Our experienceWith 20 years know-how in the field of Medium Voltage networkprotection, DERVASIL designs and manufactures lightningarresters with zinc oxide varistors and synthetic housings.

Our productsDERVASIL offers:›› A range of latest generation arresters:

5 kA or 10 kA arresters with fault indicator or disconnector.Arresters for power follow current breaking.D.C. voltage arresters.DERVASIL arresters do not have internal spark gaps. They exhibit stable characteristics, with practically constant, very short response times (30 to 50 ns), and better behaviour underpollution.Direct injection of Silicone Rubber ensures both absolute sealing, exceptional resistance to pollution and excellent behaviour without explosion in case of short-circuitThey have been tested in accordance with the latest version of IEC Standard 60099-4.

›› New range of composite insulators: suspension insulators, tension insulators and support insulators.

Our R & D departmentDERVASIL has comprehensive calculation and testing equipmentfor the design of lightning arresters. Our facilities are available tocustomers for specific applications.

Our quality and environmental systemDERVASIL is ISO 9001 and ISO 14001 system certified.Our production process is approved by EDF and incorporates allroutine tests required by IEC Standard 60099-4. !

This documentation is not as per agreement.Items represented are proposed while stock lasts.

DERVASIL reserve the right to stop productionor modify specifications without prior notice.

Non-contractual pictures

Com ST

dervasil

couve catalogue Dervsasil 28/05/08 10:20 Page 3

Page 3: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

General contents

Gene

ral c

onte

nts

Ligthning arrester construction 5

General references index 8

AZB, AZBD, AZC series 10 kA arrester

A.C medium voltage network protection10

EZB, EZBD series 5 kA arrester

A.C medium voltage network protection22

AZ--T series 10 kA arrester

D.C medium voltage network protection30

Accessories 34

Composite insulators 40

Ligthning arrester specification 43

catalogue Dervasil 28/05/08 10:21 Page 1

Page 4: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

2 3

Direct injection of SiliconeRubber over the internal module.This ensures both sealingof the varistor/tubeinterface and the geometryof external insulation toguarantee length ofleakage distance.

Use of Silicone Rubber:• The stability of the SiO

molecule gives toSilicone Rubber excellentinherent resistance to UVradiation, pollution andflame without the needfor of special additives.

• When new, Siliconematerial is already veryhydrophobic. It hasmoreover the property ofrestoring thishydrophobiccharacteristic after strongelectrical dischargeactivity due to salt fogsand pollution.

Identification andtraceability ensured byengraved marking.

Polymeric Glass FilledTube, up-sized greatly towithstand service andmounting mechanicalstrength requirements.

The contacts betweenmetal oxide varistors areprovided by springwashers, which arespecially designed todistribute lightning currentimpulses on the varistorsurface and to increasearrester energy capability.

Substantial connectingelectrodes to fix power arcfeet during internal short-circuit and thus to avoidarrester breaking down.

HIGH RELIABILITY ARRESTERSAZB / EZB / AZC SERIES

Designed and manufactured according to quality system ISO 9001-2000 and environmental system ISO 14001

Direct injection of SiliconeRubber over the internal module.This ensures both sealingand the geometry ofexternal insulation toguarantee length ofleakage distance.

Use of Silicone Rubber:• The stability of the SiO

molecule gives toSilicone Rubber excellentinherent resistance to UVradiation, pollution andflame without the needfor of special additives.

• When new, Siliconematerial is already veryhydrophobic. It hasmoreover the property ofrestoring thishydrophobiccharacteristic after strongelectrical dischargeactivity due to salt fogsand pollution.

Identification andtraceability ensured byengraved marking.

Fiber Glass Epoxy Wrap,up-sized greatly towithstand service andmounting mechanicalstrength requirements.

Substantial connectingelectrodes to fix power arcfeet during internal short-circuit and thus to avoidarrester breaking down.

Polymeric GlassFilled Tube

Fiber Glass EpoxyWrap

HIGH MECHANICAL WITHSTANDARRESTERS AZBD / EZBD SERIES

catalogue Dervasil 28/05/08 10:21 Page 2

Page 5: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

2 3

Direct injection of SiliconeRubber over the internal module.This ensures both sealingof the varistor/tubeinterface and the geometryof external insulation toguarantee length ofleakage distance.

Use of Silicone Rubber:• The stability of the SiO

molecule gives toSilicone Rubber excellentinherent resistance to UVradiation, pollution andflame without the needfor of special additives.

• When new, Siliconematerial is already veryhydrophobic. It hasmoreover the property ofrestoring thishydrophobiccharacteristic after strongelectrical dischargeactivity due to salt fogsand pollution.

Identification andtraceability ensured byengraved marking.

Polymeric Glass FilledTube, up-sized greatly towithstand service andmounting mechanicalstrength requirements.

The contacts betweenmetal oxide varistors areprovided by springwashers, which arespecially designed todistribute lightning currentimpulses on the varistorsurface and to increasearrester energy capability.

Substantial connectingelectrodes to fix power arcfeet during internal short-circuit and thus to avoidarrester breaking down.

HIGH RELIABILITY ARRESTERSAZB / EZB / AZC SERIES

Designed and manufactured according to quality system ISO 9001-2000 and environmental system ISO 14001

Direct injection of SiliconeRubber over the internal module.This ensures both sealingand the geometry ofexternal insulation toguarantee length ofleakage distance.

Use of Silicone Rubber:• The stability of the SiO

molecule gives toSilicone Rubber excellentinherent resistance to UVradiation, pollution andflame without the needfor of special additives.

• When new, Siliconematerial is already veryhydrophobic. It hasmoreover the property ofrestoring thishydrophobiccharacteristic after strongelectrical dischargeactivity due to salt fogsand pollution.

Identification andtraceability ensured byengraved marking.

Fiber Glass Epoxy Wrap,up-sized greatly towithstand service andmounting mechanicalstrength requirements.

Substantial connectingelectrodes to fix power arcfeet during internal short-circuit and thus to avoidarrester breaking down.

Polymeric GlassFilled Tube

Fiber Glass EpoxyWrap

HIGH MECHANICAL WITHSTANDARRESTERS AZBD / EZBD SERIES

catalogue Dervasil 28/05/08 10:21 Page 2

Page 6: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

4 5

We offer various technological solutions for over voltage protection:

The energy capability of lightning arresters is not infinite. In rare cases,approximately 1 lightning strike in 10,000 exceeds this energy capability. Thearrester then fails in permanent short-circuit; the line circuit breaker opens andcauses definitive outage of power supply.Depending on the service quality required, the network operator has a choicebetween several installation systems.

AZB--0/AZBD--0/AZC--0/EZB--0/EZBD--0 : Arrester module is installed alonebetween line and grounding bracket. In this case the network operator must deploymaintenance staff to locate and change the failed arrester. As it is not easy to identify afailed arrester from the outside, several hours may elapse before the line can beenergised again.

AZB--1/AZBD--1/AZC--1/EZB--1/EZBD--1: A 150 A sensitivity fault indicatoris fitted with the arrester. A black silicone band is clamped around the arrester housingand is visible from several hundreds metres away. When the arrester fails, the band fallsoff and maintenance personnel just have to locate the arrester without black band.Outage duration is significantly reduced. This device can be utilized for networks withgrounded or low ohmic neutral, with high ground fault currents.

AZP--/AZBDP--/AZCP--/EZP--/EZBDP-- : For network with impedancegrounded or ungrounded neutral, with low ground fault currents, we offer 15 A sensitivityfault indicator. This device is screwed onto the arrester and indicates the short-circuit byan orange signal, which is visible from a distance of several hundred metres.Maintenance staff can thus quickly locate the arrester to be changed.

AZB--2/AZBD--2/AZC--2/EZB--2/EZBD--2 : Arrester module is fixed to thepole by insulating bracket. It is connected to ground by a disconnector. When short-circuit occurs, this device disconnects the arrester. The operator can then energize lineagain without having to change the arrester. The power supply is restored quickly butover voltage protection is removed. The network operator must implement periodicmaintenance inspection to replace disconnected arresters.

AZICS--/AZCICS-- : For operators whose network is already spark gap protected,this arrester improves spark gap performances by eliminating power follow currents.There are no more spurious flashovers nor therefore micro cuts and risks to safety. Thistechnological solution can be adapted to rigid insulators or tension insulator strings. Thearrester module is supplied with arcing horn and can be directly fixed to the spark gapside.

AZE--T : Fitted with specific varistors for DC voltage, this arrester is designed for overvoltage protection in DC railway systems. Its high energy capability and resistance tovibrations, make it suitable for installation on locomotives.

AZB / EZB /AZC series:

Zinc oxide varistors are connected in series with aluminium electrodesinto polymeric tube. The Silicone rubber is directly injected into thetube and over the zinc oxide varistor stack. This ensures both sealingand geometry of external insulation.This construction provides both absolute sealing, exceptional resistance to pollution and excellent behaviour without explosion incase of short-circuits.

Application GuideThis guide provides recommendations for selection and application

of DERVASIL lightning arresters to be used for overvoltage protection.

DERVASIL Lightning Arrester Technology:DERVASIL Lightning arrester is a combination of zinc oxide varistors, internal fiber glass structure and Silicone rubber housing.DERVASIL offers two technologies.

AZBD / EZBD series:

Zinc oxide varistors are connected in series with aluminium electrodesto form a complete stack. This stack is tightly wrapped with glass filament impregnated with epoxy resin. This assembly is cured to forma rigid and mechanically strong rod.The Silicone rubber is directly injected over this rod and over aluminiumelectrodes to ensure both sealing and geometry of external insulation.This construction reduces external dimensions and weight and improvesmechanical performance of lightning arresters.

Basic characteristics of DERVASIL Lightning Arrester for three phase systemNominal discharge current In and line discharge class:In IEC 600099-4 the energy absorption capability of lightning arrester is linked to the nominal discharge current In and to the line dischargeclass. As a general rule, the following values of In and line class are suitable:

In system where line distances between arresters are below 5 km or for areas with low ground flash density and low earth resistance, 5 kAlightning arresters may be sufficient. For areas with high lightning flash density or high earth resistance, 10 kA class 1 lightning arrester arepreferable.

For better protection level or for important installations 10 kA class 2 lightning arrester are recommended.

For specific applications as cable or capacitor bank protection, DERVASIL experts can determine good choice.

Continuous Operating Voltage Uc :Uc is the maximum permissible voltage which may be continuously applied between the lightning arrester terminals. As a general rule, Ucshould be:

System with solidly grounded neutralUc higher than 0.58*Un max system

System with low ohmic neutralUc higher than 0.87*Un max system

U maxbiphased

Neutral

U maxbiphased

Neutral

Z < 40 ohms

catalogue Dervasil 28/05/08 10:21 Page 4

Page 7: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

4 5

We offer various technological solutions for over voltage protection:

The energy capability of lightning arresters is not infinite. In rare cases,approximately 1 lightning strike in 10,000 exceeds this energy capability. Thearrester then fails in permanent short-circuit; the line circuit breaker opens andcauses definitive outage of power supply.Depending on the service quality required, the network operator has a choicebetween several installation systems.

AZB--0/AZBD--0/AZC--0/EZB--0/EZBD--0 : Arrester module is installed alonebetween line and grounding bracket. In this case the network operator must deploymaintenance staff to locate and change the failed arrester. As it is not easy to identify afailed arrester from the outside, several hours may elapse before the line can beenergised again.

AZB--1/AZBD--1/AZC--1/EZB--1/EZBD--1: A 150 A sensitivity fault indicatoris fitted with the arrester. A black silicone band is clamped around the arrester housingand is visible from several hundreds metres away. When the arrester fails, the band fallsoff and maintenance personnel just have to locate the arrester without black band.Outage duration is significantly reduced. This device can be utilized for networks withgrounded or low ohmic neutral, with high ground fault currents.

AZP--/AZBDP--/AZCP--/EZP--/EZBDP-- : For network with impedancegrounded or ungrounded neutral, with low ground fault currents, we offer 15 A sensitivityfault indicator. This device is screwed onto the arrester and indicates the short-circuit byan orange signal, which is visible from a distance of several hundred metres.Maintenance staff can thus quickly locate the arrester to be changed.

AZB--2/AZBD--2/AZC--2/EZB--2/EZBD--2 : Arrester module is fixed to thepole by insulating bracket. It is connected to ground by a disconnector. When short-circuit occurs, this device disconnects the arrester. The operator can then energize lineagain without having to change the arrester. The power supply is restored quickly butover voltage protection is removed. The network operator must implement periodicmaintenance inspection to replace disconnected arresters.

AZICS--/AZCICS-- : For operators whose network is already spark gap protected,this arrester improves spark gap performances by eliminating power follow currents.There are no more spurious flashovers nor therefore micro cuts and risks to safety. Thistechnological solution can be adapted to rigid insulators or tension insulator strings. Thearrester module is supplied with arcing horn and can be directly fixed to the spark gapside.

AZE--T : Fitted with specific varistors for DC voltage, this arrester is designed for overvoltage protection in DC railway systems. Its high energy capability and resistance tovibrations, make it suitable for installation on locomotives.

AZB / EZB /AZC series:

Zinc oxide varistors are connected in series with aluminium electrodesinto polymeric tube. The Silicone rubber is directly injected into thetube and over the zinc oxide varistor stack. This ensures both sealingand geometry of external insulation.This construction provides both absolute sealing, exceptional resistance to pollution and excellent behaviour without explosion incase of short-circuits.

Application GuideThis guide provides recommendations for selection and application

of DERVASIL lightning arresters to be used for overvoltage protection.

DERVASIL Lightning Arrester Technology:DERVASIL Lightning arrester is a combination of zinc oxide varistors, internal fiber glass structure and Silicone rubber housing.DERVASIL offers two technologies.

AZBD / EZBD series:

Zinc oxide varistors are connected in series with aluminium electrodesto form a complete stack. This stack is tightly wrapped with glass filament impregnated with epoxy resin. This assembly is cured to forma rigid and mechanically strong rod.The Silicone rubber is directly injected over this rod and over aluminiumelectrodes to ensure both sealing and geometry of external insulation.This construction reduces external dimensions and weight and improvesmechanical performance of lightning arresters.

Basic characteristics of DERVASIL Lightning Arrester for three phase systemNominal discharge current In and line discharge class:In IEC 600099-4 the energy absorption capability of lightning arrester is linked to the nominal discharge current In and to the line dischargeclass. As a general rule, the following values of In and line class are suitable:

In system where line distances between arresters are below 5 km or for areas with low ground flash density and low earth resistance, 5 kAlightning arresters may be sufficient. For areas with high lightning flash density or high earth resistance, 10 kA class 1 lightning arrester arepreferable.

For better protection level or for important installations 10 kA class 2 lightning arrester are recommended.

For specific applications as cable or capacitor bank protection, DERVASIL experts can determine good choice.

Continuous Operating Voltage Uc :Uc is the maximum permissible voltage which may be continuously applied between the lightning arrester terminals. As a general rule, Ucshould be:

System with solidly grounded neutralUc higher than 0.58*Un max system

System with low ohmic neutralUc higher than 0.87*Un max system

U maxbiphased

Neutral

U maxbiphased

Neutral

Z < 40 ohms

catalogue Dervasil 28/05/08 10:21 Page 4

Page 8: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

System Line to Line Voltage (kV) Solidly Grounded

NeutralLow Ohmic

NeutralHigh impedance, compensated

or Underground NeutralNominal Maximum

6.9 7.25 6 9 910 11 9 12 1510 11.8 9 12 15

10.6 12 9 12 1511 12 9 12 15

11.4 12 9 12 1512 13.2 9 15 18

12.6 13.8 9 15 1813.4 15 9 15 1815 16.5 12 18 2115 18 12 18 21

15.4 17.5 12 18 2120 22 15 24 2722 24 18 27 3023 24.5 18 27 3025 27.5 21 30 3330 33 24 36 4233 36 27 42 …

34.5 36.5 27 42 …

76

System with high impedance grounded, compensated or ungrounded neutralUc higher than Un max system

Neutre

Uc = Umax

U maxbiphasé

Rated Voltage Ur :Ur is the maximum power frequency temporary voltage applied for 10s for which the lightning arrester is calculated in order topass operating duty test (IEC 60099-4 standard).Ur is calculated by DERVASIL for each lightning arrester.

Commonly Applied Voltage Rating of Dervasil Arrester (kV)

Lightning Impulse Protective LevelThe lightning impulse protective level (LIPL) of lightning arrester is the maximum residual voltage at nominal discharge current In.

When lightning impulse wave reaches equipment to be protected, current discharge flows through lightning arrester and connecting cables.Overvoltage on equipment is the sum of lightning arrester residual voltage and induced voltage in cables. To warranty goodprotection, Protective Level of lightning arrester must be much lower than lightning impulse withstand voltage of the equipment.To take into account live ageing of insulation material, we recommend:LIPL lower than 0.6*BIL

Following Basic Insulation Levels (BIL) are defined by IEC 60071-1 according nominal voltage of the system.

Un (kV) 3.6 7.2 12 17.5 24 36

BIL (kV) 40 60 75 95 125 170

24 36 45 57 75 102LIPL of

LightningArrester

Equipment to be protected Ures < 0.6 x BIL

Basic characteristics of DERVASIL Lightning Arrester for DC voltage

Continuous Operating Voltage Ucdc :Ucdc is the maximum permissible voltage which may be continuously applied between the lightning arrester terminals.

