designing a high-fidelity full-scope training simulator for a triple-pressure ccgt power plant
DESCRIPTION
This presentation describes the design and implementation of a high-fidelity, full-scope training simulator for a triple-pressure CCGT Power Plant. For more information, please visit GSES.com, email [email protected], or follow GSE on Twitter @GSESystems and Facebook.com/GSESystems. Thanks for viewing!TRANSCRIPT
![Page 1: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/1.jpg)
Design and Implementation of a High-Fidelity, Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant
![Page 2: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/2.jpg)
2
Summary
• Introduction • Plant configuration • Simulator configuration • DCS configuration • Model • Conclusion
![Page 3: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/3.jpg)
3
Introduction
• Two new CCGT plants • Commissioned last 2 years • Training improvement
• 18-month project • New training center in
Didcot, England
![Page 4: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/4.jpg)
4
Introduction
• Pembroke, Wales – Sea water cooled – ~450 MW – 5 units
• Staythorpe, England – Cooling water towers – ~430 MW – 4 units – Light oil (not used)
![Page 5: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/5.jpg)
5
Plant Configuration
• Alstom GT26 gas turbine – Two-stage combustion, HP and LP turbine – Efficiency 39.6% – Compression ratio 33.3:1
![Page 6: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/6.jpg)
6
Plant Configuration
• Triple-pressure boiler – LP system adds ~8 MW – HP system T = 565 C, P = 138 bar(a) – Exit flue gas temperature ~85 C – Allows for higher total efficiency – Steam turbine output >160 MW
• Overall efficiency >58%
![Page 7: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/7.jpg)
7
Plant Configuration
• Once-through coolers (OTC) – Compressor air-cooled
by feed water – Cooled air used to cool
blades – Steam feeds back to
HRSG – Preserved efficiency – Helix type Hx
• Single shaft with a clutch – Allows fast and flexible
run-ups
![Page 8: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/8.jpg)
8
Schematic of Modeled HRSG
![Page 9: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/9.jpg)
9
GSE Simulation Software Overview
JTopmeret JControl JLogic JElectric ISIS
Soft Panels JStation SmartTutor
DCS Operator Stations
JADE
I/O Systems Simulator DCS
SimExec
Power Plant
![Page 10: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/10.jpg)
10
Simulator Description
• A high-fidelity full-replica type simulator – HMI and control system identical – Hardware (I/O cards) emulated
• Emulator controlled by “ITS Link Tool” – JStation™ controls emulator via ITS interface
• Both simulators/DCSs on same hardware – Different domains, requires a system reboot
(dual-boot hardware) of DCS – Same for simulator hardware
![Page 11: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/11.jpg)
11
Simulator Architecture
![Page 12: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/12.jpg)
12
DCS Configuration
• ABB 800xA (Graphics, BoP, common parts) • ABB AC160 (GT and ST controllers)
– AC160 controller translated to AC400
• I/O communication done with OPC server – Reading and writing in SimExec database – 10 Hz
• Allows for on-the-fly snapping of ICs (backtracks)
• Saves 5 h historical data in ICs (trends)
![Page 13: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/13.jpg)
13
Modeling Tools
• JTopmeret™ – Gas turbine – HRSG – Main steam – BoP
• JElectric™ – Electric generation – Electric distribution
• ISIS™ – Components – Mal and remote
functions
• JStation™ – Connected to ITS
• JDesigner™ – Operator hard desk
![Page 14: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/14.jpg)
14
GT and Compressor Model
• Efficiency crucial for temperatures
• Non-ideal Rankine • Air humidity, pressure
and temperature impacts on efficiency
• Compressor and gas turbine work-based isentropic efficiency
![Page 15: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/15.jpg)
15
Combustion Model
• If sufficient oxygen, ideal combustion • Using available gas species in JTopmeret – "#↓4 + &↓2 → "&↓2 + &↓2 + #↓2 & + "#↓4 – '&↓( and CO based on empirical data
• Combustion energy added into JTopmeret gas enthalpy – Dynamic flue gas specific heat (Cp), based on
temperature and gas species to achieve correct gas temperatures
![Page 16: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/16.jpg)
16
JTopmeret
• JTopmeret – Mass, thermal and impulse balance
– Two-phase – Non-condensables
– Oil
– All models run at 40 Hz – Flexible and robust enough to handle most aspects
of a CCGT simulator
![Page 17: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/17.jpg)
17
Gas Turbine System Model
• GT modeled in JTopmeret – Air inlet – VIGVs – Compressor – Gas turbine – OTC air side – GT enclosure – GT cooling
![Page 18: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/18.jpg)
18
HRSG/Main Steam Model
• HRSG modeled in JTopmeret – Flue gas side – Steam/water side – Drums and evaporators with natural circulation – Feed water tank, pumps and heaters – OTC water/steam side
• Main steam modeled in JTopmeret – Turbines – Condenser
![Page 19: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/19.jpg)
19
Possible Future Projects
• MXL2 upgrade on Staythorpe and Pembroke commissioned – Possible simulator upgrade
• Increased air flow • New LP turbine blades (higher efficiency) • New control functions:
– ‘M’ mode maximum load (+ 13-23 MW) – ‘XL’ mode, flexible mode with lower temperatures
(longer time between inspections)
![Page 20: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/20.jpg)
20
Conclusions
• JTopmeret flexible and powerful enough for modeling a complete CCGT plant – New JTopmeret release includes fully integrated
combustion, gas turbine and compressor models – Should be able to handle future upgrades
• Successfully integrated with ABB systems – Communicating and controlling with 800xA and
AC400 emulators – AC160 can be translated to AC400
![Page 21: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/21.jpg)
![Page 22: Designing a High-Fidelity Full-Scope Training Simulator for a Triple-Pressure CCGT Power Plant](https://reader036.vdocument.in/reader036/viewer/2022062312/5571be56d8b42ac0228b4e59/html5/thumbnails/22.jpg)
For more information: Go to: www.GSES.com
Call: 800.638.7912
Email: [email protected]
Follow us on: Twitter @GSESystems