Kirk Mescher, PE, LEED® AP
Design of Commercial Ground Source Heat Pumps
1
- and - Lisa Meline, PE, LEED® AP
![Page 2: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/2.jpg)
Kirk Mescher, PE, LEED® AP
Steps to Improving Ground Source Design
![Page 3: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/3.jpg)
Learning Objectives
• What documents are required to effectively communicate a ground source system design?
• Energy simulations • Ground Loop 101 • What makes water source heat pump installations
unique? • What makes a good ground source installation?
3
![Page 4: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/4.jpg)
Seminar Scope Limitation • Today’s Seminar will concentrate on:
– Design considerations for vertical ground loop heat exchanger systems
– The design will be applicable to horizontal bore systems, surface water systems and open loop systems
– We will not discuss, other than to introduce, the concept of a standing column system
4 4
![Page 5: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/5.jpg)
Some Background
• Vocabulary • Codes and Standards • References
5 5
![Page 6: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/6.jpg)
ASHRAE HVAC Applications Handbook Chapter 34 Geothermal resources classification by temperature: High Temperature t > 150 C (300 F) Intermediate Temperature 90 C (195 F) < t < 150C (300 F) Low Temperature t < 90 C (195 F) • Direct Use • Ground-Coupling
6
![Page 7: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/7.jpg)
Vocabulary
• Ground Source, Geo-Exchange, Ground Coupled – A heating and cooling system that uses the ground as a moderator. The ground acts as a heat sink for heating and cooling energy.
• Geothermal – A heating system that typically uses “hot rocks” or a high temperature aquifer for direct heating or energy production.
• Central Plant – A heating and/or cooling system where multiple facilities are tied together such that the single plant can produce the necessary energy or resource.
7
![Page 8: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/8.jpg)
Vocabulary
• Well – A water-producing bore typically with a submersible pump.
• Bore – An approximately 15 cm (6 in.) hole drilled into the geological formation.
• Borehole, U-loop Heat Exchanger, etc. – A typically vertical u-loop pipe (or ground probe) placed into a bore and grouted into position.
• Bore Field – Accumulation bores designed to be connected with header piping to support a ground source heating and cooling system.
8
![Page 9: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/9.jpg)
Vocabulary
• GCHP – Ground Coupled Heat Pump • EER – Energy Efficiency Ratio • SEER – Seasonal Energy Efficiency Ratio
– Does NOT apply to GCHP
• COP – Coefficient of Performance
9
When making comparisons, be sure you are comparing equal terms. These terms can be applied to equipment or SYSTEMS. It is best to compare SYSTEM performance.
WARNING>>>>>>>WARNING>>>>>>WARNING>>>>>>WARNING>>>>>>
9
![Page 10: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/10.jpg)
Codes and Standards (US) • International Mechanical Code
– Chapter 12
• IGSHPA - Closed-Loop/Geothermal Heat Pump Systems - Design and Installation Standards
• ASHRAE Standard 90.1 – Variable flow requirements – Isolation valves
• CSA C448 - Design and Installation of Earth Energy Systems
10 10
![Page 11: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/11.jpg)
Getting Started:
• References – ASHRAE CHAPTER 34 – HVAC
Applications Volume – ASHRAE TC 6.8 Geothermal Heat Pump
and Energy Recovery Applications – Various Journal articles
• Attend seminars like this
11
![Page 12: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/12.jpg)
12
Recommended ASHRAE Design Guide for Commercial and Institutional Buildings
![Page 13: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/13.jpg)
Ground Source
• What is it? – Efficient system connected with the
ground? • Heat recovery system?
– Recover energy from season to season?
13 13
![Page 14: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/14.jpg)
Are Ground Source Systems a Renewable Energy Source?
14
![Page 15: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/15.jpg)
The earth absorbs nearly half of the sun’s energy.
Ground Source Energy
15
![Page 16: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/16.jpg)
Energy Efficient Heating: Coefficient of Performance
or building
16
![Page 17: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/17.jpg)
What is a Geo-Exchange Heating and Cooling System?
17
KEY: Ground Coupled heat exchanger Piping Network Pumps Water source heat pumps Controls
VFD
PD
T
17
![Page 18: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/18.jpg)
18
How Geo-Exchange Works
Thermal Conductivity
Bore field acts as a battery, storing heating energy in the summer and releasing it in the winter
Geothermal Bore Field
18
![Page 19: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/19.jpg)
19
Real-World Loading
Heat in bore field is likely to increase
Cooling Energy >> Heating Energy
Geothermal Bore Field
19
![Page 20: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/20.jpg)
20
Hybrid Geo-Exchange Systems
Cooling Dominated
FLUID COOLER
Excess Heat
20
![Page 21: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/21.jpg)
Ever see this?
Is this sufficient to define the System requirements?
