1 Maximum inputs for packaged blower versions are given for the standard combustion air blower without an inlet air filter. 2 For proper performance, this pressure must be kept constant across the burner operating range. 3 See Design Guide 110 for more information about typical fuel composition and properties. 4 All weights are approximate. All information is based on laboratory testing. Different chamber conditions will affect the data. All inputs based upon gross calorific values and standard conditions; 1 atmosphere, 70°F (21°C). Eclipse reserves the right to change the construction and/or configuration of our products at any time without being obliged to adjust earlier supplies accordingly. Parameter Specification Blower Type Chamber Pressure "w.c. (mbar) 50 Hz 60 Hz Maximum Input, Btu/h (kW) 1 Contact factory for chamber pressures outside the given range, or varying chamber pressure conditions. -5.0 (-12.4) 3,500,000 (1020) 3,550,000 (1040) -2.0 (-5.0) 3,170,000 (920) 3,220,000 (940) 0 (0.0) 2,950,000 (860) 3,000,000 (880) 2.0 (5.0) 2,690,000 (780) 2,740,000 (800) 5.0 (12.4) 2,250,000 (660) 2,300,000 (670) Minimum Input On-Ratio, Btu/h (kW) Lower inputs may be achieved. Contact factory. 65,000 (19) Main Gas Inlet Pressure, "w.c. (mbar) 2 Fuel pressure at ratio regulator inlet Natural Gas 20 to 55 (50 to 140) Propane/Butane 20 to 35 (50 to 90) High Fire Flame Length, inches (mm) Measured from the outlet end of the combustor Natural Gas 60 (1524) Propane/Butane 65 (1650) Maximum Chamber Temperature, °F (°C) Alloy Tube 1500 (815) Block and Holder 1900 (1038) Flame Detection Alloy Tube Flamerod or UV Scanner Block and Holder UV scanner only Fuel For any other mixed gas, contact Eclipse, Inc. Natural Gas, Propane, Butane 3 Blower Motor Power, Hp 1.5 Weight, lbs (kg) 4 Alloy Tube 90 (41) Refractory 214 (97) Approvals Eclipse RatioMatic Burners Model RM0300 Datasheet 110-5 8/22/2012 Version 5

Upload: lekhanh

Post on 25-Feb-2018

221 views

Category:

Documents


3 download

TRANSCRIPT

Eclipse RatioMaticBurners

Model RM0300

Datasheet 110-58/22/2012

Version 5

1 Maximum inputs for packaged blower versions are given for the standard combustion air blower without an inlet airfilter.

2 For proper performance, this pressure must be kept constant across the burner operating range.3 See Design Guide 110 for more information about typical fuel composition and properties.4 All weights are approximate.• All information is based on laboratory testing. Different chamber conditions will affect the data.• All inputs based upon gross calorific values and standard conditions; 1 atmosphere, 70°F (21°C).• Eclipse reserves the right to change the construction and/or configuration of our products at any time without being

obliged to adjust earlier supplies accordingly.

Parameter SpecificationBlower Type Chamber Pressure

"w.c. (mbar) 50 Hz 60 Hz

Maximum Input, Btu/h (kW)1

Contact factory for chamber pressures outside the given range, or varying chamber pressure conditions.

-5.0 (-12.4) 3,500,000 (1020) 3,550,000 (1040)-2.0 (-5.0) 3,170,000 (920) 3,220,000 (940)

0 (0.0) 2,950,000 (860) 3,000,000 (880)2.0 (5.0) 2,690,000 (780) 2,740,000 (800)5.0 (12.4) 2,250,000 (660) 2,300,000 (670)

Minimum Input On-Ratio, Btu/h (kW)Lower inputs may be achieved. Contact factory. 65,000 (19)

Main Gas Inlet Pressure, "w.c. (mbar)2Fuel pressure at ratio regulator inlet

Natural Gas 20 to 55 (50 to 140)Propane/Butane 20 to 35 (50 to 90)

High Fire Flame Length, inches (mm)Measured from the outlet end of the combustor

Natural Gas 60 (1524)Propane/Butane 65 (1650)

Maximum Chamber Temperature, °F (°C) Alloy Tube 1500 (815)Block and Holder 1900 (1038)

Flame Detection Alloy Tube Flamerod or UV ScannerBlock and Holder UV scanner only

FuelFor any other mixed gas, contact Eclipse, Inc. Natural Gas, Propane, Butane3

Blower Motor Power, Hp 1.5Weight, lbs (kg)4 Alloy Tube 90 (41)