European standard EN 50163 defines several voltage values:

Umax1 : Highest permanent voltage Umax2 : Highest non-permanent voltage present for maximum 300s

As general rules we recommend Ucdc higher than Umax2

Following table gives Umax1, Umax2, recommended Ucdc and lightning arrester type for most frequent DC network :

Nominal Voltage(V)

Umax 1(V)

Umax 2(V)

RecommandedUcdc (V)

RecommandedLightning Arrester

600 720 770 1000 AZE 010T

750 900 950 1200 AZE 012T

1500 1800 1950 2400 AZE 020T

3000 3600 3900 4000 AZE 040T

Z > 40 ohms ou

Z = infini

catalogue Dervasil 28/05/08 10:21 Page 6

Page 9: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

System Line to Line Voltage (kV) Solidly Grounded

NeutralLow Ohmic

NeutralHigh impedance, compensated

or Underground NeutralNominal Maximum

6.9 7.25 6 9 910 11 9 12 1510 11.8 9 12 15

10.6 12 9 12 1511 12 9 12 15

11.4 12 9 12 1512 13.2 9 15 18

12.6 13.8 9 15 1813.4 15 9 15 1815 16.5 12 18 2115 18 12 18 21

15.4 17.5 12 18 2120 22 15 24 2722 24 18 27 3023 24.5 18 27 3025 27.5 21 30 3330 33 24 36 4233 36 27 42 …

34.5 36.5 27 42 …

76

System with high impedance grounded, compensated or ungrounded neutralUc higher than Un max system

Neutre

Uc = Umax

U maxbiphasé

Rated Voltage Ur :Ur is the maximum power frequency temporary voltage applied for 10s for which the lightning arrester is calculated in order topass operating duty test (IEC 60099-4 standard).Ur is calculated by DERVASIL for each lightning arrester.

Commonly Applied Voltage Rating of Dervasil Arrester (kV)

Lightning Impulse Protective LevelThe lightning impulse protective level (LIPL) of lightning arrester is the maximum residual voltage at nominal discharge current In.

When lightning impulse wave reaches equipment to be protected, current discharge flows through lightning arrester and connecting cables.Overvoltage on equipment is the sum of lightning arrester residual voltage and induced voltage in cables. To warranty goodprotection, Protective Level of lightning arrester must be much lower than lightning impulse withstand voltage of the equipment.To take into account live ageing of insulation material, we recommend:LIPL lower than 0.6*BIL

Following Basic Insulation Levels (BIL) are defined by IEC 60071-1 according nominal voltage of the system.

Un (kV) 3.6 7.2 12 17.5 24 36

BIL (kV) 40 60 75 95 125 170

24 36 45 57 75 102LIPL of

LightningArrester

Equipment to be protected Ures < 0.6 x BIL

Basic characteristics of DERVASIL Lightning Arrester for DC voltage

Continuous Operating Voltage Ucdc :Ucdc is the maximum permissible voltage which may be continuously applied between the lightning arrester terminals.

European standard EN 50163 defines several voltage values:

Umax1 : Highest permanent voltage Umax2 : Highest non-permanent voltage present for maximum 300s

As general rules we recommend Ucdc higher than Umax2

Following table gives Umax1, Umax2, recommended Ucdc and lightning arrester type for most frequent DC network :

Nominal Voltage(V)

Umax 1(V)

Umax 2(V)

RecommandedUcdc (V)

RecommandedLightning Arrester

600 720 770 1000 AZE 010T

750 900 950 1200 AZE 012T

1500 1800 1950 2400 AZE 020T

3000 3600 3900 4000 AZE 040T

Z > 40 ohms ou

Z = infini

catalogue Dervasil 28/05/08 10:21 Page 6

Page 10: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

8

A.C medium voltagenetwork protection

A.C

med

ium

vol

tage

net

wor

k pr

otec

tion

10kA

arre

ster

10 kA arrester - Class 1AZB seriesAZBD series

10 kA arrester - Class 2AZC series

General characteristics AZB, AZBD, AZC 10

Standard arrester AZB-0, AZBD-0, AZC-0 16

Arrester with 150 A fault indicator AZB--1, AZBD--1, AZC--1 17

Arrester with 15 A fault indicator AZP--, AZBDP-, AZCP--, 18

Arrester with disconnector AZB--2, AZBD--2, AZC--2 19

Arrester for power follow current breaking AZICS--, AZCICS-- 20

General references indexReference PageReference PageReference PageReference Page

AZ 5050.......34AZB 030.......16AZB 031.......17AZB 032.......19AZB 060.......16AZB 061.......17AZB 062.......19AZB 090.......16AZB 091.......17AZB 092.......19AZB 120.......16AZB 121.......17AZB 122.......19AZB 150.......16AZB 151.......17AZB 152.......19AZB 180.......16AZB 181.......17AZB 182.......19AZB 210.......16AZB 211.......17AZB 212.......19AZB 240.......16AZB 241.......17AZB 242.......19AZB 270.......16AZB 271.......17AZB 272.......19AZB 300.......16AZB 301.......17AZB 302.......19AZB 330.......16AZB 331.......17AZB 332.......19AZB 360.......16AZB 361.......17AZB 362.......19AZB 390.......16AZB 391.......17AZB 392.......19AZBD 030.....16AZBD 031.....17AZBD 032.....19AZBD 060.....16AZBD 061.....17AZBD 062.....19AZBD 090.....16AZBD 091.....17AZBD 092.....19AZBD 120.....16AZBD 121.....17AZBD 122.....19AZBD 150.....16AZBD 151.....17AZBD 152.....19AZBD 180.....16AZBD 181.....17AZBD 182.....19AZBD 210.....16AZBD 211.....17AZBD 212.....19

AZBD 240.....16AZBD 241.....17AZBD 242.....19AZBD 270.....16AZBD 271.....17AZBD 272.....19AZBD 300.....16AZBD 301.....17AZBD 302.....19AZBD 330.....16AZBD 331.....17AZBD 332.....19AZBD 360.....16AZBD 361.....17AZBD 362.....19AZBD 390.....16AZBD 391.....17AZBD 392.....19AZBD 420.....16AZBD 422.....19AZBDP 03 .....18AZBDP 06 .....18AZBDP 09 .....18AZBDP 12 .....18AZBDP 15 .....18AZBDP 18 .....18AZBDP 21 .....18AZBDP 24 .....18AZBDP 27 .....18AZBDP 30 .....18AZBDP 33 .....18AZBDP 36 .....18AZBDP 39 .....18AZBDP 42 .....18AZC 030 ......16AZC 031 ......17AZC 032 ......19AZC 060 ......16AZC 061 ......17AZC 062 ......19AZC 090 ......16AZC 091 ......17AZC 092 ......19AZC 120 ......16AZC 121 ......17AZC 122 ......19AZC 150 ......16AZC 151 ......17AZC 152 ......19AZC 180 ......16AZC 181 ......17AZC 182 ......19AZC 210 ......16AZC 211 ......17AZC 212 ......19AZC 240 ......16AZC 241 ......17AZC 242 ......19AZC 270 ......16AZC 271 ......17AZC 272 ......19

AZC 300 ......16AZC 301 ......17AZC 302 ......19AZC 330 ......16AZC 331 ......17AZC 332 ......19AZC 360 ......16AZC 361 ......17AZC 362 ......19AZC 390 ......16AZC 391 ......17AZC 392 ......19AZCICS 090....20AZCICS091...20AZCICS 120....20AZCICS 121....20AZCICS 150....20AZCICS 151....20AZCICS 180....20AZCICS 181....20AZCICS 200....20AZCICS 201....20AZCICS 240....20AZCICS 241....20AZCICS 300....20AZCICS 301....20AZCICS 360....20AZCICS 361....20AZCP 03.......18AZCP 06.......18AZCP 09.......18AZCP 12.......18AZCP 15.......18AZCP 18.......18AZCP 21.......18AZCP 24.......18AZCP 27.......18AZCP 30.......18AZCP 33.......18AZCP 36.......18AZCP 39.......18AZE 010 T ....30AZE 012 T ....30AZE 020 T ....30AZE 030 T ....30AZE 040 T ....30AZE 050 T ....30AZE 060 T ....30AZE 080 T ....30AZICS 090....20AZICS 091....20AZICS 120....20AZICS 121....20AZICS 150....20AZICS 151....20AZICS 180....20AZICS 181....20AZICS 200....20AZICS 201....20AZICS 240....20AZICS 241....20

AZICS 300....20AZICS 301....20AZICS 360....20AZICS 361....20AZNEMA ......35AZP 03 .........18AZP 06 .........18AZP 09 .........18AZP 12 .........18AZP 15 .........18AZP 18 .........18AZP 21 .........18AZP 24 .........18AZP 27 .........18AZP 30 .........18AZP 33 .........18AZP 36 .........18AZP 39 .........18AZPTR ...........34CAP M10......37DSIL 3 ...........42DSIL 15 .........40DSIL 20 .........40DSIL 30 .........40EZB 030 .......26EZB 031 .......27EZB 032 .......28EZB 060 .......26EZB 061 .......27EZB 062 .......28EZB 090 .......26EZB 091 .......27EZB 092 .......28EZB 120 .......26EZB 121 .......27EZB 122 .......28EZB 150 .......26EZB 151 .......27EZB 152 .......28EZB 180 .......26EZB 181 .......27EZB 182 .......28EZB 210 .......26EZB 211 .......27EZB 212 .......28EZB 240 .......26EZB 241 .......27EZB 242 .......28EZB 270 .......26EZB 271 .......27EZB 272 .......28EZB 300 .......26EZB 301 .......27EZB 302 .......28EZB 330 .......26EZB 331 .......27EZB 332 .......28EZB 360 .......26EZB 361 .......27EZB 362 .......28EZB 390 .......26

Reference Page

EZB 391 .......27EZB 392 .......28EZBD 030 .....26EZBD 031 .....27EZBD 032 .....28EZBD 060 .....26EZBD 061 .....27EZBD 062 .....28EZBD 090 .....26EZBD 091 .....27EZBD 092 .....28EZBD 120 .....26EZBD 121 .....27EZBD 122 .....28EZBD 150 .....26EZBD 151 .....27EZBD 152 .....28EZBD 180 .....26EZBD 181 .....27EZBD 182 .....28EZBD 210 .....26EZBD 211 .....27EZBD 212 .....28EZBD 240 .....26EZBD 241 .....27EZBD 242 .....28EZBD 270 .....26EZBD 271 .....27EZBD 272 .....28EZBD 300 .....26EZBD 301 .....27EZBD 302 .....28EZBD 330 .....26EZBD 331 .....27EZBD 332 .....28EZBD 360 .....26EZBD 361 .....27EZBD 362 .....28EZBD 390 .....26EZBD 391 .....27EZBD 392 .....28EZBD 420 .....26EZBD 421 .....28EZBD 422 .....28EZX 1 ...........34EZX 2 ...........34EZX 3 ...........34RC 3.............42RC 15...........40RC 20...........40RC 30...........40ZC-B1M ........36

catalogue Dervasil 28/05/08 10:21 Page 8

Page 11: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

8

A.C medium voltagenetwork protection

A.C

med

ium

vol

tage

net

wor

k pr

otec

tion

10kA

arre

ster

10 kA arrester - Class 1AZB seriesAZBD series

10 kA arrester - Class 2AZC series

General characteristics AZB, AZBD, AZC 10

Standard arrester AZB-0, AZBD-0, AZC-0 16

Arrester with 150 A fault indicator AZB--1, AZBD--1, AZC--1 17

Arrester with 15 A fault indicator AZP--, AZBDP-, AZCP--, 18

Arrester with disconnector AZB--2, AZBD--2, AZC--2 19

Arrester for power follow current breaking AZICS--, AZCICS-- 20

General references indexReference PageReference PageReference PageReference Page

AZ 5050.......34AZB 030.......16AZB 031.......17AZB 032.......19AZB 060.......16AZB 061.......17AZB 062.......19AZB 090.......16AZB 091.......17AZB 092.......19AZB 120.......16AZB 121.......17AZB 122.......19AZB 150.......16AZB 151.......17AZB 152.......19AZB 180.......16AZB 181.......17AZB 182.......19AZB 210.......16AZB 211.......17AZB 212.......19AZB 240.......16AZB 241.......17AZB 242.......19AZB 270.......16AZB 271.......17AZB 272.......19AZB 300.......16AZB 301.......17AZB 302.......19AZB 330.......16AZB 331.......17AZB 332.......19AZB 360.......16AZB 361.......17AZB 362.......19AZB 390.......16AZB 391.......17AZB 392.......19AZBD 030.....16AZBD 031.....17AZBD 032.....19AZBD 060.....16AZBD 061.....17AZBD 062.....19AZBD 090.....16AZBD 091.....17AZBD 092.....19AZBD 120.....16AZBD 121.....17AZBD 122.....19AZBD 150.....16AZBD 151.....17AZBD 152.....19AZBD 180.....16AZBD 181.....17AZBD 182.....19AZBD 210.....16AZBD 211.....17AZBD 212.....19

AZBD 240.....16AZBD 241.....17AZBD 242.....19AZBD 270.....16AZBD 271.....17AZBD 272.....19AZBD 300.....16AZBD 301.....17AZBD 302.....19AZBD 330.....16AZBD 331.....17AZBD 332.....19AZBD 360.....16AZBD 361.....17AZBD 362.....19AZBD 390.....16AZBD 391.....17AZBD 392.....19AZBD 420.....16AZBD 422.....19AZBDP 03 .....18AZBDP 06 .....18AZBDP 09 .....18AZBDP 12 .....18AZBDP 15 .....18AZBDP 18 .....18AZBDP 21 .....18AZBDP 24 .....18AZBDP 27 .....18AZBDP 30 .....18AZBDP 33 .....18AZBDP 36 .....18AZBDP 39 .....18AZBDP 42 .....18AZC 030 ......16AZC 031 ......17AZC 032 ......19AZC 060 ......16AZC 061 ......17AZC 062 ......19AZC 090 ......16AZC 091 ......17AZC 092 ......19AZC 120 ......16AZC 121 ......17AZC 122 ......19AZC 150 ......16AZC 151 ......17AZC 152 ......19AZC 180 ......16AZC 181 ......17AZC 182 ......19AZC 210 ......16AZC 211 ......17AZC 212 ......19AZC 240 ......16AZC 241 ......17AZC 242 ......19AZC 270 ......16AZC 271 ......17AZC 272 ......19

AZC 300 ......16AZC 301 ......17AZC 302 ......19AZC 330 ......16AZC 331 ......17AZC 332 ......19AZC 360 ......16AZC 361 ......17AZC 362 ......19AZC 390 ......16AZC 391 ......17AZC 392 ......19AZCICS 090....20AZCICS091...20AZCICS 120....20AZCICS 121....20AZCICS 150....20AZCICS 151....20AZCICS 180....20AZCICS 181....20AZCICS 200....20AZCICS 201....20AZCICS 240....20AZCICS 241....20AZCICS 300....20AZCICS 301....20AZCICS 360....20AZCICS 361....20AZCP 03.......18AZCP 06.......18AZCP 09.......18AZCP 12.......18AZCP 15.......18AZCP 18.......18AZCP 21.......18AZCP 24.......18AZCP 27.......18AZCP 30.......18AZCP 33.......18AZCP 36.......18AZCP 39.......18AZE 010 T ....30AZE 012 T ....30AZE 020 T ....30AZE 030 T ....30AZE 040 T ....30AZE 050 T ....30AZE 060 T ....30AZE 080 T ....30AZICS 090....20AZICS 091....20AZICS 120....20AZICS 121....20AZICS 150....20AZICS 151....20AZICS 180....20AZICS 181....20AZICS 200....20AZICS 201....20AZICS 240....20AZICS 241....20

AZICS 300....20AZICS 301....20AZICS 360....20AZICS 361....20AZNEMA ......35AZP 03 .........18AZP 06 .........18AZP 09 .........18AZP 12 .........18AZP 15 .........18AZP 18 .........18AZP 21 .........18AZP 24 .........18AZP 27 .........18AZP 30 .........18AZP 33 .........18AZP 36 .........18AZP 39 .........18AZPTR ...........34CAP M10......37DSIL 3 ...........42DSIL 15 .........40DSIL 20 .........40DSIL 30 .........40EZB 030 .......26EZB 031 .......27EZB 032 .......28EZB 060 .......26EZB 061 .......27EZB 062 .......28EZB 090 .......26EZB 091 .......27EZB 092 .......28EZB 120 .......26EZB 121 .......27EZB 122 .......28EZB 150 .......26EZB 151 .......27EZB 152 .......28EZB 180 .......26EZB 181 .......27EZB 182 .......28EZB 210 .......26EZB 211 .......27EZB 212 .......28EZB 240 .......26EZB 241 .......27EZB 242 .......28EZB 270 .......26EZB 271 .......27EZB 272 .......28EZB 300 .......26EZB 301 .......27EZB 302 .......28EZB 330 .......26EZB 331 .......27EZB 332 .......28EZB 360 .......26EZB 361 .......27EZB 362 .......28EZB 390 .......26

Reference Page

EZB 391 .......27EZB 392 .......28EZBD 030 .....26EZBD 031 .....27EZBD 032 .....28EZBD 060 .....26EZBD 061 .....27EZBD 062 .....28EZBD 090 .....26EZBD 091 .....27EZBD 092 .....28EZBD 120 .....26EZBD 121 .....27EZBD 122 .....28EZBD 150 .....26EZBD 151 .....27EZBD 152 .....28EZBD 180 .....26EZBD 181 .....27EZBD 182 .....28EZBD 210 .....26EZBD 211 .....27EZBD 212 .....28EZBD 240 .....26EZBD 241 .....27EZBD 242 .....28EZBD 270 .....26EZBD 271 .....27EZBD 272 .....28EZBD 300 .....26EZBD 301 .....27EZBD 302 .....28EZBD 330 .....26EZBD 331 .....27EZBD 332 .....28EZBD 360 .....26EZBD 361 .....27EZBD 362 .....28EZBD 390 .....26EZBD 391 .....27EZBD 392 .....28EZBD 420 .....26EZBD 421 .....28EZBD 422 .....28EZX 1 ...........34EZX 2 ...........34EZX 3 ...........34RC 3.............42RC 15...........40RC 20...........40RC 30...........40ZC-B1M ........36

catalogue Dervasil 28/05/08 10:21 Page 8

Page 12: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

10 11

A.C medium voltage network protection10 kA arrester - Class 1

AZB series General characteristics

Tested in accordance with I.E.C 60099-4 standard.

