dialing it in: a year of tuning the ncar-wyoming supercomputing center
DESCRIPTION
Dialing it in: A Year of Tuning the NCAR-Wyoming Supercomputing Center. Aaron Andersen, Deputy Director of Operations, National Center for Atmospheric Research(NCAR). NCAR ’ s Founding Mission. - PowerPoint PPT PresentationTRANSCRIPT
Dialing it in: A Year of Tuning the NCAR-Wyoming Supercomputing Center
Aaron Andersen, Deputy Director of Operations, National Center for Atmospheric Research(NCAR)
Aaron AndersenNov., 2013
“… to provide, or arrange for provision of facilities for the scientific community as a whole whose initial cost and upkeep lie beyond the capability of individual universities or research groups.”
Preliminary Plans for a National Institute for Atmospheric Research,
1959, NCAR Blue Book
NCAR’s Founding Mission
Aaron AndersenNov., 2013
History of Computing at NCAR
Exotic CoolingFreon R-22
Fluorinert
Water
Return of Liquid CoolingWater
Warm Water
FR3
Aaron AndersenNov., 2013
• Key to Optimum Performance (Three M’s)• Monitoring
• Measurement
• Maintenance
• Infrastructure Support Group – Cheyenne• Electricians
• Mechanics
• Building Automation Controls
• HVAC Technician
• Commissioning Agent• Measurement & Verification 12 months post completion
Aaron AndersenNov., 2013
Tuning the Facility – Student Interns
• Clair Christofersen - 2012• University of Miami Ohio
• BS Mechanical Engineering – Applied Math
• Air Flow Modeling (CFD Analysis)
• Jason Jones - 2012• Clemson University -> Georgia Tech
• BS Mechanical Engineering
• Air Flow, Water Flow and Total Energy
• Ademola Olarinde - 2013• Texas A&M Kingsville
• MS Mechanical Engineering
Aaron AndersenNov., 2013
65F (18.3 C) Degree Chilled Water
Evaporative Solution
Aaron AndersenNov., 2013
Liquid Cooling – ASHRAE 2011 Guidelines
121 hrs1.38%
8639 hrs98.62%
Aaron AndersenNov., 2013
Characterize Building Response
Aaron AndersenNov., 2013
• Saw an increase in mechanical consumption in winter months
• Energy Recovery Heat Pumps consuming way more electricity than expected
• Why do we care?• $5000 per month
• What is the root cause?
Mechanical Load in Winter
Aaron AndersenNov., 2013
• Heat Rejection from Yellowstone is too low 1.2MW vs. 4MW Design
• Significantly greater heating demand from the building during winter months
• Commissioning Agent identified the same problem and possible culprit, large Air Handling Units
Root Cause
Aaron AndersenNov., 2013
Why This Matters
Aaron AndersenNov., 2013
• UPS Efficiency• Only Critical Systems are Covered on UPS
• Disk• Network• AuthN/AuthZ• Login• Management
• Low load causes low efficiency
• Firmware upgrade moves UPS efficiency from 70% ~ 95%
• Maintenance really matters• Cleaning strainers improve pump energy by 20 KW
• More frequent maintenance than recommended
• Water Usage• Zero Blow down for Cooling Tower saving 40%
• Negotiated reduction in Sewer cost ~$2500/month
Other Issues
Aaron AndersenNov., 2013
PUE Trend Since Startup
Aaron AndersenNov., 2013
PUE – One Year Aug 2012 – July 2013