design guide & standards june 2003
TRANSCRIPT
![Page 1: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/1.jpg)
University of Connecticut
Telecommunications Design Guide & Standards
June 2003
University Information Technology Services
369 Fairfield Way, Unit 1209
Storrs, Connecticut
![Page 2: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/2.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 i
Table of Contents
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1 Definitions and Acronyms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.2 Turn-key Solution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1.3 UCONN Specific Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.4 Regulatory Requirements, Codes and Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.5 Certification Requirements and Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2. Telecommunication Rooms and Pathways . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.1 Telecommunication Rooms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.2 Telecommunication Pathways . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
3. Cabling, Terminations and Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
3.1 Backbone (Riser) Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
3.2 Horizontal Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
4. Work Area Outlets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
4.1 Typical WAO Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
4.2 Program Space WAO Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
4.3 WAO Faceplates and Labeling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
5. Voice System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
5.1 Passive Voice Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
5.2 Active Voice Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
6. LAN System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
6.1 Passive LAN Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
6.2 Active LAN Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
6.3 Wireless LAN (WLAN) Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
7. SMATV Video System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
7.1 SMATV Video System Performance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
7.2 Academic and Administrative Buildings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
7.3 Student Housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
![Page 3: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/3.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 ii
8. Building Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
8.1 Building Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
8.2 Point-of-service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
8.3 Public Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
9. Close-out Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
9.1 Test Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
9.2 As-builts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
9.3 Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
10. Outside Plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
10.1 Pathways . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
10.2 Maintenance Holes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
10.3 Outside Plant As-Built Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Appendix
A Parts List
B Typical TR Layout
C Binding Post Information Form
D LAN Switch Audit Form
E Typical WAO Configurations
F WAO Faceplate Labeling
G TR Termination Labeling
H Typical Rack Elevation for LAN Equipment
I Typical Logical LAN Diagram
![Page 4: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/4.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 1
1. Introduction
The purpose of this document is to establish a strategic direction for the physical and logical
connectivity of telecommunications systems at the University of Connecticut. A properly designed
and constructed telecommunications systems based on industry standards will promote an efficient,
long-lasting and cost-effective telecommunications system. UCONN recognizes and adopts industry
standards and practices as interpreted by BICSI. As such, this document is intended to identify and
define requirements specific to UCONN. The implementation of this design guide and standards will
ensure a flexible, uniform telecommunications environment that will allow for the growth of high
speed, high bandwidth required by specialized applications used in a higher education environment.
This design guide is a living document and as such, the criteria contained within are subject to
revisions and updates as needed due to technological advances within the telecommunications
industry.
1.1 Definitions and Acronyms
To establish a common understanding, this document and the University of Connecticut use the
following definitions, terms and acronyms.
UCONN, the University of Connecticut, is the owner of all property and completed projects,
unless otherwise specified in the project. As the owner, UCONN has the right to enforce or
modify all applicable codes, standards, and UCONN specific requirements.
UNIVERSITY ITS, University Information Technology Services, is the department that is
responsible for maintaining all of UCONN’s telecommunications systems. As such, UNIVERSITY
ITS shall be entitled to final approval of the design, parts, and equipment proposed for UCONN’s
telecommunications cabling and systems.
UCIMT, University Center for Instructional Media and Technology, is the department that is
responsible for maintaining all audio/visual systems (AV) for UCONN’s Hi-tech Classrooms. As
such, UCIMT shall be entitled to final approval of all AV designs proposed for UCONN’s Hi-tech
Classrooms.
The term “shall” is used to denote requirements set forth by UCONN that are not negotiable or
arbitrary.
The term “should” is used where UCONN strongly recommends certain guidelines or practices.
![Page 5: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/5.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 2
AFF – Above Finished Floor AOR – Area of Refuge/Rescue AV – Audio Visual BDF – Building Distribution Frame CATV – Cable Television EF – Entrance Facility HVAC – Heating, Ventilating, and Air-conditioning IDF – Intermediary Distribution Frame LAN – Local Area Network MDF – Main Distribution Frame MH – Maintenance Hole OEM – Original Equipment Manufacturer OTDR – Optical Time Domain Reflectometer RCDD – Registered Communications Distribution Designer RF – Radio Frequency SMATV – Satellite Master Antennae Television TLT – Telecommunications Infrastructure Layout Technician TR – Telecommunications Room UTP – Unshielded Twisted Pair VMIU – Video Mask Interdiction Unit WAO – Work Area Outlet WI-FI – Wireless Fidelity WLAN – Wireless Local Area Network
Refer to section 1.4 for abbreviations or acronyms of regulatory and industry agencies.
1.2 Turn-key Solution
All telecommunication designs and installations for UCONN administrative, academic, residence
halls and apartment buildings shall be such that at the completion of the project, UCONN is
provided with complete and operational voice, LAN and SMATV video systems consistent with
the guidelines set forth in this document. Designs and installations shall incorporate existing
systems to ensure a seamless co-existence of newly installed and existing systems. Certified
personnel as specified in Section 1.5 shall perform all designs and installations.
Telecommunications drawings shall be identified as T-series in the approved construction
drawings. The telecommunications section of the specification manual shall be numbered
separately and distinctly from other sections as proposed by the Construction Specifications
Institute for the MasterFormat™.
Designs for TRs, cable pathways, voice, LAN and SMATV video systems shall be provided to
UNIVERSITY ITS for approval prior to bid. Submittals of all parts and equipment shall be
provided to UNIVERSITY ITS for approval prior to purchase.
![Page 6: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/6.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 3
1.3 UCONN Specific Materials
UCONN has standardized on specific brands and warranties for telecommunications cabling and
system requirements. All design specifications and bids submitted shall be based on materials
and equipment as specified, without substitution. UCONN’s parts and materials list will be
updated continually to amend discontinued items or technological changes. As such,
modifications to the parts and materials specified in the bid package may be required.
UCONN requires manufacturer’s extended system warranties on all cabling. Refer to section 9.3
to ensure compliance with required warranties.
The parts and materials list should not be considered a complete list as additional parts may be
required to provide complete solutions. All materials, equipment, hardware, and components
used shall be new and free from defects in materials, composition, and installed workmanship.
Materials and equipment shall be installed, placed, terminated, tested, handled, and processed in
a manner consistent with manufacturer’s instructions, prevailing codes, ordinances, regulations,
standards or UCONN specific requirements whichever is more stringent.
1.4 Regulatory Requirements, Codes and Standards
All work on UCONN campuses shall be in compliance with the following industry codes,
standards, and practices, as well as, UCONN specific requirements. It is the responsibility of all
trades to know and comply with the most current revisions of all codes, standards, and practices
set forth by the following agencies.
ANSI - American National Standards Institute
ASME - American Society of Mechanical Engineers
ASTM - American Society for Testing and Materials
BICSI - Business Industry Consulting Services International
EIA - Electronic Industry Association
FCC - Federal Communications Commission
IEEE - Institute of Electrical and Electronics Engineers Inc.
NEC - National Electrical Code
NEMA - National Electrical Manufactures Association
NFPA - National Fire Protection Association
OSHA - Occupational Safety and Health Administration
SCTE - Society of Cable Television Engineers
State of Connecticut and Local Building Codes
TIA - Telecommunications Industry Association
UL - Underwriters Laboratories
![Page 7: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/7.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 4
All code requirements, industry standards and practices, and UCONN specific requirements shall
be enforced, however, where they differ, the more stringent or UCONN specific requirements
shall be applied.
1.5 Certification Requirements and Documentation
A TLT, who is a BICSI certified RCDD, shall approve and stamp all engineered prints relating to
the telecommunications infrastructure including all TRs, riser diagrams identifying cable counts
and sizes, WAO locations, and logical designs. Current certifications shall be provided to
UCONN/UNIVERSITY ITS in conjunction with print and/or design submittals.
The cabling vendor shall provide documentation supporting their active status as a qualified
certified installer prior to award of the bid and/or installation of cabling components. Copies of the
certificates shall be provided to UNIVERSITY ITS prior to installation.
All SMATV video systems shall be designed and engineered by an SCTE Broadband
Communications Engineer. All SMATV video systems shall be installed and tested by SCTE
Broadband Communications Technician(s).
All trades working on the installation of the telecommunications infrastructure, voice, LAN, and
SMATV video systems shall provide licenses and/or certifications as required for manufacturers’
warranties.
2. Telecommunication Rooms and Pathways
Telecommunication rooms are designed specifically to house telecommunications equipment and
wiring. These rooms have specific requirements due to the nature, size and complexity of the
equipment and wiring housed in the room and shall not be combined with other building support
systems.
Telecommunication pathways provide a means of distributing cabling within a building. Pathways
include but are not limited to conduits, trays, sleeves and ducts between TRs, and between TRs and
WAOs.
Fire safety codes and regulations shall be met. Where applicable, plenum spaces shall be identified
on drawings and plenum rated cabling and materials shall be specified.
![Page 8: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/8.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 5
2.1 Telecommunication Rooms
Design considerations include, but are not limited to, location, size, lighting, ceiling, flooring,
HVAC, grounding, power, doors, relay racks, clearances, and pathways required to complete the
voice, LAN and SMATV video systems. Modifications may be necessary due to University and/or
building specific needs, which typically require a minimum of 80sf of useable floor space.
Detailed layouts for relay racks, cable management, backboards, termination fields, power outlets
and appropriate clearances shall be shown on the T-drawings. Flame retardant plywood
backboards shall be installed on all walls from floor to ceiling. One wall shall be designated for
the voice system and one wall for the SMATV video system.
UCONN’s LAN system requires a minimum of two floor-mounted, relay racks per TR. Racks shall
be dedicated for either active equipment or passive terminations. Planned rack usage shall not
exceed 288 connections or 30 rack mount units (RMU). Additional active and passive racks shall
be required to avoid exceeding these limits. These specifications may require room sizes to be
larger than those specified by BICSI and industry standards, which bases TR size on square
footage of service area.