Zinc oxide varistors.

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

30

A B

Physical characteristics

Arrester

type

Leakage

distance (mm)

Height

H (mm)

Unit weight

(kg) Lightningimpulse

1.2/50 µs

50 Hz 60s

Wet

A min

(mm)

B min

(mm)

Insulation withstandof housing (kV)

Mounting clearances

AZB_ 03_ 400 185 1.2 100 37 110 130AZB_ 06_ 400 185 1.4 100 37 110 130AZB_ 09_ 400 185 1.5 100 37 140 160AZB_ 12_ 400 185 1.6 100 37 140 160AZB_ 15_ 555 231 1.8 120 46 180 200AZB_ 18_ 555 231 2.1 120 46 180 200AZB_ 21_ 710 254 2.3 130 51 240 260AZB_ 24_ 710 254 2.4 130 51 240 260AZB_ 27_ 760 276 2.7 150 56 270 290AZB_ 30_ 1 000 345 3.0 190 70 320 340AZB_ 33_ 1 000 345 3.1 190 70 340 360AZB_ 36_ 1 000 345 3.2 190 70 340 360AZB_ 39_ 1 000 345 3.2 190 70 340 360

A.C medium voltage network protection10 kA arrester - Class 1

Nominal discharge current: 10 kA 8/20 µs impulseLine discharge class: 1High current withstand: 2 x 100 kA 4/10µs impulsesLong duration current withstand: 18 x 250 A 2000 µs impulses

Energy absorption capacity 1.8 kJoule/kV of Uc for one x 2000 µs impulse4.6 kJoule/kV of Uc for one 4/10 µs impulse

Rated frequency 48 to 62 HzService temperature - 40°C to + 40°C (+ 60°C short duration)Specified continuous load (SCL) 100 N.mSpecified short term load (SSL) 250 N.mMax tension strength 1 kNMax torsion strength 30 N.mPollution area I.E.C 60815 3Short circuit rating after over voltage failure as Appendix 0 of I.E.C 60099-4 20000 A for 0.2s / 600 A for 1s

AZB line arrester does not have spark gaps in series. The zinc oxidevaristors are designed to withstand the continuous phase to groundvoltage of network. They are capable of bearing increasedoperational voltages over a long period. The temporary over voltagecharacteristics give the duration T and corresponding TOV withrespect to continuous voltage Uc. The curve E = 0 is valid for arresters without energy preloading. Theother curve is valid for arresters, which are already absorbedimpulses corresponding to their maximum energy absorptioncapability.

AZB_ 03_ 3 2.55 11.1 8.7 9.3 10.1 11.3 13.6 7.2 7.8AZB_ 06_ 6 5.1 22.6 17.4 18.9 20.5 23.0 26.7 14.7 15.9AZB_ 09_ 9 8.4 33.6 25.9 28.1 30.5 34.2 39.7 23.8 25.8AZB_ 12_ 12 10.2 40.9 31.6 34.2 37.2 41.7 48.4 26.4 28.6AZB_ 15_ 15 12.7 51.3 39.6 42.9 46.6 52.2 60.6 33.1 35.9AZB_ 18_ 18 15.3 64.6 49.9 54.0 58.7 65.7 76.3 42.7 46.3AZB_ 21_ 21 17.5 69.3 53.6 58.0 63.0 70.6 81.9 47.2 51.2AZB_ 24_ 24 19.5 73.2 56.5 61.2 66.5 74.5 86.5 47.2 51.2AZB_ 27_ 27 22.0 84.3 65.1 70.5 76.6 85.8 99.6 54.4 59.0AZB_ 30_ 30 24.4 95.4 73.7 79.8 86.7 97.1 112.7 61.6 66.8AZB_ 33_ 33 27.0 100.9 78.0 84.4 91.8 102.8 119.3 65.1 70.6AZB_ 36_ 36 29.0 111.5 86.1 93.2 101.4 113.5 131.8 72.0 78.0 AZB_ 39_ 39 32.0 111.5 86.1 93.2 101.4 113.5 131.8 72.0 78.0

k = TOV / Uc

TOV duration

Electrical and mechanical characteristics

Temporary over voltage capability

Protective characteristics

Arrestertype

UrRated

voltage(kVrms)

UcContinuousoperatingvoltage(kVrms)

Residualvoltage

wave 1/4 µsat 10 kA

(kV)2.5 kA 5 kA

10 kA Nominaldischarge

current20 kA 40 kA

Residualvoltage

wave 30/80 µs125 A 500 A

(kV)

Residual voltage wave 8/20 µs (kV)

H

120

M10

catalogue Dervasil 28/05/08 10:21 Page 10

Page 13: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

10 11

A.C medium voltage network protection10 kA arrester - Class 1

AZB series General characteristics

Tested in accordance with I.E.C 60099-4 standard.

Zinc oxide varistors.

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

30

A B

Physical characteristics

Arrester

type

Leakage

distance (mm)

Height

H (mm)

Unit weight

(kg) Lightningimpulse

1.2/50 µs

50 Hz 60s

Wet

A min

(mm)

B min

(mm)

Insulation withstandof housing (kV)

Mounting clearances

AZB_ 03_ 400 185 1.2 100 37 110 130AZB_ 06_ 400 185 1.4 100 37 110 130AZB_ 09_ 400 185 1.5 100 37 140 160AZB_ 12_ 400 185 1.6 100 37 140 160AZB_ 15_ 555 231 1.8 120 46 180 200AZB_ 18_ 555 231 2.1 120 46 180 200AZB_ 21_ 710 254 2.3 130 51 240 260AZB_ 24_ 710 254 2.4 130 51 240 260AZB_ 27_ 760 276 2.7 150 56 270 290AZB_ 30_ 1 000 345 3.0 190 70 320 340AZB_ 33_ 1 000 345 3.1 190 70 340 360AZB_ 36_ 1 000 345 3.2 190 70 340 360AZB_ 39_ 1 000 345 3.2 190 70 340 360

A.C medium voltage network protection10 kA arrester - Class 1

Nominal discharge current: 10 kA 8/20 µs impulseLine discharge class: 1High current withstand: 2 x 100 kA 4/10µs impulsesLong duration current withstand: 18 x 250 A 2000 µs impulses

Energy absorption capacity 1.8 kJoule/kV of Uc for one x 2000 µs impulse4.6 kJoule/kV of Uc for one 4/10 µs impulse

Rated frequency 48 to 62 HzService temperature - 40°C to + 40°C (+ 60°C short duration)Specified continuous load (SCL) 100 N.mSpecified short term load (SSL) 250 N.mMax tension strength 1 kNMax torsion strength 30 N.mPollution area I.E.C 60815 3Short circuit rating after over voltage failure as Appendix 0 of I.E.C 60099-4 20000 A for 0.2s / 600 A for 1s

AZB line arrester does not have spark gaps in series. The zinc oxidevaristors are designed to withstand the continuous phase to groundvoltage of network. They are capable of bearing increasedoperational voltages over a long period. The temporary over voltagecharacteristics give the duration T and corresponding TOV withrespect to continuous voltage Uc. The curve E = 0 is valid for arresters without energy preloading. Theother curve is valid for arresters, which are already absorbedimpulses corresponding to their maximum energy absorptioncapability.

AZB_ 03_ 3 2.55 11.1 8.7 9.3 10.1 11.3 13.6 7.2 7.8AZB_ 06_ 6 5.1 22.6 17.4 18.9 20.5 23.0 26.7 14.7 15.9AZB_ 09_ 9 8.4 33.6 25.9 28.1 30.5 34.2 39.7 23.8 25.8AZB_ 12_ 12 10.2 40.9 31.6 34.2 37.2 41.7 48.4 26.4 28.6AZB_ 15_ 15 12.7 51.3 39.6 42.9 46.6 52.2 60.6 33.1 35.9AZB_ 18_ 18 15.3 64.6 49.9 54.0 58.7 65.7 76.3 42.7 46.3AZB_ 21_ 21 17.5 69.3 53.6 58.0 63.0 70.6 81.9 47.2 51.2AZB_ 24_ 24 19.5 73.2 56.5 61.2 66.5 74.5 86.5 47.2 51.2AZB_ 27_ 27 22.0 84.3 65.1 70.5 76.6 85.8 99.6 54.4 59.0AZB_ 30_ 30 24.4 95.4 73.7 79.8 86.7 97.1 112.7 61.6 66.8AZB_ 33_ 33 27.0 100.9 78.0 84.4 91.8 102.8 119.3 65.1 70.6AZB_ 36_ 36 29.0 111.5 86.1 93.2 101.4 113.5 131.8 72.0 78.0 AZB_ 39_ 39 32.0 111.5 86.1 93.2 101.4 113.5 131.8 72.0 78.0

k = TOV / Uc

TOV duration

Electrical and mechanical characteristics

Temporary over voltage capability

Protective characteristics

Arrestertype

UrRated

voltage(kVrms)

UcContinuousoperatingvoltage(kVrms)

Residualvoltage

wave 1/4 µsat 10 kA

(kV)2.5 kA 5 kA

10 kA Nominaldischarge

current20 kA 40 kA

Residualvoltage

wave 30/80 µs125 A 500 A

(kV)

Residual voltage wave 8/20 µs (kV)

H

120

M10

catalogue Dervasil 28/05/08 10:21 Page 10

Page 14: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

Unit weight

(kg)

12 13

A.C medium voltage network protection10 kA arrester - Class 1

A.C medium voltage network protection10 kA arrester - Class 1

Nominal discharge current: 10 kA 8/20 µs impulseLine discharge class: 1High current withstand: 2 x 100 kA 4/10µs impulsesLong duration current withstand: 18 x 250 A 2000 µs impulses

Energy absorption capacity 1.8 kJoule/kV of Uc for one x 2000 µs impulse4.6 kJoule/kV of Uc for one 4/10 µs impulse

Rated frequency 48 to 62 HzService temperature - 40°C to + 40°C (+ 60°C short duration)Specified continuous load (SCL) 200 N.mSpecified short term load (SSL) 350 N.mMax tension strength 15 kNMax torsion strength 70 N.mPollution area I.E.C 60815 3Short circuit rating after over voltage failure as Appendix 0 of I.E.C 60099-4 20000 A for 0.2s / 600 A for 1s

AZBD line arrester does not have spark gaps in series. The zincoxide varistors are designed to withstand the continuous phase toground voltage of network. They are capable of bearing increasedoperational voltages over a long period. The temporary over voltagecharacteristics give the duration T and corresponding TOV withrespect to continuous voltage Uc. The curve E = 0 is valid for arresters without energy preloading. Theother curve is valid for arresters, which are already absorbedimpulses corresponding to their maximum energy absorptioncapability.

AZBD_ 03_ 3 2.55 11.1 8.7 9.3 10.1 11.3 13.6 7.2 7.8AZBD_ 06_ 6 5.1 22.8 17.6 19.0 20.7 23.2 26.9 14.7 15.9AZBD_ 09_ 9 8.4 36.9 28.5 30.8 33.5 37.5 43.6 23.8 25.8AZBD_ 12_ 12 10.2 40.9 31.6 34.2 37.2 41.7 48.4 26.4 28.6AZBD_ 15_ 15 12.7 48.0 37.1 40.1 43.6 48.8 56.7 31.0 33.6AZBD_ 18_ 18 15.3 64.6 49.9 54.0 58.7 65.7 76.3 42.7 46.3AZBD_ 21_ 21 17.5 73.2 56.5 61.2 66.5 74.5 86.5 47.2 51.2AZBD_ 24_ 24 19.5 73.2 56.5 61.2 66.5 74.5 86.5 47.2 51.2AZBD_ 27_ 27 22.0 84.3 65.1 70.5 76.6 85.8 99.6 54.4 59.0AZBD_ 30_ 30 24.4 102.4 79.1 85.7 93.1 104.3 121.0 66.1 71.7AZBD_ 33_ 33 27.0 102.4 79.1 85.7 93.1 104.3 121.0 66.1 71.7 AZBD_ 36_ 36 29.0 109.5 84.6 91.5 99.5 111.4 129.4 70.6 76.6 AZBD_ 39_ 39 32.0 109.5 84.6 91.5 99.5 111.4 129.4 70.6 76.6 AZBD_ 42_ 42 35.0 127.6 98.6 106.7 116.0 129.9 150.8 82.4 89.3

AZBD series General characteristics Electrical and mechanical characteristics

Temporary over voltage capability

Protective characteristics

Tested in accordance with I.E.C 60099-4 standard.

Zinc oxide varistors.

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

High mechanical resistance.

Can be used as cable support.

H

A B

Arrestertype

UrRated

voltage(kVrms)

UcContinuousoperatingvoltage(kVrms)

Residualvoltage

wave 1/4 µsat 10 kA

(kV)2.5 kA 5 kA

10 kA Nominaldischarge

current20 kA 40 kA

Residualvoltage

wave 30/80 µs125 A 500 A

(kV)

Residual voltage wave 8/20 µs (kV)

Physical characteristics

Arrester

type

Leakage

distance (mm)

Height

H (mm) Lightningimpulse

1.2/50 µs

50 Hz 60s

Wet

A min

(mm)

B min

(mm)

Insulation withstandof housing (kV)

Mounting clearances

110

30

M10

k = TOV / Uc

TOV duration

AZBD_ 03_ 230 140 1.2 100 37 110 130AZBD_ 06_ 230 140 1.4 100 37 110 130AZBD_ 09_ 315 170 1.5 100 37 140 160AZBD_ 12_ 375 180 1.6 100 37 140 160AZBD_ 15_ 500 195 1.8 120 46 180 200AZBD_ 18_ 540 230 2.1 120 46 180 200AZBD_ 21_ 660 245 2.3 130 51 240 260AZBD_ 24_ 660 245 2.4 130 51 240 260AZBD_ 27_ 750 270 2.7 150 56 270 290AZBD_ 30_ 830 305 3.0 190 70 320 340AZBD_ 33_ 960 320 3.1 190 70 340 360AZBD_ 36_ 960 320 3.2 190 70 340 360AZBD_ 39_ 1 050 360 3.2 190 70 340 360AZBD_ 42_ 1 050 360 3.2 190 70 360 380

catalogue Dervasil 28/05/08 10:21 Page 12

Page 15: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

Unit weight

(kg)

12 13

A.C medium voltage network protection10 kA arrester - Class 1

A.C medium voltage network protection10 kA arrester - Class 1

Nominal discharge current: 10 kA 8/20 µs impulseLine discharge class: 1High current withstand: 2 x 100 kA 4/10µs impulsesLong duration current withstand: 18 x 250 A 2000 µs impulses

Energy absorption capacity 1.8 kJoule/kV of Uc for one x 2000 µs impulse4.6 kJoule/kV of Uc for one 4/10 µs impulse

Rated frequency 48 to 62 HzService temperature - 40°C to + 40°C (+ 60°C short duration)Specified continuous load (SCL) 200 N.mSpecified short term load (SSL) 350 N.mMax tension strength 15 kNMax torsion strength 70 N.mPollution area I.E.C 60815 3Short circuit rating after over voltage failure as Appendix 0 of I.E.C 60099-4 20000 A for 0.2s / 600 A for 1s

AZBD line arrester does not have spark gaps in series. The zincoxide varistors are designed to withstand the continuous phase toground voltage of network. They are capable of bearing increasedoperational voltages over a long period. The temporary over voltagecharacteristics give the duration T and corresponding TOV withrespect to continuous voltage Uc. The curve E = 0 is valid for arresters without energy preloading. Theother curve is valid for arresters, which are already absorbedimpulses corresponding to their maximum energy absorptioncapability.

