1
DC 55 High Volume Grating Panel Air Flow Test
StaticPressure
WithoutDamper
With Damper(50% Opened)
Ins.In H20 CFM CFM
0.010 818.1 411.4
0.020 1067.1 594.5
0.030 1311.9 734.5
0.040 1497.9 864.0
0.050 1696.9 958.8
0.060 1775.2 1049.4
0.070 1935.8 1141.3
0.080 2065.3 1224.8
0.090 2134.8 1307.2
0.100 2310.2 1403.2