Note: The use of one rack may be appropriate in installations where
LAN counts are minimal and future growth is limited. However, any
deviation from UCONN’s standard requirements is subject to approval by
UNIVERSITY ITS.
All TRs shall have a minimum of 12” wide ladder rack, installed around the perimeter and over the
equipment racks to provide a cable pathway. The pathway shall be strong and well secured to
support the weight of the cables and any possible splice enclosures. Each equipment rack shall
be securely fastened to the ladder rack to provide seismic bracing.
A minimum of three 20-amp, dedicated, quad power outlets, one for each area of voice, LAN and
SMATV video terminations. One quad power outlet box should be placed in close proximity to
the voice termination field and one for the SMATV video field. One quad power outlet box should
be mounted high on the wall near the location of the racks, or if the racks are located in the center
of the room, the outlet box should be mounted on the ladder rack or active relay rack.
All TRs shall be locked and keyed per UCONN specifications.
![Page 9: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/9.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 6
2.2 Telecommunication Pathways
Design considerations include, but are not limited to, conduits, cable trays, sleeves, ducts, pull
boxes, conduit fill, building layout, and other utilities. Due to University and/or building specific
needs, modifications may be necessary.
Detailed layouts of pathways shall be shown and labeled on T-drawings. UNIVERSITY ITS shall
approve design of all cable pathways before the release of the bid package.
All pathway conduits, trays, sleeves, ducts, pull boxes, etc. shall be sized to accommodate proper
cable bend radii, current cable counts, maintenance, future growth and adequate firestopping
where needed.
2.2.1 Backbone (Riser) Pathways
Use a minimum of three 4” trade size conduits or sleeves for cabling between TRs. Upon
completion, there shall be a minimum of one spare conduit or sleeve for future use. Where
possible, a riser pathway should extend to the roof to accommodate future cabling needs.
Vertical ladder rack shall be installed from floor to ceiling to establish a cable pathway
between riser sleeves.
2.2.2 Horizontal Pathways
All penetrations shall be sleeved with metallic conduit or equivalent. All sleeves shall be
reamed, have a plastic bushing installed on each end, and extend 4” beyond the wall or
ceiling on each side. Sleeves shall be of sufficient size to accommodate cabling and fire
stopping plus 40% spare capacity to allow for growth.
Cable pathways shall be accessible and follow the corridors of the building. Where cable tray
or conduit is not specified, a continuous pathway of independent cable supports shall be
provided. The distance between supports shall not exceed 48” and shall be fastened to the
building structure.
Conduits shall provide a pathway from each WAO box to an accessible common cable
pathway. Conduits shall be sized to accommodate the number of cables specified for
installation with room for additional fill. Conduits shall be a minimum of 1” in diameter. All
conduits used for WAOs shall stub into an outlet box. Box-connectors and plastic bushings
shall be installed on all conduits.
![Page 10: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/10.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 7
2.2.2.1 Outlet Boxes
All concealed outlet boxes shall be a minimum of 4-11/16” x 4-11/16” x 2-1/8” with a
single gang plaster ring. Each outlet box shall have a minimum of 1” diameter conduit
stubbed to an accessible cable pathway system. All conduits and outlet boxes shall be
grounded.
2.2.2.2 Surface Mounted Raceway
Raceway shall be metallic and sized to accommodate the number of cables specified for
installation with proper cable bend radii and room for additional fill. Split or dual channel
raceway shall be specified for installations that require both power and
telecommunication services to share raceway.
All surface-mounted raceway shall be identified and labeled on the print set with the
contents and the from-to locations.
2.2.2.3 Modular Furniture and Paneling
Furniture and paneling shall accommodate UCONN specific materials. UNIVERISTY ITS
shall be consulted to ensure compliance with University telecommunications needs.
3. Cabling, Terminations, and Testing
This section pertains to the inside plant cabling as UCONN provides and installs all outside plant
cabling and terminations. All installations shall be such that cables are labeled and routed neatly
for ease of identification. See Section 1.3. UCONN Specific Materials
3.1 Backbone (Riser) Cabling
Each horizontal cross-connect shall have a direct backbone to the main cross-connect.
3.1.1 Optical Fiber Backbone Cabling and Termination Requirements
The minimum strand count for optical fiber backbone cable is 12 strands of singlemode and
12 strands of multimode optical fiber cable.
Singlemode optical fiber shall be 9/125-micron. UCONN uses FC/APC-type connector
pigtails fusion spliced to backbone singlemode optical fiber. Singlemode optical fibers shall
be fusion spliced. Mechanical splices are not acceptable.
![Page 11: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/11.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 8
Multimode optical fiber shall be 62.5/125-micron. UCONN uses ST-type ceramic tip, heat
epoxy core connectors.
All optical fiber jumpers used for the LAN system shall be duplex OEM assembled cables.
3.1.1.1 Optical Fiber Testing Specifications
Testing shall be done in accordance to OEM requirements for extended warranty.
All singlemode optical fiber strands shall be tested using a power meter in one direction
at 1310nm and 1550nm. No loss shall exceed the sum of .75db per mated connector
plus .3db per splice plus the calculated cable length attenuation.
All multimode and singlemode optical fiber strands (other than pigtail splices) shall be
tested with an OTDR. OTDR traces shall be provided at 850nm for multimode and
1310nm for singlemode in one direction.
Printed test results shall be provided in a binder to UNIVERSITY ITS as part of the
closeout documentation. Test results shall be labeled by strand and include from-to
information, test speed, test date and time, and certification of the operator(s) performing
the tests.
3.1.2 UTP Backbone Cabling and Termination Requirements
Specify to have two UTPs for every voice WAO plus 40% growth capacity for each TR. Size
accordingly in 100 pair increments. All backbone cabling shall terminate on 110-punch
blocks using C-5 connectors.
A binding post spreadsheet shall be provided to UNIVERSITY ITS for cross-connect
identification purposes. UNIVERSITY ITS shall receive this information in order to activate
dial tone at least one week prior to building service needs or four weeks prior occupancy
which ever comes first.
3.1.2.1 UTP Backbone Testing Specifications
Each cable shall be tested for point-to-point continuity, the absence of opens, shorts,
crosses and grounds, as well as verification of binding post locations. All testing shall be
performed using certified calibrated testers and shall be done in accordance to OEM
requirements for warranty.
![Page 12: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/12.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 9
Documentation shall include the testing equipment make, model, and setting(s) used, as
well as, cable identification numbers, from-to locations of each cable, and test date and
times.
3.1.3 Coaxial Backbone Cabling and Termination Requirements
Specify Parameter III .500 hard-line coaxial CATV-R distribution cable to be installed
between TRs. No kinks or damage to the outer sheath are allowable. All connectors shall be
terminated with OEM specified tools. At least 10 feet of slack shall be left neatly routed
around the perimeter of the termination area in each TR. Minimum bend radius restrictions
shall be observed for all coaxial backbone cable.
Power supply voltage (60 VAC) shall not be run through F-connectors in the backbone.
3.1.3.1 Coaxial Backbone Testing Specifications
Each cable shall be tested for point-to-point continuity. Testing shall be done in
accordance to OEM requirements for warranty. All testing shall be performed using
certified calibrated testers.
Documentation shall include the testing equipment make, model, and setting(s) used, as
well as, cable identification numbers, from-to locations of each cable, test date and times.
3.2 Horizontal Cabling
All cables shall be continuous and without interruption from the WAO to the termination point in
the TR. In-line splices, splits, taps or bridges are not acceptable in horizontal station cabling
runs.
3.2.1 UTP Horizontal Cabling and Termination Requirements
UTP cabling shall be 4-pair, Category 5e, and green in color. Cable shall be in accordance
with OEM manufacturer’s requirements for warranty as specified in section 1.3.
The TR end of the cable shall terminate onto 110-punch blocks using C-4 connectors for
voice and 48-port patch panels using 8-pin, 8-conductor, T568B modular connectors for LAN.
The WAO end of the cable shall terminate on an 8-pin, 8-conductor, T568B modular
connector. Connectors for Category 5e shall be white for voice and green for LAN.
![Page 13: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/13.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 10
3.2.1.1 UTP Horizontal Testing Specifications
Testing shall be done in accordance to OEM manufacturer’s requirements as specified to
meet the appropriate end-to-end solution for warranty. All testing shall be performed
using certified calibrated testers.
Documentation shall include the testing equipment make, model, and setting(s) used, as
well as, cable identification numbers, from-to locations of each cable, and test date and
times.
3.2.2 Coaxial Horizontal Cabling and Termination Requirements
Each end of the coaxial cable shall be terminated with F-style compression fittings. Positive
compression type connectors with minimal signal leakage characteristics shall be installed
with OEM installation tool. Hex crimp connectors are not acceptable.
The TR end of the cable shall be connected to either a ground block F-81, splitter, or VMIU,
mounted neatly and securely to the termination backboard. The WAO end of the cable shall
be connected to an F-style insert.
Each coaxial cable shall be labeled with the corresponding 5-digit WAO faceplate label on the
tab of a cable tie identifier, using a fine point indelible marker. For student housing locations,
the cable shall have an additional cable tie identifier near the interdiction output port that is
labeled with the 3-digit room number. All labels shall be legible and identifiable.
3.2.2.1 Coaxial Horizontal Testing Specifications
All coaxial cable shall be tested with a TDR for length, impedance and continuity.
All coaxial cables shall be tested to assure compliance with FCC standards for
broadband CATV systems. A frequency response sweep of the building distribution
system shall be performed. The response shall meet the minimum FCC requirements
for frequency response and ripple.
The contractor shall provide electronic copies of the test results for all coaxial cables. All
tests shall be saved with a filename incorporating the jack number into the name.
UCONN currently uses Stealthware.