21
![Page 22: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/22.jpg)
System Definition Requirements • Design parameters
– Flow – Pressure loss – Water quality and
volume – Antifreeze solution and
volume, if required
• Header pipe definition – Material – Diameter – Pressure class rating – Circuit isolation
requirements – Flush/purge provisions
22
![Page 23: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/23.jpg)
System Definition Requirements • Vertical bore definition
– Drilling technique if available – Casing requirements, if any – Bore depth and approximate bore
diameter – Grout Definition
• Thermal Conductivity • Placement method
• Equipment specification – Airflow and pressure drop – Heating and cooling capacity – EER and COP – Water flow and pressure drop – Electrical characteristics – Air filtration specification
23
![Page 24: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/24.jpg)
System Definition Requirements • Inside Building
– Piping specification – Pumping system – Control Specification – System diagram
• Air separation • Compression • Make-up
• Commissioning – Piping installation
inspections and testing
– Purge volume and flow
– Purge procedure – System start-up
procedure – Start-up
documentation
24
![Page 25: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/25.jpg)
Key to Good System Design
A. Is ground source a proper selection?
B. Interior Design C. Physical Constraints of the Ground D. System Integration
25
![Page 26: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/26.jpg)
Developing 12-Steps
A. Proper selection 1. Calculate peak and OFF-peak loads 2. Estimate energy to and from the bore field
B. Interior Design 3. Select operating temperatures 4. Correct heat pump operation for actual conditions 5. Select HPs for peak load (heating or cooling) and
minimize duct runs 6. Arrange HPs into building circuits
26
![Page 27: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/27.jpg)
Developing 12-Steps C. Physical Constraints of the Ground
7. Conduct investigation for thermal properties and drilling conditions
8. Determine ground heat exchanger arrangement 9. Calculate optimum ground heat exchanger
dimensions
D. System Integration 10. Iterate to determine optimum operating
temperatures, flows, materials 11. Layout Interior piping for minimum head loss 12. Select pumps and control methodology
![Page 28: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/28.jpg)
Is Ground Source A Proper Selection?
A 28
![Page 29: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/29.jpg)
Ground Source “The Efficiency Silver Bullet”
• The most efficient HVAC system there is!!!
• It works everywhere!!! • XXX m/kW (xx ft/ton) is adequate
everywhere!!!
29
![Page 30: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/30.jpg)
Applicability • Depends on:
– Building energy balance – Undisturbed ground temps – Site characteristics
• Is there a hybrid design opportunity? – High heating and low cooling demand – High cooling with low heating demand
30
A
![Page 31: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/31.jpg)
Preliminary Ground Source Sizing
• Building energy estimate • Idea of how the building will operate • Drilling requirements • Some reference of ground thermal
conductivity and thermal diffusivity
31
A
31
![Page 32: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/32.jpg)
Preliminary Estimates
• Don’t use ‘Rules of Dumb’ • Perform the Calculations!
– Bin data or 8760 hour simulation to understand the energy coming into the facility and going out
32
A
![Page 33: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/33.jpg)
Energy Estimates
Building Name Winnebago School Location Rockford IL 10 MonthBuilding Area 40,000 SQ. FT. Occupancy 400 Persons
COOLING 91 TONS Minimum Ventilation 0.05 cfm/sq. ft.HEAT 800.9 MBTUH min vent 2000 cfm
Occupancy Ventilation 12 CFM/personSummer design temp 75 F Setback 78 F occupant vent 4800 cfm
Wetbulb 63 F Total Ventilation 6800 cfmRel Humidity 51.6 % RH
Specific Humidity 66.8 Grains Lighting 1 W/ft 2̂Summer Design enthalpy 28.4 BTU/# Power 0.3 w/ft 2̂
Days /Week 5WinterDesign Temp 70 F Setback 68 F Occupied 55 Hrs/week
Wet Bulb 54 F Building UA 4739 Btuh/FRel Humidity 33.6 % RH
Specific Humidity 36.5 Grains FUEL COST 5.42 $/mcfWinter Design enthalpy 22.5 BTU/# 154.1140142 Fuel Efficiency 0.8
Ele rate 0.1 $/kwhEconomizer 0 (1-yes, 0-no)
Humidification 0 (1-yes, 0-no) CALCULATION OF BUILDING UAERU 0 (1-yes, 0-no) # of Floors 1
ERU Efficiency 0.7 (0-1.00) Roof Area 40000 2667
33
A
![Page 34: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/34.jpg)
Calculate Peak and Off-Peak Loads
1
34
![Page 35: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/35.jpg)
Building Name Winnebago School Location Rockford IL 10 MonthBuilding Area 40000 SQ. FT.
COOLING 91 TONSHEAT 800.9 MBTUH
COOLING LOAD 995.2 MBTUH HEATING LOAD -717.0 MBTUHCOOLING ENERGY 349528 KBTU HEATING ENERGY -1073139 KBTU
FLCH 319 FLHH 1340 539-12 930 9-12 -8011-4 1095 1-4 -7365-8 371 5-8 -6688-8 221 8-8 -658
tons 91 438 sq ft/ton BTUH/FT^2 20.02ton hours 29127 ton hours 71543
Calculation of Peak and Off-Peak Loads
35
1
![Page 36: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/36.jpg)
Annual Energy Usage Building Name Belvidere Washington Scho Location Chicago DataBuilding Area 96370 SQ. FT.
