Design your application for superior performance Size heat exchangers for a perfect match Danfoss XGC gasketed plate heat exchangers districtenergy.danfoss.com MAKING MODERN LIVING POSSIBLE One global partner With Danfoss you get one reliable partner for support, warranty and service. Danfoss and our service partners are nearby present on all world continents.

Upload: truongquynh

Post on 29-Jul-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

Design your application for superior performance Size heat exchangers for a perfect matchDanfoss XGC gasketed plate heat exchangers

districtenergy.danfoss.com

MAKING MODERN LIVING POSSIBLE

Oneglobal partner

With Danfoss you get one reliable partner for support, warranty and service. Danfoss and our service partners are nearby present on all world continents.

Demands for quality, efficiency and economyBasically every customer demands the security of a stable and efficient operation of the heating and cooling installation. To avoid low comfort periods in the building or downtime caused by maintenance and repair, the system installation has to be service friendly. A gasketed plate heat ex-changer meets these requirements as an efficient and high-quality solution.

Since large scale heat exchangers are extensive investments, the total economy of the system investment is of significant importance. It is necessary that the operating cost is minimized with high energy efficiency and expectancy of a long total system lifetime.

These demand conditions require superior performance of all parts of the system installation and high quality of all components. Your supplier must fulfil these demands.

Danfoss XGC gasketed plate heat exchangers Danfoss XGC heat exchangers are designed for demanding temperature, pressure and flow conditions. Danfoss offers a very comprehensive range of efficient heat exchangers for applica-tions in any scale.

The heat exchangers are built on a module based concept. Frames, plates and connections can be combined to form a number of different exchanger types. By using different types of plates,

with different characteristics, the exchangers can be adapted to a wide variety of applications.

The XGC heat exchangers can easily be dismantled for inspection, cleaning and maintenance. Another benefit of the XGC gasketed plate heat exchangers is that they can easily be expanded or adapted by adding or replacing plates when the conditions change.

The product range is suited for appli-cations requiring high energy efficiency like district cooling interchangers, district heating substations or cooling/heating pressure breakers.

Designed in every scale for superior energy efficiency and performance

XGC-140XGC-100XGC-060

XGC-085 XGC-145 XGC-205 XGC-265 XGC-325

XGC-430XGC-330XGC-230

XGC-008 XGC-009XGC-013XGC-016 XGC-026

XGC-042XGC-044

XGC-051XGC-054 XGC-091 XGC-118

The XGC range offers:• Tall and narrow types with long thermal length to achieve close temperature approach• Compact types for general heating, HVAC and hot water systems• Large flow systems • Double wall types for separation of drinking water from heating or cooling water

Connection size, DN 32-50

DN 150

DN 300

DN 500

DN 200

DN 100

Product range specifications:

Flow range: 10 - 4000 m3/h

Working pressure: 10 - 25 bar

Connections: DN 32 – DN 500

Temperature: -20° to +180°C

Type Connections Width B Height H Length D E F (DN) (mm) (mm) (mm) (mm) (mm)

XGC 008 0.075 32 180 774 72 640 60

XGC 009 0.088 40 250 725 90 555 100

XGC 013 0.12 50 320 832 140 592 135

XGC 016 0.135 50 320 832 140 592 135

XGC 026 0.27 100 450 1110/1265 164/220 779 226

XGC 042 0.44 100 450 1520/1675 164/220 1189 226

XGC 044 0.44 100 450 1675 220 1189 226

XGC 051 0.55 150 585/630 1730 300 1143 300

XGC 054 0.552 150 630 1730 300 1143 300

XGC 091 0.91 150 626 2390 300 1800 285

XGC 118 1.18 150 626 2870 300 2280 285

XGC 060 0.56 200 825 1700 350 910 420

XGC 100 1.01 200 825 2280 350 1490 420

XGC 140 1.46 200 825 2860 350 2070 420

XGC 085 0.91 300 1060 1985 360 1140 570

XGC 145 1.53 300 1060 2565 360 1720 570

XGC 205 2.14 300 1060 3215 360 2300 570

XGC 265 2.76 300 1060 3795 360 2880 570

XGC 325 3.37 300 1060 4375 360 3460 570

XGC 230 2.37 500 1380/1510/1540 3172 450 2090 700

XGC 330 3.27 500 1380/1510/1540 3782 450 2700 700

XGC 430 4.17 500 1380/1510/1540 4392 450 3310 700

Dimensions

In every scale – options from 77 cm to 4,4 meters!