![Page 14: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/14.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 11
4. Work Area Outlets
WAOs consist of voice, LAN and/or SMATV services. Voice and LAN services use 4-pair UTP cables
terminated on 8-pin, 8-conductor, T568B modular connector jacks. SMATV services use RG-6
coaxial cables terminated on F-type modular connector jacks. UCONN uses typical variations of
WAOs. UCONN has established minimum WAO requirements based on program space. WAOs are
typically 18” AFF unless otherwise noted. Refer to Section 8. Building Systems for system specific
requirements.
4.1 WAO Configurations
The following descriptions are for typical WAO configurations. Other configurations may be needed
to meet specific application requirements.
Standard
Two 4-pair UTP cables terminated on 8-pin, 8-conductor, T568B modular connector jacks, one for
a voice connection and one for a LAN connection.
Wall Phone
One 4-pair UTP cable terminated on 8-pin, 8-conductor, T568B modular connector jacks for a
voice connection, 48”AFF.
LAN
Two 4-pair UTP cables terminated on 8-pin, 8-conductor, T568B modular connector jacks for LAN
connections.
SMATV
One RG-6 coaxial cable terminated on F-type modular connector jack.
Multi-media
Two 4-pair UTP cables terminated on 8-pin, 8-conductor, T568B modular connector jacks, one for
a voice connection and one for a LAN connection and one RG-6 coaxial cable terminated on an
F-type modular connector jack.
4.2 Program Space WAO Requirements
The following are minimal WAO requirements based on typical program spaces. Additional
WAOs may be required for ancillary devices (printers, fax machines, etc.), specific needs of the
occupant(s), and size or intended use of the room.
![Page 15: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/15.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 12
Faculty/Staff Offices
Two standard WAO located on opposite walls.
Dean/Director Offices
One standard WAO and one multi-media WAO located on opposite walls.
Clerical Staff/Graduate Student Offices and Work Areas
One standard WAO shall be provided for each desk or workspace.
Conference Rooms
One standard WAO and one multi-media WAO located on opposite walls.
Lounges/Break Rooms
One multi-media WAO.
Computer Labs
One LAN WAO for every two computers, one SMATV or multi-media WAO, one wall phone WAO
located near the door.
Classrooms
One multi-media WAO located near the teaching station and one wall phone WAO located near
the door.
Hi-tech Classrooms
UCIMT maintains all Hi-tech Classrooms and shall be consulted for specific WAOs and AV
requirements. Cabling specifically for AV shall use pathways designed specifically for the AV
system and shall at no time be located in pathways designed for cabling of UCONN’s voice, LAN,
and SMATV video systems.
Student Housing
Double occupancy bedrooms shall have one standard WAO and one multi-media WAO located
on opposite walls.
Single occupancy bedrooms shall have one multi-media WAO.
Common areas, such as living rooms, in apartments or suites shall have one SMATV WAO.
Study rooms and lounges shall have one standard WAO and one multi-media WAO located on
opposite walls.
![Page 16: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/16.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 13
4.3 WAO Faceplates and Labeling
All faceplates shall be flush-mounted, single gang and specified to match electrical faceplate in
quality and finish.
UCONN uses colored jacks in addition to location in the faceplate to identify the jack application.
A white jack or jack that matched the faceplate shall be used to identify a voice application and a
green jack shall be used to identify a LAN application. Where applicable, the top position of the
faceplate shall be used for voice, the bottom or middle position for LAN and the bottom position
for SMATV video.
WAO faceplates shall be numbered from left to right around the room when entering through the
door. Faceplates shall be labeled with a black on white printed label. Handwritten labels will not
be accepted. Each faceplate shall be identified with a 5-digit label. This format shall identify the
room number and the outlet location within the room. For example: 10102 would be room 101
(10102), outlet location 2 (10102).
Student housing applications may differ if room numbers include alpha designations. For
example: 101A1 would be room 101 (101A1), bedroom A (101A1), outlet location 1 (101A1).
T-drawings should include an example of each type of WAO configuration, a WAO numbering
submittal of each floor based on the room numbering scheme provided by UCONN and a
summary of all WAO faceplate counts.
5. Voice System
UCONN owns a Centrex System and provides and maintains all dial tone for the University. As such,
UNIVERITY ITS performs all end-user service requests, including adds, moves and changes.
5.1 Passive Voice Equipment
The voice system shall be terminated on 110 wiring blocks with jumper troughs. Distribution rings
for cable management shall be installed on the backboard for voice cabling. The voice backbone
110 wiring blocks shall be placed together on the backboard in the left-most position to allow
room for expansion. The voice station 110 wiring blocks shall be placed in the right-most position
with room for expansion.
All building services requiring voice circuits such as, fire alarm and elevator shall be terminated
on a separate 110 wiring block. Typically the building services 110 wiring block should be located
to the right of the voice station 110 wiring block field.
![Page 17: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/17.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 14
Every row on the 110 wiring blocks shall be labeled with designation strips including a printed
label with the identification number of backbone or station cable. Backbone 110 field labels shall
be white and station 110 field labels shall be blue. Building service 110 field labels shall be red.
Each station label on the 110 wiring block shall consist of the corresponding 5-digit WAO
faceplate label, followed by the 1-digit port number. For example, WAO faceplate label 10102,
port 1 shall be labeled 101021. Building services shall be labeled accordingly as “FIRE” or “ELEV
1”, “ELEV 2”, etc.
5.2 Active Voice Equipment
UNIVERSITY ITS performs all horizontal voice cross-connects needed for dial tone.
6. LAN System
UCONN owns and maintains the LAN system and provides core connectivity to all buildings. As
such, UNIVERSITY ITS will determine all core and distribution needs including configuration of all
LAN hardware. No external links or gateways to other networking resources may be installed on the
UCONN network.
The building LAN shall be designed to provide a turn-key solution which includes at a minimum, LAN
switches, patch cables, optical fiber cables, station cables and any ancillary materials necessary for
the activation of the network for the project. UNIVERSITY ITS shall approve LAN designs prior to
release of the bid package.
The LAN design shall provide one Ethernet switch port for every LAN jack with a minimum of twelve
spare ports per TR for future growth. UNIVERSITY ITS and the University occupants of the building
shall be consulted regarding special networking requirements.
All LAN hardware shall be delivered to UNIVERSITY ITS for configuration approximately six weeks
prior to installation. Prior to core connectivity of the LAN system, UNIVERSITY ITS shall receive the
LAN system cross-connect spreadsheet detailing the switch port to LAN jack location.
![Page 18: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/18.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 15
6.1 Passive LAN Equipment
The LAN system shall be terminated on 48-port patch panels, wired for T568B with rear wire
management shall be installed in the equipment rack designated for passive use. Horizontal
cable managers shall be installed above and below each patch panel for LAN cabling.
Building services requiring a LAN connection, such as HVAC or power monitoring, shall be
terminated on patch panels. Requirements for building services shall follow the LAN WAO
configuration.
Each port on the patch panel shall be labeled on the front with printed labels. Labels on the patch
panel shall consist of the corresponding 5-digit WAO faceplate label, followed by the 1-digit port
number. For example, WAO faceplate label 10102, port 2 shall be labeled 101022.
6.2 Active LAN Equipment
All LAN hardware needed to provide a turn-key solution shall be included in the design. LAN
hardware shall consist of aggregate and edge switches and associated components as needed to
complete the LAN system for the project. LAN switches shall be installed in the equipment rack
designated for active use with cable mangers above and below each switch. In addition, one
power-strip with surge suppression is required per active rack.
The LAN design shall accommodate all necessary connections between the core and aggregate
layers and the edge switch stack(s). All switches shall be connected using the appropriate
module. If a building consists of only one TR, please consult UNIVERSITY ITS, as an aggregate
switch may not be required.
A star configuration shall be used for TR and building aggregation design. At least one port on
the aggregate switch is required for UNIVERSITY ITS to provide a core connection. Each
aggregation point shall be connected to an uninterruptible power supply (UPS). Where an
aggregation point serves more than one building, a redundant power supply (RPS) is also
required.
A cascade configuration shall be used for each TR edge stack design. Each edge switch stack
requires a minimum of one port on the aggregation switch for uplink connection(s). Each stack
shall not exceed five edge switches.
![Page 19: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/19.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 16
6.3 Wireless LAN Systems
A WLAN system has not been approved for release. UCONN is in the process of defining
policies and usage requirements for all WLAN systems. These policies and requirements will be
specified in a UCONN WLAN White Paper.
UNIVERSITY ITS authorizes and manages the use of all Industrial, Scientific, and Medical (ISM)
bands on University premises defined by the FCC for use with unlicensed devices including: 902-
928 MHz (26 MHz), 2.4-2.4835 GHz (83.5 MHz) and 5.725-5.85 GHz (125MHz) frequencies. All
unlicensed ISM band devices shall comply with UCONN’s application of these bands for use on
the University premises.
UNIVERSITY ITS shall approve all WLAN designs prior to release of the bid package in addition
to submittals before installation of the system. Unauthorized installations are not permitted and
are subject to removal from UCONN’s network.
6.3.1 WLAN Design Requirements
UCONN’s proposed WLAN system is based on the IEEE 802.11b (802.11g, once ratified)
standard. All WLAN designs shall include: clearly defined projected areas of contained
coverage, access point quantities, locations, antenna type and placement, and appropriate
channel selection. An in-line Power over Ethernet (PoE) LAN switch and termination of LAN
jacks for Access Points on a separate patch panel may be required for larger installations.
One LAN WAO shall be provided for each access point location. All access points and
accessories shall be accessible for service and protected from theft and damage. The design
should note the exact location of the access point in relation to the finished ceiling.
All WLAN hardware shall be delivered to UNIVERSITY ITS for configuration approximately
six weeks prior to installation. In designs that include wireless network interface cards (NIC),
UNIVERSITY ITS shall be provided with all MAC addresses and corresponding user names.
