diesel generator set mtu 16v2000 ds1100

5
mtu 16V2000 DS1100 Diesel Generator Set Product highlights 380V - 415V/50 Hz/prime power for stationary emergency/ fuel consumption optimized/16V2000G26F/air charge air cooling Bene�ts Low fuel consumption Optimized system integration ability High reliability and availability of power Long maintenance intervals Optimized ratio between size and power Wide operating range without derating Support Global product support offered Standards Engine-generator set is designed and manufactured in facilities certified to standards ISO 2008:9001 and ISO 2004:14001 Generator set complies to G3 according to ISO 8528 Generator meets NEMA MG1, BS5000, ISO, DIN EN and IEC standards NFPA 110 Power rating System rating: 1000 kVA Accepts rated load in one step per NFPA 110 Generator set complies to G3 according to ISO 8528-5 Generator set exceeds load steps according to ISO 8528-5 Performance assurance certi�cation (PAC) Engine-generator set tested to ISO 8528-5 for transient response 85% load factor for continuous power applications Verified product design, quality and performance integrity All engine systems are prototype and factory tested Complete range of accessories available Control panel Power panel Fuel system Fuel connections with shut-off valve mounted to base frame Starting/charging system Exhaust system Mechanical radiator Oversized voltage alternators Emissions Fuel consumption optimized NOx emission optimized, Tier 2 compliant and NEA (ORDE) optimization optionally available Certi�cations CE certification option VDE4110 certification Optional equipment and finishing shown. Standard may vary.

Upload: others

Post on 12-Mar-2022

21 views

Category:

Documents


0 download

TRANSCRIPT

mtu 16V2000 DS1100Diesel Generator Set

Product highlights

380V-415V/50Hz/primepowerforstationaryemergency/fuelconsumptionoptimized/16V2000G26F/airchargeaircooling

Bene�ts— Lowfuelconsumption— Optimizedsystemintegrationability— Highreliabilityandavailabilityofpower— Longmaintenanceintervals— Optimizedratiobetweensizeandpower— Wideoperatingrangewithoutderating

Support— Globalproductsupportoffered

Standards— Engine-generatorsetisdesignedandmanufacturedinfacilitiescertifiedtostandardsISO2008:9001andISO2004:14001

— GeneratorsetcompliestoG3accordingtoISO8528— GeneratormeetsNEMAMG1,BS5000,ISO,DINENandIECstandards

— NFPA110

Powerrating— Systemrating:1000kVA— AcceptsratedloadinonestepperNFPA110— GeneratorsetcompliestoG3accordingtoISO8528-5— GeneratorsetexceedsloadstepsaccordingtoISO8528-5

Performanceassurancecerti�cation(PAC)— Engine-generatorsettestedtoISO8528-5fortransientresponse— 85%loadfactorforcontinuouspowerapplications— Verifiedproductdesign,qualityandperformanceintegrity— Allenginesystemsareprototypeandfactorytested

Completerangeofaccessoriesavailable— Controlpanel— Powerpanel— Fuelsystem— Fuelconnectionswithshut-offvalvemountedtobaseframe— Starting/chargingsystem— Exhaustsystem— Mechanicalradiator— Oversizedvoltagealternators

Emissions— Fuelconsumptionoptimized— NOxemissionoptimized,Tier2compliantandNEA(ORDE)optimizationoptionallyavailable

Certi�cations— CEcertificationoption— VDE4110certification

Optionalequipmentandfinishingshown.Standardmayvary.Optionalequipmentandfinishingshown.Standardmayvary.

Application data 1)

1 AlldatarefersonlytotheengineandisbasedonISOstandardconditions(25°Cand100mabovesealevel).

2 EmissionoptimizeddatarefertoTNOxemissionoptimizedandNEA(ORDE)optimized/Tier2compliantengines.

3 ValuesreferencedareinaccordancewithISO3046-1.Conversioncalculatedwithfueldensityof0.83g/ml.Allfuelconsumptionvaluesrefertoratedenginepower.

