DDA Compliance Check list for requirements, for lift installations with Level 1 facilities BS EN81-70 Is access to the lift adequately signposted from the building entrance? Does the lift serve all levels? Does the lift serve the main entry level? Are automatic doors fitted? Is clear opening 800mm wide or more? (900 mm wide for type-3 lifts) Is an electronic door detector edge fitted? Is the door dwell time adjustable between 2 to 15 seconds to allow adequate time for Disabled USers to enter lift? Is there a clear space of 1500mm wide x 1500mm deep on each landing in front of the lift openings? Is there adequate lighting on lift lobbies? Are pushes on landing located between 900mm and 1100mm above floor level and a minimum of 500mm from return? Do pushes have audible and visual acceptance of call acceptance? Is there a tactile floor designation plate on each landing adjacent to the push plate? Are landing indicators in accordance with Table 2? Is the car operating panel located on one side wall of the car with first push at 400mm back from car front? Are car pushes locate between 900mm and 1100mm above floor level? Are the alarm and door open buttons located at 900mm above car floor level? Is the main car push button green and does it protrude 5mm beyond plate? Are all push buttons of a tactile type and compliant size and do they contrast with faceplate material? Does the alarm button illuminate when pressed and is it yellow? Is there a position indicator within the lift car and is it 30-60mm high, located between 1600-1800mm above floor? Is the lift car internal size suitable for wheelchair access? See Table 1. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Provide adequate signage as per BS 8300. Convert doors to full power operation. If practical, increase door opening width by replacing entrances. Install electronic detector edge(s). Install adjustable door open timer unless this facility already exists on controller. If practical, relocate any obstructions to achieve cleat dimensions. Client to upgrade lighting to achieve 100 lux at floor level. Replace pushes with integral call acceptance and tactile pressels at height required to comply. Replace pushes with integral audible/visual call acceptance and tactile pressels. Provide 100mm min. character tactile floor designation plate to return of door. Variable requirements, see Table 2. Replace car operating panel with integral audible/visual call acceptance and tactile pressels, locate in side wall where practical 400mm from front at height required. See item 14 above. See item 14 above. See item 14 above. See item 14 above. Modify wiring for acceptance lamp or change alarm button to comply Provide position indicator to show floor levels. If practical, increase the size of the lift car to comply. Beware of increased loading! Ref Item Compliant Action Required To Comply Yes or No? DATE: BY: ADDRESS: CONTINUED OVERLEAF

Upload: hakhanh

Post on 05-Feb-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DDA Compliance - Guideline Lift Services · PDF fileTYPE ACCESS REQUIREMENT ... Lift arrival sounders should be fitted wither on car or at each floor with different tones (1 for UP

DDA ComplianceCheck list for requirements, for lift installations with Level 1 facilities BS EN81-70

Is access to the lift adequately signposted from the building entrance?

Does the lift serve all levels?

Does the lift serve the main entry level?

Are automatic doors fitted?

Is clear opening 800mm wide or more? (900 mm wide for type-3 lifts)

Is an electronic door detector edge fitted?

Is the door dwell time adjustable between 2 to 15 seconds to allow adequate time for Disabled USers to enter lift?

Is there a clear space of 1500mm wide x 1500mm deep on each landing in front of the lift openings?

Is there adequate lighting on lift lobbies?

Are pushes on landing located between 900mm and 1100mm above floor level and a minimum of 500mm from return?

Do pushes have audible and visual acceptance of call acceptance?

Is there a tactile floor designation plate on each landing adjacent to the push plate?

Are landing indicators in accordance with Table 2?

Is the car operating panel located on one side wall of the car with first push at 400mm back from car front?

Are car pushes locate between 900mm and 1100mm above floor level?

Are the alarm and door open buttons located at 900mm above car floor level?

Is the main car push button green and does it protrude 5mm beyond plate?

Are all push buttons of a tactile type and compliant size and do they contrast with faceplate material?

