Page 1: Daylight & Sunlight

Daylight & SunlightINTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT

Wood Street library, Forest Road

18 January 2021GIA No: 17026

CHARTERED SURVEYORS

Page 2: Daylight & Sunlight

© Crown copyright and database rights 2017. OS 100047514

SOURCES OF INFORMATION:Information Received iR-16-17-17026Release Number Rel_06_17026_DSDIssue Number 03Site Photos gia3D models VERtEXOS Data FinD Maps

PROJECT DATA:

Client london Borough of Waltham Forest

Architect haworth tompkins

Project Title Wood Street library, Forest Road

Project Number 17026

REPORT DATA:

Report Title internal Daylight, Sunlight and Overshadowing Report

GIA Department Daylight & Sunlight

Dated 18 January 2021

Prepared by PaDu

Checked by nC

Type Planning

Revisions No: Date: Notes: Signed:

Page 3: Daylight & Sunlight

18 January 2021 1

CHARTERED SURVEYORS

COntEntS

1 EXECutiVE SuMMaRy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2 intRODuCtiOn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

3 BRE guiDElinES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

4 MEthODOlOgy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

5 COnCluSiOnS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

6 SitE OVERViEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

7 intERPREtatiOn OF RESultS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

8 intERnal Daylight anD Sunlight aSSESSMEntS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

9 OVERShaDOWing aSSESSMEntS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Page 4: Daylight & Sunlight

2 WOOD StREEt liBRaRy, FORESt ROaD INTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT (17026)

The purpose of this report is to ascertain whether the proposed development will provide acceptable daylight and sunlight amenity for the enjoyment of future occupants. To this end, all habitable rooms have been assessed for daylight quantity and distribution, all living areas with a southerly aspect have been analysed for their access to sunlight and the communal outdoor area at ground level has been tested for overshadowing.

GIA worked alongside Haworth Tompkins throughout the design in order to optimise the daylight and sunlight amenity within the site. Such collaboration entailed an iterative process of high-level review and technical assessments, resulting in a number of design alterations which led to a scheme optimised for daylight and sunlight as far as possible.

The results of the assessments undertaken demonstrate that the majority of assessed rooms will offer very good daylight and sunlight amenity, with 76% meeting or exceeding the recommended daylight levels and 100% offering good sky visibility.

In addition, 100% of living areas with a southerly aspect enjoy excellent levels of sunlight both annually and in winter. These are considered to be very good results for a scheme of this size.

Most of the rooms falling short of the recommended daylight levels will do so just marginally, owing to their generous size or the provision of balconies, which provide private amenity while acting as shading devices consequently reducing the daylight and sunlight availability of the rooms behind/beneath them. This balance is very common within residential schemes and generally considered acceptable.

With regard to overshadowing, the communal open space at ground level will exceed BRE’s recommendation for a space to be well sunlight throughout the year, with excellent sunlit provision during the summer months.

Overall therefore, the proposed development is considered to offer excellent daylight and sunlight amenity to future residents. Further details on the design strategies adopted and results achieved can be found in Section 5 of this report.

1 EXECutiVE SuMMaRy

Page 5: Daylight & Sunlight

18 January 2021 3

CHARTERED SURVEYORS

2 intRODuCtiOn

2.1 intRODuCtiOn anD OBJECtiVEGIA has been instructed to provide a report upon the potential availability of Daylight and Sunlight to the proposed accommodation within the residential scheme prepared by Haworth Tompkins. GIA was specifically instructed to carry out the following:

• To create a 3D computer model of the proposal based upon drawings prepared by Haworth Tompkins.

• Carry out a daylight assessment using the methodologies set out in the BRE guidance for Average Daylight Factor, No-Sky Line and Room Depth Criterion.

• Carry out a sunlight assessment using the methodologies set out in the BRE guidance for Annual Probable Sunlight Hours (APSH) to the fenestration facing within 90° of due south.

• Carry out an overshadowing assessment using the methodology set out in the BRE guidance for Sun Hours On Ground (SHOG) for all relevant amenity areas.

• Prepare a report setting out the analysis and our findings.

Page 6: Daylight & Sunlight

4 WOOD StREEt liBRaRy, FORESt ROaD INTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT (17026)

The Building Research Establishment (BRE) have set out in their handbook ‘Site Layout Planning for Daylight and Sunlight a Guide to Good Practice (2011)’ (BRE BR209), guidelines and methodology for the measurement and assessment of daylight and sunlight within proposed buildings.

3 BRE guiDElinES

This document states that it is intended to be used in conjunction with the daylight recommendations found within the British Standard BS8206-2:2008 and The Applications Manual on Window Design of the Chartered Institution of Building Services Engineers (CIBSE. 1999).

The guide also provides advice on site layout planning to determine the quality of daylight and sunlight within open spaces between buildings.

It is important to note, however, that this document is a guide and states that its aim “is to help rather than constrain the designer”.

The document provides advice, but also clearly states that it “is not mandatory and this document should not be seen as an instrument of planning policy.” The report also acknowledges in its introduction that “in special circumstances the developer or planning authority may wish to use different target values. For example, in a historic city centre a higher degree of obstruction may be unavoidable if new developments are to match the height and proportions of existing buildings.”

It is an inevitable consequence of the built-up urban environment that daylight and sunlight will be more limited in these areas. It is well acknowledged that in such situations there may be many other conflicting and potentially more important planning and urban design matters to consider other than just the provision of ideal levels of daylight and sunlight.

In May 2019 the British Standard BS8206-2:2008 was superseded by the new European Standard on daylight “BS EN 17037:2018 Daylight in buildings”. The Standard adopts a new methodology for testing daylight and sunlight in proposed developments based on climatic data as opposed the ‘Standard CIE overcast sky’ adopted in BS8206-2:2008, and also includes views out and glare.

