design finalreport2
TRANSCRIPT
Chemistry
Ammonia act as a weak base in water where it dissociates to form ionized ammonium as shown in Equation (1). In order
to remove ammonia we need to shift the reaction left to yield more unionized ammonia, which can be easily liberated
out of water. Consequently we can increase the pH to make this shift occur and as shown on Figure 995, that for a pH
above 10 almost 90% of the ammonia exists as the desired unionized form and at pH 11 almost 99% of the ammonia
exist as the desired form. At pH less than 10, unionized ammonia content decreased significantly, thus for a robust
operation it is desirable to keep the pH above 11.
NH 3+H 2O↔NH 4+¿+OH−¿¿ ¿ (1)
Figure 995. Ammonia Dissociation at Different pH (Gay, 2009)
Pilot Plant Study
A pilot stripping column is constructed to simulate the ammonia stripping process. The data obtained
showed significant ammonia removal at pH 10 and greater and at pH 10 and greater less than 20 ppm
of ammonia is left in the treated stream.
Mass and Energy Balance
Mass Balance
The backwash system contain complex system that allows different modes of operation to regenerate the backwash
sand filter without causing any down time. For different modes of operation, flow path and flow rate are altered
resulting difficulty to perform mass balance. However the backwash system is designed to meet the objective of
delivering 10 m3/hr of feed to the stripping column and thus simplified process shown in Figure 996 is used to perform
mass balance.
Table 994. Mass Balance Table
Mass Balance (kg/hr)
Storm Water Heated Feed Alkaline Stream Air Air + NH3 Water Sulfuric Acid
Product
NH3 10 10 0 0 10 0 0 0H2O 9964 9964 0.25 0 0 9964 0.25 9965NaOH 0 0 0.25 0 0 0.25 0 0.25H2SO4 0 0 0
4268 4268 0 0.25 0.25
Air 0 0 0 0 0 0 0 0
Sum 9974 9974 0.5426
8 42789964.2
5 0.5 9965.5
The hand calculated mass balance is shown in the Table xxx. Storm water contains ammonia and trace amount of other
impurities which may yield unexpected reaction and affect the result of this study. However, a pilot plant study was
conducted by Yara, and no unexpected reaction was observed and the design objective of less than 20 ppm of ammonia
in the product stream was achieved. Consequently, it is safe to assume impurities pose negligible effect on the removal
of ammonia. Under the condition that the storm water is assumed to contain only ammonia and no unexpected
reactions would occur in the process, the mass balance is significantly simplified and the hand calculated data Table xxx
replicated the data calculated using HYSYS, Figure 998.
Energy Balance
Energy balance was performed on the over all system and the system has a net of 540 kW consumption. This system was
assumed to operate under adiabatic, 100% efficient with no unexpected reactions. In order to consider these factors we
will have to consult distributors to find the type of insulation, the brand of pumps and perform a more detailed reaction
analysis. These details are recommended for future work but are not included in the scope of this design.
There are three types of energy conversion considered and they are shown in Table xxx below. The three types of energy
include chemical, electrical, and thermal energy conversion. The chemical energy is associated with enthalpy of
dissociation, via when solid NaOH dissociates in water heat is produced. Enthalpy of dissociation calculation was
performed and a sample calculation is shown in Appendix A. The electrical energy are associated with running the pump.
The thermal energy is required to bring up the temperature of storm water and air feed. When comparing chemical,
electrical and thermal energy transfer, heating yield the most significance and enthalpy of formation is almost negligible.
The total energy balance yield a deficit of 540 kW for an adiabatic, 100% efficient system with no unexpected reactions.
Table xxx. Energy Balance Table
Energy Balance ΔHf (kJ/mol) Amount (mol/hr) Energy Input (kW)NaOH (s)+H 2O→Na+¿+OH−¿+H 2O ¿ ¿
-44.5 6.25 -0.077H 2SO4+2OH
−¿→SO42−¿+2H 2O ¿ ¿
-206.96 2.54 -0.15NH 3+H 2O↔NH 4
+¿+OH−¿¿ ¿3.62 10 0.010
Pumps 40 horsepower 29.8 29.8 Cp (kJ/kg*K) ∆T Air 4268 kg/hr 1.005 40 47.66Storm Water 9974 kg/hr 4.179 40 463.13 Sum 540.40
Sample Calculation: Enthalpy of Ammonia Dissociation at Standard Condition
NH 3+H 2O↔NH 4+¿+OH−¿¿ ¿
Table xxx. Enthalpy of Formation (Politechnika Gdanska)
Species ΔHof (kJ/mol)
NH3(aq) -80.29H2O(l) -285.83
NH4+
(aq) -132.51OH-
(aq) -229.99
ΔH=Σ ΔH f , products−Σ ΔH f reactants
ΔH o=(−132.51−229.99 ) kJmol
−(−80.29−285.83) kJmol
ΔH o=3.62 kJmol
HYSYS Simulation
Figure 996 HYSYS Simulation
The process simulation was performed using AspenTech’s HYSYS 2006 version and the pfd is shown in
Figure 996. The purpose of this simulation is to assess the feasibility of the chemistry of removing
Ammonia to the desire level of less than 10 ppm. Control and backwash sand filtration systems are not
included because HYSYS lacked the ability to perform these simulations. For the complete over view
and discussion of the process please see the PFD section below.
