datasheet ec inline filter unit swiss climate control · eccentrifugalmodule-radical...

6
ENERGY EFFICIENCY EC Inline Filter Unit Max. m3/h 500m3/h 800m3/h 1200m3/h Product code ART-1224 ART-1222 ART-1223 Fan manufacturer ebm-papst K3G190-RC05-03 ebm-papst K3G190-RD45-03 ebm-papst K3G220-RD53-03 W / A / VACC 83/0.75/200-240 169/1.35/200-240 168/1.4/200-240 Max. Pa 700 1200 930 Connection in mm D Ø 125 Ø 200 Ø 200 Weight in kg 13.4 17.2 23.2 Dimensions in mm L1 L2 W H1 H2 650 695 310 310 350 650 695 400 400 440 950 995 400 400 440 Associated products Granulate AKF 500GL ø125 (ART-1209) Standard AKF 500ZL ø125 (ART-1009) Granulate AKF 800GL ø200 (ART-1218) Standard AKF 800ZL ø200 (ART-1018) Pollen Filter ø200 800m3/h (ART-10322) Granulate AKF 1200G ø200 (ART-1225) Standard AKF 1200Z ø200 (ART-1022) Pollen Filter ø200 1200m3/h (ART-10330) Impeller material PA plastic PA plastic PA plastic Housing material Aluminium/Steel Aluminium/Steel Aluminium/Steel ErP directive overall efficiency: Actual 40% 56% 57.8% Request 2015 43.1% 43.1% DATASHEET EC Inline Filter Unit SPECIFICATIONS English DS_Unit_A4 Our motors with modern EC-technology reach excellent efficiencies and save up to 50% energy compared to conventional motor technology. The slightly higher investment costs compared to conventional motors usually pay for themselves within a very short operating time thanks to lower energy consumption and lower installation costs. www.carbonactive.ch Swiss Climate Control Airflow

Upload: others

Post on 30-Mar-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DATASHEET EC Inline Filter Unit Swiss Climate Control · ECcentrifugalmodule-RadiCal backward-curved,single-intake withhousing K3G190-RD45-03 Technicaldescription Weight 1.8kg Fansize

ENERGY EFFICIENCY

EC Inline Filter UnitMax. m3/h 500m3/h 800m3/h 1200m3/h

Product code ART-1224 ART-1222 ART-1223

Fan manufacturer ebm-papstK3G190-RC05-03

ebm-papstK3G190-RD45-03

ebm-papstK3G220-RD53-03

W / A / VACC 83/0.75/200-240 169/1.35/200-240 168/1.4/200-240

Max. Pa 700 1200 930

Connection in mm D Ø 125 Ø 200 Ø 200

Weight in kg 13.4 17.2 23.2

Dimensions in mm L1 L2 W H1 H2

650695310310350

650695400400440

950995400400440

Associated products

Granulate AKF 500GL ø125 (ART-1209)Standard AKF 500ZL ø125 (ART-1009)

Granulate AKF 800GL ø200 (ART-1218)Standard AKF 800ZL ø200 (ART-1018)

Pollen Filter ø200 800m3/h (ART-10322)

Granulate AKF 1200G ø200 (ART-1225)Standard AKF 1200Z ø200 (ART-1022)

Pollen Filter ø200 1200m3/h (ART-10330)

Impeller material PA plastic PA plastic PA plastic

Housingmaterial Aluminium/Steel Aluminium/Steel Aluminium/Steel

ErP directive overall efficiency:

Actual 40% 56% 57.8%

Request 2015 43.1% 43.1%

DATASHEETEC Inline Filter Unit

SPECIFICATIONS

English

DS_Unit_A4

Our motors with modern EC-technology reach excellent effi ciencies and save up to 50% energy compared to conventional motor technology.