Following on from the review of the European Standard by a dedicated commission of UK experts (which included the author of the BRE BR209 guidance Dr. Paul Littlefair), the British Standard Institution appended to BS EN 17037:2018 a UK National Annex which brings the recommended light levels in line with those of BS8206-2:2008.

BRE is currently looking to update and re-publish BR209 to align their guidance with the new BS EN 17037:2018 in 2020. Until then, the position of BRE can be summarised from a post by Dr. Littlefair on the LinkedIn Planning Daylight & Sunlight Group (BRE BR209): “Until BR 209 is rewritten, we are adopting a flexible approach to applying the two standards, for example in assessing the daylight and sunlight available in new buildings. So, for example, if we were reviewing a daylight report for a local authority, we would consider it reasonable to accept either average daylight factor tables using BS 8206 or median daylight factors/median illuminance calculated using EN 17037, provided they were calculated and presented properly”.

Given the above and the reference to the BRE guidance in planning policies, the assessments within this report are carried out with the criteria and methodologies set out in BRE BR209 and BS8206-2:2008. It is not considered that calculations undertaken according to BS EN 17037:2018 would alter the conclusions meaningfully.

Page 7: Daylight & Sunlight

18 January 2021 5

CHARTERED SURVEYORS

2.2 DaylightThe BRE set out various methods for assessing the daylight within a proposed building within section 2.1 and Appendix C of the handbook. These are summarised below.

Vertical Sky Component (VSC)

This method of assessment can be undertaken using a skylight indicator or a Waldram diagram. It measures from a single point, at the centre of the window (if known at the early design stage), the quantum of sky visible taking into account all external obstructions. Whilst these obstructions can be either other buildings or the general landscape, trees are usually ignored unless they form a continuous or dense belt of obstruction.

The VSC method is a useful ‘rule of thumb’ but has some significant limitations in determining the true quality of daylight within a proposed building. It does not take into account the size of the window, any reflected light off external obstructions, any reflected light within the room, or the use to which that room is put. Appendix C of the guide goes into more detail on these matters and sets forward alternative methods for assessment to overcome these limitations.

Appendix C of the BRE guide: Interior Daylighting Recommendations, states:

“The British Standard Code of practice for daylighting (BS 8206-2) and the CIBSE Lighting Guide LG 10 Daylighting and window design contain advice and guidance on interior daylighting. The guidance contained in this publication (BR 209) is intended to be used with BS 8206-2 and LG 10. Both these publications refer to BR 209.

For skylight BS 8206-2 and LG 10 put forward three main criteria, based on average daylight factor (ADF); room depth; and the position of the no sky line.”

These assessments are set out below.

average Daylight Factor (aDF)

“If a predominantly daylit appearance is required, then the ADF should be 5% or more if there is no supplementary electric lighting, or 2% or more if supplementary electric lighting is provided. There are additional recommendations for dwellings of 2% for kitchens, 1.5% for living rooms and 1% for bedrooms. These additional recommendations are minimum values of ADF which should be attained even if a predominantly daylit appearance is not achievable.”

This method of assessment takes into account the total glazed area to the room, the transmittance quality of the glazing proposed, the total area of the room surfaces including ceilings and floors, and the internal average reflectance for the room being assessed. The method also takes into account the Vertical Sky Component and the quantum of reflected light off external surfaces.

This is, therefore, a significantly more detailed method of assessment than the Vertical Sky Component method set out above.

Room Depth Criterion (RDC)

Where it has access to daylight from windows in one wall only, the depth of a room can become a factor in determining the quantity of light within it. The BRE guidance provides a simple method for examining the ratio of room depth to window area. However, whilst it does take into account internal surface reflections, this method also has significant limitations in that it does not take into account any obstructions outside the window and therefore draws no input from the quantity of light entering the room.

no Sky line (nSl)

This third method of assessment is a simple test to establish where within the proposed room the sky will be visible through the windows, taking into account external obstructions. The assessment is undertaken at working plane height (850mm above floor level) and the method of calculation is set out in Appendix D of the BRE handbook.

Appendix C of the BRE handbook states “If a significant area of the working plane (normally more than 20%) lies beyond the no sky line (ie it receives no direct skylight) then the distribution of daylight in

Page 8: Daylight & Sunlight

6 WOOD StREEt liBRaRy, FORESt ROaD INTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT (17026)

the room will look poor and supplementary electric lighting will be required.” To guarantee a satisfactory daylight uniformity, the area which does not receive direct skylight should not exceed 20% of the floor area, as quantified in the BS 8206 Part 2 2008.

Summary

The Average Daylight Factor gives a more detailed assessment of the daylight within a room and takes into account the highest number of factors in establishing a quantitative output.

However, the conclusion of Appendix C of the BRE guide states:

“[All three of] the criteria need to be satisfied if the whole of the room is to look adequately daylit. Even if the amount of daylight in a room (given by the Average Daylight Factor) is sufficient, the overall daylight appearance will be impaired if its distribution is poor.”

In most urban areas it is important to recognise that the distribution of daylight within a room may be difficult to achieve, given the built-up nature of the environment. Consequently, most local authorities seek to ensure that there is sufficient daylight within the room as determined by the Average Daylight Factor calculation. However, the additional recommendations of the BRE and British Standard for residential accommodation, set out above, ought not to be overlooked.

3.1 SunlightThe BRE provide guidance in respect of sunlight quality for new developments within section 3.1 of the handbook. It is generally acknowledged that the presence of sunlight is more significant in residential accommodation than it is in commercial properties, and this is reflected in the BRE document.

It states, “in housing, the main requirement for sunlight is in living rooms, where it is valued at any time of the day, but especially in the afternoon. Sunlight is also required in conservatories. It is viewed as less important in bedrooms and in kitchens where people prefer it in the morning rather than

the afternoon.”

The BRE guide considers the critical aspects of orientation and overshadowing in determining the availability of sunlight at a proposed development site.