AZBD_ 03_ 3 2.55 11.1 8.7 9.3 10.1 11.3 13.6 7.2 7.8AZBD_ 06_ 6 5.1 22.8 17.6 19.0 20.7 23.2 26.9 14.7 15.9AZBD_ 09_ 9 8.4 36.9 28.5 30.8 33.5 37.5 43.6 23.8 25.8AZBD_ 12_ 12 10.2 40.9 31.6 34.2 37.2 41.7 48.4 26.4 28.6AZBD_ 15_ 15 12.7 48.0 37.1 40.1 43.6 48.8 56.7 31.0 33.6AZBD_ 18_ 18 15.3 64.6 49.9 54.0 58.7 65.7 76.3 42.7 46.3AZBD_ 21_ 21 17.5 73.2 56.5 61.2 66.5 74.5 86.5 47.2 51.2AZBD_ 24_ 24 19.5 73.2 56.5 61.2 66.5 74.5 86.5 47.2 51.2AZBD_ 27_ 27 22.0 84.3 65.1 70.5 76.6 85.8 99.6 54.4 59.0AZBD_ 30_ 30 24.4 102.4 79.1 85.7 93.1 104.3 121.0 66.1 71.7AZBD_ 33_ 33 27.0 102.4 79.1 85.7 93.1 104.3 121.0 66.1 71.7 AZBD_ 36_ 36 29.0 109.5 84.6 91.5 99.5 111.4 129.4 70.6 76.6 AZBD_ 39_ 39 32.0 109.5 84.6 91.5 99.5 111.4 129.4 70.6 76.6 AZBD_ 42_ 42 35.0 127.6 98.6 106.7 116.0 129.9 150.8 82.4 89.3

AZBD series General characteristics Electrical and mechanical characteristics

Temporary over voltage capability

Protective characteristics

Tested in accordance with I.E.C 60099-4 standard.

Zinc oxide varistors.

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

High mechanical resistance.

Can be used as cable support.

H

A B

Arrestertype

UrRated

voltage(kVrms)

UcContinuousoperatingvoltage(kVrms)

Residualvoltage

wave 1/4 µsat 10 kA

(kV)2.5 kA 5 kA

10 kA Nominaldischarge

current20 kA 40 kA

Residualvoltage

wave 30/80 µs125 A 500 A

(kV)

Residual voltage wave 8/20 µs (kV)

Physical characteristics

Arrester

type

Leakage

distance (mm)

Height

H (mm) Lightningimpulse

1.2/50 µs

50 Hz 60s

Wet

A min

(mm)

B min

(mm)

Insulation withstandof housing (kV)

Mounting clearances

110

30

M10

k = TOV / Uc

TOV duration

AZBD_ 03_ 230 140 1.2 100 37 110 130AZBD_ 06_ 230 140 1.4 100 37 110 130AZBD_ 09_ 315 170 1.5 100 37 140 160AZBD_ 12_ 375 180 1.6 100 37 140 160AZBD_ 15_ 500 195 1.8 120 46 180 200AZBD_ 18_ 540 230 2.1 120 46 180 200AZBD_ 21_ 660 245 2.3 130 51 240 260AZBD_ 24_ 660 245 2.4 130 51 240 260AZBD_ 27_ 750 270 2.7 150 56 270 290AZBD_ 30_ 830 305 3.0 190 70 320 340AZBD_ 33_ 960 320 3.1 190 70 340 360AZBD_ 36_ 960 320 3.2 190 70 340 360AZBD_ 39_ 1 050 360 3.2 190 70 340 360AZBD_ 42_ 1 050 360 3.2 190 70 360 380

catalogue Dervasil 28/05/08 10:21 Page 12

Page 16: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

14 15

A.C medium voltage network protection10 kA arrester - Class 2

A.C medium voltage network protection10 kA arrester - Class 2

Nominal discharge current: 10 kA 8/20 µs impulseLine discharge class: 2High current withstand: 2 x 100 kA 4/10µs impulsesLong duration current withstand: 18 x 500 A 2000 µs impulses

Energy absorption capacity 5.5 kJoule/kV of Uc for 2 x 2000 µs impulses4.6 kJoule/kV of Uc for one 4/10 µs impulse

Rated frequency 48 to 62 HzService temperature - 40°C to + 40°C (+ 60°C short duration)Specified continuous load (SCL) 100 N.mSpecified short term load (SSL) 250 N.mMax tension strength 1 kNMax torsion strength 30 N.mPollution area I.E.C 60815 3Short circuit rating after over voltage failure as Appendix 0 of I.E.C 60099-4 20000 A for 0.2s / 600 A for 1s

0

0,1

0,2

0,3

0,4

0,5

0,6

0,7

0,8

0,9

1

1,1

1,2

1,3

1,4

1,5

1,6

0,1 1 10 100 1000 10000 100000

Preloaded Energy = max Capability

Preloaded Energy = 0

AZC line arrester does not have spark gapsin series. The zinc oxide varistors aredesigned to withstand the continuous phaseto ground voltage of network. They arecapable of bearing increased operationalvoltages over a long period. The temporaryover voltage characteristics give the durationT and corresponding TOV with respect tocontinuous voltage Uc. The curve E = 0 is valid for arresters withoutenergy preloading. The other curve is validfor arresters, which are already absorbedimpulses corresponding to their maximumenergy absorption capability.

AZC_ 03_ 3 2.55 11.7 9.3 9.9 10.6 11.9 13.8 7.8 8.5AZC_ 06_ 6 5.1 18.7 14.9 16.0 17.0 19.1 22.1 12.6 13.6AZC_ 09_ 9 8.4 29.8 23.8 25.4 27.1 30.4 35.2 20.0 21.7AZC_ 12_ 12 10.2 36.9 29.4 31.4 33.5 37.6 43.6 24.7 26.8AZC_ 15_ 15 12.7 48.0 38.3 40.9 43.6 49.0 56.7 32.2 34.8AZC_ 18_ 18 15.3 55.0 43.9 46.9 50.0 56.2 65.0 36.9 40.0AZC_ 21_ 21 17.5 66.1 52.7 56.4 60.1 67.5 78.1 44.4 48.0AZC_ 24_ 24 19.5 73.2 58.3 62.4 66.5 74.7 86.5 49.1 53.1AZC_ 27_ 27 22.0 84.3 67.2 71.9 76.6 86.0 99.6 56.6 61.2AZC_ 30_ 30 24.4 91.3 72.8 77.9 83.0 93.2 107.9 61.3 66.3AZC_ 33_ 33 27.0 102.4 81.7 87.4 93.1 104.6 121.0 68.7 74.4AZC_ 36_ 36 29.0 109.5 87.3 93.4 99.5 111.7 129.4 73.5 79.5 AZC_ 39_ 39 32.0 120.6 96.2 102.8 109.6 123.1 142.5 80.9 87.6

AZC series General characteristics Electrical and mechanical characterisitcs

Temporary over voltage capability

Protective characteristics

Tested in accordance with I.E.C 60099-4 standard.

Zinc oxide varistors.

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

Arrestertype

UrRated

voltage(kVrms)

UcContinuousoperatingvoltage(kVrms)

Residualvoltage

wave 1/4 µsat 10 kA

(kV)2.5 kA 5 kA

10 kA Nominaldischarge

current20 kA 40 kA

Residualvoltage

wave 30/80 µs125 A 500 A

(kV)

Residual voltage wave 8/20 µs (kV)

Physical characteristics

Arrester

type

Leakage

distance (mm)

Height

H (mm)

Unit weight

(kg) Lightningimpulse

1.2/50 µs

50 Hz 60s

Wet

A min

(mm)

B min

(mm)

Insulation withstandof housing (kV)

Mounting clearances

AZC_ 03_ 400 185 1.2 100 37 110 130AZC_ 06_ 400 185 1.4 100 37 110 130AZC_ 09_ 400 185 1.5 100 37 140 160AZC_ 12_ 400 185 1.6 100 37 140 160AZC_ 15_ 555 231 1.8 120 46 180 200AZC_ 18_ 555 231 2.1 120 46 180 200AZC_ 21_ 710 254 2.3 130 51 240 260AZC_ 24_ 710 254 2.4 130 51 240 260AZC_ 27_ 760 276 2.7 150 56 270 290AZC_ 30_ 1 000 345 3.0 190 70 320 340AZC_ 33_ 1 000 345 3.1 190 70 340 360AZC_ 36_ 1 000 345 3.2 190 70 340 360AZC_ 39_ 1 000 345 3.2 190 70 340 360

A B

H

120

30

M10

k = TOV / Uc

TOV duration

catalogue Dervasil 28/05/08 10:21 Page 14

Page 17: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

14 15

A.C medium voltage network protection10 kA arrester - Class 2

A.C medium voltage network protection10 kA arrester - Class 2

Nominal discharge current: 10 kA 8/20 µs impulseLine discharge class: 2High current withstand: 2 x 100 kA 4/10µs impulsesLong duration current withstand: 18 x 500 A 2000 µs impulses

Energy absorption capacity 5.5 kJoule/kV of Uc for 2 x 2000 µs impulses4.6 kJoule/kV of Uc for one 4/10 µs impulse

Rated frequency 48 to 62 HzService temperature - 40°C to + 40°C (+ 60°C short duration)Specified continuous load (SCL) 100 N.mSpecified short term load (SSL) 250 N.mMax tension strength 1 kNMax torsion strength 30 N.mPollution area I.E.C 60815 3Short circuit rating after over voltage failure as Appendix 0 of I.E.C 60099-4 20000 A for 0.2s / 600 A for 1s

0

0,1

0,2

0,3

0,4

0,5

0,6

0,7

0,8

0,9

1

1,1

1,2

1,3

1,4

1,5

1,6

0,1 1 10 100 1000 10000 100000

Preloaded Energy = max Capability

Preloaded Energy = 0

AZC line arrester does not have spark gapsin series. The zinc oxide varistors aredesigned to withstand the continuous phaseto ground voltage of network. They arecapable of bearing increased operationalvoltages over a long period. The temporaryover voltage characteristics give the durationT and corresponding TOV with respect tocontinuous voltage Uc. The curve E = 0 is valid for arresters withoutenergy preloading. The other curve is validfor arresters, which are already absorbedimpulses corresponding to their maximumenergy absorption capability.

AZC_ 03_ 3 2.55 11.7 9.3 9.9 10.6 11.9 13.8 7.8 8.5AZC_ 06_ 6 5.1 18.7 14.9 16.0 17.0 19.1 22.1 12.6 13.6AZC_ 09_ 9 8.4 29.8 23.8 25.4 27.1 30.4 35.2 20.0 21.7AZC_ 12_ 12 10.2 36.9 29.4 31.4 33.5 37.6 43.6 24.7 26.8AZC_ 15_ 15 12.7 48.0 38.3 40.9 43.6 49.0 56.7 32.2 34.8AZC_ 18_ 18 15.3 55.0 43.9 46.9 50.0 56.2 65.0 36.9 40.0AZC_ 21_ 21 17.5 66.1 52.7 56.4 60.1 67.5 78.1 44.4 48.0AZC_ 24_ 24 19.5 73.2 58.3 62.4 66.5 74.7 86.5 49.1 53.1AZC_ 27_ 27 22.0 84.3 67.2 71.9 76.6 86.0 99.6 56.6 61.2AZC_ 30_ 30 24.4 91.3 72.8 77.9 83.0 93.2 107.9 61.3 66.3AZC_ 33_ 33 27.0 102.4 81.7 87.4 93.1 104.6 121.0 68.7 74.4AZC_ 36_ 36 29.0 109.5 87.3 93.4 99.5 111.7 129.4 73.5 79.5 AZC_ 39_ 39 32.0 120.6 96.2 102.8 109.6 123.1 142.5 80.9 87.6

AZC series General characteristics Electrical and mechanical characterisitcs

Temporary over voltage capability

Protective characteristics

Tested in accordance with I.E.C 60099-4 standard.

Zinc oxide varistors.

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

Arrestertype

UrRated

voltage(kVrms)

UcContinuousoperatingvoltage(kVrms)

Residualvoltage

wave 1/4 µsat 10 kA

(kV)2.5 kA 5 kA

10 kA Nominaldischarge

current20 kA 40 kA

Residualvoltage

wave 30/80 µs125 A 500 A

(kV)

Residual voltage wave 8/20 µs (kV)

Physical characteristics

Arrester

type

Leakage

distance (mm)

Height

H (mm)

Unit weight

(kg) Lightningimpulse

1.2/50 µs

50 Hz 60s

Wet

A min

(mm)

B min

(mm)

Insulation withstandof housing (kV)

Mounting clearances

AZC_ 03_ 400 185 1.2 100 37 110 130AZC_ 06_ 400 185 1.4 100 37 110 130AZC_ 09_ 400 185 1.5 100 37 140 160AZC_ 12_ 400 185 1.6 100 37 140 160AZC_ 15_ 555 231 1.8 120 46 180 200AZC_ 18_ 555 231 2.1 120 46 180 200AZC_ 21_ 710 254 2.3 130 51 240 260AZC_ 24_ 710 254 2.4 130 51 240 260AZC_ 27_ 760 276 2.7 150 56 270 290AZC_ 30_ 1 000 345 3.0 190 70 320 340AZC_ 33_ 1 000 345 3.1 190 70 340 360AZC_ 36_ 1 000 345 3.2 190 70 340 360AZC_ 39_ 1 000 345 3.2 190 70 340 360

A B

H

120

30

M10

k = TOV / Uc

TOV duration

catalogue Dervasil 28/05/08 10:21 Page 14

Page 18: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

Ur (kVrms) 3 6 9 12 15 18 21 24 27 30 33 36 39 42

Arrester reference AZBD 031 AZBD 061 AZBD 091 AZBD 121 AZBD 151 AZBD 181 AZBD 211 AZBD 241 AZBD 271 AZBD 301 AZBD 331 AZBD 361 AZBD 391 AZBD 421AZBD--1

Ur (kVrms)

Arrester referenceAZB--0

Arrester referenceAZC--0

3 6 9 12 15 18 21 24 27 30 33 36 39

AZB 030 AZB 060 AZB 090 AZB 120 AZB 150 AZB 180 AZB 210 AZB 240 AZB 270 AZB 300 AZB 330 AZB 360 AZB 390

AZC 030 AZC 060 AZC 090 AZC 120 AZC 150 AZC 180AZC 210 AZC 240 AZC 270 AZC 300 AZC 330 AZC 360 AZC 390

AZB--0 Class 1 and AZC--0 Class 2

1716

A.C medium voltage network protection10 kA arrester

A.C medium voltage network protection10 kA arrester

Can be connected to line and ground with aluminium or coppercables from 25 mm2 up to 148 mm2 (with or without terminal).

Mounting:Vertical type installation: EZX bracketHorizontal type installation: EQ 50-50

See mounting bracket section page 34.

Three-arrester packaging in cardboard box.

Ordering example: 300 AZB 030.

Fault indicator is a black silicone band which is clamped around thearrester housing and is visible from a distance of several hundredsmetres. When the arrester fails in short-circuit, the power arcgenerated inside arrester opens the housing and cuts the band,which falls on the ground. Absence of black band indicates arresterto be changed. It operates above 150 A current within 1 second.

Can be connected to line and ground with aluminium or coppercables from 25 mm2 up to 148 mm2 (with or without terminal).

Mounting:Vertical type installation: EZX bracketHorizontal type installation: EQ 50-50

See mounting bracket section page 34.

Three-arrester packaging in cardboard box.

Ordering example: 300 AZB 031.

Ur (kVrms) 3 6 9 12 15 18 21 24 27 30 33 36 39

Arrester reference AZB 031 AZB 061 AZB 091 AZB 121 AZB 151 AZB 181 AZB 211 AZB 241 AZB 271 AZB 301 AZB 331 AZB 361 AZB 391AZB--1

Arrester reference AZC 031 AZC 061 AZC 091 AZC 121 AZC 151AZC 181 AZC 211 AZC 241 AZC 271 AZC 301 AZC 331 AZC 361 AZC 391AZC--1

Indicator

AZBD--0 Class 1

AZB--1 Class 1 and AZC--1 Class 2

AZBD--1 Class 1

Standard arrester Arrester with 150 A fault indicator

Ur (kVrms) 3 6 9 12 15 18 21 24 27 30 33 36 39 42

Arrester reference AZBD 030 AZBD 060 AZBD 090 AZBD 120 AZBD 150 AZBD 180 AZBD 210 AZBD 240 AZBD 270 AZBD 300 AZBD 330 AZBD 360 AZBD 390 AZBD 420AZBD--0

catalogue Dervasil 28/05/08 10:21 Page 16

Page 19: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

Ur (kVrms) 3 6 9 12 15 18 21 24 27 30 33 36 39 42

Arrester reference AZBD 031 AZBD 061 AZBD 091 AZBD 121 AZBD 151 AZBD 181 AZBD 211 AZBD 241 AZBD 271 AZBD 301 AZBD 331 AZBD 361 AZBD 391 AZBD 421AZBD--1

Ur (kVrms)

Arrester referenceAZB--0

Arrester referenceAZC--0

3 6 9 12 15 18 21 24 27 30 33 36 39

AZB 030 AZB 060 AZB 090 AZB 120 AZB 150 AZB 180 AZB 210 AZB 240 AZB 270 AZB 300 AZB 330 AZB 360 AZB 390

AZC 030 AZC 060 AZC 090 AZC 120 AZC 150 AZC 180AZC 210 AZC 240 AZC 270 AZC 300 AZC 330 AZC 360 AZC 390

AZB--0 Class 1 and AZC--0 Class 2

1716

A.C medium voltage network protection10 kA arrester

A.C medium voltage network protection10 kA arrester

Can be connected to line and ground with aluminium or coppercables from 25 mm2 up to 148 mm2 (with or without terminal).

Mounting:Vertical type installation: EZX bracketHorizontal type installation: EQ 50-50

See mounting bracket section page 34.

Three-arrester packaging in cardboard box.

Ordering example: 300 AZB 030.