The slightly higher investment costs compared to conventional motors usually pay for themselves within a very short operating time thanks to lower energy consumption and lower installation costs.

www.carbonactive.ch

Swiss Climate Control

Airflow

Page 2: DATASHEET EC Inline Filter Unit Swiss Climate Control · ECcentrifugalmodule-RadiCal backward-curved,single-intake withhousing K3G190-RD45-03 Technicaldescription Weight 1.8kg Fansize

EC centrifugal module - RadiCalbackward-curved, single-intake

with housing

K3G190-RD45-03

ebm-papst Mulfingen GmbH & Co. KG

Bachmühle 2 · D-74673 Mulfingen

Phone +49 7938 81-0

Fax +49 7938 81-110

[email protected]

www.ebmpapst.com

Limited partnership · Headquarters Mulfingen

Amtsgericht (court of registration) Stuttgart · HRA 590344

General partner Elektrobau Mulfingen GmbH · Headquarters Mulfingen

Amtsgericht (court of registration) Stuttgart · HRB 590142

Nominal data

Type K3G190-RD45-03

Motor M3G055-CF

Phase 1~

Nominal voltage VAC 230

Nominal voltage range VAC 200 .. 240

Frequency Hz 50/60

Method of obtaining data ml

Speed (rpm) min-1 4120

Power consumption W 169

Current draw A 1.35

Min. ambient temperature °C -25

Max. ambient temperature °C 60ml = Max. load · me = Max. efficiency · fa = Free air · cs = Customer specification · ce = Customer equipmentSubject to change

Data according to ErP DirectiveActual Req. 2015

01 Overall efficiency ηes % 56 43.1

02 Measurement category A

03 Efficiency category Static

04 Efficiency grade N 74.9 62

05 Variable speed drive YesData obtained at optimum efficiency level.The ErP data is determined using a motor-impeller combination in a standardized measurement setup.

09 Power consumption Ped kW 0.16

09 Air flow qv m³/h 565

09 Pressure increase pfs Pa 524

10 Speed (rpm) n min-1 4055

11 Specific ratio* 1.01* Specific ratio = 1 + pfs / 100 000 Pa LU-132500

Item no. 51200-5-9980 · ENU · Change 85329 · Approved 2016-07-28 · Page 1 / 5

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Page 3: DATASHEET EC Inline Filter Unit Swiss Climate Control · ECcentrifugalmodule-RadiCal backward-curved,single-intake withhousing K3G190-RD45-03 Technicaldescription Weight 1.8kg Fansize

EC centrifugal module - RadiCalbackward-curved, single-intake

with housing

K3G190-RD45-03

Technical description

Weight 1.8 kg

Fan size 190 mm

Rotor surface Thick-film passivated

Impeller material PA plastic

Housing material PA plastic

Number of blades 7

Direction of rotation Clockwise, viewed toward rotor

Degree of protection IP54

Insulation class "B"

Max. permitted ambient temp.for motor (transport/storage)

+ 80 °C

Min. permitted ambient temp. formotor (transport/storage)

- 40 °C

Installation position Any

Condensation drainage holes None, open rotor

Mode S1

Motor bearing Ball bearing

Technical features - Output 10 VDC, max. 10 mA- Tach output- Power limiter- Motor current limitation- Soft start- Control input 0-10 VDC / PWM- Control interface with SELV potential safely disconnected from the mains- Overvoltage detection- Thermal overload protection for electronics/motor- Line undervoltage detection

EMC immunity to interference According to EN 61000-6-2 (industrial environment)

EMC interference emission According to EN 61000-6-4 (industrial environment)

Touch current according to IEC60990 (measuring circuit Fig. 4,TN system)

<= 3.5 mA

Motor protection Locked-rotor protection

With cable Variable

Protection class I (with customer connection of protective earth)

Conformity with standards EN 60335-1; CE

Approval CSA C22.2 No. 77; UL 2111; EAC; CCC

Item no. 51200-5-9980 · ENU · Change 85329 · Approved 2016-07-28 · Page 2 / 5

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Page 4: DATASHEET EC Inline Filter Unit Swiss Climate Control · ECcentrifugalmodule-RadiCal backward-curved,single-intake withhousing K3G190-RD45-03 Technicaldescription Weight 1.8kg Fansize

EC centrifugal module - RadiCalbackward-curved, single-intake

with housing

K3G190-RD45-03

Product drawing

1 Cable PVC 3G AWG20, 3x crimped splices

2 Cable PVC 4x AWG22, 4x crimped splices

3 Mounting dimensions

Item no. 51200-5-9980 · ENU · Change 85329 · Approved 2016-07-28 · Page 3 / 5

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Page 5: DATASHEET EC Inline Filter Unit Swiss Climate Control · ECcentrifugalmodule-RadiCal backward-curved,single-intake withhousing K3G190-RD45-03 Technicaldescription Weight 1.8kg Fansize

