Prevent Unplanned Outages with On-line PD Measurement of MV/HV Power Cables

Cable Partial Discharge Measuring Systems

Ammar Khan Technical Application Specialist – Cables CBM

1 Dated: June 21, 2016

Page 2: Descarga Parcial de Cables - Conferencia Virtual

• Partial discharge theory

• Power cable structure

• PD detection and localization

• Why online PD measurement

• Sensors used for online PD measurement

• Qualitrol offerings

• Case Studies

Overview

2

Page 3: Descarga Parcial de Cables - Conferencia Virtual

PARTIAL DISCHARGE THEORY

3

Page 4: Descarga Parcial de Cables - Conferencia Virtual

• According to IEC 60270

Partial discharge (PD) is a localized electrical discharge that only partially bridges the insulation

between conductors and which may or may not occur adjacent to a conductor.

• The term ‘partial discharge’ includes a wide group of discharge phenomena – (i) internal discharges occurring in voids or cavities within solid or

liquid dielectrics; – (ii) surface discharges appearing at the boundary of different

insulation materials; – (iii) corona discharges occurring in gaseous dielectrics in the

presence of inhomogeneous fields; – (iv) continuous impact of discharges in solid dielectrics forming

discharge channels (treeing).

What is Partial Discharge?

4

Page 5: Descarga Parcial de Cables - Conferencia Virtual

PD Phenomenon

5

HV across conductor

PD Pulses

Breakdown in cavity

Page 6: Descarga Parcial de Cables - Conferencia Virtual

The detection and measurement of discharges is based on the exchange of energy taking place during the discharge. These exchanges are manifested as:

– (i) electrical pulse currents – (ii) dielectric losses – (iii) E.M. radiation (light) – (iv) sound (noise) – (v) increased gas pressure – (vi) chemical reactions

Results of Partial Discharges

6

Page 7: Descarga Parcial de Cables - Conferencia Virtual

POWER CABLE STRUCTURE

7

Page 8: Descarga Parcial de Cables - Conferencia Virtual

• Designed life of power cables is approximately 40 years • Cable Types that can be tested using Qualitrol Online PD Technology:

– XLPE (Cross Linked PolyEthylene) – EPR (Ethylene Propylene Rubber) – PE (PolyEthylene) – PILC (Paper Insulated Lead Covered)

Power Cable, its Basic Structure

8

Page 9: Descarga Parcial de Cables - Conferencia Virtual

A Power Cable Circuit

9

Joints

Terminations Cross-bonding Links

Page 10: Descarga Parcial de Cables - Conferencia Virtual

Multi point grounding

10

Solid grounding

Page 11: Descarga Parcial de Cables - Conferencia Virtual

Distributed PD measurement

11

Zone 1 Zone 2 Zone 3

Page 12: Descarga Parcial de Cables - Conferencia Virtual

PD DETECTION AND LOCALIZATION

12

Page 13: Descarga Parcial de Cables - Conferencia Virtual

PD Detection into Cables

13

Long Cable

Defect

Measurement EndRemote End

PD at Cable Terminations

• PD in cable induces HF signals

• The signals travel in both

directions

• Signals attenuate during

propagation and reflect back at

terminations

• Detection Principle

• Capture the HF signals emitted

by PD at termination point

• Analyse signals to identify PD

fault and differentiate with Noise

or External PD signals

Long Cable

Defect

Measurement EndRemote End

PD in Joints and inside the Cables

Page 14: Descarga Parcial de Cables - Conferencia Virtual

PD Fault Localization

14

• Time Domain Reflectometry (TDR)

Principle is used to locate PD.

Measure time difference between

main and reflected HF signals (∆T)

• For Longer cables, reflected pulse

may not reach to the measurement

end Requires a signal injector at the

other end to inject same HF signal

• For accurate localisation requires Accurate length of cable

Cable Return Time (Tr)

Long Cable

Defect

Measurement End

Remote End

ΔT

Long Cable

Measurement EndRemote End

Tr

Page 15: Descarga Parcial de Cables - Conferencia Virtual

WHY ONLINE PD MEASUREMENT

15

Page 16: Descarga Parcial de Cables - Conferencia Virtual

• No need to de-energize the cable system • Non destructive testing • Accurate Detection of Incipient Faults under operating conditions • Accurate Localization or Zoning of Incipient Faults • Trending Fault Severity via regular CHECKUPs • Helps in scheduling maintenance and planned outage • Ensure that cable is defect free after repair / workmanship

Why Online PD Monitoring?

16

• Most of the incipient faults or defects in power cables generate PD signals well before the actual failure except water trees. • PD monitoring helps in identifying the incipient faults before the break down -> Saves cost of UNPLANNED OUTAGE

Page 17: Descarga Parcial de Cables - Conferencia Virtual

SENSORS USED FOR ONLINE PD MEASUREMENT

17

Page 18: Descarga Parcial de Cables - Conferencia Virtual

• HFCT (High Frequency Current Transformers) – To detect any PD signal coming from Cable insulation – One for each Cable – Installed at termination / joints

• TEV (Transient Earth Voltage) – To detect any external PD signals coming from termination

or nearby Switchgear Panel – One for each Termination – Installed near the openings or vents of terminations

• RF Antenna (Radio Frequency)

– For Noise gating – One for each Termination – Installed near to termination (Either TEV or RF Antenna)

Sensors used for Online PD Measurement

18

Page 19: Descarga Parcial de Cables - Conferencia Virtual

• High Frequency Current Transformers – Inductive type sensor – Split core to install sensor easily – Different variants to fit the purpose (current (up to 1000A), diameter