Fault indicator is a black silicone band which is clamped around thearrester housing and is visible from a distance of several hundredsmetres. When the arrester fails in short-circuit, the power arcgenerated inside arrester opens the housing and cuts the band,which falls on the ground. Absence of black band indicates arresterto be changed. It operates above 150 A current within 1 second.

Can be connected to line and ground with aluminium or coppercables from 25 mm2 up to 148 mm2 (with or without terminal).

Mounting:Vertical type installation: EZX bracketHorizontal type installation: EQ 50-50

See mounting bracket section page 34.

Three-arrester packaging in cardboard box.

Ordering example: 300 AZB 031.

Ur (kVrms) 3 6 9 12 15 18 21 24 27 30 33 36 39

Arrester reference AZB 031 AZB 061 AZB 091 AZB 121 AZB 151 AZB 181 AZB 211 AZB 241 AZB 271 AZB 301 AZB 331 AZB 361 AZB 391AZB--1

Arrester reference AZC 031 AZC 061 AZC 091 AZC 121 AZC 151AZC 181 AZC 211 AZC 241 AZC 271 AZC 301 AZC 331 AZC 361 AZC 391AZC--1

Indicator

AZBD--0 Class 1

AZB--1 Class 1 and AZC--1 Class 2

AZBD--1 Class 1

Standard arrester Arrester with 150 A fault indicator

Ur (kVrms) 3 6 9 12 15 18 21 24 27 30 33 36 39 42

Arrester reference AZBD 030 AZBD 060 AZBD 090 AZBD 120 AZBD 150 AZBD 180 AZBD 210 AZBD 240 AZBD 270 AZBD 300 AZBD 330 AZBD 360 AZBD 390 AZBD 420AZBD--0

catalogue Dervasil 28/05/08 10:21 Page 16

Page 20: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

1918

A.C medium voltage network protection10 kA arrester

A.C medium voltage network protection10 kA arrester

The fault indicator is screwed on the arrester. By setting off anelectro-thermal device, short-circuit current activates orange signalwhich is visible from several hundred metres. Operating sensitivityis shown in the Time-Current Curve.Can be connected to line and ground with aluminium or coppercables from 25 mm2 up to 148 mm2 (with or without terminal).

Mounting:For transformer protection:- Vertical position on transformer tank with AZPTR bracket (See mounting bracket section page 34)

- Vertical position on cross arm with AZPTR and AZNEMA brackets(See mounting bracket section page 34)

- Horizontal position with AZ 50-50 bracket (See mounting bracketsection page 34)

For cable connection protection:- Horizontal position with AZ 50-50 bracket (See mounting bracketsection page 34)

Three-arrester packaging in cardboard box.Ordering example: 300 AZP 03.

Disconnector is connected between arrester and ground. In case ofshort-circuit, It cuts off ground connection of arrester.Operating sensitivity is shown in the Time-Current Curve.

Can be connected to line with aluminium or copper cables from 25 mm2 up to 148 mm2 (with or without terminal) and to groundwith flexible cable.

Delivered with disconnector and insulating bracket.

Arrester can be supplied with ground copper cable (cross section: 16 mm2, length: 50 cm).

Mounting:Vertical type installation: insulating bracket alone or AZNEMAbracketsSee mounting bracket section page 34.

Three-arrester packaging in cardboard box.

Ordering example: 300 AZB 032.

Time (s)Time current curve

Current (A)

Fault indicator detail

"Flag opening" 150

25

Ø12Operating area

Operating area

Disconnector Bracket

Time current curve

Time (s)

Current (A)

Arrester with 15 A fault indicator Arrester with disconnector and insulating bracket

AZP-- Class 1, AZCP-- Class 2 and AZBDP-- Class 1 AZB--2 Class 1, AZC--2 Class 2 and AZBD--2 Class 1

Ur (kVrms) 3 6 9 12 15 18 21 24 27 30 33 36 39 42

Arrester reference AZB 032 AZB 062 AZB 092 AZB 122 AZB 152 AZB 182 AZB 212 AZB 242 AZB 272 AZB 302 AZB 332 AZB 362 AZB 392AZB--2

Arrester reference AZC 032 AZC 062 AZC 092 AZC 122 AZC 152 AZC 182 AZC 212 AZC 242 AZC 272 AZC 302 AZC 332 AZC 362 AZC 392AZC--2

Arrester reference AZBD 032 AZBD 062 AZBD 092 AZBD 122 AZBD 152 AZBD 182 AZBD 212 AZBD 242 AZBD 272 AZBD 302 AZBD 332 AZBD 362 AZBD 392 AZBD 422AZBD--2

Ur (kVrms) 3 6 9 12 15 18 21 24 27 30 33 36 39 42

Arrester reference AZP 03 AZP 06 AZP 09 AZP 12 AZP 15 AZP 18 AZP 21 AZP 24 AZP 27 AZP 30 AZP 33 AZP 36 AZP 39AZP--

Arrester reference AZCP 03 AZCP 06 AZCP 09 AZCP 12 AZCP 15 AZCP 18 AZCP 21 AZCP 24 AZCP 27 AZCP 30 AZCP 33 AZCP 36 AZCP 39AZCP

Arrester reference AZBDP 03 AZBDP 06 AZBDP 09 AZBDP 12 AZBDP 15 AZBDP 18 AZBDP 21 AZBDP 24 AZBDP 27 AZBDP 30 AZBDP 33 AZBDP 36 AZBDP 39 AZBDP 42AZBDP

M10

20

catalogue Dervasil 28/05/08 10:21 Page 18

Page 21: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

1918

A.C medium voltage network protection10 kA arrester

A.C medium voltage network protection10 kA arrester

The fault indicator is screwed on the arrester. By setting off anelectro-thermal device, short-circuit current activates orange signalwhich is visible from several hundred metres. Operating sensitivityis shown in the Time-Current Curve.Can be connected to line and ground with aluminium or coppercables from 25 mm2 up to 148 mm2 (with or without terminal).

Mounting:For transformer protection:- Vertical position on transformer tank with AZPTR bracket (See mounting bracket section page 34)

- Vertical position on cross arm with AZPTR and AZNEMA brackets(See mounting bracket section page 34)

- Horizontal position with AZ 50-50 bracket (See mounting bracketsection page 34)

For cable connection protection:- Horizontal position with AZ 50-50 bracket (See mounting bracketsection page 34)

Three-arrester packaging in cardboard box.Ordering example: 300 AZP 03.

Disconnector is connected between arrester and ground. In case ofshort-circuit, It cuts off ground connection of arrester.Operating sensitivity is shown in the Time-Current Curve.

Can be connected to line with aluminium or copper cables from 25 mm2 up to 148 mm2 (with or without terminal) and to groundwith flexible cable.

Delivered with disconnector and insulating bracket.

Arrester can be supplied with ground copper cable (cross section: 16 mm2, length: 50 cm).

Mounting:Vertical type installation: insulating bracket alone or AZNEMAbracketsSee mounting bracket section page 34.

Three-arrester packaging in cardboard box.

Ordering example: 300 AZB 032.

Time (s)Time current curve

Current (A)

Fault indicator detail

"Flag opening" 150

25

Ø12Operating area

Operating area

Disconnector Bracket

Time current curve

Time (s)

Current (A)

Arrester with 15 A fault indicator Arrester with disconnector and insulating bracket

AZP-- Class 1, AZCP-- Class 2 and AZBDP-- Class 1 AZB--2 Class 1, AZC--2 Class 2 and AZBD--2 Class 1

Ur (kVrms) 3 6 9 12 15 18 21 24 27 30 33 36 39 42

Arrester reference AZB 032 AZB 062 AZB 092 AZB 122 AZB 152 AZB 182 AZB 212 AZB 242 AZB 272 AZB 302 AZB 332 AZB 362 AZB 392AZB--2

Arrester reference AZC 032 AZC 062 AZC 092 AZC 122 AZC 152 AZC 182 AZC 212 AZC 242 AZC 272 AZC 302 AZC 332 AZC 362 AZC 392AZC--2

Arrester reference AZBD 032 AZBD 062 AZBD 092 AZBD 122 AZBD 152 AZBD 182 AZBD 212 AZBD 242 AZBD 272 AZBD 302 AZBD 332 AZBD 362 AZBD 392 AZBD 422AZBD--2

Ur (kVrms) 3 6 9 12 15 18 21 24 27 30 33 36 39 42

Arrester reference AZP 03 AZP 06 AZP 09 AZP 12 AZP 15 AZP 18 AZP 21 AZP 24 AZP 27 AZP 30 AZP 33 AZP 36 AZP 39AZP--

Arrester reference AZCP 03 AZCP 06 AZCP 09 AZCP 12 AZCP 15 AZCP 18 AZCP 21 AZCP 24 AZCP 27 AZCP 30 AZCP 33 AZCP 36 AZCP 39AZCP

Arrester reference AZBDP 03 AZBDP 06 AZBDP 09 AZBDP 12 AZBDP 15 AZBDP 18 AZBDP 21 AZBDP 24 AZBDP 27 AZBDP 30 AZBDP 33 AZBDP 36 AZBDP 39 AZBDP 42AZBDP

M10

20

catalogue Dervasil 28/05/08 10:21 Page 18

Page 22: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

20

A.C medium voltagenetwork protection

A.C

med

ium

vol

tage

net

wor

k pr

otec

tion

5kA

arre

ster

5 kA arresterEZB seriesEZBD series

General characteristics EZB, EZBD 22

Standard arrester EZB--0, EZBD--0 26

Arrester with 150 A fault indicator EZB--1, EZBD--1 27

Arrester with disconnector EZB--2, EZBD--2 28

A.C medium voltage network protection10 kA arrester

AZICS / AZCICS--0: Arresters improve spark gaz performances byeliminating power follow currents. Arrester module is supplied witharcing horn and replaces one horn of spark gap. AZICS / AZCICS--1arrester modules are installed in parallel with rigid insulators.

AZICS--0 / AZCICS--0: Delivered with mounting bracket on groundside and an arcing horn.

AZICS--1/ AZCICS--1: Delivered with mounting bracket on crossarmside and arcing horn.NB: Concerning connection and horn on line side, contact us.

Three-arrester packaging in cardboard box.

Ordering example: 300 AZICS 120.

Arrester for power follow current breaking

AZICS-- Class 1, AZCICS-- Class 2

Mounting configurations

Spark gap mounting AZICS--0 / AZCICS--0 Rigid insulator mounting AZICS--1 / AZCICS--1

Un (kVrms) System 9 12 15 18 20 24 30 36

3 6 9 12 15 18 24 30

Arrester reference AZICS 090 AZICS 120 AZICS 150 AZICS 180 AZICS 200 AZICS 240 AZICS 300 AZICS 36010 kA Class 1

Arrester reference AZCICS 090 AZCICS 120 AZCICS 150 AZCICS 180 AZCICS 200 AZCICS 240 AZCICS 300 AZCICS 36010 kA Class 2

Arrester reference AZICS 091 AZICS 121 AZICS 151 AZICS 181 AZICS 201 AZICS 241 AZICS 301 AZICS 36110 kA Class 1

Arrester reference AZCICS 091 AZCICS 121 AZCICS 151 AZCICS 181 AZCICS 201 AZCICS 241 AZCICS 301 AZCICS 36110 kA Class 2

Ur (kVrms) Lightning arrester

catalogue Dervasil 28/05/08 10:21 Page 20

Page 23: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

20

A.C medium voltagenetwork protection

A.C

med

ium

vol

tage

net

wor

k pr

otec

tion

5kA

arre

ster

5 kA arresterEZB seriesEZBD series

General characteristics EZB, EZBD 22

Standard arrester EZB--0, EZBD--0 26

Arrester with 150 A fault indicator EZB--1, EZBD--1 27

Arrester with disconnector EZB--2, EZBD--2 28

A.C medium voltage network protection10 kA arrester

AZICS / AZCICS--0: Arresters improve spark gaz performances byeliminating power follow currents. Arrester module is supplied witharcing horn and replaces one horn of spark gap. AZICS / AZCICS--1arrester modules are installed in parallel with rigid insulators.

AZICS--0 / AZCICS--0: Delivered with mounting bracket on groundside and an arcing horn.

AZICS--1/ AZCICS--1: Delivered with mounting bracket on crossarmside and arcing horn.NB: Concerning connection and horn on line side, contact us.

Three-arrester packaging in cardboard box.

Ordering example: 300 AZICS 120.

Arrester for power follow current breaking

AZICS-- Class 1, AZCICS-- Class 2

Mounting configurations

Spark gap mounting AZICS--0 / AZCICS--0 Rigid insulator mounting AZICS--1 / AZCICS--1

Un (kVrms) System 9 12 15 18 20 24 30 36

3 6 9 12 15 18 24 30

Arrester reference AZICS 090 AZICS 120 AZICS 150 AZICS 180 AZICS 200 AZICS 240 AZICS 300 AZICS 36010 kA Class 1

Arrester reference AZCICS 090 AZCICS 120 AZCICS 150 AZCICS 180 AZCICS 200 AZCICS 240 AZCICS 300 AZCICS 36010 kA Class 2

Arrester reference AZICS 091 AZICS 121 AZICS 151 AZICS 181 AZICS 201 AZICS 241 AZICS 301 AZICS 36110 kA Class 1

Arrester reference AZCICS 091 AZCICS 121 AZCICS 151 AZCICS 181 AZCICS 201 AZCICS 241 AZCICS 301 AZCICS 36110 kA Class 2

Ur (kVrms) Lightning arrester

catalogue Dervasil 28/05/08 10:21 Page 20

Page 24: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

2322

A.C medium voltage network protection5 kA arrester

A.C medium voltage network protection5 kA arrester

Tested in accordance with I.E.C 60099-4 standard.

Zinc oxide varistors.

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

Nominal discharge current: 5 kA 8/20 µs impulseHigh current withstand: 2 x 65 kA 4/10 µs impulseLong duration current withstand: 18 x 150 A 2000 µs impulse

Energy absorption capacity 1.8 kJoule/kV of Uc for one x 2000 µs impulse 2 kJoule/kV of Uc for one 4/10 µs impulse

Rated frequency: 48 to 62 HzService temperature - 40°C to + 40°C (+ 60°C short duration)Specified continuous load (SCL) 100 N.mSpecified short term load (SSL) 250 N.mMax tension strengt 1 kNMax torsion strength 30 N.mPollution area I.E.C 60815 3Short circuit rating after over voltage failure as Appendix 0 of I.E.C 60099-4 16000 A for 0.2s / 600 A for 1s

EZB series General characteristics

Physical characteristics

Arrester

type

Leakage

distance (mm)

Height

H (mm)

Unit weight

(kg) Lightningimpulse

1.2/50 µs

50 Hz 60s

Wet

A min

(mm)

B min

(mm)

Insulation withstandof housing (kv)

Mounting clearances

EZB_ 03_ 400 185 1.2 100 37 110 130EZB_ 06_ 400 185 1.4 100 37 110 130EZB_ 09_ 400 185 1.5 100 37 140 160EZB_ 12_ 400 185 1.6 100 37 140 160EZB_ 15_ 555 231 1.8 120 46 180 200EZB_ 18_ 555 231 2.1 120 46 180 200EZB_ 21_ 710 254 2.3 130 51 240 260EZB_ 24_ 710 254 2.4 130 51 240 260EZB_ 27_ 760 276 2.7 150 56 270 290EZB_ 30_ 1 000 345 3.0 190 70 320 340EZB_ 33_ 1 000 345 3.1 190 70 340 360EZB_ 36_ 1 000 345 3.2 190 70 340 360EZB_ 39_ 1 000 345 3.2 190 70 340 360

EZB line arrester does not have spark gapsin series. The zinc oxide varistors aredesigned to withstand the continuousphase to ground voltage of network. Theyare capable of bearing increasedoperational voltages over a long period.The temporary over voltage characteristicsgive the duration T and correspondingTOV with respect to continuous voltage Uc. The curve E = 0 is valid for arresters withoutenergy preloading. The other curve is validfor arresters, which are already absorbedimpulses corresponding to their maximumenergy absorption capability.

EZB_ 03_ 3 2.55 11.2 9.5 10.3 11.5 13.2 14.9 8.2EZB_ 06_ 6 5.1 22.0 18.5 20.1 22.5 25.8 29.2 16.1EZB_ 09_ 9 8.4 32.0 27.5 29.9 33.4 38.4 43.5 23.9EZB_ 12_ 12 10.2 43.0 36.4 39.7 44.4 51.1 57.7 31.8EZB_ 15_ 15 12.7 53.0 45.4 49.5 55.4 63.7 72.0 39.6EZB_ 18_ 18 15.3 64.0 54.4 59.3 66.4 76.3 86.3 47.4EZB_ 21_ 21 17.5 74.0 63.4 69.1 77.3 88.9 100.5 55.3EZB_ 24_ 24 19.5 74.0 63.4 69.1 77.3 88.9 100.5 55.3EZB_ 27_ 27 22.0 85.0 72.4 78.9 88.3 101.6 114.8 63.1EZB_ 30_ 30 24.4 95.0 81.4 88.7 99.3 114.2 129.1 71.0EZB_ 33_ 33 27.0 106.0 90.4 98.5 110.3 126.8 143.3 78.8EZB_ 36_ 36 29.0 113.7 99.4 108.3 121.2 139.4 157.6 86.6EZB_ 39_ 39 32.0 113.7 99.4 108.3 121.2 139.4 157.6 86.6

Electrical and mechanical characteristics

Temporary over voltage capability

Protective characteristics

Arrestertype

UrRated

voltage(kVrms)

UcContinuousoperatingvoltage(kVrms)

Residualvoltage

wave 1/4 µsat 10 kA

(kV)2.5 kA 10 kA

5 kA Nominaldischarge

current20 kA 40 kA

Residualvoltage

wave 30/80 µsat 500 A

(kV)

Residual voltage wave 8/20 µs (kV)

0

0,1

0,2

0,3

0,4

0,5

0,6

0,7

0,8

0,9

1

1,1

1,2

1,3

1,4

1,5

1,6

1,7

1,8

1,9

0,1 1 10 100 1000 10000 100000

Preloaded Energy = max Capability

Preloaded Energy = 0

A B

H

120

30

M10

k = TOV / Uc

TOV duration

catalogue Dervasil 28/05/08 10:21 Page 22

Page 25: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

2322

A.C medium voltage network protection5 kA arrester

A.C medium voltage network protection5 kA arrester

Tested in accordance with I.E.C 60099-4 standard.

