3
Contents
Comfort and well-being in every room ........................................................................4
Range overview .............................................................................................................5
The room controllers.....................................................................................................6
The room units: the key to individual comfort ..........................................................8
Applications .................................................................................................................10
Installation....................................................................................................................13
Engineering and commissioning ...............................................................................14
Integration into the building automation and control system................................17
Overview of the Desigo RXC equipment ...................................................................20
LON®, LONWORKS®, LONMARK®, LonTalk® , and Neuron® are registered trademarks of Echelon
Corporation, USA.
4
Comfort and well-being in every room
Most people in the industrial world spend some 90% of their time indoors. About one third of this time is spent at work. Against this background, it is clear that good indoor air quality, the right tempe-rature and draught-free air renewal are vital prerequisites for motivation and a sense of well-being. The Desigo RXC room automation system provides individual demand-based comfort for the users of public buildings, offices, schools, hotels, etc.
The room controllers and room units in the Desigo RXC range control and monitor comfort conditions in rooms and self-contained zones. These functions are finely tuned to the specific requirements of the area concerned (room or zone).
This makes it possible to satisfy individual comfort requirements and create a sense of well-being while at the same time saving energy.
Easy control of HVAC, lighting and blinds
The modular design of the Desigo RXC range means that if required, the operation of lighting and blinds can be combined with HVAC control. Using just one operator unit, room users can adjust all the room functions to suit their requirements.
Stand-alone operation at field level, or integration into the building automation and control system
The devices in the Desigo RXC range communicate with each other and with other LONMARK-compatible devices using a standard protocol (LONMARK® over LON bus). If required, devices at the field level can be integrated seamlessly into the Desigo building automation and control system. This is where all the higher-level control and coordination tasks, such as time scheduling or energy optimization activities are performed.
01715
M
Integrated operation of HVAC, lighting and blinds
5
Range overview
Desigo RXC is an innovative range of room controllers, extension modules and room units. Data communications are based on LONWORKS technology.
The Desigo RXC hardware
The range comprises compact and modular room controllers, easy-to-operate room units and controllers in room-style housings. The input and output configurations of the controllers, and the style of housing are optimized for each specific field of application. The modular room controllers include basic modules for HVAC control, which can be combined with extension modules for lighting and blind control.
The HVAC functions are operated via standard room units or controllers in a room-style housing. A configurable flexible room unit is available for combined operation (HVAC, lighting, blinds).
RXC20..RXC21..RXC22..
RXC32..
RXC10..
QAX3...QAX8...QAX9...
RXC30..RXC40..RXC41..
RXC31..RXC40..RXC41..
QAX50..QAX51..
Ele
ctri
cal
HV
AC
Fan coil unit
Radiator
Chilled ceiling
Blinds
Lighting
Room unitsModular
Compact
Room controllers
StandardWireless
VAV
Controller inroom-stylehousing
Flexible
10333Z03en_01
RXC39.. RXC40..RXC41..
The Desigo RXC software
All the room controllers, and the flexible room unit, are loaded with application software (referred to here simply as the "application") which contains the control program for the associated room or area. The devices are pre-programmed with the required appli-cation before they leave the factory.
Siemens Building Automation maintains a comprehensive library of applications covering a wide range of HVAC and electrical applications (see the overview on page 10).
The RXT10 commissioning and service tool is used for the engineering and commissioning of a network incorporating the Desigo RXC range. This tool also supports the creation of communications bindings between LONMARK-compatible devices (Desigo RXC or third-party devices).
6
The room controllers
RXC10, the room controller in a room-style housing:
This controller is a cost-effective combination of a room unit and an HVAC controller. It is particularly suitable for radiator-and-chilled-ceiling applications, and for simple VAV systems.
RXC20, RXC21, RXC22 and RXC39 compact room controllers
The input / output configuration and mounting options of these controllers make them ideal for fan coil applications. They can be installed in the fan coil unit, in control panels or on ducting.
Applications for radiators and chilled ceilings are also available.
RXC32 compact room controller
The RXC32 controller is particularly suitable for standard single-duct VAV systems. It comes with a built-in volume sensor.