(up to 150mm internal diameter)) – Sensitivity: Up to 10mV / mA – Frequency Response: 200kHz – 15MHz

• Installation requires – Individual cable earth – Cable insulation gland – Installation is done while the cable is energised

Sensors: HFCT, Options for Installation

19

Page 20: Descarga Parcial de Cables - Conferencia Virtual

• Transient Earth Voltage Sensor – Capacitive type sensor – Integrated magnets help to attach it to

metallic body – Sensitivity: Up to 100mV / V

• Installation requires:

– Metal Switchgear should not be double skinned / walled

• RF Antenna – Can be used in place of TEV – Used to perform noise gating

20

Earthed metal clad

TEV

HFCT

Vent

Sensors: TEV and RF Antenna Installation

Page 21: Descarga Parcial de Cables - Conferencia Virtual

Sensors Positioning

21

HFCT

Page 22: Descarga Parcial de Cables - Conferencia Virtual

Sensors Positioning

22

Page 23: Descarga Parcial de Cables - Conferencia Virtual

Online Cable PD Measurement Topology

23

Sensors (HFCT, TEV)

Termination

Portable System / Permanent Installation

Sensors cables

Page 24: Descarga Parcial de Cables - Conferencia Virtual

QUALITROL OFFERINGS ON CABLE PD MEASUREMENT

24

Page 25: Descarga Parcial de Cables - Conferencia Virtual

Field Service

25

• Field Service

•Sit Survey and feasibility of Online PD measurement

•Risk Assessment

•Method statement document shared with the customer

•Testing of 6-9 cables per day

•Detailed report with further recommendations within 5 days as standard or

more days depending on the number of days of testing

Page 26: Descarga Parcial de Cables - Conferencia Virtual

Portable System

26

•Portable System (Periodic Measurement)

•Main Unit (4 simultaneous channels)

•Accessory Box

•Sensors

•Cables

Page 27: Descarga Parcial de Cables - Conferencia Virtual

Sensors

27

•High Frequency Current Transformers (HFCT)

•Transient Earth Voltage Sensor (TEV)

HFCT-150 1000A

3mV/mA

HFCT-100 500A, 1000A 3-5mV/mA

HFCT-60 50A, 500A, 5-10mV/mA

HFCT-30 50A

10mV/mA

Page 28: Descarga Parcial de Cables - Conferencia Virtual

Continuous Monitoring Solution

Page 29: Descarga Parcial de Cables - Conferencia Virtual

Continuous PD Monitoring Software

29

Page 30: Descarga Parcial de Cables - Conferencia Virtual

Continuous PD Monitoring Software

30

Page 31: Descarga Parcial de Cables - Conferencia Virtual

CASE STUDIES HIGH NOISE ENVIRONMENTS

31

Page 32: Descarga Parcial de Cables - Conferencia Virtual

Case Study 1: Lab Verification of Technology

Maximum magnitude phase resolved distribution of mixed signals including noise, PD, interference were applied together to test the system and separated out by the system

Page 33: Descarga Parcial de Cables - Conferencia Virtual

Case Study 2: GIS Substation

33

Cable Termination

GIS termination

220kV, XLPE

Around 500m length

Cable Termination

Remote end

Terminating to Overhead lines

Page 34: Descarga Parcial de Cables - Conferencia Virtual

Case Study 2: High Noise Environment

34

Before performing any filtering on Channel A single cycle data, high noise level and too much interference can be seen. Not sure which is PD or which is noise. Also not sure that there is any PD?

After filtering, white noise level is decreased. Interference signals can still be seen at the same locations. However, some more pulses appeared in the middle. These pulses in the middle may or may not be PD

Page 35: Descarga Parcial de Cables - Conferencia Virtual

Case Study 2: Extracted Noise Pulses

35

Channel A noise pulse shape, its maximum magnitude phase resolved distribution and pulse count phase resolved distribution

Page 36: Descarga Parcial de Cables - Conferencia Virtual

Case Study 2: Extracted PD Pulses

36

Channel A PD pulse shape, its maximum magnitude phase resolved distribution and pulse count phase resolved distribution By TDR, it states that PD is located at remote end.

Page 37: Descarga Parcial de Cables - Conferencia Virtual

Case Study 3: Metalclad Switchgear

37

Cable Termination

Metal clad

10kV, XLPE

Around 1367m length

One HFCT on the earth shield of cable

Other two beneath the metal housing as earth shield was available there

Page 38: Descarga Parcial de Cables - Conferencia Virtual

Case Study 3: Interference and PD

38

Before performing any filtering on Channel A single cycle data, low noise level but too much interference can be seen. Not sure which is PD or which is noise. Also not sure that there is any PD?

Page 39: Descarga Parcial de Cables - Conferencia Virtual

Case Study 3: Extracted Noise Signals

39

Noise pulse shape, its maximum magnitude phase resolved distribution and pulse count phase resolved distribution

Page 40: Descarga Parcial de Cables - Conferencia Virtual

Case Study 3: Extracted PD Signals

40

Channel A PD pulse shape, its maximum magnitude phase resolved distribution and pulse count phase resolved distribution. By TDR, it states that PD is located at remote end.

Page 41: Descarga Parcial de Cables - Conferencia Virtual

Case Study 3: Extracted PD Signals

41

Channel C PD pulse shape, its maximum magnitude phase resolved distribution and pulse count phase resolved distribution

Page 42: Descarga Parcial de Cables - Conferencia Virtual

THANK YOU

End of Session

42