diesel generator set mtu 16v2000 ds1100
TRANSCRIPT
mtu 16V2000 DS1100Diesel Generator Set
Product highlights
380V-415V/50Hz/primepowerforstationaryemergency/fuelconsumptionoptimized/16V2000G26F/airchargeaircooling
Bene�ts— Lowfuelconsumption— Optimizedsystemintegrationability— Highreliabilityandavailabilityofpower— Longmaintenanceintervals— Optimizedratiobetweensizeandpower— Wideoperatingrangewithoutderating
Support— Globalproductsupportoffered
Standards— Engine-generatorsetisdesignedandmanufacturedinfacilitiescertifiedtostandardsISO2008:9001andISO2004:14001
— GeneratorsetcompliestoG3accordingtoISO8528— GeneratormeetsNEMAMG1,BS5000,ISO,DINENandIECstandards
— NFPA110
Powerrating— Systemrating:1000kVA— AcceptsratedloadinonestepperNFPA110— GeneratorsetcompliestoG3accordingtoISO8528-5— GeneratorsetexceedsloadstepsaccordingtoISO8528-5
Performanceassurancecerti�cation(PAC)— Engine-generatorsettestedtoISO8528-5fortransientresponse— 85%loadfactorforcontinuouspowerapplications— Verifiedproductdesign,qualityandperformanceintegrity— Allenginesystemsareprototypeandfactorytested
Completerangeofaccessoriesavailable— Controlpanel— Powerpanel— Fuelsystem— Fuelconnectionswithshut-offvalvemountedtobaseframe— Starting/chargingsystem— Exhaustsystem— Mechanicalradiator— Oversizedvoltagealternators
Emissions— Fuelconsumptionoptimized— NOxemissionoptimized,Tier2compliantandNEA(ORDE)optimizationoptionallyavailable
Certi�cations— CEcertificationoption— VDE4110certification
Optionalequipmentandfinishingshown.Standardmayvary.Optionalequipmentandfinishingshown.Standardmayvary.
Application data 1)
1 AlldatarefersonlytotheengineandisbasedonISOstandardconditions(25°Cand100mabovesealevel).
2 EmissionoptimizeddatarefertoTNOxemissionoptimizedandNEA(ORDE)optimized/Tier2compliantengines.
3 ValuesreferencedareinaccordancewithISO3046-1.Conversioncalculatedwithfueldensityof0.83g/ml.Allfuelconsumptionvaluesrefertoratedenginepower.
Engine Fuelconsump.opt. Emissionopt.2)
Manufacturer mtu mtu Model 16V2000G26F 16V2000G26F Type 4-cycle 4-cycle Arrangement 16V 16V Displacement:l 35.7 35.7 Bore:mm 135 135 Stroke:mm 156 156 Compressionratio 17.5 17.5 Ratedspeed:rpm 1500 1500 Enginegovernor ADEC(ECU9) ADEC(ECU9) Speedregulation ±0.25% ±0.25% Maxpower:kWm 890 890 Meaneffectivepressure:bar 19.9 19.9 Aircleaner dry dry
FuelsystemMaximumfuellift:m 5 5 Totalfuelflow:l/min 30 30
Fuelconsumption3)
At100%ofpowerrating:l/hr g/kWh 205/191 216/201 At75%ofpowerrating: l/hr g/kWh 156/194 165/205 At50%ofpowerrating: l/hr g/kWh 108/202 115/214
LubeoilsystemTotaloilsystemcapacity:l 102 102 Max.lubeoiltemp.(alarm):°C 103 103 Max.lubeoiltemp.(shutdown):°C 105 105 Min.lubeoilpressure(alarm):bar 4.5 4.5 Min.lubeoilpressure(shutdown):bar 4 4
CombustionairrequirementsCombustionairvolume:m3/s 1.03 1.19 Max.airintakerestriction:mbar 40 40
Cooling/radiatorsystem Fuelconsump.opt. Emissionopt.2)
Coolantflowrate(HTcircuit):m3/hr 41.6 41.6 Heatrejectiontocoolant:kW 370 350 Heatradiatedtochargeaircooling:kW 145 205 Heatradiatedtoambient:kW 40 40 Fanpowerformech.radiator(40°C): 43.4 43.4 Fanpowerformech.radiator(50°C): 43.4 43.4 Airflowrequiredformech.radiator(40°C) cooledunit:m3/min 1462 1462 Airflowrequiredformech.radiator(50°C) cooledunit:m3/min 1462 1462 Enginecoolantcapacity (withoutcoolingequipment):l 70 70 Radiatorcoolantcapacity(40°C):l 74 74 Radiatorcoolantcapacity(50°C):l 106 106 Max.coolanttemperature(warning):°C 102 102 Max.coolanttemperature(shutdown):°C 105 105
ExhaustsystemExhaustgastemp.(afterturbocharger):°C 530 515 Exhaustgasvolume:m³/s 2.78 3.07 Maximumallowablebackpressure:mbar 50 50 Minimumallowablebackpressure:mbar 30 30
GeneratorProtectionclass IP23 IP23 Insulationclass H H Voltageregulation(steadystate) ±0.25% ±0.25% Radointerferenceclass N N
Representsstandardfeatures
Representsoptionalfeatures
Engine
4-cycle Standardsinglestageairfilter Oildrainextension&shut-offvalve Fullflowoilfilters Closedcrankcaseventilation
Governor-electronicisochronous ADEC/ECU9 Commonrailfuelinjection Dryexhaustmanifold Electricstartingmotor(24V)
Fuelconsumptionoptimizedengine NOxemissionoptimizedengine Tier2optimizedengine NEA(ORDE)optimizedengine
Generator
LeroySomerlowvoltagegenerator MeetsNEMAMG1,BS5000,IEC60034-1,VDE0530,DINEN12601,AS1359 andISO8528requirements Superiorvoltagewaveform Solidstate,volts-per-Hertzregulator 4polethree-phasesynchronous generator Brushless,self-excited,self-regulating,self-ventilated Digitalvoltageregulator Anticondensationheater StatorwindingY-connected, accessibleneutral(broughtout)
