DESIGO™ Building automation & control system System description

Page 2: DESIGO System description - This area is password protected [401]

2 / 76

DESIGO™ Building automation & control system System description CM110660en_02 31.01.2007

Page 3: DESIGO System description - This area is password protected [401]

3 / 76

Table of contents

The DESIGO building automation and control system: the open system ...............5 The scalable system: for all projects sizes ......................................................................5 Open to integration ..........................................................................................................5 Easy to operate ...............................................................................................................5 Long-term investment protection and economy at every stage.......................................5 The DESIGO system topology......................................................................................6 System functions...........................................................................................................7 Operation and monitoring ................................................................................................7 Trend/History ...................................................................................................................8 Alarm management .........................................................................................................9 Scheduler/Calendar .......................................................................................................10 Access rights ................................................................................................................. 11 Communication networks...........................................................................................12 Communication standards: specifically designed for building services .........................12 The management level: DESIGO INSIGHT ................................................................13 The taskbar....................................................................................................................14 Plant Viewer...................................................................................................................15 Scheduler ......................................................................................................................16 Alarm Viewer .................................................................................................................17 Alarm Router .................................................................................................................18 Trend Viewer .................................................................................................................19 Object Viewer ................................................................................................................20 Log Viewer.....................................................................................................................22 Report Viewer ................................................................................................................23 Reaction Processor .......................................................................................................24 Operation and monitoring with Web technology ............................................................25 The DESIGO PX automation level ..............................................................................29 A family of freely programmable operator units .............................................................29 Operation at the automation level..................................................................................30 A family of freely programmable automation stations.............................................36 The field level: the DESIGO TX-I/O™ modules .........................................................40 Overview of TX-I/O modules..........................................................................................41 Room automation: DESIGO RX..................................................................................42 Convenient room automation with DESIGO RX ............................................................42 Range overview – DESIGO RXC ..................................................................................43 Range overview – DESIGO RXB ..................................................................................44 Range overview – DESIGO RXL...................................................................................45 The room unit: the key to individual comfort ..................................................................46 Applications ...................................................................................................................47 Integration into the building management system .........................................................48

Page 4: DESIGO System description - This area is password protected [401]

4/76

DESIGO OPEN..............................................................................................................50 The management level: INSIGHT OPEN.......................................................................51 DESIGO SX OPEN ........................................................................................................52 The automation level: PX OPEN....................................................................................53 The field level: I/O OPEN...............................................................................................56 DESIGO tools and software blocks ............................................................................57 DESIGO tools ................................................................................................................57 Programming with D-MAP .............................................................................................58 Libraries ......................................................................................................................58 Energy management....................................................................................................59 Energy management with CAFM solutions....................................................................59 Pharma Solution ..........................................................................................................62 Regulatory compliance add-on for DESIGO INSIGHT ..................................................62 InfoCenter .....................................................................................................................64 GxP compliant monitoring and reporting........................................................................64 Data security ..................................................................................................................64 Reliable data archiving...................................................................................................64 Technical solutions for 21 CFR Part 11 ..........................................................................65 The automation level: SIMATIC S7 for industrial applications ................................66 SIMATIC S7 modular automation station .......................................................................66 Local operation and monitoring......................................................................................67 Web-based operation and monitoring with S7 WEB......................................................67 SIMATIC S7 automation software ..................................................................................69 Appendix ......................................................................................................................70 System topologies..........................................................................................................70

Page 5: DESIGO System description - This area is password protected [401]

5 / 76

The DESIGO building automation and control system: the open system

DESIGO is an up-to-date family of freely programmable management and automation stations for the full spectrum of building services applications. With system functions such as alarm management, time scheduling, and trend logging, combined with sophisticated control functions, DESIGO is a highly versatile asset in a building. Innovative Web technology, high-performance open databases and open communications make DESIGO a financially wise investment in the future.

The scalable system: for all projects sizes

With its graded range of automation stations, room controllers and operator units, DESIGO is ideally suited to projects of all sizes and for all types of building. A flat system topology permits low-cost entry with small systems which can be extended and expanded when required.

Open to integration

DESIGO is consistent in its support of open communications, making it easy to connect a wide variety of building services equipment on the basis of standard open data interfaces:

• BACnet for the automation level and management level network • LONWORKS and KNX S-mode (EIB) for the networking of the room automation

system and distributed secondary processes • M bus, Modbus, OPC and other interfaces for universal connection of third-party

devices and systems

Easy to operate

DESIGO INSIGHT uses life-like graphics to portray complex issues simply.

Typical aspects of air conditioning, such as psychrometric charts and heating curves, or control routines such as load shedding and mains recovery are illustrated with clarity. The interfaces, designed in accordance with ergonomic principles, permit optimum use of the system and can be mastered quickly by operators. Access is also available via the intranet and Internet.

Long-term investment protection and economy at every stage

DESIGO places emphasis on long-term investment protection by focusing consistently on compatibility.As it moves into the future, the DESIGO system takes both the automation systems of today and the VISONIK, INTEGRAL and SIMATIC S7 systems, and integrates them seamlessly. Changes in use, system expansion and retrofit projects can all be handled in gradual stages.

David Chen
文字方塊
圖控軟體需為視窗作業版多工即時之圖型監控軟體,可與控制器通信協定相容,且為正版授權
David Chen
矩形
David Chen
箭頭
Page 6: DESIGO System description - This area is password protected [401]

6 / 76

The DESIGO system topology

The DESIGO system can be divided into three levels: the management level, the automation level and the field level. By virtue of distributed intelligence, each of these levels operates both autonomously and in a network.

The principal DESIGO system components: • DESIGO INSIGHT, the management

station, for higher-level operation and monitoring, graphics-based display of the process, automatic alarm distribution and a wide range of different data analysis options.

• DESIGO PX, the automation system for control, operation and monitoring of the primary plant. By use of PX-WEB, the automation system can be operated via a Web client.

• The TX-I/O modules and the PTM-module, which provide the interface to the devices at the field level, the sensors and actuators.

• DESIGO RX, the room automation system, for control of comfort conditions in individual rooms and for operation of lighting and blinds.

• DESIGO OPEN, for the integration of a wide variety of plant at all levels of the system.

Figure 1 Overall topology of the DESIGO system

One of the key benefits of DESIGO is its scope for gradual expansion, from the smallest systems through to large, distributed systems. Scalability is illustrated by further examples of topologies in the appendix.

Page 7: DESIGO System description - This area is password protected [401]

7 / 76

System functions

Operators of the DESIGO building automation and control system have a versatile range of equipment at their disposal, offering convenient access to the system and the plant.

Operation and monitoring

Operator station • The DESIGO INSIGHT management station is a powerful and user-friendly interface

for monitoring of the overall system. User access to DESIGO INSIGHT can be matched to the level of responsibility of a given user of the building automation and control system.DESIGO INSIGHT Web Access allows access to the management level using Web technology.

• The PX-WEB software uses Web technology to map all plant and system information from the automation level to a standard Web browser.

Room operator unit • With the QAX… product range, room users can view and operate the setpoints and

measured values used for individual room control. Operation in the control panel • The user-friendly, graphics-based PXM10 operator unit allows full local operation of

the automation stations. • The network-compatible graphics-based PXM20 operator unit presents all plant and

system information in an easy-to-understand format, with a plain-text commentary.

Manual operation • The DESIGO TX-I/O modules in the PTM… product range include facilities for

manual/emergency operation of plant and for the display of operating states. • The PXC36-S compact automation station incorporates slide switches which can be

configured for manual operation or as freely-assignable outputs.

Figure 2

David Chen
文字方塊
動態圖形介面具支援中文語系與中文顯示能力
David Chen
矩形
David Chen
箭頭
David Chen
文字方塊
圖控軟體本身即為網路伺服器(Web Server),可透過專屬網路直接連接環控主機電腦連接圖控系統,畫面與圖控主機操作畫面。
David Chen
箭頭
Page 8: DESIGO System description - This area is password protected [401]

8 / 76

Trend/History

Fully integrated trend data processing allows effortless evaluation and analysis of real-time (online) data and (offline) historical data. The trend feature simplifies the monitoring and fine-tuning of the plant. In the DESIGO system this feature is implemented in the form of trend log objects, in compliance with BACnet standard.

Data for trend analysis can be logged in a variety of different ways, satisfying a whole range of requirements:

Trend logging options: Sampling options: • Continuous logging • Single run • Transient run (logging for a

defined period)

• Polling • COV polling (Change of Value) • Event-driven polling

Trend graphs can be displayed both on the PXM20 operator unit and on the management station. The management station also allows displays in color and in 2D or 3D.

Figure 3 Trend Viewer on DESIGO INSIGHT management station and PXM20 operator unit

With the Online Trend option, individual data points are registered on a COV basis or through polling, and displayed immediately. The values are stored temporarily to allow the analysis of transient response patterns, for example.

The Offline Trend option by contrast, does not depend on a permanent connection between the automation station and the operator unit, since the values in the automation station can be stored temporarily for retrieval on the operator unit as needed.

Features of Online Trend: Features of Offline Trend: • Real-time display of process data • Can be based on changes in the value

of a data point (COVs) or on periodic sampling by Trend Viewer (times can be configured)

• Offline data display, no connection required

• Longer periods of time (day, month) • Data acquisition in the automation

system • The data is uploaded to the

management level at regular intervals or as needed

Online trend

Offline trend

Page 9: DESIGO System description - This area is password protected [401]

9 / 76

Alarm management

One of the most important features of a building automation and control system is the ability to generate alarms automatically in response to faults which may occur in the HVAC and other plant, or in the automation system itself. The management of alarms (generation, display and handling) must be simple, efficient and consistent at all levels of the system. DESIGO uses the BACnet alarm functions, and supports the following three types of alarm with up to 256 alarm priority levels:

• Simple alarm (for alarms not requiring user interaction) • Basic alarms (for alarms requiring acknowledgment) • Extended alarms (alarms requiring acknowledgement and reset)

When an alarm occurs, it is automatically detected, registered and transferred to operator units such as PXM20 or PX-WEB, or to the DESIGO INSIGHT management station. Informative alarm messages are also transmitted to remote devices such as mobile phones, fax machines, printers or PCs and Web browsers, via SMS and e-mail. Clear alarm lists provide a view of all pending and time-stamped alarms at a glance, and permit straightforward processing. Operators are alerted to incoming and pending alarms by means of pop-up windows and audible and visual signals.

Alarms are transferred on the basis of time, priority and/or plant type, using an outstandingly powerful alarm routing system at the management station. This ensures the uninterrupted routing of alarms, whether or not there is an operator sitting at the management station. Users are supported in their work by various overview options which help ensure a fast and correct response even in critical alarm situations.

Figure 4 Alarm messages on the PXM20 operator unit and the DESIGO INSIGHT management station

Alarm messages

Alarm routing

Page 10: DESIGO System description - This area is password protected [401]

10 / 76

Scheduler/Calendar

One of the basic functions of a building automation and control system is time control of procedures and processes.

The plant in the building is operated on the basis of business and working hours, and holidays.

Time schedules ensure that the heating and lighting are switched off automatically at the end of the working day, that the temperature in the building is reduced at night, and that the plant is not kept running for longer than necessary. They can also be used to switch off the air conditioning in certain rooms during holidays.