A decision tree was used to find a suitable simulation thermodynamic model is shown in the Apendix
Figure 999. The decision tree has suggested Henry’s Law to be sufficient, however there is not such
model in the ASPEN HYSYS 2006 version. Consequently we have chosen General NRTL model which
complies with Henry’s law at low pressure and temperature, and thus was an ideal selection.
As shown in Figure 996, the Storm Water feed is preheated to 60 degree Celsius and alkalized with
NaOH to PH 11 and sent to the randomly packed stripping column. According to our chemistry, more
than 99% of the ammonia will be in the unionized form at this temperature and pH and can be easily
removed. The column packing and counter current air provides the disturbance required to break the
suspension of the ammonia and water and thus liberating ammonia out of water. The resulting product
stream contains almost no ammonia as shown in the simulation report, Figure 998.
PFD The complete process Flow diagram is shown below.
Figure 997. Process Flow Diagram
NaOH/H2SO4 Addition
T-100 NaOH Mixing tank and T-300 H2SO4 are units used to add NaOH and H2SO4 respectively. Sodium
Hydroxide is required to raise the pH of the storm water to shift the ammonia from ionized form to unionized
form for ease of separation as discussed in the chemistry section above. The amount of NaOH required to
alkalize 10 m3 of storm water to PH 11 is determined to be 0.4 kg/hr and amount of H2SO4 required to
neutralize the same amount of sodium hydroxide is determined to be 0.5kg/hr. These results are based on
following equations (2) and (3) and the sample calculation for the amount of NaOH required is shown in
Appendix A.
NaOH (s)+H 2O→Na+¿+OH−¿+H 2O ¿ ¿ (2)
H 2SO4+2OH−¿→SO4
2−¿+2H 2O ¿ ¿ (3)
From our research that PH 10 is sufficient to achieve our design objective, however at pH 10 the process are
not robust for fluctuation and may result ineffective removal of ammonia when pH is below 10. Since these
calculations show that the amount of acid and base required is small and thus it is economically sustainable to
bring pH to 11 and make the process more robust to fluctuations. In reality, because the predominant
importance of maintaining desired pH, pH controls are implemented to prevent undesired pH change and the
details will be discussed in the process control section.
Figure 998. HYSYS Simulation Report
Figure 999. EOS Flow Table (Hamid, 2007, p. 8)
Hazard and Operability Study
The relative risk of a deviation was defined as the product of the frequency and consequence. Both
frequency and consequence were ranked relatively on a scale of 1-4, where 4 represent a frequent
deviation or severe safety concerns. Frequency rating is based on Ulrich, where likeliness of incident
for common plant units is listed. Consequence rating is based on human judgment with reference to
Material Safety Data Sheets listed in Appendix D. The maximum relative risk achievable on this scale is
16. The 3D diagram of the relative risk graph is shown below in Figure 995.
No flow
Low Flow
Low pressure
Low Temp
0
2
4
6
8
10
12
Heat Exchanges
Stripping Column
NaOH Mixing Tank
Sulfuric Acid Mixing Tank
Backwash Sand Filter
Pumps
Piping
HAZOP
Rela
tive
Risk
Figure 995. HAZOP
HAZOP analysis identified some severe problems such as heat exchanger subject to no flow, backwash
sand filter subject to high flow or high pressure, stripping column subject to high temperature etc.
Most these problems were identified as the result of pressure build up from abnormal flow condition.
Thus flow meter and pressure relief should be installed to provide methods of controlling flow and
mitigate the risk of pressure build up. For detailed HAZOP and list of recommendations please refer to
Table 996. HAZOP Decision Table in Appendix E.
