuit:1.2U -
continuously;1.4UN - 10s
DL/T 478-2001
Specific ratingdefined byManufacturerin IEC 60255-6: 1988
5 Electrical insulation
5.1 Insulation resistance 100MΩ IEC 60255-5:2000(GB/T 14598.3-2006,IDT)
5.2 Insulation resistance in dryheat
1.5MΩ DL/T 478-2001 Not defined inIEC60255-5
5.3 Dielectric voltage AC 2kV (Ui≥63V)/1kV (Ui<63V)
500V isdefined forless then 63Vin IEC 60255-5
5.4 Impulse voltage 5kV (Ui≥63V) /1kV(Ui<63V)
IEC 60255-5:2000(GB/T 14598.3-2006,IDT)
6 Mechanical property
6.1 Vibration 1 class IEC60255-21-1(GB/T 11287-2000,IDT)
CSC-326 Numerical Transformer Protection Equipment Manual
-8-
6.2 Shock 1 class
6.3 Bump 1 class
IEC60255-21-2(GB/T 14537-1993,IDT)
7 EMC
7.1 Burst disturbance 3 class:• common mode2.5kV,• differential mode1.0kV
IEC 60255-22-1(GB/T 14598.13-1998,IDT)IEC 61000-4-12
Add 100kHzharsh moreIEC60255-22-1
7.2 ESD disturbance 4 class: contact -8kV IEC 60255-22-2(GB/T 14598.14-1998,IDT)IEC 61000-4-2
Harsh more 3class of IEC60255-22-2
7.3 Radiated electromagneticdisturbance
3 class: 10V/m IEC 62505-22-3(GB/T 14598.9-2002,IDT)IEC 61000-4-3
7.4 Fast burst disturbance 4 class:• communication port --2kV;• others ports--4kV
IEC60255-22-4(GB/T14598.10-1996,IDT)IEC 61000-4-4
Harsh more 3class of IEC60255-22-4
7.5 Surge disturbance 4 class:• communication port
--2kV;• others ports --4kV
IEC 60255-22-5,IEC 61000-4-5
Harsh more 3Class of IEC60255-22 -5
7.6 Conducted disturbance ofRF
3 class: 10V IEC 60255-22-6IEC 61000-4-6
7.7 Power frequency magneticfield disturbance
5 class: 100A/m IEC 61000-4-8 No defined inIEC60255-22
7.8 Pulse frequency magneticfield disturbance
5 class: 1000A/m IEC 61000-4-9 No defined inIEC60255-22
7.9 Damped oscillatorymagnetic disturbance
5 class:100A/m IEC 61000-4-10 Actual up to120A/m,Nodefinedin IEC 60255 -22
7.10 interruptions in auxiliaryenergizing quantities
50ms GB/T 8367-1987(eqv IEC60255-11)IEC 61000-4-11
7.11 Electromagnetic emissionlimits
IEC 60255-25(GB/T14598.16-2002, IDT)
8 safety
8.1 IP rating IP20 IEC 60529,GB 16836-1997
8.2 Insulation cooperation Clearance andcreepage distance
IEC 60255-5:2000GB 16836-1997
8.3 Maximum temperature ofmaterial
According with thestandard
GB 16836-1997
8.4 Flammability of insulationmaterials
V0 class IEC 60950GB 16836-1997
8.5 Protection againstElectric shock
I class IEC 60536GB 16836-1997
CSC-326 Numerical Transformer Protection Equipment Manual
-9-
9 Trip relay contact
9.1 Capacity of contact cut out 50W9.2 Current of long time 5A
3.2 Function data
3.2.1 Differential protection unit data
Table 4: Differential protection unit data
Differential protection Setting ranges
High-current stage ID>>
Differential current ID>
Restraint current IR1 Restraint current IR2 Percentage of slope 2 2nd harmonic restraint ratio 5th harmonic restraint ratioTimes
Operating time(At 2 times of set value ID>)
Operating time(At 1.5 times of set value
ID>>) Drop-off timeDrop-off ratio
Tolerances
Pickup characteristic Inrush Restraint Additional Delay TimesOthers
Percentage of slop 1 Percentage of slop 3
settable 0.5A-100A
settable 0.1A-20A
0.2Ie~1.0Ie
2Ie~10Ie
0.2~0.70.05~0.300.10~0.60
less than 30ms
less than 20ms
approx. 40msapprox. 0.7
±5% of set value or ±0.02IN
±5% of set value±1% of set value or 10ms
0.2 fixed0.7 fixed
3.2.2 Restricted earth fault protection unit data
Table 5: Restricted earth fault protection unit data
Restricted earth fault
protection
Setting ranges
Differential current I0D>
Percent restrained K0D>Times
Operating time (At 2 times of set value) Drop-off timeDrop-off ratio
Tolerance
Pickup characteristic Additional time delay
0.3Ie~1.0Ie(Ie: nominal currentof the reference side )0.2~0.7
less than 30ms
approx. 40msapprox. 0.7
±5% of set value or ±0.02IN
less than 30ms
CSC-326 Numerical Transformer Protection Equipment Manual
-10-
3.2.3 Overflux protection unit data
Table 6: Overflux protection unit data
Overflux protection
(Definite-time and
inverse-time
Overflux )
Setting Ranges
Reference voltage UN
Ratio( >N
N
ff
UU
/
/):
Time Delay T Pair of Values for Characteristic
of V/fTimes
At 1.2 times of set value Drop-off timeDrop-off ratio
Tolerance
Ratio( >N
N
ff
UU
/
/):
Time delays for definitecharacteristic
Time delays for Inversecharacteristic
40~100V
1.00~1.50
0.1s~9999.0s1.10/1.15/1.20/1.25/1.30/1.35/1.40
less than 40msapprox. 40msNot less than 0.96
±2.5% of the set value or lessthan 40ms
±3.0% of the set value or lessthan 40ms
3.2.4 Definite-time and IDMTL overcurrent protection unit data
Table 7: Definite-time and IDMTL overcurrent protection unit data
Definite-time
overcurrent
protection (with
selective direction)
Setting ranges
Current I>Time delay TThe sensitive angle of directional
elementTimes
Pickup time I> Operating time At 1.2 times ofset value Drop-off time I>Tolerance
Current pickup I> Angle of the directional element Time delaysDrop-off ratio
I>,Directional element:
Voltage thresholdAngle of the directional element
0.1×IN to 20×IN
0.1 to 20s-45°
approx. 20msless than 40ms
approx. 40ms
±3% of set value or ±0.02IN
±3°not more than 40ms
not more than 0.90
1V170°±2°
IDMTL overcurrent
protection (with
selective direction )
Setting ranges
Current I>The sensitive angle of directional
elementTimes
Pickup time I> Operating time At 1.2 times of
0.1×IN to 20×IN
-45°
approx. 20msless than 100ms
CSC-326 Numerical Transformer Protection Equipment Manual
-11-
set value Drop-off time I> Minimum operating time Maximum operating timeTolerance
Current pickup I> Angle of the directional element Time delaysDirectional element:
Voltage thresholdAngle of the directional element
approx. 40ms100ms100s
±3% of set value or ±0.02IN
±3°not more than ±5% or 0.3s
1V170°±2°
3.2.5 Definite-time and IDMTL neutral current protection unit data
Table 8: Definite-time and IDMTL neutral current protection unit data
Definite-time neutral
current protection
(with selective
direction)
Setting ranges
Current 3I0>Time delay TTimes
Pickup time 3I0> Operating time At 1.2 times ofset value Drop-off time 3I0>Tolerance
Current pickup 3I0> Angle of the directional element Time delaysDrop-off ratio
3I0>Directional element:
Zero voltage thresholdAngle of the directional element
0.1×IN to 20×IN
0.1 to 20s
approx. 20msless than 40ms
approx. 40ms
±3% of set value or ±0.02IN
±3°not more than 40ms
approx. 0.9
0.5V160°±3°
IDMTL neutral current
protection (with
selective direction)
Setting ranges
Current 3I0>Times
Pickup time 3I0> Operating time At 1.2 times ofset value Drop-off time 3I0> Minimum operating time Maximum operating timeTolerance
Current pickup 3I0> Angle of the directional element Time delaysDirectional element:
Voltage thresholdAngle of the directional element
0.1×IN to 20×IN
approx. 20msless than 100ms
approx. 40ms100ms100s
±3% of set value or ±0.02IN
±3°not more than ±5% or 0.3s
1V160°±3°
3.2.6 Neutral displacement protection unit data
Table 9: Neutral displacement protection unit data
Neutral displacement
protection(for HV,MV
and LV side of the
transformer)
Setting ranges
Voltage 3U0>
Time delay TTimes
2 to 300V(HV & MV ),2 to 100V (LV )0.1 to 20s
CSC-326 Numerical Transformer Protection Equipment Manual
-12-
Pickup time 3U0> Operating time At 1.2 times ofset value Drop-off time 3U0>Tolerance
Voltage pickup 3U0> Time delaysDrop-off ratio
3U0>
approx. 20msless than 40ms
approx. 40ms
±5% of set value or ±0.1Vnot more than 40ms
approx. 0.9
3.2.7 Thermal overload protection unit data
Table 10: Thermal overload protection unit data
Thermal overload
protection
Setting ranges
Current I>Thermal heating/cooling time
const1-H/C hot spot weighting factorTimes
Operating times are calculatedfrom IEC Cold Curve and IEC HotCurve.IEC Cold Curve
IEC Hot Curve
Tolerance
Current pickup I>Thermal trip time
0.1×IN to 10×IN
0.0s~9000.0s
0.0~1.0
−
−−=
22
22 )/1(ln
θ
τII
ICHIt
eq
Peq
±3% of set value or ±0.02IN
not more than ±5% or 0.3s
3.2.8 Pole discordance protection unit data
Table 11: Pole discordance protection unit data
Pole discordance
protection
Setting ranges
Current 3I0>Current I2>Time delay T
Times
Pickup time 3I0> ,I2>Operating time At 1.2 times of
set value Drop-off time 3I0>, I2>Tolerance
Current pickup 3I0>, I2> Time delaysDrop-off ratio
3I0>, I2>
0.1×IN to 20×IN
0.1×IN to 20×IN
0.1 to 20s
approx. 20msless than 40ms
approx. 40ms
±3% of set value or ±0.02IN
not more than 40ms
approx. 0.9
−=
22
2
lnθ
τII
It
eq
eq
CSC-326 Numerical Transformer Protection Equipment Manual
-13-
3.2.9 Over load protection unit data
Table 12: Over load protection unit data
Overload protection Setting ranges
Operating quantity Setting range Alarm time delay
Reset ratioTolerance
Current I> Time delays
Definite time, one stage.0.1-20A0.1-3600 seconds. Currentoverload is used only for alarm.Not less than 0.96
±3% of set value or ±0.02IN
approx. 40ms
3.2.10 Negative Phase Sequence Imbalance Detection protection unit data
Table 13: Negative phase sequence imbalance detection protection unit data
Negative Phase
Sequence Imbalance
Detection protection
Setting ranges
Current setting (I2>) Time delay
0.1-20A0.1-20s
CSC-326 Numerical Transformer Protection Equipment Manual
-14-
4. Hardware functions
4.1 Hardware arrangements
9TE2TE 9TE9TE 4TE 4TE 8TE 4TE4TE 4TE4TE 2TE6TE4TE 4TE
CSC-326 Numer i cal Tr ansf ormer Pr ot ect i on(Model 1)
AI 3
6SF.001.041.2
6SF.001.041.2
6SF.001.041.2
AI 1
1 2
AI 2
6SF.004.071.2
6SF.004.100.1
6SF.004.071.2
3 4 5 6
MASTER
7
DI
12
POWER
6SF.009.030
6SF.004.125.1~3
4TE4TE
6SF.004.041.3
10
DO2
6SF.004.044
9
DO1
11
6SF.004.045
DO3
Fig.3: Arrangement diagram of the CSC-326 system module (Model 2)
9TE2TE 9TE9TE 4TE 4TE 8TE 4TE4TE 4TE4TE 2TE6TE4TE 4TE
CSC-326 Numer i cal Tr ansf ormer Pr ot ect i on(Model 2)
AI 3
6SF.001.041.2
6SF.001.041.2
AI 1
1
6SF.004.071.2
6SF.004.100.1
6SF.004.071.2
2 3 4 5
MASTER
6
DI
10
POWER
6SF.009.030
6SF.004.125.1~3
4TE4TE
6SF.004.041.3
8
DO2
6SF.004.044
7
DO1
9
6SF.004.045
DO3
Fig.4: Arrangement diagram of the CSC-326 system modules (Model 1)
4.2 Operations of complete units
Analog input unit (AI)
There are 3 analog input units, which consists of voltage and current transformers. 36
analog inputs at most are available in the analog input section. The parameters of the
current and voltage transformers are as follows:
Phase current transformer: rated current 5A or 1A.
Phase voltage transformer: rated voltage 63.5V, linearity range 1V~100V.
Open delta voltage transformer: linearity range 3V~300V.
Protection CPU plug-in unit (CPU)
CPU unit is a key element; the same two units are used for redundancy. CPU plug-in
CSC-326 Numerical Transformer Protection Equipment Manual
-15-
unit is responsible for all the protection function A/D conversation software and hardware
self monitoring and diagnostics.
Communication master plug-in unit (MASTER)
The function of this unit is device master and communication. The main functions are
as follows:
Receiving and storing the fault report and event report of the CPU unit, output for
printing and communicating with the monitoring system and protection engineering
workstation by Lon network or Ethernet network
Output report to the display screen and operating the device with the keyboard of the
front panel.
The standard RS-232 port in front panel is suitable for connecting a PC. The PC based
software CSPC can be used for convenient and transparent setting, recording disturbance
and evaluation as well as commissioning. 2 RS485 and 2 Ethernet interfaces (or 2 electric
or fiber Ethernet interfaces, selective) are equipped on the rear board. It is convenient to
connect to a substation automation system or to a protection data master unit.
Digital input plug-in unit (DI)
The CPU obtains external information through the digital inputs such as blocking
commands for protective functions or position indications of circuit breakers.
Digital output plug-in unit (DO)
The CPU issues commands to external equipment via the output contacts. These
output commands are generally used to operate circuit breakers or other switching
devices. They can also be connected to other protective devices, annunciators, or external
carrier equipment for use in Pilot-Relaying schemes.4 digital input plug-in units and 39
outputs at most are provided.
Power supply plug-in unit (POW)
The CSC-326 can be supplied with power supply voltage 110V or 220V. The output of
power supply unit is +24V, ±12V, +5V.
4.3 Front panel
SI O
QUI T SET
F1 F3F2 -+F4
RESET
Fig.5: Front panel of CSC 326
CSC-326 Numerical Transformer Protection Equipment Manual
-16-
5 Protection functions
5.1 Differential protection unit(ANSI-87T)
5.1.1 Function description
Basic principle
The numerical current differential protection of the CSC-326 is a fast short-circuits
protection for transformers. The protected zone is selectively limited by the CTs at its ends.
When an external fault causes a heavy current to flow through the protected transformer,
differences in the magnetic characteristics of the current transformers CT1 and CT2 under
conditions of saturation may cause a significant current to flow through the differential
element. To prevent the protection from such erroneous operation, a stabilizing current is
brought in.
1Iɺ
2Iɺ
T
The protected object
Fig.6: Basic principle of differential protection for two ends (single phase)
Current restraint
The differential current diffI and the restraining current resI are calculated by the
following formula (5-1):
≠−=
=
∑
∑−
=
••
=
•
1
1
(max)
1
)(2
1N
i
ijres
N
i
idiff
jiIII
II
(5-1)
Where, iIɺ is the current vector of side I,
iIɺ is the vector of current of HV, MV and LV windings;
N- Total current input, suppose it is N sides;
(max)jIɺ - The maximum current vector of the N input, suppose it is side j;
1
1
( )N
i
i
I i j−
=
≠∑ - Sum of the other current input, not including side j.
diffI is derived from the fundamental frequency current and produces the tripping
effect quantity, resI counteracts this effect iIɺ is the current of every side. To clarify the
situation, three important operating conditions with ideal and matched measurement
qualities should be examined.
Transformers are subject to a number of influences that induce differential currents
CSC-326 Numerical Transformer Protection Equipment Manual
-17-
even during normal operation, such as automatic ratio compensation, automatic vector
group compensation, instantaneous differential protection, treble slope percentage
differential protection, inrush stabilization, over-flux stabilization, CT saturation recognition
and CT failure supervision etc.
Automatic Ratio compensation
Differences in the matching of CTs to the rated current of the transformer are not
uncommon. These differences result in an error that leads to a differential current.
The characteristic values of the transformer, i.e. rated apparent power, rated voltages
and primary rated CT currents, are entered in the protective device, and the rated current
of the every side of the transformer NI1 is calculated automatically according to the
following formula:
N
NN
U
SI
1
13
=
Where, NS - Rated apparent power of the transformer
1NU -Rated voltage
The secondary rated current is calculated by the following formula, for differential
protection, eI is taken as the reference current.
CTHV
Ne
n
II
1=
Rated current of the High voltage side is taken as the reference current. The digitized
currents are automatic matched the rated current of the high voltage side of the
transformer, and a correction factor KCT for MV or LV side is calculated according to the
following formula:
CTHV
CTMV
NHV
NMV
CTHV
CTMV
NMVN
NHVN
CTMVNMV
CTHVNHV
NMV
NHVCTMV
n
n
U
U
n
n
US
US
nI
nI
I
IK ⋅=⋅===
1
1
1
1
1
1
2
2
3/
3/
/
/
CTHV
CTLV
NHV
NLV
CTHV
CTLV
NLVN
NHVN
CTLVNLV
CTHVNHV
NLV
NHVCTLV
n
n
U
U
n
n
US
US
nI
nI
I
IK ⋅=⋅===
1
1
1
1
1
1
2
2
3/
3/
/
/
Where, CTMVK - Correction factor for middle voltage side
CTLVK - Correction factor for Low voltage side
NI1 - Primary rated current of the transformer ( NHVI1 for high voltage side,
NMVI1 for middle voltage side, NLVI1 for low voltage side)
NI 2 - Secondary rated current of the transformer ( NHVI2 for high voltage side,
NMVI2 for middle voltage side, NLVI2 for low voltage side)
CTn - CT ratio of the transformer ( CTHVn for high voltage side, CTMVn for
middle voltage side, CTLVn for low voltage side)
NU1 - Rated voltage of the transformer ( NHVU1 for high voltage side, NMVU1 for
middle voltage side, NLVU1 for low voltage side)
The primary and secondary rated currents for HV side are automatically calculated by
CPU according to the common parameters of the transformer, KCT for every side is
calculated too. You can look over these settings form the menu ‘Set for Test’. These
CSC-326 Numerical Transformer Protection Equipment Manual
-18-
settings are very helpful for engineer to test the differential protection.
Automatic Vector group compensation
Transformers have different vector groups, which cause a shift of the phase angles
between the primary and the secondary side. Without adequate correction, this phase shift
would cause a differential current.
Transformers often have a wye-delta connection, to allow a maximum of versatility in
the use of the CSC326. All imaginable vector group compensations have been integrated in
the software. If the setting “Vector Group Angle (VET GRP ANGLE)” and the settings for
every connection type (wye or delta, 1-delta, 0-wye) are entered to the device, the vector
group compensation is automatically completed.