The ideal time schedules help save energy and increase the service life of the plant. This is another area where DESIGO excels with its straightforward and exceptionally user-friendly operation.

Time-switching operations in the DESIGO building automation and control system are implemented in accordance with the BACnet standard, using the BACnet objects "Schedule" and "Calendar" for flexible operation of the building. From simple 7-day schedules to recurring exceptions, these powerful functions make programming easy.

By use of standard BACnet functions, the BACnet time schedules can be operated system-wide from the user-friendly operator units PXM20 and PX-WEB and from the DESIGO INSIGHT management station.

Figure 5 Time schedule on PXM20 operator unit and DESIGO INSIGHT management station

For safety reasons, schedules and calendars are stored in the automation station, so that in the event of a network or PC failure, the automation level can continue to operate autonomously.

Saving energy and increasing the service life of plant

Page 11: DESIGO System description - This area is password protected [401]

11 / 76

Access rights

Access rights can be used to filter information from the plant and system based on the individual requirements of a user. The resident engineer or the service engineers, for example, only have access to the information they strictly need. A distinction can also be made between read access and write access. Certain users may be able to read a value but not modify it, while other users may have extended access rights, enabling them both to read and to modify values.

Only authorized personnel are granted access to the system via the operator units. When a user enters a user name and password, the system verifies the associated access rights and enables access to the relevant plant. Read and write access rights can be defined in detail, right down to individual information points.

The following classes of access are supported in the DESIGO system:

• Internal • Extended service • Basic service • Administration • Extended operation • Standard operation • Basic operation In addition to the above, it is possible to enable or disable the use of the various applications, access to individual graphics pages and access to entire sites from the management station for specific user groups. The tailoring of the environment to each user ensures clear areas of responsibility, so simplifying cooperation between the various user groups.

Freely-definable access rights

Users supported system-wide

Page 12: DESIGO System description - This area is password protected [401]

12 / 76

Communication networks Communication standards: specifically designed for building services

With the BACnet (Building Automation and Control network) open communications protocol, compliant devices can be interconnected at low cost. The worldwide BACnet standard was developed specifically for the needs of building services, under the auspices of ASHRAE (the American Society of Heating, Refrigerating and Air-Conditioning Engineers). BACnet networks provide all subscribers with access to all the data and functions of the connected devices.

For the exchange of information among its own system components, DESIGO uses three standard protocols, recognized worldwide: BACnet, LONWORKS and KNX S-mode (EIB). The BACnet communication protocol is used for the exchange of information between one DESIGO PX automation station and another, and between BACnet PXM20 operator units and DESIGO INSIGHT.

DESIGO uses Ethernet/IP, LonTalk or PTP (point-to-point, modem or null-modem) as the transport medium. At the room automation level, DESIGO RX communicates in accordance with the LONWORKS standard or KNX S-mode (EIB).

DESIGO Terminal Server and DESIGO WEB make optimum use of the advantages of modern IT technology for the benefit of building services. Properly selected and used, they have a significant influence on the ability to fine-tune the running of the building and on the comfort and satisfaction of building users.

DESIGO Terminal Server provides all the functions of the management system in the form of terminal services over the network. These services can be accessed simultaneously by different users in independent sessions. In addition to the operation and monitoring programs for daily operation of the plant, engineering tools are also provided, allowing modification and expansion of the system while it is running. This makes the DESIGO Terminal Server the optimum solution for professional building operators who need unrestricted access to building data via their intranet or extranet, from any location.

DESIGO WEB is a genuine Web solution based on Microsoft IIS (Internet Information Server). The programs for operation of the management system are mapped to ASPs (Active Server Pages) in special interfaces optimized for Microsoft Internet Explorer.

In the case of BACnet/IP over Ethernet, the standard transport protocol UDP is used, since BACnet already provides adequate mechanisms for the control of data transport. Like TCP, UDP is a transport protocol, but unlike TCP, it is a wireless protocol.

DESIGO is a native BACnet system, and as such, every device incorporates BACnet as a basic, integrated and permanently available feature. The management stations and automation stations are all implemented as full BACnet nodes. BACnet is integrated directly without the need for any special conversion of data. BACnet communications can be generated without additional hardware or services.

DESIGO is compatible with the communications resources of the legacy automation systems UNIGYR, VISONIK, INTEGRAL and SIMATIC S7 and allows their seamless integration. Changes in use, system expansion and retrofit projects can all be handled in gradual stages.

BACnet, LONWORKS and KNX S-mode (EIB)

DESIGO Terminal Server DESIGO WEB

DESIGO Terminal Server

DESIGO WEB

BACnet/IP

Native BACnet

Connection of legacy systems

David Chen
文字方塊
圖控軟體本身即為網路伺服器(Web Server),可透過專屬網路直接連接環控主機電腦連接圖控系統,畫面與圖控主機操作畫面。
David Chen
矩形
Page 13: DESIGO System description - This area is password protected [401]

13 / 76

The management level: DESIGO INSIGHT

The clearly structured, modular, object-oriented software of the DESIGO INSIGHT management station is based on the latest standard Windows technology: Windows XP, MS-SQL, and .NET.

The functional scope and ease of use of the software reduces operating costs and familiarization time, while at the same time maintaining operational reliability. The DESIGO INSIGHT applications are presented below:

DESIGO INSIGHT via the taskbar Provides a quick overall view of the system and is used to start whichever user applications are required.

• Plant Viewer: Realistic plant graphics for fast, targeted monitoring and operation of the system.

• Time Scheduler: Central programming of all time-controlled building services functions.

• Alarm Viewer: Provides a detailed overall view of alarms from between one and 1,000 buildings for the fast location and elimination of faults.

• Alarm Router: Flexible transmission of alarms to printers, fax machines, mobile phones and e-mail.

• Trend Viewer: Convenient analysis of trend data for fine-tuning the operation of plant.

• Report Viewer: Retrieval of values tailored to customer needs and displayed in report form. Reports are used for information, analysis of plant operation and for evaluation and documentation purposes.

• Object Viewer: An efficient tool for navigation through the hierarchical tree-structure to all the data points in the system. These points can then be read or manipulated, depending on the access rights of the user concerned.

• Log Viewer: Alarms, errors and user activities are logged in chronological order, and can be displayed for further evaluation, as needed.

• Reaction Processor: System-wide monitoring of plant and processes for certain criteria (events). If one (or a combination) of these criteria are fulfilled, the Reaction Processor initiates the appropriately preconfigured reactions. This permits central time control of plant without time scheduler/calendar functions.

• System Configurator: Used to configure the general setup of the DESIGO INSIGHT management station and the associated applications.

• Graphics Builder: Powerful tool for efficient creation of customized plant graphics.

• Open drivers, such as BACnet, OPC, KNX S-mode (EIB), LONWORKS, etc. For direct integration of various interfaces into the management station.

• Online operator tools for existing systems

Figure 6 Plant graphics in Plant Viewer

David Chen
文字方塊
★符合MICROSOFT WINDOWS技術標準,如OLE、COM、DCOM、ODBC、OPC、DNA。 ★採開放式系統設計,具CLIENT/SERVER架構多工處理(MULT1-TASKING),多人操作之32位元WINDOWS環境下執行。 ★資料儲存虛符合ODBC標準,可利用MICROSOFT SQL、HISTORIAN建立。
David Chen
矩形
Page 14: DESIGO System description - This area is password protected [401]

14 / 76

The taskbar

The shell is the first application to appear when DESIGO INSIGHT is started. It is displayed with a taskbar which provides fast and direct access to all the user applications, and displays important status information.

In the case of several remote sites, it is possible to switch from one site to another via the taskbar, subject to the appropriate access rights. This ensures clear demarcation lines between the various areas of responsibility.

Figure 7 The DESIGO INSIGHT taskbar

The user's entry into the system is simplified by user-specific start-sequences with preselected programs and plant. The icons on the taskbar provide access to the main user applications:

Connect and disconnect sites

Log in, log out, restart, lock or shut down

Plant Viewer – the graphical interface to the plant

Alarm Viewer – displays the state of abnormal alarm points

Trend Viewer – displays graphs containing live data

Log Viewer – displays all event messages including alarms

Object Viewer – shows all data points in the system, in list form

Scheduler – allows the user to modify plant switch times

Report Viewer – displays reports showing momentary values gathered and collated by the user

Reaction Processor – for automated initiaiton of process reactions across systems

Alarm Router – routes alarms to printers, fax machines, mobile phones and e-mail systems

Number of current system alarms

Online Help

Number of connected sites

Pending alarms in order of priority

Background and safety features of DESIGO INSIGHT: • Life Check feature for checking the

connection to the automation systems • Automatic DESIGO INSIGHT start and

login via Windows user login. • Alarm upload after system start • Password expiry • Check on unauthorized login attempts • User and password can be

synchronized with those of the Windows user

• Management station locked by timeout after period without user activity

• Time synchronization between management station and automation stations

• Verification of hard disk memory capacity and availability of database

• Verification of correct running of all DESIGO INSIGHT applications

David Chen
文字方塊
★資料儲存可以使用MICROSOFT ACCESS、Microsoft SQL 2005(標準中文版)建立資料庫,報表及資料庫管理。
Page 15: DESIGO System description - This area is password protected [401]

15 / 76

Plant Viewer

Plant Viewer displays the areas of a building and the associated plant in graphical form. The user works interactively with these views to monitor and control the data points throughout the building. Values can be modified and alarms can be acknowledged by clicking on the object concerned.

Plant Viewer is based on the Citect process display software supplied by Citect Pty Ltd. Citect is a world leader in the supply of SCADA systems.

Numerous windows of different sizes can be displayed simultaneously (overlapping or tiled). Even large graphics, such as floor plans etc. can be accommodated, and the freely definable page size makes them easy to view.

Figure 8

Measured values, setpoints, operating modes and alarms are displayed on the screen in real-time, and updated continuously. The form of display is determined in the engineering phase. Changes are indicated either by the object symbol (e.g. through animation or a change in shape or color), or by the movement, color, shape, or text of the values affected.

Other features of Plant Viewer: • Genuine multitasking with fully dynamic

functioning of all active pages • Object-oriented operation and

monitoring of plant • Freely definable page sizes for versatile

handling of several pages in the same screen

• Page selection via dialog box, context menu or hyperlinks

• Integrated standard page selection features based on the page naming strategy. Standard functions such as Last/Next/Top etc

• Object-oriented navigation between applications

• Definition of, and quick access to "Favorite" pages

• ToolTips for all dynamic objects, with the option of User, Technical or System Designation

• Context-specific information such as text, photos or maintenance information can be added to each dynamic symbol

• Black-and-white or color graphics printing

• Import of Windows 32-bit supported graphics file formats, such as AutoCAD and PXC

• User privileges for access to different levels

• Tools for efficient and error-free engineering

Process display

Real-time display

Page 16: DESIGO System description - This area is password protected [401]

16 / 76

Scheduler

The Time Scheduler application in DESIGO INSIGHT can be used for central programming of all time-controlled functions in the building services plant, including the individual room control system.

The facilities for graphics-based operation of the weekly schedules and exception programs enable the user to modify and optimize time schedules simply, whenever necessary.

