Insulated roof garden 16 TECHNICAL PROPOSAL INSULATED ROOF GARDEN ISSUE: 016 DATE: 11.12 REVISION: 3 BY: POLYGLASS POLYGLASS SPA Registered Office: Viale Jenner, 4 - 20159 MILANO Head Office: Via dell’Artigianato, 34 31047 Ponte di Piave (TV) - Italy Tel. +39 04227547 - Fax +39 0422854118 www.polyglass.com - [email protected] Detail A Detail A 1 Laying surface 2 Concrete gradient screed 3 Bituminous primer 4 Vapour barrier 5 Thermal insulation panel 6 Bituminous membrane (1st layer) 7 Bituminous membrane (2nd layer) 8 Double separation layer 9 Protective screed 10 Gravel drainage layer 11 Non-woven fabric drainage layer 12 Cultivated soil 13 Vertical turn-up protected with screen and plaster 14 Finishing element 15 Shock absorber

Upload: others

Post on 19-Feb-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Detail A - PolyglassPOLYSHIELD TS 4 and POLYSHIELD TS 4 Mineral: In compliance with EN 13707 product standards (layers for roofing). ANTIRADICE PE: In compliance with EN 13707 product

Insulated roof garden

16TECHNICAL PROPOSAL

Insulated roof garden

Issue: 016

date: 11.12

reVIsIon: 3

by: Polyglass

POLYGLASS SPARegistered Office: Viale Jenner, 4 - 20159 MILANO

Head Office: Via dell’Artigianato, 3431047 Ponte di Piave (TV) - Italy

Tel. +39 04227547 - Fax +39 0422854118www.polyglass.com - [email protected]

Detail A

Detail A

1 laying surface

2 Concrete gradient screed

3 bituminous primer

4 Vapour barrier

5 thermal insulation panel

6 bituminous membrane (1st layer)

7 bituminous membrane (2nd layer)

8 double separation layer

9 Protective screed

10 gravel drainage layer

11 non-woven fabric drainage layer

12 Cultivated soil

13 Vertical turn-up protected with screen and plaster

14 finishing element

15 shock absorber

Page 2: Detail A - PolyglassPOLYSHIELD TS 4 and POLYSHIELD TS 4 Mineral: In compliance with EN 13707 product standards (layers for roofing). ANTIRADICE PE: In compliance with EN 13707 product

TECHNICAL SPECIFICATIONS ITEMS

1. Flat roofing in concrete and masonry, concrete or prestressed slabs.

2. Sand and cement gradient screed or expanded material filling that requires an approx. 2 cm thick finishing layer in sand and cement or in cement grout. This will avoid the need to torch the first membrane if polystyrene beads are used for filling and prevent the formation of bumps after the drying of the screed if expanded perlite is used as filling.

3. All surfaces on which the waterproofing layer is laid on-site must be previously given a coat of a bituminous primer (POLYPRIMER HP 45 PROFESSIONAL by POLYGLASS S.p.A.) with 20÷25 viscosity in FORD Cup no. 4 at 25 °C. Wait until the primer is completely dry (15-20 hours) before applying the waterproofing layer.

4. A vapour barrier composed of an elastomeric plastomeric waterproofing membrane for professional use made of bitumen modified with polypropylene reinforced with reinforced fibre glass bonded to a 6/100 mm thick aluminium strip (POLYVAP RADONSHIELD 3 mm by POLYGLASS S.p.A. (produced by UNI EN ISO 9001:2008 and UNI EN ISO14001:2004 certified Quality System; conformity marking with intended use as per EN 13970 vapour barrier) will be laid over the entire surface. This membrane with -10 °C cold flexibility is made with the quality standards ensured by N.A.T.® (NO AGEING TECHNOLOGY, an innovative productive system that permits control over the polymeric ageing process of bituminous membranes). The continuity of the vapour barrier will be ensured by overlapping the membrane by at least 10 cm on the sides and 15 cm on the heads and uninterrupted bonding by torching with propane gas. The vapour barrier must be turned up and bonded to the walls to at least 5 cm above the top of the insulation layer envisioned. A plastic or metal vent pipe (EPDM, 20/10 lead, or 8/10 stainless steel) must be connected to the vapour barrier.

5. Thermal insulation layer made using polyurethane PUR VB foam panels by POLYGLASS S.p.A faced with resin coated glass fibre on one side and bituminized glass fibre on the other. The panels can be fastened using special bituminous glues like POLYFIx, mechanical fastening with metal washers and fixings or by torching the vapour barrier. The total thickness of the layer must be calculated in accordance with the current standards in force for the climatic area in question (Law 10/91 and amendments in Decree Law 311). The panels must be staggered, making sure that the entire sides of each panel lie atop the previous one in order to avoid thermal bridges. The type of mechanical fastening for each panel chosen on the basis of the height of the roofing and the local climate and wind power extraction usually requires 4 or 5 fastening points per panel or square metre.