Zinc oxide varistors.

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

Nominal discharge current: 5 kA 8/20 µs impulseHigh current withstand: 2 x 65 kA 4/10 µs impulseLong duration current withstand: 18 x 150 A 2000 µs impulse

Energy absorption capacity 1.8 kJoule/kV of Uc for one x 2000 µs impulse 2 kJoule/kV of Uc for one 4/10 µs impulse

Rated frequency: 48 to 62 HzService temperature - 40°C to + 40°C (+ 60°C short duration)Specified continuous load (SCL) 100 N.mSpecified short term load (SSL) 250 N.mMax tension strengt 1 kNMax torsion strength 30 N.mPollution area I.E.C 60815 3Short circuit rating after over voltage failure as Appendix 0 of I.E.C 60099-4 16000 A for 0.2s / 600 A for 1s

EZB series General characteristics

Physical characteristics

Arrester

type

Leakage

distance (mm)

Height

H (mm)

Unit weight

(kg) Lightningimpulse

1.2/50 µs

50 Hz 60s

Wet

A min

(mm)

B min

(mm)

Insulation withstandof housing (kv)

Mounting clearances

EZB_ 03_ 400 185 1.2 100 37 110 130EZB_ 06_ 400 185 1.4 100 37 110 130EZB_ 09_ 400 185 1.5 100 37 140 160EZB_ 12_ 400 185 1.6 100 37 140 160EZB_ 15_ 555 231 1.8 120 46 180 200EZB_ 18_ 555 231 2.1 120 46 180 200EZB_ 21_ 710 254 2.3 130 51 240 260EZB_ 24_ 710 254 2.4 130 51 240 260EZB_ 27_ 760 276 2.7 150 56 270 290EZB_ 30_ 1 000 345 3.0 190 70 320 340EZB_ 33_ 1 000 345 3.1 190 70 340 360EZB_ 36_ 1 000 345 3.2 190 70 340 360EZB_ 39_ 1 000 345 3.2 190 70 340 360

EZB line arrester does not have spark gapsin series. The zinc oxide varistors aredesigned to withstand the continuousphase to ground voltage of network. Theyare capable of bearing increasedoperational voltages over a long period.The temporary over voltage characteristicsgive the duration T and correspondingTOV with respect to continuous voltage Uc. The curve E = 0 is valid for arresters withoutenergy preloading. The other curve is validfor arresters, which are already absorbedimpulses corresponding to their maximumenergy absorption capability.

EZB_ 03_ 3 2.55 11.2 9.5 10.3 11.5 13.2 14.9 8.2EZB_ 06_ 6 5.1 22.0 18.5 20.1 22.5 25.8 29.2 16.1EZB_ 09_ 9 8.4 32.0 27.5 29.9 33.4 38.4 43.5 23.9EZB_ 12_ 12 10.2 43.0 36.4 39.7 44.4 51.1 57.7 31.8EZB_ 15_ 15 12.7 53.0 45.4 49.5 55.4 63.7 72.0 39.6EZB_ 18_ 18 15.3 64.0 54.4 59.3 66.4 76.3 86.3 47.4EZB_ 21_ 21 17.5 74.0 63.4 69.1 77.3 88.9 100.5 55.3EZB_ 24_ 24 19.5 74.0 63.4 69.1 77.3 88.9 100.5 55.3EZB_ 27_ 27 22.0 85.0 72.4 78.9 88.3 101.6 114.8 63.1EZB_ 30_ 30 24.4 95.0 81.4 88.7 99.3 114.2 129.1 71.0EZB_ 33_ 33 27.0 106.0 90.4 98.5 110.3 126.8 143.3 78.8EZB_ 36_ 36 29.0 113.7 99.4 108.3 121.2 139.4 157.6 86.6EZB_ 39_ 39 32.0 113.7 99.4 108.3 121.2 139.4 157.6 86.6

Electrical and mechanical characteristics

Temporary over voltage capability

Protective characteristics

Arrestertype

UrRated

voltage(kVrms)

UcContinuousoperatingvoltage(kVrms)

Residualvoltage

wave 1/4 µsat 10 kA

(kV)2.5 kA 10 kA

5 kA Nominaldischarge

current20 kA 40 kA

Residualvoltage

wave 30/80 µsat 500 A

(kV)

Residual voltage wave 8/20 µs (kV)

0

0,1

0,2

0,3

0,4

0,5

0,6

0,7

0,8

0,9

1

1,1

1,2

1,3

1,4

1,5

1,6

1,7

1,8

1,9

0,1 1 10 100 1000 10000 100000

Preloaded Energy = max Capability

Preloaded Energy = 0

A B

H

120

30

M10

k = TOV / Uc

TOV duration

catalogue Dervasil 28/05/08 10:21 Page 22

Page 26: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

2524

A.C medium voltage network protection5 kA arrester

A.C medium voltage network protection5 kA arrester

Tested in accordance with I.E.C 60099-4 standard.

Zinc oxide varistors.

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

High mechanical resistance.

Can be used as cable support.

EZBD series General characteristics

Physical characteristics

Arrester

type

Leakage

distance (mm)

Height

H (mm)

Unit weight

(kg) Lightningimpulse

1.2/50 µs

50 Hz 60s

Wet

A min

(mm)

B min

(mm)

Insulation withstandof housing (kV)

Mounting clearances

EZBD_ 03_ 230 140 1.2 100 37 110 130EZBD_ 06_ 230 140 1.4 100 37 110 130EZBD_ 09_ 315 170 1.5 100 37 140 160EZBD_ 12_ 375 180 1.6 100 37 140 160EZBD_ 15_ 500 195 1.8 120 46 180 200EZBD_ 18_ 540 230 2.1 120 46 180 200EZBD_ 21_ 660 245 2.3 130 51 240 260EZBD_ 24_ 660 245 2.4 130 51 240 260EZBD_ 27_ 750 270 2.7 150 56 270 290EZBD_ 30_ 830 305 3.0 190 70 320 340EZBD_ 33_ 960 320 3.1 190 70 340 360EZBD_ 36_ 960 320 3.2 190 70 340 360EZBD_ 39_ 1 050 360 3.2 190 70 340 360EZBD_ 42_ 1 050 360 3.2 190 70 360 380

EZBD line arrester does not have sparkgaps in series. The zinc oxide varistors aredesigned to withstand the continuousphase to ground voltage of network. Theyare capable of bearing increasedoperational voltages over a long period.The temporary over voltage characteristicsgive the duration T and correspondingTOV with respect to continuous voltage Uc. The curve E = 0 is valid for arresters withoutenergy preloading. The other curve is validfor arresters, which are already absorbedimpulses corresponding to their maximumenergy absorption capability.

EZBD_ 03_ 3 2.55 11.2 9.5 10.3 11.5 13.2 14.9 8.2EZBD_ 06_ 6 5.1 22.0 18.5 20.1 22.5 25.8 29.2 16.1EZBD_ 09_ 9 8.4 32.0 27.5 29.9 33.4 38.4 43.5 23.9EZBD_ 12_ 12 10.2 43.0 36.4 39.7 44.4 51.1 57.7 31.8EZBD_ 15_ 15 12.7 53.0 45.4 49.5 55.4 63.7 72.0 39.6EZBD_ 18_ 18 15.3 64.0 54.4 59.3 66.4 76.3 86.3 47.4EZBD_ 21_ 21 17.5 74.0 63.4 69.1 77.3 88.9 100.5 55.3EZBD_ 24_ 24 19.5 74.0 63.4 69.1 77.3 88.9 100.5 55.3EZBD_ 27_ 27 22.0 85.0 72.4 78.9 88.3 101.6 114.8 63.1EZBD_ 30_ 30 24.4 95.0 81.4 88.7 99.3 114.2 129.1 71.0EZBD_ 33_ 33 27.0 106.0 90.4 98.5 110.3 126.8 143.3 78.8EZBD_ 36_ 36 29.0 113.7 99.4 108.3 121.2 139.4 157.6 86.6EZBD_ 39_ 39 32.0 113.7 99.4 108.3 121.2 139.4 157.6 86.6EZBD_ 42_ 42 35.0 127.6 106.7 116.0 129.9 150.8 170.5 92.8

Electrical and mechanical characteristics

Temporary over voltage capability

Protective characteristics

Arrestertype

UrRated

voltage(kVrms)

UcContinuousoperatingvoltage(kVrms)

Residualvoltage

wave 1/4 µsat 10 kA

(kV)2.5 kA 10 kA

5 kA Nominaldischarge

current20 kA 40 kA

Residualvoltage

wave 30/80 µsat 500 A

(kV)

Residual voltage wave 8/20 µs (kV)

H

A B110

30

M10

Nominal discharge current: 5 kA 8/20 µs impulseHigh current withstand: 2 x 65 kA 4/10 µs impulseLong duration current withstand: 18 x 150 A 2000 µs impulse

Energy absorption capacity 1.8 kJoule/kV of Uc for one x 2000 µs impulse 2 kJoule/kV of Uc for one 4/10 µs impulse

Rated frequency: 48 to 62 HzService temperature - 40°C to + 40°C (+ 60°C short duration)Specified continous load (SCL) 250 N.mSpecified short term load (SSL) 350 N.mMax tension strength 15 kNMax torsion strength 70 N.mPollution area I.E.C 60815 3Short circuit rating after over voltage failure as Appendix 0 of I.E.C 60099-4 16000 A for 0.2s / 600 A for 1s

0

0,1

0,2

0,3

0,4

0,5

0,6

0,7

0,8

0,9

1

1,1

1,2

1,3

1,4

1,5

1,6

1,7

1,8

1,9

0,1 1 10 100 1000 10000 100000

Preloaded Energy = max Capability

Preloaded Energy = 0

k = TOV / Uc

TOV duration

catalogue Dervasil 28/05/08 10:21 Page 24

Page 27: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

2524

A.C medium voltage network protection5 kA arrester

A.C medium voltage network protection5 kA arrester

Tested in accordance with I.E.C 60099-4 standard.

Zinc oxide varistors.

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

High mechanical resistance.

Can be used as cable support.

EZBD series General characteristics

Physical characteristics

Arrester

type

Leakage

distance (mm)

Height

H (mm)

Unit weight

(kg) Lightningimpulse

1.2/50 µs

50 Hz 60s

Wet

A min

(mm)

B min

(mm)

Insulation withstandof housing (kV)

Mounting clearances

EZBD_ 03_ 230 140 1.2 100 37 110 130EZBD_ 06_ 230 140 1.4 100 37 110 130EZBD_ 09_ 315 170 1.5 100 37 140 160EZBD_ 12_ 375 180 1.6 100 37 140 160EZBD_ 15_ 500 195 1.8 120 46 180 200EZBD_ 18_ 540 230 2.1 120 46 180 200EZBD_ 21_ 660 245 2.3 130 51 240 260EZBD_ 24_ 660 245 2.4 130 51 240 260EZBD_ 27_ 750 270 2.7 150 56 270 290EZBD_ 30_ 830 305 3.0 190 70 320 340EZBD_ 33_ 960 320 3.1 190 70 340 360EZBD_ 36_ 960 320 3.2 190 70 340 360EZBD_ 39_ 1 050 360 3.2 190 70 340 360EZBD_ 42_ 1 050 360 3.2 190 70 360 380

EZBD line arrester does not have sparkgaps in series. The zinc oxide varistors aredesigned to withstand the continuousphase to ground voltage of network. Theyare capable of bearing increasedoperational voltages over a long period.The temporary over voltage characteristicsgive the duration T and correspondingTOV with respect to continuous voltage Uc. The curve E = 0 is valid for arresters withoutenergy preloading. The other curve is validfor arresters, which are already absorbedimpulses corresponding to their maximumenergy absorption capability.

EZBD_ 03_ 3 2.55 11.2 9.5 10.3 11.5 13.2 14.9 8.2EZBD_ 06_ 6 5.1 22.0 18.5 20.1 22.5 25.8 29.2 16.1EZBD_ 09_ 9 8.4 32.0 27.5 29.9 33.4 38.4 43.5 23.9EZBD_ 12_ 12 10.2 43.0 36.4 39.7 44.4 51.1 57.7 31.8EZBD_ 15_ 15 12.7 53.0 45.4 49.5 55.4 63.7 72.0 39.6EZBD_ 18_ 18 15.3 64.0 54.4 59.3 66.4 76.3 86.3 47.4EZBD_ 21_ 21 17.5 74.0 63.4 69.1 77.3 88.9 100.5 55.3EZBD_ 24_ 24 19.5 74.0 63.4 69.1 77.3 88.9 100.5 55.3EZBD_ 27_ 27 22.0 85.0 72.4 78.9 88.3 101.6 114.8 63.1EZBD_ 30_ 30 24.4 95.0 81.4 88.7 99.3 114.2 129.1 71.0EZBD_ 33_ 33 27.0 106.0 90.4 98.5 110.3 126.8 143.3 78.8EZBD_ 36_ 36 29.0 113.7 99.4 108.3 121.2 139.4 157.6 86.6EZBD_ 39_ 39 32.0 113.7 99.4 108.3 121.2 139.4 157.6 86.6EZBD_ 42_ 42 35.0 127.6 106.7 116.0 129.9 150.8 170.5 92.8

Electrical and mechanical characteristics

Temporary over voltage capability

Protective characteristics

Arrestertype

UrRated

voltage(kVrms)

UcContinuousoperatingvoltage(kVrms)

Residualvoltage

wave 1/4 µsat 10 kA

(kV)2.5 kA 10 kA

5 kA Nominaldischarge

current20 kA 40 kA

Residualvoltage

wave 30/80 µsat 500 A

(kV)

Residual voltage wave 8/20 µs (kV)

H

A B110

30

M10

Nominal discharge current: 5 kA 8/20 µs impulseHigh current withstand: 2 x 65 kA 4/10 µs impulseLong duration current withstand: 18 x 150 A 2000 µs impulse

Energy absorption capacity 1.8 kJoule/kV of Uc for one x 2000 µs impulse 2 kJoule/kV of Uc for one 4/10 µs impulse

Rated frequency: 48 to 62 HzService temperature - 40°C to + 40°C (+ 60°C short duration)Specified continous load (SCL) 250 N.mSpecified short term load (SSL) 350 N.mMax tension strength 15 kNMax torsion strength 70 N.mPollution area I.E.C 60815 3Short circuit rating after over voltage failure as Appendix 0 of I.E.C 60099-4 16000 A for 0.2s / 600 A for 1s

0

0,1

0,2

0,3

0,4

0,5

0,6

0,7

0,8

0,9

1

1,1

1,2

1,3

1,4

1,5

1,6

1,7

1,8

1,9

0,1 1 10 100 1000 10000 100000

Preloaded Energy = max Capability

Preloaded Energy = 0

k = TOV / Uc

TOV duration

catalogue Dervasil 28/05/08 10:21 Page 24

Page 28: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

2726

A.C medium voltage network protection5 kA arrester

A.C medium voltage network protection5 kA arrester

Can be connected to line and ground with aluminium or coppercables from 25 mm2 up to 148 mm2 (with or without terminal).

Mounting:Vertical type installation: EZX bracketHorizontal type installation: EQ 50-50

See mounting bracket section page 34.

Three-arrester packaging in cardboard box.

Ordering example: 300 EZB 030.

EZB--0 and EZBD--0Fault indicator is a black silicone band which is clamped around thearrester housing and is visible from a distance of several hundredsmetres. When the arrester fails in short-circuit, the power arcgenerated inside arrester opens the housing and cuts the band,which falls on the ground. Absence of black band indicates arresterto be changed. It operates above 150 A current within 1 second.

Can be connected to line and ground with aluminium or coppercables from 25 mm2 up to 148 mm2 (with or without terminal).

Mounting:Vertical type installation: EZX bracketHorizontal type installation: EQ 50-50

See mounting bracket section page 34.

Three-arrester packaging in cardboard box.

Ordering example: 300 EZB 031.