ProtectionIP23 lessthan5%harmonicdistorsion 2/3pitchstatorwindings Noloadtofullloadregulation ±0.25%voltageregulationnoloadto fullload InsulationclassH,utilizationacc.toH RadiosuppressionEN55011,group1,cl.B Shortcircuitcapability3xInfor10sec Sustainedshortcircuitcurrentofup to300%oftheratedcurrentforupto 10seconds(LeroySomergenerator) WindingandbearingRTDs (withoutmonitoring)
ExcitationbyAREP+PMI MountingofCT´s:3x2coreCT´s Voltagesetpointadjustment±10V Sustainedshortcircuitcurrentofup to250%oftheratedcurrentforupto 10seconds(Marathongenerator) Marathonlowvoltagegenerator Oversizedgenerator
Standardandoptionalfeatures
Systemratings(kW/kVA)
Generatormodel Voltage withmechanicalradiator**
kWel kVA* AMPS
LeroySomerLSA50.2M6 (Lowvoltage LeroySomerstandard)
380 V 800 1000 1519
400 V 800 1000 1443
415 V 800 1000 1391
LeroySomerLSA50.2L7 (Lowvoltage LeroySomeroversized)
380 V 800 1000 1519
400 V 800 1000 1443
415 V 800 1000 1391
Marathon740RSL7183 (Lowvoltage Marathonstandard)
380 V 800 1000 1519
400 V 800 1000 1443
415 V 800 1000 1391
Marathon742RSL7185 (Lowvoltage Marathonoversized)
380 V 800 1000 1519
400 V 800 1000 1443
415 V 800 1000 1391 *cosphi=0.8 **BE,fueloptimized:max.poweravailableupto:openpowerunit40°C/400m;NOxemissionoptimized,EPATier2compl.,NEA:standardoperatingconditions/open powerunit25°C/100m Electricaloutputsmayvarydependingongeneratorvoltageandambientconditions.Forpoweroutputsconsultyourmtudealer. Intakeairdepression/mbar:15mbar Exhaustbackpressure/mbar:30mbar
Standard and optional features
Representsstandardfeatures
Representsoptionalfeatures
Coolingsystem
Jacketwaterpump Thermostat(s)
Airchargeaircooling Mechanicalradiator
Jacketwaterheater
Powerpanel
Availablein600x600 Phasemonitoringrelay230V/400V
Supplyforbatterycharger Supplyforjacketwaterheater
Plugsocketcabinetfor230V compatibleEuro
Fuelsystem
Flexiblefuelconnectorsmountedto baseframe
Fuelfilterwithwaterseparator Switchablefuelfilterwithwaterseparator
Fuelcooler
Starting/chargingsystem
24Vstarter Starterbatteries,cables,rack, disconnectswitch
Batterycharger Redundantstarter2x7.5KW
Mountingsystem
Weldedbaseframe Resilientengineandgeneratormounting Modularbaseframedesign
Exhaustsystem
Exhaustbellowswithconnectionflange Exhaustsilencerwith 10dB(A)soundattenuation
Exhaustsilencerwith 30dB(A)soundattenuation
Exhaustsilencerwith 40dB(A)soundattenuation Y-connection-pipe
Controlpanel
Pre-wiredcontrolcabinetforeasy applicationofcustomizedcontroller(V1+) Islandoperation(V2) Automaticmainsfailureoperationwith ATS(V3a) Automaticmainsfailureoperation incl.controlofgeneratorandmainsbreaker(V3b) Islandparalleloperationofmultiplegensets(V4) Automaticmainsfailureoperationwithshort(<10s)mainsparallel overlapsynchronization(V5) Mainsparalleloperationofa singlegenset(V6)
Mainsparalleloperationofmultiplegensets(V7) Baslercontroller Deifcontroller Completesystemmetering Digitalmetering Engineparameters Generatorprotectionfunctions Engineprotection SAEJ1939engineECUcommunications Parametrizationsoftware Multilingualcapability Multipleprogrammablecontactinputs Multiplecontactoutputs Eventrecording
IP54frontpanelratingwith integratedgasket Differentexpansionmodules Remoteannunciator Daytankcontrol Generatorwinding-andbearingtemperaturemonitoring Differentialprotectionwith multi-functionprotectionrelay ModbusTCP-IP
Weights and dimensions
Drawing above for illustration purposes only, based on a standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design. See website for unit specific template drawings.
Sound data
— Consultyourlocalmtudistributorforsounddata.
Emissionsdata
— Consultyourlocalmtudistributorforemissionsdata.
Ratingdefinitionsandconditions
— Primepowerforstationaryemergencyratingsapplytoinstallationsservedbyareliableutilitysource.Thestandbyratingisapplicabletovaryingloadsforthedurationofapoweroutage.A10%overloadcapacityisavailableforonehourintwelve.RatingsareinaccordancewithISO8528-1,ISO-3046-1,BS5514andAS2789.Averageloadfactor:≤85%.Operatinghours/year:max.500.
— Consultyourlocalmtudistributorforderatinginformation.
Subjecttochange.|3239751|Edition01/21|ESM2021-01.
Weightsanddimensionsarebasedonopenpowerunitsandareestimatesonly.Consultthefactoryforaccurateweightsanddimensionsforyourspecificengine-generatorset.
System Dimensions(LxWxH) Weight(dry/lesstank)
Openpowerunit(OPU) 4440x1990x2200mm 6550kg