This information is required for authentication and access to the WLAN system.
6.3.2 WLAN Testing and Documentation
All installations shall be field tested with a WI-FI certified device for signal strength and
coverage. As-built documentation of floor layouts shall illustrate all RF radiation patterns
emitted from each access point. RF leakage outside the scope of the project shall be
included in the diagram.
![Page 20: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/20.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 17
7. SMATV Video System
UCONN owns and maintains the SMATV video system and provides core connections to all
buildings. As such, UNIVERSITY ITS will determine and provide all core and distribution needs to the
demarcation of each building.
The SMATV video distribution system shall be designed to provide a turn-key solution that includes
video hardware, cables and any ancillary materials necessary for the delivery of video from the
building demarcation point to each WAO. UNIVERSITY ITS shall approve the design of the SMATV
video system before the release of the bid package.
Student housing video distribution systems differ from academic video distribution systems as they
utilize addressable interdiction systems, where academic systems employ traditional passive
equipment.
All splitters, directional couplers, taps or other active or passive devices are to be confined within
TRs. No equipment shall be mounted above ceilings, within walls or in any other locations.
Passive equipment and materials shall be 1,000 MHz.
7.1 SMATV Video System Performance Requirements
Distribution of the SMATV video system shall be balanced to provide each video WAO location
with the minimum acceptable carrier signal level for any CATV channel between 2 and 80 is 3
dBmV. No visual carrier shall differ from an adjacent carrier by more than 3dB. The maximum
difference between the highest and lowest visual carrier levels shall not exceed 13dB. At each
video WAO location 15 dBmV at channel 80 and 12 dBmV at channel 2 will be the maximum
allowed output. The minimum level at any output is 4 dBmV at channel 80 and 1 dBmV at
channel 2.
Minimum C/N ratio shall be 45 dB at the end of the horizontal run. Composite Second Order
(CSO) shall not exceed 55 dB at the end of the horizontal run. Composite Triple Beat (CTB)
shall not exceed 55 dB at the end of the horizontal run. Hum to Carrier shall not exceed 3% at
the end of the horizontal run.
7.1.1 Amplifier and Tap Levels
Levels entering any amplifier shall be flat between channels 2 and 80, at manufacturer
specified requirements.
![Page 21: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/21.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 18
7.1.2 Return Path
Return path shall be installed such that a modulator tuned to CATV channel T8, inserted at
+55 dBmV into any video outlet will produce a signal level of no less than +20 dBmV at the
diplexer located in the amplifier in the TR where the optical fiber feed is located. Each
amplifier shall have all electronics for 5-42 Mhz return-capability installed, configured and
balanced.
7.2 Academic and Administrative Buildings
UCONN’s SMATV video system in academic and administrative buildings requires amplifiers and
passive electronics. The design of the SMATV video system in these locations is required to
meet the specified performance levels for signal at each video WAO location.
7.3 Student Housing
UCONN’s SMATV video system in residence halls or apartment buildings require interdiction taps
to provide service to all video WAO locations. UNIVERSITY ITS controls interdiction units using
an automated system.
Interdiction units require line-powered 60VAC for operation, and require additional internal
directional couplers, pads and equalizers to be correctly configured and installed for operation.
Interdiction units have specific, manufacturer recommended operational windows for input and
output levels for proper operation.
In cases where one residence unit may require multiple drops, a splitter may be installed in the
TR, in close proximity to the VMIU. Layout of splitter and cable management shall be presented
prior to installation and approved by UNIVERSITY ITS. Drop amplifiers are not permitted to
extend horizontal coaxial lengths unless approved by UNIVERSITY ITS in writing.
Power passing taps shall be used to provide signal and power to each VMIU. In cases where a
single VMIU port feeds multiple horizontal runs, all performance requirements at the WAO
locations shall be met. Length of the cable runs shall be considered in the design due to the
limited output levels of the interdiction devices. Determining maximum horizontal cable length by
calculating the output levels of taps to accommodate multiple locations within each residence unit
is the responsibility of the system designer/engineer.
![Page 22: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/22.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 19
7.3.1 Testing Interdiction in Student Housing
UNIVERSITY ITS shall be provided with a spreadsheet of the VMIU port-to-room
assignments. This information is used to map the specific interdiction port address used
to serve a specific room and shall include: interdiction unit serial and digital numbers from
the barcode label on the housing, building name as identified by UCONN, and the
corresponding room/suite numbers as assigned by UCONN. UNIVERSITY ITS shall
receive this information at least five days prior to testing. For installations of more than
12 interdiction units, additional time will be required to input the data into the interdiction
system controller prior to operational testing.
Two operational tests will be used to verify interdiction unit configuration and operation.
One test is a visual inspection of each output port. This test is performed with a cable
ready television at the WAO. Video service is turned on and off using the management
system. The other test checks the interdiction units. Each port shall be shown to jam
channels 49-53 and 61-64. Both of these tests require a coordinated effort.
UNIVERSITY ITS will work with the installer and assist in controlling the video signal from
the head end. Both UNIVERSITY ITS and the installer will perform the inspections at the
WAOs.
7.3.2 Leakage Testing
UNIVERSITY ITS will conduct a cumulative signal leakage survey of the SMATV video
system and coaxial cable plant after installation and prior to building occupancy. The
project schedule shall accommodate time for UNIVERSITY ITS to perform leakage
testing and for the installer to correct and repair all leaks exceeding FCC regulation.
UNIVERSITY ITS will require a minimum of 3 days notice to schedule and prepare for
testing and a minimum of 1 working day for every 48 horizontal coaxial drops to perform
inspections and system testing.
UNIVERSITY ITS will provide a list of all leaks exceeding the FCC stated maximum of 20
µV/m measured at 3 meters. The contractor shall be responsible for repairing any signal
leak beyond 20 µV/m as required to be within compliance of FCC regulations. The
reported leaks shall be repaired and documentation of the repairs shall be submitted to
UNIVERSITY ITS before UCONN will accept the system as complete.
![Page 23: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/23.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 20
8. Building Systems
Building systems is a term used by UCONN when referring to additional systems such as building
monitoring, point-of-service, and public safety systems including Code Blue Emergency Phones.
UCONN shall be consulted to determine which building systems are required. Once these systems
are identified, telecommunications requirements shall be provided to UNIVERITY ITS on a
spreadsheet. Building systems WAO requirements shall be identified on the T-drawings to ensure
that UCONN voice and/or LAN system requirements are included in the telecommunications design.
8.1 Building Monitoring
Building monitoring systems include HVAC, power logic monitoring, intrusion detection and any
other monitoring system that may be required.
8.2 Point-of-service
Point-of-service systems include any systems that use card reader technology. These systems
are currently used for building access, point-of-sale transactions, and any other system UCONN
may use to provide these types of services to the University community.
8.3 Public Safety
Public safety systems include emergency and/or needs compliance systems for ADA
requirements. These systems comprise of fire alarm/AOR control systems, elevator
monitoring and phones, building access phones, and ride phones.
8.3.1 Code Blue Emergency Phones
UCONN Public Safety specifies Code Blue Emergency phone locations and UNIVERISTY
ITS provides the phone and cabling. Provisions for foundations and conduit pathways for all
Code Blue Emergency Phones need to be provided by the project.
Each Code Blue Emergency Phone requires two one-inch conduits, one for voice service and
one for electrical service. The telecommunications conduit shall terminate in the main TR of
the building from where service will be provided. This conduit will have a pull string installed,
tied off at both ends, and will be labeled in the TR as “Code Blue”. The electrical conduit
shall terminate in the electrical panel to provide 110VAC power on a dedicated 15-amp circuit
with emergency power backup for each Code Blue phone.
![Page 24: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/24.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 21
UNIVERSITY ITS shall be provided with as-built drawings that include conduit locations,
electrical panel number and breaker information.
9. Close-out Documentation
UNIVERSITY ITS shall be provided with all test results, as-builts, and warranty information no later
than thirty days from completion of project.
9.1 Test Results
All test results shall be submitted to UNIVERSITY ITS. A soft copy from the tester and an
electronic format is preferred. If UCONN does not have a software program capable of reading
the format, then either the software shall be provided or a hardcopy of the test results shall be
submitted in a ring binder.
9.2 As-builts
UNIVERSITY ITS shall be provided with the electronic media of all documentation as well as a
hard copy. As-built documents shall consist of the bid/construction package including all
addendums and modifications from the original scope. All changes shall be highlighted, noted, or
written in red. This package should include diagrams showing all risers, cable pathways, floor
layouts, and TR diagrams.
Riser diagrams shall include:
1. One-line diagrams for UTP copper cabling with cable counts.
2. One-line diagrams for optical fiber cabling with cable counts.
3. One-line diagrams for coaxial cabling with cable sizes.
Floor diagrams shall include:
1. TR locations and room numbers.
2. WAO locations and faceplate labels.
3. Horizontal cabling pathways.
TR diagrams shall include:
1. Butterfly layouts.
2. TR room numbers.
3. Backboard layouts for voice and video systems.
4. Rack elevations for LAN system.
![Page 25: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/25.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 22
All voice system 110-binding post information, LAN system cross-connects, and student housing
SMATV video system VMIU port-to-jack information shall be entered in Microsoft Excel
spreadsheets. UNIVERSITY ITS shall receive these spreadsheets as either a hardcopy or an
electronic file prior to testing and/or activation of the systems.
9.3 Warranty
UNIVERSITY ITS shall be provided with copies of all OEM system and equipment warranties.
UCONN requires manufacturer’s extended system warranties on all cabling. The approved
manufacturer warranties for structured cabling are NetClear by Ortronics, and ClearBIT or
SureBIT by Hubbell for copper cabling and Corning LANscape Extended Warranty Program for
optical fiber.