The guide proposes minimizing the number of dwellings whose living room face solely north unless there is some compensating factor such as an appealing view to the north, and it suggests a number of techniques to do so. Furthermore, it discusses massing solutions with a sensitive approach to overshadowing, so as to maximize access to sunlight.

At the same time, it acknowledges that the site’s existing urban environment may impose orientation or overshadowing constraints which may not be possible to overcome.

To quantify sunlight access for interiors where sunlight is expected, it refers to the BS 82606-2 criterion of Annual Probable Sunlight Hours. APSH is defined as “the total number of hours in the year that the sun is expected to shine on unobstructed ground, allowing for average levels of cloudiness at the location in question.” In line with the recommendation, APSH is measured from a point on the inside face of the window, should the locations have been decided. If these are unknown, sunlight availability is checked at points 1.6m above the ground or the lowest storey level on each main window wall, and no more than 5m apart. If a room has multiple windows on the same wall or on adjacent walls, the highest value of APSH should be taken into account. If a room has two windows on opposite walls, the APSH for each can be added together.

The summary of section 3.1 of the guide states as follows:

“In general, a dwelling or non-domestic building which has a particular requirement for sunlight, will appear reasonably sunlit provided that:

• At least one main window faces within 90 degrees of due south, and

• The centre of at least one window to a main living room can receive 25% of annual probable sunlight hours, including at least 5% of annual probable sunlight hours in the winter months between 21 September and 21 March. “

Page 9: Daylight & Sunlight

18 January 2021 7

CHARTERED SURVEYORS

In paragraph 3.1.11 the BRE guidance suggests that if a room faces significantly North of due East or West it is unlikely to meet the recommended levels proposed by the BS 8206-2. As such, it is clear that only windows facing within 90 degrees of due South can be assessed using this methodology.

It is also worth noting how paragraph 5.3 of the BS 8206-2 suggests that with regards to sunlight duration “the degree of satisfaction is related to the expectation of sunlight. If a room is necessarily north facing or if the building is in a densely-built urban area, the absence of sunlight is more acceptable than when its exclusion seems arbitrary”.

3.2 OVERShaDOWingThe BRE guidance in respect of overshadowing of amenity spaces is set out in section 3.3 of the handbook. Here it states as follows:

“Sunlight in the spaces between buildings has an important impact on the overall appearance and ambiance of a development. It is valuable for a number of reasons, to:

• provide attractive sunlit views (all year)• make outdoor activities, like sitting out and

children’s play more pleasant (mainly warmer months)

• encourage plant growth (mainly spring and summer)

• dry out the ground, reducing moss and slime (mainly in colder months)

• melt frost, ice and snow (in winter)• dry clothes (all year)”

Again, it must be acknowledged that in urban areas the availability of sunlight on the ground is a factor which is significantly controlled by the existing urban fabric around the site in question and so may have very little to do with the form of the development itself. Likewise, there may be many other urban design, planning and site constraints which determine and run contrary to the best form, siting and location of a proposed development in terms of availability of sun on the ground.

The summary of section 3.3 of the guide states as follows:

“3. 3 .17 It is recommended that for it to appear adequately sunlit throughout the year, at least half of a garden or amenity area should receive at least two hours of sunlight on 21 March. If as a result of new development an existing garden or amenity area does not meet the above, and the area which can receive two hours of sun on 21 March is less than 0.8 times its former value, then the loss of sunlight is likely to be noticeable. If a detailed calculation cannot be carried out, it is recommended that the centre of the area should receive at least two hours of sunlight on 21 March.”

3.3 FuRthER RElEVant inFORMatiOnFurther information can be found in The Daylight in Urban Areas Design Guide (Energy Saving Trust CE257, 2007) which provides the following recommendation with regards to VSC levels in urban areas:

“If ‘theta’ (Visible sky angle) is greater than 65° (obstruction angle less than 25° or VSC at least 27 percent) conventional window design will usually give reasonable results.

If ‘theta’ is between 45° and 65° (obstruction angle between 25° and 45°, VSC between 15 and 27 percent), special measures such as larger windows and changes to room layout are usually needed to provide adequate daylight.

If ‘theta’ is between 25° and 45° (obstruction angle between 45° and 65°, VSC from 5 to 15 percent), it is very difficult to provide adequate daylight unless very large windows are used.

If ‘theta’ is less than 25° (obstruction angle more than 65°, VSC less than 5 percent) it is often impossible to achieve reasonable daylight, even if the whole window wall is glazed.”

Page 10: Daylight & Sunlight

8 WOOD StREEt liBRaRy, FORESt ROaD INTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT (17026)

4 MEthODOlOgy

The three dimensional representation of the proposed development has been modelled using the scheme drawings provided to us by Haworth Tompkins. This has been placed in the context of its surrounding buildings which have been modelled from survey information, photogrammetry, OS and site photographs. This allows for a precise model, which in turn ensures that analysis accurately represents the amount of daylight and sunlight available to the building facades, internal and external spaces, considering all of the surrounding obstructions and orientation.

4.1 SiMulatiOn aSSuMPtiOnSWhere no values for reflectance, transmittance and maintenance factor were specified by the designer the following values from BS 8206-2:2008, Annex A, tables A.1-A.6 were used for the calculation of Average Daylight Factor values. These values are shown in Table 1.

As specificed by Haworth Tompkins, a medium veneer floor finish (e.g. carpet) has been assumed for all affordable and intermediate units as well as for the bedrooms within the market provision, whilst a light veneer finish (e.g. wooden floor) has been used for the remaining LKDs within the market units.

In order to undertake the daylight, sunlight and overshadowing assessments set out in the following pages, we have prepared a three dimensional computer model and used specialist lighting simulation software.