RXC30 and RXC31 modular room controllers
The RXC30 basic module is fully optimized for radiator and chilled-ceiling control as well as the control of two rows of lights.
The RXC31 basic module provides flexible control solutions for VAV supply and extract air systems. A configurable interface (DC 0 ... 10 V) permits the connection of compact volume controllers.
The RXC31 basic module is designed for special applications.
RXC40 and RXC41 extension modules for lighting and blinds
The modular room controllers RXC30 / 31 / 38 can be combined with either one or two extension modules, type RXC40 and / or RXC41. These are simply plugged into the basic module. As a result, only the basic module needs to be loaded with an application and connected to the LON bus.
The RXC40 extension module allows two additional rows of lights to be switched and dimmed; the RXC41 module permits the switching of two drive motors for blinds.
Free scope for mounting
Apart from the RXC10, the room controllers can be mounted wherever preferred (e.g. in ceiling voids, under floors, in VAV boxes, ducting etc.).
Inputs and outputs
The range of functions of the inputs and outputs is determined by the particular application and its parameters. For example, the AC 24 V outputs can be configured for thermic valve actuators or for 3-position actuators (depending on the application).
7
Connections / functions RXC.10 RXC20 RXC21 RXC22 RXC30 RXC31 RXC32 RXC38 RXC39 RXC40 RXC41
Power supply AC 24 V AC 230 V AC 230 V AC 230 V AC 230 V AC 24 V AC 24 V AC 24 V AC 24 V Via RXC3...
LON bus (LONMARK compatible)
PPS2 interface for standard room unit (PPS2)
Socket for commissioning and service tool
Plug-in connection between basic module and extension modules
Digital inputs 1) 2 2 2 2 4 3 2 3 4 4 4
Analog input for LG-Ni 1000 temp. sensor
1 1 1 1 4) 1 1 4) 2 4)
DC 0 ..10 V analog inputs 3 4) 3 4) 1 4)
AC 24 V outputs 2) 2 2 4 2 2 6 4 6 2
Volt-free relay outputs 3) 1 3 4 7) 2 2 2 4
Output DC 1 ... 10 V for dimming 2
DC 0 ..10 V outputs 5) 1 2 2 4
Built-in volume sensor
Built-in room temperature sensor
Room temperature setpoint adjustment
Selection of operating mode ( / Auto) 6)
1) For window switches, presence detectors, dew point sensors, thermostats, or switches for lighting and blinds 2) To drive valve actuators or external contactors for electric heating coils (for details refer to the applications library CA110300) 3) For control of fans, lights or blind drives (not for RXC20 / RXC21 and RXC22) 4) One of the DC 0 ... 10 V inputs can be selected for LG-Ni1000 sensors 5) Outputs for compact volume controller DC 0 ... 10 V 6) Operating mode Auto: Comfort mode
: PreComfort (Standby) or Economy, depending on control from the building automation and control system (see page 17)
7) One relay output for electric re-heater
8
The room units: the key to individual comfort
The room units in the Desigo RXC range cover a wide variety of needs represented by the various room occupants. When designing these stylish room units, the designers also paid special attention to ergonomic factors.
The HVAC system, lighting and blinds can be operated in various ways:
• In the conventional manner, with standard room units for HVAC, and electric switches to control lighting and blinds
• With the integrated room unit, which combines the operation of HVAC, lighting and blinds in a single device.
• With wireless room units, which offer scope for location anywhere in the room, and permit averaging.
Conventional room units
The standard room units, types QAX30.1 ... QAX39.1, are available for HVAC appli-cations. They are connected to the room controller via a special (PPS2) interface. In addition to the built-in temperature sensor, all room units incorporate a socket for the RXT10 commissioning and service tool.
For applications involving the control of lighting and blinds, conventional switches can be used. This option is primarily of interest in systems retrofitted with Desigo RXC.
Integrated room units
The QAX50 and QAX51 flexible room units combine the operation of HVAC, lighting and blinds in a single device. The functions of each room unit are defined with appli-cation software in accordance with the room configuration. The room units are then fitted accordingly with the appropriately labeled pushbuttons. These integrated room units communicate with the room controllers via the LON bus.