All warranty registrations for LAN and SMATV system equipment shall be provided to
UNIVERSITY ITS.
10. Outside Plant
This section pertains to outside plant structure as UCONN provides and installs all outside plant
cabling and terminations. As such, UNIVERSITY ITS shall be consulted regarding outside plant
pathways. UCONN uses an underground conduit system to provide pathways for
telecommunications cabling. Contact UCONN Architectural and Engineering Services for specific
guidelines and requirements for installation of maintenance holes and conduits. UCONN
Architectural and Engineering Services and agencies such as “Call Before You Dig” shall be
contacted prior to breaking ground.
Outside plant pathways include, but are not limited to, conduits, maintenance holes, hand-holes, and
pull-boxes. All outside plant pathways will become property of UCONN upon completion of the
project.
10.1 Pathways
UCONN buildings are fed with a minimum of one 4” conduit and one multi-cell from a
telecommunications maintenance hole. Multi-cell conduits shall be type C with a minimum of four
cells. A minimum of one 4” conduit shall be included in the design as spare to accommodate
future growth to the building.
Duct banks between maintenance holes shall be designed to include a minimum of six 4”
conduits. A minimum of three 4” conduits shall be noted in the design for spare to accommodate
future growth.
![Page 26: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/26.jpg)
University of Connecticut
Telecommunications Design Guide & Standards June 2003 23
Conduits shall be encased in concrete. Conduit runs shall not exceed a maximum distance of
400 feet for installations with a combined bend radius of 180 degrees between any two pulling
spaces. Any changes in direction between pulling spaces shall be included in the maximum
combined bend radius of 180 degrees. For straight installations between pulling spaces, the
maximum distance shall not exceed 600 feet. Where sharp bends or turns are unavoidable,
prefabricated fittings, joint boxes and/or pull boxes may be required. All joints shall be watertight.
A positive drain slope shall be maintained and all unused conduits shall be capped to prevent
water accumulation.
Installation of conduits and duct banks shall include provisions of all necessary accessories
including, but not limited to, couplings, bends, universal terminators at maintenance holes and
each building, slip couplings, and adapters fitting PVC to rigid duct, pull strings, etc. Steel and
PVC ducts shall be encased in a concrete envelope with duct separators. Conduits and duct
banks shall have a warning ribbon at least 12 in. above the underground installation.
10.2 Maintenance Holes
UCONN telecommunication maintenance holes shall be pre-cast with splay entrance and 6 feet
by 12 feet by 7 feet high. Minimum depth from ground surface to top of manhole roof shall be
one foot).
Standard hardware required for construction and utilization of maintenance holes shall be
provided. This includes rocking bolt assemblies, vertical support brackets, pulling irons, ladder
support hooks, covers, etc. The cover shall be labeled “telephone” or “communications.”
All conduits shall enter and exit on opposite pre-cored end walls only. Conduits shall be neatly
stacked and splayed into pre-cored knockouts starting on the bottom to allow for future
expansion. All splays shall be outside the maintenance hole to allow for maximum workable
space inside the maintenance hole. At no time shall conduits enter on the sidewall of the
manholes. A water barrier shall be installed at each construction joint
10.3 Outside Plant As-Built Documentation
As-built drawings shall identify and label all conduits, duct banks, maintenance holes, pull-boxes,
hand-holes and junction boxes. Documentation shall include cross sectional diagrams of duct
banks and butterfly diagrams of all maintenance holes, pull-boxes, hand-holes, and junction
boxes.
![Page 27: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/27.jpg)
University of Connecticut Appendix A
Telecommunications Design Guide & Standards June 2003 1
Parts List
OUTSIDE PLANT
Solution Description Manufacturer Part # Detail/Specific Requirements
* Maintenance Hole Rotondo & Son 38Y-4046-1 Telephone Maintenance Hole
* Multi-cell Conduit Carlon MX-4way PVC/Rigid Multi-Gard
VOICE SYSTEM TERMINATIONS
Solution Description Manufacturer Part # Detail/Specific Requirements
Hubbell 110 Wiring Block Hubbell 110BLK100FTK4 100-pair Field Termination Kit with 4-pair Connecting Blocks
Hubbell 110 Wiring Block Hubbell 110BLK100FTK5 100-pair Field Termination Kit with 5-pair Connecting Blocks
Hubbell 110 Wiring Block Hubbell 110BLK300FTK4 300-pair Field Termination Kit with 4-pair Connecting Blocks
Hubbell 110 Wiring Block Hubbell 110BLK300FTK5 300-pair Field Termination Kit with 5-pair Connecting Blocks
Hubbell 110 Wiring Block Hubbell 110TRA Cable Management Trough with Legs
Ortronics 110 Wiring Block Ortronics OR-30200145 110 Wiring Blocks with Legs, 100pr
Ortronics 110 Wiring Block Ortronics OR-30200007 110 Wiring Blocks with Legs, 300pr
Ortronics 110 Wiring Block Ortronics OR-30200109 110C Connecting Blocks, 4 Pair
Ortronics 110 Wiring Block Ortronics OR-30200110 110C Connecting Blocks, 5 Pair
Ortronics 110 Wiring Block Ortronics OR-30200140 Cable Management Trough w/Legs
Ortronics 110 Wiring Block Ortronics OR-70400272 110 Designation Kit (Labeling Kit)
BACKBONE CABLING
Solution Description Manufacturer Part # Detail/Specific Requirements
Hubbell Copper Cable General Cable 2133144 100pr Cat 3 UTP, CMR, Gray
Hubbell Copper Cable General Cable 2133373 300pr Cat 3 UTP, CMR, Gray
Hubbell Copper Cable General Cable 2131377 100pr Cat 3 UTP, CMP, Gray, Plenum Rated
![Page 28: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/28.jpg)
University of Connecticut Appendix A
Telecommunications Design Guide & Standards June 2003 2
BACKBONE CABLING (Cont.)
Solution Description Manufacturer Part # Detail/Specific Requirements
Hubbell Copper Cable General Cable 2131474 300pr Cat 3 UTP, CMP, Gray, Plenum Rated
Hubbell Copper Cable Mohawk M55211 100pr Cat 3 UTP, CMR, Gray
Hubbell Copper Cable Mohawk M57098 300pr Cat 3 UTP, CMR, Gray
Hubbell Copper Cable Mohawk M56128 100pr Cat 3 UTP, CMP, Gray, Plenum Rated
Hubbell Copper Cable Mohawk M57211 300pr Cat 3 UTP, CMP, Gray, Plenum Rated
Ortronics Copper Cable Berk-Tek 10032472 100pr Cat 3 UTP, CMR, Gray
Ortronics Copper Cable Berk-Tek 10032494 300pr Cat 3 UTP, CMR, Gray
Ortronics Copper Cable Berk-Tek 10032113 100pr Cat 3 UTP, CMP, Gray, Plenum Rated
Ortronics Copper Cable Berk-Tek 10032124 300pr Cat 3 UTP, CMP, Gray, Plenum Rated
Corning Optical Fiber Corning 0xxK81-33130-24 MIC Riser, Multimode (xx = Number of Strands)
Corning Optical Fiber Corning 0xxR81-33131-24 MIC Riser, Singlemode (xx = Number of Strands)
Corning Optical Fiber Corning 0xxK88-33130-29 MIC Plenum Riser, Multimode (xx = Number of Strands)
Corning Optical Fiber Corning 0xxR88-33131-29 MIC Plenum Riser, Singlemode (xx = Number of Strands)
Corning Optical Fiber Corning 0xxK61-31230-24 Fan-Out Riser, Multimode, Exposed Tray (xx = Number of Strands)
Corning Optical Fiber Corning 0xxR61-31231-24 Fan-Out Riser, Singlemode, Exposed Tray (xx = Number of Strands)
Corning Optical Fiber Corning 0xxK68-31230-29 Fan-Out Plenum Riser, Multimode, Exposed Tray (xx = Number of Strands)
Corning Optical Fiber Corning 0xxR68-31231-29 Fan-Out Plenum Riser, Singlemode, Exposed Tray (xx = Number of Strands)
* Coaxial Cable CommScope P3-500 JCAR Parameter III .500 Riser
* Coaxial Cable CommScope P3-500 JCAP Parameter III .500 Riser, Plenum Rated
* Connector Gilbert GRS-500-CH-DU-03 Pin Connector .500
![Page 29: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/29.jpg)
University of Connecticut Appendix A
Telecommunications Design Guide & Standards June 2003 3
FIBER TERMINATIONS
Solution Description Manufacturer Part # Detail/Specific Requirements
Hubbell Optical Fiber, Patch Cords Hubbell DFPCSCSCCxMM SC to SC 62.5/125, Multimode (x = Length in Meters)
Hubbell Optical Fiber, Patch Cords Hubbell DFPCSTSCCxMM ST to SC 62.5/125, Multimode (x = Length in Meters)
Hubbell Optical Fiber, Patch Cords Hubbell DFPCSTSTCxMM ST to ST 62.5/125, Multimode (x = Length in Meters)
Ortronics Optical Fiber, Patch Cords Ortronics OR-
61150D080xxM44C FC/APC to FC/APC, Singlemode (xx = Length in Meters)
Ortronics Optical Fiber, Patch Cords Ortronics OR-
61150D080xxM49C FC/APC to SC, Singlemode (xx = Length in Meters)
Ortronics Optical Fiber, Patch Cords Ortronics OR-
61150D620xxM33C ST to ST 62.5/125, Multimode (xx = Length in Meters)
Ortronics Optical Fiber, Patch Cords Ortronics OR-
61150D620xxM39C ST to SC 62.5/125, Multimode (xx = Length in Meters)
Ortronics Optical Fiber, Patch Cords Ortronics OR-
61150D620xxM99C SC to SC 62.5/125, Multimode (xx = Length in Meters)
* Optical Fiber, Patch Cords Corning 2121-02R5131-xxxM FC/APC to FC/APC, Singlemode (xxx = Length in
Meters)
* Optical Fiber, Patch Cords Corning 2158-02R5131-xxxM FC/APC to SC, Singlemode (xxx = Length in Meters)
* Optical Fiber, Patch Cords Corning 5050-02K5141-xxxM ST to ST 62.5/125, Multimode (xxx = Length in Meters)
* Optical Fiber, Patch Cords Corning 5039-02K5141-xxxM ST to SC 62.5/125, Multimode (xxx = Length in Meters)
* Optical Fiber, Patch Cords Corning 3939-02K5141-xxxM SC to SC 62.5/125, Multimode (xxx = Length in Meters)
Corning Optical Fiber, Pigtail Corning CCH-CP06-21-P03RH 6 Fiber FC Pigtail, Singlemode (Includes Panel)
Corning Connector Corning 95-100-44BP ST Multimode Epoxy & Polish Connector
Corning Housing Panel Corning CCH-CP06-15 LANscape ST Multimode
Corning Closet Connector Housing Corning CCH-04U LANscape 4U (Accepts 12 Housing Panels)
Corning Closet Connector Housing Corning CCH-02U LANscape 2U (Accepts 4 Housing Panels)
Corning Cable Mgmt. Component Corning CJP-01U LANscape 1U Jumper Management Panel
Corning Cable Mgmt. Component Corning CJP-02U LANscape 2U Jumper Management Panel
![Page 30: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/30.jpg)
University of Connecticut Appendix A
Telecommunications Design Guide & Standards June 2003 4
FIBER TERMINATIONS (Cont.)