Principal functions:

• Graphics-based overview and manipulation of all time schedules in the system

• Easy graphics-based programming of switch times

• Programs invoked directly from the plant graphics

• Logging of user activities

• Direct entry of various operating modes (e.g. Comfort, Standby, Energy Hold-off etc.)

• Storage and processing are independent of the management station

• Reports printed in different display formats

• Calendars operated via the same easy-to-use interface

Figure 9 System Browser view, and overview of daily profiles in the Time Scheduler application

Graphics-based operation

Page 17: DESIGO System description - This area is password protected [401]

17 / 76

Alarm Viewer

The Alarm Viewer application displays alarms by type, and provides the user with helpful information as to the system intervention required. With its extensive filter and search functions, Alarm Viewer facilitates fast and well-targeted access to the required information.

In larger systems with more than one management station, all management stations access the same alarm database. An alarm for any given management station is entered in this database and automatically displayed on all other management stations.

Functions in Alarm Viewer: • View, acknowledge and reset single or

multiple alarms. • Display the associated alarm property

sheet with detailed data point information.

• Read associated alarm help text with operating instructions or additional information in text form

• Object-oriented navigation to other applications, such as Plant Viewer and Log Viewer

Figure 10 Alarm Viewer

Pop-up windows

The pop-up window is an important means of attracting the attention of the user in the event of an alarm. Incoming alarms are displayed in a pop-up window that opens on the Windows desktop and appears in the foreground of all other applications (including third-party applications).

If several alarms occur, they are displayed one after the other. To further alert the user to the alarm with an audible signal, an audio file (.wav) can be added to each alarm window defined.

The appearance of the pop-up window can be varied for each alarm category. From this window, the user can invoke helpful instructions about the required response to the alarm, or jump directly to other applications such as Plant Viewer or Alarm Viewer.

Figure 11

Page 18: DESIGO System description - This area is password protected [401]

18 / 76

Alarm Router

The Alarm Router application is a highly effective feature of building automation and control. Important messages or events in the building automation and control system are transferred to specific receivers without the need for any user action at the management station. Alarm Router is a background application which starts when DESIGO INSIGHT is started, whether or not a user or site is connected. Alarms and important system events can be transferred via the following media:

• Printers • Fax machines • Pagers • Mobile phones • E-mail systems Alarms can be grouped according to various criteria. A routing table defines the conditions under which these alarm groups are to be routed to the assigned receivers. In the event of connection problems, the alarm messages can be transmitted to alternative receivers. The criteria include the following, for example:

• Time schedules and exceptions (e.g. at night, switch to the printer in the security guard's office)

• Responsibility for the site (e.g. send a fax to the company responsible for maintaining the air conditioning)

• Urgency of the alarm (e.g. only call resident engineer by pager in the case of high priority alarms)

Figure 12

Criteria for the transfer of alarms

Page 19: DESIGO System description - This area is password protected [401]

19 / 76

Trend Viewer

The Trend Viewer application is used to review current process data in real time (online) and past process data (offline) over a period of time. Trend Viewer is an easy-to-handle tool which can be used to optimize the operation of plant and reduce costs.

Activities in Trend Viewer:

• Process values and measured values logged over a period of time

• Minimum and maximum values retained in graphs irrespective of time range

• Monitoring of current plant conditions • Plant optimization and fine-tuning • Response times appropriate for the

support of large trend databases

Up to ten process values can be displayed in 2D and 3D graphs in a single trend view. Both online and offline data can be displayed simultaneously in separate windows, enabling the user to compare past and current situations.

Figure 13 Objects can be dragged from the System Browser and dropped directly into Trend Viewer

Essentially, trend data can be displayed in three different modes:

• Online trend logging: displays real-time process data which is updated whenever a change of value (COV) occurs, or as the result of a time-based scan

• Offline trend logging: displays past process data which has been uploaded to a database at the management level.

• Archive data: displays older data which has been moved from the trend database into archive files

The trend views can be saved and invoked at a later date. Online trend data is continuously logged and stored in the trend database.

Drag

Drop

Page 20: DESIGO System description - This area is password protected [401]

20 / 76

Object Viewer

Object Viewer helps users of the building automation and control system to navigate efficiently through the entire structure. The hierarchically organized data objects are easy to select, view and modify.

Object Viewer supports three different hierarchical views: • Technical View

The technical view is the plant-based standard view associated with the technical designation.

• User View The user view is based on customer-specific user designations (user addresses). The address structure and contents are defined as part of the DESIGO PX engineering process.

• System View The system view is a standard hierarchical view, representing the topology of the BACnet network, whereby a site contains devices and each device contains objects.

Technical View User View System View

Figure 14 Various System Browser views

Page 21: DESIGO System description - This area is password protected [401]

21 / 76

System Browser

The left pane of Object Viewer contains the System Browser, which displays a hierarchically structured view of the system (in a tree-structure). The right pane of Object Viewer displays the contents of the currently selected object.

Figure 15 Detailed alarm display in Object Viewer

Functions in Object Viewer:

• Fast navigation through the building automation and control system

• Fast location of objects and alarms • Detailed information on the properties of

each object • Display of real-time data from the

process • Modification of setpoints and

parameters, and manual override of outputs

• Jump functions Back / Next

• Modification and definition of object-related text

• Function with wildcarding for quick and direct access to certain objects

• Object search in other views by changing view in context-menu

• Read/Write access levels are supported.

• Object Editor: A user-friendly user interface for editing all imported objects

Page 22: DESIGO System description - This area is password protected [401]

22 / 76

Log Viewer

Log Viewer provides users with access to all events that have occurred within the system. Events and user activities are archived in chronological order in the log database and can be viewed whenever required.

The data logging system is a background service performed by the Event Handler in DESIGO INSIGHT, which continuously logs reported events as follows:

• Alarm events from the process level, such as plant alarms and high priority warnings. The alarm is logged when it occurs, and thereafter upon acknowledgment, reset and return to normal.

• System events from DESIGO INSIGHT management stations and PX automation stations. Examples are communication failures, selection procedures, start-up, shutdown, hard-disk monitoring, battery checks etc.

• User events for reporting user activities on management station. These include authorized and unauthorized user log-in procedures and the modification of values, parameters and setpoints etc.

• Status events from the process level, such as plant ON/OFF etc. The user interface of Log Viewer has the same "look & feel" as the Alarm Viewer and is based on the same versatile sort and filter functions.

Figure 16

Functions in Log Viewer:

• Query-configurations can be stored and re-used. The status bar displays the current filter and sort status

• The Log Viewer display is divided into five tabs: All, Alarm, System, User and Status, enabling the user to pre-select events of a particular category

• Columns can be flexibly rearranged, re-sized or hidden as required

• The events logged for a specific object, such as events associated with a given site, automation station or data point, can be located quickly in the left pane (System Browser).

• Logging of changes in the project configuration

• Parameter modification feature includes original parameter value

The logged data is stored on a Microsoft SQL server with password protection, or exported via SQL..

Event Handler

Page 23: DESIGO System description - This area is password protected [401]

23 / 76

The archiving function serves to remove data from the runtime databases. This is necessary firstly to create space for new data in cases where storage capacity is normally limited, and secondly, to store the data in a suitable form for retrieval at a later date. The removed data is archived in a safe location for later retrieval and display if required. Data is archived in DESIGO INSIGHT automatically on the basis of time or quantity of data accumulated, or manually by the user.

Report Viewer

Report Viewer allows the user to select an existing report template and utilize it to start the acquisition of momentary data values. A report is then created for the plant data defined in the template. The values shown are a "snapshot" of the data at the time when it was recorded. In conjunction with Reaction Processor application, it is also possible to initiate preselected reports automatically.

For documentation purposes, the on-screen reports can be printed or saved in PDF format. If exported into a CSV file, the logged data values can be evaluated in other programs (e.g. Microsoft Excel or Microsoft Access).

Filter options

In order to display only the data actually required by the user, queries can be based on filter criteria entered by the user (e.g. use of wildcards in the address mask, searches by plant, data point type, time, date etc.).

Search queries can be saved for repeated use.

Standard report templates

The following standard report templates are supplied with DESIGO INSIGHT:

• Reports on alarm and fault states (active, unacknowledged, acknowledged etc.) • Reports on log entries (alarm, system and user events) • Reports on plant states (manual control, maintenance required, measured room

values, actual values, setpoint settings etc.)

Custom reports

Report Builder is an application for customers who need to create their own report templates to take account of special requirements. The basic license does cover use of the reporting function with standard templates, but a separate license is needed for use of Report Builder. .

Log and trend data archiving

Page 24: DESIGO System description - This area is password protected [401]

24 / 76

Creating and displaying reports via the Web

A user working at a DESIGO WEB client PC can use Web Report Viewer to select existing report templates on the DESIGO INSIGHT computer and to start the logging of momentary values. The report generated in this way is displayed in DESIGO WEB and can be downloaded from the Web server to the client computer as a PDF document for saving or printing.

Reaction Processor

Reaction Processor is an event program capable of monitoring plants and processes throughout the system for the fulfillment of certain criteria (i.e. the occurrence of specific events). If one (or a combination) of these criteria is fulfilled, Reaction Processor initiates the appropriately preconfigured reactions.

Global time scheduler with calendar feature

To enable reactions to be carried out at predefined times of day (time schedules) or on particular dates (calendar/date), the management level of DESIGO INSIGHT includes a global time scheduler with calendar features. In this way, equipment and devices at the automation level can still be controlled on the basis of time or date, even if they do not have their own time schedule or calendar functions.

Entries in Reaction Processor

Every monitored event has an entry in Reaction Processor, with the following format:

If condition(s): "XYZ" fulfilled (event), then start action(s): "a,b,c" (reaction). Users themselves can define these entries in Reaction Processor.

Reaction Processor can monitor the following events: • Time:

Reaction triggered when a specific time is reached.

• Value Change of value (COV, On/Off) as the trigger.

• Combinations of date, time, value, comparison.

• Date: Date (e.g. public holiday as the trigger

• Comparison: Out-of-limits value, greater than, smaller than

Reaction Processor can trigger the following (re)actions: • Override current values in the plant

e.g. setpoint adjustment or switch-control of plant

• Start the creation of a report: Batch commands (with several steps) are also possible

• Start third-party programs Third-party programs are started via command line

• Send report to recipient X, Y or Z via file, e-mail or printer

• Delay Reactions executed after a delay

• Time Scheduler/Calendar For plant/devices without their own time scheduler/calendar functions

What events trigger reactions?

What reactions can be triggered?

Page 25: DESIGO System description - This area is password protected [401]

25 / 76

Main uses of Reaction Processor

• Reaction Processor can be used to automate repetitive routine user activities. • For plant integrated at the automation level without a time clock or time schedule,

Reaction Processor includes a global time scheduler and calendar program. • Automated open-loop and closed-loop control and switching of plant, based on the

occurrence of events monitored while the plant is running. • Automated initiation and routing of reports

Operation and monitoring with Web technology

DESIGO WEB and DESIGO Terminal Server make optimum use of the advantages of modern IT technology for the benefit of building services. Properly selected and used, they have a significant influence on the ability to fine-tune the running of the building and on the comfort and satisfaction of building users.