The following paragraph explains the basic principle of numerical vector group
connection in an exemplary way for an Y(N)d11 transformer.
A
B
C
Side 1
A
B
C
Side 2
AIɺ
BIɺ
CIɺ
BIɺ
CIɺ
AIɺ
AIAI3
⋅
⋅=
′
′
′
C
B
A
C
B
A
I
I
I
I
I
I
ɺ
ɺ
ɺ
ɺ
ɺ
ɺ
1
1-
0
0 1-
1 0
1- 1
3
1
⋅
⋅=
′
′
′
C
B
A
C
B
A
I
I
I
I
I
I
ɺ
ɺ
ɺ
ɺ
ɺ
ɺ
1
0
0
0 0
1 0
0 1
1
Fig.7: Vector Group compensation for a Y(N)d11 Transformer (Isolated Star-point)
Deducting on side 1 the current ( BA II ɺɺ − ) results in the current AI ′ɺ , this has the same
direction as AI ′ɺ on side 2. Multiplying it with 31 matches the absolute value. The matrix
describes the conversion for all three phases. The zero sequence currents are eliminated in
this case.
CSC-326 performs automatic phase angle compensation for the entire common
transformer winding connections. This simplifies application of the relay as all CTs could be
connected in wye.
Some cautions for the setting “Vector Group Angle (VET GRP ANGLE)” are follows:
CSC-326 Numerical Transformer Protection Equipment Manual
-19-
Table 14: Instruction for Vector Group Angle setting
Setting name Values
HV WIND CONN/Y-0 D-1 0 0 0 1 1 1 0 1
MV WIND CONN/Y-0 D-1 0 1 0 1 1 0 1 0
LV WIND CONN/Y-0 D-1 1 1 0 1 0 0 0 1
VET GRP ANGLE odd odd even even odd odd -- --
Remarks Y-Y-D-
1/3/5/
7/9/11
Y-D-
D-
1/3/
5/7/
9/11
Y-Y-
Y-
0/2/
4/6/
8/10
/12
D-D-
D-
0/2/4
/6/8/
10/12
D-D-Y-
1/3/5/
7/9/11
D-Y-Y-
1/3/5/
7/9/11
invali
d
invalid
Remark: for two winding transformer, no setting “MV WIND CONN/Y-0 D-1”.
Instantaneous differential characteristics
An instantaneous (unrestrained) differential characteristics entail over-current
protection is provided for fast tripping on heavy internal faults. As soon as the differential
current rises above the threshold >>DI (setting >>DI ), a trip signal is issued regardless of
the magnitude of the restraining current. This is always the case when short-circuit current
is higher than 1/Ud*IN.
This stage can operate even when, for example, a considerable second harmonic is
present in the differential current, which is caused by current transformer saturation by a
DC component in the short-circuit current, and which could be interpreted by the inrush
inhibit function as an inrush current.
This high-current stage evaluates the fundamental component of the differential
current as well as the instantaneous values, Instantaneous value processing ensures fast
tripping even in case the fundamental component of the current is strongly reduced by
current transformer saturation. Fast trip area is shown in the Fig.8.
Treble slope percent differential protection
Percent differential protection uses a treble-slope dual break-point operating
characteristic with magnetizing inrush and over-flux inhibits integrated. Operation
characteristics of the differential protection with fault characteristic see in Fig.8.
Branch 1 represents the sensitivity threshold of the differential protection
(setting >DI ) and considers constant error currents such as magnetizing currents. Branch
2 considers current-proportional errors which may result from transformation errors of the
main CTs or the input CTs of the relay or which may be caused by mismatching or by the
influence of tap changers in transformers with voltage control. In the range of high
currents, which may give rise to CT saturation, branch 3 provides for additional
stabilization.
CSC-326 Numerical Transformer Protection Equipment Manual
-20-
IR1
ID>
Idiff
Ires
Restraint current
Differential current
Slope 3
Slope 2
Slope 1
Trip area
block area
ID>>
Fast trip area
IR2
Fig.8: Differential protection characteristics for transformers
The currents diffI and resI are compared by the differential protection with the
operating characteristic according to the following formula (5-2),
<+×+−+−≥
≤<+×+−≥
≤+≥
resRDRRRRresdiff
RresRDRRresdiff
RresDresdiff
IIIISIISIISI
IIIIISIISI
IIIISI
21112223
211112
11
)()(
)( (5-2)
Where, 1S - Slope of the branch 1, is fixed 0.2.
2S - Slope of the branch 2, (setting “DIFF SLOPE”).
3S - Slope of the branch 3, is fixed 0.7.
DI - Setting for the sensitivity threshold of the differential protection, (setting
“DIFF ID>”)
1RI - Setting for the first breakpoint restraint current, (setting “DIFF IR1”)
2RI - Setting for the second breakpoint restraint current, (setting “DIFF IR2”)
If the quantities result into a locus in the trip area, a trip signal is given. This stage
can’t operate when it is the inrush or over-flux stabilization.
Selective inrush stabilization schemes
CSC-326 provides 2 schemes to cope with the magnetizing inrush conditions. One
scheme is 2nd harmonic stabilization; the other scheme is fuzzy recognition of inrush
conditions based on the waveform. The two schemes are convenient for user to select by
the setting“2nd HAR NOT WAVE” (1- 2nd harmonic; 0-fuzzy recognition of inrush based on
waveform)
1) 2nd harmonic stabilization
In particular, high short-time magnetizing currents may be present in transformers
during power-up. Since these currents are seen only on one side of the transformer, they
act like fault current entering from one side.
The inrush currents can amount to a multiple of the rated current and are
characterized by a considerable 2nd harmonic content which is practically absent in the
case of short-circuit. If the second harmonic content exceeds a selective threshold (setting
“DIFF 2nd HAR RATIO”), tripping is blocked.
CSC-326 Numerical Transformer Protection Equipment Manual
-21-
The ratio between the 2nd harmonic and the fundamental frequency component is
used for inrush discrimination; it is formula (5-3):
φφ dhard IKI 2.2 > (5-3)
Where, 2φdI - 2nd harmonics magnitude of differential current
2.harK - Setting for 2nd harmonics ratio
φdI - Fundamental frequency component of differential current.
In “modern type” transformers, the 2nd harmonics content may not exceed the
threshold value in all three phases on switch-on. To avoid spurious tripping, the cross block
function is activated. As soon as an inrush current is detected in one phase, the other
phases of the differential protection stage are blocked.
2) Fuzzy recognition of inrush based on the waveform
Assume differential current derivative as ( )I k , sampling number per cycle is 2n, for
sequence of number:
nknkIkInkIkIkX ...2,1),)()(/()()()( =++++= (5-4)
Since the smaller )(kX is, the more fault current information the point contains.
Degree of confidence for fault current is larger for this point. Otherwise, the larger )(kX is,
the more inrush current information the point contains. Degree of confidence for inrush
current is larger for this point. Assume membership function as )]([ kXA , for nk ...2,1= , get
the fuzzy similarity coefficient N with point of one cycle:
∑=
=n
k
nkXAN
1
/)]([
(5-5)
Assume threshold K, if N>K, consider as fault current. Otherwise, consider as inrush
current.
The blocking mode is for each phase, which means that current is considered as inrush
current. Percentage differential current protection of this phase is blocked.
Over-flux stabilization
Unwanted differential currents may also be caused by transformer over-flux due to
excessive voltage.
Steady-state over-flux of the transformer is characterized by odd harmonic content.
The 3rd or 5th harmonic is suitable to provide stabilization. But, as the 3rd harmonic is
often eliminated in power transformers, the use of 5th harmonic is common.
The cross block feature with 5th harmonics works in the same way as with 2nd
harmonics. If the fifth harmonic content exceeds a selective threshold (setting “DIFF 5th
HAR RATIO”), tripping is blocked.
CT Failure supervision and CT saturation recognition
CT failure supervision can be enabled or disabled through setting “CT FAIL DET ON”
(1-on, 0-off), when CT failure, if the differential protection is in trip area, the differential
will trip.
The criteria for CT failure detection are as follows:
1) All three phases are normal, and the differential current is near to zero. When one
CSC-326 Numerical Transformer Protection Equipment Manual
-22-
phase current is decreased to less than a threshold (half of the memory current),
maybe CT failure occurs in the mutative phase.
2) Only one phase in one side has no current and all three phases in others sides are
normal and differential current is more than a threshold, maybe CT failure occurs
in the phase without current.
CT saturation recognition is integrated in differential protection. The criteria for CT
saturation are as follows:
1) 2nd and 3rd harmonic current of all phase current, if the result of 2nd and 3rd
harmonic is more than a threshold (fixed in the software), maybe CT saturation occurs.
2) Making use of the sampling differential to judge whether internal fault induce the
CT saturation.
If the CT saturation induced by external fault, the differential protection will be
blocked, whereas the protection will give trip signal.
Tripping Logic of the differential protection is shown in Fig.9.
IDIFF>> Trip
INST DIFF ON
22. dAdAIKI >
22. dBdBIKI >
22. dCdCIKI >
55. dAdAIKI >
55. dBdBIKI >
55. dCdCIKI >
CT Fail
SetdAII >
dBII >
dCII > DIFF Alarm5s
>=1
&INST DIFF A ACT
PER DIFF ON
>=1
ID>
&IDIFF> Trip
>=1
2nd HAR ON
5th HAR ON
>=1 &
&
CT FAIL DET ON
Set
Set
>=1
INST DIFF B ACT
INST DIFF C ACT
CT FAIL &
DIFF ALARM ON
&
Fig.9: Tripping logic of the differential protection
Differential current alarm
When the imbalance differential current is more than a threshold (fixed DI3.0 , DI is
CSC-326 Numerical Transformer Protection Equipment Manual
-23-
setting), alarm will be given to remind user to detect the secondary circuit and the setting
“DIFF ALARM ON” (1-on, 0-off) can be used to enable or disable this function.
In order to avoid the incorrect alarm, a step is adopted for the threshold when the
differential current is less than limits. It is shown in following formula. Timer for alarm is
fixed to 5 seconds.
==<
==<
AIAIAI
AIAIAI
nalarmDD
nalarmDD
5 if ,3.0 ,3.03.0
1 if ,1.0 ,1.03.0
.
.
5.1.2 Settings of differential protection
Table 15: Setting of Differential protection
No Setting TitleSetting
options
Default
settingComment
1 DIFF ID>> 0.5…100A 20Instantaneous Differential(ID>>) current setting
2 DIFF ID> 0.1…20A 2Percentage Differential (ID>)current setting
3 DIFF IR1 0.1…5A 2The 1st breakpoint restraintcurrent (IR1)
4 DIFF IR2 0.1…50A 2The 2nd breakpoint restraintcurrent (IR2)
5 DIFF SLOPE 0.2…0.7 0.7 the 2nd slope
6DIFF 2nd HAR
RATIO0.05…0.30 0.15 2nd harmonic(HAR) ratio
7DIFF 5th HAR
RATIO0.10…0.60 0.35 5th harmonic(HAR) ratio
8 IDIFF ON 1/0 0Instantaneous differential(IDIFF)protection ON 1-on; 0-off.
9 PDIFF ON 1/0 0Percentage differential(PDIFF)protection ON 1-on; 0-off.
10 2nd HAR NOT WAVE 1/0 0
2nd harmonic(HAR) inhibit notthe fuzzy recognition based onthe waveform(WAVE)1-2nd harmonic on;0- waveform on
11 5th HAR ON 1/0 0 5th harmonic (HAR) inhibit on1-on; 0-off.
12 DIFF ALARM ON 1/0 0Differential current(DIFF)Alarming on1-on; 0-off.
13 CT FAIL DET ON 1/0 0 CT FAIL Detection(DET) on1-on; 0-off.
Remark: above the double line for settings, below double lines for Control word.
Note: When the equipment is delivered, the differential protection function is switched to 0
(OFF), This is because this protection function must not be used before at least the vector
group angle and common parameters for every side have been correctly set. Without these
settings the equipment may show unpredictable behavior.(e.g. tripping)!
CSC-326 Numerical Transformer Protection Equipment Manual
-24-
5.2 Restricted earth fault protection unit(ANSI-87TN)
5.2.1 Function description
The restricted earth fault protection detects earth faults in transformers. It is sensitive,
and more sensitive than the classical differential protection. Typical application would be
star-point earthing transformers and auto-transformers.
A precondition is that a CT is installed in the star-point connection, i.e. between the
star-point and earth. The star-point CT and the three phase CTs define the limits of the
protected zone exactly.
Examples are illustrated in the Figures 10 to 11.
A
B
C
Side 1
A
B
C
Side 2
CSC-326 013Iɺ
2.AIɺ
2.BIɺ
2.CIɺ
Fig.10: Restricted earth fault protection on an earthed transformer winding
A
B
C
CSC-326
A
B
C
013Iɺ
2.AIɺ
2.BIɺ
2.CIɺ
3.AIɺ
3.BIɺ
3.CIɺ
Fig.11: Restricted earth fault protection on an auto-transformer
Basic principle
During healthy operation, no neutral current 013Iɺ flows through the neutral lead, the
residual current 2.2.2.023 CBA IIII ɺɺɺɺ ++= is zero (Fig.9). For auto-transformer the residual
current 2.2.2.023 CBA IIII ɺɺɺɺ ++= and 3.3.3.033 CBA IIII ɺɺɺɺ ++= are zero (Fig.11).
When an earth fault occurs in the protected zone, a neutral current 013I will flow;
depending on the neutral point earthing conditions of the power system a further neutral
CSC-326 Numerical Transformer Protection Equipment Manual
-25-
current may be recognized in the residual current path of the phase CTs. Since all currents,
which flow into the protected zone, are defined positive, the residual current from the
system will be more or less in phase with the neutral point current.
When an earth fault occurs outside the protected zone, a neutral point current 013I will
flow equally; but the residual current of the phase CTs 023I is now of equal magnitude and
in phase opposition with the neutral point current.
When a fault without earth connection occurs outside the protected zone, a residual
current may occur in the residual current path of the phase CT, which is caused by
different saturation of the phases under strong through-current conditions. This current
could simulate a fault in the protected zone. Wrong tripping must be avoided under such
condition.
The differential current 0diffI and the restraining current 0resI are calculated according
to formula (5-6),
3,3,3max
333
3.02.01.00
3.02.01.00
=
++=
IIII
IIII
res
diff
ɺɺɺ
ɺɺɺ
(5-6)
0diffI and 0resI are compared by the restricted earth fault protection with the operating
characteristic according to the following formula (5-7), Ratio compensation and CT fault
recognition etc are integrated in the protection.
>×≥
≤≥
DDresresDdiff
DDresDdiff
SIIISI
SIIII
000000
00000
/
/ (5-7)
Where, DI 0 - setting for the sensitivity threshold of restricted earth fault protection
DS0 - Slope of the branch
Diff0I
Res0I
0DI
DS0
Trip area
block area
Fig.12: Characteristic of restricted earth fault protection
Percent differential protection uses a dual-slope operating characteristic, Restraint
characteristic of restricted earth fault protection see in Fig.12.
Zero differential Ratio compensation
If 3-phase CT ratio is unequal to REF CT ratio, the difference in currents results anerror that leads to a zero differential current. So the reference side is taken and zerodifferential ratio compensation is calculated by the software.
For normal transformer, zero differential ratios are calculated according to thefollowing formula:
CSC-326 Numerical Transformer Protection Equipment Manual
-26-
HV
REFHVREFHV
n
nK = ;
MV
REFMVREFMV
n
nK = ;
LV
REFLVREFLV
n
nK =
Where, REFHVK - ratio compensation for HV NCT;
REFMVK - ratio compensation for MV NCT;
REFLVK - ratio compensation for LV NCT;
For auto-transformer, zero differential ratios are calculated according to the followingformula:
HV
MVMV
n
nK = ,
HV
REFREF
n
nK =
Where, MVK - ratio compensation for MV CT;
REFK - ratio compensation for common winding NCT;
Reference side selection is shown in Table 16.
Table 16: Reference side selection for REF functions
Type function HV REF MV REF LV REF
2 winding HV CT --- LV CT
3 winding HV CT MV CT ---
Auto-transformer HV CT --- ---
Remark: ”---“shows that the function is not configured.
REF zero differential current alarm
When the imbalance zero differential current is more than a threshold (fixed DI 03.0 , DI 0
is setting), alarm will be given to remind user to detect the secondary circuit.
In order to avoid the incorrect alarm, a step is adopted for the threshold when the
zero differentials current is less than limits. It is shown in following formula. Timer for
alarm is fixed to 5 seconds.
==<
==<
AIAIAI
AIAIAI
nalarmDD
nalarmDD
5 if ,3.0 ,3.03.0
1 if ,1.0 ,1.03.0
.
.
REF ON
& REF Trip
REF AlarmIdiff0>0.3I0D
& 5s
Fig.13: Tripping logic of the restricted earth fault protection.
Tripping Logic of the restricted earth fault protection is shown in Fig.13.
5.2.2 Settings of Restricted earth fault protection
CSC-326 Numerical Transformer Protection Equipment Manual
-27-
Table 17: Setting of Restricted earth fault protection
No Setting TitleSetting
options
Default
settingComment
1 HV REF I> 0.1…10A 2 Restricted earth fault setting
2 HV REF SLOPE 0.2…0.7 0.5Slope setting for restricted earth faultprotection
3 HV REF ON 1/0 0HV Restricted earth fault (REF) ON1-on; 0-off.
4 MV REF I> 0.1…10A 2 Restricted earth fault setting
5 MV REF SLOPE 0.2…0.7 0.5Slope setting for restricted earth faultprotection
6 MV REF ON 1/0 0MV Restricted earth fault (REF) ON1-on; 0-off.
7 LV REF I> 0.1…10A 2 Restricted earth fault setting
8 LV REF SLOPE 0.2…0.7 0.5Slope setting for restricted earth faultprotection
9 LV REF ON 1/0 0LV Restricted earth fault (REF) ON1-on; 0-off.
Remarks: 1. Different functions for HV, MV and LV are distinguished by treble lines;
2. In one function, above the double line for settings, below double lines for
Control word.
5.3 Over-flux protection unit (ANSI 24)
5.3.1 Function description
The over-flux protection is used to detect impermissible over-flux conditions which can
endanger transformers. The over-flux protection must pick up when the induction
admissible for the protected transformers is exceeded. The transformer is endangered, for
example, if the power station block is disconnected from the system for full-load, and if the
voltage regulator either does not operate or does not operate sufficiently fast to control the
associated voltage rise. Similarly, decrease in frequency, e.g. in island system, can
endanger the transformer because of increased induction.
An increase in induction above the rated values leads very quickly to saturation of the
iron core and to large eddy current losses. The over-flux protection feature servers to
measure the voltage/frequency ratio which is proportional to the B induction and puts it in
relation to the BN nominal induction. In this context, both voltage and frequency are
related to nominal values of the object to be protected transformer. The formula (5-8) is
for calculating the voltage/hertz ratio. The calculation is based on the maximum voltage of
the three phase voltages. The frequency range from 25Hz to 65Hz can be monitored in this
way.
