SIZE DWG NO SH REV A REVISION HISTORY REV DESCRIPTION ZONE APPROVED DATE YYYY-MM-DD THIS DOCUMENT SHALL BE REVISED IN ITS ENTIRETY. ALL SHEETS OF THIS DOCUMENT ARE THE SAME REVISION LEVEL AS INDICATED. REVISION DESCRIPTION IS FULLY STATED ON FIRST SHEET OF DOCUMENT DRAWING TYPE SIGNATURES DRAWN DRAWN DATE CHECKED CHECKED DATE ENGRG ENGRG DATE GENERAL ELECTRIC COMPANY GE Energy APPLIED PRACTICES ADDITIONAL APPROVALS SEE PLM FOR APPROVAL INFORMATION SIM TO: SIZE CAGE CODE DWG NO A SHEET 399A4822 399A4822 1 B FIRST MADE FOR ML: DM:720103 CC:0414 Device Summary © COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates. GE CLASS II (INTERNAL NON CRITICAL) 2012-12-11 BALLA, SANKAR LUBBERT, MARK BALLA, SANKAR A DEVICE SUMMARY SYSTEM 4027 UPDATED PER ISS-0034683. REFER ISSUE NOTES IN DEVICE SUMMARY FOR DETAILS OF CHANGE. ECO0090698 SELVAM VELUSAMY. 2013-02-06 DRAWN SV ENGINEER MLL B AS PER ISS0050596 RM THE FOLLOWING DEVICES WERE ADDED: 20TW-7,96WW-4,VA16-4. AS PER ISS0050596 RM THE FOLLOWING DEVICE IS MODIFIED: PI-WW-13 2013-07-22 DRAWN 502209130 ENGINEER 502036044 1 of 67 DWG Number 399A4822 Rev B Released 7/23/2013 Page 1 of 67 GE Proprietary Information - Class II (Internal) US EAR - NLR

Upload: zillur-rahman

Post on 24-Sep-2015

50 views

Category:

Documents


5 download

DESCRIPTION

ffsf

TRANSCRIPT

  • SIZE DWG NO SH REVAREVISION HISTORY

    REV DESCRIPTIONZONE APPROVEDDATEYYYY-MM-DD

    THIS DOCUMENT SHALL BE REVISED IN ITS ENTIRETY. ALL SHEETS OFTHIS DOCUMENT ARE THE SAMEREVISION LEVEL AS INDICATED.

    REVISION DESCRIPTION IS FULLY STATED ON FIRST SHEET OF DOCUMENT

    DRAWING TYPESIGNATURES

    DRAWNDRAWN DATECHECKEDCHECKED DATE

    ENGRGENGRG DATE

    GENERAL ELECTRIC COMPANYGE Energy

    APPLIED PRACTICES ADDITIONAL APPROVALS

    SEE PLM FOR APPROVALINFORMATION

    SIM TO:

    SIZE CAGE CODE DWG NO

    ASHEET

    399A4822

    399A4822

    1 B

    FIRST MADE FOR ML: DM:720103 CC:0414

    Device Summary

    COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    2012-12-11BALLA, SANKAR

    LUBBERT, MARK

    BALLA, SANKAR

    A DEVICE SUMMARY SYSTEM 4027 UPDATED PER ISS-0034683. REFER ISSUE NOTES IN DEVICE SUMMARY FOR DETAILS OF CHANGE. ECO0090698 SELVAM VELUSAMY.

    2013-02-06 DRAWNSV ENGINEERMLL

    B AS PER ISS0050596 RM THE FOLLOWING DEVICES WERE ADDED:20TW-7,96WW-4,VA16-4.AS PER ISS0050596 RM THE FOLLOWING DEVICE IS MODIFIED:PI-WW-13

    2013-07-22 DRAWN502209130 ENGINEER502036044

    1 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 1 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    2 BSystem Title0415 CONTROL DEVICES -TURBINE0416 LUBE OIL SYSTEM0417 COOL & SEAL AIR SYSTEM0419 CONTROL AIR0420 COOLING WATER SYSTEM0422 GAS FUEL SYSTEM0426 FIRE PROTECTION SYSTEM0432 INLET AIR HEATING0434 HYDRAULIC SUPPLY SYSTEM0436 HEAT & VENT SYSTEM0440 LOAD EQUIPMENT0442 TURBINE & COMPRESSOR WASH0471 INLET AND EXHAUST0474 HAZARDOUS GAS DETECTION0477 FUEL PURGE0492 PERFORMANCE MONITOR4027 H2 ACCESSORIES (Ref. G2FA)4035 FUEL GAS CHROMATOGRAPGH

    2 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 2 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    3 B

    NOTES

    Rev "B"

    Device System Operation

    20TW-7 0442 Added96WW-4 0442 AddedVA16-4 0442 AddedPI-WW-13 0442 Modified

    Sivasubramaniam22JUL13-----------------------------------------Rev "A"

    Device System Operation

    PSL-2950 4027 Deleted

    Selvam Velusamy06FEB13

    3 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 3 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    4 B

    SWITCH SETTINGSContact Condition Additional Contacts

    NO- Normally open CEC-

    Additional contact:Normally closedElectrically common

    NC- Normally closed CES-

    Additional contact:Normally closedElectrically separate

    ()- Parenthesis indicates sets of contacts

    OEC-

    Additional contact:Normally openElectrically common

    OES-

    Additional contact:Normally openElectrically separate

    Example: NORM=(2) NO-CEC

    4 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 4 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    5 B

    Device System Settings20-TQ2-2 0417 SOLENOID VALVE

    DE-ENERGIZED:3 TO 1 OPEN; 2 PLUGGEDENERGIZED: 1 TO 2 OPEN; 3 PLUGGED125 VDC; DE-ENERGIZED TO TRIP OPEN VA7-2

    20-TQ2-4 0417 SOLENOID VALVEDE-ENERGIZED : 3 TO 1 OPEN; 2 PLUGGEDENERGIZED : 1 TO 2 OPEN; 3 PLUGGED125 VDC; DE-ENERGIZED TO TRIP CLOSED VA7-3

    20AP-1 0419 APU SHUTOFF VALVE.DE-ENERGIZED: 1 TO 2 CLOSEDENERGIZED: 1 TO 2 OPEN230 VAC; 50 HZ; SINGLE PHASEPROTECTS DESSICANT FROM OVER TEMPERATURE. CONTROL SIGNAL NAME IS L20AP1, APU TROUBLE RELAY (SHUT-OFF VALVE CLOSE RELAY). WIRE TO MKV / MARKVI.

    20CB-1 0417 COMPRESSOR BLEED SOL VALVENORM=B TO C OPEN; A CLOSED

    20CB-2 0417 COMPRESSOR BLEED SOL VALVENORM B TO C OPEN; A CLOSED

    20CM-1 0417 CASE TEMP. MANAGEMENT FLOW CONTROL DAMPERFAILED POSITION = CLOSED

    20FGC-1 0422 FUEL GAS CONTROL VALVE SOLENOID VALVEDE-ENERGIZED: 1 TO 2 OPENENERGIZED: 1 TO 2 CLOSED125 VDC;

    20FGC-2 0422 FUEL GAS CONTROL VALVE SOLENOID VALVEDE-ENERGIZED: 1 TO 2 OPENENERGIZED: 1 TO 2 CLOSED125 VDC;

    20FGC-3 0422 FUEL GAS CONTROL VALVE SOLENOID VALVEDE-ENERGIZED: 1 TO 2 OPENENERGIZED: 1 TO 2 CLOSED125 VDC;

    20FGS-1 0422 FUEL GAS STOP VALVE SOLENOID VALVEDE-ENERGIZED: 1 TO 2 OPENENERGIZED: 1 TO 2 CLOSED125 VDC;

    20PG-1 0477 GAS FUEL SYSTEM PURGE SOLENOID VALVEDE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGEDENERGIZED: 1 TO 2 OPEN; 3 PLUGGED125 VDC;

    5 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 5 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    6 B

    Device System Settings20PG-2 0477 GAS FUEL SYSTEM PURGE SOLENOID VALVE

    DE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGEDENERGIZED: 1 TO 2 OPEN; 3 PLUGGED125 VDC;

    20PG-5 0477 GAS FUEL SYSTEM PURGE SOLENOID VALVEDE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGEDENERGIZED: 1 TO 2 OPEN; 3 PLUGGED125 VDC; PART OF VA13-5

    20PG-6 0477 GAS FUEL SYSTEM PURGE AIR SOLENOID VALVEDE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGEDENERGIZED: 1 TO 2 OPEN; 3 PLUGGED125 VDC; PART OF VA13-6

    20QB-1 0434 LIFT OIL SUPPLY ISOLATION VALVEDE-ENERGIZED: 1 TO 2 CLOSEDENERGIZED: 1 TO 2 OPEN230 VAC; 50 HZ; 1 PH

    20TH-1 0432 INLET HEATING CONTROL VALVE TRIP SOLENOID VALVE125 VDC; DE-ENERGIZE TO TRIP VA20-1ENERGIZE TO OPERATE VA20-1 AREA CLASSIFICATION : NON-RATEDPROTECTION METHOD : D-FLAMEPROOF

    20TV-1 0434 TURBINE COMPRESSOR IGV SOLENOID VALVE125 VDC;

    20TW-4 0442 OFF-LINE COMPRESSOR WASH WATER INJ SOLENOID VALVEDE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGEDENERGIZED: 1 TO 2 OPEN; 3 PLUGGED125 VDC; 20.60 W; 0.1600 A;PART OF VA16-1

    20TW-6 0442 ON-LINE COMPRESSOR WASH WATER INJ SOLENOID VALVEDE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGEDENERGIZED: 1 TO 2 OPEN; 3 PLUGGED125 VDC; 20.60 W; 0.1600 A;PART OF VA16-3

    20TW-7 0442 GFC WATER INJ SOLENOID VALVEDE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGEDENERGIZED: 1 TO 2 OPEN; 3 PLUGGED125 VDC; 20.60 W; 0.1600 A;PART OF VA16-4

    6 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 6 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    7 B

    Device System Settings20VG-1 0422 FUEL GAS VENT SOLENOID VALVE TEST

    DE-ENERGIZED: 1 TO 3 OPEN; 2 PLUGGEDENERGIZED: 2 TO 1 OPEN; 3 PLUGGED125 VDC;

    20VG-2 0477 FUEL GAS VENT SOLENOID VALVEDE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGEDENERGIZED: 1 TO 2 OPEN; 3 PLUGGED125 VDC; 10.60 W; 0.0800 A;PART OF VA13-8

    20VG-4 0477 GAS FUEL VENT SOLENOID VALVEDE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGEDENERGIZED: 1 TO 2 OPEN; 3 PLUGGED125 VDC; 10.60 W; 0.0800 A;PART OF VA13-13

    20VG-8 0422 FUEL GAS VENT SOLENOID VALVEDE-ENERGIZED: 1 TO 3 OPEN; 2 PLUGGEDENERGIZED: 2 TO 1 OPEN; 3 PLUGGED125 VDC;

    20VS4-1 0422 FUEL GAS AUXILIARY STOP VALVE20VS4-4 0422 FUEL GAS SAFETY SHUTOFF VALVE-SOLENOID VALVE20WDET 0442 SOLENOID, 2 WAY VALVE TO RECIRCULATE WATER BACK TO TANK.

