![Page 1: Data Center Predictive Modeling - cfroundtable.orgData Center Predictive Modeling ... •CFO telling me cloud computing means zero capex and flexible right-sized opex. 3 What are others](https://reader030.vdocument.in/reader030/viewer/2022040906/5e7b5209f3986c5899143d1a/html5/thumbnails/1.jpg)
11
Data Center Predictive ModelingHow to minimize TCO through system level optimization
Jim Rodriguez – GM Americas
![Page 2: Data Center Predictive Modeling - cfroundtable.orgData Center Predictive Modeling ... •CFO telling me cloud computing means zero capex and flexible right-sized opex. 3 What are others](https://reader030.vdocument.in/reader030/viewer/2022040906/5e7b5209f3986c5899143d1a/html5/thumbnails/2.jpg)
22
What’s happening out there?...
• Increasingly dynamic environment
• Interdependency accelerates complexity
• Spiraling energy costs
• Regulatory compliance and governance
• CFO telling me cloud computing means zero capex and flexible right-sized opex
![Page 3: Data Center Predictive Modeling - cfroundtable.orgData Center Predictive Modeling ... •CFO telling me cloud computing means zero capex and flexible right-sized opex. 3 What are others](https://reader030.vdocument.in/reader030/viewer/2022040906/5e7b5209f3986c5899143d1a/html5/thumbnails/3.jpg)
33
What are others are saying?.... “Energy costs are the fastest-rising cost element in the data center portfolio, and yet data center managers are still not paying sufficient attention to the process of measuring, monitoring and modeling energy use in data centers.”
Rakesh Kumar, research vice president at Gartner.
“The lifecycles of data centers are getting shorter and shorter. The needs of today’s data centers are much more complex than they were twenty five or even five years ago.”
Lisa Richarde - Data Center Journal
![Page 4: Data Center Predictive Modeling - cfroundtable.orgData Center Predictive Modeling ... •CFO telling me cloud computing means zero capex and flexible right-sized opex. 3 What are others](https://reader030.vdocument.in/reader030/viewer/2022040906/5e7b5209f3986c5899143d1a/html5/thumbnails/4.jpg)
444
Data Center Predictive Modelling – A Solution?
•Modeling is not new!
•Modeling can help when things get complex
•Modeling can help create detailed future energy and data costs
•Modeling can provide advanced energy‐planning and accounting capabilities
•Enable thousands of man‐hour analyses to be run in minutes
•Avoid disruption of business operations
![Page 5: Data Center Predictive Modeling - cfroundtable.orgData Center Predictive Modeling ... •CFO telling me cloud computing means zero capex and flexible right-sized opex. 3 What are others](https://reader030.vdocument.in/reader030/viewer/2022040906/5e7b5209f3986c5899143d1a/html5/thumbnails/5.jpg)
55
How does it work?
![Page 6: Data Center Predictive Modeling - cfroundtable.orgData Center Predictive Modeling ... •CFO telling me cloud computing means zero capex and flexible right-sized opex. 3 What are others](https://reader030.vdocument.in/reader030/viewer/2022040906/5e7b5209f3986c5899143d1a/html5/thumbnails/6.jpg)
66
Simulation Modeling
6
![Page 7: Data Center Predictive Modeling - cfroundtable.orgData Center Predictive Modeling ... •CFO telling me cloud computing means zero capex and flexible right-sized opex. 3 What are others](https://reader030.vdocument.in/reader030/viewer/2022040906/5e7b5209f3986c5899143d1a/html5/thumbnails/7.jpg)
77
PUE is not a single number for a data center
![Page 8: Data Center Predictive Modeling - cfroundtable.orgData Center Predictive Modeling ... •CFO telling me cloud computing means zero capex and flexible right-sized opex. 3 What are others](https://reader030.vdocument.in/reader030/viewer/2022040906/5e7b5209f3986c5899143d1a/html5/thumbnails/8.jpg)
88
Financial outputs
8
![Page 9: Data Center Predictive Modeling - cfroundtable.orgData Center Predictive Modeling ... •CFO telling me cloud computing means zero capex and flexible right-sized opex. 3 What are others](https://reader030.vdocument.in/reader030/viewer/2022040906/5e7b5209f3986c5899143d1a/html5/thumbnails/9.jpg)
99
![Page 10: Data Center Predictive Modeling - cfroundtable.orgData Center Predictive Modeling ... •CFO telling me cloud computing means zero capex and flexible right-sized opex. 3 What are others](https://reader030.vdocument.in/reader030/viewer/2022040906/5e7b5209f3986c5899143d1a/html5/thumbnails/10.jpg)
1010
An example simulation model
Base Scenario• 3.5 MW design IT capacity
• 2N+1 Infrastructure
• Running at 90% of rated capacity
• Using the old ASHRAE spec (45-55% RH)
• Poor airflow management
• No power management
• No virtualization
![Page 11: Data Center Predictive Modeling - cfroundtable.orgData Center Predictive Modeling ... •CFO telling me cloud computing means zero capex and flexible right-sized opex. 3 What are others](https://reader030.vdocument.in/reader030/viewer/2022040906/5e7b5209f3986c5899143d1a/html5/thumbnails/11.jpg)
1111
An example simulation model
Base Scenario
• Located in Europe
• Chilled water / Dry cooler design
• Power cost of $0.08/kWh rising to $0.10/kWh
• Carbon intensity of 0.573kg / kWh
![Page 12: Data Center Predictive Modeling - cfroundtable.orgData Center Predictive Modeling ... •CFO telling me cloud computing means zero capex and flexible right-sized opex. 3 What are others](https://reader030.vdocument.in/reader030/viewer/2022040906/5e7b5209f3986c5899143d1a/html5/thumbnails/12.jpg)
1212
Scenario 1 – Implement Best Practice
• Airflow management (aisle containment)
• Variable Frequency Drives in the CRAC units
• New ASHRAE spec
• Enable power management on servers
![Page 13: Data Center Predictive Modeling - cfroundtable.orgData Center Predictive Modeling ... •CFO telling me cloud computing means zero capex and flexible right-sized opex. 3 What are others](https://reader030.vdocument.in/reader030/viewer/2022040906/5e7b5209f3986c5899143d1a/html5/thumbnails/13.jpg)
1313
Scenario 2 – Implement Economizer
• Airflow management (aisle containment)
• Variable Speed Drives in the CRAC units
• New ASHRAE spec
• Enable power management on servers
• Implement an indirect waterside economizer
![Page 14: Data Center Predictive Modeling - cfroundtable.orgData Center Predictive Modeling ... •CFO telling me cloud computing means zero capex and flexible right-sized opex. 3 What are others](https://reader030.vdocument.in/reader030/viewer/2022040906/5e7b5209f3986c5899143d1a/html5/thumbnails/14.jpg)
1414
Results Comparison
4-Year Cost / Energy / Carbon Analysis
Scenario Energy (GWh)
Carbon (Tons) Energy Cost
Base 231 122,000 $43.4m
Implement Best Practices
168 89,000 $31.6m
Add Economizer 147 78,000 $30.2m
Savings 84 44,000 $12.7m