They distribute building information to the person who needs it, and in the exact location where it is needed. In addition to flexibility of operation, both solutions contribute substantially to a reduction in the day-to-day costs of modifications, expansion, maintenance and data backup.

Both solutions are based on leading software standards and are therefore compatible with today's IT security strategies (firewalls, Virtual Private Networks (VPN) etc.).

DESIGO Terminal Server

DESIGO Terminal Server provides all the functions of the management system in the form of terminal services over the network. These services can be accessed simultaneously by different users in independent sessions. In addition to the operation and monitoring programs for day-to-day operation of the plant, engineering tools are also provided, allowing modification and expansion of the system while it is running.

This makes DESIGO Terminal Server the optimum solution for professional property managers who need unrestricted access to building data via their intranet or extranet, from any location. All the user requires is a simple, standard network-compatible terminal device such as a PC, Net PC or Web pad with a Microsoft operating system. The terminal device must be a "Thin Client", i.e. one on which no other software components are installed.

Security is a priority: Remote access from client devices is via Microsoft Remote Desktop Web Connection with the highly encrypted Remote Desktop Protocol (RDP)5.0 which uses RSA's RC4 cipher with the option of 40, 56 or 128-bit encryption.

DESIGO Terminal Server is based on the Windows Server 2003 operating system with the Terminal Server component, and runs on standard server hardware. The hardware and software specification depends on how intensively it is used, with the number of users requiring simultaneous access being a decisive factor.

Page 26: DESIGO System description - This area is password protected [401]

26 / 76

DESIGO WEB

DESIGO WEB is a genuine Web solution based on Microsoft IIS (Internet Information Server). The programs for operation of the management system are mapped to ASPs (Active Server Pages) in special interfaces optimized for Microsoft Internet Explorer.

Functions in DESIGO WEB: • Operation of graphics (Plant Viewer) • Operation of data points (Object Viewer) • Alarms and log (Alarm Viewer, Log

Viewer)

• Trend data (Trend Viewer) • Time schedules (Scheduler)

This makes DESIGO WEB the optimum solution for those responsible for technical services (such as the house engineer, building operator or security staff) who track the daily running of the building and need easy access to all the key functions. In addition, it makes new options available, enabling selected building data and user access to be allocated relevantly to tenants and users of the building (e.g. room operation, time schedules and display of room conditions).

Figure 17 WEB Plant Viewer

Figure 18 WEB report

Page 27: DESIGO System description - This area is password protected [401]

27 / 76

Figure 19 WEB Alarm Viewer

Figure 20 WEB Scheduler

Figure 21 WEB Calendar

Page 28: DESIGO System description - This area is password protected [401]

28 / 76

Figure 22 WEB Trend Viewer

Page 29: DESIGO System description - This area is password protected [401]

29 / 76

The DESIGO PX automation level

The most striking features of DESIGO PX are the consistent openness of the system and the scalability of the system with its freely programmable automation stations and operator units. DESIGO PX reliably meets all expectations associated with the control and monitoring of building services.

A family of freely programmable operator units

Room users and building operators all benefit from an extensive range of operator units which can be used for targeted modification of room conditions or of the whole plant.

19660Z19_02 Figure 23

The right operator unit in the right place: • Monitoring and operation via PX-WEB:

In the event of faults in the plant, DESIGO PX transmits SMS messages and e-mails and allows remote diagnostics via Web client.

• For the house engineer: With optimized operator units, it is easy to check the functioning of the building services plant or to take account of changes in occupancy by modifying the comprehensive time schedules.

• For building users: Optimized operator units provide simple and direct local operation of the plant. So, for example, the room temperature in a meeting room can be adapted to individual requirements, simply and without fuss.

Page 30: DESIGO System description - This area is password protected [401]

30 / 76

Operation at the automation level PXM20 plant operator terminal and PXM20-E

The PXM20 and PXM20-E network-compatible operator terminal allows full operation of all automation stations connected to a BACnet network. As a BACnet client, the PXM20 automatically reads the data from the automation stations. It is therefore always up to date and can be replaced while the system is in operation.

The operator terminal has a high-resolution illuminated display for graphics and text, keys for operation, and a common alarm indicator with an audible signal. It can be installed remotely in a control panel door to operate compact and modular automation stations, or it can be plugged directly into a modular automation station.

The clearly arranged function buttons and fast access buttons ensure correct operation, even by inexperienced users.

PXM20 operator unit

Graphics-based heating curve display Alarm summary

Online trend Time scheduler

PXM20 operator functions • Alarm monitoring with acknowledgement

and visual and audible alarm indication • Data point display and operation of all

measured values, setpoints, plant states, operating states and parameters

• Graphics-based display and operation of time schedules, exception calendar, online-trend and heating curve

• User-friendly guidance through the plant functions

• Favorites, configurable overview of main values in the plant

• Multi-level access protection

Types PXM20 Operator unit, communication over LonTalk

PXM20-E Operator unit, communication over Ethernet/IP

Page 31: DESIGO System description - This area is password protected [401]

31 / 76

PXM10 plant operator terminal

The PXM10 operator terminal allows full local operation of a DESIGO PXC automation station. The unit incorporates user-friendly "one-button" operation and a high-quality display panel.

The PXM10 can be installed remotely in a control panel door to operate compact and modular automation stations, or it can be plugged directly into a modular automation station.

PXM10 operator unit Setpoint and measured value display

Alarm display Scheduler

PXM10 operator functions

• Display of measured values, setpoints, plant states and operating modes

• Setpoint adjustment where required • Visual alarm display

• Alarm display with scope for acknowledgement

• Graphics-based display of time schedules

Page 32: DESIGO System description - This area is password protected [401]

32 / 76

DESIGO touch panel

The touch panel ensures convenient operation and display of complex building services plant. With its fast start-up, it is always ready for use. With a Windows CE operating system and a sturdy design requiring neither a hard disk, nor a fan, the touch panel is equally suitable for control panel mounting and room installation. The time required to train staff is less than with conventional technology.

Functions of the DESIGO touch panel • Maximum flexibility, and optimum

assistance for users of the technology • Easy to add new operator controls and

functions • Versatile guidance of users in the event

of alarms

Figure 24 DESIGO touch panel

Page 33: DESIGO System description - This area is password protected [401]

33 / 76

QAX… room operator units

Up to five bus-compatible QAX... room devices can be connected to the PPS bus of each automation station. The various options include:

• Digital display options • Status display • Plant switching functions

QAX30.1 QAX31.1 QAX32.1 QAX33.1 QAX34.1 QAX84.1/PPS22)

Function overview QAX30.1 QAX90.11)

QAX31.1 QAX91.11)

QAX32.1 QAX33.1 QAX34.1 QAX84.1/PPS22)

Room temperature sensor • • • • • • Setpoint correction • • • • • Operating mode switch • • • • Fan speed switch • • • LCD display for room temperature, setpoint adjustment and operating mode

• •

1) Wireless room unit 2) Flush-mounted room unit

Page 34: DESIGO System description - This area is password protected [401]

34 / 76

Web operation with PX-WEB

With its integrated Internet technology, the embedded Web server allows full operation of the plant associated with the PXC, PXR and PXE automation stations by use of a standard Web browser. The operating concept and functional scope are like those of the PXM20.

PXC..-U modular automation station Web server, PXG80-W / WN Operation and display via Web client (touch panel)

Main functions of PX-WEB:

• Operation via Web browser or mobile clients (mobile phone, PocketPC or PDA)

• Simple plug-and-play functions; no engineering needed

• User-friendly guidance through the plant functions

• Full access to all measured values, setpoints, plant and operating states, and parameters

• Comprehensive data point operation and setpoint entry using clear text

• Alarm management via SMS (to specified telephone number) or by e-mail

• Operation of time schedules, exception calendar and heating curve graph

• Reading of trend data, with the facility to export data to Microsoft Excel for evaluation purposes

• Collation of main values via "Favorites" • Support of multiple level access

protection • Facility to display additional plant

graphics • Modem and Ethernet version available

PX-WEB type summary

PXG80-W Web client access via analog or ISDN modem, or null modem. Alarms via SMS

PXG80-WN Web client access via Ethernet/IP Alarm handling via SMS and e-mail

PXC…-U + PX30-W1 Web client access via Ethernet/IP to all automation stations connected to a BACnet network; alarms via SMS and e-mail, generic Web functions/operation

PXC…-U + PXA30-W0 or PXA30-W2

Web client access via Ethernet/IP to the connected automation station (with PXA30-W0) or (with PXA30-W2) to all automation stations connected to a BACnet network; alarms via SMS and e-mail, graphics-based Web functions/operation

Page 35: DESIGO System description - This area is password protected [401]

35 / 76

Plant operation Alarm Viewer

PXM20

E-mail BACnet / IP

BACnet / LonTalk

PXG80-W

PXC...-E.D

Ethernet / IP

DESIGO INSIGHT

PXC...-T.D

Web clientMobile phone

Telephone line

PXC...-Uwith PXM20-E

TX-I/O modules

PXC...-Uwith PXM20

PXC...-Uwith PXM20

PTM-I/O modules TX-I/O modules

PX WEB

1066

0Z02

en_0

2

PX WEB

Web topology

Page 36: DESIGO System description - This area is password protected [401]

36 / 76

A family of freely programmable automation stations

With its modular system design, DESIGO PX can be ideally adapted to specific requirements and needs, making cost-effective DDC technology a possibility even in small HVAC systems. Whether for new buildings or modernization projects, investment costs are limited to the system components that are actually needed. This innovative system strategy allows phased expansion of DESIGO PX into a building automation and control system as and when required.

DESIGO PX is based on industry standards designed not only for the present but also for communications technologies. BACnet / LonTalk or Ethernet IP are not mere "buzzwords" to us. On the contrary, they emphasize the openness of our systems and our use of the latest communications technology for maximum overall efficiency. Our consistent and coordinated use of standard technologies ensures straightforward and cost-effective integration of third-party systems and components.

Figure 25

Modular system for universal application

BACnet communications for maximum openness

Page 37: DESIGO System description - This area is password protected [401]

37 / 76

Automation stations – compact series

The mounting technique and fixed configuration of integrated I/Os in the compact–series automation stations make them ideal for control of small and distributed plant.The I/Os in these automation stations can be adapted to various types of signal.

The automation stations are installed directly in the control panel.The operator units are connected to the BACnet automation bus or via the PPS bus or HMI port.

PXC22-E.D automation station PXC52 automation station

Types

BACnet/LonTalk PXC12.D PXC22.D PXC236.D PXC36-S PXC52

BACnet/LonTalk and modem connection

PXC12-T.D PXC22-T.D PXC36-T.D PXC10-TL

BACnet/IP PXC12-E.D PXC22-E.D PXC36-E.D

I/O Total 12 22 36 36 52 10

UI 4 12 18 12 16 4

DI 2 0 4 12 16 4

AO 4 4 6 6 8 0

DO 2 6 8 6 12 2

I/O configuration of the compact-series automation stations

UI Universal inputs, which can be connected to passive (LG-Ni 1000) and active (DC 0…10 V) sensor elements, or to binary volt-free contacts, for signaling functions. Additional option of 20 Hz counters with PXC…D.

