24 May 2012 PMI Revision 00 1 DDCMIS (DIGI T AL DISTRIBUTED CONTROLS AND MANAMAGEMENT INFORMATION SYSTEMS)

Upload: sam

Post on 05-Apr-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 1/58

Page 2: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 2/58

24 May 2012 PMI Revision 00  2

Page 3: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 3/58

24 May 2012 PMI Revision 00  3

• INTEGRATED PLANT CONTROL SYSTEM FORSG, TG AND BALANCE OF PLANT.

• INTEGRATED PLANT OPERATION THROUGH

FULLY INTERCHANGEABLE OPERTAOR WORKSTATIONS (OWS) FOR SG, TG AND BALANCEOF PLANT

• IT MAY BE REMEMBERED THAT THE TERM

DDCMIS USED TO BE REFERRED FOR THESO-CALLED “BOP - C&I”  , THE “SG-C&I”, i.e.FSSS, BOILER PROTECTION AND “TG-C&I” i.e.ATRS, TURBINE PROTECTION etc.

Page 4: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 4/58

Page 5: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 5/58

Page 6: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 6/58

24 May 2012 PMI Revision 00  6

maxDNA

SYSTEM

HMI

REDUNDANT

SERVERS

RedundantF.G.Controllers

ENGG.STN.

FOR CONTROL SYS.

HMIENGG. STN

FOR HMI

PROCONTROL

SYSTEM

Measurement system / I/O

subsystem

I.P. BUS Max. 4nos. rdundant

MMI LAN

Page 7: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 7/58

24 May 2012 PMI Revision 00  7

Page 8: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 8/58

24 May 2012 PMI Revision 00  8

• CONTROL SYSTEM

• MAN-MACHINE INFORMATION AND PLANT

INFORMATION SYSTEM (MMIPIS)

• REDUNDANT DATA COMMUNICATION SYSTEM(DCS).

• MASTER & SLAVE CLOCK SYSTEM.

Page 9: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 9/58

24 May 2012 PMI Revision 00  9

• SEQUENCE OF EVENT (SOE ) ANDANNUNCIATION SYSTEM FUNCTIONS.

• SYSTEM PROGRAMMING FACILITY:-

a) TUNING & CONFIGURATION FOR

CONTROL SYSTEM.

b) MODIFICATION & PROGRAMDEVELOPMENT FOR MMIPIS.

Page 10: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 10/58

Page 11: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 11/58

24 May 2012 PMI Revision 00  11

PROCONTROL P13/42 CONTAINS A BUSSYSTEM:-

• P-42 REPRESENTS INTRA PLANT BUS, IS

RESPONSIBLE FOR SIGANL TRANSPORT.

• P-13 REPRESENTS LOCAL BUS, ISRESPONSIBLE FOR SIGANL CONVERSION AND

SIGNAL PROCESSING.

Page 12: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 12/58

24 May 2012 PMI Revision 00  12

Page 13: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 13/58

24 May 2012 PMI Revision 00  13

Page 14: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 14/58

24 May 2012 PMI Revision 00  14

Page 15: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 15/58

24 May 2012 PMI Revision 00  15

Page 16: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 16/58

Page 17: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 17/58

24 May 2012 PMI Revision 00  17

Page 18: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 18/58

24 May 2012 PMI Revision 00  18

CONTROL SYSTEM

PROGRAMMING & MMIPIS M & S

CONFIGURATION SYSTEM CLOCK

SG- C&I BOP- C&I TG- C&I

SYSTEM SYSTEM SYSTEM

DCS

Page 19: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 19/58

24 May 2012 PMI Revision 00  19

SG-C&I SYSTEM

SG-C&I SYSTEM CONSISTS OF :

1. BURNER MANAGEMENT SYSTEM (BMS).

2. SOOT BLOWER CONTROL SYSTEM (SBC). 

3. SECONDARY AIR DAMPER CONTROL SYSTEM(SADC).

4. AUXILIARY PRDS CONTROL SYSTEM (APRDS).

Page 20: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 20/58

Page 21: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 21/58

Page 22: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 22/58

24 May 2012 PMI Revision 00  22

TG-C&I SYSTEM FEATURES

• TRIPLE REDUNDANT OR 2 X 100 % REPEATEDTWICE CONFIGURATION FOR THE TURBINE

PROTECTION SYSTEM (TPS). FOR THIS,SAFETY SYSTEM HARDWARE OR FAIL-SAFEHARDWARE SHALL BE USED.