Solution Description Manufacturer Part # Detail/Specific Requirements
Corning Closet Connector & Splice Housing Corning CCS-03U LANscape 3U (Accepts 4 Housing Panels and 4 Splice
Trays)
Corning Closet Splice Housing Corning CJH-02U LANscape 2U, Used with CJP-02U (Accepts 4 Splice Trays)
Corning Closet Splice Housing Corning CSH-03U LANscape 3U (Accepts 12 Splice Trays)
Corning Closet Splice Tray Corning M67-048 LANscape (Accepts 12 Singlemode Splices)
Corning Closet Splice Tray Corning M67-068 LANscape (Accepts 6 Singlemode splices)
HORIZONTAL CABLING & ACCESSORIES
Solution Description Manufacturer Part # Detail/Specific Requirements
Hubbell Copper Cable, Horizontal General Cable 6133512 PlatinumPlus 350 Cat 5e UTP, CMR, Green
Hubbell Copper Cable, Horizontal General Cable 6131547 PlatinumPlus 350 Cat 5e UTP, CMP, Green, Plenum
Rated
Hubbell Copper Cable, Horizontal Mohawk M56165 MegaLAN 400 Cat 5e UTP, CMR, Green
Hubbell Copper Cable, Horizontal Mohawk M56166 MegaLAN 400 Cat 5e UTP, CMP, Green, Plenum
Rated
Hubbell Faceplate, Single Gang Hubbell IFP Series Plastic (Standard Configurations are 2, 3 or 4 Ports)
Hubbell Faceplate, Single Gang Hubbell P630S1GJ8 Stainless Steel Wall Phone Plate (RJ45, T568B Jack)
Hubbell Faceplate, Single Gang Hubbell SSF series Stainless Steel (Standard Configurations are 2, 3 or 4
Ports)
Hubbell Jack Hubbell HXJ5EGN RJ45, T568B, Cat 5e, Green (LAN Applications)
Hubbell Jack Hubbell HXJ5EOW RJ45, T568B, Cat 5e, Office white (Voice Applications)
Hubbell Jack Hubbell SFB10 Blank, 10/pack, Office white
Hubbell Jack Hubbell SFFX Snap-fit F-Connector, Office white
Hubbell Outlet Box Hubbell AMO Multimedia Outlet (Accepts 6 Brackets)
Hubbell Outlet Box Hubbell OFPPL Multimedia Outlet (4-port and Fiber Brackets)
![Page 31: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/31.jpg)
University of Connecticut Appendix A
Telecommunications Design Guide & Standards June 2003 5
HORIZONTAL CABLING & ACCESSORIES (Cont.)
Solution Description Manufacturer Part # Detail/Specific Requirements
Hubbell Patch Panel Hubbell P5E48UE 48-port 2U Patch Panel, Universal (T568B Wiring)
Hubbell Wire Management Hubbell PCBLMGT Rear Wire Management Bar for P5E48UE
Hubbell Wire Management Hubbell HC219ME3N 19" 2U 3.50"x3.50" Cable Management
Hubbell Copper Cable, Patch Cords Hubbell PC5ESGNxx Speedgain Xcelerator Cat 5e, Green (xx = Length in
Feet)
Ortronics Copper Cable, Horizontal Berk-Tek 10032428 LANMark 350 Cat 5e UTP, CMR, Green
Ortronics Copper Cable, Horizontal Berk-Tek 10032086 LANMark 350 Cat 5e UTP, CMP, Green, Plenum Rated
Ortronics Faceplate, Single Gang Ortronics OR-403005xx Plastic TracJack Series (xx = Port Configuration)
Ortronics Faceplate, Single Gang Ortronics OR-403004xx Stainless Steel TracJack Series (xx = Port
Configuration)
Ortronics Faceplate, Single Gang Ortronics OR-854045212 Stainless Steel Wall Phone Plate (TracJack T568B
Wiring)
Ortronics Jack Ortronics OR-42100002 Blank, 10/pack, Fog White
Ortronics Jack Ortronics OR-63700006 F-Connector, Fog White
Ortronics Jack Ortronics OR-TJ5E00-25 RJ45, T568B, Clarity Cat 5e, Green (LAN Applications)
Ortronics Jack Ortronics OR-TJ5E00 RJ45, T568B, Clarity Cat 5e, Fog White (Voice Applications)
Ortronics Outlet Box Ortronics OR-40400056 6-port Surface Mount Box
Ortronics Patch Panel Ortronics OR-808004818 Cable Management Panel
Ortronics Patch Panel Ortronics OR-PHD5E6U48 Clarity 5E 48-port 2U Patch Panel, High Density (T568B Wiring)
Ortronics Wire Management Ortronics OR-60400057 5 Metal Rings 3" x 4", 2U
Ortronics Copper Cable, Patch Cords Ortronics OR-MC5Exx-05 Clarity 5E, 4 Pair, 24 AWG, Stranded, GTP. Green
(xx = Length in Feet)
* Coaxial Cable, Horizontal CommScope 5740 RG-6 Quad Shield, 75 Ohm, Non-plenum
* Coaxial Cable, Horizontal CommScope 2227V RG-6 Quad Shield, 75 Ohm, Plenum
![Page 32: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/32.jpg)
University of Connecticut Appendix A
Telecommunications Design Guide & Standards June 2003 6
HORIZONTAL CABLING & ACCESSORIES (Cont.)
Solution Description Manufacturer Part # Detail/Specific Requirements
* Connector Gilbert GF325CHT F-to-pin Connector
* Connector Gilbert GKSKSM Housing-to-housing Connector
* Connector Gilbert GTRMT Housing Terminator
* Connector Thomas&Betts SNS6PB Snap-n-seal RG 6 Quad Shield F-series, Plenum (Requires OEM Compression Tool)
* Connector Thomas&Betts SNS6QS Snap-n-seal RG 6 Quad Shield F-series, Non-plenum (Requires OEM Compression Tool)
* Cable Identifier Thomas&Betts TY551M Ty-Rap Cable Identifier (Required on Coaxial Cable for Student Housing)
* Compression Tool Thomas&Betts IT1000 Includes Compression Tool with Cable Prep
* Compression Tool Thomas&Betts SNSIT Requires Cable Prep T&B CPT-6590
* Cable Prep Thomas&Betts CPT-6590 For use with Compression Tool T&B SNSIT
LAN SYSTEM EQUIPMENT
Solution Description Manufacturer Part # Detail/Specific Requirements
* GBIC Module Cisco WS-G5483 1000BASE-T GBIC
* GBIC Module Cisco WS-G5484 1000BASE-SX Short Wavelength GBIC (Multimode Only)
* GBIC Module Cisco WS-G5486 1000BASE-LX/LH Long Haul GBIC (Singlemode or Multimode)
* Ethernet Switch Cisco WS-C2950G-24-EI 24-port 10/100 with 2 GBIC Slots, Enhanced Image (Requires SNTE-C2950-G24 8x5x4 Warranty)
* Ethernet Switch Cisco WS-C2950G-48-EI 48-port 10/100 with 2 GBIC Slots, Enhanced Image (Requires SNTE-C2950-G48 8x5x4 Warranty)
* Ethernet Switch Cisco WS-C3550-12G 10-port 1000BaseX plus 2-port 10/100/1000BaseT (Requires SNTE-C3550-12G 8x5x4 Warranty)
* Ethernet Switch Cisco WS-C3550-12T 10-port 10/100/1000BaseT plus 2-port 1000BaseX (Requires SNTE-C3550-12T 8x5x4 Warranty)
* Redundant Power System (RPS) Cisco PWR675-AC-RPS-
N1= Cisco RPS 675 with 1 connector cable (Requires SNTE-PWR675-AC-RPS-N1 8x5x4 Warranty)
* RPS Cable Cisco CAB-RPS-1614= 1.2 Meter Cable for Cisco RPS 675
![Page 33: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/33.jpg)
University of Connecticut Appendix A
Telecommunications Design Guide & Standards June 2003 7
SMATV SYSTEM EQUIPMENT
Solution Description Manufacturer Part # Detail/Specific Requirements
* Fiber Receiver C-Cor HX8L13 series Optiworx Fiber Optical Forward Path Receiver (SC/UPC Connector)
* Fiber Transmitter C-Cor 1074320 Optiworx Shelf and Power Supply Manual
* Fiber Transmitter C-Cor HX2281EC Optiworx Fiber Shelf
* Fiber Transmitter C-Cor/ Optiworx HX8L13 series Fiber Optic Transmitter (Connector SC/UPC, APC)
* Fiber Transmitter C-Cor/ Optiworx HXFAN110 Shelf and Power Supply Fan Assembly
* Splitter Fiberdyne Labs FTSCAPC Optical Splitter Terminators
* Splitter Fiberdyne Labs Per Design Optical Splitter (SC/APC Only)
* Tap Motorola FFT8-N/PE series Starline 2000 Power Extracting Tap
PATHWAYS & SPACES
Solution Description Manufacturer Part # Detail/Specific Requirements
* Ladder Rack Hubbell HLSxx12G NextFrame 12" Wide Cable Runway, Gray (xx = Length in Feet, 06 or 10)
* Ladder Rack Accessory Hubbell HLCD12 NextFrame 12" Wide Cable Radius Drop
* Ladder Rack Accessory Hubbell HLCD06 NextFrame 6" Wide Cable Radius Drop for Stringer
* Ladder Rack Hubbell HLI1290G NextFrame 12" Wide Inside Radius Bend
* Ladder Rack Hubbell HLF1290G NextFrame 12" Wide Flat Turns Bend
* Ladder Rack Hubbell HLO1290G NextFrame 12" Wide Outside Radius Bend
* Ladder Rack Chatsworth 10250-x12 12" Wide Universal Cable Runway (Gray)
* Ladder Rack Accessory Chatsworth 12100-x12 12" Wide Cross-member Radius Drop
* Ladder Rack Accessory Chatsworth 12101-x01 10.25" Wide Cross-member Stringer Radius Drop
* Ladder Rack Chatsworth 10724-x12 12" Wide Inside Radius Bend
![Page 34: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/34.jpg)
University of Connecticut Appendix A
Telecommunications Design Guide & Standards June 2003 8
PATHWAYS & SPACES (Cont.)