DI Binary-only inputs for signaling functions. PXC10TL, PXC36-S and PXC52 also offer the option of counter functions (max. 4 x 20 Hz counters per PXC… device).

AO Analog outputs for the connection of 0 … 10 V actuators or for binary control. Via the program structure, analog outputs can also be programmed as binary switch functions and connected to 24 V/20 mA loads.

DO AC 230 V / 2A relay outputs for binary control

Ports/interfaces

PPS2 For the connection of up to 5 QAX3… room units

BACnet/ LonTalk For BACnet communications over LonTalk (depending on type)

BACnet//IP BACnet communication over Ethernet/IP (depending on type)

Tool/HMI For operator unit or DESIGO tools

Ethernet/IP BACnet PTP communication (point-to-point)

The PXC36-S automation station also incorporates built-in manual switches and additional LED indicators. The manual controls, with switch positions "Auto/Stop/Manual" or "Auto/0/1/2" can be used for direct switch control of actuators or, in software, for other user-definable purposes.

Page 38: DESIGO System description - This area is password protected [401]

38 / 76

The PXC10-TL automation station is additionally optimized for wall mounting and has a built-in 230 V supply, and freely-programmable LED buttons.

The PXC…-T.D automation stations for direct modem connection provide for remote control and alarm functions with DESIGO INSIGHT.

Automation stations – modular series

The modular-series automation stations with their flexible I/O configuration are primarily used for the control and monitoring of larger items of plant. The complete range of input/output modules, for signaling, measuring, counting, switching and positioning, supports all common types of signal.The I/O modules with local manual controls on the module housing provide the plant operator with simple manual operation of the plant directly in the control panel.This local manual control is automatically transmitted as a remote/local signal to the automation station and associated operator units.In an emergency, they operate independently of the automation station, providing stand-alone emergency operation.

Where necessary, the modular automation station can be fitted with an extension module for direct connection of a modem to allow remote management and alarm handling in conjunction with DESIGO INSIGHT or PX-WEB.

By use of special extension modules, the modular automation station can also be used as a system controller.

PXC...-U modular automation stations Extension module PXA30

Overview of automation stations

PXC64-U Modular automation station with 64 load units for the connection of DESIGO I/O modules

PXC128-U Modular automation station with 128 load units for the connection of DESIGO I/O modules

PXC00-U System controller

Automation station ports/interfaces

PPS2 For the connection of up to 5 QAX3… room units to the PXC64/128-U BACnet/LonTalk For BACnet communications over LonTalk between automation stations BACnet/IP For communication between the automation stations with BACnet/IP – via extension

module P-Bus Connection for I/O modules to the PXC64/128-U Tool/HMI For operator unit or DESIGO Tools

Page 39: DESIGO System description - This area is password protected [401]

39 / 76

Types of extension module for automation stations and system controllers

PXA30-T Extension module for remote management

PXA30-N Extension module for Ethernet/IP

PXA30-<Enter> Extension module for Ethernet/IP and remote management

PXA30-W0 PX-WEB extension module for Ethernet/IP, remote management, SMS, e-mail and alarm functions, with graphics-based Web functions for the automation station fitted with the module.

PXA30-W1 PX-WEB extension module for Ethernet/IP, remote management, SMS, e-mail and alarm functions, with graphics-based Web functions for all automation stations connected to a BACnet network.

PXA30-W2 PX-WEB extension module for Ethernet/IP, remote management, SMS, e-mail and alarm functions, with graphics-based Web functions for all automation stations connected to a BACnet network.

Overview of the extension-module functions PXA30-T PXA30-N PXA30-

<Enter> PXA30-W0 PXA30-W1 PXA30-W2

Remote Management • • BACnet/IP • • • • • Send SMS •2) • • Send e-mail •1) 2) •1) •1) Generic Web function •1) 2) •1) •1) Graphics-based Web function

•1) 2) •1)

1) Only one mode of communication: Either DESIGO INSIGHT PTP or Web PPP 2) For the automation station fitted with this module

Additional extension modules for the PXC00-U system controller

PXA30-RS… Extension module in PX OPEN for RS232/RS485 interface PXA30-RS supports 100 data points PXA30-RS1 supports 400 data points PXA30-RS2 supports 2,000 data points

PXA30-K11 Extension module for the connection of RXB/RXL, Synco 700 and KNX S-Mode (EIB) third-party devices

Page 40: DESIGO System description - This area is password protected [401]

40 / 76

The field level: the DESIGO TX-I/O™ modules

The DESIGO TX-I/O modules represent the interface to the devices at the field level, the sensors and actuators. The I/O modules are connected to the DESIGO PX modular automation stations and can be interconnected in application-specific configurations.

A versatile range of compact TX-I/O modules is available, with a small footprint for signaling, measurement, counting, switching and positioning. The I/O module system with its DIN-compliant design is optimized for installation in control panels.

The TX-I/O modules provide information on the the status of the plant either by LED, or on an optional LCD panel with pictograms for signals and warnings. Some, depending on type, have controls for manual or emergency operation.

The integrated isolating-terminals facilitate the hardware test carried out during commissioning.

Within a plant, the DESIGO TX-I/O modules can be combined without difficulty with the proven PTM modules.

For the user, the advantages of the DESIGO TX-I/O modules are as follows: • Integrated isolating-terminal feature • Integrated manual controls (optional) • Integrated diagnostic functions with

LEDs and optional LCD panel • Optimized for HVAC actuators and

sensors • DIN-compliant construction, optimized

for installation in the control panel • Streamlined, versatile range for

optimum logistics

• Modules labeled in plain text • Tool support for configuration,

diagnostics and function testing • Third-party system integration with

PTM5... DESIGO I/O OPEN modules for M-bus meters, pumps (GRUNDFOS, WILO), packaged air conditioning units (MENERGA) and variable speed drives (Siemens SED2)

Figure 26 DESIGO I/O modules with integrated isolating terminal feature and optional manual controls

DESIGO I/O OPEN allows the integration of third-party products such as pumps, M-bus meters, compact air conditioning units and variable speed drives. If pumps are connected, for example, access is available to the following information:

• Control of operating mode • Setpoint adjustment • Normal operation and fault code • Delivery head • Capacity • Speed

Page 41: DESIGO System description - This area is password protected [401]

41 / 76

Overview of TX-I/O modules

Type

TXM

1.8D

TXM

1.16

D

TXM

1.8U

TXM

1.8U

-ML

TXM

1.8X

TXM

1.8X

-ML

TXM

1.6R

TXM

1.6R

-M

Total number of inputs/outputs 8 16 8 8 8 8 6 6

Functionality

Local override facility − − − ● − ● − ●

LCD panel − − − ● − ● − −

3-colour I/O status LED ● − − − − − − ●

Green I/O status LED − ● ● ● ● ● ● −

Digital inputs (DI) Status indication (N/O or N/C) ● ● ● ● ● ● − −

Signal pulse ● ● ● ● ● ● − −

10 Hz counter (with debounce) ● 1…81) – – – – − −

25 Hz counter (bounce-free) − − ● ● ● ● − −

Analog inputs (AI) LG-Ni1000 − − ● ● ● ● − −

Pt1000 / 0...2500 ohms − − ● ● ● ● − −

T1 − − ● ● ● ● − −

DC 0...10 V − − ● ● ● ● − −

4...20 mA / 0...20 mA − − − − ● ● − −

Analog outputs (AO) DC 0...10 V − − ● ● ● ● − −

4...20 mA − − − − 5…82) 5…82) − −

Digital outputs (DO) Maintained contact, on/off − − − − − − ● ●

Maintained contact, 3-stage − − − − − − ● ●

3-position output − − − − − − ● ●

On/off pulse − − − − − − ● ●

Pulse − − − − − − ● ●

Pulse (3-stage) − − − − − − ● ●

1) The counters on the TXM1.16D module are on inputs 1 to 8 2) The 4…20mA outputs on the TXM1.8X.. module are on I/O points 5 to 8.

For I/O OPEN integration projects and for Pt100 sensors, the DESIGO PTM-I/O modules should be used. These can be used in parallel with DESIGO TX-I/O modules.

Page 42: DESIGO System description - This area is password protected [401]

42 / 76

Room automation: DESIGO RX Convenient room automation with DESIGO RX

DESIGO RX is a modern range of room controllers and room units suitable for both stand-alone operation and for communication over a network. The room controllers control and monitor thermal comfort conditions in rooms and self-contained zones while ensuring maximum energy efficiency in these spaces.

The DESIGO RXB and DESIGO RXC families of controllers represent a lasting investment in the future. They make consistent use of open communication protocols, namely LONWORKS and KNX S-mode (EIB). This is how we ensure that the room automation system is easy to expand or modify in the event of a change in use. The RXL family completes the range with an economical room solution for DESIGO.

Easy control of HVAC, lighting and blinds

The modular design of DESIGO RXC combines lighting and blinds with the HVAC control system. With a single room unit, users can adjust all the room functions to individual requirements.

The right solution for every network

DESIGO RXC uses the standard LonWorks protocol for communication, is LONMARK-compatible and can be combined with other LONMARK-compatible devices.

DESIGO RXB uses KNX S-mode (EIB) for communication, and can be combined with other KNX-S-mode (EIB) compatible equipment.

Further, with DESIGO RXL, a range of communicating room controllers with a proprietary DESIGO bus is now available.

The seamless integration of DESIGO RX into the DESIGO building automation and control system provides easy access to the additional functions of building management.

01715

M

Figure 27 Integrated operation of HVAC, lighting and blinds with DESIGO RXC

Page 43: DESIGO System description - This area is password protected [401]

43 / 76

Range overview – DESIGO RXC

DESIGO RXC is a comprehensive range of room controllers for HVAC automation, extension modules for lighting and blinds, and a graded range of tailor-made room units. DESIGO RXC uses LONWORKS technology for data communications.

The DESIGO RXC hardware

The range comprises compact and modular room controllers, easy-to-operate room units, and controllers in room-style housings.

RXC20.1RXC21.1RXC22.1

RXC32.1*

RXC10.1

QAX3...QAX8...QAX9...

RXC30.1RXC40.1RXC41.1

RXC31.1RXC40.1RXC41.1

QAX50.1QAX51.1

10660Z01en

Elec

tric

alH

VAC

Fan coil unit

Radiator

Chilled ceiling

Blinds

Lighting

Room units

modularcompact

Room controllers

Standardwireless

VAV

Controller inroom-stylehousing

flexible

Figure 28 * RXC32.1 not available in Germany (RC-DE)

The DESIGO RXC software

Each room controller contains downloadable application software (referred to as the "application") with the optimum control programs for the room or area concerned.

Siemens Building Technologies maintains a comprehensive library of reliable, field-proven applications for HVAC and electrical applications.

Page 44: DESIGO System description - This area is password protected [401]

44 / 76

The room controllers

This room controller is a cost-effective combination of a room unit and an HVAC controller for simple temperature control.

RXC20.1, RXC21.1, RXC22.1 and RXC32.1 compact controllers

These room controllers have an AC 230 V operating voltage and are ideal for fan-coil applications, radiators and chilled ceilings. The RXC32.1 controller is particularly suitable for standard single-duct VAV systems. It comes with a built-in volume sensor.