Page 11: Daylight & Sunlight

18 January 2021 9

CHARTERED SURVEYORS

MaintEnanCE FaCtORS: glaZing tyPE

tV (Normal) a.3 a.4 a.5 a.6 tV

(Total)

triple low-E (frames modelled) 0.63 8 1 1 1 0.58

triple low-E (frames not modelled) 0.63 8 1 1 0.8 0.46

triple low-E (inclined, frames modelled) 0.63 8 2 1 1 0.53

triple low-E (inclined, frames not modelled) 0.63 8 2 1 0.8 0.42

triple low-E (horizontal, frames modelled) 0.63 8 3 1 1 0.48

triple low-E (horizontal, frames not modelled) 0.63 8 3 1 0.8 0.38

Double low-E (frames modelled) 0.70 8 1 1 1 0.64

Double low-E (frames not modelled) 0.70 8 1 1 0.8 0.52

Double low-E (inclined, frames modelled) 0.70 8 2 1 1 0.59

Double low-E (inclined, frames not modelled) 0.70 8 2 1 0.8 0.47

Double low-E (horizontal, frames modelled) 0.70 8 3 1 1 0.53

Double low-E (horizontal, frames not modelled) 0.70 8 3 1 0.8 0.43

Single (frames modelled) 0.90 8 1 1 1 0.83

Single (frames not modelled) 0.90 8 1 1 0.8 0.66

Single (inclined, frames modelled) 0.90 8 2 1 1 0.76

Single (inclined, frames not modelled) 0.90 8 2 1 0.8 0.60

Single (horizontal, frames modelled) 0.90 8 3 1 1 0.68

Single (horizontal, frames not modelled) 0.90 8 3 1 0.8 0.55

Double translucent low-E (frames modelled) 0.74 8 1 1 1 0.68

Double translucent low-E (frames not modelled) 0.74 8 1 1 0.8 0.54

Double translucent low-E (inclined, frames modelled) 0.74 8 2 1 1 0.62

Double translucent low-E (inclined, frames not modelled) 0.74 8 2 1 0.8 0.50

Double translucent low-E (horizontal, frames modelled) 0.74 8 3 1 1 0.56

Double translucent low-E (horizontal, frames not modelled) 0.74 8 3 1 0.8 0.45

Table 01: Typical reflectance, transmittance and maintenance factors

REFlECtanCE ValuES:

Surrounding 0.2

Pavement 0.2

Grass 0.1

Water 0.1

Yellow brick 0.3

Red brick 0.2

Portland Stone 0.6

Concrete 0.4

Internal walls (light grey) 0.68

Internal ceiling (white paint) 0.85

Internal floor (medium veneer) 0.3

Internal floor (light veneer) 0.4

tRanSMittanCE ValuES tV

triple glazing (low-E):Pilkington K Glass 4/12/4/12/4 Argon filled 90%

0.63

Double glazing (low-E): 0.70

Single glazing:Pilkington Optifloat Clear 4mm Annealed

0.90

translucent glazing (low-E):Pilkington Optifloat Opal - 4mm K /16/4mm Opal

0.74

Page 12: Daylight & Sunlight

10 WOOD StREEt liBRaRy, FORESt ROaD INTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT (17026)

5 COnCluSiOnS

In order to ascertain the levels of daylight and sunlight within the proposed Wood Street development, technical assessments have been undertaken within all habitable rooms as well as on the proposed communal open space at ground level.

GIA worked alongside Haworth Tompkins throughout the design in order to optimise the daylight and sunlight amenity within the site. Such collaboration entailed an iterative process of high-level review and technical assessments, which have been feedbacked to the team. As a result, a number of features have been implemented within the design to improve the daylight and sunlight performance of the proposed scheme.

The final internal daylight and sunlight results can be found in pages 16 to 35 of this report, whilst the overshadowing results for the communal open space are presented in pages 36 to 38.

The main consideration during the collaborative design process was the balance between the provision of private amenity in the form of balconies, thermal comfort, privacy issues and daylight and sunlight ingress.

Some of the most effective strategies adopted from the start were:

• Locating two and three bedroom flats (family units) in areas of greater daylight ingress;

• Optimising the layouts to have the greatest amount of dual aspects living spaces;

• Rearranging flat layouts to prioritise the daylight within living areas;

• Increasing window sizes where necessary;• Adopting a balcony strategy which provides all

units with a private amenity in the form of balcony while still prioritizing daylight within main living spaces.

Balconies are required in accordance with the London Housing Design Guide. Although they provide a private outdoor amenity space, balconies inherently act as shading devices, leading to lower levels of daylight and sunlight into the rooms set behind them. To address these areas, balconies have been located in front of bedrooms, with a side access from the adjacent living space.

The results presented within this report therefore illustrate a scheme which has been optimised for

daylight and sunlight as far as possible.

5.1 COnCluSiOnS On Daylight & SunlightAll habitable rooms within the proposed scheme have been assessed for daylight quantity (by means of the Average Daylight Factor metric – ADF) and distribution (by means of the No Sky Line metric – NSL and the Room Depth Criterion – RDC). In addition, all living areas with a southerly aspect have been assessed for their access to sunlight (Annual Probable Sunlight Hours – PSH) both annually (APSH) and in winter (WPSH).

The results of the assessments undertaken show that:

• 76% of habitable rooms meet or exceed the recommended daylight quantity (ADF);

• 100% of habitable rooms enjoy sky visibility in line with or above guidance (NSL);

• 100% of habitable rooms have been designed with good proportions for uniform daylight distribution, in accordance with the RDC where applicable;

• 100% of living areas with a southerly aspect receive levels of annual sunlight (APSH) in line with those recommended or greater; and

• 100% of living areas with a southerly aspect receive levels of winter sunlight (WPSH) in line with those recommended or greater.

The above are considered excellent results for a scheme of this size.

Of the 45 open-plan combined living/kitchen/dining rooms (LKDs), 31 (69%) will receive good levels of daylight, meeting or exceeding the recommended 2% ADF. In addition, all 45 enjoy good sky visibility, with levels of NSL in line with or above recommendation and all have good access to sunlight both throughout the year and during the winter months.