*
*
f
U
fU
fU
B
BN
NNN
=== (5-8)
Where, N - ratio of volt/hertz
U - phase-neutral voltage
The over-flux protection feature includes two staged characteristics and one thermal
CSC-326 Numerical Transformer Protection Equipment Manual
-28-
characteristic for an approximate modeling of the heating which the over-flux may cause to
the protected transformers. The inverse characteristic can be set via seven points derived
from the manufacturer data (see Fig.14); In addition, a definite-time alarm stage and a
definite-time trip stage can be used.
u/f
N0
N1
N2
N3
N4
N5
N6
N7
T7 t ( s)T6 T5 T4 T3 T2 T1 T0
Pickup thresh
old u/f
Inverse trip stage
overflux trip stage
Fig.14: Inverse over-flux characteristic
Tripping Logic of the over-flux protection is shown in Fig.15.
AlarmFVf
U AB _/>
AlarmFVf
U BC _/>
AlarmFVf
UCA _/>
>=1
V/F Alarm ON
&
T AlarmDEF V/F Alarm
V/F Voltage
VP-P
AlarmFVf
U A _/>
AlarmFVf
UB _/>
AlarmFVf
UC _/>
>=1
&
CSC-326 Numerical Transformer Protection Equipment Manual
-29-
TripFVf
U AB _/>
TripFVf
U BC _/>
TripFVf
UCA _/>
>=1
V/F Trip ON
&
T Trip DEF V/F Trip
V/F Voltage
VP-P
>=1
TripFVf
U A _/>
TripFVf
U B _/>
TripFVf
UC _/>
&
IVR V/F PAB
>=1
INV V/F ON
&
INV V/F Trip
IVR V/F PBC
IVR V/F PCA
V/F Voltage
VP-P
>=1
IVR V/F PA
IVR V/F PB
IVR V/F PC
&
Fig.15: Tripping logic of over-flux protection
5.3.2 Settings of Over-flux protection
Table 18: Setting of over-flux protection
No Setting TitleSetting
options
Default
settingComment
1 HV Ubase 40…100 57.3 Nominal phase voltage in HV side
2 HV DEF V/F> Alarm 1.0...1.5 1.1 Alarming setting of volt/herz
3 HV T DEF V/F Alarm 0.1…9999s 10Timer setting for volt/herz alarmingstage
4 HV DEF V/F>> Trip 1.0...1.5 1.2Tripping setting of definite volt/herzstage
5 HV T DEF V/F Trip 0.1…9999s 10Timer setting for definite volt/herzstage
6 HV T1 IVR V/F=1.10 0.1…9999s 70 Timer setting for volt/herz=1.10
CSC-326 Numerical Transformer Protection Equipment Manual
-30-
7 HV T2 IVR V/F=1.15 0.1…9999s 60 Timer setting for volt/herz=1.15
8 HV T3 IVR V/F=1.20 0.1…9999s 50 Timer setting for volt/herz=1.20
9 HV T4 IVR V/F=1.25 0.1…9999s 40 Timer setting for volt/herz=1.25
10 HV T5 IVR V/F=1.30 0.1…9999s 30 Timer setting for volt/herz=1.30
11 HV T6 IVR V/F=1.35 0.1…9999s 20 Timer setting for volt/herz=1.35
12 HV T7 IVR V/F=1.40 0.1…9999s 10 Timer setting for volt/herz=1.40
13 HV V/F> ALARM ON 1/0 0HV Definite Overflux (V/F) Alarming on1-on; 0-off.
14HV DEF V/F> TRIP
ON1/0 0
HV Definite (DEF)Overflux (V/F) on1-on; 0-off.
15 HV IVR V/F> ON 1/0 0HV Inverse (IVR)Overflux (V/F) on1-on; 0-off.
16 MV Ubase 40...100 57.3 Nominal phase voltage in MV side
17 MV DEF V/F> Alarm 1.0...1.5 1.1 Alarming setting of volt/herz
18 MV T DEF V/F Alarm 0.1…9999s 10Timer setting for volt/herz alarmingstage
19 MV DEF V/F>> Trip 1.0...1.5 1.2Tripping setting of definite volt/herzstage
20 MV T DEF V/F Trip 0.1…9999s 10Timer setting for definite volt/herzstage
21MV T1 IVRV/F=1.10
0.1…9999s 70 Timer setting for volt/herz=1.10
22MV T2 IVRV/F=1.15
0.1…9999s 60 Timer setting for volt/herz=1.15
23MV T3 IVRV/F=1.20
0.1…9999s 50 Timer setting for volt/herz=1.20
24MV T4 IVRV/F=1.25
0.1…9999s 40 Timer setting for volt/herz=1.25
25MV T5 IVRV/F=1.30
0.1…9999s 30 Timer setting for volt/herz=1.30
26MV T6 IVRV/F=1.35
0.1…9999s 20 Timer setting for volt/herz=1.35
27MV T7 IVRV/F=1.40
0.1…9999s 10 Timer setting for volt/herz=1.40
28 MV V/F> ALARM ON 1/0 0MV Definite Overflux (V/F) Alarming on1-on; 0-off.
29MV DEF V/F> TRIP
ON1/0 0
MV Definite (DEF)Over-flux (V/F) on1-on; 0-off.
30 MV IVR V/F> ON 1/0 0MV Inverse (IVR)Over-flux (V/F) on1-on; 0-off.
Remarks: 1. Different functions for HV, MV and LV are distinguished by treble lines;
2. In one function, above the double line for settings, below double lines for
Control word.
CSC-326 Numerical Transformer Protection Equipment Manual
-31-
5.4 Definite and IDMTL overcurrent protection unit
5.4.1 Function description
This protection function is a backup protection for the transformer and the power
system. The protection comprises 2 stages definite overcurrent I> and 1 stage IDMTL
overcurrent. The integrated directional function can be applied to the overcurrent
protection via binary settings. This function is offered in every side of the transformer.
Definite overcurrent element
If the direction is disabled, the overcurrent element only use the maximum current of
three phase current, the operation criterion is
setcba IIII >),,max( (5-9)
Where, setI - setting for overcurrent protection.
If the direction is enabled, the overcurrent element operate for each phase, the
operation criterion is:
setII >Φ ( cba ,,=Φ ) (5-10)
IDMTL overcurrent element
IDMTL overcurrent element using the IEC or ANSI curves is provided. Both IEC curves
and ANSI curves can be expressed by one formula as follows,
+
−
×= B
I
I
AMt
P
S
1
(5-11)
Where, I - Fault current;
SI - current setting;
M - time multiplier;
A, P, B- the characteristic parameter for IDMTL curves, reference to table 14.
IEC IDMTL curves include four kind curves, and they are NI (Normal Inverse), VI
(Inverse), EI (Extreme Inverse), and LTI. ANSI curves include three kinds of curves, and
they are MI, VI and EI. The maximum timer t for IEC and ANSI is fixed to 100s.
In order to meet the IEC and ANSI curves, the function include setting M, setting A,
setting P, setting B and setting SI .
Table 19: parameters for IDMTL curves
IDMTL Curves Parameter A Parameter P Parameter B
IEC NI 0.14 0.02 0
IEC VI 13.5 1.0 0
IEC EI 80.0 2.0 0
IEC LTI 120.0 1.0 0
ANSI MI 0.0515 0.02 0.114
ANSI VI 19.61 2.0 0.491
ANSI EI 28.2 2.0 0.1217
CSC-326 Numerical Transformer Protection Equipment Manual
-32-
Directional element
The phase angle difference of input current and voltage of the directional element
is 90 , and the operation range is 85±lmφ . There are three separate directional elements.
lmφ is positive when voltage is leading to current.
850
bcU⋅
aI⋅
045−=lmϕ
850
bcU⋅
aI⋅
0135=lmϕ
a) Direction to transformer b) Direction to system
Figure 16: Phase-phase directional element characteristic
The directional element can be enabled via binary setting “DIR ON” (1-On, 0-Off), and
the forward direction can be selected via binary setting “DIR TO SYS” (1-direction to
system, 0-direction to transformer). In order to avoid the voltage dead zone for three-
phase fault at relay location, the memory voltage is used for directional element. Every
definite stage and IDMTL has separate binary setting to select whether direction is put on
and the direction of the directional element. The directional element voltage of every side
use the voltage on itself side.
Note: lmφ =-45º represents the voltage is lagging by current.
The logic for Definite and IDMTL overcurrent protection is shown in Fig. 17.
OC Trip
O/C ON
&I>Iset
T
O/C DIR ON
VT failure &
DIR Positive
IDMTL OC Trip
IDMTL O/C ON
&Inverse Curve>
T
IDMTL DIR ON
VT failure &
DIR Positive
Fig.17: Tripping logic for definite and IDMTL overcurrent protection.
CSC-326 Numerical Transformer Protection Equipment Manual
-33-
5.4.2 Settings of definite and IDMTL overcurrent protection
Table 20: Setting of definite and IDMTL overcurrent protection
No Setting TitleSetting
options
Default
settingComment
1 HV OC I1> 0.1…100 100Overcurrent (OC) setting for 1st stage( I1> )
2 T HV OC I1> 0.1…20s 20 Timer setting for 1st stage OC
3 HV OC I2> 0.1…100 100Overcurrent (OC) setting for 2nd stage( I2> )
4 T HV OC I2> 0.1…20s 20 Timer setting for 2nd stage OC
5IDMTL HV OC
TimeMult0.025...2.0 1
6IDMTL HV OC
CONST A0.0…130.0 20
7IDMTL HV OC
POWER P0.02...2.0 2
8IDMTL HV OC PARA
B0.0…1.0 0
9 IDMTL HV OC I> 0.1…100A 5
Ref to IEC and ANSI Curves
10 HV OC_1 ON 1/0 01st stage(_1) Overcurrent (OC) in HVside on
11 HV OC_1 DIR ON 1/0 0Direction (DIR) detection of 1st
Stage(_1) of Overcurrent (OC) in HVside
12HV OC_1 DIR TO
SYS1/0 0
Direction (DIR) of 1st stage (_1)Overcurrent (OC)to system nottransformer itself in HV side
13 HV OC_2 ON 1/0 02nd stage(_2) Overcurrent (OC) in HVside on
14 HV OC_2 DIR ON 1/0 0Direction (DIR) detection of 2nd
Stage(_2) of Overcurrent(OC) in HVside
15HV OC_2 DIR TO
SYS1/0 0
Direction (DIR) of 2nd stage (_2)Overcurrent (OC) to system nottransformer itself in HV side
16 HV IDMTL OC ON 1/0 0 IDMTL Overcurrent (OC) in HV side on
17HV IDMTL OC DIR
ON1/0 0
Direction (DIR) detection of IDMTLOvercurrent (OC) in HV side
18HV IDMTL OC DIR
TO SYS1/0 0
Direction (DIR) of IDMTL Overcurrent(OC)to system not transformer itselfin HV side
19 MV OC I1> 0.1…100 100Overcurrent (OC) setting for 1st stage( I1> )
20 T MV OC I1> 0.1…20s 20 Timer setting for 1st stage OC
21 MV OC I2> 0.1…100 100Overcurrent (OC) setting for 2nd stage( I2> )
22 T MV OC I2> 0.1…20s 20 Timer setting for 2nd stage OC
23IDMTL MV OC
TimeMult0.025…2.0 1 Ref to IEC and ANSI Curves
CSC-326 Numerical Transformer Protection Equipment Manual
-34-
24IDMTL MV OC
CONST A0.0…130.0 20
25IDMTL MV OC
POWER P0.02…2.0 2
26IDMTL MV OC PARA
B0.0…1.0 0
27 IDMTL MV OC I> 0.1…100A 5
28 MV OC_1 ON 1/0 01st stage(_1) Overcurrent (OC) withtime delay T in MV side on
29 MV OC_1 DIR ON 1/0 0Direction (DIR) detection of 1st
Stage(_1) of Overcurrent(OC) in MVside
30MV OC_1 DIR TO
SYS1/0 0
direction (DIR) of 1st stage (_1)Overcurrent (OC)to system nottransformer itself in MV side
31 MV OC_2 ON 1/0 02nd stage(_2) Overcurrent (OC) withtime delay T in MV side on
32 MV OC_2 DIR ON 1/0 0Direction (DIR) detection of 2nd
Stage(_2) of Overcurrent(OC) in MVside
33MV OC_2 DIR TO
SYS1/0 0
direction (DIR) of 2nd stage (_2)Overcurrent (OC)to system nottransformer itself in MV side
34 MV IDMTL OC ON 1/0 0 IDMTL Overcurrent (OC) in MV side on
35MV IDMTL OC DIR
ON1/0 0
Direction (DIR) detection of IDMTLOvercurrent(OC) in MV side
36MV IDMTL OC DIR
TO SYS1/0 0
Direction (DIR) of IDMTL Overcurrent(OC)to system not transformer itselfin MV side
37 LV OC I1> 0.1…100 100Overcurrent (OC) setting for 1st stage(I1>)
38 T LV OC I1> 0.1…20s 20 Timer setting for 1st stage OC
39 LV OC I2> 0.1…100 100Overcurrent (OC) setting for 2nd stage(I2>)
40 T LV OC I2> 0.1…20s 20 Timer setting for 2nd stage OC
41IDMTL LV OC
TimeMult0.025...2.0 1
42IDMTL LV OC
CONST A0.0…130.0 20
43IDMTL LV OC
POWER P0.02…2.0 2
44IDMTL LV OC PARA
B0.0…1.0 0
45 IDMTL LV OC I 0.1…100A 5
Ref to IEC and ANSI Curves
46 LV OC_1 ON 1/0 01st stage(_1) of Overcurrent (OC) in LVside on
47 LV OC_1 DIR ON 1/0 0Direction (DIR) detection of 1st
Stage(_1) of Overcurrent(OC) in LVside
CSC-326 Numerical Transformer Protection Equipment Manual
-35-
48LV OC_1 DIR TO
SYS1/0 0
Direction (DIR) of 1st stage (_1)Overcurrent (OC)to system nottransformer itself in LV side
49 LV OC_2 ON 1/0 02nd stage(_2) of Overcurrent (OC) in LVside on
50 LV OC_2 DIR ON 1/0 0Direction (DIR) detection of 2nd stage(_2) of Overcurrent(OC) in LV side
51LV OC_2 DIR TO
SYS1/0 0
Direction (DIR) of 2nd stage (_2)Overcurrent (OC)to system nottransformer itself in LV side
52 LV IDMTL OC ON 1/0 0 IDMTL Overcurrent (OC) in LV side on
53LV IDMTL OC DIR
ON1/0 0
Direction (DIR) detection of IDMTLOvercurrent(OC) in LV side
54LV IDMTL OC DIR
TO SYS1/0 0
Direction (DIR) of IDMTL Overcurrent(OC)to system not transformer itselfin LV side
5.5 Definite and IDMTL Neutral current protection unit
5.5.1 Function description
This protection function is a backup protection for the transformer and the power
system. The protection comprises 2 stages definite residual current 3I0> and 1 stage
IDMTL neutral current. The integrated directional function can be applied to the neutral
current protection via binary settings.
This protection is only using as backup protection for transformer and adjacent
element for ground fault in directly earthed system. This function is offered in every side of
the transformer.
Zero sequence overcurrent element
Zero sequence overcurrent element calculated by three phase current for every side.
setII 00 33 > (5-12)
Where, setI 03 - setting of zero sequence overcurrent.
IDMTL neutral current element
IDMTL neutral current curves are same to IDMTL overcurrent curves, it is reference to
IDMTL overcurrent.
Zero sequence directional element
Voltage and current for zero sequence directional elements all are calculated by three
phase quantity. The maximum sensitive angle lmφ is -100°. The operation range is 80±lmφ .
The forward direction can be selected with control word as pointing to the transformer or
system.
CSC-326 Numerical Transformer Protection Equipment Manual
-36-
800
03⋅
U
03⋅
I
080=lmϕ
800
03⋅
U
03⋅
I
0100−=lmϕ
a) Direction to transformer b) Direction to system
Figure 18: Characteristic of zero sequence direction elements
The logic for Definite and IDMTL overcurrent protection is shown in Fig.19.
NC Trip
N/C ON
&3I0>3I0set
T
N/C DIR ON
VT failure &
DIR Positive
IDMTL NC Trip
IDMTL N/C ON
&Inverse Curve>
T
IDMTL DIR ON
VT failure &
DIR Positive
Fig.19: Tripping logic for definite and IDMTL neutral current protection
5.5.2 Settings of definite and IDMTL neutral current protection
Table 21: Setting of definite and IDMTL neutral current protection
No Setting TitleSetting
options
Default
settingComment
1 HV NC I01> 0.1…100 100Neutral Current (NC) setting for 1st
stage ( I01> )
2 T HV NC I01> 0.1…20s 20 Timer setting for 1st stage NOC
3 HV NC I02> 0.1…100 100Neutral Current (NC) setting for 2nd
stage ( I02> )
4 T HV NC I02> 0.1…20s 20 Timer setting for 2nd stage NOC
5IDMTL HV NC
TimeMult0.025..2.0 1
6IDMTL HV NC CONST
A0.0…130.0 20
7IDMTL HV NC POWER
P0.02...2.0 2
8 IDMTL HV NC PARA B 0.0…1.0 0
Ref to IEC and ANSI Curves
CSC-326 Numerical Transformer Protection Equipment Manual
-37-
9 IDMTL HV NC I0> 0.1…100A 5
10 HV NC_1 ON 1/0 01st stage(_1) Neutral Current (NC) inHV side on
11 HV NC_2 ON 1/0 02nd stage(_2) Neutral Current (NC) inHV side on
12 HV NC_1 DIR ON 1/0 0Direction(DIR) detection of 1st
stage(_1) Neutral Current (NC) inhigh voltage (HV)side on
13 HV NC_1 DIR TO SYS 1/0 0Direction (DIR) of 1st stage (_1)Neutral Current (NOC)to system nottransformer itself in HV side
14 HV NC_2 DIR ON 1/0 0Direction(DIR) detection of 2nd stage(_2) Neutral Current (NC) in highvoltage (HV)side on
15 HV NC_2 DIR TO SYS 1/0 0Direction (DIR) of 2nd stage (_2)Neutral Current (NC)to system nottransformer itself in HV side
16 HV IDMTL NC ON 1/0 0IDMTL Neutral Current (NC) in HVside on
17 HV IDMTL NC DIR ON 1/0 0Direction(DIR) detection of IDMTLNeutral Current (NC) in high voltage(HV)side on
18HV IDMTL NC DIR TO
SYS1/0 0
Direction (DIR) of IDMTL NeutralCurrent (NC)to system nottransformer itself in HV side
19 MV NC I01> 0.1…100 100Neutral Current (NC) setting for 1st
stage (I01>)
20 T MV NC I01> 0.1…20s 20 Timer setting for 1st stage NOC
21 MV NC I02> 0.1…100 100Neutral Current (NC) setting for 2nd
stage (I02>)
22 T MV NC I02> 0.1…20s 20 Timer setting for 2nd stage NOC
23IDMTL MV NC
TimeMult0.025...2.0 1
24IDMTL MV NC CONST
A0.0...130.0 20
25IDMTL MV NC POWER
P0.02…2.0 2
26 IDMTL MV NC PARA B 0.0…1.0 0
27 IDMTL MV NC I0> 0.1...100A 5
Ref to IEC and ANSI Curves
28 MV NC_1 ON 1/0 01st stage(_1) Neutral Current (NC) inMV side on
29 MV NC_2 ON 1/0 02nd stage(_2) Neutral Current (NC) inMV side on
30 MV NC_1 DIR ON 1/0 0Direction(DIR) detection of 1st
stage(_1) Neutral Current (NC) inMV side on
31 MV NC_1 DIR TO SYS 1/0 0Direction (DIR) of 1st stage (_1)Neutral Current (NOC)to system nottransformer itself in MV side
CSC-326 Numerical Transformer Protection Equipment Manual
-38-
32 MV NC_2 DIR ON 1/0 0Direction(DIR) detection of 2nd
stage(_2) Neutral Current (NC) inMV side on
33 MV NC_2 DIR TO SYS 1/0 0Direction (DIR) of 2nd stage (_2)Neutral Current (NC)to system nottransformer itself in MV side
34 MV IDMTL NC ON 1/0 0IDMTL Neutral Current (NC) in MVside on
35 MV IDMTL NC DIR ON 1/0 0Direction(DIR) detection of IDMTLNeutral Current (NC) in high voltage(MV)side on
36MV IDMTL NC DIR TO
SYS1/0 0
Direction (DIR) of IDMTL NeutralCurrent (NC)to system nottransformer itself in MV side
37 LV NC I01> 0.1…100.0 100Neutral Current (NC) setting for 1st
stage (I01>)
38 T LV NC I01> 0.1…20s 20 Timer setting for 1st stage NOC
39 LV NC I02> 0.1…100 100Neutral Current (NC) setting for 2nd
stage (I02>)
40 T LV NC I02> 0.1…20s 20 Timer setting for 2nd stage NOC
41 IDMTL LV NC TimeMult 0.025...2.0 1
42 IDMTL LV NC CONST A 0…130 20
43 IDMTL LV NC POWER P 0.02...2.0 2
44 IDMTL LV NC PARA B 0.0…1.0 0
45 IDMTL LV NC I0> 0.1…100A 5
Ref to IEC and ANSI Curves
46 LV NC_1 ON 1/0 01st stage(_1) Neutral Current (NC) inLV side on
47 LV NC_1 DIR ON 1/0 0Direction(DIR) detection of 1st
stage(_1) Neutral Current (NC) inhigh voltage (LV)side on
48 LV NC_1 DIR TO SYS 1/0 0Direction (DIR) of 1st stage (_1)Neutral Current (NOC)to system nottransformer itself in LV side
49 LV NC_2 ON 1/0 02nd stage(_2) Neutral Current (NC) inLV side on
50 LV NC_2 DIR ON 1/0 0Direction(DIR) detection of 2nd
stage(_2) Neutral Current (NC) inhigh voltage (LV)side on
51 LV NC_2 DIR TO SYS 1/0 0Direction (DIR) of 2nd stage (_2)Neutral Current (NC)to system nottransformer itself in LV side
52 LV IDMTL NC ON 1/0 0IDMTL Neutral Current (NC) in LVside on
53 LV IDMTL NC DIR ON 1/0 0Direction(DIR) detection of IDMTLNeutral Current (NC) in high voltage(LV)side on
54LV IDMTL NC DIR TO
SYS1/0 0
Direction (DIR) of IDMTL NeutralCurrent (NC)to system nottransformer itself in LV side
CSC-326 Numerical Transformer Protection Equipment Manual
-39-
5.6 Neutral displacement protection unit
5.6.1 Function description
This protection is often used for the transformer which the neutral is not earthed. The
protection comprises 2 stage 3U0>, 1st stage for alarming, 2nd stage for tripping. This
function is offered in every side of the transformer.
