Gear Drive Centrifugal Chiller Job01 Tag CVGF-1 CVGF0500 1 Certified in accordance with the Water-Chilling Packages Using the Vapor Compression Cycle Certification Program, which is based on AHRI Standard 550/590. Sound pressure measured in accordance with AHRI Standard 575-94. CVGF Model Evap tube type TECU Compressor size 500 0.025 Evap tube thickness Motor size 316 2 Pass Evaporator water box pass Motor frequency 60 Hz 700 Cond shell size Motor voltage 380 C Cond bundle size Impeller size 920 IECU Cond tube type Orifice size 23 0.028 Cond tube thickness 700 Evap shell size 2 A Evap bundle size Gross capacity 500.00 tons R134a refrigerant charge 397 kg Primary power 285.90 kW Shipping weight 10141 kg 0.163 kW/kW Gross efficiency Operating weight 11768 kg Sound level IPLV 0.155 kW/kW Wye-delta starter type Unit Mounted WD 44.00 F Evap leaving temp Cond entering temp 85.00 F 75.70 L/s Evap flow rate 94.62 L/s Cond flow rate 53.95 F Evap entering temp 94.28 F Cond leaving temp 2.40 gpm/ton Evap flow/capacity 3.00 gpm/ton Cond flow/capacity Evap water box type Non-marine Non-marine Cond water box type 59.0 kPa Evap pressure drop 27.4 kPa Cond pressure drop Evap water box pressure 150 psi Cond water box pressure 150 psi 0.017600 m2-deg C/kW Evap fouling factor 0.044000 m2-deg C/kW Cond fouling factor Water Evap fluid type Water Cond fluid type N/A Evap fluid concentration N/A Cond fluid concentration Motor LRA 3162.00 A Minimum circuit ampacity 604.35 A Unit rated load amps 480.30 A Maximum over current protection 1000.00 A 22-May-2013 59049.00 E Selection code revision level 31.7.0.0 Product Version

Upload: juan-yenque

Post on 10-Feb-2016

16 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: CVGF 500tr Selection at AHRI Condition

Gear Drive Centrifugal Chiller

Job01

Tag CVGF-1 CVGF0500

1

Certified in accordance with the Water-Chilling Packages Using the Vapor Compression Cycle Certification Program, which is

based on AHRI Standard 550/590.

Sound pressure measured in accordance with AHRI Standard 575-94.

CVGFModel Evap tube type TECU

Compressor size 500 0.025Evap tube thickness

Motor size 316 2 PassEvaporator water box pass

Motor frequency 60 Hz 700Cond shell size

Motor voltage 380 CCond bundle size

Impeller size 920 IECUCond tube type

Orifice size 23 0.028Cond tube thickness

700Evap shell size 2

AEvap bundle size

Gross capacity 500.00 tons R134a refrigerant charge 397 kg

Primary power 285.90 kW Shipping weight 10141 kg

0.163 kW/kWGross efficiency Operating weight 11768 kg

Sound levelIPLV 0.155 kW/kW

Wye-delta starter type Unit Mounted WD

44.00 FEvap leaving temp Cond entering temp 85.00 F

75.70 L/sEvap flow rate 94.62 L/sCond flow rate

53.95 FEvap entering temp 94.28 FCond leaving temp

2.40 gpm/tonEvap flow/capacity 3.00 gpm/tonCond flow/capacity

Evap water box type Non-marine Non-marineCond water box type

59.0 kPaEvap pressure drop 27.4 kPaCond pressure drop

Evap water box pressure 150 psi Cond water box pressure 150 psi

0.017600 m2-deg C/kWEvap fouling factor 0.044000 m2-deg C/kWCond fouling factor

WaterEvap fluid type WaterCond fluid type

N/AEvap fluid concentration N/ACond fluid concentration

Motor LRA 3162.00 A Minimum circuit ampacity 604.35 A

Unit rated load amps 480.30 A Maximum over current protection 1000.00 A

22-May-2013 59049.00 EachSelection code revision level31.7.0.0Product Version