Flush mounting room units with elegant design
The QAX84.1/PPS2room unit can be used in connection with standard switches and for in-wall mounting. It is delivered with a Siemens Delta-I bezel, but can also be ordered in separate components to fit in bezels from various manufacturers: Operator unit (QAZ84.1) and PPS2 flush mounting bus coupling unit (RXZ80.1 / PPS2).
Wireless room operation
The wireless room units, types QAX90.1 and QAX91.1 are used in conjunction with the RXZ90.1 receiver (PPS2). They are ideal for:
• Use in renovation projects (no wiring required) • Rooms with flexible partitioning and furnishing • Simple derivation of average temperature values (max. 5 sensors)
EnOcean room units
The batteryless and wireless room units, types QAX95.1 and QAX96.1 are used in conjunction with a gatewaRXZ95.1 (LONWORKS).
9
- +
Aut oA u to
RXC20..RXC21..RXC22..RXC30..RXC31..RXC32..RXC38..RXC39..
RXC30..RXC31..RXC38..RXC39.. +RXC40.. +RXC41..
HVAC
QAX50..QAX51..
LON-Bus
HVAC, lighting and blinds HVAC, lighting and blinds
Conventional room units Integrated room units
- +
Aut o
RXC30..RXC31..RXC38..RXC39.. +RXC40.. +RXC41..
10333z01en_02
QAX3...QAX8...QAX9...
QAX3...QAX8...QAX9...
Room unit functions
QAX 30.1, 31.1
QAX 32.1
QAX 33.1
QAX 34.1
QAX 84.1/ PPS2
QAX 39.1
QAX 50.., 51..
QAX 90.1, 91.1
QAX 95.1, 96.1
Built-in room temperature sensor
Room temperature setpoint adjustment QAX 31.1
QAX 91.1
QAX 96.1
Selection of operating mode ( /Auto)1) Selection of operating mode ( /Auto)1)
and fan speed
LCD display for room temperature, operating mode and fan speed
Exchangeable pushbuttons for control of lighting and blinds
Downloadable application software for operation of lighting and blinds
PPS2 interface to room controller
LONMARK-compatible bus communication
Wireless room units 2)
Batteryless EnOcean technology 3)
1) Operating mode Auto: Comfort mode : PreComfort (Standby) or Economy, depending on control from the building automation and control system (see page 17)
2) The RXZ90.1 receiver is the PPS2 interface for the QAX90.1 / 91.1 room units 3) The RXZ95.1 gateway is the LONWORKS interface to the QAX95.1 / 96.1 room units
10
Applications
The scope of the Desigo RXC range is defined by the pre-programmed application software. The next pages provide an overview of the options available and the devices required.
The applications can be downloaded with the RXT10 commissioning and service tool, which contains the complete applications library.
Due to intelligently defined default values in the applications, engineering involves simply determining a small number of parameters, e.g.:
• 2-position or 3-position control of valves and actuators • Temperature setpoints • Manual or automatic fan control For the complete list of applications, refer to the currently valid compatibility list (Valid Version Set) in the applications library, document CA110300.
Fan coil systems (examples)
Appl. Description Controller
FNC02 Two-pipe system with change-over RXC20 / RXC21
FNC03 Two-pipe system with change-over and electric re-heater RXC20 / RXC21
RXC22
FNC04 Four-pipe system RXC20 / RXC21
FNC08 Four-pipe system with room supply air cascade control RXC21
FNC10 Two-pipe system with change-over and outside air damper RXC21
FNC12 Four-pipe system with outside air damper RXC21
etc.
Common functions
• Window contact, occupancy sensor, four operating modes • Manual fan control via room unit • Automatic fan control
(RXC20 single-speed, RXC21, RXC22 three-speed) • Options with 2-pipe systems: heating only, cooling only or change-over, via LON bus
Heated / chilled ceilings and radiators (examples)
Appl. Description Controller
CLC01 Chilled ceiling RXC20 / RXC10
CLC02 Chilled ceiling and radiator RXC20 / RXC10
CLC03 Chilled ceiling and electric radiator RXC20
CLC06 Chilled / heated ceiling, two-pipe system with change-over via LON bus
RXC20 / RXC10
CLC07 Chilled / heated ceiling and radiator, two-pipe system with change-over via LON bus
RXC20
RAD01 LTHW radiator RXC20 / RXC10
RAD03 Electric radiator RXC20
etc.