    230 VAC; 50 HZ; 1 PH;DE-ENERGIZED: 1 TO 2 CLOSEDENERGIZED: 1 TO 2 OPEN CONTROL SIGNAL NAME IS L20WDET. WIRE TO MK V / MK VI. MK V / MK VI OUTPUT SIGNAL IS DRY CONTACT.

    23BL-1 0436 FAN MOTOR HEATER FOR 88BL-160.00 W; 230 VAC; 1 PH; 50 HZ;

    23BL-2 0436 FAN MOTOR HEATER FOR 88BL-260.00 W; 230 VAC; 1 PH; 50 HZ;

    23BN-1 0417 SPACE HEATER100.0 W; 230 VAC; 1 PH; 50 HZ;MAX WATTAGEFOR MOTOR 88BN-1

    23BN-2 0417 SPACE HEATER100.0 W; 230 VAC; 1 PH; 50 HZ;MAX WATTAGEFOR MOTOR 88BN-2

    23BT-1 0436 HEATER-TURBINE COMPT FAN MOTOR200.0 W; 230 VAC; 1 PH; 50 HZ;HAZARDOUS ZONE: ZONE 2PROTECTION METHOD: `D` - FLAMEPROOF

    7 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 7 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    8 B

    Device System Settings23BT-2 0436 HEATER-TURBINE COMPT FAN MOTOR

    200.0 W; 230 VAC; 1 PH; 50 HZ;HAZARDOUS ZONE: ZONE 2PROTECTION METHOD: `D` - FLAMEPROOF

    23CM-1 0417 CASE TEMP. MANAGEMENT BLOWER MOTOR SPACE HEATER120.0 W; 230 VAC; 1 PH; 50 HZ;FOR MOTOR 88CM-1

    23HG-1 0440 SPACE HEATER-GENERATOR2.250 KW; 400 VAC; 3 PH; 50 HZ;

    23HG-2 0440 SPACE HEATER-GENERATOR2.250 KW; 400 VAC; 3 PH; 50 HZ;

    23HL-1 0436 SPACE HEATER-LUBE OIL SKID20.00 KW; 400 VAC; 3 PH; 50 HZ;HEATING FOR FREEZE PROTECTION

    23HL-3 0436 SPACE HEATER-ACCESSORY COMPT, LUBE OIL REGION3.600 KW; 400 VAC; 1 PH; 50 HZ;USED FOR HUMIDITY CONTROL

    23HQ-1 0434 HEATER-HYDRAULIC OIL PUMP MOTOR60.00 W; 230 VAC; 1 PH; 50 HZ;

    23HQ-2 0434 SPACE HEATER-HYDRAULIC PUMP MOTOR60.00 W; 230 VAC; 1 PH; 50 HZ;

    23HT-1A 0436 SPACE HEATER-TURBINE COMPARTMENT30.00 KW; 400 VAC; 3 PH; 50 HZ;HEATING FOR FREEZE PROTECTION

    23HT-1B 0436 SPACE HEATER-TURBINE COMPARTMENT30.00 KW; 400 VAC; 3 PH; 50 HZ;HEATING FOR FREEZE PROTECTION

    23HT-3A 0436 SPACE HEATER-TURBINE COMPARTMENT3.600 KW; 400 VAC; 1 PH; 50 HZ;HEATING FOR HUMIDITY CONTROL

    23HT-3B 0436 SPACE HEATER-TURBINE COMPARTMENT3.600 KW; 400 VAC; 1 PH; 50 HZ;HEATING FOR HUMIDITY CONTROL

    23IC-1 0471 MOTOR HEATER FOR DEVICE 88IC-135.00 W; 230/480 VAC; 1 PH; 50 HZ;

    23KE-1 0440 HEATER-GENERATOR COLLECTOR ENCLOSURE150.0 W; 230 VAC; 1 PH; 50 HZ;

    23QA-1 0416 HEATER-AUX LUBE OIL PUMP MOTOR100.0 W; 230 VAC; 1 PH; 50 HZ;

    23QA-2 0416 SPACE HEATER-AUX LUBE OIL PUMP MOTOR100.0 W; 230 VAC; 1 PH; 50 HZ;

    23QS-1 0416 HEATER-SEAL OIL PUMP MOTOR60.00 W; 230 VAC; 1 PH; 50 HZ;

    8 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 8 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    9 B

    Device System Settings23QT-1 0416 IMMERSION HEATER-LUBE OIL TANK

    12.00 KW; 400 VAC; 3 PH; 50 HZ;23QT-2 0416 IMMERSION HEATER-LUBE OIL TANK

    12.00 KW; 400 VAC; 3 PH; 50 HZ;23QT-3 0416 IMMERSION HEATER-LUBE OIL TANK

    12.00 KW; 400 VAC; 3 PH; 50 HZ;23QV-2A 0416 SPACE HEATER-FOR 88QV-1A

    60.00 W; 230 VAC; 1 PH; 50 HZ;23QV-2B 0416 SPACE HEATER-FOR 88QV-1B

    60.00 W; 230 VAC; 1 PH; 50 HZ;23TG-1 0416 TURNING GEAR MOTOR HEATER

    75.00 W; 230 VAC; 1 PH; 50 HZ;23TK-1 0417 TURBINE SHELL & EXHAUST FRAME BLOWER MOTOR HEATER

    225.0 W; 230 VAC; 1 PH; 50 HZ;MAX WATTAGEFOR MOTOR 88TK-1

    23TK-2 0417 TURBINE SHELL & EXHAUST FRAME BLOWER MOTOR HEATER225.0 W; 230 VAC; 1 PH; 50 HZ;MAX WATTAGEFOR MOTOR 88TK-2

    23TW-1 0442 HEATER-WATER WASH PUMP MOTOR60.00 W; 230 VAC; 1 PH; 50 HZ;(PART OF 88TW-1)

    23VG-1 0436 HEATER-VENTILATION FAN MOTOR (LOAD COMPT)60.00 W; 230 VAC; 1 PH; 50 HZ;

    23VG-2 0436 HEATER-VENTILATION FAN MOTOR (LOAD COMPT)60.00 W; 230 VAC; 1 PH; 50 HZ;

    23VS-1 0436 SPACE HEATER-VALVE COMPARTMENT20.00 KW; 400 VAC; 3 PH; 50 HZ;HEATING FOR FREEZE PROTECTION

    23VS-3 0436 SPACE HEATER-ACCESSORY COMPT, GAS FUEL MOD REGION3.600 KW; 400 VAC; 1 PH; 50 HZ;USED FOR HUMIDITY CONTROL

    23WK-1 0442 IMMERSION HEATER WATER WASH45.00 KW; 400 VAC; 3 PH; 50 HZ;

    23WK-2 0442 IMMERSION HEATER WATER WASH45.00 KW; 400 VAC; 3 PH; 50 HZ;

    23WS-1 0442 WATER WASH SKID SPACE HEATER10.00 KW; 400 VAC; 3 PH; 50 HZ;

    26TG-1 0416 THERMOSTAT, TURNING GEAR MOTOR WINDING

    9 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 9 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    10 B

    Device System Settings26TW-4 0442 -5 TO 50 MV, TEMPERATURE ELEMENT FOR TANK TEMPERATURE.

    TYPE J THERMOCOUPLE1 ELEMENT; INCREASING: 180.0 +/- 5.0 F OR 82.22 +/- 2.778 CDECREASING: 52.0 +/- 2.0 F OR 11.11 +/- 1.111 CTHIRD SET-POINT 75.0 +/- 2 F INCREASING

    26VW-3 0442 TEMP. ELEMENT FOR COMPT. SPACE HEATER AND VENT FAN.TYPE J THERMOCOUPLE1 ELEMENT; OPERATE VENT FAN AT 95 DEGREES F INCREASING.OPERATE SPACE HEATER AT 65 DEGREES F DECREASING. ALARM AT 43 DEGREES F DECREASING.ALARM AT 130 DEGREES F INCREASING.

    27AD-1 0419 APU LOSS OF POWER ALARMCONTROL SIGNAL NAME IS L27AD1. WIRE TO MK V / MK VI.

    27TF-1 0471 GT AIR FILTER GENERAL ALARM DISPATCHING

    1 PH, 2A RESISTIVE, 125VDC, 0.2A INDUCTIVENORM=(1) NO;

    27WD-1 0442 WATER WASH SKID LOSS OF POWER ALARM RELAYWIRE TO MKV / MK VI

    28FD-15 0415 FLAME DETECTOR COMBUSTION CHAMBER #1528FD-16 0415 FLAME DETECTOR COMBUSTION CHAMBER #1628FD-17 0415 FLAME DETECTOR COMBUSTION CHAMBER #1728FD-18 0415 FLAME DETECTOR COMBUSTION CHAMBER #182FP-1A 0426 FIRE PROTECTION-INITIAL DISCHARGE TIMER (ZONE 1)

    (ZONE 1)INITIAL DISCHARGE

    2FP-1AE 0426 FIRE PROTECTION-EXTENDED DISCHARGE TIMER (ZONE 1)(ZONE 1)EXTENDED DISCHARGE

    2FP-2A 0426 FIRE PROTECTION-INITIAL DISCHARGE TIMER (ZONE 2)(ZONE 2)INITIAL DISCHARGE

    2FP-2AE 0426 FIRE PROTECTION-EXTENDED DISCHARGE TIMER (ZONE 2)(ZONE 2)EXTENDED DISCHARGE

    2FP-3A 0426 FIRE PROTECTION-INITIAL DISCHARGE TIMER (ZONE 3)(ZONE 3)INITIAL DISCHARGE

    10 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 10 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    11 B

    Device System Settings2FP-3AE 0426 FIRE PROTECTION-EXTENDED DISCHARGE TIMER (ZONE 3)

    (ZONE 3)EXTENDED DISCHARGE

    30FP-10A 0426 FIRE PROTECTION TRIP CONTACTZONE 1 PRE-DISCHARGE CONTACTNORM=(1) NO-CEC; CONTACT IS AVAILABLE FOR CUSTOMER USE. CLOSES UPON START OF PRE-DISCHARGE TIMER. CONTACT RATED FOR 5A@24VDC OR 120VAC.