With regards to ADF levels it is also worth noting that 12 of the 14 LKDs falling short of ADF recommendation still achieve the 1.5% ADF suggested for living areas and fall just short of the 2% recommended for rooms including a kitchen. Such results are typical of contemporary living, where open-plan layouts are preferred and kitchens are located to the rear of the room, where they inevitably receive less natural light. Should these rooms be considered acceptably daylit, it could be concluded

Page 13: Daylight & Sunlight

18 January 2021 11

CHARTERED SURVEYORS

that 43 (96%) of the 45 proposed LKDs perform well in terms of daylight ingress.

The remaining two LKDs falling short of the 1.5% ADF suggested for living areas are room no. 4 (Ground Floor, Unit 05) and room no. 89 (Fifth Floor, Unit 32), with 1.2% and 1.1% ADF respectively. However, both rooms still enjoy very good levels of sky visibility and sunlight provision, well exceeding the recommended levels of NSL, APSH and WPSH. In addition, all the other bedrooms within these units exceed the minimum ADF level recommended.

21 (96%) of the 22 proposed living areas meet or exceed the 1.5% ADF recommended, with the only exception of room no. 83 (Fifth Floor, Unit 35) which falls marginally short of recommendation achieving 1.4% ADF. Furthermore, all 22 living areas comply with the recommendation for daylight distribution and sunlight quantum, meeting or exceeding the minimum targets suggested.

Of the 93 proposed bedrooms, 69 (74%) meet or exceed the suggested target for ADF, while 13 of the 24 bedrooms falling short of the ADF recommendation do so just marginally (by 0.1-0.2%). The remaining 11 bedrooms see levels of ADF lower than recommended owing to their location behind balconies.

As previously mentioned, balconies reduce the levels of light ingress within rooms located behind/below them and therefore these have been located in front of bedrooms in order to prioritise main living spaces. As a result, all bedrooms falling short of the suggested ADF target are located in units where the main living space far exceeds the daylight recommendation, therefore providing future occupants with good levels of daylight and sunlight from within the living space.Furthermore, all 93 proposed bedrooms meet or exceed the recommendation for NSL and therefore will have very good sky visibility.

In conclusion, the great majority of rooms will enjoy very good daylight and sunlight amenity with the main shortfalls experienced within secondary spaces such as bedrooms which are located behind balconies to prioritise daylight within living spaces.

Overall therefore, the proposed development is considered to perform very well in terms of daylight and sunlight amenity.

5.2 COnCluSiOnS On OVERShaDOWingBRE recommends that, in order for an outdoor space to be well sunlit throughout the year, at least half of its area (50%) should receive direct sunlight for two hours or more on the Spring equinox (21st March). Therefore, the communal open space at ground level has been assessed against this criterion.

The results of the assessment show that the area well exceed BRE’s recommendation of 50%, with 96% of the space receiving two or more hours of direct sunlight on 21st March.

Furthermore, in order to provide a better understanding of the sunlight availability throughout the year, sun exposure assessments have been carried out for the Spring Equinox (21st March) and Summer Solstice (21st June).

In the summer, when outdoor spaces are most likely to be utilised for daytime activities, the sunlight availability is excellent, with the great majority of the space receiving direct sunlight for six hours or more.

Therefore, the proposed development will also offer excellent access to sunlight within the communal open space at ground level.

Page 14: Daylight & Sunlight

12 WOOD StREEt liBRaRy, FORESt ROaD INTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT (17026)

n

6 SitE OVERViEW

Fig. 01: Top view

Wood St

Albion R

d

Fulbourne Rd

Kingsley Rd Forest Rd

Page 15: Daylight & Sunlight

18 January 2021 13

CHARTERED SURVEYORS

Wood St

Fulbourne Rd

Forest Rd

Fig. 02: Perspective view

Page 16: Daylight & Sunlight

14 WOOD StREEt liBRaRy, FORESt ROaD INTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT (17026)

ROOM REF.

ROOM USE ADF (%) NSL (%) RDC ANNUAL WINTER

DAYLIGHT QUANTUM

DAYLIGHT DISTRIBUTIONSUNLIGHT QUANTUM

(PROBABLE SUNLIGHT HOURS)

Building C - SIXTH FLOOR

686 L/K/D 2.8 99 N/A687 L/K/D 2.5 100 N/A 78 27688 Bedroom 1.1 90 MET689 Bedroom 1.4 87 MET690 Bedroom 1.4 89 MET691 Bedroom 2 85 N/A692 Bedroom 1.6 82 MET693 Bedroom 1.4 95 MET694 Bedroom 1.6 98 MET695 Bedroom 2.2 93 N/A696 Living Room 2.6 100 N/A 56 24697 Bedroom 2.5 100 N/A698 Bedroom 2.3 97 MET699 L/K/D 1.3 95 MET 57 28700 Living Room 1.8 96 N/A 64 27701 Bedroom 1.4 98 MET702 Living Room 1.2 96 MET 39 14

7 intERPREtatiOn OF RESultS

KEy tO unDERStanDing thE taBlES - Daylight

Daylight QuantuM

Daylight DiStRiButiOn

Room Depth Criterion (RDC)

Defines adequate room proportions that enable good distribution of light. It applies to rooms lit by windows in one wall only.

MET : The room meets the Room Depth criterion

NOT MET: The room does not meet BRE’s RDC

N/A (Not Applicable): The room is not lit by windows in one wall only, and cannot be assessed by BRE’s RDC

no-Skyline (nSl)

Refers to the percentage of the room with a view of the sky from a working plane at desk hight.

BRE recommends the NSL to be at least 80% for the room to guarantee satisfactory daylight uniformity.

average Daylight Factor (aDF)

Refers to the average percentage of daylight flux in a room against an external unobstructed plane.