COOLING 138 TONSHEAT 1531.7 MBTUH
Base Electrical Usage
Lights and Other Electrical Usage 427208.21 KwhAnnual Energy $ 27768.534
$0.29 $/ft^2
Geothermal One Pipe System Output Kbtu/sq. ft./yr24.53
HVAC Energy Use 265435.6 KWH $17,253.32
$0.18 $/ft^2Other Energy Use $0.29 $/ft^2 System EER 13.89
$0.47 $/ft^2 System COP 3.84
SYSTEM HEATING AND COOLING EFFICIENCY AFFECTS PERFORMANCE, DESIGN AND SIZING
36
1
![Page 37: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/37.jpg)
Estimate Energy To and From the Bore Field
2
37
![Page 38: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/38.jpg)
Remember from the Introduction…
Thermal Conductivity
Bore field acts as a battery, storing heating energy in the summer and releasing it in the winter
Ground Source Bore Field
2
38
![Page 39: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/39.jpg)
Building uses more energy for cooling than for heating
Seasonal Energy Usage
Seasonally Stored Energy for Cooling
Seasonally Stored Energy for Heating
2
39
![Page 40: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/40.jpg)
10-Month School In Colder Climate
2
40
![Page 41: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/41.jpg)
Loop Sizing Inputs
Energy Pulses Building Name Winnebago School Location Rockford IL 10 MonthBuilding Area 40000 SQ. FT.
COOLING 91 TONSHEAT 800.9 MBTUH
COOLING LOAD 995.2 MBTUH HEATING LOAD -717.0 MBTUHCOOLING ENERGY 349528 KBTU HEATING ENERGY -1073139 KBTU
FLCH 319 FLHH 1340 539-12 930 9-12 -8011-4 1095 1-4 -7365-8 371 5-8 -6688-8 221 8-8 -658
tons 91 438 sq ft/ton BTUH/FT^2 20.02ton hours 29127 ton hours 71543
41
2
![Page 42: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/42.jpg)
Interior Design
B 42
![Page 43: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/43.jpg)
Heat Pumps
43
![Page 44: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/44.jpg)
Effect of Temperature Control on Performance
44
VFD
PD
T T
System EER
0
5
10
15
20
25
30
30 40 50 60 70 80 90 100 110 120 TEMP (F)
EER
2
2.5
3
3.5
4
4.5
5
5.5
6
6.5
7
CO
P
UNIT EER Variable Flow EER UNIT COP Variable Flow COP
![Page 45: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/45.jpg)
Water Source Heat Pumps (Self-Contained Approach)
• Many consider: Traditional Equipment • Horizontal Units • Vertical Units • Water to Water • Console Units
45
![Page 46: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/46.jpg)
Water Source HP’s, Traditionally
– “100’s of noisy boxes” above the ceiling – “Require” cooling towers or boilers “to work right” – 2-pipe controlled water distribution
• Water flow control • Motorized isolation valves • Variable speed drives
– Have maintenance issues • Low flow at the end of the distribution • Low temp difference
46
![Page 47: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/47.jpg)
New Paradigm • Many different heat pump systems
• When properly designed and implemented, ground loops can provide all system heat rejection and heat addition
• Water distribution – Traditional 2-pipe variable capacity – Individual circulations – Circulators with central pumps – One pipe
• Lower maintenance costs – Simpler distribution – Managing flow to the units
47
![Page 48: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/48.jpg)
Heat Exchanger Configurations
Courtesy Water Furnace
Open Loop Surface Water
Horizontal Bore Vertical Bore
48
![Page 49: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/49.jpg)
Improving System Design: Simplicity
49
Everything should be made as simple as possible, but not simpler. ~Albert Einstein
![Page 50: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/50.jpg)
Why Simple?
• Complexity adds $; does it add value?
– How many control points do we need? – Does variable speed pumping add enough
value? – Do we require digital control?
• Why ask the question – It’s $ – Maintenance – Operation – Installation
![Page 51: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/51.jpg)
Select Preliminary Loop Operating Temperatures
and Flow Rate
3
51
![Page 52: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/52.jpg)
Selecting Operating Temperatures • A good starting point
– Undisturbed ground temp • Cooling 10-20ºC (20-35ºF) Above • Heating 5-10ºC (10-15ºF) Below
• Generally, max cooling inlet temps should be below 32.2ºC (90ºF)
• Generally, min heating above 0ºC (Use 7-8ºC to start)
• Final selection based on energy balance • It’s ALL about SYSTEM EER and COP
3
52
![Page 53: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/53.jpg)
Correct Heat Pump Operation for
Actual Conditions
4
53
![Page 54: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/54.jpg)
HP Performance Ratings
• AHRI/ISO/ASHRAE/ANSI 13256-1 - Water-source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps
• EN 14825 - Air Conditioners, Liquid chilling packages and heat pumps, with electrically driven compressors, for space heating and cooling – Testing and rating at part-load conditions and calculations of seasonal performance
54
![Page 55: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/55.jpg)
55
Why Adjust Unit Capacity?