    30FP-1A 0426 TROUBLE ANNUNCIATOR CONTACTNORM=(1) NC; 125VDC CONTACT; CONTACT WIRED TO TCP AND OPENS TO INDICATE A FAULT IN THE FIRE PROTECTION SYSTEM

    30FP-1B 0426 SUPERVISORY ANNUNCIATOR CONTACTNORM=(1) NC; 125VDC CONTACT; CONTACT WIRED TO TCP AND OPENS TO INDICATE THE FIRE PROTECTION FLUID HAS BEEN ISOLATED FROM THE PROTECTED SPACES

    30FP-20A 0426 FIRE PROTECTION TRIP CONTACT (ZONE 2)ZONE 2 PRE-DISCHARGE CONTACTNORM=(1) NO-CEC; CONTACT IS AVAILABLE FOR CUSTOMER USE. CLOSES UPON START OF PRE-DISCHARGE TIMER. CONTACT RATED FOR 5A@24VDC OR 120VAC.

    30FP-2A 0426 TROUBLE ANNUNCIATOR CONTACTNORM=(1) NC; CUSTOMER CONTACT. OPENS TO INDICATE A TROUBLE CONDITION WITH THE FP SYSTEM. CONTACT RATED FOR 5A@24VDC OR 120VAC

    30FP-30A 0426 FIRE PROTECTION TRIP CONTACT (ZONE 3)ZONE 3 PRE-DISCHARGE CONTACTNORM=(1) NO-CEC; CONTACT IS AVAILABLE FOR CUSTOMER USE. CLOSES UPON START OF PRE-DISCHARGE TIMER. CONTACT RATED FOR 5A@24VDC OR 120VAC.

    30FP-3A 0426 SUPERVISORY ANNUNCIATOR CONTACTNORM=(1) NC; CUSTOMER CONTACT. OPENS TO INDICATE A SUPERVISORY FAULT CONDITION WITH THE FP SYSTEM. CONTACT RATED FOR 5A@24VDC OR 120VAC

    30GCX-1 4035 FG CHROMATOGRAPH - GC A- TROUBLE ALARMSIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315

    30GCX-2 4035 FG CHROMATOGRAPH - GC B - TROUBLE ALARM

    SIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A31530GCX-3 4035 FG CHROMATOGRAPH - GC A - CALIBRATION GAS ERROR ALARM

    SIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A31530GCX-4 4035 FG CHROMATOGRAPH - GC B - CALIBRATION GAS ERROR ALARM

    SIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315

    11 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 11 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    12 B

    Device System Settings30SG-1 0415 DIAGNOSTIC IGNITION EXCITER SWITCH

    NORM=NO; CLOSE ON EXCITER FAILURE;33-TQ2-2 0417 LIMIT SWITCH

    LIMIT SWITCHNORM=(1) NO-CEC; CONTACTS CLOSE TO INDICATE VALVE VA7-2 OPEN

    33-TQ2-3 0417 LIMIT SWITCHLIMIT SWITCHNORM=(1) NO-CEC; CONTACTS CLOSE TO INDICATE VALVE VA7-2 CLOSED

    33-TQ2-4 0417 LIMIT SWITCHLIMIT SWITCHNORM=(1) NO-CEC; CONTACTS CLOSE TO INDICATE VALVE VA7-3 OPEN

    33-TQ2-5A 0417 LIMIT SWITCHLIMIT SWITCHNORM=(1) NO-CEC; CONTACTS CLOSE TO INDICATE VALVE VA7-3 CLOSED

    33-TQ2-5B 0417 LIMIT SWITCHLIMIT SWITCHNORM=(1) NO-CEC; CONTACTS CLOSE TO INDICATE VALVE VA7-3 CLOSED

    33-TQ2-5C 0417 LIMIT SWITCHLIMIT SWITCHNORM=(1) NO-CEC; CONTACTS CLOSE TO INDICATE VALVE VA7-3 CLOSED

    33CB-1 0417 COMPRESSOR BLEED VALVE LIMIT SWITCHNORM=(1) NO; SWITCH IS CLOSED WHEN VA2-1 VALVE IS OPEN

    33CB-2 0417 COMPRESSOR BLEED VALVE LIMIT SWITCHNORM=(1) NO; SWITCH IS CLOSED WHEN VA2-2 VALVE IS OPEN

    33CB-3 0417 COMP BLEED VALVE LIMIT SWITCHNORM=(1) NO; SWITCH IS CLOSED WHEN VA2-3 VALVE IS OPEN

    33CB-4 0417 COMP BLEED VALVE LIMIT SWITCHNORM=(1) NO; SWITCH IS CLOSED WHEN VA2-4 VALVE IS OPEN

    33CB-5 0417 COMPRESSOR BLEED VALVE LIMIT SWITCHNORM=(1) NO; SWITCH IS CLOSED WHEN VA2-1 VALVE IS CLOSED

    33CB-6 0417 COMPRESSOR BLEED VALVE LIMIT SWITCHNORM=(1) NO; SWITCH IS CLOSED WHEN VA2-2 VALVE IS CLOSED

    12 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 12 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    13 B

    Device System Settings33CB-7 0417 COMPRESSOR BLEED VALVE LIMIT SWITCH

    NORM=(1) NO; SWITCH IS CLOSED WHEN VA2-3 VALVE IS CLOSED

    33CB-8 0417 COMPRESSOR BLEED VALVE LIMIT SWITCHNORM=(1) NO; SWITCH IS CLOSED WHEN VA2-4 VALVE IS CLOSED

    33FP-31 0426 FIRE PROTECTION-LOCK-OUT VALVE/LIMIT SWITCHNORM=(2) NC-OEC; SUPERVISES DISCHARGE PIPING ISOLATION VALVE. SWITCH IS CLOSED WHEN VALVE IS OPEN

    33FP-31E 0426 FIRE PROTECTION-LOCK-OUT VALVE/LIMIT SWITCHNORM=(2) NC-OEC; SUPERVISES DISCHARGE PIPING ISOLATION VALVE. SWITCH IS CLOSED WHEN VALVE IS OPEN

    33FP-32 0426 FIRE PROTECTION-LOCK-OUT VALVE/LIMIT SWITCHNORM=(2) NC-OEC; SUPERVISES DISCHARGE PIPING ISOLATION VALVE. SWITCH IS CLOSED WHEN VALVE IS OPEN

    33FP-32E 0426 FIRE PROTECTION-LOCK-OUT VALVE/LIMIT SWITCHNORM=(2) NC-OEC; SUPERVISES DISCHARGE PIPING ISOLATION VALVE. SWITCH IS CLOSED WHEN VALVE IS OPEN

    33FP-33 0426 FIRE PROTECTION-LOCK-OUT VALVE/LIMIT SWITCHNORM=(2) NC-OEC; SUPERVISES DISCHARGE PIPING ISOLATION VALVE. SWITCH IS CLOSED WHEN VALVE IS OPEN

    33FP-33E 0426 FIRE PROTECTION-LOCK-OUT VALVE/LIMIT SWITCHNORM=(2) NC-OEC; SUPERVISES DISCHARGE PIPING ISOLATION VALVE. SWITCH IS CLOSED WHEN VALVE IS OPEN

    33PG-1 0477 FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCHNORM=(2) NO-CES;

    33PG-10 0477 FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCHNORM=(2) NO-CES; CLOSED WITH VALVE OPENPART OF VA13-5

    33PG-11 0477 FUEL GAS PURGE VALVE LIMIT SWITCHNORM=(2) NO-CES; CLOSED WITH VALVE CLOSEDPART OF VA13-6

    33PG-12 0477 FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCHNORM=(2) NO-CES; CLOSED WITH VALVE OPENPART OF VA13-6

    13 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 13 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    14 B

    Device System Settings33PG-15 0477 FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCH

    NORM=(2) NO-CES; CLOSED WITH VALVE 55% OPEN; PART OF VA13-2

    33PG-16 0477 FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCHNORM=(2) NO-CES; CLOSED WITH VALVE CLOSED; SPAREPART OF VA13-2

    33PG-2 0477 FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCHNORM=(2) NO-CES; CLOSED WITH VALVE OPEN;

    33PG-3 0477 FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCHNORM=(2) NO-CES; CLOSED WITH VALVE CLOSED;

    33PG-4 0477 FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCHNORM=(2) NO-CES; CLOSED WITH VALVE 17% OPEN; PART OF VA13-2

    33PG-9 0477 FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCHNORM=(2) NO-CES; CLOSED WITH VALVE CLOSED; PART OF VA13-5

    33TH-3 0432 INLET HEATING ISOLATION VALVE LIMIT SWITCHNORM=(1) NO-CEC; CONTACT CLOSED WITH VM15-1 FULL OPEN AREA CLASSIFICATION : NON-RATEDPROTECTION METHOD : D-FLAMEPROOF

    33VG-4 0422 GAS FUEL VENT VALVE-LIMIT SWITCHNORM=(1) NO-CEC; SWITCH CLOSES WHEN VALVE CLOSES

    33VG-8 0422 GAS FUEL VENT VALVE-LIMIT SWITCHNORM=(1) NO-CEC; SWITCH CLOSES WHEN VALVE OPENS

    33VG-9 0422 GAS FUEL VENT VALVE-LIMIT SWITCHNORM=(1) NO-CEC; SWITCH CLOSES WHEN VALVE CLOSES

    33VS4-1 0422 FUEL GAS STOP VALVE-LIMIT SWITCHSWITCH CLOSES WHEN VALVE OPENSNORM=(1) NO-CEC;

    33VS4-2 0422 FUEL GAS STOP VALVE-LIMIT SWITCHSWITCH CLOSES WHEN VALVE CLOSESNORM=(1) NO-CEC;

    33VS4-4 0422 FUEL GAS STOP VALVE-LIMIT SWITCHSWITCH CLOSES WHEN VALVE OPENSNORM=(1) NO-CEC;

    33VS4-5 0422 FUEL GAS STOP VALVE-LIMIT SWITCHSWITCH CLOSES WHEN VALVE CLOSESNORM=(1) NO-CEC;

    14 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 14 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    15 B

    Device System Settings34AD-1 0419 AIR DRYER

    100.0 W; 230 VAC; 1 PH; 50 HZ;HEATLESS DRYER

    34TF-1 0471 TURBINE INLET AIR FILTER-SELF CLEANING SEQUENCER1 PH230 VAC; 50 HZ;