BRE recommends ADF levels of 2% for rooms with kitchens (including LKDs and studios with kitchens), 1.5% for living rooms and studies, and 1% for bedrooms.

Page 17: Daylight & Sunlight

18 January 2021 15

CHARTERED SURVEYORS

ROOM REF.

ROOM USE ADF (%) NSL (%) RDC ANNUAL WINTER

DAYLIGHT QUANTUM

DAYLIGHT DISTRIBUTIONSUNLIGHT QUANTUM

(PROBABLE SUNLIGHT HOURS)

Building C - SIXTH FLOOR

686 L/K/D 2.8 99 N/A687 L/K/D 2.5 100 N/A 78 27688 Bedroom 1.1 90 MET689 Bedroom 1.4 87 MET690 Bedroom 1.4 89 MET691 Bedroom 2 85 N/A692 Bedroom 1.6 82 MET693 Bedroom 1.4 95 MET694 Bedroom 1.6 98 MET695 Bedroom 2.2 93 N/A696 Living Room 2.6 100 N/A 56 24697 Bedroom 2.5 100 N/A698 Bedroom 2.3 97 MET699 L/K/D 1.3 95 MET 57 28700 Living Room 1.8 96 N/A 64 27701 Bedroom 1.4 98 MET702 Living Room 1.2 96 MET 39 14

KEy tO unDERStanDing thE taBlES - Sunlight

Sunlight DiStRiButiOn

Winter Probable Sunlight hours (WPSh)

BRE recommends at least 5% of Winter Probable Sunlight Hours for rooms where sunlight is expected.

annual Probable Sunlight hours (aPSh)

BRE recommends at least 25% of Annual Probable Sunlight Hours for rooms where sunlight is expected.

Probable Sunlight hours (PSh)

Refers to the average of hours during a year in which a surface receives direct sunlight (%).

BRE states that sunlight is most appreciated in living areas and the greatest expectation of sunlight is within south facing rooms. PSH assessments therefore consider all of the living rooms with a main window facing within 90 degrees of due south.

Page 18: Daylight & Sunlight

16 WOOD StREEt liBRaRy, FORESt ROaD INTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT (17026)

ROOM REF. ROOM USE ADF (%) NSL (%) RDC ANNUAL WINTER

WOOD STREET - FIRST FLOOR

1 L/K/D 2.3 99 N/A 47 122 Bedroom 2.5 99 MET3 Bedroom 1.8 97 MET4 L/K/D 1.2 96 N/A 31 65 Bedroom 1.9 100 N/A6 Bedroom 1.2 98 MET7 Bedroom 1.3 97 MET8 Bedroom 1.6 100 N/A9 L/K/D 1.9 100 N/A 49 1510 L/K/D 1.8 99 N/A 46 1211 Bedroom 1 98 MET12 Bedroom 1 99 MET13 L/K/D 1.8 99 N/A 47 13

SUNLIGHT QUANTUM (PROBABLE SUNLIGHT HOURS)

DAYLIGHT DISTRIBUTIONDAYLIGHT QUANTUM

8 intERnal Daylight anD Sunlight aSSESSMEntS

Table 02: Assessment Data

Wood Street - First Floor

Page 19: Daylight & Sunlight

18 January 2021 17

CHARTERED SURVEYORS

n

Fig. 03: Floor Plan

Page 20: Daylight & Sunlight

18 WOOD StREEt liBRaRy, FORESt ROaD INTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT (17026)

ROOM REF. ROOM USE ADF (%) NSL (%) RDC ANNUAL WINTER

SUNLIGHT QUANTUM (PROBABLE SUNLIGHT HOURS)

DAYLIGHT DISTRIBUTIONDAYLIGHT QUANTUM

WOOD STREET - SECOND FLOOR

14 L/K/D 2.4 99 N/A 49 1415 Bedroom 2.5 99 MET16 Bedroom 1.9 97 MET17 Bedroom 2.7 98 MET18 Bedroom 2.4 99 MET19 Bedroom 2.7 99 N/A20 Living Room 2 98 N/A21 Bedroom 0.5 97 MET22 Living Room 2.4 98 N/A23 Bedroom 0.8 95 MET24 Living Room 1.5 95 N/A25 L/K/D 1.6 100 N/A 33 726 Bedroom 2.6 100 N/A27 Bedroom 1.4 95 MET28 Bedroom 2 100 N/A29 L/K/D 2 100 N/A 49 1530 L/K/D 1.9 99 N/A 47 1331 Bedroom 1.1 98 MET32 Bedroom 1.1 99 MET33 L/K/D 1.8 99 N/A 47 13

Table 03: Assessment Data

Wood Street - Second Floor

Page 21: Daylight & Sunlight

18 January 2021 19

CHARTERED SURVEYORS

n

Fig. 04: Floor Plan

Page 22: Daylight & Sunlight

20 WOOD StREEt liBRaRy, FORESt ROaD INTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT (17026)

ROOM REF. ROOM USE ADF (%) NSL (%) RDC ANNUAL WINTER

SUNLIGHT QUANTUM (PROBABLE SUNLIGHT HOURS)

DAYLIGHT DISTRIBUTIONDAYLIGHT QUANTUM

WOOD STREET - THIRD FLOOR

34 L/K/D 2.5 99 N/A 49 1435 Bedroom 2.6 99 MET36 Bedroom 1.9 97 MET37 Bedroom 2.7 98 MET38 Bedroom 2.4 99 MET39 Bedroom 2.8 100 N/A40 Living Room 2.2 100 N/A41 Bedroom 0.6 97 MET42 Living Room 2.5 98 N/A43 Bedroom 0.9 95 MET44 Living Room 1.5 95 N/A45 L/K/D 1.6 100 N/A 33 746 Bedroom 2.7 100 N/A47 Bedroom 1.4 95 MET48 Bedroom 2.1 100 N/A49 L/K/D 2 100 N/A 50 1550 L/K/D 1.9 99 N/A 49 1451 Bedroom 1.1 98 MET52 Bedroom 1.1 99 MET53 L/K/D 1.9 99 N/A 49 14

