TRANSCRIPT
© 2019 Johnson Controls, Inc. 1 of 2 Specifications subject to change.
Form No. DFS-18XHP2-2020 Effective Date 7/31 X Series
SUBMITTAL DATA SHEET
DHX18NWB21S/DHX184CSB21S 18,000 BTU/H Wall Mounted Heat Pump System
Job Name: Location: Purchaser: Order No.:Engineer: Submitted To: For: Ref: Approval: Construction: Submitted By: Date: Unit Designation: Schedule No.: Model No.:
DHX18NWB21S
DHX18CSB21S
System Ratings DHX18NWB21S
CoolingRated Cooling Capacity 18000Cooling Capacity (Min-Max) 7,165-20,000
Power Input (Max) 2600
20
12.5
HeatingRated Heating Capacity 19,800Heating Capacity (Min-Max) 7,336-23,498
Power Input (Max) 2600
10
Operating RangeCooling 0~115 (-18~46)
Heating -4~75 (-20~24)
Piping Connection - Liquid (O.D.) 1/4
Piping Connection - Gas (O.D.) 1/2Flared
Max. Total Piping Length 82 (25)
Max. Piping Height 33 (10)
Connection Method
in. (m)in. (m)
in.in.
Btu/h Btu/h
Btu/h Btu/h
HSPF
W
SEER
EER
W
( )
( )
DHX18NWB21SCross-flow
OutPut Power 60
FLA 0.38
Set Temperature Range 61 86 (16 30)
Airflow High to Low 559/489/412/335
SoundPressureLevel High to Low 47/43/39/35
Net Weight / Gross Weight 27.6(12.5)/34.2(15.5)
Amps
Indoor Model Number
( )
CFM
dB(A)
lbs (kg)
Fan Motor - Type
W
Outdoor Model Numer DHX18CSB21SDC Inverter Driven Rotary
RLA 7.2
R410A
Charge 60 (1.7)
Fan Motor - Output Power 60
FLA 0.36
Sound Pressure Level dB(A) 55
Power SuplyRated Voltage 208/230-1-60Net Weight / Gross Weight lbs (kg) 113.6(51.5)/123.5(56)MCA 16
MOCP 25
oz (kg)
Amps
dB(A)
Compressor -Type
Amps
Refrigerant - Type
W
V-PH-Hz
Amps
Ampsft.ft.
FEATURESCompact and Quiet Design
High Efficiency DC Inverter Technology
Wireless Remote with LCD Display
Low Ambient Cool to 0 deg F
Vertical Swing LouverDRCPX
(Standard)CS532AH
(Optional)
•
•
•
•
•
ACCESSORIES
DWUNI(Optional)
DWCPX2(Optional)
• Simple Wired Controller DWCPX2
• Advanced Wired Controller DWUNI
• Central Controller DCCRMW
• Wi-Fi Module CS532AH
© 2020 Johnson Controls, Inc. 2 of 2 Specifications subject to change
DHX18NWB21S/DHX18CSB21S Unit: inch
Unit: inch
Indoor Unit Dimensions
Outdoor Unit Dimensions
W 38 13/64H 11 13/16D 8 5/6
Dimensions
Liquid Line Valve 1/4-in OD Flared
Gas Line Valve 1/2-in OD Flared
Drain Connector 5/8-in OD
Notes:
1. Recommended cable type between Outdoor and Indoor Unit,14-4 AWG Stranded Copper THHN 600V Wire2. Power wiring cable size must comply with applicable national and local codes3. Test conditions are based on AHRI 210/240