• FOR OTHERS, CONFIGURATION SIMILAR TO

OLCS/CLCS TO BE USED.

Page 23: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 23/58

24 May 2012 PMI Revision 00  23

BOP-C&I SYSTEM

BOP-C&I SYSTEM CONSISTS OF : 

1. OPEN LOOP CONTROL SYSTEM (OLCS).

2. CLOSED LOOP CONTROL SYSTEM (CLCS).

OLCS INCLUDES THE SEQUENCE CONTROL ANDTHE INTERLOCK OF ALL THE PLANT SYSTEMS

WHICH ARE NOT COVERED IN SG-C&I AND TG-C&I.THIS INCLUDES MAJOR AUXILIARIES LIKE FD/ID/PAFANS, AIR-PREHEATER, BFP/CEP/CWP/ BCWP/ DMCWP/CLCWP AND ELECTRICAL BREAKERS. 

Page 24: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 24/58

Page 25: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 25/58

Page 26: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 26/58

24 May 2012 PMI Revision 00  26

MAN-MACHINE INTERFACE AND

PLANT INFORMATION SYSTEM• LATEST STATE-OF-THE-ART WORKSTATIONS

 /PCs AND SERVERS BASED ON OPEN-

ARCHITECTURE AND INDUSTRY STANDARDHARDWARE AND SOFTWARE TO ENSUREBETTER CONNECTIVITY.

• HARDWARE FROM COMPAQ/DIGITAL, HP, SUN

MICRO-SYSTEM OR OTHER MAJOR SUPPLIERS• OPERATING SYSTEM WINDOWS-2000, OPEN-

VMS OR UNIX.

Page 27: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 27/58

24 May 2012 PMI Revision 00  27

MAN-MACHINE INTERFACE AND

PLANT INFORMATION SYSTEM• 64/ 32-BIT SERVER/OWS WITH HIGH-SPEED AND

LARGE MEMORY (256/512 MB RAM, 8 GB HDD FORSERVER AND 128/256 MB RAM AND 4/6 GB HDD FOROWS) TO ENSURE FAST RESPONSE.

• PROVISION OF LVS (LARGE VIDEO SCREEN).

• CONNECTION TO OTHER SYSTEM THROUGHSTATIONWIDE WAN.

Page 28: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 28/58

24 May 2012 PMI Revision 00  28

• VPC OPERATION

• OTHER OPERATOR INFORMATIONS THROUGHVARIOUS DISPLAYS

• ALARMS, LOGS, HISTORICAL AND LONG TERMSTORAGE.

• PERFORMANCE AND OTHER CALCULATIONS

Page 29: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 29/58

24 May 2012 PMI Revision 00  29

Page 30: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 30/58

24 May 2012 PMI Revision 00  30

Page 31: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 31/58

Page 32: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 32/58

24 May 2012 PMI Revision 00  32

SEQUENCE OF EVENT (SOE )

AND ANNUNCIATION SYSTEM FUNCTIONS 

• ORIGINALLY THESE USED TO BE STAND-ALONESYSTEM (DIODE AUCTIONEERING, DBTC ETC

REQUIRED)• NOW INTEGRATED -THEREFORE THE DIODE

AUCTIONEERING, DBTC ETC NOT REQUIRED.

• SOE - 1mS RESOLUTION, STORAGE OF REPOTS

FOR LONG DURATION• ANNUNCIATION LOGIC THROUGH OLCS/CLCS

CONTROLLERS.