Refractory 214 (97)Approvals

Performance Graphs

NOx Emission data is given for:• Ambient combustion air ~70°F (21°C)• Less than 700°F (370°C) firing chamber• Minimal process air velocity• Low fire input adjusted to 40,000 Btu/h (12 kW)• ppm volume, dry @ 3% O2

• Neutral chamber pressure

Emissions from the burner are influenced by:• Chamber conditions• Fuel type• Firing rate• Ratio regulator adjustment• Combustion air temperature

CO emission is largely influenced by chamber conditions. Contact your local Eclipse representative for an estimateof CO emission on your application

Control Zone

0

10

100

1000

0 500 1000 1500 2000 2500 3000 3500Input (x 1000 Btu/h)

% E

xces

s A

ir

0 200 400 600 800 1000

Input (kW)

Typical Ratio Control

Input and excess air atlow fire changes with

ratio regulator adjustment

Fuel Orifice ∆P vs. Input∆P Measured Between Taps B and D

Input (x 1000 Btu/h)

Input (kW)

0 500 1000 1500 2000 2500 3000 3500

0 200 400 600 800 1000

Fuel

Orif

ice

(mba

r) ±

5%

0

1

2

3

4

0.0

2.5

5.0

7.5

10.0

Fuel

Orif

ice

∆P ("

w.c.

) ± 5

%

Natural Gas (30.0 mm)Propane (25.5 mm)Butane (22.0 mm)

Air

∆P ("

w.c

.) ±

5%

0

2

4

6

8

10

12

0 500 1000 1500 2000 2500 3000 3500

0 145 290 435 580 725 870 1025

Input (x 1000 Btu/h)

0

5

10

15

20

25

30

Input (kW)

Air

∆P (m

bar)

± 5

%

Air ∆P vs. Input(Measured Between Tap C

& the Chamber with the Burner Firing)

Input (x 1000 Btu/h)

0 200 400 600 800 1000Input (kW)

40

50

60

70

80

90

100

0 500 1000 1500 2000 2500 3000 3500

NO

X ppm

@ 3

% O

2

NOX Emission (On ratio)

Propane/Butane

Natural Gas

2 Eclipse RatioMatic RM0300, V5, Datasheet 110-5, 8/22/2012

Dimensions & SpecificationsDimensions in mm (in)

242(9.5)

303(11.9)

99(3.9)

Tap C

SparkRod

Fuel Inlet1-1/2” NPT/

Rc 1.5

Tap BTap D

4X Ø12(0.5)

Ø263 B.C.(10.4)

292.6(11.5)

502(19.8)

Flame Rodor UV

ScannerAdapter

Peepsight

270.5(10.6)

172.7(6.8)

A

149.1 (5.9) ActuatorConnection Point(1/2” NPT or M16without Thread)

120.9 (4.8) ActuatorConnection Point(1/2” NPT or M16without Thread)

16(0.6)277

(10.9)

Shown with Alloy Combustor

B

696.1(27.4)

C

1/2” NPT/Rc 0.5

Pilot Option

198(7.8)

Blower Size A B50 Hz 533 (21) 394 (15.5)60 Hz 488 (19.2) 363 (14.3)

Combustor Type CStraight Stainless Steel Alloy Tube 351 (13.8)Straight Stainless Steel Alloy Tube 427 (16.8)

Air Inlet 4” NPT/Rc 4or 4” Welded Pipe4X Ø14

(0.6)

□330.2(13)

182(7.2)

143.5(5.7)

286(11.3)

25(1.0) 344

(13.5)

□275(10.8)

6X Ø14(0.6) Ø348

(13.7)

350(13.8)

Ø300(11.8)

Square Block and Holder

Round Block and Holder

3Eclipse RatioMatic RM0300, V5, Datasheet 110-5, 8/22/2012

Da

Combustor Options

Burner ConfigurationN

ozzl

e

Square Block & HolderAlloy Tube

F

4 x Ø12 (0.5)

Ø265 (10.4)bolt circle

E

Noz

zle

Round Block & Holder344

(13.5) 6 x Ø14 (0.6)

Noz

zle

Ø348 (13.7)bolt circle

17(0.7)

Ø200 (7.8) OD345

(13.5)147(5.8)

6(0.3)

44(1.7)

□278(10.9)

□330(13)

□381(15)

4 x Ø14 (0.6)

147(5.8)

Ø303(11.9)

44(1.7)6

(0.3)

154 (6.1) 350 (13.8)230 (9.1) 426 (16.8)

E F

Upright Left Hand Piping

Inverted Left Hand Piping

Upright Right Hand Piping

Inverted Right Hand Piping

tasheet 110-5 8/22/2012