EC centrifugal module - RadiCalbackward-curved, single-intake

with housing

K3G190-RD45-03

Connection diagram

No. Conn. Designation Color Function/assignment

CON10 L black Supply connection, power supply, phase, see nameplate for voltage range

CON11 N blue Supply connection, power supply, neutral conductor, see nameplate for voltage range

CON12 PE green/yellow Ground connection

2 0- 10V PWM yellow 0-10 V / PWM control input, Ri=100 kΩ, SELV

4 Tach white Tach output, open collector, 1 pulse per revolution, Isink max = 10 mA, SELV

3 +10 V red Fixed voltage output 10 VDC +/-3 %, Imax. 10 mA, short-circuit-proof, power supply for ext.devices (e.g. pot), SELV

1 GND blue Reference ground for control interface, SELV

Item no. 51200-5-9980 · ENU · Change 85329 · Approved 2016-07-28 · Page 4 / 5

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Page 6: DATASHEET EC Inline Filter Unit Swiss Climate Control · ECcentrifugalmodule-RadiCal backward-curved,single-intake withhousing K3G190-RD45-03 Technicaldescription Weight 1.8kg Fansize

EC centrifugal module - RadiCalbackward-curved, single-intake

with housing

K3G190-RD45-03

Curves: Air performance 50 Hz

Druck p f s[Pa]für Rho=1,2kg/m^3

qv[m^3/h]1.2001.1001.0009008007006005004003002001000

qv[cfm]7006005004003002001000

p fs[

Pa]

1.300

1.250

1.200

1.150

1.100

1.050

1.000

950

900

850

800

750

700

650

600

550

500

450

400

350

300

250

200

150

100

50

0

pfs

_E

[IN

H2O

]

5,2

5

4,8

4,6

4,4

4,2

4

3,8

3,6

3,4

3,2

3

2,8

2,6

2,4

2,2

2

1,8

1,6

1,4

1,2

1

0,8

0,6

0,4

0,2

0

p f s[Pa]

p f s[Pa]

p f s[Pa]

p f s[Pa] 1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

Measurement: LU-132500-1

Air performance measured according to ISO5801 installation category A. For detailedinformation on the measurement setup,contact ebm-papst. Intake sound level:Sound power level according to ISO 13347 /sound pressure level measured at 1 mdistance from fan axis. The values given arevalid under the specified measuringconditions and may vary due to conditions ofinstallation. For deviations from the standardconfiguration, the parameters have to bechecked on the installed unit.

Measured values

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

U

V

230

230

230

230

230

230

230

230

230

230

230

230

230

230

230

230

f

Hz

50

50

50

50

50

50

50

50

50

50

50

50

50

50

50

50

n

min-1

4440

4235

4120

4150

3700

3700

3700

3700

3000

3000

3000

3000

2300

2300

2300

2300

Ped

W

161

165

169

160

93

110

125

114

50

59

67

61

22

26

30

27

I

A

1.35

1.35

1.35

1.35

0.81

0.93

1.06

0.97

0.43

0.50

0.57

0.52

0.19

0.22

0.26

0.23

LpAin

dB(A)

72

67

63

66

69

64

61

64

64

59

56

59

58

53

51

54

LwAin

dB(A)

81

75

72

74

77

72

70

72

73

68

65

67

67

62

59

61

qV

m3/h

975

800

600

370

815

700

550

330

660

565

445

270

505

435

340

205

pfs

Pa

0

300

500

700

0

233

415

556

0

153

273

365

0

90

160

215

qV

cfm

575

470

355

220

480

410

325

195

390

335

260

160

300

255

200

120

pfs

inH2O

0.00

1.20

2.01

2.81

0.00

0.94

1.67

2.23

0.00

0.61

1.10

1.47

0.00

0.36

0.64

0.86

U = Power supply · f = Frequency · n = Speed (rpm) · Ped = Power consumption · I = Current draw · LpAin = Sound pressure level intake side · LwAin = Sound power level intake side

qV = Air flow · pfs = Pressure increase

Item no. 51200-5-9980 · ENU · Change 85329 · Approved 2016-07-28 · Page 5 / 5

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com