Indicator

EZB--1 and EZBD--1

Ur (kVrms) 3 6 9 12 15 18 21 24 27 30 33 36 39 42

Arrester reference EZB 030 EZB 060 EZB 090 EZB 120 EZB 150 EZB 180 EZB 210 EZB 240 EZB 270 EZB 300 EZB 330 EZB 360 EZB 390EZB--0

Arrester reference EZBD 030 EZBD 060 EZBD 090 EZBD 120 EZBD 150 EZBD 180 EZBD 210 EZBD 240 EZBD 270 EZBD 300 EZBD 330 EZBD 360 EZBD 390 EZBD 420EZBD--0

Ur (kVrms) 3 6 9 12 15 18 21 24 27 30 33 36 39 42

Arrester reference EZB 031 EZB 061 EZB 091 EZB 121 EZB 151 EZB 181 EZB 211 EZB 241 EZB 271 EZB 301 EZB 331 EZB 361 EZB 391EZB--1

Arrester reference EZBD 031 EZBD 061 EZBD 091 EZBD 121 EZBD 151 EZBD 181 EZBD 211 EZBD 241 EZBD 271 EZBD 301 EZBD 331 EZBD 361 EZBD 391 EZBD 421EZBD--1

Standard arrester Arrester with 150 A fault indicator

catalogue Dervasil 28/05/08 10:21 Page 26

Page 29: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

2726

A.C medium voltage network protection5 kA arrester

A.C medium voltage network protection5 kA arrester

Can be connected to line and ground with aluminium or coppercables from 25 mm2 up to 148 mm2 (with or without terminal).

Mounting:Vertical type installation: EZX bracketHorizontal type installation: EQ 50-50

See mounting bracket section page 34.

Three-arrester packaging in cardboard box.

Ordering example: 300 EZB 030.

EZB--0 and EZBD--0Fault indicator is a black silicone band which is clamped around thearrester housing and is visible from a distance of several hundredsmetres. When the arrester fails in short-circuit, the power arcgenerated inside arrester opens the housing and cuts the band,which falls on the ground. Absence of black band indicates arresterto be changed. It operates above 150 A current within 1 second.

Can be connected to line and ground with aluminium or coppercables from 25 mm2 up to 148 mm2 (with or without terminal).

Mounting:Vertical type installation: EZX bracketHorizontal type installation: EQ 50-50

See mounting bracket section page 34.

Three-arrester packaging in cardboard box.

Ordering example: 300 EZB 031.

Indicator

EZB--1 and EZBD--1

Ur (kVrms) 3 6 9 12 15 18 21 24 27 30 33 36 39 42

Arrester reference EZB 030 EZB 060 EZB 090 EZB 120 EZB 150 EZB 180 EZB 210 EZB 240 EZB 270 EZB 300 EZB 330 EZB 360 EZB 390EZB--0

Arrester reference EZBD 030 EZBD 060 EZBD 090 EZBD 120 EZBD 150 EZBD 180 EZBD 210 EZBD 240 EZBD 270 EZBD 300 EZBD 330 EZBD 360 EZBD 390 EZBD 420EZBD--0

Ur (kVrms) 3 6 9 12 15 18 21 24 27 30 33 36 39 42

Arrester reference EZB 031 EZB 061 EZB 091 EZB 121 EZB 151 EZB 181 EZB 211 EZB 241 EZB 271 EZB 301 EZB 331 EZB 361 EZB 391EZB--1

Arrester reference EZBD 031 EZBD 061 EZBD 091 EZBD 121 EZBD 151 EZBD 181 EZBD 211 EZBD 241 EZBD 271 EZBD 301 EZBD 331 EZBD 361 EZBD 391 EZBD 421EZBD--1

Standard arrester Arrester with 150 A fault indicator

catalogue Dervasil 28/05/08 10:21 Page 26

Page 30: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

D.C medium voltagenetwork protection

D.C

med

ium

vol

tage

net

wor

k pr

otec

tion

10kA

arre

ster

10 kA arrester - Class 2AZE--T series

General characteristics 30

150M10

20

28

A.C medium voltage network protection5 kA arrester

Disconnector is connected between arrester and ground. In case ofshort-circuit. It cuts off ground connection of arrester.Operating sensitivity is shown in the Time-Current Curve.

Can be connected to line with aluminium or copper cables from 25 mm2 up to 148 mm2 (with or without terminal) and to groundwith flexible cable.

Delivered with disconnector and insulating bracket.

Mounting:Vertical type installation: insulating bracket alone or AZNEMA bracketsSee mounting bracket section page 34.

Three-arrester packaging in cardboard box.

Ordering example: 300 EZB 032.

25

Ø12

Time current curve

Time (s)

Current (A)

Arrester with disconnector and insulating bracket

EZB--2 and EZBD--2

DisconnectorBracket

Ur (kVrms) 3 6 9 12 15 18 21 24 27 30 33 36 39 42

Arrester reference EZB 032 EZB 062 EZB 092 EZB 122 EZB 152 EZB 182 EZB 212 EZB 242 EZB 272 EZB 302 EZB 332 EZB 362 EZB 392EZB--2

Arrester reference EZBD 032 EZBD 062 EZBD 092 EZBD 122 EZBD 152 EZBD 182 EZBD 212 EZBD 242 EZBD 272 EZBD 302 EZBD 332 EZBD 362 EZBD 392 EZBD 422EZBD--2

catalogue Dervasil 28/05/08 10:21 Page 28

Page 31: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

D.C medium voltagenetwork protection

D.C

med

ium

vol

tage

net

wor

k pr

otec

tion

10kA

arre

ster

10 kA arrester - Class 2AZE--T series

General characteristics 30

150M10

20

28

A.C medium voltage network protection5 kA arrester

Disconnector is connected between arrester and ground. In case ofshort-circuit. It cuts off ground connection of arrester.Operating sensitivity is shown in the Time-Current Curve.

Can be connected to line with aluminium or copper cables from 25 mm2 up to 148 mm2 (with or without terminal) and to groundwith flexible cable.

Delivered with disconnector and insulating bracket.

Mounting:Vertical type installation: insulating bracket alone or AZNEMA bracketsSee mounting bracket section page 34.

Three-arrester packaging in cardboard box.

Ordering example: 300 EZB 032.

25

Ø12

Time current curve

Time (s)

Current (A)

Arrester with disconnector and insulating bracket

EZB--2 and EZBD--2

DisconnectorBracket

Ur (kVrms) 3 6 9 12 15 18 21 24 27 30 33 36 39 42

Arrester reference EZB 032 EZB 062 EZB 092 EZB 122 EZB 152 EZB 182 EZB 212 EZB 242 EZB 272 EZB 302 EZB 332 EZB 362 EZB 392EZB--2

Arrester reference EZBD 032 EZBD 062 EZBD 092 EZBD 122 EZBD 152 EZBD 182 EZBD 212 EZBD 242 EZBD 272 EZBD 302 EZBD 332 EZBD 362 EZBD 392 EZBD 422EZBD--2

catalogue Dervasil 28/05/08 10:21 Page 28

Page 32: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

30

M10

3130

D.C medium voltage network protection 10 kA arrester - Class 2

D.C medium voltage network protection 10 kA arrester - Class 2

Nominal discharge current: 10 kA 8/20 µs impulseLine discharge class: 2High current withstand: 2 x 100 kA 4/10µs impulsesLong duration current withstand: 20 x 600 A 2000 µs impulses

Energy absorption capacity 3.6 kJoule/kV of Uc for one x 2000 µs impulse4.6 kJoule/kV of Uc for one 4/10 µs impulse

Service temperature - 40°C to + 40°C (+ 60°C short duration)Permanent cantilever strength 100 N.mMax cantilever strength for one minute 250 N.mMax torsion strength 30 N.mPollution area I.E.C 60815 3Short circuit rating after over voltage failure as Appendix 0 of I.E.C 60099-4 20000 A for 0.2s / 600 A for 1s

AZE--T line arrester does not have spark gaps in series. The zincoxide varistors are designed to withstand the continuous phase toground voltage of network. They are capable to bear increasedoperational voltages over a long period. The temporary over voltagecharacteristics give the duration T and corresponding TOV per unitContinuous Voltage Uc. The curve E = 0 is valid for arresters without energy preloading. Theother curve is valid for arresters, which are already absorbedimpulses corresponding to maximum energy absorption capability.

AZE 010T 1.06 2.9 2.4 2.5 2.7 3.0 3.3 2.2AZE 012T 1.36 3.7 3.0 3.2 3.4 3.7 4.2 2.7AZE 020T 2.7 7.5 5.9 6.3 6.8 7.5 8.3 5.4AZE 030T 3.2 8.7 7.1 7.6 8.2 9.0 10.0 6.5AZE 040T 4.1 11.2 8.9 9.5 10.2 11.2 12.5 8.1AZE 050T 5.4 15.0 11.9 12.6 13.6 15.0 16.7 10.8AZE 060T 6.8 18.7 14.8 15.8 17.0 18.7 20.8 13.5AZE 080T 8.1 22.5 17.8 19.0 20.4 22.5 25 16.2

30M10

M10

30

H

A

AZE--T General characteristics Electrical and mechanical characteristics

Tested in accordance with I.E.C 60099-4 standardand EN 50123-5.

Zinc oxide varistors.

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

Can be connected to line and ground with aluminium or copper cables from 25 mm2 up to 148 mm2

(with or without terminal).

One-arrester packaging in cardboard box.

Ordering example: 300 AZE 040T.

Physical characteristics

AZE 010T 400 185 1.2 100 37 110AZE 012T 400 185 1.2 100 37 110AZE 020T 400 185 1.3 100 37 110AZE 030T 400 185 1.4 100 37 110AZE 040T 400 185 1.4 100 37 110AZE 060T 400 185 1.5 100 37 110AZE 080T 400 185 1.6 100 37 110

Arrester

reference

Leakage

distance (mm)

Height

(mm)

Unit weight

(kg)

Mounting clearances

A min(mm)

Lightningimpulse

1.2/50 µs

50 Hz 60s

wet

Insulation withstandof housing (kV)

K = TOV / Uc

Energy preloading = 0

Energy preloading = maximumenergy absorption capability

TOV duration

Temporary over voltage capability

Protective characteristics

Arrestertype

Continuousoperating voltage

Ucdc (kV)10 kA

(1/4 µs)2.5 kA 5 kA 10 kA 20 kA 40 kA

500 A(30/80 µs)

Residual Voltage (kV)

120

catalogue Dervasil 28/05/08 10:21 Page 30

Page 33: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

30

M10

3130

D.C medium voltage network protection 10 kA arrester - Class 2

D.C medium voltage network protection 10 kA arrester - Class 2

Nominal discharge current: 10 kA 8/20 µs impulseLine discharge class: 2High current withstand: 2 x 100 kA 4/10µs impulsesLong duration current withstand: 20 x 600 A 2000 µs impulses

Energy absorption capacity 3.6 kJoule/kV of Uc for one x 2000 µs impulse4.6 kJoule/kV of Uc for one 4/10 µs impulse

Service temperature - 40°C to + 40°C (+ 60°C short duration)Permanent cantilever strength 100 N.mMax cantilever strength for one minute 250 N.mMax torsion strength 30 N.mPollution area I.E.C 60815 3Short circuit rating after over voltage failure as Appendix 0 of I.E.C 60099-4 20000 A for 0.2s / 600 A for 1s

AZE--T line arrester does not have spark gaps in series. The zincoxide varistors are designed to withstand the continuous phase toground voltage of network. They are capable to bear increasedoperational voltages over a long period. The temporary over voltagecharacteristics give the duration T and corresponding TOV per unitContinuous Voltage Uc. The curve E = 0 is valid for arresters without energy preloading. Theother curve is valid for arresters, which are already absorbedimpulses corresponding to maximum energy absorption capability.

AZE 010T 1.06 2.9 2.4 2.5 2.7 3.0 3.3 2.2AZE 012T 1.36 3.7 3.0 3.2 3.4 3.7 4.2 2.7AZE 020T 2.7 7.5 5.9 6.3 6.8 7.5 8.3 5.4AZE 030T 3.2 8.7 7.1 7.6 8.2 9.0 10.0 6.5AZE 040T 4.1 11.2 8.9 9.5 10.2 11.2 12.5 8.1AZE 050T 5.4 15.0 11.9 12.6 13.6 15.0 16.7 10.8AZE 060T 6.8 18.7 14.8 15.8 17.0 18.7 20.8 13.5AZE 080T 8.1 22.5 17.8 19.0 20.4 22.5 25 16.2

30M10

M10

30

H

A

AZE--T General characteristics Electrical and mechanical characteristics

Tested in accordance with I.E.C 60099-4 standardand EN 50123-5.

Zinc oxide varistors.

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

Can be connected to line and ground with aluminium or copper cables from 25 mm2 up to 148 mm2

(with or without terminal).

One-arrester packaging in cardboard box.

Ordering example: 300 AZE 040T.

Physical characteristics

AZE 010T 400 185 1.2 100 37 110AZE 012T 400 185 1.2 100 37 110AZE 020T 400 185 1.3 100 37 110AZE 030T 400 185 1.4 100 37 110AZE 040T 400 185 1.4 100 37 110AZE 060T 400 185 1.5 100 37 110AZE 080T 400 185 1.6 100 37 110

Arrester

reference

Leakage

distance (mm)

Height

(mm)

Unit weight

(kg)

Mounting clearances

A min(mm)

Lightningimpulse

1.2/50 µs

50 Hz 60s

wet

Insulation withstandof housing (kV)

K = TOV / Uc

Energy preloading = 0

Energy preloading = maximumenergy absorption capability

TOV duration

Temporary over voltage capability

Protective characteristics

Arrestertype

Continuousoperating voltage

Ucdc (kV)10 kA

(1/4 µs)2.5 kA 5 kA 10 kA 20 kA 40 kA

500 A(30/80 µs)

Residual Voltage (kV)

120

catalogue Dervasil 28/05/08 10:21 Page 30

Page 34: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

32

Accessories

Acce

ssor

ies

Basic configurations 34

Optional bracket 35

Application examples 35

Surge counter with leakage current meter 36

Insulating cap 37

catalogue Dervasil 28/05/08 10:21 Page 32

Page 35: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

32

Accessories

Acce

ssor

ies

Basic configurations 34

Optional bracket 35

Application examples 35

Surge counter with leakage current meter 36

Insulating cap 37

catalogue Dervasil 28/05/08 10:21 Page 32

Page 36: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

Vertical position on transformertank with 2 AZPTR brackets

Vertical position on cross arm withAZPTR and AZNEMA brackets

Horizontal position on transformersupport with AZ 50 - 50 brackets

Horizontal positionwith AZ 50 - 50 brackets

3534

AccessoriesAccessories

Ø 12.5

L

3 6 9 12 15 18 21 24 27 30 33 36

Bracket reference EZX 1 EZX 2 EZX 3

Bracket L (mm)

EZX 1 100EZX 2 150EZX 3 210

3 6 9 12 15 18 21 24 27 30 33 36

Bracket reference AZ 50 50

3 6 9 12 15 18 21 24 27 30 33 36

Bracket reference AZPTR

Shown with AZB--2 arrester Bracket AZNEMA

Available options with basic configurations including EZX, AZ 50-50 or AZPTR brackets.

Ø 13

50

200

A

B

Basic configurations Optional bracket

Application exemples

(82 < A < 107) - (105 < B < 131)

Arrester rated voltage

Ur (kVrms)

Arrester rated voltage

Ur (kVrms)

Arrester rated voltage

Ur (kVrms)

catalogue Dervasil 28/05/08 10:21 Page 34

Page 37: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

Vertical position on transformertank with 2 AZPTR brackets

Vertical position on cross arm withAZPTR and AZNEMA brackets

Horizontal position on transformersupport with AZ 50 - 50 brackets

Horizontal positionwith AZ 50 - 50 brackets

3534

AccessoriesAccessories

Ø 12.5

L

3 6 9 12 15 18 21 24 27 30 33 36

Bracket reference EZX 1 EZX 2 EZX 3

Bracket L (mm)

EZX 1 100EZX 2 150EZX 3 210

3 6 9 12 15 18 21 24 27 30 33 36

Bracket reference AZ 50 50

3 6 9 12 15 18 21 24 27 30 33 36

Bracket reference AZPTR

Shown with AZB--2 arrester Bracket AZNEMA

Available options with basic configurations including EZX, AZ 50-50 or AZPTR brackets.

Ø 13

50

200

A

B

Basic configurations Optional bracket

Application exemples

(82 < A < 107) - (105 < B < 131)

Arrester rated voltage

Ur (kVrms)

Arrester rated voltage

Ur (kVrms)

Arrester rated voltage

Ur (kVrms)

catalogue Dervasil 28/05/08 10:21 Page 34

Page 38: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

ZC-B1M Surge counter with leakage current meter for Dervasil lightning arrester

3736

AccessoriesAccessories

ZC-B1M Surge counter is a device to record the number of lightning and switching surgedischarges. ZC-B1M Surge counter can be used with class 1 & 2 DERVASIL lightning arrestersand also similar arresters of other manufacturers. Number of discharges is recorded by 5-digit cyclometer and readings can be taken through theinspection window.Leakage current of lightning arrester is measured by 0-3mA scale readingmilliammeter.ZC-B1M Surge counter does not need any auxiliary power supply

Technical description

Insulating capfor Dervasil lightning arrester

The Dervasil insulating cap (Polyamid molded) is especially designed to feet on lighting arrester.

Technical description

Insulating cap

ZC-B1M Surge counter operates on lightning impulse current (8/20µs wave) more than 100A and can operate perfectly if the interval of multiple lightning strokes is more than 0.2s.Potential across the ZC-B1M Surge counter is less than 50V crest under normal operating conditions.Residual voltage at 10kA(8/20µs wave) of the ZC-B1M Surge counter is less than 3 kV and has negligible effect on the protection level of the lightning arrester.Discharge current capability is 100kA (4/10µs wave) and 1000A (2ms rectangular wave)

Performance

Dimensions

ZC-B1M Surge counter is connected between the earth terminal of thelightning arrester and the earth. It should be mounted as close as possibleto the lightning arrester and length of connecting wires should be as shortas possible. The connecting wire used between surge counter andlightning arrester should an insulated wire with impulse withstand voltagemore than 5 kV.

