detecting open phase conductors
DESCRIPTION
Detecting Open Phase ConductorsTRANSCRIPT
Slide 1
Detecting Open Phase ConductorsBob Wilson – ABB Inc.
2015 Texas A&M Relay Conference – March 31, 2015
Slide 2
Effects of Open Phase ConductorsModerate to Severe Neutral Current
All three sequence networks are involved Creates a phase imbalance resulting in
moderate to heavy neutral current in grounded wye systems
P on
xo oy
N on
xo oy
0 on
xo oy
Slide 3
Effects of Open Phase ConductorsUnbalanced Currents and Voltages
Imbalance in loads results in downstream imbalanced voltage
Imbalanced voltages cause excessive heating in three phase motors and transformers
Slide 4
Open Phase ConductorsConventional Protection is Largely Ineffective
Ground protection is based on 3Io magnitude Ground protection must not trip for worst-case
natural load unbalance, usually under peak load conditions
Ground pickup settings may be only slightly less than phase pickup settings.
Complete loss of one phase may be undetectable except at full load conditions
A
B
C
3I0
Ia + Ib + Ic = 3Io
A
B
C
3I0
Slide 5
Open Phase ConductorsWorst Heavy Load Unbalance Dictates Ground Pickup
Ia + Ib + Ic = 3Io
A
B
C
3I0
Neutral current pickup must be above 250A in this example
Heavy Load Assumptions (50% unbalance)Ia = 250 ∠ 0Ib = 500 ∠ 240Ic = 500 ∠ 120I1= 416.67 ∠ 0I0 = 83.33 ∠ 180 I2 = 83.33 ∠ 1803I0 = 250A
Slide 6
Open Phase ConductorsConventional Ground Protection is Largely Ineffective
Ia + Ib + Ic = 3Io
A
B
C
3I0
Light Load Assumptions (100% unbalance)Ia = 0 ∠ 0Ib = 200 ∠ 240Ic = 200 ∠ 120I1 = 133.33 ∠ 180 I0 = 66.67 ∠ 180 I2= 66.67 ∠ 180
A complete loss of one phase under light-to-medium load conditions does not produce enough zero sequence current to detect an open conductor condition
3I0 = 200A
Slide 7
Open Phase ConductorsNegative Sequence also Ineffective
Ia + Ib + Ic = 3Io
A
B
C
3I0
Light Load Assumptions (100% unbalance)Ia = 0 ∠ 0Ib = 200 ∠ 240Ic = 200 ∠ 120I1 = 133.33 ∠ 180 I0 = 66.67 ∠ 180 I2 = 66.67 ∠ 180
In a grounded wye system, the negative sequence current is no larger than the zero sequence current
Slide 8
Open Phase Conductors46PD Phase Discontinuity Protection
50% Unbalance
3I0 = 250A
= 0.20
Heavy Load Conditions
46PD is based on I2/I1 ratio
Slide 9
Open Phase Conductors46PD Phase Discontinuity Protection
Light Load Conditions
The 46PD responds to percentage unbalance and therefore provides improved sensitivity under less than maximum load conditions.
Slide 10
Open Phase ConductorsConclusions
Detection of open phase conductors is a challenge Zero sequence and negative sequence elements are mostly ineffective 46PD (percentage unbalance) offers additional sensitivity when load
levels decrease Even 46PD cannot detect all open phase events
Slide 11
Open Phase Conductors
Questions?