Solution Description Manufacturer Part # Detail/Specific Requirements
* Ladder Rack Chatsworth 10822-x12 12" Wide E-Bend
* Ladder Rack Chatsworth 10723-x12 12" Wide Outside Radius Bend
* Relay Rack Corning CDF-ER-7A-19 LANscape Closet Distribution Frame (Requires (2) CDF-ISB-7)
* Vertical Manager Corning CDF-ISB-7 LANscape Interbay Storage
* Power Strip Middle Atlantic PD-915R Rack Power Distribution Panel
* Uninterruptible Power Supply (UPS) APC SU2200RM3U Smart-UPS 2200VA RM 3U 120V
* Uninterruptible Power Supply (UPS) APC SU2200RMXLNET Smart-UPS XL 2200VA RM 5U 120V
* UPS Backplate APC SU029RM3U Backplate for Smart-UPS SU220RM3U (20A Alternate to Standard Plate)
* UPS Backplate APC SU029RM Backplate for Smart-UPS SU2200RMXLNET (20A Alternate to Standard Plate)
* UPS Management Card APC AP9617 SNMP Card with Ethernet Interface
* UPS Management Card APC AP9618 SNMP Card with Ethernet Interface, Environmentals
and Out-of-Band
* UPS Management Card APC AP9619 SNMP Card with Ethernet Interface and Environmentals
SURFACE MOUNT RACEWAY & SPECIALTY PLATES
Solution Description Manufacturer Part # Detail/Specific Requirements
* Raceway Wiremold V700 series Steel Surface Mount (Accommodates up to (4) Cat 5e Cables)
* Raceway Wiremold V4000 series Steel Surface Mount (Accommodates up to (66) Cat 5e Cables)
* Raceway Wiremold ALA4800 series Aluminum Surface Mount (Accommodates up to (62) Cat 5e Cables)
* Raceway Wiremold V4050/G4050 Bracket For Wiremold 4000 Series (Requires CM-EPLA End Plate)
* Raceway Wiremold CM-EPLA End Plate for Wiremold 4000 Series
* Raceway Wiremold S2-EPL End Plate for Wiremold 4000 Series
![Page 35: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/35.jpg)
University of Connecticut Appendix A
Telecommunications Design Guide & Standards June 2003 9
SURFACE MOUNT RACEWAY & SSPECIALTY PLATES (Cont.)
Solution Description Manufacturer Part # Detail/Specific Requirements
* Raceway Wiremold CM-ARA Angled Adapter for Wiremold 4000 Series
Ortronics Raceway Ortronics OR-40300656 Angled Bezel for Wiremold 4000 Series
Ortronics Raceway Wiremold ALA-MABRT Cover Plate for Wiremold 4800 Series (6-port Bezel Included)
Ortronics Raceway Wiremold ALA-ABRT Cover Plate for Wiremold 4800 Series (2-port Bezel Included)
Hubbell Raceway Wiremold ALA-2A Cover Plate for Wiremold 4800 Series
Hubbell Bezel Hubbell HWM2KI10 Bezel for Wiremold 4000 & 4800 Series (Accepts 2 Hubbell HXJ Jacks)
Hubbell Faceplate Wiremold 5507RJ Faceplate for Wiremold 4000 Series (Accepts 2 Hubbell HXJ Jacks)
Hubbell Faceplate Wiremold 5507FRJ Faceplate for Wiremold 4000 Series (Accepts 2 Hubbell HXJ Jacks)
Ortronics Faceplate Wiremold 5507-4TJ Faceplate for Wiremold 4000 Series (Accepts 4 Ortronics TracJack Jacks)
Ortronics Faceplate Wiremold 5507-6TJ Faceplate for Wiremold 4000 Series (Accepts 6 Ortronics TracJack Jacks)
Hubbell Furniture Bezel Hubbell FP2GY Bezel for Steelcase Furniture (Accepts 2 Hubbell HXJ Jacks)
Hubbell Furniture Bezel Hubbell FP4GY Bezel for Steelcase Furniture (Accepts 4 Hubbell HXJ Jacks)
Hubbell Furniture Bezel Hubbell FP4BGY Bezel for Steelcase Furniture (Accepts 4 Hubbell HXJ Jacks)
Ortronics Furniture Bezel Ortronics OR-40300633 Fog White for Steelcase Furniture (Accepts 4 Ortronics TracJack Jacks)
Ortronics Furniture Plate Ortronics OR-40700072 .625" D Modular Furniture Plate
Ortronics Furniture Adapter Ortronics OR-42100009 Adapter for OR-40700072 (Accepts 3 Ortronics TracJacks)
![Page 36: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/36.jpg)
University of Connecticut Appendix B
Telecommunications Design Guide & Standards June 2003 1
Typical TR Layout
Doo
r3'
-0"
X 7
'-0"
Sw
ing
Out
10'-0
"
8'0"
3/4"
ply
woo
d pa
inte
dbo
th s
ides
with
an
intu
mes
cent
pai
nt.
From
floo
r to
8'-0
" A
FF.
Typi
cal o
f all
wal
ls.
120
volt
20 a
mp
"Qua
d"ou
tlet.
Typ
ical
of t
hree
.
(4) 4
" con
duit
slee
ves.
Typi
cal t
o th
ete
leco
mm
unic
atio
ns r
oom
abov
e, b
elow
, and
to th
eca
ble
path
way
s ou
tsid
eth
e ro
om.
Cab
le tr
ay:
A n
etw
ork
of 1
2" la
dder
rack
ing
to c
reat
e a
path
way
from
the
poin
t whe
reth
e ca
bles
ent
er th
e te
leco
mm
unic
atio
ns ro
om to
ove
r the
tele
com
mun
icat
ions
bac
kboa
rds
and
equi
pmen
t rac
ks.
It w
ill b
e se
cure
lyfa
sten
ed to
eac
h w
all a
nd to
the
top
of e
ach
equi
pmen
t rac
k.
Tele
com
mun
icat
ions
Gro
undi
ng B
usba
r
Act
ive
Equ
ipm
ent R
ack
Pas
sive
Equ
ipm
ent R
ack
Futu
reE
quip
men
t Rac
k
Voi
ce R
iser
Term
inat
ion
Fiel
d
Voi
ce H
oriz
onal
Term
inat
ion
Fiel
d
Voi
ce E
quip
men
tTe
rmin
atio
n Fi
eld
HU
SK
Yvi
sion
-Ter
min
atio
nFi
eld
DA
TE
7/11
/200
3
SC
ALE
NTS
TIT
LE
TYP
ICA
L TR
RO
OM
BU
TTE
RFL
Y D
RA
WIN
G
5'-0"
![Page 37: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/37.jpg)
University of Connecticut Appendix C
Telecommunications Design Guide & Standards June 2003 1
Binding Post Information Form
![Page 38: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/38.jpg)
University of Connecticut Appendix D
Telecommunications Design Guide & Standards June 2003 1
LAN Switch Audit Form
![Page 39: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/39.jpg)
University of Connecticut Appendix E
Telecommunications Design Guide & Standards June 2003 1
Typical WAO Configurations
The following diagrams represent the most common configurations for WAO. Other configurations may
be required to meet specific application requirements.
1
10105
1
2
10102
1
2
3
10103
1
2
3
4
10104
1
10101
SMATVONLY
C
Voice/LAN
2Voice/Voice
2
LAN/LAN
Voice/LAN/
SMATV
C
Voice/LAN/LAN
2
Voice/Voice/LAN
2
3 Voice/Voice/Voice
3LAN/LAN/
LAN
Voice/LAN/
Voice/LAN
22
Voice/LAN/LAN/
LAN
3
4LAN/LAN/LAN/LAN
Voice/LAN/LAN/SMATV
C 2
TVSMATVONLY
WallMountVoiceONLY
Note: Eithersymbol is
acceptable
W
UCONN uses colored jacks in addition to location in the faceplate to identify the jack application. A white
jack or jack that matched the faceplate shall be used to identify a voice application and a green jack shall
be used to identify a LAN application. Where applicable, the top position of the faceplate shall be used for
voice, the bottom or middle position for LAN and the bottom position for SMATV video.
