data sheet plate heat exchanger xgm050...xgm050 is a gasketed plate heat exchanger, which will be...
TRANSCRIPT
-
© Danfoss | 2019.02 VD.JQ.B3.02 | 1
Plate Heat ExchangerXGM050
Data sheet
Description
Micro Plate Heat Exchangers - a revolutionarytechnology from Danfoss.Characterized by their unique plate pattern,MPHEs enable heat to be transferred moreefficient than any previous model of heatexchangers.
Ordering
Tailor made ordering1-pass/2-pass gasketed heat exchanger type XGM050• The heat exchanger shall be ordered at a Danfoss sales company or at Danfoss Kamnik.• Tailor Made orders: the code will created when contacting Danfoss Kamnik.• With the order please attach the Hexact Datasheet, Punchlist, Plate Arrangement Drawing and
BOM.
For further details please contact Danfoss sales representative.
XGM 050 H – 1 – 10
Number of plates Number of Passes (1 = 1-pass)
Channel type (L-M-H)
Connection size (DN 50)
Micro plate™ plates
Gasketed heat exchanger
Benefits:• Energy and cost savings• Better heat transfer• Lower pressure loss• Longer life time
more on: MPHE.danfoss.com
XGM050 is a gasketed plate heat exchanger, which will be available in plate corrugation H, M and L. It will be available in 1-pass (with 4 connections) and 2-pass version (with 6 connections). Heat exchangers can be dimensioned in Danfoss calculation software “Hexact” which can be downloaded from MPHE.danfoss.com.
Main data:• Min. temperature −10 °C• Max. temperature 150 °C• Max. working pressure 16 bar
(10&25 bar on request)• Circulation water / glycolic water up to 50 %• Connection size G 2A or DN 50
Approvals:• Pressure Equipment Directive (PED)• GOST/Russia
-
Data sheet XGM050
2 | VD.JQ.B3.02 © Danfoss | 2019.02
Accessories - Insulation (Aluminium stucco and mineral wool)
Type coverage (plate number)Code No.
L H&M
10-20 10-28 004H4230
21-48 29-70 004H4231
49-76 71-110 004H4232
77-104 112-150 004H4233
105-132 152-190 004H4234
133-162 192-232 004H4235
163-190 234-272 004H4236
Note: Aluminium stucco and mineral wool insulation can be used for 1-pass and 2-pass version
Accessories - Insulation (Coated steel sheet and polyester insulation)
Type coverage (plate number)Code No.
L H&M
10-20 10-28 004H4270
21-48 29-70 004H4271
49-76 71-110 004H4272
77-104 111-150 004H4273
105-132 152-190 004H4274
133-162 192-232 004H4275
163-200 234-272 004H4276
Note: Coated steel sheet and polester insulation can be used for 1-pass. (2-pass versions are available on enquiry)
Ordering (continuous) 1-pass gasketed heat exchanger XGM050
Picture No of plates(n)
ConnectionXGM050H XGM050M XGM050L
Code no.
20
Thread G2"
079B0050 079B0069 079B0088
30 079B0051 079B0070 079B0089
40 079B0052 079B0071 079B0090
50 079B0053 079B0072 079B0091
60 079B0054 079B0073 079B0092
70 079B0055 079B0074 079B0093
80 079B0056 079B0075 079B0094
90 079B0057 079B0076 079B0095
100 079B0058 079B0077 079B0096
110 079B0059 079B0078 079B0097
120 079B0060 079B0079 079B0098
130 079B0061 079B0080 079B0099
140 079B0062 079B0081 079B0100
150 079B0063 079B0082 079B0101
160 079B0064 079B0083 079B0102
170 079B0065 079B0084 079B0103
180 079B0066 079B0085 079B0104
190 079B0067 079B0086 079B0105
200 079B0068 079B0087 -
Note: brackets has to be ordered separately
1-pass gasketed heat exchanger XGM050
Picture No of plates(n)
ConnectionXGM050H XGM050M XGM050L
Code no.