Page 33: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 33/58

Page 34: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 34/58

24 May 2012 PMI Revision 00  34

• Event Activated logs

 – SOE

 – Post Trip Log

 – Start-Up Log

• Time Activated Logs

 – Daily Log

 – Shift Log

• Maintenance Data Log

• On Demand Logs

Page 35: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 35/58

Page 36: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 36/58

24 May 2012 PMI Revision 00  36

• Displays all the alarms in the order of theiroccurrence

 – Useful for analysing the cause of the major

failures. – All digital DATA and Analog values crossing the

limits will be displayed in this window in the orderof their occurrence.

Page 37: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 37/58

24 May 2012 PMI Revision 00  37

REAL TIME TREND

• Operator can configure the required points for realtime trending purpose and can see the real time

trend and in case of any deviation (abnormalchange) can react quickly.

OPERATOR GUIDANCE MESSAGES

• Operator Guidance messages can be displayed onthe DAS monitors when rolling or any importantactivity is going on.

Page 38: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 38/58

24 May 2012 PMI Revision 00  38

• CPU

• I/O CARDS

• CRTS

• PRINTERS

• NETWORK

Page 39: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 39/58

Page 40: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 40/58

Page 41: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 41/58

* Di it l I t M d l

Page 42: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 42/58

24 May 2012 PMI Revision 00  42

* Digital Input Module

Process 16 Digital Inputs

Page 43: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 43/58

24 May 2012 PMI Revision 00  43

* Analog Output Module

4 Outputs

Outputs are short circuit protected

Scan time 8 millisecond

Resolution 12 Bit

Page 44: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 44/58

24 May 2012 PMI Revision 00  44

* Digital Output Module

16 Outputs are available

Contact Rating

5 A 240 V AC

3 A 30 V DC

0.3 A 110 V DC

Page 45: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 45/58

Page 46: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 46/58

24 May 2012 PMI Revision 00  46

SYSTEM

PROGRAMMINGFACILITY

Page 47: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 47/58

24 May 2012 PMI Revision 00  47

SYSTEM PROGRAMMING FACILITY

• LATEST TREND - COMBINED CONTROL

SYSTEM TUNING & MMIPIS PROGRAMMING

• SELF-DOCUMENTATION

• ENGINEERING WORKSTATIONS

Page 48: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 48/58

24 May 2012 PMI Revision 00  48

• Graphical object-orientedconfiguration software tool.

• Includes self-documentation

of configuration.• True object-orientedfeatures includingencapsulation and

inheritance.• Library of standard

algorithms or “objects”. 

Object-Oriented Configuration

Page 49: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 49/58

Page 50: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 50/58

Page 51: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 51/58

24 May 2012 PMI Revision 00  51

• POWER SUPPLY SYSTEM 

• CABLING & TERMINATION OF SG/TG C&I SYSTEM/ 

EQUIPMENT.

• OPERATION PHILOSOPHY , CONTROL AREA AND

BACK-UP INSTRUMENTATION & GEOGRAPHICAL

DISTRIBUTION - COMBINED CYCLE PLANTS.

• REDUNDANCY

• DESIGN CRITERIA

Page 52: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 52/58

24 May 2012 PMI Revision 00  52

CONTROL SYSTEM POWER SUPPLY 

• TWO SETS OF DC POWER SUPPLIES - ONE SET FORSG/TG-C&I AND OTHER FOR BOP-C&I EACH WITH 2 X100 % CHARGER AND 2 X 100 % BATTERY. 

• OTHER IMPORTANT AC LOADS LIKE MMIPIS, PANELINSTRUMENTS, ANALYSERS ETC. SHALL BEPOWERED FROM UPS COMPRISING OF 2 X 100 %CHARGER, 2 X 100 % INVERTER AND 1 X 100 %

BATTERY.• HEAVY DUTY Ni-Cd BATTERIES HAVE BEEN

ENVISAGED FOR LONGER LIFE & LESSERMAINTENANCE

Page 53: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 53/58

24 May 2012 PMI Revision 00  53

• EXTENSIVE GROUPING OF SIGNALS BY LARGE

SCALE USE OF JBs AT STRATEGIC LOCATIONS.