RXC30.1 and RXC31.1 modular controllers

These room controllers for VAV, radiators and chilled ceilings are can be extended with connectable modules (RXC40 and RXC41) for lighting and blinds.

Range overview – DESIGO RXB

DESIGO RXB is an innovative range of room controllers and room units. Data communications are based on KNX S-mode technology (EIB).

The DESIGO RXB devices are Konnex Association-certified and are processed with the ETS engineering and commissioning tool.

The DESIGO RXB hardware

The range consists of compact controllers, controllers in a room-style housing and room units for HVAC operation.

RXB21.1RXB22.1 QAX3... , QAX9... ,

QAX8...

RXB10.1

e.g. DELTA profil

10660Z20en_01

VAV

Chilled ceilings

Radiator-type heating

Lighting

Blinds

Fan coil units

HVA

CEl

ectr

ical

EIB/KNX componentselectrical applications

Figure 29

RXC10.1, the controller in a room-style housing

Page 45: DESIGO System description - This area is password protected [401]

45 / 76

The DESIGO RXB software

Each DESIGO RXB device is loaded with a software module (referred to as the "application") containing the application software for a group of HVAC applications. The required application is enabled in the commissioning phase.

Siemens Building Technologies maintains a comprehensive library of reliable, field-proven applications for HVAC applications.

RXB10.1 controller in room-style housing

This room controller is a cost-effective combination of room unit functions and HVAC control. It supports radiator-and-chilled-ceiling applications, and simple VAV systems.

RXB21.1 and RXB22.1 compact room controllers

The input/output configuration of these room controllers is optimized for fan-coil application. The controllers can be installed in the fan coil unit, in control panels or on ducting. These controllers also communicate with the Synco 700 control system.

Range overview – DESIGO RXL

These controllers also communicate with the Synco 700 control system.

DESIGO RXL is an innovative range of room controllers and room units for cost effective room management solutions. Data communication is based on a proprietary DESIGO bus which provides the transition to BACnet. DESIGO incorporates a whole range of integrated functions including time scheduling, trend, heating/cooling demand, central control of setpoints and numerous other features. DESIGO RXL thus fits into the overall expandable modular system, ensuring long-term cost-effectiveness.

Commissioning and parameter-setting of the RXL controllers is carried out with the ACS software tool or directly on the controller via the QAX34.3 room operator unit. The parameters can be set via the room unit without the need for a network connection.

The Service LED shows the operational status of the room controller at all times.

The DESIGO RXL hardware

The range consists of the RXL compact controllers and type QAX3…, QAX8…, QAX9… room units for HVAC operation.

RXL22 room controller QAX34.3room unit

Page 46: DESIGO System description - This area is password protected [401]

46 / 76

RXL21.1 and RXL22.1 compact room controllers

Each of these room controllers is loaded with wide-ranging standard applications for fan-coil systems. The required application is enabled in the commissioning phase.

The room unit: the key to individual comfort

The QAX.. room units cover a wide spectrum of possible operating scenarios. The range includes units which measure the room temperature and allow setpoint adjustment, operating mode selection or fan-speed control and an LCD display. The QAX9.. room units are wireless devices.

Special value has been placed on the design of the room units and to the ergonomic principles associated with operation.

Examples from the QAX3… range QAX34.3 QAX84.1/PPS2 QAX50 range

The QAX84.1/PPS2 room unit is based on the QAX34.1 unit (identical software and LCD) and is a flush-mounted variant. Thus, the unit can be used with the electrical frames of other manufacturers and still satisfies highest design standards.

The QAX5…integrated room unit operates with LONWORKS and combines the operation of HVAC, lighting and blinds in a single device. The keypad can be configured with the combination of buttons and switches best suited to the application.

Page 47: DESIGO System description - This area is password protected [401]

47 / 76

Applications

The field-proven downloadable applications make DESIGO RX highly versatile. An extensive range of standard applications is available for fan-coil units, VAV, radiators and chilled ceilings.

The control parameters are matched to the relevant room at the commissioning stage.

Examples of integrated applications for DESIGO RXC

The HVAC applications covered by the basic controllers RXC30.1 and RXC31.1 can be combined with control of lighting and blinds.

Electrical function

Lighting zone Blind

Application HVAC application

On/Off Dimming control Up/Down

INT01 CLC 2 x

INT03 CLC 2 x 2 x

INT05 CLC 2 x 4 x

INT15 VAV 2 x 2 x

INT17 VAV 2 x

CLC: Chilled ceiling and radiator-type heating

VAV: Variable air volume system

T

LON

70225

Controller + extension modules

Page 48: DESIGO System description - This area is password protected [401]

48 / 76

Integration into the building management system

PXC...D

PXR...

PPS2

PXM20

BACnet / LonTalk

RXC... QAX5...

PPS2

QAX...

LonWorks

RXC...

RS232

PXC...-U

BACnet / Ethernet / IP

PXM10QAX...

RXB...

PXA30-K11RS232

PXM10

DESIGO INSIGHT

PXC...-E.D

Bus

RXL... Synco 700

Synco 700

PXA30-K11

PXG80-WN

PPS2

QAX...

PXA30-N

BACnet routerPXG80-N

PXC00-Uwith PXM20

Web client

PXC00-Uwith PXM20

TX-I/O modules

LONWORKSThird -party

KNX / EIBThird -party

1066

0Z03

en_0

2

KNX S-mode / EIB

PX-WEB

Figure 30

Stand-alone operation at field level

The room automation system performs its control tasks and communicates autonomously over the LONWORKS bus or KNX S-mode (EIB) bus.

Further, with DESIGO RXL, a range of communicating room controllers with a proprietary DESIGO bus is now available.

Page 49: DESIGO System description - This area is password protected [401]

49 / 76

Integration into the automation level

Freely programmable automation stations with a LONWORKS or KNX interface connect the DESIGO RX room automation system into the building automation and control system, at the same time making other functions available.

• Conversion of LONWORKS objects or KNX objects into BACnet objects • Interface to BACnet for networks with RXL room controllers • Concentration of room data and simple operation • Grouping for optimization across rooms • System functions and optimizer software such as time schedules, trends, alarm

generation etc. • Coordination with the primary plant • Safety functions, e.g. in the event of storm warnings

Integration into the management level

Automation ensures that all data and functions of the room automation system can also be viewed and operated at the management level.

The control and operation of the RX devices with DESIGO INSIGHT opens the way to a range of additional functions including the following:

• Operation and monitoring of rooms via plant graphics • Logging and archiving of trend data • Time schedules for building use and room occupancy • Central control and override of setpoints, operating modes, lighting, blinds etc.

Page 50: DESIGO System description - This area is password protected [401]

50 / 76

DESIGO OPEN

DESIGO OPEN focuses specifically on consistent open communications throughout the system; in other words, it promotes the simple connection of a wide variety of building services on the basis of standard open data interfaces. For this purpose, DESIGO OPEN offers a portfolio of solutions for cost-effective integration of third-party systems and devices.

These quality solutions have the following outstanding project-specific and user-specific features:

Features:

• Management functions across system boundaries

• Uniform user-interface • Full integration of third-party systems

into the building automation and control system

• Use of recognized standard communication protocols and powerful standard integration platforms

• Expansion and replacement of individual components at any time

• Optimum cost/benefit ratio for operation and maintenance.

• Technical support throughout the entire project cycle for long-term investment protection

The levels of the building automation and control system model provide an important basis for integration.

• Management level with operation and monitoring, and data maintenance • Automation level with direct process control of the primary plant • Field level with terminal unit process control and sensors/actuators.

PXC...I/O OPEN

RS232RS485

RS232

DESIGO INSIGHT

PXA30-K11

SX OPC

PXR11/ PXR12

LONWORKS

PXA30-RS

10660Z04en_02

PXC64-Uwith PXM20...

ModbusM-busThird-party system

Third-party

Third-party

Peer-to-peer communicationover BACnet

RXB / RXLRoomcontroller

OPCThird-party

KNX / EIBThird-party

LONWORKSThird-partyRXC

Roomcontroller

PXC00-Uwith PXM20...

Fiel

d le

vel

Aut

omat

ion

leve

lM

anag

emen

t lev

el

KNX S-mode / EIB or bus

Synco 700

Third-partyBACnet

Possible PXA30-N

Possibleadapter

BACnet / LonTalk or BACnet / IP

Possiblerouter

Possiblerouter

Possiblerouter

Possible PXA30-NPossible PXA30-N

PXC00-Uwith PXM20...

PTM-I/Omodules

TX-I/O modules

Figure 31

Page 51: DESIGO System description - This area is password protected [401]

51 / 76

The management level: INSIGHT OPEN

INSIGHT OPEN is a modern integration platform for direct connection to the management level which uses vendor-neutral visualization systems based on SCADA technology. SCADA (Supervisory Control and Data Acquisition) systems are software products from the field of industrial automation, and can be used to connect various automation systems using a variety of device drivers.

SCADA technology is ideal for connecting stand-alone third-party systems or open automation buses and field buses, where the emphasis is on operation and display rather than on reliable cross-disciplinary interconnection. Vertical connections are implemented with communication cards or system-specific interfaces plugged directly into a management system PC. INSIGHT OPEN makes use of the technological potential of Citect, a leading SCADA system supplied by Citect Pty Ltd. Australia.

INSIGHT OPEN is an adjunct to the DESIGO INSIGHT management station and provides the following functions for the integrated third-party system or device:

Functions in INSIGHT OPEN: • Graphical operation of the plant and the

process • Alarm display and operation • Dynamic trend curves and long-term data

storage

• Operation via data point topology in Object Viewer

• Log book and message archiving • Alarm routing to message receivers • Access protection

In networks, INSIGHT OPEN runs on Windows 2000 or Windows XP.

INSIGHT OPEN provides an OPC client (OLE for process control) for the connection of third-party systems. This supports the specifications of Data Access Version 1.0a and Version 2.0.

As a consequence, INSIGHT OPEN is an integral component of the process control system and subject to the same high expectations in respect of reliability and minimum downtime.

The process values transferred from third-party systems to the DESIGO INSIGHT management station are mapped as SCADA process variables, or "variable tags". Special tags are used for alarm and trend variables:

• Alarm tag, alarm process variable • Trend tag, trend process variable Unlike the data points in the building automation and control system, the process variables (tags) each contain one item of information only. Alarms and trend logs are SCADA objects which are generated by and calculated in the I/O server.

Vendor-neutral protocols: Vendor-specific protocols • BACnet • LONWORKS • KNX S-mode (EIB) • Profibus

• SIMATIC S7, S5 • SIPORT NT (access control) • AlgoRex (fire detection system)

SCADA technology

Page 52: DESIGO System description - This area is password protected [401]

52 / 76

DESIGO SX OPEN

SX OPEN is an innovative integration platform used to connect OPC-based third-party systems to an open BACnet network. SX OPEN forms a powerful bridge between OPC, and BACnet by replicating an OPC client in OPC and a BACnet server on BACnet.