Engine Fuelconsump.opt. Emissionopt.2)

Manufacturer mtu mtu Model 16V2000G26F 16V2000G26F Type 4-cycle 4-cycle Arrangement 16V 16V Displacement:l 35.7 35.7 Bore:mm 135 135 Stroke:mm 156 156 Compressionratio 17.5 17.5 Ratedspeed:rpm 1500 1500 Enginegovernor ADEC(ECU9) ADEC(ECU9) Speedregulation ±0.25% ±0.25% Maxpower:kWm 890 890 Meaneffectivepressure:bar 19.9 19.9 Aircleaner dry dry

FuelsystemMaximumfuellift:m 5 5 Totalfuelflow:l/min 30 30

Fuelconsumption3)

At100%ofpowerrating:l/hr g/kWh 205/191 216/201 At75%ofpowerrating: l/hr g/kWh 156/194 165/205 At50%ofpowerrating: l/hr g/kWh 108/202 115/214

LubeoilsystemTotaloilsystemcapacity:l 102 102 Max.lubeoiltemp.(alarm):°C 103 103 Max.lubeoiltemp.(shutdown):°C 105 105 Min.lubeoilpressure(alarm):bar 4.5 4.5 Min.lubeoilpressure(shutdown):bar 4 4

CombustionairrequirementsCombustionairvolume:m3/s 1.03 1.19 Max.airintakerestriction:mbar 40 40

Cooling/radiatorsystem Fuelconsump.opt. Emissionopt.2)

Coolantflowrate(HTcircuit):m3/hr 41.6 41.6 Heatrejectiontocoolant:kW 370 350 Heatradiatedtochargeaircooling:kW 145 205 Heatradiatedtoambient:kW 40 40 Fanpowerformech.radiator(40°C): 43.4 43.4 Fanpowerformech.radiator(50°C): 43.4 43.4 Airflowrequiredformech.radiator(40°C) cooledunit:m3/min 1462 1462 Airflowrequiredformech.radiator(50°C) cooledunit:m3/min 1462 1462 Enginecoolantcapacity (withoutcoolingequipment):l 70 70 Radiatorcoolantcapacity(40°C):l 74 74 Radiatorcoolantcapacity(50°C):l 106 106 Max.coolanttemperature(warning):°C 102 102 Max.coolanttemperature(shutdown):°C 105 105

ExhaustsystemExhaustgastemp.(afterturbocharger):°C 530 515 Exhaustgasvolume:m³/s 2.78 3.07 Maximumallowablebackpressure:mbar 50 50 Minimumallowablebackpressure:mbar 30 30

GeneratorProtectionclass IP23 IP23 Insulationclass H H Voltageregulation(steadystate) ±0.25% ±0.25% Radointerferenceclass N N

Representsstandardfeatures

Representsoptionalfeatures

Engine

4-cycle Standardsinglestageairfilter Oildrainextension&shut-offvalve Fullflowoilfilters Closedcrankcaseventilation

Governor-electronicisochronous ADEC/ECU9 Commonrailfuelinjection Dryexhaustmanifold Electricstartingmotor(24V)

Fuelconsumptionoptimizedengine NOxemissionoptimizedengine Tier2optimizedengine NEA(ORDE)optimizedengine

Generator

LeroySomerlowvoltagegenerator MeetsNEMAMG1,BS5000,IEC60034-1,VDE0530,DINEN12601,AS1359 andISO8528requirements Superiorvoltagewaveform Solidstate,volts-per-Hertzregulator 4polethree-phasesynchronous generator Brushless,self-excited,self-regulating,self-ventilated Digitalvoltageregulator Anticondensationheater StatorwindingY-connected, accessibleneutral(broughtout)

ProtectionIP23 lessthan5%harmonicdistorsion 2/3pitchstatorwindings Noloadtofullloadregulation ±0.25%voltageregulationnoloadto fullload InsulationclassH,utilizationacc.toH RadiosuppressionEN55011,group1,cl.B Shortcircuitcapability3xInfor10sec Sustainedshortcircuitcurrentofup to300%oftheratedcurrentforupto 10seconds(LeroySomergenerator) WindingandbearingRTDs (withoutmonitoring)

ExcitationbyAREP+PMI MountingofCT´s:3x2coreCT´s Voltagesetpointadjustment±10V Sustainedshortcircuitcurrentofup to250%oftheratedcurrentforupto 10seconds(Marathongenerator) Marathonlowvoltagegenerator Oversizedgenerator

Standardandoptionalfeatures

Systemratings(kW/kVA)

Generatormodel Voltage withmechanicalradiator**

kWel kVA* AMPS

LeroySomerLSA50.2M6 (Lowvoltage LeroySomerstandard)

380 V 800 1000 1519

400 V 800 1000 1443

415 V 800 1000 1391

LeroySomerLSA50.2L7 (Lowvoltage LeroySomeroversized)