Does the alarm button illuminate when pressed and is it yellow?

Is there a position indicator within the lift car and is it 30-60mm high, located between 1600-1800mm above floor?

Is the lift car internal size suitable for wheelchair access? See Table 1.

1

234

5

67

8

910

11

12

13

14

15

16

17

18

19

20

21

Provide adequate signage as per BS 8300.

Convert doors to full power operation.

If practical, increase door opening width by replacing entrances.

Install electronic detector edge(s).

Install adjustable door open timer unless this facility already exists on controller.

If practical, relocate any obstructions to achieve cleat dimensions.

Client to upgrade lighting to achieve 100 lux at floor level.

Replace pushes with integral call acceptance and tactile pressels at height required to comply.

Replace pushes with integral audible/visual call acceptance and tactile pressels.

Provide 100mm min. character tactile floor designation plate to return of door.

Variable requirements, see Table 2.

Replace car operating panel with integral audible/visual call acceptance and tactile pressels, locate in side wall where practical 400mm from front at height required.

See item 14 above.

See item 14 above.

See item 14 above.

See item 14 above.

Modify wiring for acceptance lamp or change alarm button to comply

Provide position indicator to show floor levels.

If practical, increase the size of the lift car to comply. Beware of increased loading!

Ref Item Compliant Action Required To Comply Yes or No?

DATE: BY: ADDRESS:

CONTINUED OVERLEAF

Page 2: DDA Compliance - Guideline Lift Services · PDF fileTYPE ACCESS REQUIREMENT ... Lift arrival sounders should be fitted wither on car or at each floor with different tones (1 for UP

Is there a speech synthesiser fitted?

Is there a hands-free autodialler fitted with contact to a 24-hour source of assistance and is it fitted with an inductive loop cou-pler and visual confirmation of call?

Is there adequate lighting within the lift car?

Is the car flooring of a non-slip type?

Is there adequate colour contrast between car and landing floor finishes?

Are there handrails fitted within the lift car at a height of 900mm above floor level?

For car types 1 & 2, is there a mirror on the rear wall of a single entry car, 900mm above floor level?

Is temporary activation of adjustable door dwell period and voice annunciator provided?

Is the drive system capbale of achieving stopping accuracy of +_ 10mm?

2223

24

2526

27

28

29

30

Provide and fit speech unit with driver board for existing controller.

Install hands-free autodialler complete with inductive loop, preferably as part of new COP, alternatively, as a separate fitting. Client to provide telephone!

Upgrade lighting to achieve 100 lux at floor level.

Replace car flooring with contrasting non-slip type.

Replace floor covering to contrast with landing flooring colour.

Provide new 35mm min. dia. tubular handrail to at least one side wall.

Provide new laminated safety glass mirror, securely mounted to rear car wall

Not essential requirment, but advisable on busy or group lifts.

Upgrade or replace drive system as appropriate with new shaft controls.

Check list for requirements, continued

WHERE ‘YES’ IS INSERTED IN COLUMN, NO ACTION IS REQUIRED

Ref Item Compliant Action Required To Comply Yes or No?

TYPE ACCESS REQUIREMENT (WHEELCHAIR TYPE) CAR SIZE/ CAPACITY

1 Unaccompanied Manual or Electric Wheelchair 1000mm wide x 1250mm deep / 6-Person

2 Accompanied Manual or Electric Wheelchair 1100mm wide x 1400mm deep / 8-Person

3 Any type of wheelchair 2000mm wide x 1400mm deep / 16-Person

CONTROL SYSTEM TYPE TYPE AND LOCATION OF INDICATION

Simple Automative Push Button Audible indication of doors opening on landings.

Collective control Direction of departure arrows should be fitted which are 40-70 mm high, located above or adjacent to doors.

Lift arrival sounders should be fitted wither on car or at each floor with different tones (1 for UP and 2 for DOWN).

TABLE 1

TABLE 2