For HV and MV side, neutral displacement protection adopts the open delta voltage.
For LV side, neutral displacement protection adopts the zero sequence voltage calculated
by three-phase voltage.
3U0 Alarm
3U0> Alarm ON
&3U0> T1
3U0 Trip
3U0> Trip ON
&3U0> T2
Fig.20: Tripping logic for neutral displacement protection
The logic for neutral displacement protection is shown in Fig. 20.
5.6.2 Settings of neutral displacement protection
Table 22: Setting of neutral displacement protection
No Setting TitleSetting
options
Default
settingComment
1 HV 3U0> ALARM 2.0…300.0 300Neutral voltage setting for alarmingstage
2 T HV 3U0> ALARM 0.1…20s 20 Timer setting for neutral voltage
3 HV 3U0> TRIP 2.0…300.0 300Neutral voltage setting for trippingstage
4 T HV 3U0> TRIP 0.1…20s 20 Timer setting for neutral voltage
5 HV 3U0> ALARM ON 1/0 0Neutral displacement (3U0) alarm inHV side on
6 HV 3U0> TRIP ON 1/0 0Neutral displacement (3U0) trip in HVside on
7 MV 3U0> ALARM 2.0…300.0 300Neutral voltage setting for alarmingstage
8 T MV 3U0> ALARM 0.1…20s 20 Timer setting for neutral voltage
9 MV 3U0> TRIP 2.0…300.0 300Neutral voltage setting for trippingstage
10 T MV 3U0> TRIP 0.1…20s 20 Timer setting for neutral voltage
11 MV 3U0> ALARM ON 1/0 0Neutral displacement (3U0) alarm inMV side on
12 MV 3U0> TRIP ON 1/0 0Neutral displacement (3U0) trip in MVside on
13 LV 3U0> ALARM 2.0…300.0 300Neutral voltage setting for alarmingstage
14 T LV 3U0> ALARM 0.1…20s 20 Timer setting for neutral voltage
CSC-326 Numerical Transformer Protection Equipment Manual
-40-
15 LV 3U0> TRIP 2.0…300.0 300Neutral voltage setting for trippingstage
16 T LV 3U0> TRIP 0.1…20s 20 Timer setting for neutral voltage
17 LV 3U0> ALARM ON 1/0 0Neutral displacement (3U0) alarm in LVside on
18 LV 3U0> TRIP ON 1/0 0Neutral displacement (3U0) trip in LVside on
5.7 Thermal overload protection unit
5.7.1 Function description
Transformer design has changed, with less and less metal being used per MVA of
transformed power. This has reduced the withstand time a transformer can be allowed to
be run in an overloaded state. It is becoming more important to provide an additional
thermal protection to supplement the Winding Temperature device.
Thermal overload protection characteristic is provided as THERMAL IEC 60255-8. There
are IEC cold and IEC hot curves.
The cold curve is:
−=
22
2
ln
θ
τII
It
eq
eq (5-13)
The hot curve is:
−
−−=
22
22 )/1(ln
θ
τII
ICHIt
eq
Peq (5-14)
Where, t - thermal trip time;
eqI - equivalent thermal current, ( )CBAeq IIII ++=3
1 ;
τ - thermal time constant;
θI - rms thermal current setting;
( CH /1− ) - hot spot weighting factor;
PI - prior current takes into account cyclic loading.
When the thermal overload is accumulated to 80% of the total thermal ability, the
alarm report “TEM Alarm” will be given.
5.7.2 Settings of thermal overload protection
Table 23: Setting of thermal overload protection
No Setting TitleSetting
options
Default
settingComment
1 HV TEM OLD I> 0.1...25.0 2 Setting for thermal overload
2HV TEM OLD Time
Const0…9000s 10
Time constant for thermal overloadprotection
3HV Weight Factor
H/C0.0...1.0 0 Hot cool weight factor H/C
4 HV TEM OLD ON 1/0 0 Thermal overload in HV side on
CSC-326 Numerical Transformer Protection Equipment Manual
-41-
5.8 Pole discordance protection unit
5.8.1 Function description
Pole discordance protection evaluates current components and the circuit-breaker
auxiliary contact. The contact for circuit breaker pole discordance is shown in Fig.21.
(NO_PhA means normal open contact for phase A/B/C; NC_PhA means normal close
contact for phase A, the contact definition for phase B and C are same as phase A)
NO_PhA
NO_PhB
NO_PhC
NC_PhA
NC_PhB
NC_PhC To DI PD
Fig 21. Contact connection for circuit breaker pole discordance
The components include negative sequence current I2> and zero sequence current
3I0>. It can be started by external via digital input.
Pole discordance protection is provided for HV CB1, HV CB2 and MV CB.
The logic for pole discordance protection is shown in Fig. 22.
CB PD TripCB PD DI
&
CB PD ON
1≥
CUR ELE ON
&
1≥
I2>I2set
3I0>I0set
T
Fig.22: Tripping logic for circuit breaker pole discordance protection
If digital input for CB PD is existing, all three phase current are larger than a threshold(fixed in the software, for 1A CT, the threshold is 0.06A; for 5A CT, the threshold is 0.3A.),and the delay time is fixed 10 seconds. “DI PD Alarm” report will be given to remind userto detect auxiliary contact and CT circuit.
The logic for pole discordance contact alarm is shown in Fig.23.
DI PD Alarm
CB PD DI
&
CB PD ON
10s
IB>Iset
IA>Iset
IC>Iset
Fig.23: Digital Input Alarm logic for circuit breaker pole discordance protection
5.8.2 Settings of pole discordance protection
Table 24: Setting of pole discordance protection
CSC-326 Numerical Transformer Protection Equipment Manual
-42-
N
oSetting Title
Setting
options
Default
settingComment
1 HV CB PD 3I0> 0.1...100 100Zero sequence current setting of Circuit breakerpole discordance
2 HV CB PD I2> 0.1…100 100negative sequence current setting of Circuitbreaker pole discordance
3 T HV CB PD 0.1…20s 20 Timer setting for circuit breaker pole discordance
4 HV CB PD ON 1/0 0Circuit break(CB) pole discordance (PD) in HVside on
5HV CB PD CUR
ELE ON1/0 0
Circuit break(CB) pole discordance (PD)withCurrent (CUR)element(ELE) in HV side on
6 HV CB2 PD 3I0> 0.1…100 100Zero sequence current setting of Circuit breakerpole discordance
7 HV CB2 PD I2> 0.1…100 100negative sequence current setting of Circuitbreaker pole discordance
8 T HV CB2 PD 0.1…20s 20 Timer setting for circuit breaker pole discordance
9 HV CB2 PD ON 1/0 0Circuit break(CB) pole discordance (PD) in HVside 2 on
10HV CB2 PD CUR
ELE ON1/0 0
Circuit break(CB) pole discordance (PD)withCurrent (CUR)element(ELE) in HV side 2 on
11 MV CB PD 3I0> 0.1…100 100Zero sequence current setting of Circuit breakerpole discordance
12 MV CB PD I2> 0.1…100 100negative sequence current setting of Circuitbreaker pole discordance
13 T MV CB PD 0.1…20s 20 Timer setting for circuit breaker pole discordance
14 MV CB PD ON 1/0 0Circuit break(CB) pole discordance (PD) in MVside on
15MV CB PD CUR
ELE ON1/0 0
Circuit break(CB) pole discordance (PD)withCurrent (CUR)element(ELE) in MV side on
5.9 Other auxiliary protection unit
5.9.1 Function description
Other auxiliary protections are provided. For example, overload protection, overcurrent
blocking voltage regulation protection etc. The overload protection is to protect all sides of
windings of transformer continuous overload currents. The protection only comprises a
definite time alarm stage. Overcurrent blocking voltage regulation protection is to judge
whether the voltage tap changer can be regulated or not, if the current more than the
setting “BLK VOL REGU I>”, the contact is given to block the tap changer regulation
device. Overload and overcurrent blocking voltage regulation protection use the maximum
current element of three phases.
The logic for overload and the overcurrent blocking voltage regulation protection is
shown in Fig.24.
CSC-326 Numerical Transformer Protection Equipment Manual
-43-
Load AlarmOLD ON&
Max(IA,IB,IC)>Iset
T
BLK VOL REGUBLK VOL REGU ON&
Max(IA,IB,IC)>Iset
T
Fig.24: The logic for overload and overcurrent blocking voltage regulation protection
Negative imbalance detection function is for detect negative current for every side.
The setting “HV1 I2 DET ON ”,” HV2 I2 DET ON”, “MV I2 DET ON” and ” LV I2 DET ON” are
provided to enable or disable the negative current detection function of every side. One
delay time setting is common for every side. The logic is shown in Fig.25.
I2 AlarmI2 DET ON&
I2>I2.set
T
Fig.25: The logic for negative imbalance detection protection
External digital input operated record disturbance functions are also provided.
5.9.2 Settings of other auxiliary protection
Table 25: Setting of pole discordance protection
No Setting TitleSetting
options
Default
settingComment
1 HV LOAD I> 0.1…100.0 100 Overcurrent Setting of overload
2 T HV LOAD I> 0.1…3600s 20 Timer setting for overload
3 HV OLD ON 1/0 0 Overload (LOAD)in HV side on
4HV BLK VOL
REG I>0.1…100.0 100
Overcurrent Setting of blocking voltageregulation
5T HV BLK VOL
REGU I>0.1…3600s 20 Timer setting for blocking voltage regulation
6HV BLK VOL
REGU ON1/0 0
Blocking(BLK) voltage(VOL) regulation (REGU)inHV side on
7 MV LOAD I> 0.1...100.0 100 Overcurrent Setting of overload
8 T MV LOAD I> 0.1…3600s 20 Timer setting for overload
9 MV OLD ON 1/0 0 Overload (LOAD)in MV side on
10MV BLK VOL
REGU I>0.1...100.0 100
Overcurrent Setting of blocking voltageregulation
11T MV BLK VOL
REGU I>0.1…3600s 20 Timer setting for blocking voltage regulation
12MV BLK VOL
REGU ON1/0 0
Blocking(BLK) voltage(VOL) regulation (REGU)inMV side on
13 LV LOAD I> 0.1...100.0 100 Overcurrent Setting of overload
14 T LV LOAD I> 0.1…3600s 20 Timer setting for overload
15 LV OLD ON 1/0 0 Overload (LOAD)in LV side on
CSC-326 Numerical Transformer Protection Equipment Manual
-44-
16 LWIND OLD I> 0.1...100.0 100Overcurrent Setting of overload for winding indelta
17T LWIND OLD
I>0.1…3600s 20 Timer setting for overload
18 LWIND OLD ON 1/0 0 Winding(WIND) Overload(LOAD) in LV side on
5.10 VT failure
5.10.1 Function description
VT failure includes three phase VT failure element and single or two phase VT failure
element.
1) 3 phases VT failure element: voltages of three phases all are under 18V and current
of any phase is larger than threshold (fixed in the software, for 1A CT, the threshold is
0.06A; for 5A CT, the threshold is 0.3A.), confirm three VT failure over 10s. The logic for 3
phases VT failure is shown in Fig.26.
VT Fail
&
10s
UB<18V
UA<18V
UC<18V
IB>Iset
IA>Iset
IC>Iset
>=1
&
Fig.26: The logic for 3 phases VT failure.
2) 1 or 2 phases VT failure element: If 03U added by three phase voltage is larger
than 18V and three phase-phase voltages are not equal, difference between two phase-
phase voltage is larger than 18V(in order to discriminate ground fault in indirectly earthed
system), confirm VT failure over 10s. The logic for one or two phase VT failure is shown in
Fig.27.
VT Fail
>=1
10s
|UBC-UCA|>18V
|UAB-UBC|>18V
|UCA-UAB|>18V &
VUUU CBA 18>++ ɺɺɺ
Fig.27: The logic for 1or 2 phases VT failure.
6 Operation
6.1 Safety precautions
During the equipment tests and start-up, the general safety regulations applicable to
electrical systems must be complied with. Failure to comply with these regulations might
cause harm to the working staff and damage to property. All the inspections and tests
must only be carried out by specially trained personnel.
• Check the enclosure shell has been grounded reliably and maintain electric
continuity to earth.
• The general safety regulations applicable to equipments must be strictly complied
CSC-326 Numerical Transformer Protection Equipment Manual
-45-
with.
• Insert or pull out models must be strictly prohibit during the equipment tests and
operation.
• During operation, nobody is allowed to press the keyboard on the panel optionally.
• During operation, nobody is allowed to operate the following commands:
Burst into drive.
Modification and solidify settings.
Set up numbers of running CPU.
Change setting group.
Change equipment address in communication net.
6.2 Dialog with the equipment
6.2.1 Menu frame
Table 26 is the menu frame about the Man-Machine Interface (MMI).
Table 26: Menu frame for MMI
Abbr.
(LCD Display)Meaning
Remarks
OpStatus Operating Status
AI Analog Input Inspecting the analog input of the equipment.
Status Equipment Status Inspecting the equipment status.
Version Version Showing the version information of the CPU inthe equipment.
EquipCode Equipment Code Showing the code information of any modulein the equipment.
DI Digital Input Inspecting the status of digital inputs.
Measure Measuring Values Showing the measure quantities of theequipment (the value of the current has beenaltered basing on the CT adjustingcoefficient).
Settings Settings SetupCommPara
BayName Name of Bay Unit Inputting the name of the primary power unitwith ISN (internal statement number).
CommAddr CommunicationAddress
Setting the address of the LON-NET.
TimeMode Timing Mode
BaudR485 Baud Rate of 485
EquipPara Equipment Parameter Setting the equipment parameter.
ProtSet Protection Setting the equipment setting.
ProtContWd
QueryRep
EventRpt Event Report
Latest Rpt The latest report Listing the time of the latest operating report,inspecting the content by pressing the SETkey.
Last 6 Rpts Last 6 reports Listing the time of the latest six operating
report, selecting the report with ∆ and ∇
CSC-326 Numerical Transformer Protection Equipment Manual
-46-
key, inspecting the content with SET key.
QueryRpt by Date Query report by date Listing the time of the operating reports whichis searched by time sect, selecting the report
with ∆ and ∇ key, inspecting the content bypressing the SET key.
StartRpt Startup Report
Latest Rpt The latest report Listing the time of the latest starting report,inspecting the content by pressing SET key.
Last 6 Rpts Last 6 reports Listing the time of the latest six starting
reports, selecting the report with ∆ and ∇key, inspecting the content with SET key.
QueryRpt by Date Query report by date Listing the time of the starting reports whichis searched by time sect, selecting the report
with ∆ and ∇ key, inspecting the contentwith SET key.
AlarmRpt Alarm Report
Last 6 Rpts Last 6 reports Listing the time of the latest six alarm
reports, selecting the report with ∆ and ∇key, inspecting the content with SET key.
QueryRpt by Date Query report by date Listing the time of the alarm reports which issearched by time sect, selecting the report
with ∆ and ∇ key, inspecting the content bypressing the SET key.
Log Operating Log
Last 6 Rpts Last 6 reports Listing the time of the latest six running
reports, selecting the report with ∆ and ∇key, inspecting the content with SET key.
QueryRpt by Date Query report by date Listing the time of the running reports whichis searched by time sect, selecting the report
with ∆ and ∇ key, inspecting the content bypressing the SET key.
Setup Equipment Setup
SOEReset SOE Reset Option
Automatic Reset Automatic Reset
Manual Reset Manual Reset
Manual resetting or automatic resetting.
Protocol Protocol Option
V1.20 Protocol Communication ProtocolV1.20
V1.10 Protocol Communication ProtocolV1.10
Choosing the protocol for the equipmentcommunication with exterior V1.20 or V1.10.The bright option is the current setup, select
the protocol with ∆ and ∇ key, set up it bypressing SET key.
ModifyPW Modify Password Modifying operation password.
SetPrint Print Setup
RecPrt Setup Setup for print recordvalues
The user can choose AC channels and Binaryrecord message.
Print Mode Setup for print mode Setting print mode, which can be figure ordata mode.