Heat transferarea per

plate (m2)

Wide span frame types to fit your needs

Frame types

Frame type NI and PI Frame type N and P

Plate materials• AISI 304 / EN 1.4301• AISI 316 / EN 1.4401• Titanium Grade 1• 254 SMO• C-276• Titanium Grade 11• Nickel 200/201

Gaskets• Nitril• EPDM• FKM, Viton®

Max. working pressure• T-frame 6 bar• NI/N 10 bar• PI/P 16 bar• SI/S 25 bar

Max. working temp.• Nitril 140°C• EPDM 170°C• FKM 180°C

Approvals• PED 97/23/EC

Plates, gaskets materials, working conditions

Double wall heat exchangers – No risk of flow media contamination with double wall heat exchangers.The plates are welded together around the port holes in pairs. This design requires one additional plate per flow channel.

In case a plate or gasket is leaking, the primary and secondary media will not be mixed. The leakage will also be visible from outside. The Heat exchangers are approved for drinking water. Even if medium 1 should leak, it cannot mix with medium 2.

Gasket

Gasket

Medium 1

Medium 2

Special demanding applications– we manage the challenges!

Gasketed heat exchangers for district cooling

The district cooling systems with plate heat exchangers often replace traditional air-conditioning system in buildings. As the district cooling plant transfers cold water through the network to building and end-users, the district cool-ing system offers operating flexibility, lower operation costs and reduced start-up investment.

Due to the increased heat exchanger sur-face required for efficient transfer of cold water into the cooling system, gasketed plate heat exchangers are typically the preferred choice.

District Cooling at Stockmann Store-house, Helsinki, Finland: Substation with large scale gasketed heat exchangers from Danfoss.

- Outer dimensions of the substation: Length 15 m, width 6.5 m and height 3.5 m

- Capacity of the cooling substation is 7.7 MW, divided into 3 circuits

- The substation includes 7 large gasketed plate heat exchangers

- Pipe sizes on the primary side are DN 300, on the secondary side DN 150/250/300

Picture: Stockmann Oyj Abp

Service and maintenance – efficient operation and reduced downtime

Dirt and scale can block your heat exchanger and cause unplanned downtime. Through a partnership agreement with a leading service provider, Danfoss offer service at customer site or in service centres located strategic places worldwide. If you have no time for servicing, a service engineer will attend your site to inspect the plate heat exchanger. The engineer will work out an individual action plan to fit your requirements,

carry out performance diagnostics, high pressure washing of plates while hanging in the frame, plate inspection, checking and replacing gaskets as needed and reassemble the unit.

A fouled plate pack can be replaced with a spare plate pack to reduce the service time on the unit. The fouled plates will be carefully packed and shipped to the closest service centre.

At partner service centres, Danfoss can provide you the advanced service that cannot be performed on site. We offer high level competence together with advanced equipment to ensure comprehensive service. We clean the plates and put in new gaskets. Every plate is thoroughly inspected to locate any pinhole or cracks. After a final hydrostatic test they are packed and shipped back to your location.

One global partnerWith Danfoss you get one reliable partner for support, warranty and service. Danfoss and our service partners are nearby present on all world continents.

E-mail: [email protected] · www.districtenergy.danfoss.com

Controls for every district heating and cooling application

Danfoss provides a complete range of automatic controls, heat exchangers and substations needed throughout the process of generating and distri-buting heat or cooling to homes and buildings. Our products contribute to individual comfort, reduce energy consumption as well as providing reliable and lasting operations and guarantee minimum servicing.

The product range consists of controllers for all purposes: • Differential pressure and flow controllers • Self-acting temperature controllers • Electronic controllers • Motorized control valves • Ball valves • Heat meters Danfoss offers a wide range of pre-fabricated substation for heating and cooling with XGC heat exchangers.

VB.EJ.B1.02 24487 · www.factorx.dk

System performance benefits - enabled by Danfoss automatic controls

Differential pressure control provides:Hydraulic balancing of the district heating network

• Ensures adequate heat or cooling supply to all subscribers• Reduces flow in the network • Reduces energy loss • Increases pump performance

Flow control and flow limitation provide:Exact limitation of the flow

• Secures adequate heat or cooling supply to all subscribers• Establishes a reliable basis for settling of fixed subscriber costs • Ensures optimum hydraulic balance

Temperature controllers provide:Exact temperature control

• Ensures adequate temperatures in your system• Offers modular design possibilities (e.g. controller + safety thermostat) • Offers safety functions (according to DIN standards)

Constant differential pressure (∆p) across the control valve

• Enables accurate temperature control and low return temperature• Prolongs the life of the control equipment

Low diffenrential pressure (∆p) across the control valve

• Prevents cavitation• Reduces noise emission in the system