• Under ISO 13256-1 – What is the system fan static pressure for
rating? – What is the pumping energy based upon?
• What are the entering water and air conditions?
4
55
![Page 56: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/56.jpg)
56
Adjusting Unit Capacity • ISO 13256-1
– 0 kPa static pressure – 25ºC (77ºF EWTc) / 0ºC (32ºF) EWTh – 19ºC (66.2ºF) EWB Cooling – 20ºC (68ºF) EDB Heating – Pumping power is included
Some manufacturer’s programs properly adjust the capacity based on your operating conditions, some do not. The point is, capacity adjustment is required to properly select the required equipment.
4
56
![Page 57: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/57.jpg)
57
1 3 2
Heat Pump Ratings
![Page 58: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/58.jpg)
Select HPs for Peak Load (Heating or Cooling) and
Minimize Duct Runs
5
58
![Page 59: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/59.jpg)
Schedule HP Equipment
59
5
59
HEAT PUMP UNIT SCHEDULCOOLING HEATING WATER H.P. PUMP
S.A. ESP CAPACITY (BTH) EWT EER CAP. TOTAL EWT COP FLOW WPD HEAD (CFM) (IN W.C.) TOTAL SENSIBLE (° F) (BTH) (°F) (GPM) (FT) (FT)
1,050 0.35 30.1 20.4 90 12.9 26.7 40 3.7 7.5 16.2 24.2 1,050 0.35 30.1 20.4 90 12.9 26.7 40 3.7 7.5 16.2 24.2 1,050 0.35 30.1 20.4 90 12.9 26.7 40 3.7 7.5 16.2 24.2 900 0.55 25.7 16.7 90 14.1 22.7 40 3.6 7.4 14.7 22.7 900 0.55 25.7 16.7 90 14.1 22.7 40 3.6 7.4 14.7 22.7 1,050 0.35 30.1 20.4 90 12.9 26.7 40 3.7 7.5 16.2 24.2 1,050 0.35 30.1 20.4 90 12.9 26.7 40 3.7 7.5 16.2 24.2 1,050 0.35 30.1 20.4 90 12.9 26.7 40 3.7 7.5 16.2 24.2 1,050 0.35 30.1 20.4 90 12.9 26.7 40 3.7 7.5 16.2 24.2 1,830 0.80 62.6 46.1 90 16.1 54.1 40 3.8 12.5 7.4 15.4 1,830 0.80 62.6 46.1 90 16.1 54.1 40 3.8 12.5 7.4 15.4 1,050 0.35 30.1 20.4 90 12.9 26.7 40 3.7 7.5 16.2 24.2 3,440 0.50 113.6 79.1 90 13.3 109.3 40 3.8 25.0 15.0 23.0 3,440 0.50 113.6 79.1 90 13.3 109.3 40 3.8 25.0 15.0 23.0
![Page 60: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/60.jpg)
Arrange HPs into Building Circuits
6
60
![Page 61: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/61.jpg)
Physical Constraints of the Ground
C 61
![Page 62: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/62.jpg)
Conduct Investigation for Thermal Properties and
Drilling Conditions
7
62
![Page 63: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/63.jpg)
• Thermal Conductivity • Deep Earth Temperature • Thermal Diffusivity
Thermal Properties for Design
![Page 64: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/64.jpg)
Thermal Conductivity Testing
y = 5.1007Ln(x) + 64.27R2 = 0.9806
0
10
20
30
40
50
60
70
80
90
0 5 10 15 20 25 30 35 40 45 50
GPMtemp intemp outaverage TempLog. (average Temp)
Time Period Slope Average He (Btu/hr-ft) at Input (W/ft) Thermal Conductivity (Btu/hr-ft-°F)
10—44 4.3 72.5 21.25 1.34
The purpose of the test is to determine the physical properties of the ground surrounding the bore hole. This will be explained in further detail in Module 2.