103Type 103 Protocol Select Setting the type of function 103.
Print Print
ProtSet Protection Setting Printing setting.
CSC-326 Numerical Transformer Protection Equipment Manual
-47-
Report Report
EventRpt Event Report
Latest Rpt The latest report Listing the time of the latest operating report,inspecting the content with pressing the SETkey.
Last 6 Rpts Last 6 reports Listing the time of the latest six operating
reports, selecting the report with ∆ and ∇key, inspecting the content with SET key.
QueryRpt by Date Query report by date Listing the time of the operating reports whichis searched by time sect, selecting the report
with ∆ and ∇ key, inspecting the contentwith SET key.
StartRpt Startup Report
Latest Rpt The latest report Listing the time of the latest starting report,inspecting the content by pressing the SETkey.
Last 6 Rpts Last 6 reports Listing the time of the latest six starting
reports, selecting the report with ∆ and ∇key, inspecting the content with SET key.
QueryRpt by Date Query report by date Listing the time of the starting reports whichis searched by time sect, selecting the report
with ∆ and ∇ key, inspecting the content bypressing the SET key.
AlarmRpt Alarm Report
Last 6 Rpts Last 6 reports Listing the time of the latest six-alarm report,
selecting the report with ∆ and ∇ key,inspecting the content with SET key.
QueryRpt by Date Query report by date Listing the time of the alarm reports which issearched by time sect, selecting the report
with ∆ and ∇ key, inspecting the content bypressing the SET key.
Log Operating Log
Last 6 Rpts Last 6 reports Listing the time of the latest six running
report, selecting the report with ∆ and ∇key, inspecting the content with SET key.
QueryRpt by Date Query report by date Listing the time of the running reports whichis searched by time sect, selecting the report
with ∆ and ∇ key, inspecting the content bypressing the SET key.
EquipPara Equipment Parameter Printing equipment parameter.
Setup Equipment Setup Printing equipment setup.
OpStatus Operating Status
AI Analog Input Printing analog input.
Status Equipment Status Printing equipment state.
Version Version Printing the version of CPU in the equipment.
EquipCode Equipment Code Printing equipment code.
DI Digital Input Printing digital input.
Connector ON/OFF Connector ON/OFF Printing strap state.
PrtSample Print Sampling Data Printing sampling data.
Test DO Digital Output DriveTest
Digital output driving.
CSC-326 Numerical Transformer Protection Equipment Manual
-48-
Set Time Set Time
Testing Testing
SimuReSig Simulate Remote Signal
Simu Alarm Simulate Alarm
Simu Trip Simulate Tripping
Simu Connt Simulate Connector
Simu DI Simulate DigitalInput(DI)
Simu Transmit Rec Simulate transmittingrecord data
Simu MST Alarm
SwSetGrp Switch Setting Group
ViewDrift View AI Zero Drift Inspecting the zero shift of specified CPU.
AdjDrift Adjust AI Drift Adjusting the zero shift of all CPU. Choosing
the channels with ∆ and ∇ key, fixing onechannel with SET key, moving the cursor onENSURE and pressing the SET key tocomplete regulating.
ViewScale View AI Scale Inspecting the scale of specified CPU.
AdjScale Adjust AI Scale Adjusting the scale of all CPU. Choosing the
channels with ∆ and ∇ key, fixing onechannel and setting the voltage/current valuewith SET key, moving the cursor on ENSUREand pressing the SET key to completeregulating.
PrtSample Print Sampling Data
Contrast LCD ContrastRegulation
Regulating LCD lightness.
OpConnt Connector Operation
OpSoftConnt Soft Connector ON/OFF
ViewConnt View Connector Status
The operation of switching straps into or outof service.
Table 27: the menu frame of the DebuggingMenu
Abbr.
(LCD Display)Meaning
Remarks
SetCPU Set CPU Setting CPU.
ViewMem View Memory Viewing the memory of the equipment.
ClrConfig Clear Configuration
EquipConfig Equipment Configuration
EquipOpt Equipment Option
LED Set LED Set Setup for LED Type.
ConntMode Connector Mode Setup for Connector mode.
SetLCD_Bkdg Set background LCD Setup for background LCD mode.
MasterVer Master Version Choosing Master version.
6.2.2 Display flowing
The display includes <circular display>, < MainMenu >, < DebuggingMenu >, <the
CSC-326 Numerical Transformer Protection Equipment Manual
-49-
message window for active pop-up>.
The equipment circularly displays the analogue quantities and the setting group. There
is the present time on the top of the screen. You can fix one screen of information to be
displayed by pressing QUIT key, and keep on circularly displaying by pressing the QUIT key
again.
The equipment menu includes the MainMenu and the DebuggingMenu.
You can enter the MainMenu by pressing the SET key when the screen is in circularly-
displaying state. You can enter the DebuggingMenu by pressing the QUIT+SET keys (only
for manufacturer).
There are four shortcut keys and two functional keys at the bottom of liquid crystal
screen. The main intention is to predigest user’s manipulation. The descriptions of these
keys are as Table 28.
Table 28: Shortcut key application
Shortcut key Remarks
F1Printing latest tripping event, page down andup function for changing setting screen
F2Printing settings in preset fixed value zone,page down and up function for changingsetting screen
F3 Printing sample values
F4 Printing device information and running status
F5Functional key, current setting group plus1.Note: there are 0,1,2,3 four setting groupstotal
F6Functional key, current setting group minus1.Note: there are 0,1,2,3 four setting groupstotal.
6.3 Annunciations
6.3.1 Event report
Table 29: List of event report
No
.
Abbr.
(LCD Display)Comment
1 Relay Start Relay Startup(Start)
2 Relay Reset Relay Reset (Reset)
3 IDIFF> Trip A
4 IDIFF> Trip B
5 IDIFF> Trip C
Treble slope percent Differential protection (IDIFF>) tripping (Trip)for phase A/B/C
6 IDIFF>> Trip A
7 IDIFF>> Trip B
8 IDIFF>> Trip C
Instantaneous Differential protection (IDIFF>>)tripping (Trip) for
phase A/B/C
9 HV REF Trip HV Restricted Earth fault (REF) protection tripping(Trip)
CSC-326 Numerical Transformer Protection Equipment Manual
-50-
10 MV REF Trip MV Restricted Earth fault (REF) protection tripping(Trip)
11 LV REF Trip LV Restricted Earth fault (REF) protection tripping(Trip)
12 HV DEF V/F Trip
13 HV IVR V/F Trip
HV Overflux protection(V/F) tripping (Trip) with definite (DEF) and
inverse(IVR) time characteristic
14 MV DEF V/F Trip
15 MV IVR V/F Trip
MV Overflux protection(V/F) tripping (Trip) with definite (DEF) and
inverse(IVR) time characteristic
16 HV IDMTL OC Trip HV IDMTL Overcurrent(OC) tripping(Trip)
17 HV OC_1 Trip
18 HV OC_2 Trip
Overcurrent protection (OC) stage 1 (_1) or stage 2 (_2) tripping
(Trip) in High Voltage (HV) side with time delay T
19 HV EDIS Trip Phase to Earth Distance (EDIS) tripping in HV side
20 HV DIS_1 Trip
21 HV DIS_2 Trip
Phase to phase Distance (DIS) prot. Stage 1(_1) or Stage 2 (_2)
tripping in HV side with time delay T
22 HV IDMTL NC Trip HV IDMTL Neutral current (NC) tripping(Trip)
23 HV NC_1 Trip
24 HV NC_2 Trip
Neutral Current protection (NC) Stage 1 (_1) or Stage 2 (_2)
tripping (Trip) in High Voltage (HV) side with time delay T.
25 HV 3U0 TRIP Neutral displacement (3U0)protection tripping (Trip) in HV side
26 HV TEM OVLD Trip HV Thermal (TEM) Overload(OVLD) tripping (Trip)
27 MV IDMTL OC TRIP MV IDMTL Overcurrent(OC) tripping(TRIP)
28 MV OC_1 Trip
29 MV OC_2 Trip
Overcurrent protection (OC) stage 1 (_1) or stage 2 (_2) tripping
(Trip) in Middle Voltage (MV) side with time delay T
30 MV EDIS Trip Phase to Earth Distance(EDIS) protection tripping in MV side
31 MV DIS_1 Trip
32 MV DIS_2 Trip
Phase to phase Distance (DIS) prot. Stage 1(_1) or Stage 2(_2)
tripping in MV side with time delay T
33 MV IDMTL NC Trip MV IDMTL Neutral current (NC) tripping(TRIP)
34 MV NC_1 Trip
35 MV NC_2 Trip
Neutral Current protection (NC) Stage 1 (_1) or Stage 2 (_2)
tripping (Trip) in Middle Voltage (HV) side with time delay T.
36MV 3U0 Trip
Neutral displacement (3U0)protection tripping (Trip) in MV sidewith time delay T
37 MV TEM OVLD Trip MV Thermal (TEM) Overload(OVLD) tripping (Trip)
38 LV IDMTL OC Trip LV IDMTL Overcurrent(OC) tripping(Trip)
39 LV OC_1 Trip
40 LV OC_2 Trip
Overcurrent protection (OC) stage 1 (_1) or stage 2 (_2) tripping
(Trip) in Low Voltage (LV) side with time delay T
41 LV IDMTL NC Trip LV IDMTL Neutral current (NC) tripping(Trip)
42 LV NC_1 Trip
43 LV NC_2 Trip
Neutral Current protection (NC) Stage 1 (_1) or Stage 2 (_2)tripping (Trip) in Low Voltage (LV) side with time delay T.
44 LV 3U0 Trip Zero sequence voltage (3U0) protection tripping (Trip) in LV side
45 LV TEM OVLD Trip LV Thermal (TEM) Overload(OVLD) tripping (TRIP )
46 HV Neu IDMTL HV Neutral current IDMTL
CSC-326 Numerical Transformer Protection Equipment Manual
-51-
47 MV Neu IDMTL MV Neutral current IDMTL
48 HV CB1 PD Trip
49 MV CB2 PD Trip
Circuit-Breaker (CB) Pole discordance(PD) protection tripping(Trip)in HV side with time delay T.
50 MV CB PD Trip Circuit-Breaker (CB) Pole discordance(PD) protection tripping(Trip)in MV side with time delay T.
51 REF Optd Restricted Earth Fault protection operated disturbance record
52 TRAFO Trip TRAFO BUCH Trip disturbance record
53 WTI High Trip Winding Temperature Indicator High Trip disturbance record
54 OTI High Trip Oil Temperature Indicator High Trip disturbance record
55 PRD Trip Pressure Release Trip disturbance record
56 OLTC Trip OLTC Trip disturbance record
57 BUCH Alarm BUCH Alarm disturbance record
58 WTI High Alarm Winding Temperature Indicator High Alarm disturbance record
59 OTI High Alarm Oil Temperature Indicator High Alarm disturbance record
60 LowOilLevelAlarm Low Oil Level Alarm disturbance record
6.3.2 Alarm report
The following is the illustration for device alarm message.
1) Alarm I is severe alarm. When alarm I happens, the alarm lamp on the front panel
of the device will flash, all of protection function will be switched out of service and the trip
power of protection will be blocked by the device.
2) Alarm II is other alarm. When alarm II happens, the alarm lamp on the front panel
of the device will light continuously, and the device will alarm the corresponding abnormal
status (for example, the circuit-breaker failure startup digital input is abnormal), and will
not block the trip power of protection.
The alarm messages and alarm types are as Table 30.
Table 30: List of alarm report
No. Abbr.
(LCD Display)Comment Alarm I/II
1Sampling Err Sampling data of analog input (AI) are
error.Alarm I
2 EquipPara Err Equipment parameter is error. Alarm I
3 ROM Verify ErrCRC verification to sum of ROM of CPUis error.
Alarm I
4 Setting Err Setting value is error Alarm I
5 Set Group Err Pointer of setting group is error Alarm I
6 DO No Response Digital output (DO) has no response. Alarm I
7 DO Breakdown Digital output (DO) is of breakdown. Alarm I
8 DI Err Digital input (DI) is error. Alarm II
9 SysConfig Err System configuration is error. Alarm I
10 CAN Comm Fail CAN communication failure --
CSC-326 Numerical Transformer Protection Equipment Manual
-52-
11 CAN Comm Recover CAN communication Recovery --
12 DI Module Err Digital input (DI) module is error. --
13 DO Module Err Digital output (DO) module is error. --
14 DI Config Err Digital input configuration is error. Alarm II
15 DO Config Err Digital output configuration is error. Alarm I
16 DI Comm Fail Communication failure in digital input(DI)
Alarm II
17DO Comm Fail Communication failure in digital output
(DO)Alarm II
18Test DO Un-reset Digital output (DO)-test has not been
reset.Alarm II
19ConntMdUnconfirm Connector mode has not been
confirmed.Alarm II
20 DI Breakdown Digital input (DI) is of breakdown. Alarm II
21 DI Input Err The input of digital input (DI) is error. Alarm II
22 NO/NC Discord2-position input discordance, i.e. statusof NC and NO discord.
Alarm II
23 DI Check ErrSelf-checking circuit of digital input(DI) is error.
Alarm II
24 DI EEPROM Err EEPROM of digital input (DI) is error. Alarm II
25 DO EEPROM Err EEPROM of digital output (DO) is error. Alarm I
26 SRAM Check Err SRAM self-checking is error. Alarm II
27 FLASH Check Err Flash self-checking is error. Alarm II
28 CT Fail CT failure --
29 DIFF Alarm Imbalance differential current alarm --
30HV REF Alarm HV Imbalance zero differential current
alarm--
31MV REF Alarm MV Imbalance zero differential current
alarm--
32LV REF Alarm LV Imbalance zero differential current
alarm--
33 HV V/F Alarm HV Overflux alarm --
34 MV V/F Alarm MV Overflux alarm --
35 HV VT Fail HV VT failure --
36 H Neu Disp Alarm HV neutral displacement alarm --
37 HV Load Alarm HV overload alarm --
38 HV Blk Vol Regu HV Blocking Voltage Regulation --
39 MV VT Fail MV VT failure --
40 M Neu Disp Alarm MV neutral displacement alarm --
41 MV Load Alarm MV overload alarm --
42 MV Blk Vol Regu MV Blocking Voltage Regulation --
43 LV VT Fail LV VT failure --
44 L Neu Disp Alarm LV neutral displacement alarm --
49 LV Load Alarm LV overload alarm --
50 LW Load Alarm overload in LV delta winding alarm --
CSC-326 Numerical Transformer Protection Equipment Manual
-53-
51 DI HV PD Alarm DI for HV CB1 Pole discordance Alarm II
52 DI HV PD2 Alarm DI for HV CB2 Pole discordance Alarm II
53 DI MV PD Alarm DI for MV CB Pole discordance Alarm II
54 HV CB1 On DI for HV CB1 Closed
55 HV CB2 On DI for HV CB2 Closed
56 MV CB On DI for MV CB Closed
57 LV CB On DI for LV CB Closed
58 HV CB1 Off DI for HV CB1 Open
59 HV CB2 Off DI for HV CB2 Open
60 MV CB Off DI for MV CB Open
61 LV CB Off DI for LV CB Open
62 HV TEM Alarm HV Thermal overload Alarm
63HV1 I2 Alarm HV CB1 Imbalance negative current
alarmAlarm II
64HV2 I2 Alarm HV CB2 Imbalance negative current
alarmAlarm II
65MV I2 Alarm MV CB Imbalance negative current
alarmAlarm II
66LV I2 Alarm LV CB Imbalance negative current
alarmAlarm II
6.3.3 Operating report
Table 31: List of operating report
No. Description of event comment
1 SwSetGroup OK Successful to switch setting group.
2 Write Set OK Successful to write setting values.
3 WriteEquipParaOK Successful to write equipment parameter.
4 WriteConfig OK Successful to write configuration.
5 AdjScale OK Successful to adjust scale of analog input (AI).
6 SelfDesc Change Self-description of equipment has changed.
7 Connt ON/OFF OK Successful to switch on/off connector.
8 ClrConfig OK Successful to clear configuration.
9 ChgConntMode Change connector mode
10 InTestMode Enter test mode.
11 OutTestMode Exit test mode.
12 Test DO OK Successful to digital output (DO) drive-test.
13 DI Change Status of digital input (DI) has changed.
14 AdjDrift OK Successful to adjust zero drift of analog input (AI).
15 Not Used Not used.
16 CPU Reset CPU Reset.
CSC-326 Numerical Transformer Protection Equipment Manual
-54-
6.4 Testing and commissioning
The test method and report for testing see the documents “CSC-326 Numerical
transformer protection Equipment Test Method (Model 1/2)” and “CSC-326 Numerical
transformer protection Equipment Test Report (Model 1/2)”.
6.5 Putting the equipment into operation
The following items are only provided to be referred. Users should formulate the
corresponding rules for maintenance and operation according to the actual situation in
locale.
a) Check the setting lists inerrably, and then turn on DC power supply. Now the green
light - LED <Run> on panel is lit, other lights are extinguished. Under normal conditions,
LCD display on loop “year-month-day, hour : minute : second, magnitude and phase angle
of analog quantities, channel state, current setting zone: 00. Press SET key to display main
menu. Press one or several times QUIT key9exit current menu one times or step by step to
return normal state of display. Then re-check the clock by turning off DC power and then
on.
b) Connect currents (load current must be larger than 0.1In) and voltages to the
device, under normal state of loop display, press SET key to enter into main menu, then
enter into every sub-menu to check whether the polarity and the phase sequence of each
analog input are correct or not. Verify the sampled data of the protection in accordance
with the actual ones.
c) Check the protection settings. Print each set of settings that are possibly employed
in the actual operating modes, in order to check them with informed sheet of setting and
backup debugging notes.
d) Check the digital inputs in accord with the practical state, and make note. Especially
notice that there is not display of “small hand” on the upper right of LCD under normal
conditions (that means relay test state).
6.6 Configuration of functions
6.6.1 Configuration of functions
CSC-326 provided entire functions for the transformers, any functions can be
configured according to the definite project. The default configuration for CSC-326 series is
shown in table 2.
6.6.2 Settings- equipment parameters
Equipment parameters are shown as table 32.
Table 32: Equipment parameters list
No.Setting Title Setting
options
Default
settingcomments
1 DIFF TRIP 0000...FFFFH 0000HTripping (TRIP)setting for differential(DIFF)protection
2 REF TRIP 0000...FFFFH 0000HTripping (TRIP)setting for Restricted EarthFault(REF) protection of every side
3 V/F TRIP 0000...FFFFH 0000HTripping (TRIP)setting for Overfluxprotection
4 HV BU TRIP 0000…FFFFH 0000HTripping (TRIP)setting for HV Backupprotection
5 MV BU TRIP 0000…FFFFH 0000H Tripping (TRIP)setting for MV Backup
CSC-326 Numerical Transformer Protection Equipment Manual
-55-
protection
6 LV BU TRIP 0000…FFFFH 0000HTripping (TRIP)setting for LV Backupprotection
7 HV CB PD TRIP 0000…FFFFH 0000HTripping (TRIP)setting for HV CB1 Polediscordance protection
8 HV CB2 PD TRIP 0000…FFFFH 0000HTripping (TRIP)setting for HV CB2 Polediscordance protection
9 MV CB PD TRIP 0000…FFFFH 0000HTripping (TRIP)setting for MV CB Polediscordance protection
Remark:
1. No.5 “MV BU TRIP” and No 9 “MV CB PD TRIP” are only used for CSC-326(Model 2), forCSC-326(Model 1), these two settings are displayed to “Not Used”.2. All parameter settings can be set by setting 16 bits.