6. The first waterproofing layer will be composed of an elastomeric plastomeric waterproofing membrane for professional use made of a distilled bitumen-based compound modified with polypropylene BPP (APP) in 4 mm thickness with reinforcement in continuous thread non-woven polyester fabric with elevated basic weight (POLYSHIELD TS 4 by POLYGLASS S.p.A. - produced by UNI EN ISO 9001:2008 and UNI EN ISO14001:2004 certified Quality System; conformity marking with intended use as per EN 13707 Multiple layer or Single layer). This membrane with -20 °C cold flexibility is made with the quality standards ensured by N.A.T.® (NO AGEING

TECHNOLOGY an innovative productive system that permits control over the polymeric ageing process of bituminous membranes). The membrane can be applied with perfect adherence to the layer previously applied with overlaps of at least 10 cm on the sides and 15 cm on the heads bonded by light torching with propane gas. The layer must be turned up and bonded by torching along the walls.

7. The second waterproofing layer will be composed of an elastomeric plastomeric waterproofing membrane for professional use made of a distilled bitumen-based compound modified with polypropylene BPP (APP) in 4 mm thickness with reinforcement in staple non-woven polyester fabric with elevated basic weight reinforced and stabilised by longitudinal glass fibre (ANTIRADICE PE, with compound enriched by PREVENTOL B2 by BAYER by POLYGLASS S.p.a. - produced by UNI EN ISO 9001:2008 and UNI EN ISO14001:2004 certified Quality System; conformity marking with intended use as per EN 13707 Multiple layer ). This membrane with -10 °C cold flexibility is made with the quality standards ensured by N.A.T.® (NO AGEING TECHNOLOGY an innovative productive system that permits control over the polymeric ageing process of bituminous membranes). The membrane can be applied with perfect adherence to the layer previously applied with overlaps of at least 10 cm on the sides and 15 cm on the heads and bonded by light torching with propane gas. The layer must be turned up and bonded by torching without interruption along the walls. All the membranes forming the second waterproofing layer must be laid in the same direction as the first with longitudinal and transversal overlapping equal to or greater than the width of the bonding beam. The membrane must be applied under heavy protection (for roof gardens).

8. Separation layer made by laying POLYCART C by POLYGLASS S.p.A. bituminous rolled felt paper or 30+30/100 mm thick double LDPE film dry staggered over the waterproofing layers with approx. 20 cm overlaps and a vertical turn-up higher than the height of the final flooring. A compactable 10/15 mm thick polystyrene foam separation element must be positioned along all the vertical turn-ups prior to the laying of the new flooring.

9. Protective reinforced concrete screed with approx. 5 cm thick short polyester fibre.

10. Drainage layer in river gravel or in expanded clay with approx. 8~15 cm thickness.

11. Filtration layer in non-woven needle-loomed fabric with 200 g/sq m density applied over the layer previously laid with minimum overlaps of approx. 20 cm at both the sides and the heads. Laid in this way, the non-woven fabric should be turned-up for the entire height of the vertical turn-ups and all protruding details.

12. Drain column made near the vent pipes made with bricks laid in honeycomb wall faced with non-woven fabric. A drainage column made in this way permits the inspection and cleaning of the drainage tubes while also ensuring correct water drainage and outflow to prevent icing during the colder months.

13. Cultivated soil of appropriate thickness for the planting of the proposed vegetation.

14. All detail work should be a minimum of 150 mm above new finished roof surface.

Insulated roof gardenTECHNICAL PROPOSAL16

Page 3: Detail A - PolyglassPOLYSHIELD TS 4 and POLYSHIELD TS 4 Mineral: In compliance with EN 13707 product standards (layers for roofing). ANTIRADICE PE: In compliance with EN 13707 product

POLYSHIELD TS 4 and POLYSHIELD TS 4 Mineral: In compliance with EN 13707 product standards (layers for roofing).ANTIRADICE PE: In compliance with EN 13707 product standards (layers for roofing) and EN 13969 TYPE T (foundations).

Insulated roof garden TECHNICAL PROPOSAL

TECHNICAL CHARACTERISTICSTEST METHOD TECHNICAL

CHARACTERISTICSUNIT OFMEASURE

NOMINAL VALUES

NOMINAL VALUES

NOMINAL VALUES

EN 1848-1 LENGTH m 10 (-1%) 10 (-1%) 10 (-1%)EN 1848-1 WIDTH m 1 (-1%) 1 (-1%) 1 (-1%)EN 1848-1 STRAIGHTNESS mm/10 m Exceeds Exceeds ExceedsEN 1849-1 THICKNESS mm 3 (-0,2) 4 (-0,2) 4 (-0,2)EN 1849-1 MASS PER UNIT AREA kg/m2 NPD NPD NPDEN 1928-B WATERTIGHTNESS kPa Exceeds Exceeds ExceedsEN 1928-BEN 1926