Common functions • Window contact, occupancy sensor, four operating modes • Dew point sensor
70224
LON
T
Raum-Controller
70224
LON
T
Raum-Controller
11
VAV systems (examples)
Appl. Description Controller
VAV01 Single duct supply or extract air system RXC10 / RXC32
VAV02 Single-duct supply air system with re-heater / cooler RXC32
VAV03 Single-duct supply air system with electric re-heater RXC32
VAV04 Single duct supply and extract air system RXC31
VAV05 Single duct supply and extract air system with re-heater / cooler
RXC31
VAV06 Single duct supply and extract air system with electric re-heater
RXC31
etc.
Common functions
• Window contact, occupancy sensor, four operating modes • Built-in volume sensor (RXC32) • DC 0 … 10 V inputs for external pressure / volume sensors (RXC31) • Control of compact volume controllers with DC 0 ... 10 V (RXC10, RXC32) • Direct control of damper actuators (RXC31, RXC32)
Fan powered box systems (example)
Appl. Description Controller
FPB05 Fan powered Box (Fan-assisted VAV unit) with series fan and electric reheater
RXC31
Common functions
• Window contact, occupancy sensor, four operating modes • DC 0 … 10 V inputs for external pressure / volume sensors • Control of compact volume controllers with DC 0 ... 10 V • Direct control of damper actuators • DC 0 ... 10 V output for proportional control of fan
Basic applications
With the basic application software every room controller can also be used as an I/O module. The RXT10 commissioning and service tool can be used to view the signals at the hardware inputs or to process them further at the automation level or on the management station. Similarly, the outputs of the room controllers can be controlled directly via inputs.
If a room controller is ordered without an application being specified, it will be pro-grammed in the factory with the appropriate basic application before delivery. Appl. Description
00010 Basic application for RXC10
00020 Basic application for RXC20
00021 Basic application for RXC21
00022 Basic application for RXC22
00030 Basic application for RXC30
00031 Basic application for RXC31
00032 Basic application for RXC32
00034 Basic application for RXC34.1 (NOT for RXC34.1/ALG)
00038 Basic application for RXC38
00039 Basic application for RXC39
70224
LON
T
Raum-Controller
70224
LON
T
Raum-Controller
12
Combined applications
The HVAC applications covered by the modular RXC30, RXC31 and RXC39 controllers can be combined with lighting and blind control (extension modules RXC40 and RXC41).
The combined application consists of an HVAC application and one or more electrical functions.
Examples:
Appl. HVAC Appl.
Electrical function Controller
Lighting on/off1)
Lighting dimming
Blind up/down2) R
XC
30
RX
C31
RX
C40
RX
C41
INT01 CLC023) 2 x 1
INT02 CLC023) 4 x 1 1
INT03 CLC023) 2 x 2 x 1 1
INT04 CLC023) 2 x 2 x 1 1
INT05 CLC023) 2 x 4 x 1 2
etc.
INT10 VAV084) 2 x 1 1
INT11 VAV084) 4 x 1 2
INT12 VAV084) 2 x 1 1
INT15 VAV084) 2 x 2 x 1 1 1
etc.
1) With or without daylight sensor via LON bus, as required 2) With or without slat adjustment, as required 3) CLC02: Chilled ceiling and radiator-type heating 4) VAV08: Single duct supply and extract air system with radiator
The flexible room unit for made-to-measure operation
The flexible room unit was designed specifically for the operation of combined applications (see pages 8 and 9). The unit is loaded with an application for operation of lighting and blinds, and fitted with the appropriate pushbuttons.
The available applications are described in the Desigo RXC application library (CA110300).
The flexible room unit can be ordered as follows:
QAX50: with pushbuttons for HVAC, on / off control of lighting and control of blinds QAX51: with pushbuttons for HVAC, dimming control of lights and control of blinds The appropriate application is downloaded by means of the RXT10 commissioning and service tool.