The functions extend far beyond simply mapping and transfer of OPC items to BACnet. For example, the freely programmable level of SX OPEN, at which functions can be interconnected, allows the following:

• Direct mapping of OPC items to BACnet objects, for display and operation by BACnet clients

• Grouping of OPC items to create standard integrated BACnet objects • Event-driven transfer of alarms in the BACnet network • Peer-to-peer communication with other BACnet servers

SX OPEN is especially suitable for the integration of OPC-based third-party systems where there is a need to interconnect functions locally (peer-to-peer communication). It fully compensates for the disadvantages of simple SCADA technology.

The modular software package can be run on standard PC systems with Windows operating systems. Industrial control-panel PCs with no rotating parts (e.g. Siemens micro box) offer reliability, easy maintenance and minimal down time.

Features • BACnet server to BACnet 135-2004

with BACnet/IP • Data objects supported: Analog Input

and Output, Binary Input and Output, Analog and Binary Value, Multistate Input, Output and Value, Device, Notification Class

• Read and write access in accordance with BACnet rules of priority

• OPC Client Data Access 2.05a

Vendor-neutral protocols Vendor-specific protocols, e.g.

OPC server with data access for

• LONWORKS • KNX S-mode (EIB) • M-bus • Modbus • PROFIBUS

• OPC server with data access for third-party systems (e.g. BMA, EMA, access control, video, industrial PLCs, other)

Page 53: DESIGO System description - This area is password protected [401]

53 / 76

The automation level: PX OPEN

The native BACnet automation station DESIGO PX OPEN is a multifunctional integration platform used to connect third-party automation stations and open field-bus networks to the BACnet network.

PX OPEN is a family of various types of device:

• PX LON for the connection of LONWORKS devices, LONWORKS networks and the DESIGO RXC room automation system

• PX Modbus, PX M-bus and PX SCL for the connection of Modbus, M-bus or simple ASCII protocols for RS232 or RS485 (free SCL programming)

• PX KNX for the connection of KNX S-mode (EIB) devices, KNX S-mode (EIB) networks and the DESIGO RXB and RXL room automation systems, and Synco 700

The data points of the third-party are mapped to input/output functions in BACnet and are then available as fully communicating data points for further processing and further connection, e.g. for:

• Alarm handling and prioritization • Override control, priority control and commands for central operation • Grouping • Time schedules • Trend logging PX OPEN integrates up to 2000 items of information per device. The bi-directional exchange of data is event-driven, i.e. the systems only exchange information if the data point changes. Peer-to-peer communication can be implemented without difficulty in the BACnet network

The PX OPEN integration stations are positioned in a flexible configuration in the BACnet network and can be operated via the local LCD operator units.

"Simple" protocols based on ASCII strings can be connected directly to PX OPEN by use of SCL (Structured Control Language) in conjunction with a freely programmable RS232 or RS485 port.

Vendor-neutral protocols: Vendor-specific protocols • BACnet • LONWORKS • KNX S-mode (EIB) • M-bus • Modbus

• Hotel management: Fidelio • AlgoRex (fire detection system)

Page 54: DESIGO System description - This area is password protected [401]

54 / 76

DESIGO PX BACnet server As an open, native BACnet system, compliant with BACnet standard 135-2001, DESIGO PX is a high-end BACnet server, suitable for connection to higher level BACnet management systems. Each DESIGO PX automation station represents a complete, independent BACnet server in the network.

Technical features: • Open, native interface based on ISO

16484-5, optionally with BACnet/IP, BACnet/LonTalk or BACnet/PTP, depending on device

• European character set ISO 8859-1 • Data objects supported: Analog Input

and Output, Binary Input and Output, Analog and Binary Value, Multistate Input, Output and Value, Schedule and Calendar, Trend Log, Device, Notification Class

• Follows the B-BC device profile (freely programmable controller)

• Up to 1600 simultaneous BACnet COV subscriptions (simultaneous event-driven requests by BACnet clients for values)

• Read and write access in accordance with BACnet rules of priority

• The data points are read with an EDE data point list , and transferred to third-party systems

DESIGO PX automation station

The DESIGO PX automation station has been tested for BACnet compliance, and is authorized to bear the BTL mark issued by the BACnet Testing Laboratory.

DESIGO PX is listed as a BTL-tested device on the BIG EU Web site.

DESIGO PX OPC server

As an open, native BACnet system, DESIGO PX can be set up as an OPC server by use of additional drivers (BACnet Client/OPC Server). A higher-level OPC client of a third-party system then has read and write access to the automation station.

Due to technological constraints when mapping BACnet to OPC, usually only the main BACnet objects are mapped, together with between three and five of their main properties. This is because each individual item of information has to be set up in the OPC as a separate OPC item. Although access to major BACnet objects such as the Scheduler, Calendar and Trend Log is set up in the OPC server, these are not normally implemented in the higher-level OPC client, and can only be implemented at high cost. In respect of functionality and economic efficiency, direct integration with BACnet is always preferable.

OPC

Page 55: DESIGO System description - This area is password protected [401]

55 / 76

PX LON

PX LON connects LONWORKS networks to DESIGO and maps LONWORKS network variables to BACnet data points.

Main functions of PX LON: • Compression of DESIGO RXC room

controller and third-party device data • Maps DESIGO RXC applications to

BACnet for operation and monitoring (grouped as HVAC, lighting and blind control functions)

• Higher-level control and optimization functions, such as room and zone-based groups, time control, and system functions such as changeover, summer/winter compensation etc.

• Alarm handling, device monitoring • Trend storage

PX LON maps RXC applications in such a way as to produce a room view. This enables the rooms to be grouped together, for shared occupancy programs, or for shared commands for the control of lighting or blinds, for example.

PX M-bus

PX M-bus connects the M-bus consumption meters to the DESIGO system and maps meter readings and device-related meter information to BACnet data points.

Main functions of PX M-bus • Measurement of consumption data and

remote monitoring of max. 250 consumption and heat meters or up to 2,000 BACnet I/O objects

• Compression of data from consumption and heat meters at the automation level

• Alarm handling, device monitoring • Trend storage to record meter readings

PX Modbus

PX Modbus connects Modbus devices or networks supporting the Modbus protocol as specified by Modicon to the DESIGO system and maps their data points to BACnet data points. PX Modbus is particularly suitable for integrating industrial controls or chillers and linking them to the automation process.

PX KNX

PX KNX connects KNX S-mode (EIB) networks to DESIGO and maps KNX S-mode (EIB) group addresses to BACnet data points.

Main functions of PX KNX • Compression of the data from the

DESIGO RXB room controllers and other KNX data points at the automation level

• Mapping of DESIGO RXB, RXL, Synco 700 and other KNX applications to BACnet for operation and monitoring (grouped as HVAC, lighting and blind control functions)

• Higher-level control and optimization functions, such as room and zone-based groups, time control, and system functions such as changeover, summer/winter compensation etc.

• Alarm handling, device monitoring • Trend storage

Page 56: DESIGO System description - This area is password protected [401]

57 / 76

DESIGO tools and software blocks

Professional software tools and a wide range of proven application blocks are available for engineering and processing the automation stations. The programming language D-MAP is optimized for building services applications.

DESIGO tools

The DESIGO tools suite consists of the following components:

• Management of project data, creation of system topology and selection of automation stations (System Design or XWORKS Manager)

• Programming and commissioning (PX Design) • Commissioning of the BACnet routers (Router Design) DESIGO tools include project management functions such as the setting up and archiving of projects and the storage and relocation of project data for the commissioning phase. The tools are also used to define the network topology, and to design room automation systems and the integration of third-party systems.

PX Design consists of tools which can be used in conjunction with the block library for the programming of individual solutions, and for parameter setting and commissioning. The CFC (Continuous Function Chart) Editor is used as a basis for this work.

Router Design is used to configure the BACnet routers in the system.

Figure 33

Designed for technical work on customer projects, the user-friendly DESIGO software utilities are easy to use. They include planning, configuration, final adjustment and commissioning of the automation station with the associated program. A variety of report functions are available for documentation purposes.

Page 57: DESIGO System description - This area is password protected [401]

58 / 76

Programming with D-MAP

The D-MAP programming language (= DESIGO Modular Application Programming) for DESIGO PX ensures efficient programming and parameter setting for building services plant. D-MAP is optimized for building services applications. The control strategies required for and best suited to efficient operation are implemented using graphics-based data flow programming.

Efficient engineering with blocks and compounds

The project-specific HVAC applications are configured, programmed, commissioned and maintained using the CFC Editor in PX Design. The CFC Editor is a graphics editor based on blocks and data flow techniques. Predefined and tested application programs are assembled to create compound structures (referred to simply as "compounds"), and these are then made available in the libraries.

Figure 34 Creating the CFC chart with the CFC Editor

• The basic elements of D-MAP programming are blocks and "compounds" (compound functional units). These are stored in libraries.

• To create a D-MAP program, the blocks and compounds for the required functions are put together in the CFC Editor. This process involves creating instances (of blocks) or copies (of compounds) from the libraries.

• The flow of data between blocks is programmed by interconnecting the "pins" (inputs and outputs) of various blocks.

Libraries

PX Design incorporates comprehensive libraries in which the functions, function blocks and compounds are stored. The libraries contain images of actual plant, aggregates and components in a structure which can be used equally for design engineering, control, operation and monitoring and display.

Features of D-MAP programming:

Page 58: DESIGO System description - This area is password protected [401]

66 / 76

The automation level: SIMATIC S7 for industrial applications

With the SIMATIC S7 automation stations, Siemens Building Technologies offers a complete and consistent automation strategy for all types of building. A versatile range of communication options combined with a modular design enables these automation stations to be tailored to virtually any task, making them ideal for industrial applications.

The key benefits of SIMATIC S7: • Standard communication via Ethernet

TCP/IP, PROFIBUS DP, KNX S-mode (EIB), LONWORKS

• Distributed peripheral devices with DESIGO I/O or SIMATIC ET 2000

• S7 WEB for operation, display and maintenance

• Software library with standard and tested modules

A comprehensive software library is available, with standard and tested function blocks for all tasks associated with heating, ventilation, conditioning and other building services. The modular software blocks from this library can be freely combined, and configured with the necessary operating parameters, as required for the individual customer’s plant.

The communications network is critical to the operation of the building services and is therefore of special importance. For optimum industrial communications, we offer components and networks which ensure continuity from the management level to the field level. In our view, open system connections to office networks via TCP/IP are just as self-evident as the integration of third-party components via a wide range of protocols and special link modules.

SIMATIC S7 modular automation station

SIMATIC S7 is the modular automation station for all standard HVAC plant. The modular, fan-free design, simple implementation of distributed structures, and user-friendliness of SIMATIC S7 make it the convenient and cost-effective solution for a wide range of functions.

Several CPUs with different levels of performance, plus an extensive range of modules with numerous convenient functions enable the user to select only the modules actually required for the application concerned. If the required function is later extended, the automation station can simply be upgraded as required, by adding further modules.

A SIMATIC system comprises:

• A central processing unit (CPU): Various CPUs are available for different performance requirements, including CPUs with integrated inputs/outputs and associated functions, and some CPUs with an integrated PROFIBUS DP interface.