    39V-1A 0415 VIBRATION SENSOR TURBINEOUTPUT AT 1``/SEC = 150.0 MV

    39V-1B 0415 VIBRATION SENSOR TURBINEOUTPUT AT 1``/SEC = 150.0 MV

    39V-2A 0415 VIBRATION SENSOR TURBINEOUTPUT AT 1``/SEC = 150.0 MV

    39V-2B 0415 VIBRATION SENSOR TURBINEOUTPUT AT 1``/SEC = 150.0 MV

    39V-4A 0440 VIBRATION SENSOR GENERATOROUTPUT AT 1``/SEC = 150.0 MVLOCATED ON TURBINE END BEARING CAP

    39V-4B 0440 VIBRATION SENSOR GENERATOROUTPUT AT 1``/SEC = 150.0 MVLOCATED ON TURBINE END BEARING CAP

    39V-5A 0440 VIBRATION SENSOR GENERATOROUTPUT AT 1``/SEC = 150.0 MVLOCATED ON COLLECTOR END BEARING CAP

    39VS-101 0440 VIBRATION SENSOR (NON-CONT) GEN COLLECTOR ENDBENTLEY NEVADA, 3300 SERIESPROXIMITY PROBE FOR GENERATOR SHAFTRANGE:200 MV PER MILLIINCH ALARM @ 0.006``

    39VS-102 0440 VIBRATION SENSOR (NON-CONT) GEN COLLECTOR ENDBENTLEY NEVADA, 3300 SERIESPROXIMITY PROBE FOR GENERATOR SHAFTRANGE:200 MV PER MILLIINCH ALARM @ 0.006``

    39VS-11 0415 VIBRATION SENSOR (NON-CONTACTING)OUTPUT AT 1 MIL = 200.0 MV

    39VS-12 0415 VIBRATION SENSOR (NON-CONTACTING)OUTPUT AT 1 MIL = 200.0 MV

    39VS-21 0415 VIBRATION SENSOR (NON-CONTACTING)OUTPUT AT 1 MIL = 200.0 MV

    39VS-22 0415 VIBRATION SENSOR (NON-CONTACTING)OUTPUT AT 1 MIL = 200.0 MV

    15 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 15 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    16 B

    Device System Settings39VS-91 0440 VIBRATION SENSOR (NON-CONT) GEN COUPLING END

    BENTLEY NEVADA, 3300 SERIESPROXIMITY PROBE FOR GENERATOR SHAFTRANGE:200 MV PER MILLIINCHALARM @ 0.006``

    39VS-92 0440 VIBRATION SENSOR (NON-CONT) GEN COUPLING ENDBENTLEY NEVADA, 3300 SERIESPROXIMITY PROBE FOR GENERATOR SHAFTRANGE:200 MV PER MILLIINCH ALARM @ 0.006``

    43MRA-1C 0426 MANUAL DISCHARGE SWITCH (ACCESSORY COMPT)LOCATED OUTSIDE NEXT TO ACCESSORY COMPARTMENT DOOR (ZONE 1)

    43MRA-3A 0426 MANUAL DISCHARGE SWITCH (ACCESSORY MODULE)LOCATED OUTSIDE NEXT TO ACCESSORY COMPARTMENT DOOR (ZONE 3)

    43MRA-3B 0426 MANUAL DISCHARGE SWITCH (ACCESSORY MODULE)LOCATED OUTSIDE NEXT TO ACCESSORY COMPARTMENT DOOR (ZONE 3)

    43MRFP-1A 0426 FIRE PROTECTION-MANUAL DISCHARGE SWITCH (ZONE 1)NORM=(2) NC-OEC; LOCATED ON ELECTRICAL CONTROL CABINET DOOR ON CO2 SKID. SWITCH HELD OPEN WITH PIN.

    43MRFP-2A 0426 FIRE PROTECTION-MANUAL DISCHARGE SWITCH (ZONE 2)NORM=(2) NC-OEC; LOCATED ON ELECTRICAL CONTROL CABINET DOOR ON CO2 SKID. SWITCH HELD OPEN WITH PIN.

    43MRFP-3A 0426 FIRE PROTECTION-MANUAL DISCHARGE SWITCH (ZONE 3)NORM=(2) NC-OEC; LOCATED ON ELECTRICAL CONTROL CABINET DOOR ON CO2 SKID. SWITCH HELD OPEN WITH PIN.

    43MRT-1A 0426 MANUAL DISCHARGE SWITCH (TURBINE COMPT)(ZONE1)LOCATED ON COMPARTMENT WALL OUTSIDE NEXT TO DOOR

    43MRT-1B 0426 MANUAL DISCHARGE SWITCH (TURBINE COMPT)(ZONE1)LOCATED ON COMPARTMENT WALL OUTSIDE NEXT TO DOOR

    43WK-1 0442 WATER TEMP SETPOINT SWITCH (HOT-COLD)43WK-2 0442 OPERATION SETPOINT SWITCH (AUTO-MANUAL)45FA-30A 0426 FIRE DETECTOR-LUBE/HYDRAULIC COMPARTMENT

    INCREASING: 325.0 F OR 162.8 CNORM=(1) NO-SPST; (LUBE/HYDRAULIC COMP.-ACCESS.MOD-ZONE 3)

    16 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 16 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    17 B

    Device System Settings45FA-30B 0426 FIRE DETECTOR-LUBE/HYDRAULIC COMPARTMENT

    INCREASING: 325.0 F OR 162.8 CNORM=(1) NO-SPST; (LUBE/HYDRAULIC COMP.-ACCESS.MOD-ZONE 3)

    45FA-31A 0426 FIRE DETECTOR-LUBE/HYDRAULIC COMPARTMENTINCREASING: 325.0 F OR 162.8 CNORM=(1) NO-SPST; (LUBE/HYDRAULIC COMP.-ACCESS.MOD-ZONE 3)

    45FA-31B 0426 FIRE DETECTOR-LUBE/HYDRAULIC COMPARTMENTINCREASING: 325.0 F OR 162.8 CNORM=(1) NO-SPST; (LUBE/HYDRAULIC COMP.-ACCESS.MOD-ZONE 3)

    45FA-6A 0426 FIRE DETECTOR-FUEL GAS COMPARTMENTINCREASING: 425.0 F OR 218.3 CNORM=(1) NO-SPST; FUEL GAS COMP.-ACCESS.MODULE (ZONE 1)

    45FA-6B 0426 FIRE DETECTOR-FUEL GAS COMPARTMENTINCREASING: 425.0 F OR 218.3 CNORM=(1) NO-SPST; FUEL GAS COMP.-ACCESS.MODULE (ZONE 1)

    45FA-7A 0426 FIRE DETECTOR-FUEL GAS COMPARTMENTINCREASING: 425.0 F OR 218.3 CNORM=(1) NO-SPST; FUEL GAS COMP.-ACCESS.MODULE (ZONE 1)

    45FA-7B 0426 FIRE DETECTOR-FUEL GAS COMPARTMENTINCREASING: 425.0 F OR 218.3 CNORM=(1) NO-SPST; FUEL GAS COMP.-ACCESS.MODULE (ZONE 1)

    45FT-1A 0426 FIRE DETECTOR-TURBINE COMPARTMENTINCREASING: 600.0 F OR 315.6 CNORM=(1) NO-SPST; TURBINE COMPARTMENT ZONE 1

    45FT-1B 0426 FIRE DETECTOR-TURBINE COMPARTMENTINCREASING: 600.0 F OR 315.6 CNORM=(1) NO-SPST; TURBINE COMPARTMENT ZONE 1

    45FT-20A 0426 FIRE DETECTOR-#2 BEARING AREA (ZONE 2)INCREASING: 725.0 F OR 385.0 CNORM=(1) NO-SPST; #2 BEARING TUNNEL - ZONE 2

    45FT-20B 0426 FIRE DETECTOR-#2 BEARING AREA (ZONE 2)INCREASING: 725.0 F OR 385.0 CNORM=(1) NO-SPST; #2 BEARING TUNNEL - ZONE 2

    17 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 17 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    18 B

    Device System Settings45FT-21A 0426 FIRE DETECTOR-#2 BEARING AREA (ZONE 2)

    INCREASING: 725.0 F OR 385.0 CNORM=(1) NO-SPST; #2 BEARING TUNNEL - ZONE 2

    45FT-21B 0426 FIRE DETECTOR-#2 BEARING AREA (ZONE 2)INCREASING: 725.0 F OR 385.0 CNORM=(1) NO-SPST; #2 BEARING TUNNEL - ZONE 2

    45FT-2A 0426 FIRE DETECTOR-TURBINE COMPARTMENTINCREASING: 600.0 F OR 315.6 CNORM=(1) NO-SPST; TURBINE COMPARTMENT ZONE 1

    45FT-2B 0426 FIRE DETECTOR-TURBINE COMPARTMENTINCREASING: 600.0 F OR 315.6 CNORM=(1) NO-SPST; TURBINE COMPARTMENT ZONE 1

    45FT-3A 0426 FIRE DETECTOR-TURBINE COMPARTMENTINCREASING: 600.0 F OR 315.6 CNORM=(1) NO-SPST; TURBINE COMPARTMENT ZONE 1

    45FT-3B 0426 FIRE DETECTOR-TURBINE COMPARTMENTINCREASING: 600.0 F OR 315.6 CNORM=(1) NO-SPST; TURBINE COMPARTMENT ZONE 1

    45HA-IR-7 0474 IR COMBUSTIBLE GAS DETECTORHIGH ALARM SETTING AT 10% LELHIGH-HIGH ALARM SETTING AT 25% LELIR COMBUSTIBLE GAS DETECTOR ACCESSORY MODULE - LOCAL24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LELINRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3

    45HA-IR-9A 0474 IR COMBUSTIBLE GAS DETECTOR - ACCESSORY COMPARTMENTHIGH ALARM SETTING AT 10% LELHIGH-HIGH ALARM SETTING AT 25% LELIR COMBUSTIBLE GAS DETECTOR ACCESSORY MODULE - DUCT24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LELINRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3

    45HA-IR-9B 0474 IR COMBUSTIBLE GAS DETECTOR - ACCESSORY COMPARTMENTHIGH ALARM SETTING AT 10% LELHIGH-HIGH ALARM SETTING AT 25% LELIR COMBUSTIBLE GAS DETECTOR ACCESSORY MODULE - DUCT24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LELINRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3

    18 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 18 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    19 B

    Device System Settings45HA-IR-9C 0474 IR COMBUSTIBLE GAS DETECTOR - ACCESSORY COMPARTMENT