Special applications
If the existing Desigo RXC standard applications do not meet the client's requirements concerning functionality and combination of functions, HQ can realize special applications. Please write a service request, using the request form on the intranet.
T
70225
LON Room controller + extension modules
13
Installation
The room controllers in the Desigo RXC range are designed for various types of installation: • In fan coil units (mounted with screws or on DIN rails) • In control panels (on DIN rail) • In ceiling voids • Under floors • In sill or floor ducting • On VAV boxes • On flush-mounting boxes (RXC10, QAX.50 / 51) Terminal covers are required when mounting the controllers outside control panels or fan coil units (see page 21, accessories).
70229
Various options for installation
70227
Example: RXC20 with terminal covers
14
Engineering and commissioning
In the engineering phase, the number of devices, their application and the LONMARK bindings between devices, and between these devices and any third-party equipment are determined according to the distribution of rooms and zones in the building.
The network structure defined at the engineering stage (applications, parameters, LONMARK bindings etc.) is mapped to the devices in the commissioning phase.
RXT10 commissioning and service tool
The RXT10 commissioning and service tool provides efficient support both for engineering in the office and for commissioning on site. (In Desigo V5 we also admit the use of standard LNS tools, e.g. NL220, LonMaker).
The RXT10 software is designed for use on a PC running Windows XP or Windows Vista.
The commissioning and service tool is used for the following:
• Selecting the application for each room • Determining the required room controllers and setting their parameters • Integrating LONMARK-compatible third-party devices (e.g. LNS plug-ins) • Creating the LONMARK bindings • Dividing the network into segments and adding routers • Addressing the controllers • Loading the network structure (including applications) into the devices • Commissioning support • Project documentation • Graphics-based network view • etc.
Selecting the application and controllers
From the comprehensive application library, first the appropriate application is selected and then the appropriate devices (in the example below, this means application INT06 and the RXC30 basic module with extension modules RXC40 and RXC41).
Selecting the application
15
Parameter setting
Each application has a number of parameters, such as temperature setpoints, type of output sequence (2-position or 3-position), type of fan control etc. These parameters are now adjusted according to requirements. In most cases, however, the factory default settings can be retained.
Setting the temperature setpoints
Communication bindings
The bus communications in the Desigo RXC range are based on LONWORKS techno-logy. This allows devices to communicate with each other and with LONMARK-compa-tible devices from other manufacturers. So, for example, an outside temperature sensor can be connected to a number of room controllers via the LON bus.
Changes in building use can also be accommodated without the need for rewiring, simply by changing the bindings, e.g. master / slave.
The graphical user interface of the RXT10 tool can be used to create these LONMARK bindings with a convenient "drag and drop" operation.
Example: Creating bindings
16
Addressing
The physical identification number (neuron ID) of each device (Desigo RXC or a LONMARK-compatible third-party device) must be modified to match the logical address (e.g. location) in the network structure. The RXT10 tool offers various options for efficient addressing.
Loading the network structure
The network structure (applications, parameters, LONMARK bindings) must now be mapped in the individual devices: On site, this can be carried out from any point on the LON bus. It is also possible, however, to address the devices individually and download them with the network structure prior to installing them on site.
Connection of the RXT10 commissioning and service tool
For commissioning on site, a laptop running the RXT10 tool software is connected to the LON bus. All the Desigo RXC devices on the LON bus can be addressed from this point. If the room controllers are installed in a location where they cannot be seen, a room unit can also be used for access to the LON bus: all the room units also incorporate a tool socket.
Adjusting the parameters
If necessary, parameters such as temperature setpoints can be adjusted during com-missioning or later when servicing the system.
Commissioning support
The RXT10 tool includes convenient functions to support commissioning and service, for example:
• Interrogating or restoring network data • Monitoring and testing the inputs of one or more controllers • Direct control of the outputs of one or more controllers for test purposes or to
balance hydraulic circuits • Trend features for long-term data logging • Report functions for printing project data
1 2
4
1033
3Z013
Options for connecting the RXT10 tool:
1) Connection to the standard room unit
2) Connection to the room controller
3) Connection to the flexible room unit
4) Connection to the PXC....D + PXX-Lxx system controller (see page 17)
17
Integration into the building automation and control system
Management level Automation level Room level
10333Z02_01
BACnet / LonTalk
DESIGO INSIGHT
RXC... QAX5...