Table 04: Assessment Data

Wood Street - Third Floor

Page 23: Daylight & Sunlight

18 January 2021 21

CHARTERED SURVEYORS

nn

Fig. 05: Floor Plan

Page 24: Daylight & Sunlight

22 WOOD StREEt liBRaRy, FORESt ROaD INTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT (17026)

ROOM REF. ROOM USE ADF (%) NSL (%) RDC ANNUAL WINTER

SUNLIGHT QUANTUM (PROBABLE SUNLIGHT HOURS)

DAYLIGHT DISTRIBUTIONDAYLIGHT QUANTUM

WOOD STREET - FOURTH FLOOR

54 L/K/D 2.5 99 N/A 50 1555 Bedroom 2.5 99 MET56 Bedroom 1.9 97 MET57 Bedroom 2.7 98 MET58 Bedroom 2.4 99 MET59 Bedroom 2.9 100 N/A60 Living Room 2.3 100 N/A61 Bedroom 0.6 97 MET62 Living Room 2.6 98 N/A63 Bedroom 0.9 95 MET64 Living Room 1.5 95 N/A65 L/K/D 1.6 100 N/A 33 766 Bedroom 2.7 100 N/A67 Bedroom 1.4 95 MET68 Bedroom 2.1 100 N/A69 L/K/D 2.1 100 N/A 50 1570 L/K/D 1.9 99 N/A 49 1471 Bedroom 1.1 98 MET72 Bedroom 1.1 99 MET73 L/K/D 1.9 99 N/A 49 14

Table 05: Assessment Data

Wood Street - Fourth Floor

Page 25: Daylight & Sunlight

18 January 2021 23

CHARTERED SURVEYORS

nn

Fig. 06: Floor Plan

Page 26: Daylight & Sunlight

24 WOOD StREEt liBRaRy, FORESt ROaD INTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT (17026)

ROOM REF. ROOM USE ADF (%) NSL (%) RDC ANNUAL WINTER

SUNLIGHT QUANTUM (PROBABLE SUNLIGHT HOURS)

DAYLIGHT DISTRIBUTIONDAYLIGHT QUANTUM

WOOD STREET - FIFTH FLOOR

74 L/K/D 2.5 99 N/A 50 1575 Bedroom 2.7 99 MET76 Bedroom 2.1 97 MET77 Bedroom 3.2 98 MET78 Bedroom 2.8 100 N/A79 Living Room 2.5 100 N/A80 Bedroom 0.6 97 N/A81 Living Room 2.7 98 MET82 Bedroom 1 95 MET83 Living Room 1.4 95 N/A84 L/K/D 2.7 100 N/A 51 1785 Bedroom 2.4 100 N/A86 Bedroom 2 95 MET87 Bedroom 2.4 96 N/A88 L/K/D 2.3 100 N/A 64 2389 L/K/D 1.1 95 N/A 46 1390 Bedroom 1.1 98 MET91 Bedroom 1.2 99 MET92 L/K/D 2 99 N/A 49 14

Table 06: Assessment Data

Wood Street - Fifth Floor

Page 27: Daylight & Sunlight

18 January 2021 25

CHARTERED SURVEYORS

nn

Fig. 07: Floor Plan

Page 28: Daylight & Sunlight

26 WOOD StREEt liBRaRy, FORESt ROaD INTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT (17026)

ROOM REF. ROOM USE ADF (%) NSL (%) RDC ANNUAL WINTER

SUNLIGHT QUANTUM (PROBABLE SUNLIGHT HOURS)

DAYLIGHT DISTRIBUTIONDAYLIGHT QUANTUM

WOOD STREET - SIXTH FLOOR

93 L/K/D 2.6 99 N/A 48 1594 Bedroom 2.6 99 MET95 Bedroom 1.9 98 MET96 Bedroom 2.9 98 MET97 Bedroom 2.8 100 N/A98 Living Room 2.5 100 N/A99 Bedroom 0.7 96 N/A100 Living Room 2.9 97 N/A101 Bedroom 0.9 98 MET102 L/K/D 2.4 100 N/A 58 18103 L/K/D 2.5 100 N/A 68 24104 Bedroom 0.8 99 MET105 Bedroom 1.2 99 MET106 L/K/D 2 99 N/A 50 15

Table 07: Assessment Data

Wood Street - Sixth Floor

Page 29: Daylight & Sunlight

18 January 2021 27

CHARTERED SURVEYORS

nn

Fig. 08: Floor Plan

Page 30: Daylight & Sunlight

28 WOOD StREEt liBRaRy, FORESt ROaD INTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT (17026)

ROOM REF. ROOM USE ADF (%) NSL (%) RDC ANNUAL WINTER

SUNLIGHT QUANTUM (PROBABLE SUNLIGHT HOURS)

DAYLIGHT DISTRIBUTIONDAYLIGHT QUANTUM

WOOD STREET - SEVENTH FLOOR

107 L/K/D 2.6 99 N/A 48 15108 Bedroom 2.6 99 MET109 Bedroom 1.9 98 MET110 Bedroom 2.9 98 MET111 Bedroom 2.8 100 N/A112 Living Room 2.6 100 N/A113 Bedroom 0.7 96 N/A114 Living Room 3 97 N/A115 Bedroom 0.9 98 MET116 L/K/D 2.8 100 N/A 58 18117 L/K/D 2.9 100 N/A 68 24118 Bedroom 0.9 99 MET119 Bedroom 1.2 99 MET120 L/K/D 2.1 99 N/A 50 15