380 V 800 1000 1519

400 V 800 1000 1443

415 V 800 1000 1391

Marathon740RSL7183 (Lowvoltage Marathonstandard)

380 V 800 1000 1519

400 V 800 1000 1443

415 V 800 1000 1391

Marathon742RSL7185 (Lowvoltage Marathonoversized)

380 V 800 1000 1519

400 V 800 1000 1443

415 V 800 1000 1391 *cosphi=0.8 **BE,fueloptimized:max.poweravailableupto:openpowerunit40°C/400m;NOxemissionoptimized,EPATier2compl.,NEA:standardoperatingconditions/open powerunit25°C/100m Electricaloutputsmayvarydependingongeneratorvoltageandambientconditions.Forpoweroutputsconsultyourmtudealer. Intakeairdepression/mbar:15mbar Exhaustbackpressure/mbar:30mbar

Standard and optional features

Representsstandardfeatures

Representsoptionalfeatures

Coolingsystem

Jacketwaterpump Thermostat(s)

Airchargeaircooling Mechanicalradiator

Jacketwaterheater

Powerpanel

Availablein600x600 Phasemonitoringrelay230V/400V

Supplyforbatterycharger Supplyforjacketwaterheater

Plugsocketcabinetfor230V compatibleEuro

Fuelsystem

Flexiblefuelconnectorsmountedto baseframe

Fuelfilterwithwaterseparator Switchablefuelfilterwithwaterseparator

Fuelcooler

Starting/chargingsystem

24Vstarter Starterbatteries,cables,rack, disconnectswitch

Batterycharger Redundantstarter2x7.5KW

Mountingsystem

Weldedbaseframe Resilientengineandgeneratormounting Modularbaseframedesign

Exhaustsystem

Exhaustbellowswithconnectionflange Exhaustsilencerwith 10dB(A)soundattenuation

Exhaustsilencerwith 30dB(A)soundattenuation

Exhaustsilencerwith 40dB(A)soundattenuation Y-connection-pipe

Controlpanel

Pre-wiredcontrolcabinetforeasy applicationofcustomizedcontroller(V1+) Islandoperation(V2) Automaticmainsfailureoperationwith ATS(V3a) Automaticmainsfailureoperation incl.controlofgeneratorandmainsbreaker(V3b) Islandparalleloperationofmultiplegensets(V4) Automaticmainsfailureoperationwithshort(<10s)mainsparallel overlapsynchronization(V5) Mainsparalleloperationofa singlegenset(V6)

Mainsparalleloperationofmultiplegensets(V7) Baslercontroller Deifcontroller Completesystemmetering Digitalmetering Engineparameters Generatorprotectionfunctions Engineprotection SAEJ1939engineECUcommunications Parametrizationsoftware Multilingualcapability Multipleprogrammablecontactinputs Multiplecontactoutputs Eventrecording

IP54frontpanelratingwith integratedgasket Differentexpansionmodules Remoteannunciator Daytankcontrol Generatorwinding-andbearingtemperaturemonitoring Differentialprotectionwith multi-functionprotectionrelay ModbusTCP-IP

Weights and dimensions

Drawing above for illustration purposes only, based on a standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design. See website for unit specific template drawings.

Sound data

— Consultyourlocalmtudistributorforsounddata.

Emissionsdata

— Consultyourlocalmtudistributorforemissionsdata.

Ratingdefinitionsandconditions

— Primepowerforstationaryemergencyratingsapplytoinstallationsservedbyareliableutilitysource.Thestandbyratingisapplicabletovaryingloadsforthedurationofapoweroutage.A10%overloadcapacityisavailableforonehourintwelve.RatingsareinaccordancewithISO8528-1,ISO-3046-1,BS5514andAS2789.Averageloadfactor:≤85%.Operatinghours/year:max.500.

— Consultyourlocalmtudistributorforderatinginformation.

Subjecttochange.|3239751|Edition01/21|ESM2021-01.

Weightsanddimensionsarebasedonopenpowerunitsandareestimatesonly.Consultthefactoryforaccurateweightsanddimensionsforyourspecificengine-generatorset.

System Dimensions(LxWxH) Weight(dry/lesstank)

Openpowerunit(OPU) 4440x1990x2200mm 6550kg

Rolls-RoyceGroupwww.mtu-solutions.com/powergen