    HIGH ALARM SETTING AT 10% LELHIGH-HIGH ALARM SETTING AT 25% LELIR COMBUSTIBLE GAS DETECTOR ACCESSORY MODULE - DUCT24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LELINRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3

    45HGT-1 0474 HAZARDOUS ATM DETECTOR-GEN TERMINAL ENCLOSUREHIGH ALARM SETTING AT 10% LELHIGH-HIGH ALARM SETTING AT 25% LELIR COMBUSTIBLE GAS DETECTOR - GTE LOCAL SENSOR24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LELINRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3 MS

    45HGT-2 0474 HAZARDOUS ATM DETECTOR-GEN TERMINAL ENCLOSUREHIGH ALARM SETTING AT 10% LELHIGH-HIGH ALARM SETTING AT 25% LELIR COMBUSTIBLE GAS DETECTOR - GTE LOCAL SENSOR24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LELINRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3 MS

    45HGT-7A 0474 COMBUSTIBLE GAS DETECTOR - GEN COLLECTOR COMPARTMENTHIGH ALARM SETTING AT 10% LELHIGH-HIGH ALARM SETTING AT 25% LELCOMBUSTIBLE GAS DETECTOR - GCC EXTRACT DUCT SENSOR24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL, INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3MS DURATION

    45HGT-7B 0474 COMBUSTIBLE GAS DETECTOR - GEN COLLECTOR COMPARTMENTHIGH ALARM SETTING AT 10% LELHIGH-HIGH ALARM SETTING AT 25% LELCOMBUSTIBLE GAS DETECTOR - GCC EXTRACT DUCT SENSOR24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL, INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3MS DURATION

    45HGT-7C 0474 COMBUSTIBLE GAS DETECTOR - GEN COLLECTOR COMPARTMENTHIGH ALARM SETTING AT 10% LELHIGH-HIGH ALARM SETTING AT 25% LELCOMBUSTIBLE GAS DETECTOR - GCC EXTRACT DUCT SENSOR24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL, INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3MS DURATION

    19 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 19 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    20 B

    Device System Settings45HT-IR-1A 0474 IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT

    HIGH ALARM SETTING AT 8% LELHIGH-HIGH ALARM SETTING AT 17% LELIR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LELINRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3

    45HT-IR-1B 0474 IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCTHIGH ALARM SETTING AT 8% LELHIGH-HIGH ALARM SETTING AT 17% LELIR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LELINRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3

    45HT-IR-1C 0474 IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCTHIGH ALARM SETTING AT 8% LELHIGH-HIGH ALARM SETTING AT 17% LELIR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LELINRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3

    45HT-IR-1D 0474 IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCTHIGH ALARM SETTING AT 8% LELHIGH-HIGH ALARM SETTING AT 17% LELIR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LELINRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3

    45HT-IR-2A 0474 IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCTHIGH ALARM SETTING AT 8% LELHIGH-HIGH ALARM SETTING AT 17% LELIR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT (OUTDOOR UNITS)24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LELINRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3

    45HT-IR-2B 0474 IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCTHIGH ALARM SETTING AT 8% LELHIGH-HIGH ALARM SETTING AT 17% LELIR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT (OUTDOOR UNITS)24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LELINRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3

    20 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 20 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    21 B

    Device System Settings45HT-IR-2C 0474 IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT

    HIGH ALARM SETTING AT 8% LELHIGH-HIGH ALARM SETTING AT 17% LELIR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT (OUTDOOR UNITS)24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LELINRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3

    45HT-IR-2D 0474 IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCTHIGH ALARM SETTING AT 8% LELHIGH-HIGH ALARM SETTING AT 17% LELIR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT (OUTDOOR UNITS)24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LELINRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12 VDC FOR 3

    49IC-1 0471 INLET AIR SCREW AUGER MOTOR OVERLOADRATING: 15.00 A; 230 VAC; 1 PH; 50 HZ; PROTECTS 88IC-1NORM=(1) NC-CEC; AUXILIARY CONTACTS;; NORMALLY CLOSED-OPEN ON OVERLOAD

    49WS-1 0442 WATER WASH SKID HEATER OVERLOAD(INTEGRAL PART OF 23WS-1)

    4WW 0442 WATER WASH MASTER CONTROL RELAYCONTROL SIGNAL NAME IS L4WWX. WIRE TO MK V / MK VI. MK V / MK VI OUTPUT SIGNAL IS DRY CONTACT.

    62FP-1A 0426 FIRE PROTECTION-TIMER RESET SWITCH (FOR ALL ZONES)NORM=(1) NO; SWITCH TO RESET SYSTEM AFTER CO2 DISCHARGE IN ZONE 1

    62FP-2A 0426 FIRE PROTECTION-CO2 TIMER RESET SWITCH (ZONE 2)NORM=(1) NO; SWITCH TO RESET SYSTEM AFTER CO2 DISCHARGE IN ZONE 2

    62FP-3A 0426 FIRE PROTECTION-CO2 TIMER RESET SWITCH (ZONE 3)NORM=(1) NO; SWITCH TO RESET SYSTEM AFTER CO2 DISCHARGE IN ZONE 3

    63AD-4 0419 APU LOW PRESSURE SWITCH DECREASING: 85.00+-5.000 PSIG OR 586.1+-34.47 KPAGAPU LOW PRESSURE ALARM. INDICATES INSUFFICIENTAIR AVAILABLE FOR NORMAL DEVICE OPERATION. OPENS TO ALARM. SIGNAL NAME IS L63AD4. WIRE TO MKV / MK VI.

    63AG-1A 0436 GEAR/LOAD COMPT AIR PRESSURE SWITCH DECREASING: 0.4000 INH2O OR 0.0995 KPANORM=NO-CEC;

    63AG-1B 0436 GEAR/LOAD COMPT AIR PRESSURE SWITCH DECREASING: 0.4000 INH2O OR 0.0995 KPANORM=NO-CEC;

    21 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 21 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    22 B

    Device System Settings63AG-1C 0436 GEAR/LOAD COMPT AIR PRESSURE SWITCH

    DECREASING: 0.4000 INH2O OR 0.0995 KPANORM=NO-CEC;

    63AG-2A 0436 GEAR/LOAD COMPT AIR PRESSURE SWITCH DECREASING: 0.4000 INH2O OR 0.0995 KPANORM=NO-CEC;

    63AG-2B 0436 GEAR/LOAD COMPT AIR PRESSURE SWITCH DECREASING: 0.4000 INH2O OR 0.0995 KPANORM=NO-CEC;

    63AG-2C 0436 GEAR/LOAD COMPT AIR PRESSURE SWITCH DECREASING: 0.4000 INH2O OR 0.0995 KPANORM=NO-CEC;

    63AT-1A 0436 DIFFERENTIAL PRESSURE SWITCH DECREASING: 0.4000 INH2O OR 0.0995 KPANORM=NO-CEC;

    63AT-1B 0436 DIFFERENTIAL PRESSURE SWITCH DECREASING: 0.4000 INH2O OR 0.0995 KPANORM=NO-CEC;

    63AT-1C 0436 DIFFERENTIAL PRESSURE SWITCH DECREASING: 0.4000 INH2O OR 0.0995 KPANORM=NO-CEC;

    63AT-2A 0436 DIFFERENTIAL PRESSURE SWITCH DECREASING: 0.4000 INH2O OR 0.0995 KPANORM=NO-CEC;

    63AT-2B 0436 DIFFERENTIAL PRESSURE SWITCH DECREASING: 0.4000 INH2O OR 0.0995 KPANORM=NO-CEC;

    63AT-2C 0436 DIFFERENTIAL PRESSURE SWITCH DECREASING: 0.4000 INH2O OR 0.0995 KPANORM=NO-CEC;

    63AT-3 0436 DIFFERENTIAL PRESSURE SWITCH DECREASING: 0.4000 INH2O OR 0.0995 KPANORM=NO-CEC;

    63AT-4 0436 DIFFERENTIAL PRESSURE SWITCH DECREASING: 0.4000 INH2O OR 0.0995 KPANORM=NO-CEC;

    63BN-1 0417 VENT AIR PRESSURE SWITCH-#2 BEARING AREA DECREASING: 4.500+-0.1000 INH2O OR 1.120+-0.0249 KPA(INCREASING: 6.000+-0.3000 INH2O OR 1.493+-0.0747 KPA)NORM=(1) NO;

    63BN-2 0417 VENT AIR PRESSURE SWITCH-#2 BEARING AREA DECREASING: 4.500+-0.1000 INH2O OR 1.120+-0.0249 KPA(INCREASING: 6.000+-0.3000 INH2O OR 1.493+-0.0747 KPA)NORM=(1) NO;

    22 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 22 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    23 B

    Device System Settings63CA-1 0471 INLET AIR FILTER COMPRESSED AIR PRESSURE SWITCH

    DECREASING: 60.00+-5.000 PSIG OR 413.7+-34.47 KPAGNORM=(2) NO-CEC; CLOSED WHEN PRESSURIZED; 0.5A, 125VDC

    63FGD-1 0422 FUEL GAS STRAINER DP SWITCHINCREASING: 15.00+-1.000 PSID OR 103.4+-6.895 KPAD(DECREASING: 13.75+-1.250 PSID OR 94.80+-8.618 KPAD)NORM=(1) NC-OEC; SPDT;

    63FP-11A 0426 FIRE PROTECTION-CO2 SELECTOR VLV ACTUATION PRESS SWITCHINCREASING: 90.00+-20.00 PSIG OR 620.5+-137.9 KPAGNORM=(2) NO; MANUAL RESET REQUIRED; CONTACT CLOSES WHEN CO2 PRESSURE IN ZONE 1 ACTUATION LINE RISES ABOVE PRIMARY SETTING. WIRES TO 45FTX-1 AUX RELAY PANEL.

    63FP-12A 0426 FIRE PROTECTION-CO2 SELECTOR VLV ACTUATION PRESS SWITCHINCREASING: 90.00+-20.00 PSIG OR 620.5+-137.9 KPAGNORM=(2) NO; MANUAL RESET REQUIRED; CONTACT CLOSES WHEN CO2 PRESSURE IN ZONE 2 ACTUATION LINE RISES ABOVE PRIMARY SETTING. WIRES TO 45FTX-1 AUX RELAY PANEL.

    63FP-13A 0426 FIRE PROTECTION-CO2 SELECTOR VLV ACTUATION PRESS SWITCHINCREASING: 90.00+-20.00 PSIG OR 620.5+-137.9 KPAGNORM=(2) NO; MANUAL RESET REQUIRED; CONTACT CLOSES WHEN CO2 PRESSURE IN ZONE 3 ACTUATION LINE RISES ABOVE PRIMARY SETTING. WIRES TO 45FTX-1 AUX RELAY PANEL.