20
Flange DN50
079B1031 079B1050 079B1069
30 079B1032 079B1051 079B1070
40 079B1033 079B1052 079B1071
50 079B1034 079B1053 079B1072
60 079B1035 079B1054 079B1073
70 079B1036 079B1055 079B1074
80 079B1037 079B1056 079B1075
90 079B1038 079B1057 079B1076
100 079B1039 079B1058 079B1077
110 079B1040 079B1059 079B1078
120 079B1041 079B1060 079B1079
130 079B1042 079B1061 079B1080
140 079B1043 079B1062 079B1081
150 079B1044 079B1063 079B1082
160 079B1045 079B1064 079B1083
170 079B1046 079B1065 079B1084
180 079B1047 079B1066 079B1085
190 079B1048 079B1067 079B1086
200 079B1049 079B1068 -
Note: brackets has to be ordered separately, linings are not included, counter flange is included.
-
Data sheet XGM050
VD.JQ.B3.02 | 3© Danfoss | 2019.02
Ordering (continuous) Accessories - TailpiecesPicture Description Connection Code No. 1)
Solder tailpieces
G 2 / 28 mm 004B2910
G 2 / 35 mm 004B2911
G 2 / 42 mm 004B2912
Weld-on tailpieces
G 2 / DN 32 004B2907
G 2 / DN 40 004B2908
G 2 / DN 50 004B2909
1) One set contains 2 tailpieces with union nuts and gaskets.
Accessories - EPDM GasketType Code No. 1)
Gasket for XGM050L, I-p* 10 pcs 079H9032
Gasket for XGM050L, I-p* 250 pcs 079H9033
Gasket for XGM050H&M, I-p* 10 pcs 079H9034
Gasket for XGM050H&M, I-p* 250 pcs 079H9035
1) sets of 10 & 250* I-p: Industrial pack
Accessories - Plates for XGM050, (Material 1.4404) PN16
Type Code No. 1)
Plates XGM050H 1.4404, I-p* 10 pcs 004H4242
Plates XGM050M 1.4404, I-p* 10 pcs 004H4243
Plates XGM050L 1.4404, I-p* 10 pcs 004H4244
Plates XGM050H 1.4404, I-p* 250 pcs 004H4245
Plates XGM050M 1.4404, I-p* 250 pcs 004H4246
Plates XGM050L 1.4404, I-p* 250 pcs 004H4247
1) sets of 10 & 250* I-p: Industrial pack
Accessories - Special plate set(Material: 1.4404) PN16
Type Description Code No.
XGM050H: spec. plates 1-pass versions, including gasketsSets of 1 front and 1 back plate for 1 pass
versions including EPDM gaskets
079H9039
XGM050M: spec. plates 1-pass versions, including gaskets 079H9040
XGM050L: spec. plates 1-pass versions, including gaskets 079H9041
XGM050H: spec. plates 2-pass versions, including gaskets Sets of 1 front, 1 back and 1 middle plates
for 2 pass versions including EPDM gaskets
079H9045
XGM050M: spec. plates 2-pass versions, including gaskets 079H9046
XGM050L: spec. plates 2-pass versions, including gaskets 079H9047
Accessories - Other spare partsType Code No.
Linings XGM050 PN16 EPDM I-Pack, 4 Pcs 004H4263
Linings XGM050 PN25 EPDM I-Pack, 4 Pcs 004H4266
O-rings for XGM050 flanges I-Pack 10Pcs 004H4265
Accessories - BracketPicture Code No.
004H4237
NOTE: Bracket set is not included in HEX please order it separately. Set contain 2 pcs of bracket/legs.
-
Data sheet XGM050
4 | VD.JQ.B3.02 © Danfoss | 2019.02
T11
T21
T12
T22
T11
T112
T212
T12
T21
T22
Technical data Heat exchanger XGM050Type XGM050L XGM050M XGM050H
Max. working pressure PN (bar) 10, 16, 25
Max. operating temperatureoC
150
Min. operating temperature −10
Flow medium Circulation water/glycolic water up to 50 %
Volume / Channel Ltr 0.395 0.254 0.254
Connection typeCylindrical external thread acc. to DIN ISO 228/1 or
Compact flanges DN 50 EN 1.4404 1)
Connection size G 2 or DN 50
Materials
Plate Stainless steel, EN 1.4404 (AISI 316L) & EN 1.4301 (AISI 304)
Liners in connections EPDM
Gasket type Glue free
Gasket material EPDM
1) Counter flange is included.