• Signal modules (SM) for digital and analog inputs/outputs • Communication modules for bus coupling and point-to-point connections • Power supply modules for connection of the SIMATIC S7 to a supply voltage of

AC 120/230 V or DC 24 V Use:

• Connected to Ethernet TCP/IP system bus • Stand-alone, with touch panel TP177B

DESIGO R XDESIGO R XDESIGO R X

DESIGO INSIGHTDESIGO INSIGHTDESIGO INSIGHTD

ES

IGO

S7

DE

SIG

O S

7D

ES

IGO

S7

DE

SIG

O P

XD

ES

IGO

PX

DE

SIG

O P

X

DES IGO I/ODESIGO I/ODESIGO I/O

DE

SIG

O O

PE

ND

ES

IGO

OP

EN

DE

SIG

O O

PE

N

BA

Cn

etB

AC

net

BA

Cn

et

ET 200ET 200ET 200

Page 59: DESIGO System description - This area is password protected [401]

67 / 76

Local operation and monitoring

The SIMATIC OP7/OP17 operator unit is used for local operation and monitoring of the SIMATIC S7 automation stations. It provides access to all data points and the associated parameters (e.g. messages and switch commands) in all plant. The SIMATIC OP7 operator unit has a four-line text display, and the SIMATIC OP17 unit an eight-line display. Normally the unit is built into the control panel door.

The SIMATIC operator units enable the user to locate faults, operate and optimize the operation of plant, and modify switch times.

The advantages: • Clear and uniform operating philosophy

for easy operation • Easy-to-understand user guidance,

with plant view, aggregate view and data point view.

• Common alarm displays with user guidance

• Up to 4 SIMATIC S7-300 or SIMATIC S7-400 automation stations may be connected

• Password protection

Web-based operation and monitoring with S7 WEB

When it comes to operation and monitoring in the field of building automation, S7 WEB sets new standards. A standard Web browser (e.g. Internet Explorer) can be used to operate and monitor the SIMATIC S7 automation stations (SIMATIC S7-300/S7-400) via the LAN, intranet or Internet. The hardware platform is represented by the standard communications processors.

Operation takes place using standardized dialog boxes in HTML format. TCP/IP communications make it possible to operate and view heating, ventilation and air conditioning plant from any standard PC with a Web browser.

S7 WEB allows the user to locate faults from anywhere in the TCP/IP network and to operate and optimize the operation of the plant.

The features: • Modern, forward-looking design • Engineering supported by software

tools • Easy to operate, with uniform and

intuitive guidance of the user through the graphical hierarchy and operating philosophy

• Common alarm displays with user guidance

• E-mail transmission • Plant graphics • Access from any location via LAN,

intranet or Internet • Use of any standard PC with a Web

browser, without installing special software

Page 60: DESIGO System description - This area is password protected [401]

68 / 76

The field level: SIMATIC ET 200S

In conjunction with SIMATIC S7, digital and analog inputs and outputs can be linked to the central control system via the PROFIBUS DP field bus system.

The peripheral devices can perform central control sub-functions independently. Sections of the plant can be tested and commissioned in advance. In the event of an error, standalone elements can continue to operate autonomously.

The distributed peripheral devices for SIMATIC come in different sizes, formats and protection classes, and optionally, even with a freely programmable CPU. ET 200S is particularly suitable for building automation and control tasks.

Key benefits: Less wiring is required, and the plant is significantly more flexible and reliable. The extensive range of modules and the uniform approach, throughout the system, to engineering, mounting and programming mean that ET 200S can be used as a universal peripheral device system. The peripheral-device modules can be combined as required.

Network gateways to DESIGO I/O, LONWORKS and KNX S-mode (EIB)

Based on SIMATIC S7, Siemens Building Technologies offers an integration platform based on SIMATIC S7, for communication at the automation level. SIMATIC S7 is connected to the standard communications systems, LONWORKS and KNX S-mode (EIB) of the building automation and control system, by means of two network gateways, the DP/LON Link and the DP/EIB Link. This is the means by which the LONWORKS and KNX S-mode (EIB) field buses are integrated into PROFIBUS DP. In addition to the network access described, other means of access, such as the DP/AS interface link are also available.

Gateway from PROFIBUS DP to DESIGO I/O

The DP/P-bus link integrates the proven DESIGO P-bus input/output modules into SIMATIC S7. Within the SIMATIC system, the DESIGO I/Os (PTM modules) are treated as standard PROFIBUS DP data points and can therefore be accessed in the SIMATIC system.

Gateway from PROFIBUS DP to LonWorks

The DP/LON link integrates the LONWORKS bus of the building automation and control system into the standard communications system, PROFIBUS DP. For the individual room control range, DESIGO RX, the most commonly used applications are available for automated engineering.

Gateway from PROFIBUS DP to EIB The DP/EIB link is used to connect the two open standard communications systems PROFIBUS DP and the building automation bus, EIB. The DP/EIB Link is especially designed for tasks associated with control of lighting and blinds in the context of the electrical installation.

The construction of the device makes it suitable for installation in control panels and sub-distribution boards.

Page 61: DESIGO System description - This area is password protected [401]

69 / 76

SIMATIC S7 automation software

Highly modular software blocks permit maximum flexibility for the solution of complex individual tasks. Off-the-shelf "Typicals" (typical block configurations) are available for components associated with heating, ventilation and air conditioning. Standard tasks can be implemented efficiently and reliably using these Typicals. The Typicals, themselves, are composed of software blocks and can therefore be modified as required. In this way, the software combines flexibility with efficient engineering.

Software blocks

Software blocks are general control blocks which offer the user the scope and flexibility of a programmable logic controller (PLC). These blocks include logic blocks, time elements and calculator blocks.

Special control and calculator blocks for building automation and control are also available. Examples include twin-pump control, start-up control, enthalpy calculation and the calculation of heat quantity.

Input and output modules ensure the logging and control of field devices and equipment such as heating coils, fans etc.

Optimizer blocks enable the plant to be operated at the specified comfort level while consuming the smallest possible amount of energy. These blocks include the following, for example: time scheduling, Optimized Start/Stop Control (OSSC), enthalpy conversion, summer night ventilation, optimization of the h,x chart, maximum demand control.

Third-party peripheral-device blocks allow the user to obtain full access to the data in the third-party system and field devices.

Typicals

Air-handling components (such as heating coils, cooling coils, fans, dampers and air washers) are available for quick creation of ventilation and air conditioning systems. The blocks include components such as heating circuits and boilers, ideal for the automation of heating systems. The continuously expanding library of "Typicals" also includes components for chillers and special applications.

Page 62: DESIGO System description - This area is password protected [401]

70 / 76

Appendix System topologies System design for small buildings

A small automation system can be implemented with just a small number of individual PX modular or compact automation stations. As an option, this system can be expanded by adding one or more type QAX.. room units or PXM.. operator units.

PXC..-U PXC...D

PXM20

QAXPXM10

RS232 PPS2

BACnet / LonTalk

TX-I/O modules

1966

0Z11

en_0

2

Page 63: DESIGO System description - This area is password protected [401]

71 / 76

System design for small buildings with a room automation system

A small automation system can be implemented with just a small number of individual PX modular or compact automation stations. As an option, this system can be expanded by adding one or more type QAX… room units or PXM… operator units. The DESIGO RX room automation system ensures demand-based individual comfort for building users. The devices in the DESIGO RXC and RXB ranges communicate using a standard protocol, LONWORKS bus or KNX S-mode (EIB). The DESIGO RXL devices use a proprietary DESIGO bus. They can be integrated seamlessly into the DESIGO building automation and control system, making a range of additional functions available.

DESIGO RXC

PXR...

PXM20

PXM10

BACnet / LonTalk

RS232

LONWORKS

PXC...D

1066

0Z11

en_0

2

LONWORKSThird-party system

DESIGO RXB

PXC...-U

PXM20

PXM10PXC00-U

PXA30-K11

RS232

BACnet / LonTalk

Synco 700

1066

0Z05

en_0

1

KNX / EIBThird-party

KNX S-mode / EIB

DESIGO RXL

PXM20

PXC00-U

PXA30-K11

BACnet / LonTalk

Synco 700

PXC...D PXM10

RS232

Bus 1066

0Z06

_02

Page 64: DESIGO System description - This area is password protected [401]

72 / 76

System design for small to medium-sized buildings

A number of PX automation stations and RXC room controllers can be interconnected via BACnet/LonTalk and, depending on the size of the system, monitored and operated with one or more network-compatible PXM20 operator units. The RXB or RXL room controller ranges can be used as an alternative to the RXC range. Local operation of an automation station is also possible, with the easy-to-use PXM10 operator unit. For remote operation, the system can be extended to include Web operation with PX-WEB. With the Web operating software, building operators have access to all the functions of the PXM20 from anywhere and at any time. In the event of a fault, alarms can be transmitted via SMS or e-mail for added reliability.

RS232

DESIGO RXC

PXM20

PXC...D

BACnet / LonTalk

PXR...PXG80-W PXM10

DESIGO RXB / RXL

PXA30-K11

Pager

Synco 700

Web client

Telephoneline

1066

0Z07

en_0

2

PXC..-Uwith PXM20

Mobilephone

E-mail

KNX S-mode / EIB or bus

PX-WEB

Page 65: DESIGO System description - This area is password protected [401]

73 / 76

System design for medium-sized to large building complexes

The DESIGO INSIGHT management station lets you get the most out of your plant. The plant is operated using highly informative, animated graphics. Optimum building operation is ensured by use of time schedules that can be operated centrally, a clear alarm handling system and a wide range of other options. The DESIGO system can be embedded in existing IT Ethernet/LAN infrastructures.

Naturally, DESIGO INSIGHT can be expanded into a multi-user system. Web technology is implemented using DESIGO INSIGHT Web Access at the management level and DESIGO PX-WEB at the automation level.

QAX34.1

PXC...D PXC52

QAX31.1

PPS2

PXM20

BACnet / IP

PXG80-N

DESIGO INSIGHT

BACnet / LonTalk

DESIGO INSIGHT

PXM20-E

PXC...-UPXC...-E.D SIMATIC S7

PXA30-N

OPC

Ethernet

PXC64-U with PXM20

PTM-I/O modules

BACnetthird-party devices

TX-I/O modules

ADP/CC or InfoCenter

1066

0z08

EN

_02

Page 66: DESIGO System description - This area is password protected [401]

74 / 76

Distributed buildings

Remote plant can be monitored and operated by telephone. In the event of a fault, the automation stations establish a connection with the higher-level system components or display units to alert the user to the problem. At the DESIGO INSIGHT management station, the user can navigate to the associated graphics.

In the case of PX-WEB the alarm is forwarded by SMS or e-mail. For remote access, connections can be established not only by modem, but also via Ethernet/LAN. For this purpose the DESIGO INSIGHT management station and PX-WEB can be connected to any point on the LAN in the building.

Page 67: DESIGO System description - This area is password protected [401]

76 / 76

www.siemens.com/buildingtechnologies

Siemens Schweiz AG Building Technologies Group International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41 724 24 24 Fax +41 41 724 35 22

Siemens Schweiz AG Building Technologies Sennweidstrasse 47 CH-6312 Steinhausen Tel. +41 585-579 200 Fax +41 585-579 230 www.siemens.ch/sbt

The information in this document contains general descriptions of available technical options, which may not apply in all cases. As a consequence, required features should be specified on a case-by-case basis at the time the contract is concluded.