Installation

Earth terminal

Line terminal

247 mm

110 mm137 mm

285 mm

ø 220 mm

Ammeter

Reference : CAP M10

Drain hole

EARTH

Surge counter

Arrester earthterminal

Arrester

catalogue Dervasil 28/05/08 10:21 Page 36

Page 39: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

ZC-B1M Surge counter with leakage current meter for Dervasil lightning arrester

3736

AccessoriesAccessories

ZC-B1M Surge counter is a device to record the number of lightning and switching surgedischarges. ZC-B1M Surge counter can be used with class 1 & 2 DERVASIL lightning arrestersand also similar arresters of other manufacturers. Number of discharges is recorded by 5-digit cyclometer and readings can be taken through theinspection window.Leakage current of lightning arrester is measured by 0-3mA scale readingmilliammeter.ZC-B1M Surge counter does not need any auxiliary power supply

Technical description

Insulating capfor Dervasil lightning arrester

The Dervasil insulating cap (Polyamid molded) is especially designed to feet on lighting arrester.

Technical description

Insulating cap

ZC-B1M Surge counter operates on lightning impulse current (8/20µs wave) more than 100A and can operate perfectly if the interval of multiple lightning strokes is more than 0.2s.Potential across the ZC-B1M Surge counter is less than 50V crest under normal operating conditions.Residual voltage at 10kA(8/20µs wave) of the ZC-B1M Surge counter is less than 3 kV and has negligible effect on the protection level of the lightning arrester.Discharge current capability is 100kA (4/10µs wave) and 1000A (2ms rectangular wave)

Performance

Dimensions

ZC-B1M Surge counter is connected between the earth terminal of thelightning arrester and the earth. It should be mounted as close as possibleto the lightning arrester and length of connecting wires should be as shortas possible. The connecting wire used between surge counter andlightning arrester should an insulated wire with impulse withstand voltagemore than 5 kV.

Installation

Earth terminal

Line terminal

247 mm

110 mm137 mm

285 mm

ø 220 mm

Ammeter

Reference : CAP M10

Drain hole

EARTH

Surge counter

Arrester earthterminal

Arrester

catalogue Dervasil 28/05/08 10:21 Page 36

Page 40: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

Insu

lato

r

Tension insulators DSIL series 40

Support insulators RC series 40

Insulators for DC railways systems 41

Composite Insulators

catalogue Dervasil 28/05/08 10:21 Page 38

Page 41: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

Insu

lato

r

Tension insulators DSIL series 40

Support insulators RC series 40

Insulators for DC railways systems 41

Composite Insulators

catalogue Dervasil 28/05/08 10:21 Page 38

Page 42: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

4140

Tension Insulators DSIL series

Typical line voltage

(kV)

DSIL 15 15 70 401 450 195 4 87 1.3 84 58 125 138DSIL 20 20 70 476 680 270 8 87 1.5 116 81 173 192DSIL 30 30 70 576 1000 370 12 87 1.7 160 111 237 263

SpecifiedTensileload

(kN)

SectionLength

(mm)

LeakageDistance

(mm)

ArcingDistance

(mm)

Numberof Sheds

ShedDiameter

(mm)

EstimatedWeight

(kg)

Dry power fre-quency voltage

withstand

(kV)

Wet power fre-quency voltage

withstand

(kV)

Dry lightning impulse withstand

(Positive kV) (Negative kV)

Electrical characteristics

Composite insulators Insulators for DC railway systems

Support insulator RC series

Typical LineVoltage (kV)

SpecifiedCantileverLoad (kN)

Maximum CantileverLoad (kN)

SpecifiedTensile Load

(kN)

Height (mm)

LeakageDistance

(mm)

Arcing Distance

(mm)

Number ofSheds

Shed Diameter

(mm)

EstimatedWeight

(kg)

ELECTRICAL CHARACTERISTICSDry power

frequency voltagewithstand (kV)

Wet power frequency voltage

withstand (kV)(Positive kV) (Negative kV)

End fittings

Support insulator

Tested in accordance with I.E.C 61952

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

Typical LineVoltage (kV)

SpecifiedCantileverLoad (kN)

MaximumDesign

CantileverLoad (kN)

SpecifiedTensile Load

(kN)

Height (mm)

LeakageDistance

(mm)

Arcing Distance

(mm)

Number ofSheds

Shed Diameter

EstimatedWeight

ELECTRICAL CHARACTERISTICS

3 15 6 25 254 385 165 5 110 3,2 68 38 130 180

Dry power frequency voltage

withstand (kV)

Wet power frequency voltage

withstand (kV)

Socket

Ball

Clevis

Eye

Physical and electrical characteristicsTested in accordance with I.E.C. 61109

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

Physical and electrical characteristics

Tested in accordance with I.E.C. 61109

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

M16

M16

420 175 4 87 1.6 65 45 95 1051 4 30015 0.8

Insulatorreference

RC 15

650 250 8 87 1.8 95 65 140 1551 4 37020 0.8RC 20

970 350 12 87 2 130 90 195 2151 4 47030 0.8RC 30

Insulator reference

Physical and electrical characteristics

254

110

Dry lightning impulse withstand

(Positive kV) (Negative kV)

Dry lightning impulse withstand

catalogue Dervasil 28/05/08 10:21 Page 40

Page 43: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

4140

Tension Insulators DSIL series

Typical line voltage

(kV)

DSIL 15 15 70 401 450 195 4 87 1.3 84 58 125 138DSIL 20 20 70 476 680 270 8 87 1.5 116 81 173 192DSIL 30 30 70 576 1000 370 12 87 1.7 160 111 237 263

SpecifiedTensileload

(kN)

SectionLength

(mm)

LeakageDistance

(mm)

ArcingDistance

(mm)

Numberof Sheds

ShedDiameter

(mm)

EstimatedWeight

(kg)

Dry power fre-quency voltage

withstand

(kV)

Wet power fre-quency voltage

withstand

(kV)

Dry lightning impulse withstand

(Positive kV) (Negative kV)

Electrical characteristics

Composite insulators Insulators for DC railway systems

Support insulator RC series

Typical LineVoltage (kV)

SpecifiedCantileverLoad (kN)

Maximum CantileverLoad (kN)

SpecifiedTensile Load

(kN)

Height (mm)

LeakageDistance

(mm)

Arcing Distance

(mm)

Number ofSheds

Shed Diameter

(mm)

EstimatedWeight

(kg)

ELECTRICAL CHARACTERISTICSDry power

frequency voltagewithstand (kV)

Wet power frequency voltage

withstand (kV)(Positive kV) (Negative kV)

End fittings

Support insulator

Tested in accordance with I.E.C 61952

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

Typical LineVoltage (kV)

SpecifiedCantileverLoad (kN)

MaximumDesign

CantileverLoad (kN)

SpecifiedTensile Load

(kN)

Height (mm)

LeakageDistance

(mm)

Arcing Distance

(mm)

Number ofSheds

Shed Diameter

EstimatedWeight

ELECTRICAL CHARACTERISTICS

3 15 6 25 254 385 165 5 110 3,2 68 38 130 180

Dry power frequency voltage

withstand (kV)

Wet power frequency voltage

withstand (kV)

Socket

Ball

Clevis

Eye

Physical and electrical characteristicsTested in accordance with I.E.C. 61109

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

Physical and electrical characteristics

Tested in accordance with I.E.C. 61109

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

M16

M16

420 175 4 87 1.6 65 45 95 1051 4 30015 0.8

Insulatorreference

RC 15

650 250 8 87 1.8 95 65 140 1551 4 37020 0.8RC 20

970 350 12 87 2 130 90 195 2151 4 47030 0.8RC 30

Insulator reference

Physical and electrical characteristics

254

110

Dry lightning impulse withstand

(Positive kV) (Negative kV)

Dry lightning impulse withstand

catalogue Dervasil 28/05/08 10:21 Page 40

Page 44: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

4342

Insulators for DC railway systems

Tested in accordance with Italian specification TE 128

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

520

80

Insulator reference

SpecifiedCantileverLoad (kN)

SpecifiedTensile Load

(kN)

Height (mm)

LeakageDistance

(mm)

Arcing Distance

(mm)

Numberof Sheds

Shed Diameter

(mm)

EstimatedWeight

(kg)

ELECTRICAL CHARACTERISTICS

3 300 209 2 80 3.2 90 55 125 170

Dry power frequency voltage

withstand (kV)

Wet power frequency voltage

withstand (kV) (Positive kV)

1 135 520

Tested in accordance with Italian specification TE 127

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

100

324

Physical and electrical characteristics

Suspension insulator

Tension insulator

Physical and electrical characteristics

Typical LineVoltage (kV)

DSIL 3

QUESTIONS REGARDING THE NETWORK

Lightning arrester specification

• How is the neutral?❑ Solidly grounded❑ Distributed❑ High resistor grounded or compensated❑ Isolated

• Network typeUrban ❑ Yes ❑ NoRural ❑ Yes ❑ NoPercentage cables / Over head lines =……Earth line ❑ Yes ❑ No

• Rated Voltage … … … … … … … … … … … … … … … … … … … … … … Un = ……… Kv

• Monophased ❑ Biphased ❑ Triphased ❑

• Calculation according different types of networkUc = lighting arrester maximum operating voltageUn = system nominal voltage

• Solidly grounded neutral …………………………………Uc = 0,58 x 1,1 x Un• Low ohmic neutral …………………………………………Uc = 0,87 x 1,1 x Un• High impedance grounded

or compensated or isolated neutral …………………Uc = 1,1 x Un

• Arrester Class❑ In = 5kA❑ In = 10kA class 1❑ In = 10kA class 2

Residual voltage at In…Ures = …… kVTemporary over voltage withstand……………

TOV = …… kVDuration……………………… = …… s

• Leakage distance … … … … … … … … … … … … … … … … … … … …d = …… mm

• Accesssories❑ Disconnector❑ Fault indicator❑ Surge counter

APPLICATION QUESTIONNAIRE

(Negative kV)

Dry lightning impulse withstand

Insulator reference

SpecifiedCantileverLoad (kN)

SpecifiedTensile Load

(kN)

Height (mm)

LeakageDistance

(mm)

Arcing Distance

(mm)

Numberof Sheds

Shed Diameter

(mm)

EstimatedWeight

(kg)

ELECTRICAL CHARACTERISTICS

3 380 165 4 100 3.2 55 50 125 170

Dry power frequency voltage

withstand (kV)

Wet power frequency voltage

withstand (kV) (Positive kV)

9 40 324

Typical LineVoltage (kV)

DSIL 3

(Negative kV)

Dry lightning impulse withstand

catalogue Dervasil 28/05/08 10:21 Page 42

Page 45: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

4342

Insulators for DC railway systems

Tested in accordance with Italian specification TE 128

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

520

80

Insulator reference

SpecifiedCantileverLoad (kN)

SpecifiedTensile Load

(kN)

Height (mm)

LeakageDistance

(mm)

Arcing Distance

(mm)

Numberof Sheds

Shed Diameter

(mm)

EstimatedWeight

(kg)

ELECTRICAL CHARACTERISTICS

3 300 209 2 80 3.2 90 55 125 170

Dry power frequency voltage

withstand (kV)

Wet power frequency voltage

withstand (kV) (Positive kV)

1 135 520

Tested in accordance with Italian specification TE 127

Silicone rubber housing.

Outdoor and indoor use.

High resistance to vibrations.

High resistance to vandalism.

100

324

Physical and electrical characteristics

Suspension insulator

Tension insulator

Physical and electrical characteristics

Typical LineVoltage (kV)

DSIL 3

QUESTIONS REGARDING THE NETWORK

Lightning arrester specification

• How is the neutral?❑ Solidly grounded❑ Distributed❑ High resistor grounded or compensated❑ Isolated

• Network typeUrban ❑ Yes ❑ NoRural ❑ Yes ❑ NoPercentage cables / Over head lines =……Earth line ❑ Yes ❑ No

• Rated Voltage … … … … … … … … … … … … … … … … … … … … … … Un = ……… Kv

• Monophased ❑ Biphased ❑ Triphased ❑

• Calculation according different types of networkUc = lighting arrester maximum operating voltageUn = system nominal voltage

• Solidly grounded neutral …………………………………Uc = 0,58 x 1,1 x Un• Low ohmic neutral …………………………………………Uc = 0,87 x 1,1 x Un• High impedance grounded

or compensated or isolated neutral …………………Uc = 1,1 x Un

• Arrester Class❑ In = 5kA❑ In = 10kA class 1❑ In = 10kA class 2

Residual voltage at In…Ures = …… kVTemporary over voltage withstand……………

TOV = …… kVDuration……………………… = …… s

• Leakage distance … … … … … … … … … … … … … … … … … … … …d = …… mm

• Accesssories❑ Disconnector❑ Fault indicator❑ Surge counter

APPLICATION QUESTIONNAIRE

(Negative kV)

Dry lightning impulse withstand

Insulator reference

SpecifiedCantileverLoad (kN)

SpecifiedTensile Load

(kN)

Height (mm)

LeakageDistance

(mm)

Arcing Distance

(mm)

Numberof Sheds

Shed Diameter

(mm)

EstimatedWeight

(kg)

ELECTRICAL CHARACTERISTICS

3 380 165 4 100 3.2 55 50 125 170

Dry power frequency voltage

withstand (kV)

Wet power frequency voltage

withstand (kV) (Positive kV)

9 40 324

Typical LineVoltage (kV)

DSIL 3

(Negative kV)

Dry lightning impulse withstand

catalogue Dervasil 28/05/08 10:21 Page 42

Page 46: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

44

Notes

catalogue Dervasil 28/05/08 10:21 Page 44

Page 47: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

Our experienceWith 20 years know-how in the field of Medium Voltage networkprotection, DERVASIL designs and manufactures lightningarresters with zinc oxide varistors and synthetic housings.

Our productsDERVASIL offers:›› A range of latest generation arresters:

5 kA or 10 kA arresters with fault indicator or disconnector.Arresters for power follow current breaking.D.C. voltage arresters.DERVASIL arresters do not have internal spark gaps. They exhibit stable characteristics, with practically constant, very short response times (30 to 50 ns), and better behaviour underpollution.Direct injection of Silicone Rubber ensures both absolute sealing, exceptional resistance to pollution and excellent behaviour without explosion in case of short-circuitThey have been tested in accordance with the latest version of IEC Standard 60099-4.

›› New range of composite insulators: suspension insulators, tension insulators and support insulators.

Our R & D departmentDERVASIL has comprehensive calculation and testing equipmentfor the design of lightning arresters. Our facilities are available tocustomers for specific applications.

Our quality and environmental systemDERVASIL is ISO 9001 and ISO 14001 system certified.Our production process is approved by EDF and incorporates allroutine tests required by IEC Standard 60099-4. !

This documentation is not as per agreement.Items represented are proposed while stock lasts.

DERVASIL reserve the right to stop productionor modify specifications without prior notice.

Non-contractual pictures

Com ST

dervasil

couve catalogue Dervsasil 28/05/08 10:20 Page 3

Our experienceWith 20 years know-how in the field of Medium Voltage networkprotection, DERVASIL designs and manufactures lightningarresters with zinc oxide varistors and synthetic housings.

Our productsDERVASIL offers:›› A range of latest generation arresters:

5 kA or 10 kA arresters with fault indicator or disconnector.Arresters for power follow current breaking.D.C. voltage arresters.DERVASIL arresters do not have internal spark gaps. They exhibit stable characteristics, with practically constant, very short response times (30 to 50 ns), and better behaviour underpollution.Direct injection of Silicone Rubber ensures both absolute sealing, exceptional resistance to pollution and excellent behaviour without explosion in case of short-circuitThey have been tested in accordance with the latest version of IEC Standard 60099-4.

›› New range of composite insulators: suspension insulators, tension insulators and support insulators.

Our R & D departmentDERVASIL has comprehensive calculation and testing equipmentfor the design of lightning arresters. Our facilities are available tocustomers for specific applications.

Our quality and environmental systemDERVASIL is ISO 9001 and ISO 14001 system certified.Our production process is approved by EDF and incorporates allroutine tests required by IEC Standard 60099-4. !

This documentation is not as per agreement.Items represented are proposed while stock lasts.

DERVASIL reserve the right to stop productionor modify specifications without prior notice.

Non-contractual pictures

Com ST

dervasil

couve catalogue Dervsasil 28/05/08 10:20 Page 3

Page 48: Dervasil Route de Popenot - 42800 Saint Joseph - France ...vietpowergroup.vn/data/library/lje1486715405.pdf · IEC Standard 60099-4. ›› New range of composite insulators: suspension

Distributed by :

Dervasil Route de Popenot - 42800 Saint Joseph - FranceTel : +33 (0)4 77 83 22 81 - Fax : +33 (0)4 77 83 22 80Email : [email protected]

couve catalogue Dervsasil 28/05/08 10:20 Page 1

Distributed by :

Dervasil Route de Popenot - 42800 Saint Joseph - FranceTel : +33 (0)4 77 83 22 81 - Fax : +33 (0)4 77 83 22 80Email : [email protected]

couve catalogue Dervsasil 28/05/08 10:20 Page 1