Insulation properties
Type Aluminium stucco and mineral wool Coated steel sheet and polyester insulation
Heat conductivity, λ W/mK 0.035 0.045
Max temperature
Permanent°C
150 150
Short term peak 180 180
Wall thickness mm 65 25
Design and function
T11 - Primary side inT12 - Primary side outT112 - Primary side second inlet (2-pass)T21 - Secondary side inT22 - Secondary side outT212 - Secondary side second inlet (2- pass)
Danfoss 2 pass heat exchanger are made with 6 connections, as they are primarily used to heat tap water.
There is one additional connection to allow circulation of hot water and one connection to connect and extract heat from return water from heating heat exchanger.
Connections T112 and T212 can be blocked if they are not used.
-
Data sheet XGM050
VD.JQ.B3.02 | 5© Danfoss | 2019.02
L±5
18±0.5
B±2
18±0.5
Sizing XGM050 can be calculated in latest version of Danfoss calculation software “Hexact” which can be downloaded from hexact.danfoss.com.
Mounting The heat exchanger must be mounted in vertical position. Prepare the foundation for the heat exchanger if necessary, always according to local regulations. It is recommended that all pipes connected to the heat exchanger are equipped with shut-off valves for maintenance purposes.
The pipes to be connected must be mounted so that the strain caused by the thermal expansion, for instance, does not harm the heat exchanger.
The pipes must be equipped with brackets to prevent any torsional stress concentration at the heat exchanger’s pipe connections.
It is recommended that the heat exchanger is equipped with insulation.
A safety valve must be installed between the heat exchanger and the shut-off valves on the secondary side of the heat exchanger. If the safety valve is not installed, thermal expansion of fluid might destroy the heat exchanger when the shut-off valves are closed.
Dimensions 1)
XGM050H&M PN16 1)
Plate range L BWeight
(kg)
10-28 395
264
89.3 + 0.444 × n
29-70 545 90.6 + 0.444 × n
71-110 695 91.9 + 0.444 × n
111-140 845 93.2 + 0.444 × n
141-180 995 94.5 + 0.444 × n
181-200 1145 95.8 + 0.444 × n
1) Dimensions for PN 10 & 25 version can be extract from Hexact in tab “Dimensional data”.
XGM050L PN16 1)
Plate range L BWeight
(kg)
10-20 395
264
89.3 + 0.495 × n
21-48 545 90.6 + 0.495 × n
49-76 695 91.9 + 0.495 × n
77-104 845 93.2 + 0.495 × n
105-132 995 94.5 + 0.495 × n
133-162 1145 95.8 + 0.495 × n
163-190 1295 97.1 + 0.495 × n
-
Data sheet XGM050
6 | VD.JQ.B3.02 © Danfoss | 2019.02
Lmax
A
G D
C
B
E
E
Dimensions (continuous)
Type PN Pass no.Connection
typeA B C D E G Lmax
mm
XGM050 H&M
16
1 Thread G 2" 2 + 2.37 × n
304 127 576 73 765 437.5-1337.5
1 Flange DN 50 0 + 2.37 × n
2 Thread G 2" 5 + 2.37 × n
2 Flange DN 50 1 + 2.37 × n
XGM050L
1 Thread G 2" 2 + 3.57 × n
1 Flange DN 50 0 + 3.57 × n
2 Thread G 2" 5 + 3.57 × n
2 Flange DN 50 1 + 3.57 × n
Note: For block mix solution please refer to Hexact.
-
Data sheet XGM050
VD.JQ.B3.02 | 7© Danfoss | 2019.02
H
B
G
B
H
Insulation (Aluminium stucco and mineral wool)
G B HCode No.
mm
835 444
572.5 004H4230
722.5 004H4231
872.5 004H4232
1022.5 004H4233
1172.5 004H4234
1322.5 004H4235
1472.5 004H4236
G
InsulationCoated steel sheet and polyester insulation
G B HCode No.
mm
795 364
167 004H4270
263 004H4271
354 004H4272
447 004H4273
539 004H4274
636 004H4275
728 004H4276
Dimensions (continuous)
-
© Danfoss | DHS-SRMT/SI | 2019.028 | VD.JQ.B3.02
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in speci�cations already agreed.All trademarks in this material are property of the respective companies. Danfoss and all Danfoss logotypes are trademarks of Danfoss A/S. All rights reserved.