    63GCX-1 4035 CARRIER GAS - LOW PRESSURE ALARMSIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315SET TO VENDOR REQUIREMENTSREFER TO SERVICE MANUAL

    63GCX-2 4035 CALIBRATION GAS - LOW PRESSURE ALARMSIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315SET TO VENDOR REQUIREMENTSREFER TO SERVICE MANUAL

    63HF-1 0434 HYDRAULIC OIL FILTER DIFF PRESSURE ALARMINCREASING: 100.0+-3.000 PSID OR 689.5+-20.68 KPAD(DECREASING: 80.00+-10.00 PSID OR 551.6+-68.95 KPAD)NORM=(1) NC-OEC;

    63HF-2 0434 HYDRAULIC FILTER DIFF PRESSURE ALARMINCREASING: 100.0+-3.000 PSID OR 689.5+-20.68 KPAD(DECREASING: 80.00+-10.00 PSID OR 551.6+-68.95 KPAD)NORM=(1) NC-OEC;

    63HQ-1A 0434 HYDRAULIC OIL SUPPLY PRESSURE SWITCH DECREASING: 1450+-25.00 PSIG OR 9997+-172.4 KPAG(INCREASING: 1550+-25.00 PSIG OR 10687+-172.4 KPAG)NORM=(1) NO-CEC;

    23 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 23 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    24 B

    Device System Settings63HQ-1B 0434 HYDRAULIC OIL SUPPLY PRESSURE SWITCH

    DECREASING: 1450+-25.00 PSIG OR 9997+-172.4 KPAG(INCREASING: 1550+-25.00 PSIG OR 10687+-172.4 KPAG)NORM=(1) NO-CEC;

    63HQ-6A 0434 LOW HYDRAULIC OIL PUMP PH1-1 INLET PRESSURE DECREASING: 10.00+-1.000 PSIG OR 68.95+-6.895 KPAG(INCREASING: 12.00+-1.000 PSIG OR 82.74+-6.895 KPAG)NORM=(1) NO-CEC;

    63HQ-6B 0434 LOW HYDRAULIC OIL PUMP PH2-1 INLET PRESSURE DECREASING: 10.00+-1.000 PSIG OR 68.95+-6.895 KPAG(INCREASING: 12.00+-1.000 PSIG OR 82.74+-6.895 KPAG)NORM=(1) NO-CEC;

    63PG-1A 0477 PRIMARY GAS FUEL SYSTEM PURGE PRESSURE SWITCHINCREASING: 50.00+-2.000 PSIG OR 344.7+-13.79 KPAG(DECREASING: 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG)NORM=(1) NC-OEC;

    63PG-1B 0477 PRIMARY GAS FUEL SYSTEM PURGE PRESSURE SWITCHINCREASING: 50.00+-2.000 PSIG OR 344.7+-13.79 KPAG(DECREASING: 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG)NORM=(1) NC-OEC;

    63PG-1C 0477 PRIMARY GAS FUEL SYSTEM PURGE PRESSURE SWITCHINCREASING: 50.00+-2.000 PSIG OR 344.7+-13.79 KPAG(DECREASING: 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG)NORM=(1) NC-OEC;

    63PG-3A 0477 GAS FUEL SYSTEM PURGE PRESSURE SWITCHINCREASING: 50.00+-2.000 PSIG OR 344.7+-13.79 KPAG(DECREASING: 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG)NORM=(1) NC-OEC; HAZARDOUS ZONE: ZONE 2PROTECTION METHOD: ``D`` - FLAME-PROOF

    63PG-3B 0477 GAS FUEL SYSTEM PURGE PRESSURE SWITCHINCREASING: 50.00+-2.000 PSIG OR 344.7+-13.79 KPAG(DECREASING: 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG)NORM=(1) NC-OEC;

    63PG-3C 0477 GAS FUEL SYSTEM PURGE PRESSURE SWITCHINCREASING: 50.00+-2.000 PSIG OR 344.7+-13.79 KPAG(DECREASING: 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG)NORM=(1) NC-OEC;

    63QA-1A 0416 LUBE OIL BEARING HEADER PRESSURE SWITCH-AUX PUMP START DECREASING: 83.00+-2.000 PSIG OR 572.3+-13.79 KPAG(INCREASING: 91.00+-2.000 PSIG OR 627.4+-13.79 KPAG)NORM=(1) NO-CEC;

    63QA-1B 0416 LUBE OIL BEARING HEADER PRESSURE SWITCH DECREASING: 83.00+-2.000 PSIG OR 572.3+-13.79 KPAG(INCREASING: 91.00+-2.000 PSIG OR 627.4+-13.79 KPAG)NORM=(1) NO-CEC;

    24 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 24 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    25 B

    Device System Settings63QB-1 0434 BEARING LIFT OIL SUPPLY PRESSURE

    DECREASING: 2350+-40.00 PSIG OR 16203+-275.8 KPAG(INCREASING: 2500+-40.00 PSIG OR 17237+-275.8 KPAG)NORM=(1) NO-CEC;

    63QE-1 0416 EMERGENCY LUBE OIL PUMP RUNNINGINCREASING: 10.00+-1.000 PSIG OR 68.95+-6.895 KPAG(DECREASING: 8.000+-1.000 PSIG OR 55.16+-6.895 KPAG)NORM=(1) NO-CEC;

    63QQ-21 0416 MAIN LUBE OIL FILTER DIFFERENTIAL PRESSURE-ALARMINCREASING: 15.00+-1.000 PSID OR 103.4+-6.895 KPAD(DECREASING: 12.00+-2.000 PSID OR 82.74+-13.79 KPAD)NORM=(1) NC-OEC;

    63QQ-22 0416 MAIN LUBE OIL FILTER DIFFERENTIAL PRESSURE-ALARMINCREASING: 15.00+-1.000 PSID OR 103.4+-6.895 KPAD(DECREASING: 12.00+-2.000 PSID OR 82.74+-13.79 KPAD)NORM=(1) NC-OEC;

    63QQ-25 0416 SEAL OIL FILTER DIFFERENTIAL PRESSURE SWITCHINCREASING: 13.00+-1.000 PSID OR 89.63+-6.895 KPAD(DECREASING: 11.75+-1.250 PSID OR 81.01+-8.618 KPAD)NORM=(1) NC; SPDT;

    63QT-2A 0416 LOW LUBE OIL PRESSURE DECREASING: 8.000+-1.000 PSIG OR 55.16+-6.895 KPAG(INCREASING: 10.00+-1.000 PSIG OR 68.95+-6.895 KPAG)

    63QT-2B 0416 LOW LUBE OIL PRESSURE DECREASING: 8.000+-1.000 PSIG OR 55.16+-6.895 KPAG(INCREASING: 10.00+-1.000 PSIG OR 68.95+-6.895 KPAG)

    63TK-1 0417 TURBINE SHELL & EXHAUST FRAME BLOWER DSCH PRESSURE SW DECREASING: 25.00+-0.8000 INH2O OR 6.221+-0.1991 KPA(INCREASING: 28.00+-0.8000 INH2O OR 6.968+-0.1991 KPA)NORM=(1) NO;

    63TK-2 0417 TURBINE SHELL & EXHAUST FRAME BLOWER DSCH PRESSURE SW DECREASING: 25.00+-0.8000 INH2O OR 6.221+-0.1991 KPA(INCREASING: 28.00+-0.8000 INH2O OR 6.968+-0.1991 KPA)NORM=(1) NO;

    63TW-1 0442 TURBINE/COMPRESSOR WASH WATER PRESSURE DECREASING: 93.00+-2.000 PSIG OR 641.2+-13.79 KPAGNORM=(2) NO-CEC;

    63TW-2 0442 TURBINE/COMPRESSOR WASH WATER PRESSURE-PUMP TRIPINCREASING: 4.000 INHG OR 13.55 KPANORM=NC-OEC; OPENS ON INCREASING VACUUM 4 INHGV (DEC PRESS)CLOSED AT ATMOSPHERIC PRESSURE.

    65CM-1 0417 CASE TEMP. MANAGEMENT FLOW CONTROL DAMPER POSITIONER4.0MA = 0% = 20CM-1 FULL CLOSED20.0MA = 100% = 20CM-1 FULL OPEN

    25 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 25 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    26 B

    Device System Settings65EP-18 0417 VALVE POSITIONER FOR PCV

    4 MA = 3 PSIG = 100% = VA7-2 FULL OPEN20 MA = 15 PSIG = 0% = VA7-2 FULL CLOSEDPART OF VA7-2

    65EP-19 0417 I/P CONTROLLER, VALVE POSITIONER4 MA = 3 PSIG = 0% = VA7-3 FULL CLOSED20 MA = 15 PSIG = 100% = VA7-3 FULL OPENPART OF VA7-3

    65EP-3 0432 ELECTRO-PNEUMATIC TRANSDUCER4.0MA = 100% = VA20-1 FULL OPEN20.0MA = 0% = VA20-1 FULL CLOSED

    65EP-G1P 0477 GAS FUEL PURGE VALVE POSITIONER4.00 +-0.200 MA = 0% STROKE (FULLY CLOSED)20.00 +- 0.200 MA = 100% STROKE (FULLY OPEN)PART OF VA13-2

    65GC-1 0422 GAS CONTROL VALVE SERVO VALVERATED FLOW: 1.000 GPM AT 1000 PSID RATED FLOW: 3.785 LPM AT 6895 KPAG

    65GC-2 0422 GAS CONTROL VALVE SERVO VALVERATED FLOW: 1.000 GPM AT 1000 PSID RATED FLOW: 3.785 LPM AT 6895 KPAG

    65GC-3 0422 GAS CONTROL VALVE SERVO VALVERATED FLOW: 1.000 GPM AT 1000 PSID RATED FLOW: 3.785 LPM AT 6895 KPAG

    71QH-1 0416 HIGH LUBE OIL LEVEL-ALARMNORM=(1) NC-OEC; INCREASING 3.000 +- 0.250`` (76.2 +- 6.35 MM)DECREASING 1.500 +- 0.500`` (38.1 +- 12.7 MM)

    71QL-1 0416 LOW LUBE OIL LEVEL-ALARMNORM=(1) NO-CEC; DECREASING 2.000 +- 0.250`` (-50.8 +- 6.35 MM)INCREASING 1.500 +- 0.500`` (-38.1 +- 12.7 MM)

    71QL-2 0416 LOW LUBE OIL LEVEL-ALARMNORM=(1) NO-CEC; DECREASING 3.000 +- 0.250`` (-76.2 +- 6.35 MM)INCREASING 1.500 +- 0.500`` (-38.1 +- 12.7 MM)

    71TW-1 0442 WATER TANK WATER LEVEL CONTROLNORM=(2) NC-OEC; DECREASING: 15+-1 IN H20 OR 38.09 +- 2.5 CM OF WATERMAGNETICIC LEVEL SWITCH SET 15 INCHES ABOVE THE BOTTOM OF THE WATER TANK.