7
64
![Page 65: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/65.jpg)
Determine Ground Heat Exchanger (GLHX)
Arrangement
8
65
![Page 66: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/66.jpg)
Heat Exchanger Configurations
Courtesy Water Furnace
Open Loop Surface Water
Horizontal Bore Vertical Bore
66
![Page 67: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/67.jpg)
Typical Bore Detail 9
67
100m
1.2m
(1) U PE100 PN 16
1.9
![Page 68: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/68.jpg)
Calculate GLHX Requirements
9
68
![Page 69: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/69.jpg)
Output from Loop Sizing Routine
9
69
![Page 70: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/70.jpg)
Headers
![Page 71: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/71.jpg)
Basic Header Types • None
– Loop connected directly to equipment
• Close Coupled – U-loops connected to end of the pipe
• Vaults – Reverse return circuits connected to headers in valve vaults
• Reverse Return – Header piping connected to circuits with reverse return piping
and underground valves
• Direct Return – Header piping connected to circuits with direct return piping and
underground valves
71
![Page 72: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/72.jpg)
Close Coupled
72
![Page 73: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/73.jpg)
Vaults
![Page 74: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/74.jpg)
Inexperienced design keys
74
Trenching shown on both sides of the string of bores
Balance is affected by lack of reverse return
Cross trenching, direct supply and return Fix the balance issue by adding valves
![Page 75: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/75.jpg)
Reverse Return
• Circuits are generally pressure balanced throughout the system
• First supplied is last returned
• Each bore sees the same length of piping material
Reverse Return
75
![Page 76: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/76.jpg)
Direct Return
• The U-loops are in control of the pressure loss throughout the system
• The valve authority of the U-loop control flow
Direct Return
76
![Page 77: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/77.jpg)
Vault
Header Configurations Reverse Return
Direct Return
77
![Page 78: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/78.jpg)
Header Configurations
Circuit pressure loss >80% of overall PD = balanced flow
78
![Page 79: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/79.jpg)
Bore Field Don’ts PVC or Copper
Bentonite Grout
•---- use vaults •---- require cross-trenching •---- use pure Bentonite grout •---- put bores any closer than 20 ft (6.1m) OC. •---- put flow controls on loops
79
![Page 80: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/80.jpg)
Ground Loop Supplement
HDPE SDR 11 UNI-LOOP
Thermally enhanced grout
Total Field Pressure Loss 20 ft H20 (60 kPa)
20 ft (6.1m) MIN Connecting Piping DR 15.5 HDPE
Bore Field and Building Purge Assembly
Use good design practices for header design Close coupled Reverse return Direct return with knowledge of U-loop flow control
80
![Page 81: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/81.jpg)
System Integration
D 81
![Page 82: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/82.jpg)
Iterate to Optimize GLHX 1- Balancing length with operating Temperatures 2- Changing to Different Equipment 3- Balancing with Different Equipment
10
82
![Page 83: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/83.jpg)
Layout Interior Piping for Minimum Head Loss
11
83
![Page 84: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/84.jpg)
System Layouts
• Direct Flow – With 3-way control – With 3-way control and VFD – With secondary geo pump – Without loop temp control
• Reverse Return – With 3-way valve control – With secondary geo pump – Without loop temp control
84
![Page 85: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/85.jpg)
Direct Flow with 3-Way Control
Attributes Control of water temp Summer and Winter 30/7 Demand Fluid Control Flow Balance managed by
Regulator Valves Challenges System changes with each device added or subtracted from duty Pipe Length/pressure loss Control valve pressure loss/authority Heat/cool energy exchange at
bore field Central pump must be sized
for connected load Last Heat Pump can be short of water flow
T T
85
![Page 86: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/86.jpg)
86
Please do your own pump
pressure drop calculations!!!
![Page 87: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/87.jpg)
Select Pumps and Control Method,
Determine System Efficiency
12
87
But more about this in Module 3…
![Page 88: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/88.jpg)
Direct Flow without Loop Temp Control
Attributes Heat Pump flow managed by regulator valves Demand Fluid Control Flow Regulator volume control
Challenges System changes manages with flow regulators Pipe Length/ pressure loss Heat/cool energy exchange at bore field Last heat pump can be short of water flow Central pump must be sized for connected load
VFD
PD
88
![Page 89: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/89.jpg)
Reverse Return without Loop Temp Control
Attributes Demand Fluid Control Flow regulator volume control Equal pipe length to each heat pump
Challenges System changes managed with flow regulator valves Pipe Length/ pressure loss Heat/cool energy exchange at bore field Central Pump must be sized for connected load
VFD
PD
89
![Page 90: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/90.jpg)
One-Pipe Loop Distributed Primary Secondary Loop
Attributes Demand Fluid Control Secondary pump flow control Little loop temp control Unit by unit diversity No flow regulators Low system pump head Primary pump can be sized for BLOCK load conditions No drive/pump/static control head inefficiency
Challenges Temperature control Pipe Length/pressure loss Last heat pump will have warmer/cooler water
sequencer
T
90
![Page 91: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/91.jpg)
“Heat Recovery, Anyone????”
sequencer
T
Attribute
One-pipe loop allows heat pumps to recover energy from the other units in the system.
Cooling units add heat to the loop, heating units extract heat…
It doesn’t take VRF to have heat recovery.
91
![Page 92: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/92.jpg)
Piping Diagrams
Heat pump
M
FCV
GEO HEAT PUMPTraditional 2-pipe arrangement
1-pipe arrangement
92
![Page 93: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/93.jpg)
Parallel Pump Curve Parallel pump operating point 2.3 kW (8.1 Wm/kWt)
Individual pump operating point 1.3 kW (4.5 Wm/kWt)
Single pump and parallel pump operation allow for greatly reduced pump horsepower usage during normal operation. No speed control is required.