• USE OF CABLES WITH HIGHER NO OF PAIRS.

• USE OF CAGE-CLAMP CONNECTION FOR SYSTEM

CABINETS, MARSHALLING PANELS & OUTGOING

SIDE OF JBs, CJS BOXES etc.

• USE OF PLUG-IN SOCKET AND CONNECTORS FORTRANSMITTERS, SWITCHES, LS/TS etc. 

Page 54: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 54/58

24 May 2012 PMI Revision 00  54

• FLAME MONITORING SYSTEM• COAL FEEDER C&I• ELECTROMATIC SAFETY VALVES• FURNACE TEMP PROBES• ACCOUSTIC PYROMETER FOR FURNACE TEMP PROFILE• BOILER FLAME ANALYSIS SYSTEM• COAL BUNKER LEVEL MONITORING SYSTEM• ELECTRONIC DRUM LEVEL MONITORING SYSTEM

• TURBINE SUPERVISORY SYSTEM• TDBFP TURBINE SUPERVISORY SYSTEM

Page 55: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 55/58

24 May 2012 PMI Revision 00  55

• CENTRALISED OPERATION OF MAIN PLANT THROUGHOWS / LVS.

• OFF-SITE PLANTS TO BE CONTROLLED FROM THEIRLOCAL STATIONS WITH STATION-WIDE LAN DATA LINK.

• MINIMUM BACKUP INSTRUMENTATION.• GEOGRAPHICAL DISTRIBUTION - ALTHOUGH NOT VERY

USEFUL FOR POWER PLANTS AS COMPARED TOPROCESS/INDUSTRIES, BEING ADOPTED FOR FEW

AREAS WHERE SIGNALS ARE CONCENTRATED.• REDUCTION OF CABLING, MUCH LESS ERECTION &

COMMISSIONING TIME.

Page 56: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 56/58

24 May 2012 PMI Revision 00  56

• PROVENNESS

 – SUPPLIER’S EXPERIENCE 

 – SYSTEM EXPERIENCE

 – PROVENNESS VS OBSOLESCENCE

• RELIABILITY AVAILABILITY

 – HARDWARE QUALITY (PUBLISHED MTBF etc.)

 – CONFIGURATION

 – REDUNDANCY

 – FAULT TOLERANCE

• STANDARDISATION AND UNIFORMITY OF H/W

 – SAME SERIES & FAMILY OF H/W AS FAR AS POSSIBLE

 – DIFFICULTIES BECAUSE OF PACKAGING CONCEPTS &RESPOSIBILITY CENTRE & INTERFACES.

Page 57: Ddcmis Lecture

7/31/2019 Ddcmis Lecture

http://slidepdf.com/reader/full/ddcmis-lecture 57/58

24 May 2012 PMI Revision 00  57

• OPERATABILITY – DESIGN CONCEPT - FAIL SAFE ETC. – FALSE TRIP VS SAFETY – OPERATOR CONVENIENCE DURING NORMAL RUNNING &

EMERGENCY – MANAGEMENT REPORTING

• MAINTAINBILITY 

 – STANDARDISATION (AS INDICATED ABOVE) – MODULAR DESIGN AND EXPANDABILITY – DIAGNOSTIC, FAULT IDENTIFICATION AND FAULT TOLERANCE – GUARD AGAINST OBSOLESCENCE – AVAILABILTY OF SPARES

• OTHER CRITERIA – UNIT OPERATION PHILOSOPHY – MARKET TRENDS AND EVOLUTION OF INFORMATION

TECHNOLOGY – FEEDBACKS FROM EXISTING SYSTEMS