Table 08: Assessment Data

Wood Street - Seventh Floor

Page 31: Daylight & Sunlight

18 January 2021 29

CHARTERED SURVEYORS

nn

Fig. 09: Floor Plan

Page 32: Daylight & Sunlight

30 WOOD StREEt liBRaRy, FORESt ROaD INTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT (17026)

ROOM REF. ROOM USE ADF (%) NSL (%) RDC ANNUAL WINTER

SUNLIGHT QUANTUM (PROBABLE SUNLIGHT HOURS)

DAYLIGHT DISTRIBUTIONDAYLIGHT QUANTUM

WOOD STREET - EIGHTH FLOOR

121 L/K/D 2.6 99 N/A 48 15122 Bedroom 2.6 99 MET123 Bedroom 1.9 98 MET124 Bedroom 2.9 98 MET125 Bedroom 2.8 100 N/A126 Living Room 2.6 100 N/A127 Bedroom 0.7 96 N/A128 Living Room 3 97 N/A129 Bedroom 0.9 98 MET130 L/K/D 2.8 100 N/A 58 18131 L/K/D 2.9 100 N/A 68 24132 Bedroom 0.9 99 MET133 Bedroom 1.3 99 MET134 L/K/D 2.1 99 N/A 50 15

Table 09: Assessment Data

Wood Street - Eighth Floor

Page 33: Daylight & Sunlight

18 January 2021 31

CHARTERED SURVEYORS

nn

Fig. 10: Floor Plan

Page 34: Daylight & Sunlight

32 WOOD StREEt liBRaRy, FORESt ROaD INTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT (17026)

ROOM REF. ROOM USE ADF (%) NSL (%) RDC ANNUAL WINTER

SUNLIGHT QUANTUM (PROBABLE SUNLIGHT HOURS)

DAYLIGHT DISTRIBUTIONDAYLIGHT QUANTUM

WOOD STREET - NINTH FLOOR

135 L/K/D 2.7 99 N/A 54 19136 Bedroom 1.9 94 MET137 Bedroom 2.9 97 MET138 Bedroom 2.3 96 N/A139 Living Room 2.4 100 N/A140 Bedroom 0.4 94 N/A141 Living Room 2.7 97 MET142 Bedroom 0.8 99 MET143 L/K/D 3.8 100 N/A 86 30144 L/K/D 4 100 N/A 96 30145 Bedroom 0.5 97 MET146 Bedroom 0.8 91 N/A147 L/K/D 2.3 97 N/A 54 19

Table 10: Assessment Data

Wood Street - Ninth Floor

Page 35: Daylight & Sunlight

18 January 2021 33

CHARTERED SURVEYORS

nn

Fig. 11: Floor Plan

Page 36: Daylight & Sunlight

34 WOOD StREEt liBRaRy, FORESt ROaD INTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT (17026)

ROOM REF. ROOM USE ADF (%) NSL (%) RDC ANNUAL WINTER

SUNLIGHT QUANTUM (PROBABLE SUNLIGHT HOURS)

DAYLIGHT DISTRIBUTIONDAYLIGHT QUANTUM

WOOD STREET - TENTH FLOOR

148 L/K/D 2.8 99 N/A 54 19149 Bedroom 1.9 94 MET150 Bedroom 2.8 97 MET151 Bedroom 2.3 96 N/A152 Living Room 2.4 100 N/A153 Bedroom 0.5 94 N/A154 Living Room 2.6 97 MET155 Bedroom 0.9 99 MET156 L/K/D 3.8 100 N/A 87 30157 L/K/D 3.9 100 N/A 97 30158 Bedroom 0.6 97 MET159 Bedroom 0.9 91 N/A160 L/K/D 2.3 98 N/A 53 19

Table 11: Assessment Data

Wood Street - Tenth Floor

Page 37: Daylight & Sunlight

18 January 2021 35

CHARTERED SURVEYORS

nn

Fig. 12: Floor Plan

Page 38: Daylight & Sunlight

36 WOOD StREEt liBRaRy, FORESt ROaD INTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT (17026)

n

<2 2+

BRE TEST - 21ST MARCHSUN HOURS ON GROUND

96%

(BRE RECOMMENDS 2+ HOURS OF SUNLIGHT ON 21ST MARCH FOR AT LEAST 50% OF THE OPEN SPACE)

9 OVERShaDOWing aSSESSMEntS

OVERSHADOWING ASSESSMENT - COMMUNAL OPEN SPACESun hOuRS On gROunD - BRE tESt - 21St MaRCh

Page 39: Daylight & Sunlight

18 January 2021 37

CHARTERED SURVEYORS

n

21st MARCH(SPRING EQUINOX)

LONDONLatitude: 51.4Longitude: 0.0Sunrise: 06:02 GMTSunset: 18:14 GMT

Total Available Sunlight:12hrs 12mins0.0 0.5 3.01.0 3.51.5 4.02.0 4.52.5 5

SUN EXPOSURETOTAL HOURS

5.5 6.0+

OVERSHADOWING ASSESSMENT - COMMUNAL OPEN SPACE Sun EXPOSuRE On gROunD - 21St MaRCh

Page 40: Daylight & Sunlight

38 WOOD StREEt liBRaRy, FORESt ROaD INTERNAL DAYLIGHT, SUNLIGHT AND OVERSHADOWING REPORT (17026)

n

21st JUNE(SUMMER SOLSTICE)

LONDONLatitude: 51.4Longitude: 0.0Sunrise: 04:43 GMTSunset: 21:21 GMT

Total Available Sunlight:16hrs 38mins0.0 0.5 3.01.0 3.51.5 4.02.0 4.52.5 5

SUN EXPOSURETOTAL HOURS

5.5 6.0+

OVERSHADOWING ASSESSMENT - COMMUNAL OPEN SPACE Sun EXPOSuRE On gROunD - 21St JunE

Page 41: Daylight & Sunlight

18 January 2021 39

CHARTERED SURVEYORS

Page 42: Daylight & Sunlight