757 lpm @ 12.2m Parallel pumps 625 lpm @ 8.2m Single pump
93
![Page 94: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/94.jpg)
Case Study:
MEM Independence
94
![Page 95: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/95.jpg)
Case Study: MEM Independence
• Missouri Employers Mutual • Independence, Missouri • 557 m2 office facility renovated from
rooftop A/C to Ground Source • First 2 years of results – Less than
impressive $600 per year in additional operating cost.
95
![Page 96: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/96.jpg)
96
![Page 97: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/97.jpg)
Original Pumping Strategy • Continuous pumping through all heat
pumps
97
![Page 98: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/98.jpg)
Building Energy Consumption
y = -8.214ln(x) + 66.64
0
5
10
15
20
25
30
35
40
0 100 200 300 400 500 600 700 800 900 1000
BEFORE NOVEMBER 2011
98
![Page 99: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/99.jpg)
As Designed
IHCL-1
6400/12100 BTU/H2.5 GPM
39.9°F94.7°F
45°F85°F
IHCL-2
25700/48300 BTU/H9 GPM
39.3°F95.8°F
45°F85°F
IHCL-3
50000/93900 BTU/H16 GPM
38.8°F96.8°F
45°F85°F
IHCL-4
17100/32200 BTU/H5 GPM
38.2°F97.9°F
45°F85°F
IHCL-5
25700/48300 BTU/H9 GPM
39.3°F95.8°F
45°F85°F
IHCL-6
34300/64400 BTU/H12 GPM
39.3°F95.8°F
45°F85°F
IHCL-7
30000/56300 BTU/H9 GPM
38.4°F97.6°F
45°F85°F
P-1
62.5 GPM71.1/70.5 FT
P-2
62.5 GPM71.1/70.5 FT
AS-1
AV-1
HSS-1
189300/355400 BTU/H62.5 GPM
39°F96.4°F
45°F85°F
ET-1
7.3 GAL
V-1
BV-IHCL -1
STR-1V-2
V-3
BV-IHCL -2
STR-2V-4
V-5
BV-IHCL -3
STR-3V-6
V-7
BV-IHCL-4
STR-4V-8
V-9
BV-IHCL-5
STR-5V-10
V-11
BV-IHCL -6
STR-6V-12
V-13
BV-IHCL-7
ST R-7V-14
2.5"
2.5"2.5"
2.5"
1.25"1.25"
2.5"
2"1"1"
1"
2"1.25"
1.25"1.25"
1.25"
2"
2.5"
99
![Page 100: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/100.jpg)
Solutions?
• What will make the system operate more efficiently? – Distributed pumping? – ASHRAE 90.1 variable flow solution? – One-pipe solution? – Something different?
IHCL-1
6400/12100 BTU/H2.5 GPM
39.9°F94.7°F
45°F85°F
IHCL-2
25700/48300 BTU/H9 GPM
39.3°F95.8°F
45°F85°F
IHCL-3
50000/93900 BTU/H16 GPM
38.8°F96.8°F
45°F85°F
IHCL-4
17100/32200 BTU/H5 GPM
38.2°F97.9°F
45°F85°F
IHCL-5
25700/48300 BTU/H9 GPM
39.3°F95.8°F
45°F85°F
IHCL-6
34300/64400 BTU/H12 GPM
39.3°F95.8°F
45°F85°F
IHCL-7
30000/56300 BTU/H9 GPM
38.4°F97.6°F
45°F85°F
P-1
62.5 GPM71.1/70.5 FT
P-2
62.5 GPM71.1/70.5 FT
AS-1
AV-1
HSS-1
189300/355400 BTU/H62.5 GPM
39°F96.4°F
45°F85°F
ET-1
7.3 GAL
V-1
BV-IHCL -1
STR-1V-2
V-3
BV-IHCL -2
STR-2V-4
V-5
BV-IHCL -3
STR-3V-6
V-7
BV-IHCL-4
STR-4V-8
V-9
BV-IHCL-5
STR-5V-10
V-11
BV-IHCL -6
STR-6V-12
V-13
BV-IHCL-7
ST R-7V-14
2.5"
2.5"2.5"
2.5"
1.25"1.25"
2.5"
2"1"1"
1"
2"1.25"
1.25"1.25"
1.25"
2"
2.5"
100
![Page 101: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/101.jpg)
Solution Considerations: Distributed Pumping
IHCL-8
6400/12100 BTU/H2.5 GPM
39.9°F94.7°F
45°F85°F
IHCL-9
25700/48300 BTU/H9 GPM
39.3°F95.8°F
45°F85°F
IHCL-10
50000/93900 BTU/H16 GPM
38.8°F96.8°F
45°F85°F
IHCL-11