Table 996. HAZOP Decision Table
Company: Yara HAZOP Team: Ahmed Agina, Hoss Agina, Jian Gu, Jingjin ChenProcess: Ammonia
Absorbtion Drawing: Ammonia absorbtion column Date: March 10, 2014
Item: Heat Exchanger
Process Parameter
Guide word
Possible Causes Possible consequences
Frequency
Consequence
Risk
Recommendation
Storm water flow into heat exchanger No Frozen Pipe
Pressurized pipe (steam generation) 4 3 12
Implement flow control
Plugged Pipe Pressure relief valve
Pump malfunctioned
HigherImproper flow control
Insufficient removal of ammonia 3 2 6
LowerImproper flow control
Pressurized pipe (steam generation) 3 3 9
Implement flow control
Cavitation in pump Pressure relief valve
Heated oil flow into heat exchanger No
Pump malfunctioned Pressure build up 1 3 3
Pressure relief valve
Pressure Higher
Storm water flow below normal Pipe rapture hazard 3 3 9
Flow rate meter for monitoring Storm water flow
Pump Caviation Lower Leakage None 1 0 0 None
Pump malfunctioned
Temperature Higher
Storm water flow below normal Pressure build up 3 3 9
Flow rate meter for monitoring Storm water flow
LowerOil flow rate below normal Poor Ammonia removal 1 2 2
Item:Absorption Column
Storm water flow into column No Frozen Pipe None 4 0 0
Flow rate meter for monitoring Storm water flow
Plugged Pipe
Pump malfunctioned
HigherImproper flow control
Insufficient removal of ammonia 3 2 6
Flow rate meter for monitoring Storm water flow
Flooding/Leaking Storm water solution
LowerImproper flow control None 3 0 0
Flow rate meter for monitoring Storm water flow
Air rate into column No
Pump malfunctioned Poor ammonia removal 1 2 2
Preform regular lab test for the product
Pressure HigherImproper flow control
Flooding/Leaking Storm water solution 3 1 3
Flow rate meter for monitoring Storm water flow
Lower Leakage None 1 0 0
Pump malfunctioned
Temperature Higher
Storm water flow below normal Incrustation 3 4 12
Flow rate meter for monitoring Storm water flow
Lower
Heat exchanger malfunctioned Poor ammonia removal 1 2 2
Preform regular lab test for the product
Item:NaOH mixing tank
Storm water flow into column No Frozen Pipe None 4 0 0 Plugged Pipe
Pump malfunctioned
HigherImproper flow control Overflow 3 2 6
Flow rate meter for monitoring Storm water flow
Improper NaOH mixing
LowerImproper flow control None 3 0 0
NaOH Flow NoPH control malfunctioned Poor ammonia removal 3 2 6
Preform regular lab test for the product
Pressure HigherImproper flow control
Flooding/Leaking NaOH solution 3 3 9
Flow rate meter for monitoring Storm water flow
Lower Leakage None 1 0 0
Pump malfunctioned
Temperature Higher
Heat exchanger malfunctioned Incrustation 1 4 4
Clean the tank peroidically
Lower
Heat exchanger malfunctioned None 1 0 0
Item:H2SO4 mixing tank
Storm water flow into column No Frozen Pipe None 4 0 0 none Plugged Pipe
Pump malfunctioned
HigherImproper flow control Overflow 3 2 6
Flow rate meter for monitoring Storm water flow
Improper H2SO4 mixing
LowerImproper flow control None 3 0 0
H2SO4 Flow NoPH control malfunctioned
Basic solution/bad product 3 3 9
Preform regular lab test for the product
HigherPH control malfunctioned
Acidic solution/bad product, PH induced corrosion 3 3 9
Preform regular lab test for the product
LowerPH control malfunctioned
Basic solution/bad product 3 3 9
Preform regular lab test for the product
Item: Back wash sand filter
Storm water flow into filter No Frozen Pipe None 4 0 0 None Plugged Pipe
Pump malfunctioned
HigherImproper flow control Pressure build up 3 4 12
Flow rate meter for monitoring Storm water flow
LowerImproper flow control None 3 0 0 None
Percipate removal Lower
Sand was not regenerated in time
crustation/ Pump damages 2 4 8
Strict maintenance scheduel
Pressure Higher
Storm water flow above normal
Equipment rapture hazard 3 4 12
Flow rate meter for monitoring Storm water flow
Lower Leakage None 1 0 0 None
Pump malfunctioned
Temperature HigherHeat exchange None 1 0 0 None
malfunctioned
Lower
Heat exchange malfunctioned None 1 0 0 None
Item: Pumps
Storm water flow into pumps No Frozen Pipe Cavitation in pump 4 2 8
Implement flow control
Plugged Pipe
Pump malfunctioned
Pressure LossPump was not primed Pump Caviation 1 2 2
Flow rate meter for monitoring Storm water flow
High
Excess friction from blocked pipe Pressure build up 4 3 12
Pressure relief valve
Control valve malfunctioned
Temperature Higher
Heat exchanger malfunctioned Cavitation in pump 1 2 2
Flow rate meter for monitoring Storm water flow
Item: Pipe
Blockage No Frozen Pipe Pressure build up 4 3 12Implement flow control
Plugged Pipe Pressure relief valve
Pump malfunctioned
Precipatation on the pipe wall
Significant Incrustation Pressure build up 2 3 6
Replace pipe if necessary
CorrosionSignificant
failed PH control Leakage 3 3 9
Use Polyethylene or Fiber glass pipe
Steam generation
Significant Flow varation Pressure build up 3 3 9
Implement flow control
Heat exchanger malfunction
Pressure relief valve
Sulfuric Acid S2SO4
Sodium Hydroxide (NaOH)
Ammonium Hydroxide (NH4OH)
Appendices
Sample Calculation: amount of NaOH required to alkailize 10 m3/h storm water to pH 11
pOH=14−pH
pOH=14−11
pOH=3
¿
¿M
qNaOH=qStormwater׿
qNaOH=10m3
hr×1000 L1m3
×10−3molL×( 0.040kg
mol)
qNaOH=0.4kghr
http://www.engr.usask.ca/classes/CHE/422/notes/ClassOrientation-Final%20Report%20Jan%202014.pptx
http://www.engr.usask.ca/classes/CHE/422/notes/2011/guideforreport.doc