PPS2
QAX...
ON ARKL M / LonTalk
RXC...
DESIGO INSIGHT
PXM20-E
PXM20 BACnet / LonTalk
PXX-Lxx
PXC....D modular
PXX-Lxx
PXC200-E.D
BACnet / Ethernet / IP
PXC22.DPXC....D modular
ON ARKL M -compatible third-party devices
Stand-alone operation at field level
The Desigo RXC room automation system can be operated as a stand-alone system. All the required functions are made possible by means of LON communications be-tween the devices.
Integration into the automation level
Through integration into the Desigo PX automation level, a number of further functions become available (refer to the PX system description, document CM110756).
The room level is integrated into the automation level by means of the system controller PXC....D + PXX-Lxx. This controller converts the LONMARK objects into BACnet objects, and provides comprehensive grouping functions. Up to 60 room controllers can be connected to each PXX-L11 system controller, and up to 120 to each PXX-L12 system controller.
Features of the system controllers PXC....D + PXX-Lxx:
• Concentration of data of the room controllers, and easy manipulation of this data • Simple definition of groups • Implementation of system functions, e.g. time schedules, trends, alarms etc. • Coordination with the primary plant • Efficient engineering and rational commissioning
Features of the PXM20 / PXM20-E operator unit
• Operation and monitoring of the entire automation level including inputs, outputs and the room-controller operating states.
• Display and modification of time schedules • Graphics-based display of trend data
18
Integration into the management level
Because it is integrated into the automation level, the room level can also be displayed and operated at the management level.
DESIGO INSIGHT is the Windows XP / Vista-based management station within the Siemens building automation and control system. With its modular structure it covers every level of complexity - from small buildings to large building complexes and geographically separate buildings For more information refer to the Desigo system description, document CM110660.
Depending on the degree of complexity required, the DESIGO INSIGHT management station may incorporate, for example, the following program modules for the user:
• Plant Viewer: graphics-based operation of the plant • Time Scheduler: time schedules for a wide range of switching operations • Object Viewer: display and modification of data point values • Alarm Router: routing of alarm messages • etc. The DESIGO INSIGHT management station allows the following additional functions for control and operation of the room controllers:
• Monitoring and operation of rooms, plus trend logging • Building use and room occupancy time schedules • Integration of the controller data into plant graphics • Central control of setpoints, operating modes, lighting, blinds etc.
For every standard application a suitable super genie is available in DESIGO INSIGHT
19
Time schedules for building use and room occupancy
One option which is frequently employed at the automation level or in the DESIGO INSIGHT management station is the use of central Building use and Room occupancy time schedules. These make it possible to optimize the supply of energy to match varying periods of room occupancy.
The Building occupancy time schedule determines the overall period of time during which the building is in use. Outside this period, the plant (e.g. HVAC primary plant) remains available, but at reduced output.
The Room occupancy time schedule determines the occupancy times in individual rooms or groups of rooms. This enables individual tenants of the building, for example, to define their own occupancy hours.
Central and local control of operating modes
The diagram below shows an example of how the central time schedules (Building use and Room occupancy) interact with the local / Auto control button on the room unit
(operating as an occupancy function in this case).
Local control with an occupancy sensor is also possible.
Auto
01533den
05.00
07.00
Pre-Comfort (Stand-by) 2)
Auto 4) tAuto
17.00
22.00
Auto
Room operating mode
Comfort 1)
Economy 3)
Local /Auto
Central: Room occupancy
Central: Building use
Building in use
Room occupancy
Example of the routines over a typical day:
1) Comfort The room temperature is within the comfort range. 2) PreComfort (Standby) The heating or cooling output is slightly reduced
(during the temporary absence of the room occupant) 3) Economy The heating or cooling output is reduced significantly. 4) Outside the times defined by the Building use program, local operation has no influence on the operating mode.