17100/32200 BTU/H5 GPM
38.2°F97.9°F
45°F85°F
IHCL-12
25700/48300 BTU/H9 GPM
39.3°F95.8°F
45°F85°F
IHCL-13
34300/64400 BTU/H12 GPM
39.3°F95.8°F
45°F85°F
IHCL-14
30000/56300 BTU/H9 GPM
38.4°F97.6°F
45°F85°F
AS-2
AV-2
HSS-2
189300/355400 BTU/H62.5 GPM
39°F96.4°F
45°F85°F
ET-2
8 GAL
V-15
STR-8V-16
V-17
STR-9V-18
V-19
ST R-10V-20
V-21
STR-11
STR-12V-22
V-23
STR-13V-24
V-25
STR-14V-26
2.5 GPM13.3 FTP-3
9 GPM12.4 FT
P-4
16 GPM20.9 FTP-5
5 GPM10.5 FTP-6
9 GPM12.4 FTP-7
12 GPM16.2 FT
P-8
9 GPM11.7 FTP-9
2.5 GPM33.9/33.3 FT
P-10
9 GPM33.9/33.3 FTP-11
16 GPM33.9/33.3 FT
P-12
5 GPM33.9/33.3 FT
P-13
9 GPM33.9/33.3 FT
P-14
12 GPM33.9/33.3 FTP-15
9 GPM33.9/33.3 FT
P-16
V-27
V-28
2.5"
2.5"
2.5"
2"
2"
1.25"
2"
2.5"
101
![Page 102: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/102.jpg)
Solution Considerations: ASHRAE 90.1
IHCL-1
6400/12100 BTU/H2.5 GPM
39.9°F94.7°F
45°F85°F
IHCL-2
25700/48300 BTU/H9 GPM
39.3°F95.8°F
45°F85°F
IHCL-3
50000/93900 BTU/H16 GPM
38.8°F96.8°F
45°F85°F
IHCL-4
17100/32200 BTU/H5 GPM
38.2°F97.9°F
45°F85°F
IHCL-5
25700/48300 BTU/H9 GPM
39.3°F95.8°F
45°F85°F
IHCL-6
34300/64400 BTU/H12 GPM
39.3°F95.8°F
45°F85°F
IHCL-7
30000/56300 BTU/H9 GPM
38.4°F97.6°F
45°F85°F
P-1
62.5 GPM71.1/70.5 FT
P-2
62.5 GPM71.1/70.5 FT
AS-1
AV-1
HSS-1
189300/355400 BTU/H62.5 GPM
39°F96.4°F
45°F85°F
ET-1
7.3 GAL
V-1
BV-IHCL -1
STR-1V-2
V-3
BV-IHCL -2
STR-2V-4
V-5
BV-IHCL -3
STR-3V-6
V-7
BV-IHCL-4
STR-4V-8
V-9
BV-IHCL-5
STR-5V-10
V-11
BV-IHCL -6
STR-6V-12
V-13
BV-IHCL-7
ST R-7V-14
2.5"
2.5"2.5"
2.5"
1.25"1.25"
2.5"
2"1"1"
1"
2"1.25"
1.25"1.25"
1.25"
2"
2.5"
Install motorized isolation valves and variable speed primary pumps
102
![Page 103: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/103.jpg)
Solution Considerations: One-Pipe Solution
IHCL-22
6400/12100 BTU/H2.5 GPM
39.9°F94.7°F
45°F85°F
IHCL-23
25700/48300 BTU/H9 GPM
39.1°F96.2°F
44.8°F85.4°F
IHCL-24
50000/93900 BTU/H16 GPM
37.8°F98.7°F
44°F86.9°F
IHCL-25
17100/32200 BTU/H5 GPM
35.6°F102.9°F
42.4°F90°F
IHCL-26
25700/48300 BTU/H9 GPM
36.2°F101.8°F
41.8°F91°F
IHCL-27
34300/64400 BTU/H12 GPM
35.3°F103.3°F
41°F92.5°F
IHCL-28
30000/56300 BTU/H9 GPM
33.3°F107.2°F
39.9°F94.6°F
P-26
62.5 GPM30 FT
P-27
62.5 GPM30 FT
AS-4
AV-4
HSS-4
189300/355400 BTU/H62.5 GPM
39°F96.4°F
45°F85°F
ET-4
7.1 GAL2.5 GPM14.2/14.1 FTP-IHCL-22
TT -1
9 GPM13.1/13 FTP-IHCL-23
TT -2
16 GPM21.9/21.7 FTP-IHCL-24
TT -3
5 GPM11.5/11.3 FTP-IHCL-25
TT -4
9 GPM13.1/13 FTP-IHCL-26
TT -5
12 GPM17.4/17.3 FTP-IHCL-27
TT -6
9 GPM12.4/12.3 FTP-IHCL-28
TT -7
V-43
V-44
V-45
V-46
V-47
V-48
V-49
BV-IHCL-22
BV-IHCL-23
BV-IHCL-24
BV-IHCL-25
BV-IHCL-26
BV-IHCL-27
BV-IHCL-28
2.5"
2.5"
Required re-piping of the building
103
![Page 104: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/104.jpg)
Ultimate Solution
IHCL-15
6400/12100 BTU/H2.5 GPM
39.9°F94.7°F
45°F85°F
IHCL-16
25700/48300 BTU/H9 GPM
39.3°F95.8°F
45°F85°F
IHCL-17
50000/93900 BTU/H16 GPM
38.8°F96.8°F
45°F85°F
IHCL-18
17100/32200 BTU/H5 GPM
38.2°F97.9°F
45°F85°F
IHCL-19
25700/48300 BTU/H9 GPM
39.3°F95.8°F
45°F85°F
IHCL-20
34300/64400 BTU/H12 GPM