    77HT-1 0415 MAGNETIC PICKUP (OVERSPEED)GAP: 0.0500+-0.0050 IN OR 1.270+-0.1270 MM

    26 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 26 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    27 B

    Device System Settings77HT-2 0415 MAGNETIC PICKUP (OVERSPEED)

    GAP: 0.0500+-0.0050 IN OR 1.270+-0.1270 MM77HT-3 0415 MAGNETIC PICKUP (OVERSPEED)

    GAP: 0.0500+-0.0050 IN OR 1.270+-0.1270 MM77NH-1 0415 MAGNETIC PICKUP (SPEED)

    GAP: 0.0500+-0.0050 IN OR 1.270+-0.1270 MM77NH-2 0415 MAGNETIC PICKUP (SPEED)

    GAP: 0.0500+-0.0050 IN OR 1.270+-0.1270 MM77NH-3 0415 MAGNETIC PICKUP (SPEED)

    GAP: 0.0500+-0.0050 IN OR 1.270+-0.1270 MM77RP-11 0415 SHAFT ANGULAR POSITION INDICATOR (KEYPHASOR) BEARING#180HA-FS-7 0474 FLOW SWITCH

    DECREASING: 2.750+-0.2000 OR 2.750+-0.2000 ASPIRATED COMBUSTIBLE GAS DETECTOR FSDECREASING SET POINT: 2.75 CFH INCREASING SET POINT 3.0 CFH SET POINT TOLERANCE TBDSET POINT UOM: CFHNORMAL BIAS (DE-ENERGIZED) (2) NO-CECALARM ON LOW FLOW

    80HA-FS-9A 0474 FLOW SWITCH DECREASING: 2.750+-0.2000 OR 2.750+-0.2000 ASPIRATED COMBUSTIBLE GAS DETECTOR FSDECREASING SET POINT: 2.75 CFH INCREASING SET POINT 3.0 CFH SET POINT TOLERANCE TBDSET POINT UOM: CFHNORMAL BIAS (DE-ENERGIZED) (2) NO-CECALARM ON LOW FLOW

    80HA-FS-9B 0474 FLOW SWITCH DECREASING: 2.750+-0.2000 OR 2.750+-0.2000 ASPIRATED COMBUSTIBLE GAS DETECTOR FSDECREASING SET POINT: 2.75 CFH INCREASING SET POINT 3.0 CFH SET POINT TOLERANCE TBDSET POINT UOM: CFHNORMAL BIAS (DE-ENERGIZED) (2) NO-CECALARM ON LOW FLOW

    27 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 27 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    28 B

    Device System Settings80HA-FS-9C 0474 FLOW SWITCH

    DECREASING: 2.750+-0.2000 OR 2.750+-0.2000 ASPIRATED COMBUSTIBLE GAS DETECTOR FSDECREASING SET POINT: 2.75 CFH INCREASING SET POINT 3.0 CFH SET POINT TOLERANCE TBDSET POINT UOM: CFHNORMAL BIAS (DE-ENERGIZED) (2) NO-CECALARM ON LOW FLOW

    80HGT-FS-1 0474 FLOW SWITCH DECREASING: 2.750+-0.2000 OR 2.750+-0.2000 ASPIRATED COMBUSTIBLE GAS DETECTOR FSDECREASING SET POINT: 2.75 CFH INCREASING SET POINT 3.0 CFH SET POINT TOLERANCE TBDSET POINT UOM: CFHNORMAL BIAS (DE-ENERGIZED) (2) NO-CECALARM ON LOW FLOW

    80HGT-FS-2 0474 FLOW SWITCH DECREASING: 2.750+-0.2000 OR 2.750+-0.2000 ASPIRATED COMBUSTIBLE GAS DETECTOR FSDECREASING SET POINT: 2.75 CFH INCREASING SET POINT 3.0 CFH SET POINT TOLERANCE TBDSET POINT UOM: CFHNORMAL BIAS (DE-ENERGIZED) (2) NO-CECALARM ON LOW FLOW

    80HGT-FS-7A 0474 FLOW SWITCH DECREASING: 2.750+-0.2000 OR 2.750+-0.2000 ASPIRATED COMBUSTIBLE GAS DETECTOR FSDECREASING SET POINT: 2.75 CFH INCREASING SET POINT 3.0 CFH SET POINT TOLERANCE TBDSET POINT UOM: CFHNORMAL BIAS (DE-ENERGIZED) (2) NO-CECALARM ON LOW FLOW

    28 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 28 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    29 B

    Device System Settings80HGT-FS-7B 0474 FLOW SWITCH

    DECREASING: 2.750+-0.2000 OR 2.750+-0.2000 ASPIRATED COMBUSTIBLE GAS DETECTOR FSDECREASING SET POINT: 2.75 CFH INCREASING SET POINT 3.0 CFH SET POINT TOLERANCE TBDSET POINT UOM: CFHNORMAL BIAS (DE-ENERGIZED) (2) NO-CECALARM ON LOW FLOW

    80HGT-FS-7C 0474 FLOW SWITCH DECREASING: 2.750+-0.2000 OR 2.750+-0.2000 ASPIRATED COMBUSTIBLE GAS DETECTOR FSDECREASING SET POINT: 2.75 CFH INCREASING SET POINT 3.0 CFH SET POINT TOLERANCE TBDSET POINT UOM: CFHNORMAL BIAS (DE-ENERGIZED) (2) NO-CECALARM ON LOW FLOW

    80HT-FS-1A 0474 FLOW SWITCH DECREASING: 2.750+-0.2000 OR 2.750+-0.2000 ASPIRATED COMBUSTIBLE GAS DETECTOR FSDECREASING SET POINT: 2.75 CFH INCREASING SET POINT 3.0 CFH SET POINT TOLERANCE TBDSET POINT UOM: CFHNORMAL BIAS (DE-ENERGIZED) (2) NO-CECALARM ON LOW FLOW

    80HT-FS-1B 0474 FLOW SWITCH DECREASING: 2.750+-0.2000 OR 2.750+-0.2000 ASPIRATED COMBUSTIBLE GAS DETECTOR FSDECREASING SET POINT: 2.75 CFH INCREASING SET POINT 3.0 CFH SET POINT TOLERANCE TBDSET POINT UOM: CFHNORMAL BIAS (DE-ENERGIZED) (2) NO-CECALARM ON LOW FLOW

    29 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 29 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    30 B

    Device System Settings80HT-FS-1C 0474 FLOW SWITCH

    DECREASING: 2.750+-0.2000 OR 2.750+-0.2000 ASPIRATED COMBUSTIBLE GAS DETECTOR FSDECREASING SET POINT: 2.75 CFH INCREASING SET POINT 3.0 CFH SET POINT TOLERANCE TBDSET POINT UOM: CFHNORMAL BIAS (DE-ENERGIZED) (2) NO-CECALARM ON LOW FLOW

    80HT-FS-1D 0474 FLOW SWITCH DECREASING: 2.750+-0.2000 OR 2.750+-0.2000 ASPIRATED COMBUSTIBLE GAS DETECTOR FSDECREASING SET POINT: 2.75 CFH INCREASING SET POINT 3.0 CFH SET POINT TOLERANCE TBDSET POINT UOM: CFHNORMAL BIAS (DE-ENERGIZED) (2) NO-CECALARM ON LOW FLOW

    80HT-FS-2A 0474 FLOW SWITCH DECREASING: 2.750+-0.2000 OR 2.750+-0.2000 ASPIRATED COMBUSTIBLE GAS DETECTOR FSDECREASING SET POINT: 2.75 CFH INCREASING SET POINT 3.0 CFH SET POINT TOLERANCE TBDSET POINT UOM: CFHNORMAL BIAS (DE-ENERGIZED) (2) NO-CECALARM ON LOW FLOW

    80HT-FS-2B 0474 FLOW SWITCH DECREASING: 2.750+-0.2000 OR 2.750+-0.2000 ASPIRATED COMBUSTIBLE GAS DETECTOR FSDECREASING SET POINT: 2.75 CFH INCREASING SET POINT 3.0 CFH SET POINT TOLERANCE TBDSET POINT UOM: CFHNORMAL BIAS (DE-ENERGIZED) (2) NO-CECALARM ON LOW FLOW

    30 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 30 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    31 B

    Device System Settings80HT-FS-2C 0474 FLOW SWITCH

    DECREASING: 2.750+-0.2000 OR 2.750+-0.2000 ASPIRATED COMBUSTIBLE GAS DETECTOR FSDECREASING SET POINT: 2.75 CFH INCREASING SET POINT 3.0 CFH SET POINT TOLERANCE TBDSET POINT UOM: CFHNORMAL BIAS (DE-ENERGIZED) (2) NO-CECALARM ON LOW FLOW

    80HT-FS-2D 0474 FLOW SWITCH DECREASING: 2.750+-0.2000 OR 2.750+-0.2000 ASPIRATED COMBUSTIBLE GAS DETECTOR FSDECREASING SET POINT: 2.75 CFH INCREASING SET POINT 3.0 CFH SET POINT TOLERANCE TBDSET POINT UOM: CFHNORMAL BIAS (DE-ENERGIZED) (2) NO-CECALARM ON LOW FLOW

    80WW-1 0442 FLOW SWITCH-WATER WASH SKIDNORM=(2) NC-OEC; CONTACT OPENS AT 2 GPM OR 0.45 M3/HR ON INCR FLOW WATER WASH FLOW EXISTS RELAY TO TURBINE CONTROL SYSTEM AND CONTROL SIGNAL NAME IS L80WWN. WIRE TO MK V / MK VI.

    86WWX 0442 WATER WASH SKID TRIP ALARM RELAYCONTROL SIGNAL NAME IS L86WWX. WIRE TO MK V / MK VI.

    88AD-1 0419 FAN MOTOR, APU HEAT EXCHANGER2.000 HP; 1725 RPM; 230 VAC; 1 PH; 50 HZ;COOLS APU HEAT EXCHANGER. MOTOR RATING SPECIFIED IS THE MAX HP EXPECTED.