20
Overview of the Desigo RXC equipment
Desigo RXC controllers Documentation
RXC10 Room controller in room-style housing for chilled ceilings, radiator-type heaters and VAV systems (supply or extract air)
CA2N3830
RXC20, RXC21, RXC22 Room controllers for fan coil systems, chilled ceilings and radiator-type heating
CA2N3834
RXC30 Room controller for radiators and chilled ceilings, with lighting control CA2N3840
RXC31 Room controller for VAV systems (supply and extract air) CA2N3844
RXC32 Room controller for VAV systems (supply air, with built-in pressure sensor)
CA2N3845
RXC34.1 *) Laboratory fume hood controller for fast VSV control CA2N3847
RXC34.1/ALG *) Laboratory room controller for fast VSV control CM2N3848
RXC38 Room controller for special applications CM2N3841
RXC39 Room controller for fan coil systems CM2N3856
RXC40 Extension module for RXC30 / 31 / 38, / 39 for lighting control CA2N3842
RXC41 Extension module for RXC30 / 31 / 38, / 39 for control of blinds CA2N3843
Desigo RXC room units
QAX30.1 Room unit with temperature sensor CA2N1741
QAX31.1 Room unit with temperature sensor and setpoint adjuster CA2N1741
QAX32.1 Room unit with temperature sensor, setpoint adjuster and / Auto switch
CA2N1641
QAX33.1 Room unit with temperature sensor, setpoint adjuster and
/ Auto / Fan switch CA2N1642
QAX34.1 Room unit with temperature sensor, setpoint adjuster,
/ Auto / Fan switch and LCD display CA2N1645
QAX39.1 Universal setpoint adjuster CA2N1646
QAX50, QAX51 Flexible room unit with temperature sensor, setpoint adjuster,
/ Auto / Fan switch, LCD display and rocker switches for lighting and blinds
CA2N1648
QAX84.1/PPS2 Flush mounting room unit with temperature sensor, setpoint adjuster,
/ Auto / Fan switch and LCD display CA2N1649
QAX90.1 Wireless room unit with temperature sensor CA2N1643
QAX91.1 Wireless room unit with temperature sensor and setpoint adjuster CA2N1643
RXZ90.1 Receiver with PPS2 interface, for wireless room units CA2N1644
QAX95.1 EnOcean room unit with temperature sensor CM2N1660
QAX96.1 EnOcean room unit with temperature sensor and setpoint adjuster CM2N1660
QAX95.4, QAX96.4, QAX97.4, QAX98.4
Wireless and batteryless room units with EnOcean interface CM2N1663
RXZ95.1/LON EnOcean gateway with LONWORKS interface CM2N1661
*) Product phased out
21
Desigo RXC system controllers and tools for commissioning and service Documentation
PXC….D, PXC…-E.D Automation stations, modular series CM1N9222
PXX-L11, PXX-L12 Extension modules (integration of 60 / 120 RXC room controllers) CM1N9282
PXR11, PXR12 *) System controllers (integration of 60 and 120 RXC room controllers respectively)
CA1N9235
RXT10.3 Commissioning and service tool (software) CM110669
RXT20.1 Service terminal CA2N3851
Accessories
RXZ01.1 LONWORKS bus terminator 52.3 Ω CA2N3861
RXZ02.1 LONWORKS bus terminator 105 Ω CA2N3861
RXZ03.1 LONWORKS point coupler (for systems with V1 applications only) CA2N3849
RXZ10.1 Cable kit for RXT10 see CM110758
RXZ20.1 Terminal covers for RXC20, RXC21 and RXC22 CA2N3834
RXZ30.1 Terminal covers for RXC30 / 31 / 32 / 34.1*) / 38 / 39 CA2N3840
RXZ40.1 Terminal covers for RXC40 and RXC41 CA2N3842
UA1T Power amplifier for thermic valve actuators CA2N3591
---------- Air filter for RXC32 controller see CA2N3845
Third-party devices
Link Power Supply LPT bus power supply (Siemens) Order number: 6EP1252-0AA00
Desigo RXC, other documentation
Desigo RXC Applications library CA110300
Desigo RXC Planning and installation manual CA110330
Desigo RX Hardware overview CA2N3804