39.3°F95.8°F
45°F85°F
IHCL-21
30000/56300 BTU/H9 GPM
38.4°F97.6°F
45°F85°F
P-17
62.5 GPM32 FT
P-18
62.5 GPM32 FT
AS-3
AV-3
HSS-3
189300/355400 BTU/H62.5 GPM
39°F96.4°F
45°F85°F
ET-3
7.2 GAL
V-29
V-30
V-31
V-32
V-33
V-34
V-35
V-36
V-37
V-38
V-39
V-40
V-41
V-42
2.5 GPM15.3 FTP-19
9 GPM14.4 FTP-20
16 GPM22.9 FTP-21
5 GPM12.5 FTP-22
9 GPM14.4 FTP-23
12 GPM18.2 FTP-24
9 GPM13.7 FTP-25
39°F96.4°F
45°F85°F
39°F96.4°F
45°F85°FHS-1
2.5"
2.5"
2.5"
2"
1"
2"
1.25"
1.25"
2"
104
![Page 105: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/105.jpg)
Ultimate Solution IHCL-15
6400/12100 BTU/H2.5 GPM
39.9°F94.7°F
45°F85°F
IHCL-16
25700/48300 BTU/H9 GPM
39.3°F95.8°F
45°F85°F
IHCL-17
50000/93900 BTU/H16 GPM
38.8°F96.8°F
45°F85°F
IHCL-18
17100/32200 BTU/H5 GPM
38.2°F97.9°F
45°F85°F
IHCL-19
25700/48300 BTU/H9 GPM
39.3°F95.8°F
45°F85°F
IHCL-20
34300/64400 BTU/H12 GPM
39.3°F95.8°F
45°F85°F
IHCL-21
30000/56300 BTU/H9 GPM
38.4°F97.6°F
45°F85°F
P-17
62.5 GPM32 FT
P-18
62.5 GPM32 FT
AS-3
AV-3
HSS-3
189300/355400 BTU/H62.5 GPM
39°F96.4°F
45°F85°F
ET-3
7.2 GAL
V-29
V-30
V-31
V-32
V-33
V-34
V-35
V-36
V-37
V-38
V-39
V-40
V-41
V-42
2.5 GPM15.3 FTP-19
9 GPM14.4 FTP-20
16 GPM22.9 FTP-21
5 GPM12.5 FTP-22
9 GPM14.4 FTP-23
12 GPM18.2 FTP-24
9 GPM13.7 FTP-25
39°F96.4°F
45°F85°F
39°F96.4°F
45°F85°FHS-1
2.5"
2.5"
2.5"
2"
1"
2"
1.25"
1.25"
2"
1. Install variable speed circulators to pump the bore field based on temperature differential
2. Install hydronic de-coupler (bridge)
3. Install circulators on each heat pump
1
2
3
105
![Page 106: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/106.jpg)
Ultimate Solution: Building Energy Consumption
Degree days % savings
100 52.64%200 53.65%300 54.51%400 55.31%500 56.11%600 56.91%700 57.74%800 58.60%900 59.50%
1000 60.46%1100 61.48%1200 62.58%
y = -4.226ln(x) + 33.107
y = -8.214ln(x) + 66.64
0
5
10
15
20
25
30
35
40
150 250 350 450 550 650 750 850 950 1050
After November 2011 Before november 2011
106
![Page 107: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/107.jpg)
What have we learned?
107
![Page 108: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/108.jpg)
Lessons Learned • Pumping energy use is not an insignificant
issue. • Decoupling bore field and using
temperature differential to control bore field capacity offers significant benefits.
• Minimizing head on unit circulators is beneficial.
• Low efficiency circulators can provide high efficiency.
108
![Page 109: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/109.jpg)
109
Questions
? ? ?
?
? ?
?
?
? ?
?
![Page 110: Design of Commercial Ground Source Heat Pumps · 2014-04-21 · source heat pumps - testing and rating for performance - Part 1: Water-to-air and brine-to-air heat pumps • EN 14825](https://reader030.vdocument.in/reader030/viewer/2022041008/5eaefd4af232e91c44733354/html5/thumbnails/110.jpg)
HVAC System Designer
• Responsible for – Thermodynamics of the
system – Design of system hydronics – Specification of the entire
HVAC system • The ground HX is part of it!
– The entire system performance
110