    88BL-1 0436 COOLING AIR FAN MOTOR-LUBE OIL SKID5.000 HP; 3.728 KW; 1500 RPM; 400 VAC; 3 PH; 50 HZ;

    88BL-2 0436 COOLING AIR FAN MOTOR-LUBE OIL SKID5.000 HP; 3.728 KW; 1500 RPM; 400 VAC; 3 PH; 50 HZ;

    88BN-1 0417 COOLING AIR FAN MOTOR-#2 BEARING AREA20.00 HP; 14.91 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;15KW

    88BN-2 0417 COOLING AIR FAN MOTOR-#2 BEARING AREA20.00 HP; 14.91 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;15KW

    31 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 31 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    32 B

    Device System Settings88BT-1 0436 COOLING AIR FAN MOTOR-TURBINE COMPARTMENT

    50.00 HP; 37.28 KW; 1000 RPM; 400 VAC; 3 PH; 50 HZ;LEFT HAND SIDE FAN MOTOR, LOOKING DOWNSTREAMHAZARDOUS ZONE: ZONE 2PROTECTION METHOD: `D` - FLAMEPROOF

    88BT-2 0436 COOLING AIR FAN MOTOR-TURBINE COMPARTMENT50.00 HP; 37.28 KW; 1000 RPM; 400 VAC; 3 PH; 50 HZ;RIGHT HAND SIDE FAN MOTOR, LOOKING DOWNSTREAMHAZARDOUS ZONE: ZONE 2PROTECTION METHOD: `D` - FLAMEPROOF

    88CM-1 0417 CASE TEMP. MANANGEMENT(CLEARANCE CONTROL)BLOWER MOTOR50.00 HP; 37.28 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;

    88ES-1 0416 EMERGENCY SEAL OIL PUMP MOTOR20.00 HP; 14.91 KW; 3000 RPM; 125 VDC;

    88FP-1A 0426 FIRE PROTECTION-CO2 REFRIGERATION COMPRESSOR MOTOR3.000 HP; 2.237 KW; 1425 RPM; 400 VAC; 3 PH; 50 HZ;HP LISTED IS MAX VALUE. ACTUAL HP MAY BE LESS

    88FP-1B 0426 REDUNDANT FP-CO2 REFRIGERATION COMPRESSOR MOTOR3.000 HP; 2.237 KW; 1425 RPM; 400 VAC; 3 PH; 50 HZ;HP LISTED IS MAX VALUE. ACTUAL HP MAY BE LESS

    88HQ-1 0434 HYDRAULIC SUPPLY PUMP MOTOR60.00 HP; 44.74 KW; 1500 RPM; 400 VAC; 3 PH; 50 HZ;

    88HQ-2 0434 HYDRAULIC SUPPLY PUMP MOTOR60.00 HP; 44.74 KW; 1500 RPM; 400 VAC; 3 PH; 50 HZ;

    88IC-1 0471 INLET FILTER, DUST COLLECTION SYSTEM SCREW AUGER MOTOR2.000 HP; 1.491 KW; 400 VAC; 3 PH; 50 HZ;SCREW AUGER MOTOR

    88QA-1 0416 AUXILIARY LUBE OIL PUMP MOTOR125.0 HP; 93.21 KW; 2900 RPM; 400 VAC; 3 PH; 50 HZ;90 KW FOR CE APPLICATIONS

    88QA-2 0416 AUXILIARY LUBE OIL PUMP MOTOR125.0 HP; 93.21 KW; 2900 RPM; 400 VAC; 3 PH; 50 HZ;90 KW FOR CE APPLICATIONS

    88QE-1 0416 EMERGENCY LUBE OIL PUMP MOTOR20.00 HP; 14.91 KW; 1750 RPM; 125 VDC;

    88QS-1 0416 GENERATOR(AUXILIARY) SEAL OIL PUMP MOTOR30.00 HP; 22.37 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;

    88QV-1A 0416 LUBE MIST SEPARATOR OR ELIMINATOR MOTOR5.000 HP; 3.728 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;

    88QV-1B 0416 LUBE MIST SEPARATOR MOTOR5.000 HP; 3.728 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;

    88TG-1 0416 TURNING GEAR MOTOR6.400 HP; 4.772 KW; 1500 RPM; 400 VAC; 3 PH; 50 HZ;

    32 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 32 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    33 B

    Device System Settings88TK-1 0417 TURBINE SHELL & EXHAUST FRAME BLOWER MOTOR

    213.0 HP; 158.8 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;160 KW

    88TK-2 0417 TURBINE SHELL & EXHAUST FRAME BLOWER MOTOR213.0 HP; 158.8 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;160 KW

    88TW-1 0442 TURBINE/COMPRESSOR WASH WATER PUMP MOTOR25.00 HP; 18.64 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;20 HP MAY BE USED BASED ON ACTUAL PUMP PERFORMANCE.

    88VG-1 0436 LOAD COMPT COOLING AIR FAN MOTOR7.500 HP; 5.593 KW; 1500 RPM; 400 VAC; 3 PH; 50 HZ;

    88VG-2 0436 LOAD COMPT COOLING AIR FAN MOTOR7.500 HP; 5.593 KW; 1500 RPM; 400 VAC; 3 PH; 50 HZ;

    88VW-1 0442 WATER WASH UNIT VENT FAN MOTOR0.5000 HP; 0.3728 KW; 1725 RPM; 230 VAC; 1 PH; 50 HZ;

    88WS-1 0442 WATER WASH SKID SPACE HEATER BLOWER MOTOR0.1000 HP; 0.0746 KW; 1550 RPM; 230 VAC; 1 PH; 50 HZ;

    8IC-1 0471 INLET AIR SCREW AUGER MOTOR DISCONNECT15 ANORM=(3) NC-CEC; PROTECTS 88IC-1;ALSO DISCONNECTS 23IC-1

    90LT-1 0420 COOLING WATER VALVE POSITION REGULATOR - LO HX4 +- 0.200 MA = 0% STROKE (B-L POSITION, FULL UP)20 +- 0.200 MA = 100% STROKE (B-R POSITION, FULL DOWN)

    90SR-1 0422 STOP/SPEED RATIO VALVE SERVO VALVERATED FLOW: 15.00 GPM AT 1000 PSID RATED FLOW: 56.8 LPM AT 6895 KPAG

    90TV-1 0434 INLET GUIDE VANE SERVO VALVERATED FLOW: 10.00 GPM AT 1000 PSIG (38 GPM @ 6895 KPA)

    94F-1A 0426 FIRE PROTECTION TRIP CONTACT (ZONE 1)NORM=(1) NO; 125VDC CONTACT; CONTACT IS WIRED TO 45FTX-1 AUX RELAY PANEL AND CLOSES UPON START OF PRE-DISCHARGE TIMER.

    94F-1B 0426 FIRE PROTECTION TRIP CONTACT (ZONE 1)NORM=(1) NC-OEC; 125VDC CONTACT; CONTACT IS WIRED TO TCP AND OPENS UPON START OF CO2 DISCHARGE.

    94F-2A 0426 FIRE PROTECTION TRIP CONTACT (ZONE 2)NORM=(1) NO; 125VDC CONTACT; CONTACT IS WIRED TO 45FTX-1 AUX RELAY PANEL AND CLOSES UPON START OF PRE-DISCHARGE TIMER.

    94F-2B 0426 FIRE PROTECTION TRIP CONTACT (ZONE 2)NORM=(1) NC-OEC; 125VDC CONTACT; CONTACT IS WIRED TO TCP AND OPENS UPON START OF CO2 DISCHARGE.

    33 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 33 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    34 B

    Device System Settings94F-3A 0426 FIRE PROTECTION TRIP CONTACT (ZONE 3)

    NORM=(1) NO; 125VDC CONTACT; CONTACT IS WIRED TO 45FTX-1 AUX RELAY PANEL AND CLOSES UPON START OF PRE-DISCHARGE TIMER.

    94F-3B 0426 FIRE PROTECTION TRIP CONTACT (ZONE 3)NORM=(1) NC-OEC; 125VDC CONTACT; CONTACT IS WIRED TO TCP AND OPENS UPON START OF CO2 DISCHARGE.

    95FP-1 0440 GENERATOR AIR GAP FLUX PROBE95SG-2 0415 IGNITION EXCITER FOR 95SP-2

    115VAC/230 VAC, 50/60HZ, 150VA MAX INPUT1.5 MIN ON/1.5 MIN OFF/1.5 MIN ON/25 MIN OFF

    95SG-3 0415 IGNITION EXCITER FOR 95SP-3115VAC/230 VAC, 50/60HZ, 150VA MAX INPUT1.5 MIN ON/1.5 MIN OFF/1.5 MIN ON/25 MIN OFF

    95SP-2 0415 COMBUSTION CHAMBER SPARK PLUG95SP-3 0415 COMBUSTION CHAMBER SPARK PLUG96-TS2P-1A 0417 TRANSMITTER

    4.000 MA= 0.0 PSIG OR 0.0 KPAG20.00 MA= 300.0 PSIG OR 2068 KPAGPRESSURE TRANSMITERSTAGE TWO NOZZLE OSWC2-WIRE, LOOP POWERED, ANALOG

    96-TS2P-1B 0417 TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 KPAG20.00 MA= 300.0 PSIG OR 2068 KPAGPRESSURE TRANSMITERSTAGE TWO NOZZLE OSWC2-WIRE, LOOP POWERED, ANALOG

    96-TS2P-1C 0417 TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 KPAG20.00 MA= 300.0 PSIG OR 2068 KPAGPRESSURE TRANSMITERSTAGE TWO NOZZLE OSWC2-WIRE, LOOP POWERED, ANALOG

    96-TS2QP-1A 0417 TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 KPAG20.00 MA= 300.0 PSIG OR 2068 KPAGTRANSMITTERS13 PRESSURE2 WIRE, LOOP POWERED, ANALOG

    34 of 67

    DWG Number 399A4822 Rev B Released 7/23/2013 Page 34 of 67

    GE Proprietary Information - Class II (Internal) US EAR - NLR

  • COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. The information contained herein is GE Energy GAS Proprietary Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

    GE CLASS II (INTERNAL NON CRITICAL)

    SIZE DWG NO SH REVA

    GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

    AGE Energy

    DRAWN

    DRAWN DATE SHEET

    399A4822

    399A4822

    BALLA, SANKAR

    2012-12-11

    35 B

    Device System Settings96-TS2QP-1B 0417 TRANSMITTER

    4.000 MA= 0.0 PSIG OR 0.0 KPAG20.00 MA= 300.0 PSIG OR 2068 KPAGTRANSMITTERS13 PRESSURE2 WIRE, LOOP POWERED, ANALOG

    96-TS2QP-1C 0417 TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 KPAG20.00 MA= 300.0 PSIG OR 2068 KPAGTRANSMITTERS13 PRESSURE2 WIRE, LOOP POWERED, ANALO