Each faceplate shall be identified with a 5-digit label. This format shall identify the room number and the
outlet location within the room. For example: 10102 would be room 101(10102), outlet location 2 (10102).
![Page 40: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/40.jpg)
University of Connecticut Appendix F
Telecommunications Design Guide & Standards June 2003 1
WAO Faceplate Labeling
Work area outlets (WAO) shall be labeled with a 5-digit number. The number shall consist of the 3-digit
room number and the 2-digit faceplate number within the room. WAO shall be numbered starting on the
left when entering a room and continue numbering clockwise around the room. In instances where rooms
are nested within another room and denoted with a letter (see Room 106), drop the letter and continue
numbering with the left most WAO (in the subset room) and continue clockwise until the room, or suite of
rooms, is complete.
Room 102
Room 104Room 106
Room 106BRoom 106A
Room 105Room 103Room 101
Corridor
10201
10602
10603
10605
10604
10607
1060610601
10608
10501
105021030210101
10102 10301
10402
10401
10202
![Page 41: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/41.jpg)
University of Connecticut Appendix G
Telecommunications Design Guide & Standards June 2003 1
TR Termination Labeling
110 Field Terminations Each station label on the 110 wiring block shall
consist of the corresponding 5-digit WAO
faceplate label, followed by the 1-digit port
number. For example, WAO faceplate label
10102, port 1 shall be labeled 101021. Building
services shall be labeled accordingly as "FIRE"
or "ELEV 1", "ELEV 2", etc.
Patch Panel Terminations
Each port on the patch panel shall be labeled on the front with printed labels. Labels on the patch panel
shall consist of the corresponding 5-digit WAO faceplate label, followed by the 1-digit port number. For
example, WAO faceplate label 10102, port 2 shall be labeled 101022. SD
C
OR
TRO
NIC
S
43 44 45 46 47 4837 38 39 40 41 4231 32 33 34 35 3625 26 27 28 29 30
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
AT5e
101012 101022 101023 101032 101033 101034 101041 101042 101051 101052 101053 101061 101062 101063 101064 101073 101083 101084
SMATV Terminations For administrative or academic installations, each
cable for the SMATV system shall be labeled with the
corresponding 5-digit WAO faceplate label and
connected to a wall-mounted F-81. UNIVERSITY ITS
will install a jumper cable from the F-81 to the tap.
In student housing, an additional label tag (Thomas & Betts TY551M) identifying the 3-digit room number
shall be fastened near the VMIU. Where multiple
drops from one apartment are connected to a
splitter, only the cable from the splitter to the VMIU
port shall have the 3-digit room number tag.
110AW4 - 100
101011 101021 101031 101071 101072 101081101082 101091
20101
20101201
![Page 42: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/42.jpg)
University of Connecticut Appendix H
Telecommunications Design Guide & Standards June 2003 1
Typical Rack Elevation for LAN Equipment
SDSD
SD
SD
SD
26 27 28 29 30 31 3225 34 35 36 37 38 39 4033 42 43 44 45 46 47 4841
5 61 2 3 4 7 8 9 10 11 12 13 14 15 16 18 19 20 21 22 23 2417
Ortronics
SD
S D
26 27 28 29 30 31 3225 34 35 36 37 38 39 4033 42 43 44 45 46 47 4841
5 61 2 3 4 7 8 9 10 11 12 13 14 15 16 18 19 20 21 22 23 2417
Ortronics
SD
SD
26 27 28 29 30 31 3225 34 35 36 37 38 39 4033 42 43 44 45 46 47 4841
5 61 2 3 4 7 8 9 10 11 12 13 14 15 16 18 19 20 21 22 23 2417
Ortronics
SD
S D
26 27 28 29 30 31 3225 34 35 36 37 38 39 4033 42 43 44 45 46 47 4841
5 61 2 3 4 7 8 9 10 11 12 13 14 15 16 18 19 20 21 22 23 2417
Ortronics
SD
SD
26 27 28 29 30 31 3225 34 35 36 37 38 39 4033 42 43 44 45 46 47 4841
5 61 2 3 4 7 8 9 10 11 12 13 14 15 16 18 19 20 21 22 23 2417
Ortronics
SD
S D
26 27 28 29 30 31 3225 34 35 36 37 38 39 4033 42 43 44 45 46 47 4841
5 61 2 3 4 7 8 9 10 11 12 13 14 15 16 18 19 20 21 22 23 2417
Ortronics
SD
SD
A B C D E F G H J K L M
SD
1
2
3
4
5
6
SIECOR
SD
1
2
3
4
5
6
SIECOR
SD
1
2
3
4
5
6
SIECOR
SD
1
2
3
4
5
6
SIECOR
SD
1
2
3
4
5
6
SIECOR
SD
1
2
3
4
5
6
SIECOR
SD
1
2
3
4
5
6
SIEC OR
S D
1
2
3
4
5
6
SIECOR
S D
1
2
3
4
5
6
SIECOR
SD
1
2
3
4
5
6
SIECOR
SD
1
2
3
4
5
6
SIEC OR
SD
1
2
3
4
5
6
SIECOR
SDS D
SD
Smart-UPS
2 2 0 0
Test
AMERICAN POW ER CONVERSION
SD
SD
SD
SD
SD
SD
SD
SD
S D
Passive Active
19" Relay Rack
48-PortPatch Panel
Rack Mount UPS
Ethernet Switch
Horizontal WireManagement
Rack MountSurge Protector
EthernetDistribution
Switch
Fiber PanelHousing
Horizontal WireManagement
Optical FiberManagement
Vertical WireManagement
19" Relay Rack
Active
![Page 43: Design Guide & Standards June 2003](https://reader033.vdocument.in/reader033/viewer/2022042101/625653afebf4dd3b50225e1f/html5/thumbnails/43.jpg)
University of Connecticut Appendix I
Telecommunications Design Guide & Standards June 2003 1
Typical Logical LAN Diagram
SY ST RP S
STRT DUPLXSPEEDUTIL
MODE
Catalyst 2950SERI ES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
SY ST RP S
STRT DUPLXSPEEDUTIL
MODE
Catalyst 2950SERI ES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
SY ST RP S
STRT DUPLXSPEEDUTIL
MODE
Catalyst 2950SERI ES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
SY ST RP S
STRT DUPLXSPEEDUTIL
MODE
Catalyst 2950SERI ES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
TR #3Edge Switch Stack
S YST RPS
STRT DUPLXSPEE DUTIL
MODE
Catalyst 2950SE RIES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
S YST RPS
STRT DUPLXSPEE DUTIL
MODE
Catalyst 2950SE RIES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
S YST RPS
STRT DUPLXSPEE DUTIL
MODE
Catalyst 2950SE RIES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
S YST RPS
STRT DUPLXSPEE DUTIL
MODE
Catalyst 2950SE RIES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
TR #2Edge Switch Stack
SY ST RP S
STRT DUPLXSPEEDUTIL
MODE
Catalyst 2950SERI ES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
SY ST RP S
STRT DUPLXSPEEDUTIL
MODE
Catalyst 2950SERI ES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
SY ST RP S
STRT DUPLXSPEEDUTIL
MODE
Catalyst 2950SERI ES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
TR #1Edge Switch Stack
TX GBIC
Mul
timod
e Fi
ber
SX
GB
ICTX GBIC
TX GBIC
Aggregate
UPS
TX GBIC
TX GBIC
TX GBIC
TX GBIC
TX GBIC
TX GBIC
Singlmode FiberLX GBIC
SYS T RPS
STRT DUPLXSPEEDUTIL
MODE
Catalyst 2950SERI ES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
4 3
4 4
45
46
47
48
2
1
SYS T RPS
STRT DUPLXSPEEDUTIL
MODE
Catalyst 2950SERI ES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
4 3
4 4
45
46
47
48
2
1
SYS T RPS
STRT DUPLXSPEEDUTIL
MODE
Catalyst 2950SERI ES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
4 3
4 4
45
46
47
48
2
1
TREdge Switch Stack
TX GBIC
TX GBIC
TX GBIC
Sin
glem
ode
Fibe
rLX
GB
IC
(1) Building withMultiple TRs
(1) Building with(1) TR
Aggregate
UPS
POWERFAULT DATA ALARMRPS
TRAggregate Switch
(1) Building ServingMultiple Buildings
Sin
glem
ode
Fib
erLX
GB
IC
Sin
glem
ode
Fibe
rLX
GB
IC
S D
S m a rt -U P S
1 4 0 0
T es t
A M ER I CA N PO W E R CO N VE R SIO N
2
1
4
3
6
5
8
7
10
9
UTILSTAT
DUPLXSPEE D
SY STEMRPS
MODE11 12
CA TALYST 3550
S D
S m a rt- U P S
1 4 0 0
Te s t
AM E RI CA N P O W E R C O N VE RSI O N
2
1
4
3
6
5
8
7
10
9
UTILSTAT
DUPLXSPEE D
SY STEMRPS
MODE 11 12
CA TALYST 3550
SY ST RP S
STRT DUPLXSPEEDUTIL
MODE
Catalyst 2950SERI ES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
43
44
45
46
47
48
2
1
SYS T RPS
STRT DUPLXSPEEDUTIL
MODE
Catalyst 2950SERI ES3
4
5
6
7
8
9
10
1
2
11
12
13
14
15
16
19
20
21
22
23
24
25
26
17
18
27
28
29
30
31
32
35
36
37
38
39
40
41
42
33
34
4 3
4 4
45
46
47
48
2
1
UConn LAN Core