6.6.3 Settings- protection settings
Protection settings are shown in table 33 to table 42.
Table 33: Protection setting list-Common Parameter
No Setting TitleSetting
options
Default
settingComment Function
1HV WIND
CONN/Y-0 D-10-1 0
Connection for HV winding, 0:wyeconnection, 1:delta connection
2MV WIND
CONN/Y-0 D-10-1 0
Connection for MV winding, 0:wyeconnection, 1:delta connection
3 LV WINDCONN/Y-0 D-1
0-1 1Connection for LV winding, 0:wyeconnection, 1:delta connection
4 VET GRP ANGLE 0-12 11Vector Group Angle( VET GRPANGLE)
5 SN 0...3000MVA 360 Capacity of the transformer
Commonparameters fortransformer
6 HV UN 0...1000 kV 220Nominal voltage (UN) in Highvoltage (HV)side
7 HV VT RATIO 0...9999 2200Voltage transformer(VT) Ratio inHV side
8 HV CT PRI 0...9999A 1200 CT Primary(PRI) current in HV side
9 HV CT SEC 1 OR 5A 1CT Secondary(SEC) current in HVside
Commonparameters forhigh voltageside
10 HV NCT PRI(REF) 0...9999A 1200Neutral CT (NCT) Primary(PRI)current in HV side for REF
11HV NCTSEC(REF)
1 OR 5A 1Neutral CT (NCT) Secondary(SEC)current in HV side for REF
12 HV NCT PRI(BU) 0...9999A 1200Neutral CT (NCT) Primary(PRI)current in HV side for Backup(BU)
13 HV NCT SEC(BU) 1 OR 5A 1Neutral CT (NCT) Secondary(SEC)current in HV side for Backup(BU)
Common earthprotectionparameters forHV side
14 MV UN 0…1000 kV 110Nominal voltage (UN) in Middlevoltage (MV)side
15 MV VT RATIO 0...9999 1100Voltage transformer(VT) Ratio inMV side
16 MV CT PRI 0...9999A 600 CT Primary(PRI) current in MV side
17 MV CT SEC 1 OR 5A 1CT Secondary(SEC) current in MVside
Commonparameters formiddle voltageside
CSC-326 Numerical Transformer Protection Equipment Manual
-56-
18 MV NCT PRI(REF) 0...9999A 600Neutral CT Primary(PRI) current inMV side
19MV NCTSEC(REF)
1 OR 5A 1Neutral CT Secondary(SEC)current in MV side
20 MV NCT PRI(BU) 0...9999A 1200Neutral CT (NCT) Primary(PRI)current in MV side for Backup(BU)
21 MV NCT SEC(BU) 1 OR 5A 1Neutral CT (NCT) Secondary(SEC)current in MV side for Backup(BU)
Common earthprotectionparameters forMV side
22 LV UN 0…1000kV 35Nominal voltage (UN) in Lowvoltage (LV)side
23 LV VT RATIO 0...9999 350Voltage transformer(VT) Ratio inLV side
24 LV CT PRI 0…9999A 3000 CT Primary(PRI) current in LV side
25 LV CT SEC 1 OR 5A 1CT Secondary(SEC) current in LVside
26LV CT SEC IN
DELTA1 OR 5A 1
CT Secondary(SEC) current for LVwinding inside delta
Commonparameters forLV side
27 LV NCT PRI(REF) 0…9999A 1200Neutral CT Primary(PRI) current inLV side
28 LV NCT SEC(REF) 1 OR 5A 1Neutral CT Secondary(SEC)current in LV side
29 LV NCT PRI(BU) 0…9999A 1200Neutral CT (NCT) Primary(PRI)current in LV side for Backup(BU)
30 LV NCT SEC(BU) 1 OR 5A 1Neutral CT (NCT) Secondary(SEC)current in LV side for Backup(BU)
Common earthprotectionparameters forLV side
Table 34: Protection setting list–Diff Set
No Setting TitleSetting
options
Default
settingComment Function
1 DIFF ID>> 0.5...100.0A 100Instantaneous Differential (ID>>)current setting
2 DIFF ID> 0.1…100.0A 20Percentage Differential (ID>) currentsetting
3 DIFF IR1 0.1…100.0A 4The 1st breakpoint restraint current(IR1)
4 DIFF IR2 0.1…100.0A 20The 2nd breakpoint restraint current(IR2)
5 DIFF SLOPE 0.2...0.7 0.7 the 2nd slope
6DIFF 2nd HAR
RATIO0.05…0.30 0.15 2nd harmonic(HAR) ratio
7 DIFF 5th HAR RATIO 0.10…0.60 0.35 5th harmonic(HAR) ratio
DIFF
Table 35: Protection setting list–REF Set
No Setting TitleSetting
options
Default
settingComment Function
1 HV REF I> 0.1…10.0A 2 Restricted earth fault setting HV REF
CSC-326 Numerical Transformer Protection Equipment Manual
-57-
2 HV REF SLOPE 0.20…0.70 0.5Slope setting for restricted earth faultprotection
3 MV REF I> 0.1…10.0A 2 Restricted earth fault setting
4 MV REF SLOPE 0.20...0.70 0.5Slope setting for restricted earth faultprotection
MV REF
5 LV REF I> 0.1...10.0A 2 Restricted earth fault setting
6 LV REF SLOPE 0.20…0.70 0.5Slope setting for restricted earth faultprotection
LV REF
Table 36: Protection setting list–Overflux Set
No Setting TitleSetting
options
Default
settingComment Function
1 HV Ubase 40.0…100.0 57.3 Nominal phase voltage in HV side
2 HV DEF V/F> Alarm 1.0...1.5 1.1 Alarming setting of volt/herz
3 HV T DEF V/F Alarm 0.1…9999s 10Timer setting for volt/herz alarmingstage
4 HV DEF V/F>> Trip 1.0...1.5 1.2Tripping setting of definite volt/herzstage
5 HV T DEF V/F Trip 0.1…9999s 10Timer setting for definite volt/herzstage
6 HV T1 IVR V/F=1.10 0.1…9999s 70 Timer setting for volt/herz=1.10
7 HV T2 IVR V/F=1.15 0.1…9999s 60 Timer setting for volt/herz=1.15
8 HV T3 IVR V/F=1.20 0.1…9999s 50 Timer setting for volt/herz=1.20
9 HV T4 IVR V/F=1.25 0.1…9999s 40 Timer setting for volt/herz=1.25
10 HV T5 IVR V/F=1.30 0.1…9999s 30 Timer setting for volt/herz=1.30
11 HV T6 IVR V/F=1.35 0.1…9999s 20 Timer setting for volt/herz=1.35
12 HV T7 IVR V/F=1.40 0.1…9999s 10 Timer setting for volt/herz=1.40
HV V/F
13 MV Ubase 40.0...100.0 57.3 Nominal phase voltage in MV side
14 MV DEF V/F> Alarm 1.0…1.5 1.1 Alarming setting of volt/herz
15 MV T DEF V/F Alarm 0.1…9999s 10Timer setting for volt/herz alarmingstage
16 MV DEF V/F>> Trip 1.0...1.5 1.2Tripping setting of definite volt/herzstage
17 MV T DEF V/F Trip 0.1…9999s 10Timer setting for definite volt/herzstage
18MV T1 IVRV/F=1.10
0.1…9999s 70 Timer setting for volt/herz=1.10
19MV T2 IVRV/F=1.15
0.1…9999s 60 Timer setting for volt/herz=1.15
20MV T3 IVRV/F=1.20
0.1…9999s 50 Timer setting for volt/herz=1.20
21MV T4 IVRV/F=1.25
0.1…9999s 40 Timer setting for volt/herz=1.25
MV V/F
CSC-326 Numerical Transformer Protection Equipment Manual
-58-
22MV T5 IVRV/F=1.30
0.1…9999s 30 Timer setting for volt/herz=1.30
23MV T6 IVRV/F=1.35
0.1…9999s 20 Timer setting for volt/herz=1.35
24MV T7 IVRV/F=1.40
0.1…9999s 10 Timer setting for volt/herz=1.40
Table 37: Protection setting list–HV Backup Set
No Setting TitleSetting
options
Default
settingComment Function
1 HV OC I1> 0.1...100.0 100Overcurrent(OC) setting for 1st stage(I1>)
2 T HV OC I1> 0.1...20s 20 Timer setting for 1st stage OC
3 HV OC I2> 0.1...100 100Overcurrent(OC) setting for 2nd
stage (I2>)
4 T HV OC I2> 0.1…20s 20 Timer setting for 2nd stage OC
5IDMTL HV OC
TimeMult0.025…2.0 1
6IDMTL HV OC CONST
A0.0…130.0 20
7 IDMTL HV OC POWERP
0.02...2.0 2
8 IDMTL HV OC PARA B 0.0…1.0 0
9 IDMTL HV OC I 0.1…100A 5
Ref to IEC and ANSI Curves
Definite andIDMTLovercurrentprotection(with selectivedirection) inHigh voltageside
10 HV NC I01> 0.1…100.0 100Neutral Current (NC) setting for 1st
stage (I01>)
11 T HV NC I01> 0.1…20s 20 Timer setting for 1st stage NOC
12 HV NC I02> 0.1…100 100Neutral Current (NC) setting for 2nd
stage (I02>)
13 T HV NC I02> 0.1…20s 20 Timer setting for 2nd stage NOC
14IDMTL HV NC
TimeMult0.025...2.0 1
15IDMTL HV NC CONST
A0.0…130.0 20
16IDMTL HV NC POWER
P0.02…2.0 2
17 IDMTL HV NC PARA B 0.0…1.0 0
18 IDMTL HV NC I0> 0.1…100A 5
Ref to IEC and ANSI Curves
Definite andIDMTL neutralcurrentprotection(with selectivedirection) inHigh voltageside
19 HV 3U0> ALARM 2.0…300.0 300Neutral voltage setting for alarmingstage
20 T HV 3U0> ALARM 0.1…20s 20 Timer setting for neutral voltage
21 HV 3U0> TRIP 2.0…300.0 300Neutral voltage setting for trippingstage
22 T HV 3U0> TRIP 0.1…20s 20 Timer setting for neutral voltage
Neutraldisplacementprotection inHigh voltageside
CSC-326 Numerical Transformer Protection Equipment Manual
-59-
23IDMTL HV
NeuTimeMult0.025...2.0 1
24 IDMTL HV NeuConstA 0.0…130.0 20
25 IDMTL HV NeuPowerP 0.02…2.0 2
26 IDMTL HV NeuParaB 0.0…1.0 0
27 IDMTL HV Neu I0> 0.1…100A 5
Ref to IEC and ANSI Curves
IDMTL neutralcurrentprotection inHV side
28 HV TEM OLD I> 0.1...25.0 2 Setting for thermal overload
29HV TEM OLD
TimeConst0…9000s 10
Time constant for thermal overloadprotection
30 HV WeightFactor H/C 0.0…1.0 0 Hot cool weight factor H/C
Thermaloverloadprotection
31 HV LOAD I> 0.1…100.0 100 Overcurrent Setting of overload
32 T HV LOAD I> 0.1…3600s 20 Timer setting for overload
Definiteoverloadprotection
33 HV BLK VOL REGU I> 0.1...100.0 100Overcurrent Setting of blockingvoltage regulation
34T HV BLK VOL REGU
I>0.1…3600s 20
Timer setting for blocking voltageregulation
Overcurrentblockingvoltageregulation
Table 38: Protection setting list–MV Backup Set
No Setting TitleSetting
options
Default
settingComment Function
1 MV OC I1> 0.1…100 100Overcurrent (OC) setting for 1st
stage (I1>)
2 T MV OC I1> 0.1…20s 20 Timer setting for 1st stage OC
3 MV OC I2> 0.1…100 100Overcurrent (OC) setting for 2nd
stage (I2>)
4 T MV OC I2> 0.1…20s 20 Timer setting for 2nd stage OC
5 IDMTL MV OC TimeMult 0.025...2.0 1
6 IDMTL MV OC CONST A 0.0...130.0 20
7 IDMTL MV OC POWER P 0.02...2.0 2
8 IDMTL MV OC PARA B 0.0…1.0 0
9 IDMTL MV OC I 0.1…100A 5
Ref to IEC and ANSI Curves
Definite andIDMTLovercurrentprotection(withselectivedirection) inMiddlevoltage side
10 MV NC I01> 0.1...100.0 100Neutral Current (NC) setting for 1st
stage (I01>)
11 T MV NC I01> 0.1…20s 20 Timer setting for 1st stage NOC
12 MV NC I02> 0.1…100.0 100Neutral Current (NC) setting for 2nd
stage (I02>)
13 T MV NC I02> 0.1…20s 20 Timer setting for 2nd stage NOC
14 IDMTL MV NC TimeMult 0.025...2.0 1
15 IDMTL MV NC CONST A 0.0…130.0 20
Ref to IEC and ANSI Curves
Definite andIDMTLneutralcurrentprotection(withselectivedirection) inMiddlevoltage side
CSC-326 Numerical Transformer Protection Equipment Manual
-60-
16 IDMTL MV NC POWER P 0.02...2.0 2
17 IDMTL MV NC PARA B 0.0…1.0 0
18 IDMTL MV NC I0> 0.1…100A 5
19 MV 3U0> ALARM 2.0…300.0 300Neutral voltage setting for alarmingstage
20 T MV 3U0> ALARM 0.1…20s 20 Timer setting for neutral voltage
21 MV 3U0> TRIP 2.0…300.0 300Neutral voltage setting for trippingstage
22 T MV 3U0> TRIP 0.1…20s 20 Timer setting for neutral voltage
Neutraldisplacementprotectionin Middlevoltage side
23 IDMTL MV NeuTimeMult 0.025...2 1
24 IDMTL MV NeuConstA 0.0...130.0 20
25 IDMTL MV NeuPowerP 0.02...2.0 2
26 IDMTL MV NeuParaB 0.0…1.0 0
27 IDMTL MV Neu I0> 0.1…100A 5
Ref to IEC and ANSI Curves
IDMTLneutralcurrentprotectionin MV side
28 MV TEM OLD I> 0.1...25.0 2 Setting for thermal overload
29 MV TEM OLD TimeConst 0...9000s 10Time const for thermal overloadprotection
30 MV WeightFactor H/C 0.0...1.0 0 Hot cool weight factor H/C
Thermaloverloadprotection
31 MV LOAD I> 0.1...100.0 100 Overcurrent Setting of overload
32 T MV LOAD I> 0.1...3600s 20 Timer setting for overload
Definiteoverloadprotection
33 MV BLK VOL REGU I> 0.1...100.0 100Overcurrent Setting of blockingvoltage regulation
34 T MV BLK VOL REGU I> 0.1...3600s 20Timer setting for blocking voltageregulation
Overcurrentblockingvoltageregulation
Remark: all settings for MV Backup protections are used for CSC-326(Model 2), they can not beseen in CSC326 (Model 1) because the functions are not configured.
Table 39: Protection setting list–LV Backup Set
No Setting TitleSetting
options
Default
settingComment Function
1 LV OC I1> 0.1...100 100Overcurrent (OC) setting for 1st
stage (I1>)
2 T LV OC I1> 0.1…20s 20 Timer setting for 1st stage OC
3 LV OC I2> 0.1…100 100Overcurrent (OC) setting for 2nd
stage (I2>)
4 T LV OC I2> 0.1...20s 20 Timer setting for 2nd stage OC
5 IDMTL LV OCTimeMult
0.025...2.0 1
6IDMTL LV OC CONST
A0.0...130.0 20
7IDMTL LV OC POWER
P0.02...2.0 2
8 IDMTL LV OC PARA B 0.0...1.0 0
Ref to IEC and ANSI Curves
Definite andIDMTLovercurrentprotection (withselectivedirection) inMiddle voltageside
CSC-326 Numerical Transformer Protection Equipment Manual
-61-
9 IDMTL LV OC I 0.1…100A 5
10 LV NC I01> 0.1...100 100Neutral Current (NC) setting for 1st
stage (I01>)
11 T LV NC I01> 0.1...20s 20 Timer setting for 1st stage NOC
12 LV NC I02> 0.1…100 100Neutral Current (NC) setting for 2nd
stage (I02>)
13 T LV NC I02> 0.1…20s 20 Timer setting for 2nd stage NOC
14IDMTL LV NC
TimeMult0.025...2.0 1
15 IDMTL LV NC CONST A 0.0...130.0 20
16IDMTL LV NC POWER
P0.02...2.0 2
17 IDMTL LV NC PARA B 0.0...1.0 0
18 IDMTL LV NC I0> 0.1…100A 5
Ref to IEC and ANSI Curves
Definite andIDMTL neutralcurrentprotection (withselectivedirection) inMiddle voltageside
19 LV 3U0> ALARM 2.0...300.0 300Neutral voltage setting for alarmingstage
20 T LV 3U0> ALARM 0.1...20s 20 Timer setting for neutral voltage
21 LV 3U0> TRIP 2.0...300.0 300Neutral voltage setting for trippingstage
22 T LV 3U0> TRIP 0.1...20s 20 Timer setting for neutral voltage
Neutraldisplacementprotection inMiddle voltageside
23 LV LOAD I> 0.1...100 100 Overcurrent Setting of overload
24 T LV LOAD I> 0.1...3600s 20 Timer setting for overload
overloadprotection
25 LWIND OLD I> 0.1...100 100Overcurrent Setting of overload forwinding in delta
26 T LWIND OLD I> 0.1...3600s 20 Timer setting for overload
overloadprotection forwinding indelta
Table 40: Protection setting list–CB PD Set
No Setting TitleSetting
options
Default
settingComment Function
1 HV CB PD 3I0> 0.1...100 100Zero sequence current setting of Circuitbreaker pole discordance
2 HV CB PD I2> 0.1…100 100negative sequence current setting ofCircuit breaker pole discordance
3 T HV CB PD 0.1…20s 20Timer setting for circuit breaker polediscordance
Polediscordancefor Circuitbreaker 1in HV side
4 HV CB2 PD 3I0> 0.1…100 100Zero sequence current setting of Circuitbreaker pole discordance
5 HV CB2 PD I2> 0.1…100 100negative sequence current setting ofCircuit breaker pole discordance
6 T HV CB2 PD 0.1…20s 20Timer setting for circuit breaker polediscordance
Polediscordancefor Circuitbreaker 2in HV side
7 MV CB PD 3I0> 0.1…100 100Zero sequence current setting of Circuitbreaker pole discordance
Polediscordancefor Circuitbreaker inMV side
CSC-326 Numerical Transformer Protection Equipment Manual
-62-
8 MV CB PD I2> 0.1…100 100negative sequence current setting ofCircuit breaker pole discordance
9 T MV CB PD 0.1…20s 20Timer setting for circuit breaker polediscordance
Remark: settings (No.7-N0.9) for MV Circuit Breaker Pole discordance protection are used forCSC-326 (Model 2), they can not be seen in CSC326 (Model 1) because the function is notconfigured.
