    Hitec Power Protection

    Diesel Rotary UPS systems

    Ride through systems Diesel UPS systems

    www.hitec-ups.com

    The problems The solution

    7. Continuous Quality Power

    1. Spikes

    2. Frequency Variations

    3. Voltage Sags

    4. Outages

    5. Harmonic Distortions

    6. Transients

    The result

    Hitec Power ProtectionWhat we do

  • 7/28/2019 Diesel Rotary UPS Systems V1_00 _jan2008_PPT

    2/10

    Major components

    Generator

    Chokecoil

    Diesel engine

    Inductioncoupling

    Freewheelclutch

    Switchgear

    Dicon

    Control panel

    Free inner rotor principle

    AC machine

    Induction coupling

    Freewheel clutch

    Diesel engine

  • 7/28/2019 Diesel Rotary UPS Systems V1_00 _jan2008_PPT

    3/10

    Four basic principles (1)

    Simple, sure and reliable Rotary UPS/CPS concept invented and patented by Hitec

    Power Protection in 1969

    Rotary UPS/CPS = static UPS + standby generator

    Fewer components than static UPS

    Smaller footprint than static UPS

    Easy installation & operation

    Long lifespan (>25 years)

    Line-interactive system

    Rotary UPS/CPS run in parallel with utility power

    Life-guarding mission critical processes

    No power conversion

    Four basic principles (2) Active filter (choke coil + generator)

    Compensation utility voltage deviations

    Filtering of utility borne harmonic voltages

    Filtering of load borne harmonic currents

    Power factor improvement (>0.98)

    Environmental friendly system

    Most energy efficient UPS/CPS system

    Use of stored kinetic energy

    No batteries required, no chemical waste No conditioned battery room required, saving space and energy

    for ventilation and cooling

    Lowest Total Cost of Ownership (TCO)

  • 7/28/2019 Diesel Rotary UPS Systems V1_00 _jan2008_PPT

    4/10

    Diesel Rotary UPS systemSpecifications

    Diesel, UPS and energy storage combined

    Lowest TCO, 25+ years productive lifetime

    No power conversion

    High end-to-end efficiency (>96%)

    High output values

    Single unit rating Up to 2,5 MVA

    Parallel configuration rating Up to 40 MVA

    Output voltage

    LV 380 .. 480 V, 50/60 Hz

    MV Up to 24 kV, 50/60 HZ

    Voltage deviation +/- 1% Frequency deviation +/- 1%

    Options (e.g. remote monitoring, containerized designs,

    vibration monitoring, .)

    UPS Inverters

    Air Conditioning

    PFC

    Standby Batteries

    Spark-proof Lighting

    Busduct & CablingFire Protection

    & Security

    All in one

    Static UPS

    Hitec DRUPS

    Standby Diesel

  • 7/28/2019 Diesel Rotary UPS Systems V1_00 _jan2008_PPT

    5/10

    Hitec Rotary UPS

    Total losses 96%

    Total losses >8%

    100%

    25 years)

    Fire Protection

    & Security

    Air Conditioning

    Standby Batteries

    UPS Inverters PFC

    Spark-proof Lighting

    Busduct & Cabling

    It is in the windings

    Outer Rotor

    2 pole AC windings

    2 pole DC windings

    50 Hz 60Hz

    1500 RPM 1800 RPM

    Inner Rotor

    Stored Energy

    50 Hz 60Hz

    1500 1800

    3000 + 3600 +

    4500 RPM 5400 RPM

  • 7/28/2019 Diesel Rotary UPS Systems V1_00 _jan2008_PPT

    6/10

    System operation

    Dependent system load

    Speed(rpm)

    0

    n

    3n

    Time

    Utility mode

    Speed(rpm)

    0

    n

    3n

    Time

    Reactor and generator function as

    active filter. The induction

    coupling stores kinetic energy.

    Q1 Q2

    Q3

  • 7/28/2019 Diesel Rotary UPS Systems V1_00 _jan2008_PPT

    7/10

    Change-over to diesel mode

    Speed(rpm)

    0

    n

    3n

    Time

    Power problem - Q1 opens, energy

    from the inner rotor goes via the

    generator to the load. The diesel

    engine starts up and takes over

    the power supply.

    Q1 Q2

    Q3

    Diesel mode

    Speed(rpm)

    0

    n

    3n

    Time

    The outer rotor of the induction

    coupling is re-energized. The

    speed of the diesel engine is

    digitally controlled ensuring a

    constant output

    Q1 Q2

    Q3

  • 7/28/2019 Diesel Rotary UPS Systems V1_00 _jan2008_PPT

    8/10

    Back to utility mode

    Speed(rpm)

    0

    n

    3n

    Time

    Utility power is back and after it

    has stabilized the UPS/CPS

    synchronizes and closes Q1. The

    diesel engine ramps down and

    the free-wheel clutch disengages.

    Q1 Q2

    Q3

    Recording mains failure

    Mainsvoltage

    Outputvoltage

    50.5 Hz

    50 Hz

    49.5 Hz

    1 sec.

    1500 rpm

    Dynamic UPS at 100% load

    MainsVoltage

    Diesel engine RPM

    50 Hz Line

    Outputfrequency [Hz]

    Free wheel clutchengaging

    Moment ofmains failure

    Dieselstart

  • 7/28/2019 Diesel Rotary UPS Systems V1_00 _jan2008_PPT

    9/10

    Technical features D-UPS

    Uses stored kinetic energy 50/60 Hz technology

    Integrated power factor correction

    Effective filter for spikes & harmonic distortion

    High non-linear load capacity

    High peak current capability (typical 15 In)

    Very efficient with low operational costs

    Easily paralleled MV applications up to 40 MVA

    Hitec D-UPS configurations

    Unit configurations System configurations

    Single output

    Dual output

    Medium Voltage

    Parallel redundant

    Master slave

    Cross link

    Isolated redundant

    Distributed redundant

  • 7/28/2019 Diesel Rotary UPS Systems V1_00 _jan2008_PPT

    10/10

    For more information please visit our website

    Thank you for your interest

    Ride through systems Diesel UPS systems