WATERTIGHTNESS AGAINST ARTIFICIAL AGEING kPa - - Exceeds

EN 13897 WATER TIGHTNESS AFTER STRETCHING % - - -EN 13501-5 ExTERNAL FIRE PERFORMANCE - - FRoof FRoof

EN 13501-1 REACTION TO FIRE Euroclass F F FEN 12316 PEEL RESISTANCE N/50 mm - NPD -EN 12317 SHEAR RESISTANCE N/50 mm 400/150 (-20%) 650/450 (-20%) 500/400 (-20%)

EN 12311-1

TENSILE PROPERTIES MAxIMUM LOAD AT BREAK LongitudinalTransversal ELONGATION AT BREAKLongitudinalTransversal

N/50 mmN/50 mm

%%

500 (-20%)200 (-20%)

30 (-15)30 (-15)

750 (-20%)550 (-20%)

40 (-15)40 (-15)

600 (-20%)550 (-20%)

35 (-15)35 (-15)

EN 12691-A RESISTANCE TO IMPACT mm ≥600 ≥900 ≥900EN 12730-A RESISTANCE TO STATIC LOADING kg - ≥15 ≥15

EN 12310-1RESISTANCE TO TEARINGLongitudinalTransversal

NN

100 (-30%)100 (-30%)

150 (-30%)150 (-30%)

150 (-30%)150 (-30%)

EN 1107-1 DIMENSIONAL STABILITY % - ≤0,3 ≤0,3EN 13948 RESISTANCE PENETRATION ROOTS - - - Exceeds

EN 1108 FORM STABILITY UNDER CYCLIC TEMPERATURE CHANGE % - - -

EN 1109 COLD FLExIBILITY °C ≤-10 ≤-20 ≤-10EN 1110 FLOW RESISTANCE AT ELEVATED TEMPERATURE °C - ≥140 ≥110EN 1110EN 1296

ARTIFICIAL AGEING BEHAVIOUR (COLD FLExIBILITY) °C - ≥140 -

EN 1297 ARTIFICIAL AGEING BEHAVIOUR (VISIBLE DEFECTS) - - Exceeds -

EN 1928-BEN 1847

WATERTIGHTNESS AGAINST CHEMICAL kPa ≤±50%

Initial Value - Exceeds

EN 1296EN 1931

WATER VAPOUR TRANSMISSION AFTER THERMAL AGEING μ ≤±50%

Initial Value - -

EN 12039 ADHESION OF GRANULES % - - -EN 1931 WATER VAPOUR PROPERTIES μ 1000000 (±30%) 20000 20000EN 1850-1 VISIBLE DEFECTS - Absent Absent Absent

POLY

VAP

Rado

nshi

eld

POLY

SHIE

LD T

S 4

ANTI

RADI

CE P

E

16

1 laying surface

2 gradient screed

3 bituminous primer

4 Vapour barrier

5 thermal insulation panel

6 bituminous membrane (1st layer)

7 bituminous membrane (2nd layer)

8 double separation layer

9 Protective concrete screed

10 gravel drainage layer

11 filtration layer

12 soil

Page 4: Detail A - PolyglassPOLYSHIELD TS 4 and POLYSHIELD TS 4 Mineral: In compliance with EN 13707 product standards (layers for roofing). ANTIRADICE PE: In compliance with EN 13707 product

Insulated roof gardenTECHNICAL PROPOSAL

POLYGLASS SPARegistered Office: Viale Jenner, 4 - 20159 MILANO - Head Office: Via dell’Artigianato, 34 - 31047 Ponte di Piave (TV) - Italy

Tel. +39 04227547 - Fax +39 0422854118 - www.polyglass.com - [email protected]

16

11/1

2

Insulated roof garden

Issue: 016

date: 11.12

reVIsIon: 3

by: Polyglass

POLYGLASS SPARegistered Office: Viale Jenner, 4 - 20159 MILANO

Head Office: Via dell’Artigianato, 3431047 Ponte di Piave (TV) - Italy

Tel. +39 04227547 - Fax +39 0422854118www.polyglass.com - [email protected]

1 laying surface

2 Concrete gradient screed

3 bituminous primer

4 Vapour barrier

5 thermal insulation panel

6 bituminous membrane (1st layer)

7 bituminous membrane (2nd layer)

8 double separation layer

9 Protective screed

10 gravel drainage layer

11 non-woven fabric drainage layer

12 Cultivated soil

13 Vertical turn-up protected with screen and plaster

14 finishing element

15 shock absorber

Detail A

Detail A

1 laying surface

2 Concrete gradient screed

3 bituminous primer

4 Vapour barrier

5 thermal insulation panel

6 bituminous membrane (1st layer)

7 bituminous membrane (2nd layer)

8 double separation layer

9 Protective screed

10 gravel drainage layer

11 non-woven fabric drainage layer

12 drainage column in bricks laid in honeycomb pattern

covered with non-woven fabric

13 Cultivated soil

14 Vent pipe in 20/10 lead for waterproofing membrane

15 Vent pipe vapour barrier in 8/10 stainless steel