Table 41: Protection setting list–Other Set
No Setting TitleSetting
options
Default
SettingComment Function
1 HV1 I2 DET SET 0.1...20A 8Setting for HV CB1 imbalance currentdetection
2 HV2 I2 DET SET 0.1…20A 8Setting for HV CB2 imbalance currentdetection
3 MV I2 DET SET 0.1…20A 8Setting for MV CB imbalance currentdetection
4 LV I2 DET SET 0.1…20A 8Setting for LV CB imbalance currentdetection
5 T I2 DET 0.1…20s 5Timer Setting for imbalance currentdetection
Negativeimbalancedetection
Remark: Setting ”MV I2 DET SET”is only used for CSC-326 (Model 2), it can not bedisplayed in CSC326 (Model 1).
Table 42: Protection setting list–Test use Set
No Setting TitleSetting
options
Default
settingComment Function
1 HV RATED CUR PRI HV rated current in primary side
2 HV RATED CUR SEC HV rated current in secondary side
3RATIO FACTOR
KTAHRatio compensation for HV side
4 RATIO FACTORKTAM
Ratio compensation for MV side
5 RATIO FACTOR KTAL
Calculated by softwareaccording to thecommon parametersuser put into thesetting group.
Ratio compensation for LV side
Test forDifferentialprotection
Remarks:
1.These settings are only used for test, they are calculated by software automaticallyaccording to the common parameters. These settings can not be modified by user.
2. Setting ”MV I2 DET SET” is only used for CSC-326 (Model 2), it can not be seen inCSC326 (Model 1).
6.6.4 Settings- Control word setting
Control word settings are shown in table 43.
Table 43: Control word settings
No Setting TitleSetting
options
Default
settingComment Menu
1 AUTO TRANS 1/0 0Auto-transformer not common transformer1-autotransformer ; 0- not auto-transformer
CommonPara
CSC-326 Numerical Transformer Protection Equipment Manual
-63-
2 TWO WIND TRANS 1/0 0
Two-winding(TWO WIND) not three -winding transformer (TRANS)1-two-winding trans; 0-three-windingtrans
31 REF FOR AUTO
TRANS1/0 0
1 REF Function not 2 REF Function, Thissetting is used only for autotransformer1-1REF Function ; 0- 2 REF function
4 IDIFF ON 1/0 0Instantaneous differential (IDIFF)protection ON1-on; 0-off.
5 PDIFF ON 1/0 0Percentage differential (PDIFF) protectionON1-on; 0-off.
62nd HAR NOT
WAVE1/0 0
2nd harmonic (HAR) inhibit not the fuzzyrecognition based on the waveform(WAVE)1-2nd harmonic on; 0- waveform on
7 5th HAR ON 1/0 05th harmonic (HAR) inhibit on1-on; 0-off.
8 DIFF ALARM ON 1/0 0Differential current (DIFF) Alarming on1-on; 0-off.
9 CT FAIL DET ON 1/0 0CT FAIL Detection(DET) on1-on; 0-off.
Diff Set
10 HV REF ON 1/0 0HV Restricted earth fault(REF) ON1-on; 0-off.
11 MV REF ON 1/0 0MV Restricted earth fault(REF) ON1-on; 0-off.
12 LV REF ON 1/0 0LV Restricted earth fault(REF) ON1-on; 0-off.
REF Set
13HV V/F> ALARM
ON1/0 0
HV Definite Overflux (V/F) Alarming on1-on; 0-off.
14HV DEF V/F> TRIP
ON1/0 0
HV Definite (DEF)Overflux (V/F) on1-on; 0-off.
15 HV IVR V/F> ON 1/0 0HV Inverse (IVR)Overflux (V/F) on1-on; 0-off.
16 MV V/F> ALARMON
1/0 0MV Definite Overflux (V/F) Alarming on1-on; 0-off.
17 MV DEF V/F> TRIPON
1/0 0MV Definite (DEF)Overflux (V/F) on1-on; 0-off.
18 MV IVR V/F> ON 1/0 0MV Inverse (IVR)Overflux (V/F) on1-on; 0-off.
OverfluxSet
19 HV OC_1 ON 1/0 01st stage(_1) Overcurrent (OC) in HV sideon
20 HV OC_1 DIR ON 1/0 0Direction (DIR) detection of 1st Stage(_1)of Overcurrent(OC) in HV side
21HV OC_1 DIR TO
SYS1/0 0
Direction (DIR) of 1st stage (_1)Overcurrent (OC)to system nottransformer itself in HV side
22 HV OC_2 ON 1/0 02nd stage(_2) Overcurrent (OC) in HV sideon
23 HV OC_2 DIR ON 1/0 0Direction (DIR) detection of 2nd Stage(_2)of Overcurrent(OC) in HV side
24HV OC_2 DIR TO
SYS1/0 0
Direction (DIR) of 2nd stage (_2)Overcurrent (OC)to system nottransformer itself in HV side
25 HV IDMTL OC ON 1/0 0 IDMTL Overcurrent (OC) in HV side on
HVBackup
Set
CSC-326 Numerical Transformer Protection Equipment Manual
-64-
26HV IDMTL OC DIR
ON1/0 0
Direction (DIR) detection of IDMTLOvercurrent(OC) in HV side
27 HV IDMTL OC DIRTO SYS
1/0 0
Direction (DIR) of IDMTL Overcurrent(OC)to system not transformer itself inHV side
28 HV NC_1 ON 1/0 01st stage(_1) Neutral Current (NC) in HVside on
29 HV NC_2 ON 1/0 02nd stage(_2) Neutral Current (NC) in HVside on
30 HV NC_1 DIR ON 1/0 0Direction(DIR) detection of 1st stage(_1)Neutral Current (NC) in high voltage(HV)side on
31HV NC_1 DIR TO
SYS1/0 0
Direction (DIR) of 1st stage (_1) NeutralCurrent (NOC)to system not transformeritself in HV side
32 HV NC_2 DIR ON 1/0 0Direction(DIR) detection of 2nd stage(_2)Neutral Current (NC) in high voltage(HV)side on
33HV NC_2 DIR TO
SYS1/0 0
Direction (DIR) of 2nd stage (_2) NeutralCurrent (NC)to system not transformeritself in HV side
34 HV IDMTL NC ON 1/0 0 IDMTL Neutral Current (NC) in HV side on
35HV IDMTL NC DIR
ON1/0 0
Direction(DIR) detection of IDMTL NeutralCurrent (NC) in high voltage (HV)side on
36HV IDMTL NC DIR
TO SYS1/0 0
Direction (DIR) of IDMTL Neutral Current(NC)to system not transformer itself in HVside
37 HV 3U0> ALARMON
1/0 0Neutral displacement (3U0) alarm in HVside on
38 HV 3U0> TRIP ON 1/0 0Neutral displacement (3U0) trip in HV sideon
39HV NEU IDMTL OC
ON1/0 0 Neutral IDMTL OC in HV side on
40 HV TEM OLD ON 1/0 0 Thermal overload in HV side on
41 HV OLD ON 1/0 0 Overload (LOAD)in HV side on
42HV BLK VOL REGU
ON1/0 0
Blocking(BLK) voltage(VOL) regulation(REGU)in HV side on
43 MV OC_1 ON 1/0 01st stage(_1) Overcurrent (OC) with timedelay T in MV side on
44 MV OC_1 DIR ON 1/0 0Direction (DIR) detection of 1st stage(_1)of Overcurrent(OC) in MV side
45MV OC_1 DIR TO
SYS1/0 0
direction (DIR) of 1st stage (_1)Overcurrent(OC) to system nottransformer itself in MV side
46 MV OC_2 ON 1/0 02nd stage(_2) Overcurrent (OC) with timedelay T in MV side on
47 MV OC_2 DIR ON 1/0 0Direction (DIR) detection of 2nd stage(_2)of Overcurrent(OC) in MV side
48MV OC_2 DIR TO
SYS1/0 0
direction (DIR) of 2nd stage (_2)Overcurrent(OC) to system nottransformer itself in MV side
49 MV IDMTL OC ON 1/0 0 IDMTL Overcurrent (OC) in MV side on
50 MV IDMTL OC DIRON
1/0 0Direction(DIR) detection of IDMTLOvercurrent(OC) in MV side
MVBackup
Set
CSC-326 Numerical Transformer Protection Equipment Manual
-65-
51MV IDMTL OC DIR
TO SYS1/0 0
Direction(DIR) of IDMTL Overcurrent(OC)to system not transformer itself in MVside
52 MV NC_1 ON 1/0 01st stage(_1) Neutral Current (NC) in MVside on
53 MV NC_2 ON 1/0 02nd stage(_2) Neutral Current (NC) in MVside on
54 MV NC_1 DIR ON 1/0 0Direction(DIR) detection of 1st stage(_1)Neutral Current (NC) in MV side on
55MV NC_1 DIR TO
SYS1/0 0
Direction (DIR) of 1st stage (_1) NeutralCurrent (NOC)to system not transformeritself in MV side
56 MV NC_2 DIR ON 1/0 0Direction(DIR) detection of 2nd stage(_2)Neutral Current (NC) in MV side on
57 MV NC_2 DIR TOSYS
1/0 0Direction (DIR) of 2nd stage (_2) NeutralCurrent (NC)to system not transformeritself in MV side
58 MV IDMTL NC ON 1/0 0 IDMTL Neutral Current (NC) in MV side on
59MV IDMTL NC DIR
ON1/0 0
Direction(DIR) detection of IDMTL NeutralCurrent (NC) in high voltage (MV)side on
60 MV IDMTL NC DIRTO SYS
1/0 0Direction (DIR) of IDMTL Neutral Current(NC)to system not transformer itself in MVside
61 MV 3U0> ALARMON
1/0 0Neutral displacement (3U0) alarm in MVside on
62 MV 3U0> TRIP ON 1/0 0Neutral displacement (3U0) trip in MV sideon
63MV NEU IDMTL OC
ON1/0 0 Neutral IDMTL OC in MV side on
64 MV TEM OLD ON 1/0 0 Thermal overload in MV side on
65 MV OLD ON 1/0 0 Overload (LOAD)in MV side on
66MV BLK VOL REGU
ON1/0 0
Blocking(BLK) voltage(VOL) regulation(REGU)in MV side on
67 LV OC_1 ON 1/0 01st stage(_1) of Overcurrent(OC) in LV sideon
68 LV OC_1 DIR ON 1/0 0Direction (DIR) detection of 1st stage(_1)of Overcurrent(OC) in LV side
69LV OC_1 DIR TO
SYS1/0 0
Direction (DIR) of 1st stage (_1)Overcurrent(OC) to system nottransformer itself in LV side
70 LV OC_2 ON 1/0 02nd stage(_2) of Overcurrent(OC) in LVside on
71 LV OC_2 DIR ON 1/0 0Direction (DIR) detection of 2nd stage(_2)of Overcurrent(OC) in LV side
72LV OC_2 DIR TO
SYS1/0 0
Direction (DIR) of 2nd stage (_2)Overcurrent (OC)to system nottransformer itself in LV side
73 LV IDMTL OC ON 1/0 0 IDMTL Overcurrent (OC) in LV side on
74LV IDMTL OC DIR
ON1/0 0
Direction (DIR) detection of IDMTLOvercurrent(OC) in LV side
75LV IDMTL OC DIR
TO SYS1/0 0
Direction (DIR) of IDMTL Overcurrent(OC)to system not transformer itself in LVside
76 LV NC_1 ON 1/0 01st stage(_1) Neutral Current (NC) in LVside on
LVBackup
Set
CSC-326 Numerical Transformer Protection Equipment Manual
-66-
77 LV NC_1 DIR ON 1/0 0Direction(DIR) detection of 1st stage(_1)Neutral Current (NC) in high voltage(LV)side on
78 LV NC_1 DIR TOSYS
1/0 0Direction (DIR) of 1st stage (_1)9 NeutralCurrent (NOC)to system not transformeritself in LV side
79 LV NC_2 ON 1/0 02nd stage(_2) Neutral Current (NC) in LVside on
80 LV NC_2 DIR ON 1/0 0Direction(DIR) detection of 2nd stage(_2)Neutral Current (NC) in high voltage(LV)side on
81LV NC_2 DIR TO
SYS1/0 0
Direction (DIR) of 2nd stage (_2) NeutralCurrent (NC)to system not transformeritself in LV side
82 LV IDMTL NC ON 1/0 0 IDMTL Neutral Current (NC) in LV side on
83LV IDMTL NC DIR
ON1/0 0
Direction(DIR) detection of IDMTL NeutralCurrent (NC) in high voltage (LV)side on
84LV IDMTL NC DIR
TO SYS1/0 0
Direction (DIR) of IDMTL Neutral Current(NC)to system not transformer itself in LVside
85 LV 3U0> ALARMON
1/0 0Neutral displacement (3U0) alarm in LVside on
86 LV 3U0> TRIP ON 1/0 0Neutral displacement (3U0) trip in LV sideon
87 LV OLD ON 1/0 0 Overload (LOAD)in LV side on
88 LWIND OLD ON 1/0 0Winding(WIND) Overload(LOAD) in LV sideon
89 HV CB PD ON 1/0 0Circuit break(CB) pole discordance (PD) inHV side on
90 HV CB PD CUR ELEON
1/0 0Circuit break(CB) pole discordance(PD)with Current (CUR)element(ELE) in HVside on
91 HV CB2 PD ON 1/0 0Circuit break(CB) pole discordance (PD) inHV side 2 on
92HV CB2 PD CUR
ELE ON1/0 0
Circuit break(CB) pole discordance(PD)with Current (CUR)element(ELE) in HVside 2 on
93 MV CB PD ON 1/0 0Circuit break(CB) pole discordance (PD) inMV side on
94MV CB PD CUR ELE
ON1/0 0
Circuit break(CB) pole discordance(PD)with Current (CUR)element(ELE) in MVside on
CB PDSet
95 HV1 I2 DET ON 1/0 0CB1 negative imbalance detection in HVside on
96 HV2 I2 DET ON 1/0 0CB2 negative imbalance detection in HVside on
97 MV I2 DET ON 1/0 0CB negative imbalance detection in MVside on
98 LV I2 DET ON 1/0 0CB negative imbalance detection in LV sideon
99HV CB1 STATUS
ON1/0 0 CB1 Status supervision in HV side on
100 HV CB2 STATUSON
1/0 0 CB2 Status supervision in HV side on
101 MV CB STATUS ON 1/0 0 CB Status supervision in MV side on
OtherSet
CSC-326 Numerical Transformer Protection Equipment Manual
-67-
102 LV CB STATUS ON 1/0 0 CB Status supervision in LV side on
103REF OPTD Record
ON1/0 0 REF operated trigger Record on
104TRAFO Trip Record
ON1/0 0 TRAFO BUCH Trip disturbance Record on
105 BUCH AlarmRecord ON
1/0 0 BUCH Alarm disturbance Record on
106WTI High Trip
Record ON1/0 0 WTI High Trip disturbance Record on
107 WTI High AlarmRecord ON
1/0 0 WTI High Alarm disturbance Record on
108OTI High TripRecord ON
1/0 0 OTI High Trip disturbance Record on
109OTI High Alarm
Record ON1/0 0 OTI High Alarm disturbance Record on
110 LowOilLevelAlarmRecord ON
1/0 0 Low Oil Level Alarm disturbance Record on
111OLTC Trip Record
ON1/0 0 OLTC Trip disturbance Record on
112 PRD Trip RecordON
1/0 0 PRD Trip disturbance Record on
CSC-326 Numerical Transformer Protection Equipment Manual
-68-
7 Installation and commissioning
7.1 Unpacking & Repacking
• When dispatched from the factory, the equipment is packed in accordance with the
guidelines laid down in IEC 60255-21, which specifies the impact resistance of
packaging .This packing shall be removed with care, without force to the equipment
and without the use of inappropriate tools.
• The equipment should be visually checked to ensure that there are no external
traces of damage. Verify that the conformity certificates, matched documents,
accessories are consistent with the order requirements, and ensure that the type,
nameplate, numbers of the equipments are perfect and consistent with packing list.
• The transport packing can be re-used for further transport when applied in the same
way. The storage packing of the individual equipments is not suited to transport. If
alternative packing is used, this must also provide the same degree of protection
against mechanical shock, as laid down in IEC 60255-21-1 class 2 and IEC 60255-21-
2 class 1.
• Before initial energizing with supply voltage, the equipment shall be situated in the
operating area for at least two hours in order to ensure temperature equalization and
to avoid humidity influences and condensation.
7.2 Mounting
• The equipment ought to be fixed on panel or cabinet, and every connection bolt of
the equipment must be firmed.
• Using earthing coppery wires connect the equipment ground and panel (cabinet)
ground with bus line and verify the earthing is reliably.
• Checking the connection
• The equipment wiring must meet the requirements of wiring scheme.
7.3 Check before power on
• Pull out all the modules, check-up whether the mechanical structures accessory on
the board becomes flexible or there are mechanical damages and whether the wiring
is fastness.
• Check the man-machine interface is connected with faceplate reliable.
• Check the type tag of the equipment on faceplate, the lighting tag, backboard
terminal figure, terminal number tag and nameplate label of the equipment are intact
and right.
• Each module withdrawal and insertion is flexible, space between module and plug
slot are suitable right, and the insertion depth is satisfied. Verify the lock-up is
reliable. The slice of current connector for short circuit ought to be opened reliably
when module is inserted.
• Test insulation resistance in turn between analog circuits and ground, and the
circuits to each others every resistance must not be less than 100 MΩ.
CSC-326 Numerical Transformer Protection Equipment Manual
-69-
7.4 Check with power on
• Power supply check
Testing of voltage output value and its stability every class output voltage must be
maintained stable as shown in Table 44 when the input voltage of DC power supply is UN.
Table 44: Permissive range for dc supplied by the power
Rated voltage Permissive range
+5 4.8 to 5.2+12 11 to 13−12 −11 to −13+24 22 to 26
• Give alarm after power off
Energized DC power supply, the equipment for loss of power alarm ought to be excited
reliably, and its contacts as X12-c16 and X12-a16 must be opened reliably. Cut off rating
DC power supply, the relay for loss of power alarm ought to be lost magnetism reliably,
and its contacts as X12-c16 and X12-a16 must be closed reliably.
CSC-326 Numerical Transformer Protection Equipment Manual
-70-
8 Maintenance
8.1 Routine checks
• Measure resistance in turn between analog circuits and ground.
• Measure output voltage in every class.
• Check printer.
• Revise zero draft and scale.
• Verify alarm circuit.
• Verify binary input.
• Actual live tripping including circuit breaker.
• Check setting.
8.2 Relacing the back-up battery
• Battery is used to store data, record fault and inner clock in case the power is off.
• Battery is checked up timing, it will send out alarm after it is invalid or decline.
• The back-up battery should be replaced at the latest after 10 years of operation or
after alarm signal was sent out.
• Recommended battery: Lithium battery CR1/2AA, 3V/1Ah.
8.3 Fault tracing
The equipment may test all hardware components itself, including loop out of the
relay coil, Watch can find whether or not the equipment is in fault through warning lights
and warning characters which shows in liquid crystal display and print reports to tell fault
location and kind.
The method of eliminate fault is replacing fault board or eliminate external fault.
8.4 Repairs
• Users should not change modules circuit or backboard circuit in repair.
• It’s appropriate to change power board when power supply is fault.
• It’s suggested that power board should purchased per 4 or 6 years because it can’t
storage for a long time.
CSC-326 Numerical Transformer Protection Equipment Manual
-71-
9 Storage
• Although protection equipments are generally of robust construction, they require a
careful treatment prior to installation on site, since they must be carefully packed and
unpacked, without applying any force to the equipment and using suitable tools. Once
supplied, the equipment must be thoroughly inspected to ensure that they have not
undergone shipping damages. If the equipment is not immediately installed upon
reception, they must be stored in places free from dust and moisture, causticity in their
original packing.
• Storage temperature: -10°C + 40°C.
• The equipment must only be stored and carried in the special antistatic bag.
CSC-326 Numerical Transformer Protection Equipment Manual
-72-
10 Ordering
10.1 Ordering data
10.2 Ordering data sample
For example, CSC-326M2_1552WA1, it shows that,
1. Three-winding transformer or auto-transformer,
2. In HV side, rated current of CT is 1A;
3. In MV side, rated current of CT is 5A;
4. In LV side, rated current of CT is 5A;
5. Power is 220V DC;
6. Master Module type, different hardware is 125;
7. Electric Ethernet interface or Fiber Ethernet interface on Master module (2 ports) is A;
8. RS485 interface on Master module is 1.
CSC-326 Numerical Transformer Protection Equipment Manual
-73-
11 Appendix
This appendix is primarily a reference for the experienced user. General diagrams
indicating the terminal connections of the CSC326 models are included. Connection
examples show the proper connections of the device to primary equipment in typical
power system configurations. Tables with all information available in a CSC-326
equipped with all options are provided.
The main contents are as follows:
11.1 Terminal diagrams.
11.2 Connection examples.
11.3 Digital input module.
11.4 Digital output module.
11.5 Communication Protocol.
11.1 Terminal diagrams:
5
1
2
3
4
10
7
6
8
9
12
11
55 I HV2B' I HV2B
3
4
2
1
b a
X3( AI MODULE)
I LVC
I LVA
I LVB
I LVA'
I LVB'
I LVC'
1
2
3
4
b a
X2( AI MODULE)
I MVB'
I MVA'
I MVC'
I MVA
I MVB
I MVC
b a
X1( AI MODULE)
I HV1B'
I HV1A'
I HV1C'
I HV2A'
I HV1B
I HV1A
I HV1C
I HV2A
8
9
7
6
10
11
12
10
7
6
8
9
ULVB
ULVAULVN
ULVC
12
11
UMVC
UMVN UMVA
UMVB
I HV2C' I HV2C
UHVC
UHVN UHVA
UHVB
I LVWC
I LVWA
I LVWB
I LVWA'
I LVWB'
I LVWC'
I REFHVI REFHV'
I REFMVI REFMV'
X4( MASTER MODULE)
232- TRAN
232- RECV
232-GND
485- 1A
485- 1B
485- 2A
GPSGND
LONGND
LON- 1B
LON- 1A
LON- 2B
485- 2B
NOT USED
GPS
NOT USED
12
6
3
12
45
9
78
1011
1314
1615
DC+ I NPUT
X12( POWER)
2
6
4
8
12
10
14
18
16
20
R24V+ OUT
c a
R24V- OUT
DC FAI LURE
24
22
26
30
28
32
DC- I NPUT
14
DC+ I NPUT2
8
4
6
10
12
X6( DI MODULE)
c a
ALARM I
DC- I NPUT
NOT LATCHED
LATCHED
26
20
16
18
22
24
32
28
30
c
c
a
a
OI L LEVEL ALARM
OTI HI GH ALARM
PRD TRI P
OLTC BUCH TRI P
REM ACCESS BLK
RELAY TEST
RESET
I NBKMV' I NBKMV
I NBKHVI NBKHV'
UMV0N UMV0 UHV0N UHV0
DO 1
DO 2
DO 1
DO 2
DO 2
DO 1
DO 2
DO 1
DO 1
DO 2
4
2
8
6
10
14
12
20
18
16
X10( DO MODULE)
c a
26
24
22
28
32
30
DO 2( NOT LATCHED)
DO 1( LATCHED)
DO 2( NOT LATCHED)
DO 1( LATCHED)
DO 2£ NC£ ©
DO 1£ NO£ ©BLK VOL REGU
X8( DO MODULE)
a
DO 1
DO 2
DO 1
DO 2
4
2
6
8
c
DO 2
DO 1
DO 1
DO 2
DO 1
DO 2
12
10
14
16
18
20
DO 322
24
26
28
30
32 FUTURE USE 2 (NC)
HV CB1 ON
HV CB2 ON
MV CB ON
LV BU
MV BU
HV REF ACT
MV REF ACT
DO 1
DO 2
DO 3
DO 1
DI FF
REF
OVERFLUX
HV BU
CBF-1
CBF- 2
CBF- 3
PD-1
PD- 2
PD- 3
FUTURE USE 1
X11( DO MODULE)
2
c
6
4
8
12
10
20
16
18
14
a
22
24
28
30
26
32 LV CB ON
ALARM I I
CT FAI L
DI FF ACT
SI G1 COM1(LATCHED)
SI G1 COM2(LATCHED)
SI G2 COM1( NOT LATCHED)
SI G2 COM2(NOT LATCHED)
SI G3 COM1(NOT LATCHED)
SI G3 COM2(NOT LATCHED)
LON- 2A
NEU DI SP ALARMOVERLOAD
ALARM I I
CT FAI L
VT FAI L
DI FF ACT
BACK ACT
OVERLOAD
ALARM I I
CT FAI L
VT FAI L
DI FF ACT
BACK ACT
NEU DI SP ALARMOVERLOAD
OVERFLUX ACT
OVERFLUX ACT
OVERFLUX ACTVT FAI L
BACK ACT
NEU DI SP ALARM
MV CB STATUS
MV CB PD
HV CB1 PD
HV CB2 PD
HV CB2 STATUS
HV CB1 STATUS
LV CB STATUS
R24V+ I NPUT
R24V- I NPUT
REF OPTD
NOT USED
NOT USED
NOT USED
NOT USED
OTI HI GH TRI P
WTI HI GH ALARM
WTI HI GH TRI P
BUCH ALARM
TRAFO/ BUCH TRI P
Fig. 28: CSC-326 Terminal diagram on the rear board (Model 2)
74
5
1
2
3
4
10
7
6
8
9
12
11
5 I HV2B' I HV2B
3
4
2
1
b a
X3( AI MODULE)
I LVC
I LVA
I LVB
I LVA'
I LVB'
I LVC'
b a
X1( AI MODULE)
I HV1B'
I HV1A'
I HV1C'
I HV2A'
I HV1B
I HV1A
I HV1C
I HV2A
8
9
7
6
10
11
12
ULVB
ULVAULVN
ULVC
I HV2C' I HV2C
UHVC
UHVN UHVA
UHVB
I REFHVI REFHV'
X4(MASTER MODULE)
232-TRAN
232-RECV
232-GND
485- 1A
485- 1B
485- 2A
GPSGND
LONGND
LON-1B
LON-1A
LON-2B
485- 2B
NOT USED
GPS
NOT USED
12
6
3
12
45
9
78
1011
1314
1615
DC+ I NPUT
X12(POWER)
2
6
4
8
12
10
14
18
16
20
R24V+ OUT
c a
R24V- OUT
DC FAI LURE
24
22
26
30
28
32
DC- I NPUT
14
DC+ I NPUT2
8
4
6
10
12
X6( DI MODULE)
c a
ALARM I
DC- I NPUT
NOT LATCHED
LATCHED
26
20
16
18
22
24
32
28
30
c
c
a
a
REM ACCESS BLK
RELAY TEST
RESET
I NBKHVI NBKHV'
UHV0N UHV0
DO 1
DO 2
DO 1
DO 2
DO 2
DO 1
DO 2
DO 1
DO 1
DO 2
4
2
8
6
10
14
12
20
18
16
X10(DO MODULE)
c a
26
24
22
28
32
30
DO 2(NOT LATCHED)
DO 1(LATCHED)
DO 2(NOT LATCHED)
DO 1(LATCHED)
DO 2£ NC£ ©
DO 1£ NO£ ©BLK VOL REGU
X8(DO MODULE)
a
DO 1
DO 2
DO 1
DO 2
4
2
6
8
c
DO 2
DO 1
DO 1
DO 2
DO 1
DO 2
12
10
14
16
18
20
DO 322
24
26
28
30
32 FUTURE USE 2 (NC)
HV CB1 ON
HV CB2 ON
LV CB ON
LV BU
NOT USED
HV REF ACT
LV REF ACT
DO 1
DO 2
DO 3
DO 1
DI FF
REF
OVERFLUX
HV BU
CBF- 1
CBF-2
CBF-3
PD-1
PD-2
PD-3
FUTURE USE 1
X11(DO MODULE)
2
c
6
4
8
12
10
20
16
18
14
a
22
24
28
30
26
32 NOT USED
ALARM I I
CT FAI L
DI FF ACT
SI G1 COM1( LATCHED)
SI G1 COM2( LATCHED)
SI G2 COM1( NOT LATCHED)
SI G2 COM2( NOT LATCHED)
SI G3 COM1( NOT LATCHED)
SI G3 COM2( NOT LATCHED)
LON- 2A
NEU DI SP ALARMOVERLOAD
ALARM I I
CT FAI L
VT FAI L
DI FF ACT
BACK ACT
OVERLOAD
ALARM I I
CT FAI L
VT FAI L
DI FF ACT
BACK ACT
NEU DI SP ALARMOVERLOAD
OVERFLUX ACT
OVERFLUX ACT
OVERFLUX ACTVT FAI L
BACK ACT
NEU DI SP ALARM
NOT USED
NOT USED
HV CB1 PD
HV CB2 PD
HV CB2 STATUS
HV CB1 STATUS
LV CB STATUS
R24V+ I NPUT
R24V- I NPUT
NOT USED
NOT USED
NOT USED
REF OPTD
NOT USED
I REFLVI REFLV'
I NBKLVI NBKLV'OI L LEVEL ALARM
OTI HI GH ALARM
PRD TRI P
OLTC BUCH TRI P
OTI HI GH TRI P
WTI HI GH ALARM
WTI HI GH TRI P
BUCH ALARM
TRAFO/ BUCH TRI P
Fig. 29: CSC-326 Terminal diagram on the rear board (Model 1)
11.2 Connection Examples
Figure 30 illustrates the recommended standard connection for two-winding
transformers. Figure 31 illustrates the recommended standard connection for three-
winding transformers.
Differential protection embraces protection of the high voltage side and low
voltage side of the transformer cable. The permissible cable length and the CT design
(permissible load) are mutually dependent. Recalculation is advisable as for lengths of
more than 100m.
75
Typical connection 1:
2a
3a
2b
3b
IHVA1a 1b
7a 7b
8a 8bINBKHV
IHVB
IHVC
2a
3a
2b
3b
ILVA1a 1b
ILVB
ILVC
A B C
A B C
UHVA 11a
10a
10b
11b
9a
9b
UHVB
UHVC
UHVN
UHV0
UHV0N
ULVA11a
10a
10b
11b
ULVB
ULVC
ULVN
AI1
AI3
IREFHV
Transformermodule
Transformermodule
Fig. 30: Typical connection example for two-winding transformer.
76
Typical connection 2:
2a
3a
2b
3b
IHA 1a 1b
IHB
IHC
A B C
A B C
UHA 11a
10a
10b
11b
9a
9b
UHB
UHC
UHN
UH0
UH0N
UL1A11a
10a
10b
11b
UL1B
UL1C
UL1N
AI1
AI3Transformermodule
Transformermodule
AI2Transformermodule
2a
3a
2b
3b
1a 1bIMA
IMB
A B C
IMC
UMA
11a
10a
10b
11b
9a
9b
UMB
UMC
UMN
UM0
UM0N
2a
3a
2b
3b
IL1A1a 1b
IL1B
IL1C
4a 4b
5a 5b
AI2Transformermodule
IH0
IHJX
IMJ
6b6aIM0
7b7a
Fig. 31: Typical connection example for three-winding transformer.
77
11.3 Digital input module
14
DC+ I NPUT2
8
4
6
10
12
X6( DI MODULE)
c a
ALARM I
DC- I NPUT
NOT LATCHED
LATCHED
26
20
16
18
22
24
32
28
30
c
c
a
a
OI L LEVEL ALARM
OTI HI GH ALARM
PRD TRI P
OLTC BUCH TRI P
REM ACCESS BLK
RELAY TEST
RESET
MV CN STATUS
MV CB PD
HV CB1 PD
HV CB2 PD
HV CB2 STATUS
HV CB1 STATUS
LV CB STATUS OTI HI GH TRI P
WTI HI GH ALARM
WTI HI GH TRI P
BUCH ALARM
TRAFO BUCH TRI P
R24V+ I NPUT
R24V- I NPUT
REF OPTD
t o X12 a20/ c20/ a22/ c22
t o X12 a26/ c26/ a28/ c28
t o X12 a2/ c2/ a4/ c4
t o X12 a8/ c8/ a10/ c10/ a12/ c12
Di gi t al i nput - gr oup 0, No 0
Di gi t al i nput - gr oup 0, No 1
Di gi t al i nput - gr oup 0, No 2
Di gi t al i nput - gr oup 0, No 3
Di gi t al i nput - gr oup 0, No 4
Di gi t al i nput - gr oup 0, No 5
Di gi t al i nput - gr oup 0, No 6
Di gi t al i nput - gr oup 0, No 7
Di gi t al i nput - gr oup 1, No 0
Di gi t al i nput - gr oup 1, No 1
Di gi t al i nput - gr oup 1, No 2
Di gi t al i nput - gr oup 1, No 3
Di gi t al i nput - gr oup 1, No 4
Di gi t al i nput - gr oup 1, No 5
Di gi t al i nput - gr oup 1, No 6
Di gi t al i nput - gr oup 1, No 7
Di gi t al i nput - gr oup 2, No 0
Di gi t al i nput - gr oup 2, No 1
Di gi t al i nput - gr oup 2, No 2
Di gi t al i nput - gr oup 2, No 3
Di gi t al i nput - gr oup 2, No 4
Di gi t al i nput - gr oup 2, No 5
Di gi t al i nput - gr oup 2, No 6
Di gi t al i nput - gr oup 2, No 7 NOT USED
NOT USED
NOT USED
NOT USED
Fig. 32: Connection for digital input module.
11.4 Digital output module
X8( DO MODULE)
a
DO 1
DO 2
DO 1
DO 2
4
2
6
8
c
DO 2
DO 1
DO 1
DO 2
DO 1
DO 2
12
10
14
16
18
20
DO 322
24
26
28
30
32 FUTURE USE 2 (NC)
DO 1
DO 2
DO 3
DO 1
DI FF
REF
OVERFLUX
HV BU
CBF- 1
CBF- 2
CBF- 3
PD-1
PD- 2
PD- 3
FUTURE USE 1
2c 2a
4c 4a
6c 6a
8c 8a
10c 10a
12c 12a
14c 14a
16c 16a
18c 18a
20c 20a
22c 22a
24c 24a
26c 26a
28c 28a
30c 30a
32c 32a
ever y cont act i s separ at e.
Fig. 33: Connection for digital output module (X8 module)
78
DO 1
DO 2
DO 1
DO 2
DO 2
DO 1
DO 2
DO 1
DO 1
DO 2
4
2
8
6
10
14
12
20
18
16
X10( DO MODULE)
c a
26
24
22
28
32
30
DO 2( NOT LATCHED)
DO 1( LATCHED)
DO 2( NOT LATCHED)
DO 1( LATCHED)
DO 2£ NC£ ©
DO 1£ NO£ ©BLK VOL REGU
HV CB1 ON
HV CB2 ON
MV CB ON
LV BU
MV BU
HV REF ACT
MV REF ACT
6c 6a
8c 8a
10c 10a
12c 12a
14c 14a
16c 16a
18c 18a
20c 20a
22c 22a
24c 24a
26c 26a
28c 28a
30c 30a
32c 32a
2c 2a
4c 4aa r el ay, t wo cont act s
a r el ay, t wo cont act s
a r el ay, t wo cont act s
a r el ay, t wo cont act s
a r el ay, t wo cont act s
a r el ay, t wo cont act s
a r el ay, t wo cont act s
a r el ay, t wo cont act s
Fig. 34: Connection for digital output module(X10 module).
X11(DO MODULE)
2
c
6
4
8
12
10
20
16
18
14
a
22
24
28
30
26
32 LV CB ON
ALARM I I
CT FAI L
DI FF ACT
SI G1 COM1( LATCHED)
SI G1 COM2( LATCHED)
SI G2 COM1(NOT LATCHED)
SI G2 COM2( NOT LATCHED)
SI G3 COM1(NOT LATCHED)
SI G3 COM2( NOT LATCHED)
NEU DI SP ALARMOVERLOAD
ALARM I I
CT FAI L
VT FAI L
DI FF ACT
BACK ACT
OVERLOAD
ALARM I I
CT FAI L
VT FAI L
DI FF ACT
BACK ACT
NEU DI SP ALARMOVERLOAD
OVERFLUX ACT
OVERFLUX ACT
OVERFLUX ACTVT FAI L
BACK ACT
NEU DI SP ALARM
8a
10a
4a
6a
2a
18a
20a
14a
16a
28a
30a
24a
26a
12a
22a
8c
10c
4c
6c
2c
18c
20c
14c
16c
28c
30c
24c
26c
12c
22c
32c 32a
2a/ 12a/ 22a, onl y a r el ay, t hr ee cont act s2c/ 12c/ 22c, onl y a r el ay, t hr ee cont act s
Fig. 35: Connection for digital output module(X11 module).
79
11.5 Communication Protocol
Table 45: Communication protocol
Front port for communication
Connection type electric COM port
Communication protocol Interior communication protocol
Type of connector DB9 pin connector
Speed of communication 9600 bps
Rear port for local /
remote communication
only local communication
Connection type RS-232;Ethernet;RS-485
Communication protocol CSC2000
Medium of connection electric
Type of connectorRS-232:DB25 connector;Ethernet:RJ45;RS-485:twisted-pair
Speed of communicationRS-232:9600bps; Ethernet:10/100Mbps adaptable; RS-485:9600bps~38400bps
Isolation Yes
Dielectric level III
Maximum cable length RS-232:10m;Ethernet:110m ;RS-485:1.2km
Type of port required atPC end
Ethernet:RJ45;RS-485:COM port
Functions supported bythis port
RS-232:Print setting, fault report, waveform reportEthernet&RS-485:see above 12 m)
Rear port for substation automation
Connection type 3 Ethernet port;2 RS-485; 2 Lon works
Communication protocolCSC2000 or IEC 60870-5-103 or IEC 61850 for Ethernetport or RS-485; CSC2000 for Lon works
Medium of connectionEthernet port: optics/electric ;RS-485:electric;Lonworks:electric
Type of connectorEthernet port:(SC/ST)/RJ45 ; RS-485:twisted-pair;Lonworks: twisted-pair
Speed of communicationEthernet port:10/100Mbps adaptable ; RS-85:9600bps;Lonworks:78kbps
Maximum cable lengthEthernet port(optics/electric):110m/2km ; RS-485:1.2km; Lonworks:1.3km
Optical wavelength 850nm;1300nm
Permissible lineattenuation
15dB
Type of port required atPC end
Ethernet port; COM port
Standard IEC 60870-5-103; IEC 61850
80